Loop Leader - Precision Digital

5 digit Loop-powered Panel meters
with Loop-powered Backlight
+
Loop Leader ®
-
Series
Model PD683 General Purpose
Model PD688 Hazardous Area
Model PD688 Only
•
4-20 mA Input
•
5 Digit LCD, 0.6" (15.2 mm) High
•
FM Type 4X, IP65 Front
•
Shallow Depth Case 3.2” Behind Panel
•
2 V Drop (5.7 V with Backlight)
•
Loop-Powered Backlight Standard
•
Custom Engineering Units & Bargraph
•
Linear, Square Root, or Programmable Exponent
•
Maximum & Minimum Display
•
Operating Temperature Range -30 to 65°C
•
Intrinsically Safe & Non-Incendive
•
HART Protocol Transparent
Precision Digital Corporation
www.predig.com
Model PD683 & PD688 Loop-Powered Panel Meters
5 Digits
0.6" High
Engineering
Notation
Trend Arrow
Custom
Engineering
Units
Bargraph
Backlight
Standard
Actual Size
KEY FEATURES
Square Root Function
The square root extraction feature displays flow rate by
extracting the square root from a differential pressure
transmitter signal. The user selectable low-flow cutoff
feature gives a reading of zero when the flow rate drops
below a user selectable value.
Through significant innovation in technology and design,
we developed the Loop Leader® Series of loop-powered
indicators, which are loaded with standard features and built
for tough industrial environments.
Full Featured
• Displays Flow Rate
• User Selectable Low-Flow Cutoff
• Only 2 Calibration Points Required
There’s nothing stripped down or bare bones about these
indicators; they’re designed for demanding process control
applications. Standard features include a full 5 digit backlit
display with bargraph, on-screen custom engineering units,
and max/min display capabilities
Install Just About Anywhere
Indoors, outdoors, bright sunlight, dimly lit plant, wet, dirty,
hot or cold, these indicators go just about anywhere. Their
shallow-depth case, FM Type 4X front, loop-powered
FLOW
backlighting, and wide operating temperature range are all
standard features. And the PD688 with its FM Approval and
CSA and ATEX Certifications can be installed in just about Programmable Exponent
any hazardous location.
The programmable exponent function is used to linearize the
level signal in open channel flow applications using weirs
4-20 mA Input Connections
and flumes and display flow rate in engineering units.
Wiring with Backlight
Power
Supply
S+ S- B+ B4-20 mA
Transmitter
4-20 mA output
Wiring without Backlight
Power
Supply
S+ S- B+ B-
4-20 mA
Transmitter
2
Model PD683 & PD688 Loop-Powered Panel Meters
Setup & Programming
PD688 Intrinsically Safe Wiring
Easy Setup
Installation must be performed in accordance with Control
Even with all the features packed into these meters, they’re still Drawing LIM688-2.
easy to setup and get running. Everything is programmed from
Loop Input with Backlight
the front panel buttons with no pots or jumpers to deal with. In
fact, these meters can be scaled without a signal source for HAZARDOUS AREA
NON-HAZARDOUS AREA
even quicker setup.
S+ S- B+ B-
Main Menu
Loop
Input
Run
Mode
9.2 846
s et up
GPS
pr oG
I.S. Barrier
+
-
pas s
I.S. GROUND
Transmitter
Advanced Features Menu
Loop Input without Backlight
To simplify the setup process, functions not needed for most
applications are located in the Advanced Features menu.
Press and hold the Menu button for five seconds to access the
advanced features of the meter.
HAZARDOUS AREA
NON-HAZARDOUS AREA
S+ S- B+ B-
Loop
Input
Run Mode
9.2 846
<1 ohm to Ground
I.S. Barrier
GPS
+
-
Press and hold for five seconds
f unc t
Transmitter
Press Enter/Ack to Access
Menu or to Accept Setting
contr
Optional enclosures
Press Up to Scroll Menu and
to Increment Digit Value
f l t er
I.S. GROUND
<1 ohm to Ground
Press Right to Select Next Digit
PDA2801 low-cost
NEMA 4X enclosure
for one PD683 meter
Press Menu to Exit at any Time
bypas
t r end
I
Cal
i nf o
Installation
There is no need to remove the meter from its case to complete
the installation, wiring, and setup of the meter.
Mounting Dimensions
NEMA 4X
enclosures are
available in plastic,
steel, & stainless
steel for one to six
PD683 meters
Units: Inch (mm)
1.76"
(45mm)
2.50"
(64mm)
2.45"
(62mm)
0.59"
(15mm)
Go to
www.predig.com
for complete details
3.61"
(92mm)
3.2"
(81mm)
4.68"
(119mm)
Notes:
1. Panel cutout required: 3.622 x 1.772 (92 x 45)
2 Panel thickness: 0.040 – 0.250 (1.0 – 6.4)
3. Mounting brackets lock in place for easy mounting
3
Model PD683 & PD688 Loop-Powered Panel Meters
SPECIFICATIONS
Except where noted all specifications apply to operation at +25°C.
General
Display: 5 digit LCD (-99999 to 99999), 0.60" (15.2 mm) high,
7-segment, automatic lead zero blanking.
Engineering Units: 0.25" (6.4 mm) high, 14-segment
Bargraph: 20-segment, 0-100% indication
Trend Arrows: Up and down trend indication
Backlight: Bright orange LED (intensity varies with signal)
Front Panel: FM Type 4X, IP65; panel gasket provided
Display Update Rate: 2.5/second
Overrange: Display flashes 99999
Underrange: Display flashes -99999
Programming Method: Four front panel buttons
Noise Filter: Programmable from 1 to 199
Recalibration: Recommended at least every 12 months
Max/Min Display: Max/min readings reached by the process are
stored until reset by the user or until power to the meter is turned off.
Password: Programmable password restricts modification of
programmed settings.
Non-Volatile Memory: All programmed settings are stored in
non-volatile memory for a minimum of ten years if power is lost.
Voltage Drop: 2.0 V max w/o backlight, 5.7 V max with backlight
Equivalent Resistance: 100 Ω @ 20 mA without backlight, 285 Ω @ 20 mA with backlight.
Normal Mode Rejection: 64 dB at 50/60 Hz
Operating Temperature Range: -30 to 65°C
Allowable Temperature Range: -40 to 65°C† (see note below) Storage Temperature Range: -40 to 85°C
Relative Humidity: 0 to 90% non-condensing
Connections: Screw terminals accept 12 to 22 AWG wire
Enclosure: 1/8 DIN, high impact plastic, UL 94V-0, color: gray
Mounting:1/8 DIN panel cutout required. Two panel mounting
bracket assemblies provided.
Tightening Torque: 4.5 lb-in (0.5 Nm) Screw terminal connectors
Overall Dimensions: 4.68" x 2.45" x 3.79" (119 x 62 x 96 mm)
Weight: 5.7 oz (162 g)
Warranty: 3 years parts and labor
PD688 Approvals for Hazardous Locations
FM Approved & CSA Certified: Intrinsically safe with entity for
use in Class I, Div 1, Groups ABCD; Class II, Div 1, Groups EFG;
Class III, Div 1; Class I, Zone 0, Group IIC; T-code = T4.
Non-incendive: Suitable for use in Class I, Div 2, Groups ABCD;
Class II, Div 2, Groups FG; Class III, Div 2.
Entity Parameters: Ui: 30 V; Ii: 175 mA; Ci: 0; Li: 0; P i: 1.0 W
ATEX Certified: II 1G, Ex ia IIC T4, IP65, Ta = -40°C to 65°C
Note: Installation must be performed in accordance with Control Drawing LIM688-2
ordering information
Loop Leader® • PD683/PD688
Model
PD683-0K0*
PD688-0K0*
Description
General Purpose
FM Approved, CSA & ATEX Certified
* Quick Shipment Program product, typically shipped within 2 working days
Accessories
Model
Meters Description
Mounting
PDA23XX
1 - 10* Plastic NEMA 4X
Through Door
PDA24XX
1 - 2*
Inside Cover
PDA25XX
1 - 10* Plastic NEMA 4X
Through Door
PDA26XX
1 - 6*
Stainless Steel NEMA 4X
Through Door
PDA27XX
1 - 6*
Steel NEMA 4X
Through Door
PDA2801
1
Low-Cost NEMA 4X
Through Cover
Plastic NEMA 4X
Note: XX = the last two digits of the model number.
* Go to www.predig.com/esu to find individual model numbers
+
Loop Leader ®
-
Series
Your Local Distributor is:
† Below -30°C the LCD becomes less readable. See application note AN-1005.
Input
Input Range: 4-20 mA
Accuracy: ±0.03% of span ±1 count, square root and
programmable exponent: 10-100% FS.
Calibration: Scale without signal or calibrate with signal source
Calibration Range: User programmable over entire range of meter
Minimum Span: 0.40 mA between input 1 and input 2
Note: An Error message will appear if input 1 and input 2 signals are too close together.
Input Overload: Over current protection to 2 A maximum
Decimal Point: Up to 4 places (d.dddd, dd.ddd, ddd.dd, dddd.d, or ddddd)
Function: Linear, square root, or programmable exponent
Low-Flow Cutoff: -99999 to 99999 (-99999 disables cutoff function)
Temperature Drift: 50 PPM/°C from -40 to 65°C ambient
Disclaimer
The information contained in this document is subject to change without notice. Precision Digital
Corporation makes no representations or warranties with respect to the contents hereof, and
specifically disclaims any implied warranties of merchantability or fitness for a particular purpose. ©2016 Precision Digital Corporation. All rights reserved.
LDS688_J
Precision Digital Corporation
233 South Street • Hopkinton MA 01748 USA • Tel (800) 343-1001 • Fax (508) 655-8990
01/16