ABB monitoring and communications PVI-RS485

Solar inverters
ABB monitoring and communications
PVI-RS485-MODBUS Converter
PVI-RS485-MODBUS is the ABB
devices family able to convert
the proprietary Aurora Protocol
to ModBus RTU or ModBus TCP
communication protocol.
The PVI-RS485-MODBUS enables ABB
inverters to exchange data with thirdparty devices such as controller as well
as datalogger supporting ModBus (RTU
or TCP) communication protocol.
The PVI-RS485-MODBUS is a DIN rail
mounted device and can be configured
and upgraded locally by simply using
a PC (connected to the RS485 port
through ABB PVI-USB-RS232-485
Adapter) running a common testing
application able to operate as a
ModBus master for accessing data in
the PVI-RS485-MODBUS connected as
slave device.
The PVI-RS485-MODBUS is capable to
manage up to 32 ABB string inverters
or 32 ABB 55 kW inverter modules
and, according to the specific product
model, it allows customer to manage
inverter power control in range of Smart
Grid functionalities.
Highlights
− − Converters from ABB proprietary
Aurora Protocol to MODBUS RTU
− − PVI-RS485-MODBUS-STRING (for
ABB string inverters)
− − PVI-RS485-MODBUS-CENTRAL
(for ABB central inverters)
− − Converters from ABB proprietary
Aurora Protocol to MODBUS TCP
− − PVI-RS485-MODBUS-TCPSTRING (for ABB string inverters)
− − PVI-RS485-MODBUS-TCPCENTRAL-xx (for ABB central
inverters)
− − Up to 32 inverters or 55 kW modules
manageable
− − Multi-drop bus connection allowed
for RTU
− − 50 Hz transformer and cables are
provided
− − Active-reactive power control allowed
by some Modbus RTU models
Block diagram of PVI-RS485-MODBUS Converter
PVI-RS485-TCP
Modbus RTU
PVI-RS485-MODBUS
Gateway
Modbus TCP
Technical data and types
Type code
Power entry characteristic
AC input voltage range (Vac,min...Vac,max)
Nominal AC input voltage (Vac,n)
Rated frequency (fr)
DC input voltage range (V dc,min...Vdc,max)
Nominal DC input voltage (Vdc,n)
RS485 section
PVI-RS485-MODBUS
Serial interface type
Baud rate
Protocol
Number of devices
Line biasing resistor (where necessary)
Termination resistor
RS485 MODBUS section
RS485 Half-Duplex
19200 bps not modifiable
ABB Proprietary
32
Serial interface type
Baud rate
Protocol
Number of devices
Line biasing resistor (where necessary)
Termination resistor
Physical and environmental
Environmental protection rating
Ambient temperature range
Relative humidity
Compliance
Isolation
Marking
Safety and EMC standard
Available products variants
RTU STRING
TCP STRING
RTU CENTRAL
TCP CENTRAL EU version
TCP CENTRAL US version
TCP CENTRAL Core CN version
15...36 V
24 V
50 or 60 Hz
18...48 V
24 V
1 kΩ between +5 V/+D and RTN/-D
120 Ω settable via switch
RS485 Half-Duplex
19200 bps
MODBUS RTU - MODBUS/TCP
32
1 kΩ between +5 V/+D and RTN/-D
120 Ω settable via switch
IP20 (Indoor use only)
-40...+ 60°C/-40...140°F
0...95%
Yes, 2500 VDC
CE
EN55022; EN61000-6-2/3; EN61000-4-2/3/4/5/6/8/11/14/16
PVI-RS485-MODBUS-STRING (for ABB string inverters)
PVI-RS485-MODBUS-TCP-STRING (for ABB string inverters)
PVI-RS485-MODBUS-CENTRAL (for ABB central inverters)
PVI-RS485-MODBUS-TCP-CENTRAL-EU (for ABB central inverters)
PVI-RS485-MODBUS-TCP-CENTRAL-US (for ABB central inverters)
PVI-RS485-MODBUS-TCP-CENTRAL-CORE (for ABB central Core inverter)
Remark. Features not specifically listed in the present data sheet are not included in the product
Support and service
ABB supports its customers with
dedicated, global service organization
in more than 60 countries and strong
regional and national technical partner
networks providing complete range of
life cycle services.
For more information please contact
your local ABB representative or visit:
www.abb.com/solarinverters
www.abb.com/solar
www.abb.com
© Copyright 2016 ABB. All rights reserved.
Specifications subject to change without notice.
BCD.00394 Rev. D EN 06.06.2016