Liebert
Liebert UPStation® GXT2 6000 UPS
Power Availability
HIGH CAPACITY, COMPACT UPS WITH FLEXIBLE
OUTPUT VOLTAGE AND POWER DISTRIBUTION
Provides 6 kVA Of 240/120 VAC
On-Line UPS Protection For Large
Network Peripherals, Servers and
Critical Nodes, Storage Systems,
Network Routers, Bridges and Hubs
and Other Sensitive Electronics
LIEBERT DELIVERS 6 kVA OF TRUE ON-LINE
POWER IN A COMPACT 4U PACKAGE
Liebert's UPStation® GXT2 6000 is the first true online UPS that combines 6 kVA of power capacity, internal batteries and
dual output voltage in a single 4U size cabinet. This makes it an ideal fit in applications where the power requirements are
demanding — but rack space is limited. Designed for use in either rack or tower configurations, the new unit is well suited
for installations such as smaller computer rooms or communications closets.
The Liebert GXT2 6000 offers a unique combination of high level on-line UPS features in an ultra compact package that will be
2
a perfect fit for a number of applications.
Dual Voltages For Multiple Applications
Application versatility is achieved through the use of a
dual inverter design capable of providing simultaneous
output voltages of 240/120, 208/120, 230/115, 220/110,
Modular Wiring And Bypass Capability
For installation flexibility, the Liebert GXT2 6000 allows
you to choose from several different wiring configurations
made possible by the use of removable power distribution
or 200/100 VAC. The two 3 kVA inverters have a common
boxes that simply plug into the rear of the UPS. The
neutral connection. The phase relationship between each
included box provides terminal blocks for hardwired input
inverter is controlled so that two simultaneous voltages can and output connections. An optional hardwire version that
be produced. This enables the UPS to power a wide variety
of equipment with different voltages. The input is power
factor corrected to approximately .98.
includes a maintenance bypass switch is also available.
In cases where the ease of plug-and-play power
connections is desired, optional versions of the power
distribution box convert the Liebert GXT2 6000 to a
Wider Input Voltage Window Minimizes
Battery Use
The Liebert GXT2 6000 features a wide input voltage
cord-type input with receptacles for output distribution.
The input plug is an L14-30, and various combinations of
output receptacles are available as described in the
window that allows the UPS to support the critical load
specification section at the end of the brochure. This
without having to transfer to battery, extending system
distribution box also provides maintenance bypass
availability for when battery back-up is truly needed.
capability.
Patented Feature Enhances Output
Power Quality
The Liebert GXT2 6000 includes a patented output
neutral bonding feature designed to handle a condition
that results from compliance to UL 1778 which requires
that input conductors of the UPS (including neutral) be
disconnected from the input source when the UPS is in
battery mode. Disconnection of the input neutral allows
the UPS output neutral to float away from ground
potential. This patented feature provides a method for
maintaining the UPS output neutral to ground bond in
all modes of operation, thereby eliminating any voltage
induced on the UPS output neutral connection.
Liebert UPStation GXT 6000 Model shown with Optional Bypass Distribution Box
Designed For Power
Reliability And Ease-Of-Use
Other product features of the Liebert GXT2 6000 include:
•Internal automatic and manual bypass — Assures
continuity of power to critical loads during system
maintenance or in case of internal fault.
•Automatic frequency detection — The Liebert GXT2
6000 detects and matches line input frequencies of
either 60 or 50 Hz.
•Self-diagnostics — Automatically tests unit electronics
Standard power
distribution box provides
terminal blocks for
hardwired input and
output connections.
Optional power
distribution box with
terminal blocks also
includes maintenance
bypass switch.
and batteries. Designed to simplify maintenance and
Optional plug-and-play power
distribution box converts
GXT2 6000 to a cord-type
input with receptacles for
output distribution. Also
provides maintenance
bypass capability.
troubleshooting.
•Built-in serial communications for use with Liebert
MultiLink™ Automated Shutdown Software — Allows
you to monitor communication between the UPS and a
server. Also ensures a graceful unattended shutdown in
the event of an extended power failure.
•Intellislot™ communications port — Utilizes
Liebert OpenComms® Web Card to provide SNMP and
web-based management to your UPS. The card gives you
the power to monitor and control your UPS from not only
your network management station, but from any
PC running Microsoft® Internet Explorer™.
•Built-in closure signals — Provides notification to
monitoring systems of operating conditions including:
on battery, low battery, on battery shutdown and
anymode shutdown.
•Includes Windows-based configuration program —
Allows various operating parameters to be adjusted and
tests to be scheduled. This capability enables you to
customize the Liebert GXT2 6000's performance to your
specific requirements, providing a new level of power
protection control and adaptability.
•Standard two-year warranty — The Liebert GXT2 6000
UPS is backed by Liebert’s standard warranty, giving you
piece of mind with your purchase.
User replaceable hot
swappable internal batteries —
Provide five minutes of runtime at
full load. Additional runtime
with 2U battery cabinets —
Provides extended battery
runtime for applications that
require longer backup time.
Includes rear panel connection for
additional battery cabinets.
Liebert Power Monitoring Capabilities
The operation of the GXT2 6000
can be monitored using
• MultiLink™ Automated System
Shutdown Software
• OpenComms™ Nform
Monitoring System
• Liebert Universal Monitor and
Remote Power Monitor Panels
• Third Party Monitoring System
3
TOTAL CONFIDENCE IN
THE DECISION YOU'VE MADE.
Liebert UPStation® GXT2 6000 UPS
Specifications
L I E B E R T CO R P O R AT I O N
Model Number
Model Rating
DIMENSIONS in (mm)
WEIGHT lbs (kg)
Nominal Operating Frequency
Factory Default VAC
Allowable Input Phase Angle
Factory Default
Input Frequency w/o Battery Operation
Factory Default VAC
Output Phase Angle
Allowable Output Phase Angle
Factory Default
User Configurable
Frequency
Waveform
Overload Rating
Operating Temp
Storage Temp
Relative Humidity
Operating Elevation
Storage Elevation
Audible Noise
AGENCY
Surge Immunity
Transportation
Model Number
WEIGHT lbs (kg)
Type
Quantity x V x Rating
Battery Mfg / Part #
Recharge Time
Model Number
DIMENSIONS in (mm)
WEIGHT lbs (kg)
BATTERY PARAMETERS
Qty x V x Rating
Battery Mfg / Part #
ENVIRONMENTAL
Operating Temp
Storage Temp
Relative Humidity
Operating Elevation
Storage Elevation
AGENCY
Model Number
PD-HDWR
PD-HDWR-MBS
GXT2-6000RT208
4200W/5200VA at 127/220 (120 or 240 degrees only)
4200W/5200VA at 120/208 (120 or 240 degrees)
4200W/6000VA at 120/240 (180 degrees)
4200W/6000VA at 115/230 (180 degrees only)
3780W/5400VA at 110/220 (180 degrees only)
3360W/4800VA at 100/200 (180 degrees only)
Unit W x D x H in. (mm) 6.9 x 24.2 x 16.9 (176 x 615 x 430)
Unit 67 (30.3)
INPUT AC PARAMETERS
50 or 60 Hz (Factory Default = 60)
120/208 VAC at 120 degrees
L1-L2 Factory Default Input Phase Angle 120 degrees
120, 180, 240 degrees, Auto-sensing on application of AC
(Restrictions for L-N voltages other than 120 VAC)
OUTPUT PARAMETERS
L1-N, L2-N VAC 120 VAC nominal
40 - 70 Hz
120/208 VAC @ 120 degrees
L1-L2 Factory Default
120 degrees
120, 180, 240 degrees Auto-sensing on initial application of input AC
L1-N, L2-N VAC 120 VAC nominal
L1-N, L2-N VAC 100/110/115/120/127 VAC, ±3%
50 Hz or 60 Hz, Nominal
Sinewave
200% for 8 cycles; 130% for 10 seconds with transfer to bypass
ENVIRONMENTAL
+32°F to +104°F (0°C to +40°C)
+5°F to +122°F (-15°C to +50°C)
0% to 95%, non-condensing
Up to 10,000 ft. (3000m) at 104°F (40°C) without derating
50,000 ft. (15,000 m) maximum
<55 dBA, at 1 meter from the rear; <50 dBA, at 1 meter from the front or sides
Safety UL 1778, c-UL Listed (Suitable for computer room applications)
RFI/EMI FCC Part 15, Subpart B, Class A
IEEE/ANSI C62.41 Category A & B
ISTA Procedure 1A
INTERNAL BATTERY
GXT2-144BATKIT
79 (35.8)
Valve-regulated, non-spillable,
flame retardant, lead acid
12 x 12V x 9.0 AH
Yuasa / REW 45-12 FR
6 Hours to 90% capacity after
full discharge into 100% load
OPTIONAL EXTENDED BATTERY CABINET
GXT2-144VBATT
Unit W x D x H
3.5 x 24.2 x 16.9 (87 x 618 x 430)
Unit 93.6 (42.5)
Type Valve-regulated, non-spillable, flame retardant, lead acid
12 x 12V x 9.0 AH
Yuasa / REW 45-12 FR
+32°F to +104°F (0°C to +40°C)
+5°F to +122°F (-15°C to +50°C)
0% to 95%, non-condensing
Up to 10,000 ft. (3000m) at 104°F (40°C) without derating
50,000 ft. (15,000m) maximum
Safety UL 1778, c-UL Listed (Suitable for computer room applications)
RFI/EMI FCC Part 15, Subpart B, Class A
Transportation ISTA Procedure 1A
POWER DISTRIBUTION
Amp Rating
Input Power Connection
Output Power Connection
24 Amps
4-Wire Hardwired, 8-10AWG
4-Wire Hardwired, 8-10AWG
24 Amps
4-Wire Hardwired, 8-10AWG
4-Wire Hardwired, 8-10AWG
Includes: Manual Bypass Switch
with Indicator Lamps
PD-001
24 Amps
L14-30P on 10 foot cord
(1) L6-30R, (1) L14-30R, (4) 5-20/15R T-slot
Includes: Manual Bypass Switch
with Indicator Lamps
PD-002
24 Amps
L14-30P on 10 foot cord
(2) L6-20R, (2) 5-20/15R T-slot
Includes: Manual Bypass Switch
with Indicator Lamps
PD-003
24 Amps
L14-30P on 10 foot cord
(2) L6-30R, (4) 5-20/15R T-slot
Includes: Manual Bypass Switch
with Indicator Lamps
30 Amp, Supplied by User
30 Amp, Supplied by User
30 Amp, Supplied by User
Input Branch Circuit Breaker
Power Availability
1050 DEARBORN DRIVE
P.O. BOX 29186
COLUMBUS, OHIO 43229
800.877.9222 PHONE (U.S. &
CANADA ONLY)
614.888.0246 PHONE (OUTSIDE U.S.)
614.841.6022 FAX
VIA LEONARDO DA VINCI 8
ZONA INDUSTRIALE TOGNANA
35028 PIOVE DI SACCO (PD)
ITALY
39 049 9719 111 PHONE
39 049 5841 257 FAX
EMERSON NETWORK POWER ASIA PACIFIC
7/F., DAH SING FINANCIAL CENTRE
108 GLOUCESTER RD, WANCHAI
HONG KONG
852 2 572 2201 PHONE
852 2 802 9250 FAX
LIEBERT WEB SITE
http://www.liebert.com
24
X
7 TECH SUPPORT
800 222 5877 PHONE
614 841 6755 (OUTSIDE U.S.)
While every precaution has been taken to ensure accuracy and
completeness in this literature, Liebert Corporation assumes no
responsibility, and disclaims all liability for damages resulting
from use of this information or for any errors or omissions.
© 2004 Liebert Corporation. All rights reserved throughout
the world. Specifications subject to change without notice.
All names referred to are trademarks or registered trademarks
of their respective owners.
® Liebert and the Liebert logo are registered trademarks
of the Liebert Corporation.
® Keeping Business in Business is a registered trademark
of the Liebert Corporation.
The Emerson logo is a trademark and service mark
of Emerson Electric Co.
SL-23172 (R6/04)
Printed in USA