Liebert 539031G10 power cable

AC Power
For Business-Critical Continuity™
Emerson Network Power Rack PDU Systems
Product Selection Guide - North American Models
TABLE OF CONTENTS
1.0
EMERSON NETWORK POWER RACK PDU SYSTEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.1
Safety and Agency Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2.0
DETERMINING THE RIGHT EMERSON PDU FOR YOUR APPLICATION . . . . . . . . . . . . . . . . . . .2
3.0
KNURR DI-STRIP PRODUCT SELECTION GUIDE - BASIC RACK PDUS . . . . . . . . . . . . . . . . .3
3.1
Overview - Basic Rack PDUs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3.2
Basic Rack PDU Optional Cord Sets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3.3
Dimensional Drawings - Basic Rack PDUs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4.0
LIEBERT MPH PRODUCT SELECTION GUIDE - MANAGED RACK PDUS . . . . . . . . . . . . . . . 27
4.1
Overview - Managed Rack PDUs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
4.2
Specifications - Liebert MPH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
4.3
Model Number Configuration - Liebert MPH. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4.4
Managed Rack PDU Optional Cord Sets and Cable Restraints . . . . . . . . . . . . . . . . . . . . . . 30
4.5
Dimensional Drawings - Managed Rack PDUs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
5.0
LIEBERT MPX - ADAPTIVE RACK PDUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
5.1
Overview - Adaptive Rack PDUs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
5.2
MPX PRC (Power Rail Chassis). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
5.3
MPX PEM (Power Entry Module) and MPX IPC (Input Power Cord) . . . . . . . . . . . . . . . . . 36
5.4
MPX BRM (Branch Receptacle Module) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
5.5
Adaptive Rack PDU Optional Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
5.5.1
5.5.2
5.5.3
5.5.4
5.5.5
5.5.6
5.5.7
Cord Sets and Cable Restraints. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Liebert RPC™ (RPC-1000) and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Part Numbers for Liebert RPC and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ports on the Liebert RPC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Liebert RPC Capabilities and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RPC BDM—Basic Display Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Temperature/Humidity Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
37
37
38
38
39
40
40
6.0
LIEBERT MPX SYSTEM PRODUCT SELECTION GUIDE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
6.1
STEP 1 - Select an MPX PRC (Quantity x 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
6.2
STEP 2 - Select an MPX PEM / MPX IPC (Quantity x 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
6.3
STEP 3 - Select an MPX BRM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
6.4
STEP 4 - Select Communication Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
6.5
System Selection Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
6.6
Specifications for Liebert MPX Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
6.7
Dimensional Drawings - Adaptive Rack PDUs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
i
FIGURES
Figure 1
Figure 2
Figure 3
Figure 4
Figure 5
Figure 6
Figure 7
Figure 8
Figure 9
Figure 10
Figure 11
Figure 12
Figure 13
Figure 14
Figure 15
Figure 16
Figure 17
Figure 18
Figure 19
Figure 20
Figure 21
Figure 22
Figure 23
Figure 24
Figure 25
Figure 26
Figure 27
Figure 28
Figure 29
Figure 30
Figure 31
Knurr DI-STRIP 35351011 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Knurr DI-STRIP 35351021 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Knurr DI-STRIP 35351031 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Knurr DI-STRIP 35351041 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Knurr DI-STRIP 35351051 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Knurr DI-STRIP 35351061 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Knurr DI-STRIP 35351081 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Knurr DI-STRIP 35352011 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Knurr DI-STRIP 35352021 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Knurr DI-STRIP 35352031 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Knurr DI-STRIP 35352041 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Knurr DI-STRIP 35352051 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Knurr DI-STRIP 35352061 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Knurr DI-STRIP 35352078 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Knurr DI-STRIP 35353011 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Knurr DI-STRIP 35353021 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Knurr DI-STRIP 35353031 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Knurr DI-STRIP 35353041 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Knurr DI-STRIP 35353051 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Knurr DI-STRIP 35353061 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Knurr DI-STRIP 35353078 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Knurr DI-STRIP 35353088 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Liebert MPH rack mount power strip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Liebert MPH vertical power strip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Liebert MPX 1880 and 1035 models and components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
MPX PRC (Power Rail Chassis) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Liebert RPC ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
RPC BDM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Temperature/humidity sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Liebert MPX MPXPRC-1035mm mixed modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Liebert MPX MPXPRC-1880mm mixed modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
TABLES
Table 1
Table 2
Table 3
Table 4
Table 5
Table 6
Table 7
Table 8
Table 9
Specifications - Knurr DI-STRIP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Cord sets - Knurr DI-STRIP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Specifications - Liebert MPH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Cord sets and cable restraints - Liebert MPH. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Selections for Power Entry Module MPXPEM-NVAXXAXX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Selections for Power Entry Module MPXPEM-NHBXXV30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Selections for Power Entry Module MPXPEM-NHBXXX30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Selections for Power Entry Module MPXPEM-NHBXXW30 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Specifications - MPX BRM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
ii
Emerson Network Power Rack PDU Systems
1.0
EMERSON NETWORK POWER RACK PDU SYSTEMS
Emerson Network Power’s Rack PDU Systems is a family of products that delivers power and management to connected IT equipment through a global and comprehensive offering including Basic,
Managed and Adaptive Rack PDU systems.
Each PDU type offers simplified installation and easy operation. Each type is compatible with
standard rack enclosures. These Emerson Rack PDUs provide easy low-cost installation, simple
relocation, security and proven design and performance.
Emerson Rack PDUs can be set up with varying degrees of power-monitoring and management.
When power or management requirements grow, the adaptive PDUs are scalable, enabling them to
grow with the installation.
Emerson PDUs are available for the entire spectrum of power needs of every type of rack equipment.
• Knurr® DI-STRIP - Basic Rack PDU systems, provide a broad range of power distribution capacities and connectivity solutions in a robust package.
• Liebert MPH™ - Managed Rack PDUs with single-phase or three-phase capability for fixed power
input/output with remote management support; one-piece unit with monitoring at the branch
level and control at the receptacle level; available in rack-mount and zero U configurations.
• Liebert MPX™ - Adaptive Rack PDUs built with modular and scalable components that can be
installed and reconfigured on-site to meet changing input and output power connectivity needs;
with remote monitoring at the branch level and receptacle management and control at the receptacle level.
1.1
Safety and Agency Compliance
Where a conflict arises between the following documents and statements made herein, the statements
in this specification will govern.
North American Units - 120V and 208V (Single-Phase and Three-Phase)
•
•
•
•
•
UL 60950-1 Information Technology Equipment
CAN/CSA-C22.2 No. 60950-1-03 Information Technology Equipment
FCC, Title 47, Part 15 Subpart B for Class A operation as defined by ANSI Standard C63.4
ISTA Procedure 1A and 2A
RoHS Compliant
1
Determining the Right Emerson PDU for Your Application
2.0
DETERMINING THE RIGHT EMERSON PDU FOR YOUR APPLICATION
Each of the Rack PDU systems Emerson offers is well-suited for delivering power to sensitive, highcapacity, rack-mounted equipment. Determining which is best for a particular installation requires
knowing the basic power requirements of the equipment in the rack, deciding on the acceptable or
preferable level of monitoring and control and then balancing those considerations against site
requirements.
The Emerson Rack PDU product line includes models to fit all types of installations: new or established; stable or rapidly changing; contracting or expanding. Each type of installation may require
any or all types of Emerson Rack PDUs.
After determining your requirements, refer to the data and specifications for each product.
2
Knurr DI-STRIP Product Selection Guide - Basic Rack PDUs
3.0
KNURR DI-STRIP PRODUCT SELECTION GUIDE - BASIC RACK PDUS
3.1
Overview - Basic Rack PDUs
The Knurr DI-STRIP, a Basic Rack PDU system, provides a broad range of power distribution capacities and connectivity solutions in a robust package.
The Knurr DI-STRIP includes an input power cord with appropriate input plug connection and
hydraulic-magnetic branch rated overload protection as appropriate; basic rack mounting provisions
are also provided. Knurr DI-STRIP Rack PDUs are available in rack mount and vertical zero-U form
factors.
The Knurr DI-STRIP fits most standard 600mm width network equipment rack enclosures. Product
fit should be confirmed for each application.
Table 1
Specifications - Knurr DI-STRIP
INPUT
OUTPUT
Voltage
Rated
Amps
Max
Continuous
Amps
kW*
Phase
Plug
Receptacle/Socket
Configuration
035351011
120
15
12
1.4
1
NEMA 5-15P
(9) NEMA 5-15R
035351021
035351031
035351041
035351051
035351061
035351081
035352011
120
120
120
120
120
120
208-240
15
15
20
20
20
30
20
12
12
16
16
16
24
16
1.4
1.4
1.9
1.9
1.9
2.8
3.3
1
1
1
1
1
1
1
NEMA 5-15P
NEMA 5-15P
NEMA L5-20P
NEMA 5-20P
NEMA L5-20P
NEMA L5-30P
NEMA L6-20P
(12) NEMA 5-15R
(18) NEMA 5-15R
(9) NEMA 5-20 T-Slot
(12) NEMA 5-20 T-Slot
(12) NEMA 5-20 T-Slot
(24) NEMA 5-20 T-Slot
(9) IEC-C13 sockets
035352021**
208-240
20
16
3.3
1
IEC-C20 inlet
(9) IEC-C13 sockets
035352031
035352041**
035352051
035352061
208-240
208-240
208-240
208-240
20
20
30
30
16
16
24
24
3.3
3.3
4.9
4.9
1
1
1
1
NEMA L6-20P
IEC-C20 inlet
NEMA L6-30P
NEMA L6-30P
035352078
208-240
30
24
4.9
1
NEMA L6-30P
035353021
120/208
20
16
5.7
3
NEMA L21-20P
035353031
120/208
20
16
5.7
3
NEMA L21-20P
035353041
035353011
120/208
120/208
20
30
16
24
5.7
8.6
3
3
NEMA L21-20P
NEMA L21-30P
035353051
120/208
30
24
8.6
3
NEMA L21-30P
035353061
120/208
30
24
8.6
3
NEMA L21-30P
(12) IEC-C13 sockets
(12) IEC-C13 sockets
(4) IEC-C19 sockets
(24) IEC-C13 sockets
(20) IEC-C13 +
(4) IEC-C19 sockets
(18) IEC-C13 +
(6) IEC-C19 sockets
(27) IEC-C13 +
(6) IEC-C19 sockets
(27) 5-20 T-Slot
(6) IEC-C19 sockets
(18) IEC-C13 +
(6) IEC-C19 sockets
(27) IEC-C13 +
(6) IEC-C19 sockets
035353078
208-240
60
48
17.3
3
035353088
208-240
42
34
24.4
3
Part
Number
IEC60309
(3 pole, 4 wire,
250VAC, blue)
(2) IEC60309
(3 pole, 4 wire,
250VAC, blue)
All input cords are 10 ft. (3m) in length.
* Formulas used to calculate the kW:
For single-phase: input voltage x max continuous amps = watts
For three-phase: input voltage x max continuous amps x 1.73 = watts
** Knurr DI-STRIP output expansion modules require the use of a cord set for input power.
3
Form
Factor
Rack mount
or Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Rack mount
or Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
(42) IEC-C13 +
(6) IEC-C19 sockets
Vertical
(42) IEC-C13 +
(6) IEC-C19 sockets
Vertical
Knurr DI-STRIP Product Selection Guide - Basic Rack PDUs
3.2
Basic Rack PDU Optional Cord Sets
Output Cord Sets
Output cord sets are available to support conversion of Rack PDU power output receptacles to alternative power output connections and to support Rack PDU output expansion capabilities.
Conversion of power output connections can be provided on Rack PDUs with IEC-C19 receptacles.
The output cord set for these systems includes an IEC-C20 plug to connect to the IEC-C19 receptacle,
a 3 ft. (1m) power cord and receptacle to connect to user equipment. Available receptacles include:
IEC-C13 to connect to IEC-C14 equipment plugs and IEC-C19 to connect to NEMA L6-20P equipment
plugs.
Knurr DI-STRIP output expansion modules are powered via an IEC-C20 input connection. These
systems provide output expansion capabilities when connected to a receptacle on a separate Rack
PDU. The output cord set for these systems includes an IEC-C19 receptacle to connect to the IEC-C20
plug on the output expansion Knurr DI-STRIP, a 3 ft. (1m) power cord and plug to connect to the
Rack PDU receptacle providing power. Available plugs include: IEC-C20 to connect to an IEC-C19
Rack PDU receptacle.
Input Cord Sets
Input cord sets are available to support conversion of Rack PDU power input connections to
alternative power input connections. Conversion of power input can be provided on Rack PDUs with
L5-20P plug connections. The input cord set includes an L5-20R receptacle to connect to the L5-20P
Rack PDU plug, a 1 ft. (0.3m) power cord and a 5-20P plug.
Table 2
Cord sets - Knurr DI-STRIP
Cord Sets
Output Cord Sets - Power Output Conversion
539031G5
Output Cord Set - Power Output Conversion - IEC-C20 to IEC-C13, 3 ft. (1m)
539031G6
Output Cord Set - Power Output Conversion - IEC-C20 to IEC-C13, 10 ft. (3m)
539031G9
Output Cord Set - Power Output Conversion - IEC-C20 to NEMA L6-20R, 3 ft. (1m)
539031G10
Output Cord Set - Power Output Conversion - IEC-C20 to NEMA L6-20R, 10 ft. (3m)
Output Cord Sets - Power Output Expansion
539031G7
Output Cord Set - Power Output Expansion - IEC-C20 to IEC-C19, 3 ft. (1m)
539031G8
Output Cord Set - Power Output Expansion - IEC-C20 to IEC-C19, 10 ft. (3m)
539031G3
Output Cord Set - Power Output Expansion - IEC-C14 to IEC-C19, 3 ft. (1m)
539031G4
Output Cord Set - Power Output Expansion - IEC-C14 to IEC-C19, 10 ft. (3m)
Input Cord Sets - Power Input Conversion
539031G12
Input Cord Set - Power Input Conversion - L5-20R to 5-20P, 1 ft. (0.3m)
4
www.knuerr.com
5
5-15P
10 ft.
(3m)
1
Phase
120
Voltage
(VAC)
15
Rated
Amps
12
Max. Cont.
Amps
1
5-15R (9)
1
120
12
12
Max. Cont. Amps
Receptacle Type
Receptacle
Bank Type (Qty) Phase Voltage (VAC) Per Receptacle Per Bank
OUTPUT POWER
Input
Plug
Input
Cord
INPUT POWER
5-15P
(2-pole, 3-wire)
SIDE VIEW
REAR VIEW
12.2" (311mm)
17.6" (447mm)
FRONT VIEW
2"
(50mm)
1.7"
(44mm)
Rev. 3
NOTES:
1. Unit dimensions:
17.6" (447mm) L x 1.7" (44mm) W x 2" (50mm) D
2. Unit weight: 2.5 lb. (1.1kg)
3. Shipping dimensions:
18.9" (480mm) L x 2.8" (71mm) W x 3.3" (84mm) D
4. Shipping weight: 2.8 lb. (1.3kg)
5. All wiring is to be in compliance with national
and local electric codes.
6. Mounting provisions provided.
35351011
ENVIRONMENTAL:
Operating: 32°F to 131°F (0°C to 55°C), 5% - 95% RH
non-condensing, non-corrosive
Storage temperature: -4°F to 140°F (-20°C to 60°C)
AGENCY:
CSA tested to UL 60950-1
RoHS compliant (reduction of hazardous substances)
2.5"
(63mm)
Figure 1
2.9"
(73mm)
03.535.101.1
00/00 000000
3.3
120 VAC , 60Hz
Input: max. 15A
Outlets : max. 15A
NA B AS IC
DI S TR IP
Knurr DI-STRIP Product Selection Guide - Basic Rack PDUs
Dimensional Drawings - Basic Rack PDUs
Knurr DI-STRIP 35351011
www.knuerr.com
6
5-15P
10 ft.
(3m)
1
Phase
120
Voltage
(VAC)
15
Rated
Amps
12
Max. Cont.
Amps
1
5-15R (9)
1
120
12
12
Max. Cont. Amps
Receptacle Type
Receptacle
Bank Type (Qty) Phase Voltage (VAC) Per Receptacle Per Bank
OUTPUT POWER
Input
Plug
Input
Cord
INPUT POWER
5-15P
(2-pole, 3-wire)
SIDE VIEW
REAR VIEW
12.2" (311mm)
19.6" (497mm)
FRONT VIEW
2"
(50mm)
1.7"
(44mm)
Rev. 3
NOTES:
1. Unit dimensions:
19.6" (497mm) L x 1.7" (44mm) W x 2" (50mm) D
2. Unit weight: 2.7 lb. (1.2kg)
3. Shipping dimensions:
22.2" (565mm) L x 2.8" (70mm) W x 3.3" (85mm) D
4. Shipping weight: 3.1 lb. (1.4kg)
5. All wiring is to be in compliance with national
and local electric codes.
6. Mounting provisions provided.
35351021
ENVIRONMENTAL:
Operating: 32°F to 131°F (0°C to 55°C), 5% - 95% RH
non-condensing, non-corrosive
Storage temperature: -4°F to 140°F (-20°C to 60°C)
AGENCY:
CSA tested to UL 60950-1
RoHS compliant (reduction of hazardous substances)
2.5"
(63mm)
Figure 2
4.8"
(123mm)
03.535.102.1
00/00 000000
120 VAC , 60Hz
Input: max. 15A
Outlets : max. 15A
NA B AS IC
DI S TR IP
Knurr DI-STRIP Product Selection Guide - Basic Rack PDUs
Knurr DI-STRIP 35351021
NA B AS IC
DI S TR IP
www.knuerr.com
7
5-15P
10 ft.
(3m)
1
Phase
120
Voltage
(VAC)
15
Rated
Amps
12
Max. Cont.
Amps
SIDE VIEW
REAR VIEW
1
5-15R (18)
1
120
12
12
Max. Cont. Amps
Receptacle Type
Receptacle
Bank Type (Qty) Phase Voltage (VAC) Per Receptacle Per Bank
OUTPUT POWER
Input
Plug
Input
Cord
5-15P
(2-pole, 3-wire)
12.7" (323mm)
27.4" (697mm)
FRONT VIEW
2"
(50mm)
2.5"
(63mm)
Rev. 3
NOTES:
1. Unit dimensions:
27.4" (697mm) L x 1.7" (44mm) W x 2" (50mm) D
2. Unit weight: 3.3 lb. (1.5kg)
3. Shipping dimensions:
42" (1065mm) L x 2.4" (60mm) W x 3" (75mm) D
4. Shipping weight: 3.8 lb. (1.72kg)
5. All wiring is to be in compliance with national
and local electric codes.
6. Mounting provisions provided.
35351031
ENVIRONMENTAL:
Operating: 32°F to 131°F (0°C to 55°C), 5% - 95% RH
non-condensing, non-corrosive
Storage temperature: -4°F to 140°F (-20°C to 60°C)
AGENCY:
CSA tested to UL 60950-1
RoHS compliant (reduction of hazardous substances)
12.2" (311mm)
1.7"
(44mm)
Figure 3
INPUT POWER
03.535.103.1
00/00 000000
120 V AC , 60Hz
Input: max. 15A
Outlets : max. 15A
Knurr DI-STRIP Product Selection Guide - Basic Rack PDUs
Knurr DI-STRIP 35351031
8
L5-20P
10 ft.
(3m)
1
Phase
120
Voltage
(VAC)
L5-20P
(2 pole, 3 wire)
20
Rated
Amps
16
Max. Cont.
Amps
SIDE VIEW
REAR VIEW
17.6" (447mm)
FRONT VIEW
1
5-20R (9)
1
120
16
16
Max. Cont. Amps
Receptacle Type
Receptacle
Bank Type (Qty) Phase Voltage (VAC) Per Receptacle Per Bank
OUTPUT POWER
Input
Plug
Input
Cord
INPUT POWER
www.knuerr.com
Rev. 3
NOTES:
1. Unit dimensions:
17.6" (447mm) L x 1.7" (44mm) W x 2" (50mm) D
2. Unit weight: 3 lb. (1.35kg)
3. Shipping dimensions:
26.8" (680mm) L x 2.4" (60mm) W x 3.9" (100mm) D
4. Shipping weight: 3.4 lb. (1.54kg)
5. All wiring is to be in compliance with national
and local electric codes.
6. Mounting provisions provided.
35351041
ENVIRONMENTAL:
Operating: 32°F to 131°F (0°C to 55°C), 5% - 95% RH
non-condensing, non-corrosive
Storage temperature: -4°F to 140°F (-20°C to 60°C)
AGENCY:
CSA tested to UL 60950-1
RoHS compliant (reduction of hazardous substances)
2"
(50mm)
1.7"
(44mm)
Figure 4
03.535.104.1
00/00 000000
120 VAC , 60Hz
Input: max. 15A
Outlets : max. 15A
NA B AS IC
DI S TR IP
Knurr DI-STRIP Product Selection Guide - Basic Rack PDUs
Knurr DI-STRIP 35351041
NA B AS IC
DI S TR IP
9
5-20P
10 ft.
(3m)
1
Phase
120
Voltage
(VAC)
5-20P
(2-pole, 3-wire)
20
Rated
Amps
16
Max. Cont.
Amps
SIDE VIEW
REAR VIEW
1
5-20R (9)
1
120
16
16
2.5"
(63mm)
2"
(50mm)
1.7"
(44mm)
Rev. 3
NOTES:
1. Unit dimensions:
19.6" (497mm) L x 1.7" (44mm) W x 2" (50mm) D
2. Unit weight: 3.5 lb. (1.57kg)
3. Shipping dimensions:
26.8" (680mm) L x 2.4" (60mm) W x 3.9" (100mm) D
4. Shipping weight: 3.9 lb. (1.76kg)
5. All wiring is to be in compliance with national
and local electric codes.
6. Mounting provisions provided.
35351051
ENVIRONMENTAL:
Operating: 32°F to 131°F (0°C to 55°C), 5% - 95% RH
non-condensing, non-corrosive
Storage temperature: -4°F to 140°F (-20°C to 60°C)
AGENCY:
CSA tested to UL 60950-1
RoHS compliant (reduction of hazardous substances)
19.6" (497mm)
FRONT VIEW
12.2" (311mm)
Receptacle Type
Max. Cont. Amps
Receptacle
Bank Type (Qty) Phase Voltage (VAC) Per Receptacle Per Bank
OUTPUT POWER
Input
Plug
Input
Cord
INPUT POWER
4.8"
(123mm)
www.knuerr.com
Figure 5
03.535.105.1
00/00 000000
120 VAC , 60Hz
Input: max. 15A
Outlets : max. 15A
Knurr DI-STRIP Product Selection Guide - Basic Rack PDUs
Knurr DI-STRIP 35351051
www.knuerr.com
10
L5-20P
10 ft.
(3m)
1
Phase
120
Voltage
(VAC)
20
Rated
Amps
16
Max. Cont.
Amps
1
5-20R (12)
1
120
16
16
Max. Cont. Amps
Receptacle Type
Receptacle
Bank Type (Qty) Phase Voltage (VAC) Per Receptacle Per Bank
OUTPUT POWER
Input
Plug
Input
Cord
INPUT POWER
L5-20P
(2-pole, 3-wire)
SIDE VIEW
REAR VIEW
2.5"
(63mm)
2"
(50mm)
1.7"
(44mm)
Rev. 3
NOTES:
1. Unit dimensions:
19.6" (497mm) L x 1.7" (44mm) W x 2" (50mm) D
2. Unit weight: 3.2 lb. (1.47kg)
3. Shipping dimensions:
24.6" (625mm) L x 2.4" (60mm) W x 3.9" (100mm) D
4. Shipping weight: 3.5 lb. (1.6kg)
5. All wiring is to be in compliance with national
and local electric codes.
6. Mounting provisions provided.
35351061
ENVIRONMENTAL:
Operating: 32°F to 131°F (0°C to 55°C), 5% - 95% RH
non-condensing, non-corrosive
Storage temperature: -4°F to 140°F (-20°C to 60°C)
AGENCY:
CSA tested to UL 60950-1
RoHS compliant (reduction of hazardous substances)
12.2" (311mm)
19.6" (497mm)
FRONT VIEW
Figure 6
4.8"
(123mm)
03.535.106.1
00/00 000000
120 VAC , 60Hz
Input: max. 15A
Outlets : max. 15A
NA B AS IC
DI S TR IP
Knurr DI-STRIP Product Selection Guide - Basic Rack PDUs
Knurr DI-STRIP 35351061
1.8"
(46mm)
NA B AS IC
www.knuerr.com
11
L5-30P
10 ft.
(3m)
1
Phase
120
Voltage
(VAC)
30
Rated
Amps
24
Max. Cont.
Amps
5-20R (12)
5-20R (12)
1
2
1
1
120
120
16
16
20
20
24.5" (622mm)
Branch 2
Rev. 4
NOTES:
1. Unit dimensions:
43.2" (447mm) L x 1.7" (44mm) W x 3.3" (85mm) D
2. Unit weight: 7.51 lb. (3.4kg)
3. Shipping dimensions:
44.9" (1140mm) L x 2.8" (70mm) W x 6.3" (160mm) D
4. Shipping weight: 8.4 lb. (3.8kg)
5. All wiring is to be in compliance with national
and local electric codes.
6. Mounting provisions provided.
35351081
ENVIRONMENTAL:
Operating: 32°F to 131°F (0°C to 55°C), 5% - 95% RH
non-condensing, non-corrosive
Storage temperature: -4°F to 140°F (-20°C to 60°C)
AGENCY:
CSA tested to UL 60950-1
RoHS compliant (reduction of hazardous substances)
SIDE VIEW
REAR VIEW
43.2" (1097mm)
FRONT VIEW
Max. Cont. Amps
Receptacle Type
Receptacle
Branch Type (Qty) Phase Voltage (VAC) Per Receptacle Per Branch
OUTPUT POWER
Input
Plug
L5-30P
(2-pole, 3-wire)
16.6" (422mm)
Input
Cord
INPUT POWER
03.535.108.1
00/00 000000
120 VAC , 60Hz
Input: max. 15A
Outlets : max. 15A
Branch 1
20A branch circuit breakers
3.3"
(85mm)
2.1"
(53mm)
1.7"
(44mm)
Figure 7
DI S TR IP
20A branch
circuit breakers
Knurr DI-STRIP Product Selection Guide - Basic Rack PDUs
Knurr DI-STRIP 35351081
12
L6-20P
10 ft.
(3m)
1
Phase
208-240
Voltage
(VAC)
L6-20P
(2-pole, 3-wire)
20
Rated
Amps
16
Max. Cont.
Amps
SIDE VIEW
REAR VIEW
FRONT VIEW
17.6" (447mm)
1
IEC-C13 (9)
1
208-240
12
16
Max. Cont. Amps
Receptacle Type
Receptacle
Bank Type (Qty) Phase Voltage (VAC) Per Receptacle Per Bank
OUTPUT POWER
Input
Plug
Input
Cord
INPUT POWER
www.knuerr.com
Rev. 3
NOTES:
1. Unit dimensions:
17.6" (447mm) L x 1.7" (44mm) W x 2" (50mm) D
2. Unit weight: 3.2 lb. (1.4kg)
3. Shipping dimensions:
24.6" (625mm) L x 2.4" (60mm) W x 3.9" (100mm) D
4. Shipping weight: 3.4 lb. (1.5kg)
5. All wiring is to be in compliance with national
and local electric codes.
6. Mounting provisions provided.
35352011
ENVIRONMENTAL:
Operating: 32°F to 131°F (0°C to 55°C), 5% - 95% RH
non-condensing, non-corrosive
Storage temperature: -4°F to 140°F (-20°C to 60°C)
AGENCY:
CSA tested to UL 60950-1
RoHS compliant (reduction of hazardous substances)
2"
(50mm)
1.7"
(44mm)
Figure 8
03.535.201.1
00/00 000000
120 VAC , 60Hz
Input: max. 15A
Outlets : max. 15A
NA B AS IC
DI S TR IP
Knurr DI-STRIP Product Selection Guide - Basic Rack PDUs
Knurr DI-STRIP 35352011
NA B AS IC
DI S TR IP
13
IEC-C20
Inlet *
10 ft.
(3m)
1
Phase
208-240
Voltage
(VAC)
20
Rated
Amps
17.6" (447mm)
16
Max. Cont.
Amps
SIDE VIEW
REAR VIEW
12.2" (311mm)
FRONT VIEW
1
IEC-C13 (9)
1
208-240
12
16
Receptacle Type
Max. Cont. Amps
Receptacle
Bank Type (Qty) Phase Voltage (VAC) Per Receptacle Per Bank
OUTPUT POWER
* Requires a cordset
Input
Input
Cord
INPUT POWER
2.5" (63mm)
www.knuerr.com
2.9" (73mm)
2"
(50mm)
1.7"
(44mm)
Rev. 3
NOTES:
1. Unit dimensions:
17.6" (447mm) L x 1.7" (44mm) W x 2" (50mm) D
2. Unit weight: 1.5 lb. (0.7kg)
3. Shipping dimensions:
19" (483mm) L x 3" (75mm) W x 2.4" (60mm) D
4. Shipping weight: 1.7 lb. (0.8kg)
5. All wiring is to be in compliance with national
and local electric codes.
6. Mounting provisions provided.
35352021
ENVIRONMENTAL:
Operating: 32°F to 131°F (0°C to 55°C), 5% - 95% RH
non-condensing, non-corrosive
Storage temperature: -4°F to 140°F (-20°C to 60°C)
AGENCY:
CSA tested to UL 60950-1
RoHS compliant (reduction of hazardous substances)
IEC-C20 inlet
Figure 9
03.535.202.1
00/00 000000
120 V AC , 60Hz
Input: max. 15A
Outlets : max. 15A
Knurr DI-STRIP Product Selection Guide - Basic Rack PDUs
Knurr DI-STRIP 35352021
www.knuerr.com
14
L6-20P
10 ft.
(3m)
1
Phase
208-240
Voltage
(VAC)
20
Rated
Amps
16
Max. Cont.
Amps
SIDE VIEW
REAR VIEW
1
IEC-C13 (12)
1
208-240
12
16
2.5" (63mm)
2"
(50mm)
1.7"
(44mm)
Rev. 3
NOTES:
1. Unit dimensions:
19.6" (497mm) L x 1.7" (44mm) W x 2" (50mm) D
2. Unit weight: 3.4 lb. (1.5kg)
3. Shipping dimensions:
26.8" (680mm) L x 2.4" (60mm) W x 3.9" (100mm) D
4. Shipping weight: 3.7 lb. (1.68kg)
5. All wiring is to be in compliance with national
and local electric codes.
6. Mounting provisions provided.
35352031
ENVIRONMENTAL:
Operating: 32°F to 131°F (0°C to 55°C), 5% - 95% RH
non-condensing, non-corrosive
Storage temperature: -4°F to 140°F (-20°C to 60°C)
AGENCY:
CSA tested to UL 60950-1
RoHS compliant (reduction of hazardous substances)
12.2" (311mm)
FRONT VIEW
19.6" (497mm)
Max. Cont. Amps
Receptacle Type
Receptacle
Bank Type (Qty) Phase Voltage (VAC) Per Receptacle Per Bank
OUTPUT POWER
Input
Plug
Input
Cord
INPUT POWER
L6-20P
(2-pole, 3-wire)
4.8" (123mm)
03.535.203.1
00/00 000000
120 VAC , 60Hz
Input: max. 15A
Outlets : max. 15A
NA B AS IC
DI S TR IP
Knurr DI-STRIP Product Selection Guide - Basic Rack PDUs
Figure 10 Knurr DI-STRIP 35352031
www.knuerr.com
15
IEC-C20
inlet *
10 ft.
(3m)
1
Phase
208-240
Voltage
(VAC)
20
Rated
Amps
16
Max. Cont.
Amps
SIDE VIEW
REAR VIEW
1
IEC-C13 (12)
1
208-240
12
16
2.5" (63mm)
2"
(50mm)
1.7"
(44mm)
Rev. 3
NOTES:
1. Unit dimensions:
19.6" (497mm) L x 1.7" (44mm) W x 2" (50mm) D
2. Unit weight: 1.8 lb. (0.8kg)
3. Shipping dimensions:
22.6" (575mm) L x 2.4" (60mm) W x 3" (75mm) D
4. Shipping weight: 2.1 lb. (0.9kg)
5. All wiring is to be in compliance with national
and local electric codes.
6. Mounting provisions provided.
35352041
ENVIRONMENTAL:
Operating: 32°F to 131°F (0°C to 55°C), 5% - 95% RH
non-condensing, non-corrosive
Storage temperature: -4°F to 140°F (-20°C to 60°C)
AGENCY:
CSA tested to UL 60950-1
RoHS compliant (reduction of hazardous substances)
12.2" (311mm)
Max. Cont. Amps
Receptacle Type
Receptacle
Bank Type (Qty) Phase Voltage (VAC) Per Receptacle Per Bank
OUTPUT POWER
* Requires a cordset
Input
Plug
Input
Cord
INPUT POWER
03.535.204.1
00/00 000000
120 VAC , 60Hz
Input: max. 15A
Outlets : max. 15A
NA B AS IC
DI S TR IP
4.8" (123mm)
IEC-C20 INLET
19.6" (497mm)
Figure 11
FRONT VIEW
Knurr DI-STRIP Product Selection Guide - Basic Rack PDUs
Knurr DI-STRIP 35352041
16
L6-30P
10 ft. (3m)
1
2
Branch
1
IEC-C19 (2)
IEC-C19 (2)
30
Rated
Amps
Per Receptacle Type
208-240
Voltage
L6-30P
(2-pole, 3-wire)
Max. Continuous Amps
24
Max. Cont.
Amps
1
1
208-240
208-240
20
20
16
16
Branch 2
03.535.205.1
00/00 000000
120 VAC , 60Hz
Input: max. 15A
Outlets : max. 15A
NA B AS IC
DI S TR IP
20A branch circuit breaker
www.knuerr.com
3.3"
(85mm)
1.7"
(44mm)
35352051
Rev. 3
AGENCY:
CSA tested to UL 60950-1
RoHS compliant (reduction of hazardous substances)
ENVIRONMENTAL:
Operating:
32°F to 131°F (0°C to 55°C), 5% - 95% RH
non-condensing, non-corrosive
Storage Temperature: -4°F to 140°F (-20°C to 60°C)
NOTES: