Network Shutdown Module V3 – User Manual Page 1/53

Network Shutdown Module V3

User guide

Table of Contents

1   Introduction to the Network Solution ................................................................................... 4  

1.1

  Overview ............................................................................................................................................ 4  

1.2

  Monitoring the UPSs over the network ............................................................................................... 5  

1.3

  Protecting the computers / servers..................................................................................................... 6  

1.4

  Connecting the UPS........................................................................................................................... 7  

1.4.1

 

1.4.2

1.4.3

 

 

Connecting to the Network .............................................................................................................................. 7  

Select Network Architecture ............................................................................................................................ 7  

Network Performances .................................................................................................................................... 7

 

2   Installation............................................................................................................................... 8  

2.1

  Hardware Pre-requisites (Electrical and Network Connections) ......................................................... 8  

2.2

  Software Installation Pre-requisites .................................................................................................... 9  

2.2.1

 

2.2.2

 

On the System Hosting « Network Shutdown Module V3 »............................................................................ 9

On the System that Displays Web-based Graphical User Interface ............................................................. 10

 

 

2.3

  Quick Start ....................................................................................................................................... 11  

2.4

  Software Installation Procedure ....................................................................................................... 12  

2.5

  Application deployment and silent installation (advanced) ............................................................... 14  

2.6

  Uninstalling the Network Shutdown Module ..................................................................................... 14  

3   Minimal configuration steps ................................................................................................ 15  

3.1

  Introduction ...................................................................................................................................... 15  

3.2

  The IP address of the UPS that powers your server. ....................................................................... 15  

3.3

  Users accounts configuration ........................................................................................................... 16  

4   Use ......................................................................................................................................... 17  

4.1

  Monitoring the server and the UPS(s) .............................................................................................. 17  

4.1.1

 

4.1.2

 

Local access .................................................................................................................................................. 17

Remote access .............................................................................................................................................. 17

 

 

4.2

  System and UPS event log .............................................................................................................. 19  

4.3

  UPS Events list ................................................................................................................................ 20  

4.4

  Test the communication with the UPS.............................................................................................. 21  

4.4.1

 

4.4.2

 

Simple Tests .................................................................................................................................................. 21

Advanced tests............................................................................................................................................... 22

 

 

4.5

  Start and stop the Shutdown Module (advanced)............................................................................. 22  

5   Other Configuration possibilities........................................................................................ 23  

5.1

  Introduction ...................................................................................................................................... 23  

5.2

  Configure system parameters .......................................................................................................... 23  

5.3

  Shutdown Configuration................................................................................................................... 24  

5.4

  Checking for Upgrades .................................................................................................................... 25  

5.5

  Events and actions (advanced configuration)................................................................................... 26  

6   Multi-UPS Systems ............................................................................................................... 27  

6.1

  Caution ............................................................................................................................................ 27  

6.2

  Presentation..................................................................................................................................... 27  

6.3

  Create a multi-UPS configuration ..................................................................................................... 30  

7   Appendix ............................................................................................................................... 31  

7.1

  Single UPS Mode compatibility ........................................................................................................ 31  

7.2

  Multi-UPS Mode Compatibility list .................................................................................................... 31  

7.3

  Examples of Multi UPS configurations ............................................................................................. 31  

7.4

  Multi-UPS Systems and Event Management ................................................................................... 31  

7.5

  Application deployment and silent installation .................................................................................. 32  

7.5.1

 

7.5.2

7.5.3

7.5.4

 

 

 

Introduction .................................................................................................................................................... 32  

Customized installation package ................................................................................................................... 33

 

Install the Shutdown Module in silent mode .................................................................................................. 34  

Advanced installation options ........................................................................................................................ 35

 

7.6

  Single UPS Shutdown Sequence..................................................................................................... 36  

7.7

  Multi UPS shutdown sequence (example with Static Transfer Switch) ............................................. 37  

7.8

  Additional information on events and actions ................................................................................... 38  

Network Shutdown Module V3 – User Manual Page 2/53

Network Shutdown Module V3

User guide

7.8.1

 

7.8.2

 

7.8.3

 

7.8.4

 

7.8.5

 

Action settings Tab ........................................................................................................................................ 38

Events Tab ..................................................................................................................................................... 42

Test tab .......................................................................................................................................................... 44

The action parameters (execute and send email) ......................................................................................... 44

Software utilities ............................................................................................................................................. 45

7.9

  FAQ and Error messages ................................................................................................................ 47  

 

 

 

 

 

8   Glossary ................................................................................................................................ 49  

9   Acknowledgements .............................................................................................................. 50  

9.1

  SQLite.............................................................................................................................................. 50  

9.2

  Pi3Web ............................................................................................................................................ 50  

9.3

  PHP ................................................................................................................................................. 50  

9.4

  OpenSSL ......................................................................................................................................... 51  

9.5

  Lighttpd ............................................................................................................................................ 53  

9.6

  WxWidget......................................................................................................................................... 53  

Network Shutdown Module V3 – User Manual Page 3/53

Network Shutdown Module V3

User guide

1 Introduction to the Network Solution

1.1 Overview

Network Solution:

• provides information on events concerning the supply of power to the computers connected to your computer network,

• carries out automatic shutdown of computer systems,

• monitors and controls all the UPSs connected to the network.

As illustrated in the picture below, Network Solution provides these 2 main functions:

supervising the UPSs over the Network,

protecting the computers,

Network Shutdown Module V3 – User Manual Page 4/53

Network Shutdown Module V3

User guide

1.2 Monitoring the UPSs over the network

Depending on your needs, you can either use:

• your Internet browser to monitor each UPS, as

Management Card and Shutdown Module include a Web server.

• your company’s standard Network Management

System:

> HP-Openview,

> CA Unicenter,

> HP Insight Manager,

> IBM Tivoli Netview,

> …

To simplify integration of MGE UPSs with these

NMS, you can use one of the Network

Management System. These kits are available on

Management Pac 2 CD-Rom (ref 66923).

• the supervisor "Enterprise Power Manager"

> 5 nodes (free),

> 50 nodes (ref 66923),

> Unlimited (ref 66924).

Network Shutdown Module V3 – User Manual Page 5/53

Network Shutdown Module V3

User guide

1.3 Protecting the computers / servers

The Network Shutdown Module installed on each of the servers to be protected performs this function. Note that the Shutdown Module is available on several Operating Systems.

The Shutdown modules:

• continuously wait for information from the Mgt. Card connected to the MGE UPSs.

• warns administrators and users if AC power fails and proceeds with graceful system shutdown before the end of battery backup power is reached.

• offers a remote supervision interface through any web browser (with a secured SSL/HTTPS connection enabled by default),

• manages multi UPS redundant configurations ( see “Multi-UPS systems” chapter )

> Several UPSs in parallel

> 2 UPSs in Hot standby (or serial) redundancy

> 2 redundant UPSs through Static Transfer Switch

> UPSs powering a server with multiple power supplies

3 UPSs in parallel powering several servers

A UPS that powers servers with load-shedding function

Network Shutdown Module V3 – User Manual Page 6/53

Network Shutdown Module V3

User guide

1.4 Connecting the UPS

1.4.1 Connecting to the Network

This function can be performed either through network Cards inserted in the UPS (Network Management

Card)

The Network Management Card:

• manages communication with the UPS.

• periodically accesses the information concerning the UPS,

• makes this information available to the connected applications (Network Shutdown Modules, Web

Browser, Network Management Systems, Enterprise Power Manager)

1.4.2 Select Network Architecture

Below is one software and hardware architecture showing how MGE UPSs can protect several computers.

This typical example is intended to assist you in designing your own architecture.

Connection with Network Management Card

On the diagram above, the following two types of connections are required:

• the electrical power cables,

• the TCP/IP communication network.

The Network Management Card is designed to support a maximum of:

• 35 or 50 Network Shutdown Module connections in standard secure mode

Network Shutdown Module V3 – User Manual Page 7/53

Network Shutdown Module V3

User guide

Note: This user manual only applies to Network Shutdown Module V3. For previous versions of Network

Shutdown Module V2.x, please read the HTML on line manual.

2.1 Hardware Pre-requisites (Electrical and Network Connections)

Connection steps

Before installing the Network Solution, the UPS must be set up as indicated in the steps below.

• Shut down the computers to be protected by the UPS.

• How to connect UPS / card / network: o If a Network Management Card is used, insert the optional card in the UPS and connect the

UPS to the computer network.

• Start the UPS, then the computers.

• Setting up the protection o If a Network Management Card is used, it must be set up (see the Mgt. Card's user manual).

• Install Network Shutdown Module on all the other machines that are to be protected by the UPS (supplied with UPS battery backup power).

Network Shutdown Module V3 – User Manual Page 8/53

Network Shutdown Module V3

User guide

2.2 Software Installation Pre-requisites

2.2.1 On the System Hosting « Network Shutdown Module V3 »

See on APC Web site, Software / Firmware download area ‘’Software Upgrades – MGE Accessories”.

See on APC Web site, Software / Firmware download area ‘’Software Upgrades – MGE Accessories”.

2.2.1.3 Standby configuration (Windows):

In Configuration Panel -> Power Option properties:

• You must unselect the Standby configuration of your Operating System to be compliant with the Network

Shutdown Module. With the standby configuration checked your system is not protected.

• If you want to save energy, please prefer the hibernate feature.

2.2.1.4 Broadcast Message configuration (Windows):

If the “ Broadcast administrator messages / Broadcast user messages ” function is activated, on Network

Shutdown Module, you have to check that the “Messenger” Service is started.

This service is mandatory to use the broadcast messages on Windows.

2.2.1.5 Firewall configuration (Windows & Linux):

If you use Windows XP with Service Pack 2 or Windows 2003 with Service Pack 1:

(Optional) To enable a remote access for supervision and configuration you will have to open the following ports of the Windows Firewall:

4679 NSMSupervision

4680 NSMManagement (access through SSL)

These ports are reserved at IANA (Internet Assigned Numbers Authority, http://www.iana.org/).

Proceed as follows:

• Enter into Start -> Parameters-> Configuration Panel -> Windows Firewall

• In the Exception tab, click on «add a port »

• Enter the name « NSMSupervision » the number « 4679 » the protocol « TCP »

• Apply and perform the same operations for the next port

• Enter the name « NSMManagement » the number « 4680 » the protocol « TCP »

• Apply

If you use a Firewall with all ports closed by default:

To enable communication between Network Shutdown Module and Network Management Card:

• Port 80 must be opened as a destination port (for output) on the machine hosting Network Shutdown

Module.

Network Shutdown Module V3 – User Manual Page 9/53

Network Shutdown Module V3

User guide

2.2.2 On the System that Displays Web-based Graphical User Interface

Important:

The Network Shutdown Module graphical interface can be accessed remotely using a simple Web browser.

Access to this interface is secured through SSL connection (default configuration) and must also be secured through Login & password .

The Network Shutdown Module graphical interface has been tested with:

• Mozilla Firefox 2.0 or 3.0 is recommended for better performance. (Firefox is mandatory for Linux)

• Microsoft Internet Explorer V7, V8

Note: For the Web browser, we advise you against the use of the highest security level. Some configuration screens are not useable.

Javascript and Cookies must be authorized for the selected security level.

Network Shutdown Module V3 – User Manual Page 10/53

Network Shutdown Module V3

User guide

To install the Network Shutdown Module in 5 minutes, please perform the following steps on a machine running Windows 2000 / XP / 2003 / 2008 / Vista / 7 or Linux:

Step 1 (Pre-requisites)

Check that following connections are operational:

> the electrical connection between the UPS and the server to protect

> the network connection between the UPS and the Network Management Card.

Step 2 (Optional) and only for Windows Vista, XP with SP 2 or Windows 2003 with SP 1

To enable the configuration and supervision remote access, Network Shutdown Module needs the 4679 and 4680 ports to be opened in the Windows Firewall.

Step 3 (Software Installation)

On a Windows or Linux machine, execute the “Network Shutdown Module” package under an administrator account.

Step 4 (Configuration)

> In the Configuration->Power devices screen,

Enter the default Login «MGEUPS» and default Password «MGEUPS»

Then click on the Add button and

Enter the hostname or the IP address of the Network Management Card.

Save your configuration

> In the Configuration->Users window configure your password (recommended)

> For the multi-UPS configurations, please refer to chapter 6

Step 5 (Operation)

You can now supervise the UPS state and the information concerning the protected server

Network Shutdown Module V3 – User Manual Page 11/53

Network Shutdown Module V3

User guide

2.4 Software Installation Procedure

This section informs on how to install Network Shutdown Module to protect the computer system.

Before starting the installation:

• it is necessary first to install a Network Management Card in the UPS or the Mgt.

• make sure you have the necessary administrator rights to install Network Shutdown Module (for Windows and Linux).

• it is assumed that you are aware of the

installation prerequisites.

Follow these steps to install Network Shutdown Module in interactive (graphical) mode:

Connect to the APC Web Site, software / firmware download area at http://www.apc.com

‘’Software Upgrades

– MGE Accessories. Follow the instructions to download Network Shutdown Module or insert the Solution-Pac 2 CD-ROM (/HF).

For Windows: From CD ROM:

• At the first navigator screen select "Network Solutions" and follow the instructions

From the Web:

• Execute the downloaded package.

For Linux: From CD ROM:

• Mount your CD-ROM (ex: /mnt/cdrom)

• Open Default.htm from your internet browser to discover the solutions and select

"Network Solutions".

• Follow the instructions

From the web:

• Download and save the file to your computer.

• Authorize the execution right on the downloaded package (through graphical interface)

or execute the command : chmod 755 nsm_linux_xx_3_xx_xx.run

• To install execute the package (double click)

• If necessary enter the root password

• Follow the instructions

• Choose the installation language. The selected language will correspond to the one of the installed product.

• Read and accept the License Agreement

• Choose the installation directory of the Network Shutdown Module.

> Windows default value is C:\Program Files\...\NetworkShutdownModule

> Linux default value is /usr/local/…/NetworkShutdownModule

• Complete the installation.

> In the Configuration-> Power device screen,

Enter the default Login «MGEUPS» and default Password «MGEUPS»

Then click on the Add button and

Enter the IP address of the Network Management Card.

Save your configuration

Configuration of the communication parameters

Network Shutdown Module V3 – User Manual Page 12/53

Network Shutdown Module V3

User guide your (recommended)

• For multi-UPS systems, please refer to the chapter "Multi UPS systems" .

• The Network Shutdown Module is now configured by default. You can anyway customize the Network

Shutdown Module and for example configure your password (recommended).

• The installed components are automatically started.

• It is possible to test Network Shutdown Module .

• The protection function is now active on the computer and will be run automatically each time the computer is started.

Follow these steps to install Network Shutdown Module in console mode:

• For Linux, if the server doesn’t have the graphical layer installed, you have to use the specific package called nsm_linux-cli_xxx.run

• Login as root in a terminal

• Then install the Network Shutdown Module in silent mode

Note : You can configure the Network Shutdown Module either:

• through the silent mode parameters (e.g.)

./<FileName> -install –silent –agentName ‘172.17.1.2’ remote access

Network Shutdown Module V3 – User Manual Page 13/53

Network Shutdown Module V3

User guide

2.5 Application deployment and silent installation (advanced)

After customizing the Network Shutdown Module configuration (name or IP address of Network Management

Card, events and actions, etc.), you can build a Network Shutdown Module installation package that contains your specific configuration.

You can then deploy this Network Shutdown Module configuration on other machines that have the same operating system.

Network Shutdown Module application deployment

Refer to the appendix “ Application deployment and silent installation ”

2.6 Uninstalling the Network Shutdown Module

Windows:

Linux:

Shutdown Module. or

• In the Network Shutdown Module program.

• The KDE shortcut K:-> Network Shutdown Module->Uninstall is used to uninstall

Network Shutdown Module.

• The Gnome shortcut Applications -> Network Shutdown Module->Uninstall is used to uninstall Network Shutdown Module.

• In console mode, you can execute <Installation directory>/packaging/nsmInstaller – uninstall

<Installation directory> default value is /usr/local/…/NetworkShutdownModule/

Network Shutdown Module V3 – User Manual Page 14/53

Network Shutdown Module V3

User guide

3.1 Introduction

In this chapter we describe the basic and minimal configuration steps that must be performed before using the

Network Shutdown Module.

The other and optional configuration possibilities are described later .

3.2 The IP address of the UPS that powers your server.

In the Configuration -> Power device screen, click on the Add button

Then following screen appears:

Adding a power device

Power device settings

From this screen, you can define the following parameters:

• Network Name or IP address of the Network Management Card. This parameter must correspond to the

UPS that powers your machine.

Note:

For multi-UPS configurations, you have the possibility to enter several names or IP addresses (using the

[Add] button). For these advanced configurations, please refer to the Chapter « Multi – UPS systems ».

Network Shutdown Module V3 – User Manual Page 15/53

Network Shutdown Module V3

User guide

3.3 Users accounts configuration

Click on the Users item of the Configuration section on the left menu.

The default Login «MGEUPS» and default Password «MGEUPS» with Visualization – Management rights.

Note : For security reasons we advise you to remove this default login and to create a new login with new access password.

User accounts configuration

You can configure several user accounts.

To add a user account:

• enter

• select

Visualization – Management (the user will be able to access all the sections)

Visualization (the user will only access to the Supervision (*) and the About sections)

• click

Network Shutdown Module V3 – User Manual Page 16/53

Network Shutdown Module V3

User guide

4 Use

4.1 Monitoring the server and the UPS(s)

4.1.1 Local access

From the system where the Network Shutdown Module is installed,

• You can use the following shortcut:

For Windows: Start -> Programs -> Network Shutdown Module -> Supervision

For Linux (KDE): K-> Network Shutdown Module -> Supervision

For Linux (Gnome): Applications -> Network Shutdown Module -> Supervision

• You can also use the icon in the task bar:

To access to this interface:

• Double-click on the icon or

• Right click the icon in the task bar to access to the item

“Network Shutdown module Status”

4.1.2 Remote access

• From a remote machine, you can type the following URL in a Web browser for

> secured SSL access:

https://< name or IP address of computer hosting NSM>:4680/mgeups/

> or for non secured access:

http://< name or IP address of computer hosting NSM>:4679/mgeups/

Note: The Web server is “case sensitive” for the URL.

• Accept the SSL Certificate (by clicking on Yes)

To install the certificate on IE7/8 for Vista, you need to perform the following steps:

> Run IE as an administrator (Right-click the

Accepting the SSL Certificate desktop icon)

> Visit the NSM site.

> Click through the certificate error

> Click the "Certificate Error" button in the address bar.

> Click View Certificate

> Click Install Certificate

> Unlike on XP, you must click the “Place all certificates in the following store” radio button, and choose the “Trusted Root Certification

Authorities” store. If you don’t do this, the certificate goes in your personal store, and it isn’t trusted by IE.

Network Shutdown Module V3 – User Manual Page 17/53

Network Shutdown Module V3

User guide

• Enter the Login and Password (optional)

• The following page appears:

Server and UPS supervision

Section « Information on the protected server»

• Server name / IP address:

The Network name of the machine hosting the Network Shutdown Module and its IP address. system:

The operating system of the machine hosting the Network Shutdown Module.

• Contact

The location of the machine hosting the Network Shutdown Module the contact person for the machine hosting the Network Shutdown Module.

These values can be configured in the System page .

Section concerning the UPS that powers the protected server

This icon represents the status of the power device. It can have following values: Critical/Alert/Normal

• Name/ IP address:

The Network name (or IP address) of the device.

• Device:

The commercial product name.

• Link:

• Contact / Location:

Link to the device Web site (if available).

The device contact. (value of syscontact object or can also be configured in the

Device page).

The device location. (value of syslocation object or can also be configured in the Device page).

Status

• Communication:

Communication Failure).

• Power source:

• Battery:

Device communication status (OK / Network Communication Failure / device

AC Power / Battery.

Charging / Discharging / Battery fault.

• Output:

Main output status (ON/OFF/Internal Failure/On Automatic

Bypass/Manual By Pass/Overload).

Values

• Output Load Level:

• Battery capacity:

• Backup time:

The output load level of the device.

Battery capacity of the device.

The device remaining backup time.

Note that this view is impacted when any device status is affected.

Network Shutdown Module V3 – User Manual Page 18/53

Network Shutdown Module V3

User guide

4.2 System and UPS event log

In the Supervision section, Select the Log item, and the following page appears:

Network Shutdown Module event Log

Use the filter in the top right to choose the data to display:

All:

Displays all the logs.

UPS logs:

System logs:

Only displays the UPS events.

Only displays the System events.

• Use the button to clear the displayed data.

Network Shutdown Module V3 – User Manual Page 19/53

Network Shutdown Module V3

User guide

4.3 UPS Events list

The icons in the Status view represent the event severity.

Normal. With this event, the device is coming back to a normal status.

Event list:

• Communication with "Management Card " is restored.

• The system is powered by the utility.

• The UPS output is on.

• Communication restored with UPS.

OK.

• UPS returns to normal load.

OK.

• Bypass: Return on UPS.

• End of low battery alarm. lost

• Redundancy lost (for multi-UPS systems)

Warning. A problem has occurred on the device. Your application is still powered.

Event list:

• The system is powered by the UPS battery.

• Output on automatic bypass.

• Output on manual bypass. lost

• Redundancy lost (for multi-UPS systems)

Critical. A serious problem has occurred on the device. This problem requires an urgent action.

Your application might NOT BE powered anymore.

Event list:

• UPS output is off.

• Battery

• UPS

• UPS fault.

• Low battery alarm.

• System shutdown in progress...

Communication lost between the Card agent and the Network Shutdown Module.

Or communication lost between the device and the Card

Event list:

• Communication with "Management Card" has failed (Warning).

• Communication failure with UPS (Warning).

Network Shutdown Module V3 – User Manual Page 20/53

Network Shutdown Module V3

User guide

4.4 Test the communication with the UPS

After the installation, it is important to check that Network Shutdown Module communicates with the agent.

Test 1:

When Network Shutdown Module starts, an icon is displayed by default in the task bar, if you’re running

Windows or Linux (Gnome or KDE). It can indicate one of the following status conditions:

Icon Description Meaning

AC power

Utility failure / load on battery

The installation is in correct running order.

Check the power cable for the UPS. Note that this is the normal display if the AC-input power has failed.

Communication failure

The Acquisition

Engine is stopped

Battery fault

Wait an instant, then check the the computer and the Cards.

Check in the services list that communication parameters the service is started .

between

Contact the technical support department or your dealer to check battery connections or replace worn batteries.

Remark:

When your mouse is over the icon in the taskbar a summary status is displayed:

Test 2:

• You can view the Network Shutdown Module HTML supervision interface and then check that the UPS has been recognized and that the communication status is OK.

To access to this interface:

• Double-click on the icon or

• Right click the icon in the task bar to access to access to the item “Network Shutdown module Status”

Test 3:

Where possible, another procedure is to generate an event such as a loss of AC power (by disconnecting the

UPS from the wall outlet) to obtain the message below.

Network Shutdown Module V3 – User Manual Page 21/53

Network Shutdown Module V3

User guide

For test purpose, it is also possible to display the messages in verbose mode and check the content.

Messages in verbose mode:

Event log:

It is possible to consult the Event log .

Advanced trace:

We warn you against the use of disk space for this Trace mode.

To validate verbose mode :

> in the bin/dae and bin/netsystray directory of the application, rename the file called debugMode.off into debugMode.on,

> restart the Network Shutdown Module - Acquisition engine as explained hereafter,

> view the trace in the file called traceDebug.txt in the same directory.

To stop verbose mode :

> in the bin directory of the application, rename the file called debugMode.off into debugMode.on,

> restart the Network Shutdown Module - Acquisition engine as explained hereafter.

4.5 Start and stop the Shutdown Module (advanced)

(Warning, if you stop, your computer is not protected anymore).

Windows:

From the Windows services panel you can start and stop the 2 services that are created:

• Network Shutdown Module - Acquisition engine

• Network Shutdown Module - Web server

• In graphical mode, from your services panel you can start and stop the mge-nsm

Linux: service that is created.

• In console mode, you can also run the following commands:

/etc/init.d/mge-nsm start

/etc/init.d/mge-nsm stop

/etc/init.d/mge-nsm restart

Network Shutdown Module V3 – User Manual Page 22/53

Network Shutdown Module V3

User guide

5.1 Introduction

Basic configuration steps are described before (refer to Power devices and Users ).

In this chapter we describe other configuration possibilities.

5.2 Configure system parameters

Click on the System item of the Configuration section on the left menu

System parameters configuration

This page lets you enter the system parameters for the application.

It contains:

• The system administrator name.

• The system localisation.

Note:

This information is visible in the Supervision -> Status page

Network Shutdown Module V3 – User Manual Page 23/53

Network Shutdown Module V3

User guide

Shutdown Configuration page

From this screen, you can define the following parameters:

Use central configuration provided by Management Card:

With this function, all the Network Shutdown Modules will obtain their configuration from the card.

In multi-UPS context, you can select the IP of the card from which you obtain the configuration

If you unselect this option, you can modify for your computer the following parameters:

Shutdown duration:

This is the time in seconds required by the system to go through its shutdown procedure.

The Network Shutdown Modules transmit their own shutdown duration to the Card.

The role of this parameter is illustrated by the example of shutdown sequence.

> Possible values : 0 to 9999

> Default value : 120

> Unit : Second

It is on the basis of these values (shutdown duration of all the systems) that the Card sends the delayed shutdown order to the UPS.

Shutdown timer (Shutdown when timer reaches)

After AC power failure before initiating the system shutdown procedure, this is the time in seconds that the system waits.

> Possible values

> Default value

:

:

0 to 999999 this criterion for system shutdown is not enabled by default

> Unit : Second

This value must be selected to provide users with enough time to close their applications and disconnect, but within the battery backup time provided by the UPS.

See the UPS manual for information on the backup time.

If another criterion occurs before the end of the shutdown timer, the shutdown procedure is immediately run.

The role of this parameter is illustrated by the example of shutdown sequence .

Remark:

If the shutdown timer on a client is the criterion that trips the shutdown procedure, automatic restart of the client is not guaranteed (the case where AC power returns and only the client station is shut down).

Network Shutdown Module V3 – User Manual Page 24/53

Network Shutdown Module V3

User guide

Message broadcast to the administrator

A message is sent over the network to administrators connected to the server protected by Network

Shutdown Module.

Check following Windows pre-requisite

> Default value : activated

Message broadcast to users

A message is sent over the network to users connected to the server protected by Network Shutdown

Module.

Check following Windows pre-requisite

> Default value : activated

This function gives you access to software updates.

Your Network Shutdown Module will always be up to date if you select the Check automatically option.

When a new software version is detected on APC Web Site, just follow the wizard instructions.

Note: This operation will preserve your database information.

Network Shutdown Module V3 – User Manual

Check for upgrade window

Page 25/53

Network Shutdown Module V3

User guide

5.5 Events and actions (advanced configuration)

Basic principles:

Network Shutdown Module receives events (e.g. Utility Failure) from the UPS and in reply to these events executes actions (e.g. notification, e-mail, etc.).

The above interface allows links between events and actions to be configured, as well as customizing protection for the machine hosting Network Shutdown Module. events / actions

This very powerful tool enables the Network Shutdown Module behaviour to be modified intuitively.

Modifying events and actions is only necessary if you require your protection module to operate in a particular way. The default configuration ensures optimal protection of your installation. Modifying parameters must therefore be done with care as it could compromise the protection of your installation.

This advanced settings is described in appendix

Network Shutdown Module V3 – User Manual Page 26/53

Network Shutdown Module V3

User guide

6.1 Caution

Please check complete list of UPSs compatible with our Redundancy/Parallel mode service:

Caution:

We strongly recommend you contact trained technical support for setup, in order to guarantee the integrity of your high-availability system.

Recommendations:

• For the UPS Models it is better to Enable "Communication Shutoff orders" so that the UPS accepts

Network Management Card off commands.

Exception for 2 UPSs in Hot standby (Sequential redundancy) .

• The Network Management Cards MUST have the same shutdown criteria parameters.

You can use default settings (or duplicate configuration using specific tools like Mupgrade)

• For 3 phase UPS systems it is mandatory to check battery parameters before installing Network

Shutdown Module.

6.2 Presentation

With the latest version the Network Shutdown Module manages multi UPS redundant configurations.

The Network Shutdown Module V3 makes it possible

• to supervise an installation made up of several UPSs. It provides the user with an overall view of the installation by concentrating the information acquired from the individual UPSs. The data acquisition is performed through the IP network.

• to trigger the shutdown of the machine on which it is installed, taking into account the consolidated

« global » view of the electrical installation.

The Network Shutdown Module V3 manages following electrical configurations:

• Several UPSs in parallel:

Note only for MGE Galaxy 7000:

When UPS is in ‘’Power Saving mode (PSM) in progress’’, it is considered by NSM as redundant UPS.

• 2 UPSs in Hot standby (Sequential redundancy):

Note: For the UPS Model that is close to the load you have to disable "Communication Shutoff orders" so that the UPS transfers to bypass and doesn't accept Network Management

Card off commands.

(You can use the UPS display or the UPS Configuration tool)

• 2 UPSs in serial redundancy:

Network Shutdown Module V3 – User Manual Page 27/53

Network Shutdown Module V3

User guide

• 2 unitary UPSs through Static Transfer Switch:

• UPSs powering a server with multiple power supplies:

• Some simple combinations of these electrical associations are also supported by Network Shutdown module.

Important: To know the list of multi-UPS configurations that are supported by the Network Shutdown

Module, please refer to the appendix List of tested multi-UPS configurations .

The Network Shutdown module doesn’t take into account the real electrical drawing. It computes dynamically the minimal number of UPSs below which the system has to be shut down.

This minimal number of UPSs is recomputed permanently according to the following parameters:

• the nominal load of each UPS

• the output load level of each UPS

• the UPS remaining backup time of each UPS

When several UPSs electrically power the computer hosting Network Shutdown Module, the main interface is as follows:

Network Shutdown Module V3 – User Manual

Server and multi-UPS supervision

Page 28/53

Network Shutdown Module V3

User guide

Following information is displayed:

Information on the protected server section

• Server name / IP address: the Network name of the machine hosting the Network Shutdown Module and its IP address. system: the Operating System name of the machine hosting the Network Shutdown Module.

• Contact the location of the machine hosting the Network Shutdown Module the contact person for the machine hosting the Network Shutdown Module.

These values can be configured in the System page .

Multi-sources Information section:

• Power

x + y redundant(s)

> the first value x is the minimal number of UPSs that is necessary to power the load.

> the second value y is the number of UPSs in redundancy.

> the addition of these 2 values is the total number of available UPSs.

• Global estimated load level: the output load level for the global installation.

• Global estimated battery capacity: the battery capacity for the global installation.

• Global estimated backup time: the remaining backup time for the global installation. This value takes into account UPS load balancing anticipation.

Power devices List section:

In this section you will find the information, concerning the UPSs that power the server hosting Network

Shutdown Module:

The following UPS information is displayed in this page:

• Status

• Name

• Device name

• Output Load Level

• Battery Capacity

• Backup Time

• Link this icon represents the severity of the monitored device; the Network name (if available) or the IP address the device product name the output level of the device the battery capacity of the device the remaining backup time of the device link to the device Web site (if available)

Notes:

• You can sort out your device list by clicking on the column titles (Status / Name / Device Name / Load

Level / …).

A second click will reverse the sorting order.

Detailed view access: Select one of the device in the left menu and the following detailed view page appears.

The following icons of the detailed view offer these functions:

Previous device Back to list view Next device

Network Shutdown Module V3 – User Manual Page 29/53

Network Shutdown Module V3

User guide

6.3 Create a multi-UPS configuration

For the multi-UPS configurations, you have to enter the IP address of each UPS that electrically powers the machine hosting the Network Shutdown Module.

From the, Configuration->Communication page, please proceed as follows:

Multi-UPS configuration

• Click

• Key in the first IP address

• Key in the next IP addresses (Click on the Add button).

• Select the Redundancy type of your installation (Parallel, STS, Sequential, Serial, Server with multiple power supplies) according to your electrical configuration.

Note: For the Hot Standby/Sequential UPS Model refer to the specific UPS configuration

• (optional) key in the Minimal number of redundant UPSs powering your system:

The default value is 0.

If you set this parameter to a higher level you will receive the Redundancy Lost alarm when you don’t have enough redundant UPSs.

Note: We warn you against the consequences of these settings, but you also have the possibility to trigger the shutdown action on “Redundancy Lost“ alarm in the actions settings.

• Click

Network Shutdown Module V3 – User Manual Page 30/53

Network Shutdown Module V3

User guide

7 Appendix

7.1 Single UPS Mode compatibility

See on APC Web site, Software / Firmware download area ‘’Software Upgrades – MGE Accessories”.

7.2 Multi-UPS Mode Compatibility list

See on APC Web site, Software / Firmware download area ‘’Software Upgrades – MGE Accessories”.

7.3 Examples of Multi UPS configurations

Electrical drawing Description

2 UPSs of 1000 VA in parallel through a Static Transfer

Switch

1 UPS loaded at 75 %

" Minimal number of necessary

UPSs"

1

1 UPS loaded at 0%

2 UPSs of 1500 VA and a server with redundant power supply

Each UPS loaded at 25 %

2 UPSs of 1500 VA and a server with redundant power supply

Each UPS loaded at 60 %

2 UPSs of 3000 VA in hot standby configuration

1 UPS loaded at 33 %

1 UPS loaded at 0%

2 UPSs 30 KVA parallel/ redundant mode

Each UPS loaded at 40 %

2 UPSs 30 KVA parallel/power extension mode

Each UPS loaded at 60 %

4 UPSs 100 KVA parallel

(3 power extension + 1 redundant mode)

Each UPS loaded at 70 %

8 UPSs 400 KVA parallel

(7 power extension + 1 r redundant mode)

Each UPS loaded at 80 %

1

2

1

1

2

3

7

7.4 Multi-UPS Systems and Event Management

Please refer to the Events and Actions section

Network Shutdown Module V3 – User Manual Page 31/53

Network Shutdown Module V3

User guide

7.5 Application deployment and silent installation

7.5.1 Introduction

Network Shutdown Module offers powerful features to easily deploy the application on several computers:

• Silent

• Providing some command line parameters to the installer

• Re-packaging of a customized application

According to your needs you have several possibilities:

First example:

Your computers are powered by a single UPS and you are using the Network Shutdown Module default configuration.

• Step 1: Copy the Network Shutdown Module package on the different computers (according to Operating

System)

• Step 2: Execute the installation in silent mode and provide the card IP address as a parameter in the command line

Second example:

Your computers are powered by a Multi UPS system or you don’t use Network Shutdown Module default configuration.

• Step 1: Install Network Shutdown Module on a computer (interactive or silent mode)

2: Network Shutdown Module

3: (containing your configuration)

• Step 4: Copy this package on the different computers (according to the Operating System)

• Step 5: Execute the installation in silent (or possibly in interactive mode)

Network Shutdown Module V3 – User Manual Page 32/53

Network Shutdown Module V3

User guide

7.5.2 Customized installation package

After having customized the Network Shutdown Module configuration (name or IP address of Network

Management Card, events and actions, etc.), you can build a Network Shutdown Module installation package which contains your specific configuration.

You can then deploy this Network Shutdown Module configuration on other machines which have the same operating system.

Note: Specific configuration include the UPS(s) IP address(es), the event and action, … but not the install path or install mode.

Please proceed as follows to build the customized package (Windows or Linux):

Build customized package

• In

• From the dialog box, then click on "OK".

• A confirmation message is displayed when the package is built. You will find in this message the path and the name of the new package.

• Copy this package to the other machines in your chosen directory.

Note that the Customized installation package will be installed in default installation directory.

> Windows default value is C:\Program Files\...\NetworkShutdownModule

> Linux default value is /usr/local/…/NetworkShutdownModule

• Execute the package (standard installation or Silent installation).

Important:

• If you install a “customized package” on a computer where a “previous version” of Network Shutdown

Module is running:

=> The software version will be upgraded but the configuration of the “previous version” will be kept.

In order to replace a previous installation, you must first uninstall it.

Network Shutdown Module V3 – User Manual Page 33/53

Network Shutdown Module V3

User guide

7.5.3 Install the Shutdown Module in silent mode

In addition to Network Shutdown Module installation in standard mode where the user configures the parameters during the installation, it is possible to install Network Shutdown Module in silent mode i.e. with no user interaction.

Follow these steps to install Network Shutdown Module in silent mode:

• Make sure you have administrator rights.

Build a customized package with specific parameters (ex: The Network Management Card IP address, the events and actions …).

• Copy this package to the “target” machine in your chosen directory.

• (Linux) If necessary execute the command: chmod 755 nsm_linux_xx_3_xx_xx.run

• To start the installation procedure, run the command:

<Filename> -install -silent to validate silent mode for Windows.

./<Filename> -install -silent to validate silent mode for Unix.

Or to provide the card IP address as parameter to the installer run the command:

<Filename> -install -silent –agentName 192.12.13.14 (Windows)

./<Filename> -install –silent –agentName 192.12.13.14 (Linux)

Note: for the other options refer to the next paragraph

• The installed software is automatically started. It is possible to test Network Shutdown Module .

Example of secured deployment script for Linux:

We use ssh to copy the package on several machines and then execute it.

The script iterates on the machine names.

#!/bin/sh

# Notes :

# - Actions to be performed under root account

# - The target.list file contains the target machine names (1 per line)

# - All theses machines must accept automatic ssh connection.

# - It must be authorized with a key generation on the master

# (machine that executes the script) using "ssh-keygen -t rsa2",

# - Then copy the file ~/.ssh/id_rsa.pub to the target machines

# - and add its content into the file ~/.ssh/known_hosts, ie

# "cat id_rsa.pub >> ~/.ssh/known_hosts" for i in `cat target.list` do echo "Network Shutdown Module Installation on machine $i" scp nsmlinuxv3xxx.run $i:/tmp done ssh $i /tmp/nsmlinuxv3xxx.run –install -silent

Network Shutdown Module V3 – User Manual Page 34/53

Network Shutdown Module V3

User guide

7.5.4 Advanced installation options

• The installer is started with following default options:

-install -installPath <InstallPath>

By default for Windows <InstallPath> = " C:\Program Files\MGE\NetworkShutdownModule "

By default for Linux <InstallPath> = " /usr/local/MGE/NetworkShutdownModule "

• The following exclusive options define the installation / uninstallation mode :

-install

-uninstall options

(with additional options if necessary)

(with additional options if necessary)

-silent Runs the installer without user interactions

-installPath <InstallPath> Provides the installation path as parameter

-debug

-agentName

Starts installer in debug mode

Provides the Card IP name as parameter

-help For the complete list of options

Network Shutdown Module V3 – User Manual Page 35/53

Network Shutdown Module V3

User guide

7.6 Single UPS Shutdown Sequence

Typical example of the backup time provided by a UPS connected to Network Management Card:

1

As soon as it detects the loss of AC power, the Mgt. Card notifies the Network

Shutdown Modules that the system is running on battery power.

2

The Mgt. Card then continuously monitors the criteria set to trip the shutdown procedure. The procedure is launched if: occurred, expires. parameters 6

The Mgt. card centralizes the "shutdown duration" parameters for all the protected computers (machines hosting Network Shutdown Module).

This fourth tripping criterion is implicit.

3

The Mgt. Card launches the shutdown procedure:

The Mgt. Card sends to all the Network Shutdown Modules the system shutdown order.

As a result, each Network Shutdown Module proceeds with shutdown of its system.

Once all the computers have been shut down, the UPS shuts off (interrupts the supply

4

5 of power to the loads) to protect the battery.

Note. This function is not authorized on some UPSs.

Once the utility is restored, the UPS restarts all computers (if shut off the UPS output is a function available).

The diagrams below present the sequence.

Utility

Utility failure

1

2

Shutdown condition

3

Shutdown

4 5

Utility restored

Output

Maximum shutdown duration

6

Network

Management

Card Sequence

Network Shutdown Module V3 – User Manual Page 36/53

Network Shutdown Module V3

User guide

7.7 Multi UPS shutdown sequence (example with Static Transfer Switch)

Typical example of the backup time provided by 2 UPSs in redundancy through Static Transfer Switch.

ω

The Output load level of the first UPS is less than 50 %.

ω

The Output load level of the second UPS is 0 %.

1

As soon as they detect the loss of AC power, the Mgt. Cards notify the Network

Shutdown Modules that the system is running on battery power.

2

The Network Shutdown Modules continuously compute the “minimum number of necessary UPSs”.

3

In this case we suppose that the minimal number is 1.

When the first UPS stops its output, the Static Transfer Switch balances the load on the second UPS. Then we are in a typical « single UPS sequence »

ω

The Mgt. Card launches the shutdown procedure for UPS 2.

ω

As a result, each Network Shutdown Module proceeds with the shutdown of its system.

4

5

Once all the computers have been shut down, the UPS shuts off (interrupts the supply of power to the loads) to protect the battery.

Note: This function is not authorized on some UPSs.

Once the utility is restored, the UPS restarts all computers (if the shutting off the UPS output function available).

The diagrams below present the sequence.

Utility Failure Shutdown criteria on

UPS1

UPS1

Shutoff

Shutdown criteria on

UPS2

UPS 2

Shutoff

Utility Restored

1 3 4 5

Utility

UPS1 Output

UPS2 Output

2

System Shutdown

Duration

6

Shutdown Mod powered by STS

Load powered by UPS1

Load powered by

UPS2

Load unpowered

Load powered by UPS1

Network Shutdown Module V3 – User Manual Page 37/53

Network Shutdown Module V3

User guide

7.8 Additional information on events and actions

7.8.1 Action settings Tab

In the Action settings tab you can configure the actions that are executed by the Network Shutdown Module.

Action settings tab

Select an action in the Action List (e.g. User Notification) then you have the possibility to select the different tabs for the considered action:

• In

, you can configure the selected action that is executed by the Network Shutdown

Module.

• In

, you can associate the selected action with the event(s) that will be able to trigger the action. the , you can execute the action (by simulating the event occurrence).

Restore to default button takes you back to the initial configuration.

Save Change(s) button saves your configuration.

Possible operations on actions

Add ...

: Adds a new action in the Action list, all the parameters must be entered

Duplic.:

Duplicates the selected action, with all its parameters (see Add ...)

Del:

Deletes the selected action

Network Shutdown Module V3 – User Manual Page 38/53

Network Shutdown Module V3

User guide

7.8.1.1 The different actions

• There are several actions classified into two categories:

Standard actions

By default, Network Shutdown Module only uses these actions to ensure the machine's protection and to inform users.

Customized actions

These user-customized actions give access to additional functions.

Action name

User notification

Role

A message is displayed on the screen of the protected machine, its importance is indicated by a colored symbol:

- Green: Information message.

- Yellow: Alarm message.

- Red: Critical alarm message.

- Grey: Communication Lost.

Message broadcast to the administrator

A message is sent over the network to administrators connected to the server protected by Network Shutdown Module.

Note: This action only occurs if the "Administrator notification" box is checked on the

Configuration Network Shutdown Module screen.

Message broadcast A message is sent over the network to users connected to the server protected by to users Network Shutdown Module.

Note: This action only occurs if the "Administrator notification" box is checked on the

Configuration Network Shutdown Module screen.

System shutdown System and UPS shutdown according to the configured parameters .

Execute a program Execution of an application (.exe file) or script (.bat, .cmd, .sh … file).

Send an E-mail Send an alarm message by e-mail using the SMTP network server.

Network Shutdown Module V3 – User Manual Page 39/53

Network Shutdown Module V3

User guide

7.8.1.2 «System Shutdown» Action

When personalizing the action System shutdown in the action configuration page, you can choose the type of shutdown:

• For Windows, there is a choice of shutdown depending on your system and your requirements.

Click on the Parameter button, to read the help on the shutdown type:

• For Linux, only the shutdown option is currently supported.

Shutdown parameters

Shutdown (-shutdown: default selection). This option shuts down your applications and the system, but does not de-energize the computer. The system offers the user the choice to de-energize the computer, in which case it is the UPS that cuts power.

Hibernate (-standby). If your system has the hibernation function (available with Windows 2000), it is better to use it because there are a number of advantages. If the system is shut down, all work in progress and system information are automatically saved to the disk. The computer itself is also deenergized. When mains power returns, all the applications re-open exactly as they were and the user finds himself back in his work environment.

The hibernate function must first have been activated in the operating system. In the power options on the

Windows control panel, check that the hibernate option is activated on the Hibernate tab sheet.

Note: If you select hibernate, but your computer does not in fact have this function, Network Shutdown

Module nonetheless protects the installation by carrying out the normal (default) shutdown.

No force shutdown (-noforce). Shuts the system down without closing the opened applications e.g. Microsoft Word with an unsaved file. (Warning, the system shutdown is not guaranteed)

Power off ( -poweroff: system de-energized). This option shuts down your applications and the system, but does not de-energize the computer. This configuration is advised if you wish to be on hand when the system re-starts. (or for load shedding)

Network Shutdown Module V3 – User Manual Page 40/53

Network Shutdown Module V3

User guide

7.8.1.3 «Send email» Action

Follow these steps to create a Send email action:

Configure the send email action

Select "Send email"

• Click on the Add button

Name:

Enter the name of the new action (unique action identifier)

Type:

Server:

Recipient:

Enter the name of the relay SMTP server (e.g. mail.server.com)

Enter the e-mail address. To send the message to several recipients, separate their addresses by a comma or semi colon.

Sender, Subject and Message fields can be customized as above.

Notes:

1) The "Send an e-mail" action is already pre-configured as above in the installation default. You can use the Duplicate function to create new actions configured in the same way.

2) Some SMTP servers require an email address in the Sender field (and sometimes a valid email address)

... buttons let you include the variables in the program.

• Click on the

Save Changes button.

Network Shutdown Module V3 – User Manual Page 41/53

Network Shutdown Module V3

User guide

In this tab you can associate the action with the event(s) that will trigger the action:

Events Tab

• Select the action from the left hand side of the above screen

=> The list of events already associated with this event appear (checked boxes)

• Check (or uncheck) the events you wish to associate with this action

• Save your configuration using Save change(s) button.

For each event, an on-line help is displayed when the mouse pointer is positioned over it.

Following events can trig the actions. They are classed by category:

7.8.2.1 Notification alarms

These alarms are mainly dedicated to trigger user notification actions:

• Utility failure

The system is now powered by the UPS battery or [by the utility]

• 'Run time to shutdown' alarm

Alarm to indicate the remaining time before system shutdown

• UPS fault (internal fault or battery fault) Internal UPS fault or battery fault was detected or [end of Internal/Battery fault]

• UPS overload

The output is over loaded or [the output load is correct]

• Output on bypass UPS has switched to automatic or manual bypass mode or [end of bypass alarm]

Network Shutdown Module V3 – User Manual Page 42/53

Network Shutdown Module V3

User guide failed or [Communication between Network Management Card and UPS is restored]

7.8.2.2 Protection alarms

These alarms are mainly dedicated to trigger operating system shutdown actions:

• Shutdown criteria is reached One of the criteria for which the system should be shutdown has been reached

• Redundancy lost The installation has no redundancy source available anymore

or [The installation has one or several redundancy source available]

• Protection lost

The number of sources ensuring your installation protection is not sufficient or [The number of sources ensuring your installation protection is sufficient]

7.8.2.3 Multi UPS Systems and Notification Alarms

With default configuration, the Network Shutdown Module considers that the “Notification Alarms” don’t trigger the shutdown. (only the notification action is performed).

Anyway it is possible to configure a “Shutdown action” when a “Notification Alarm” event is received.

In this case:

• The first alarm reception (from one of the UPSs) will trigger the system shutdown.

7.8.2.4 Multi UPS Systems and Protection Alarms

• Shutdown criteria is reached.

With default configuration, the Network Shutdown Module triggers the shutdown when this event is received.

Anyway it is possible to configure a “Shutdown” action when the following events are received.

• Redundancy lost alarm

If the user configures a “Shutdown action” when a “Redundancy lost” event is received, the shutdown will occur when the installation has no redundant source available anymore.

The redundancy Level is configured in Configuration-> Power Devices screen

Following Alarms are taken into account for this alarm :

> UPS fault (internal fault or battery fault)

> Communication failure,

> Output on bypass,

> UPS Stopped.

Lost

If the user configures a “Shutdown action” when a “Protection Lost” event is received, the shutdown will occur when the number of sources ensuring your installation protection is not sufficient.

> Only following UPS faults are taken into account (internal fault or battery fault).

> The By-Pass events (Automatic or Manual) for maintenance reasons are not taken into account.

Network Shutdown Module V3 – User Manual Page 43/53

Network Shutdown Module V3

User guide

In the "Test" tab you can execute the action (by simulating the event occurrence).

You can select the event.

Warning! This action will be really executed. Check that you're ready to perform this test.

Some actions can trigger the shutdown!!

Test Tab

7.8.4 The action parameters (execute and send email)

The Parameter... buttons let you access following screen:

The action parameters (execute and send email)

Network Shutdown Module V3 – User Manual Page 44/53

Network Shutdown Module V3

User guide

The following parameters can be transmitted to actions:

Parameter

/object

Description

Send object name as a parameter

/value Send object value as a parameter

/message Send formatted message as a parameter (refer to label file)

/date Send date in YYYY/MM/DD - HH:MN:SS format

/ldate Send date in the local format of Network Shutdown Module host

/hostname Send Network Shutdown Module host name or IP address

7.8.5 Software utilities

The following utilities are supplied to help you to customize your "Execute" actions:

7.8.5.1 Shutdown.bat (Windows Script)

The "shutdown.bat" script lets you customize the system shutdown.

It allows:

• synchronous (which block whilst running) or asynchronous programs to be run before shutting the system down.

• programs to be time delayed. The " wait.exe

" synchronous utility, distributed in the Network Shutdown

Module default installation directory (<Program Files\...\NetworkShutdownModule), is used.

• programs with specific rights to be run.

Using mgeRunAs.exe

(Windows NT/2000/2003/XP).

• your own system shutdown solution to be used.

• For further information refer to the "shutdown.bat" file in the Network Shutdown Module installation directory. <Program Files\...\NetworkShutdownModule\bin\tools>.

7.8.5.2 Shutdown.sh (Linux Script)

The "shutdown.sh" script lets you customize the system shutdown.

• For further information refer to the "shutdown.sh" file in the Network Shutdown Module installation directory. <install_path>/bin/tools.

Presentation:

"Wait.exe" is a utility used to set up a time delay in a command file (.bat or .cmd file). It can be used in the

shutdown.bat file to wait until the end of an asynchronous task (non blocking).

Location:

The program is located in the installation directory <Program Files\...\NetworkShutdownModule\bin\tools>.

Use:

The parameter for the program is the time delay expressed in milliseconds.

Example:

Wait.exe 2000 <- The system will wait for two seconds.

Network Shutdown Module V3 – User Manual Page 45/53

Network Shutdown Module V3

User guide

Presentation:

Network Shutdown Module action is carried out in the security context of the user's account. It may be necessary to modify the context before certain actions may be run.

MgeRunAs.exe is the means for a user to run specific tools and programs with permissions that are different from those assigned to the user's account.

Localisation: The executable may be found in the Network Shutdown Module installation directory (by default <Program Files\...\NetworkShutdownModule\bin\tools>).

Instructions for use:

• Fill in the domain name as well as the user's name and password.

• Indicate the program or command to be run using the specified account. the

• Copy the command line and paste it in your application. This line may be used as it is in a Network

Shutdown Module Run action or in a script file.

Open console option opens a DOS emulation console during execution.

Remark. The information on the user profile is encrypted in the command line. Encryption also depends on the executable and the parameters mentioned. If the name of the executable or one of the parameters is changed, the command line must be generated (encrypted) again.

Network Shutdown Module V3 – User Manual Page 46/53

Network Shutdown Module V3

User guide

7.9 FAQ and Error messages

During use :

(Linux) How to use Network Shutdown Module system tray with Gnome?

The NSM systray isn’t displayed in Gnome. Some older versions of Gnome do not allow to automate

NSM Systray launch minimized to the tray on login on Gnome. To do so manually :

• Open up your GNOME menu,

• Select Preferences followed by Sessions. Switch to the Startup programs tab,

• Click Add and enter “<Installation directory>/bin/netsystray/mgeNetSystray” as the startup command,

• Click OK and you're done.

To stop NSM Systray from loading upon login, simply remove its entry from the startup programs listing.

(Linux) I’m running WindowMaker or XFCE. Can I use the NSM system tray?

Yes, you can use the systray icon, using:

• wmsystray (http://freshmeat.net/projects/wmsystray/) for WindowMaker,

(Linux) The menu or the systray are missing

Some desktop or windows manager do not provide a way to register menus with sub menu copy the NSM menu files to your desktop

$ cp <installpath>/desktop/*.menu ~/Desktop

• Solution 2:

Bookmark the NSM Supervision Page in your favorite Internet Browser,

> https://< name or IP address of computer hosting NSM>:4680/mgeups/

> or http://< name or IP address of computer hosting NSM>:4679/mgeups/ and call the uninstall from the command line using

<Installation directory>/packaging/nsmInstaller –uninstall

3:

Add the menu entries using your favorite menu editor

Entry 1: name : Supervision

: cmd : <Installation directory>/packaging/nsmInstaller –openURL <URL> with <URL>

> https://< name or IP address of computer hosting NSM>:4680/mgeups/

> or http://< name or IP address of computer hosting NSM>:4679/mgeups/

Entry 2: name : Uninstall

: cmd : <Installation directory>/packaging/nsmInstaller –uninstall

Network Shutdown Module V3 – User Manual Page 47/53

Network Shutdown Module V3

User guide

In the HTML pages.

In the page “Configuration -> Power Device”, when I click on the “Add” button the expected page is not displayed

Solution: Check if an anti popup filter is activated on your web browser and configure this filter to accept the page.

Check you don’t have the highest security level on IE

Cannot display the UPS properties page. HTTP 404 error with IE.

Solution: Check the URL entered.

> https://< name or IP address of computer hosting NSM>:4680/mgeups/

> or http://< name or IP address of computer hosting NSM>:4679/mgeups/

When you attempt to view the properties or configuration pages, the browser requests a user name and password.

Solution: The system administrator has protected access to the pages. You must request a user name and password from your administrator.

No UPS information is available.

Solution:

Check that communication between the UPS and the computer is OK.

Check also that following requirement is met

Port 80 must be opened as a destination port (for output) on the machine hosting Network Shutdown

Module.

Network Shutdown Module V3 – User Manual Page 48/53

Network Shutdown Module V3

User guide

8

Glossary

IP address / name

When TCP/IP is installed on a computer, an address and a name are assigned to the system. Each address or name are unique and the address is made up of four numbers, each between 0 and 256 (e.g.

168.8.156.210).

NMS (Network Management System)

The NMS supervises SNMP devices connected to the TCP-IP Network.

Network Shutdown Module

The Network Shutdown Module is a software module that uses the information transmitted by the Network

Management Card to inform computer users on the current status of the electrical power supplied to the computer.

If the supply of the electrical power from the MGE UPSs is at risk, the Network Shutdown Module initiates an orderly shutdown of the computer under the most secure conditions possible.

Shutdown Duration

Shutdown Timer

SSL (Secure Socket Layer, created by Netscape)

A solution for securing transactions over the internet. SSL is a communication protocol that authenticates the data exchanged, as well as ensuring its confidentiality and integrity. The protocol uses a recognized encryption method, the RSA algorithm with a public key (where RSA means Rivest, Shamir and Adleman, the inventors). An RSA key is the result of operations involving prime numbers. SSL is built into the Internet browsers on the market. The padlock in the bottom of your browser screen is automatically displayed if the server sending information uses SSL.

TCP/IP (Transmission Control Protocol / Internet Protocol)

Family of protocols for the transport and network

Network Shutdown Module V3 – User Manual Page 49/53

Network Shutdown Module V3

User guide

9 Acknowledgements

9.1 SQLite

Huge thanks from software development team to the SQLite Project http://www.sqlite.org/.

Their generous donation of the source code to the public domain helped us for this project.

9.2 Pi3Web

Huge thanks from software development to the Pi3Web Project. http://pi3web.sourceforge.net/

License

Copyright (c) 1997-2003 Pi3 Development Group. All rights reserved.

These sources, libraries and applications are FREE FOR COMMERCIAL AND NON-COMMERCIAL USE as long as the following conditions are adhered to.

Redistribution and use in source and binary forms, with or without modification, are permitted provided that the following conditions are met:

1. Redistributions of source code must retain the above copyright notice, this list of conditions and the following disclaimer.

2. Redistributions in binary form must reproduce the above copyright notice, this list of conditions and the following disclaimer in the documentation and/or other materials provided with the distribution.

3. The name of the author may not be used to endorse or promote products derived from this software without specific prior written permission.

THIS SOFTWARE IS PROVIDED ``AS IS'' AND ANY EXPRESSED OR IMPLIED WARRANTIES, INCLUDING, BUT NOT LIMITED TO,

THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE DISCLAIMED. IN NO

EVENT SHALL THE AUTHORS OR ITS CONTRIBUTORS BE LIABLE FOR ANY DIRECT, INDIRECT, INCIDENTAL, SPECIAL,

EXEMPLARY, OR CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT LIMITED TO, PROCUREMENT OF SUBSTITUTE GOODS

OR SERVICES; LOSS OF USE, DATA, OR PROFITS; OR BUSINESS INTERRUPTION) HOWEVER CAUSED AND ON ANY THEORY

OF LIABILITY, WHETHER IN CONTRACT, STRICT LIABILITY, OR TORT (INCLUDING NEGLIGENCE OR OTHERWISE) ARISING IN

ANY WAY OUT OF THE USE OF THIS SOFTWARE, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE.

All trademarks and copyrights are property of their respective owners.

Copyright © 1998-2000, 2001 Holger Zimmermann, John Roy.

9.3 PHP

Huge thanks from the software development team to the PHP Project.

--------------------------------------------------------------------

The PHP License, version 3.0

Copyright (c) 1999 - 2002 The PHP Group. All rights reserved.

--------------------------------------------------------------------

Redistribution and use in source and binary forms, with or without modification, is permitted provided that the following conditions are met:

1. Redistributions of source code must retain the above copyright

notice, this list of conditions and the following disclaimer.

2. Redistributions in binary form must reproduce the above copyright

notice, this list of conditions and the following disclaimer in

the documentation and/or other materials provided with the

distribution.

3. The name "PHP" must not be used to endorse or promote products

derived from this software without prior written permission. For

written permission, please contact [email protected].

4. Products derived from this software may not be called "PHP", nor

may "PHP" appear in their name, without prior written permission

from [email protected]. You may indicate that your software works in

conjunction with PHP by saying "Foo for PHP" instead of calling

it "PHP Foo" or "phpfoo"

5. The PHP Group may publish revised and/or new versions of the

license from time to time. Each version will be given a

distinguishing version number.

Once covered code has been published under a particular version

Network Shutdown Module V3 – User Manual Page 50/53

Network Shutdown Module V3

User guide

of the license, you may always continue to use it under the terms

of that version. You may also choose to use such covered code

under the terms of any subsequent version of the license

published by the PHP Group. No one other than the PHP Group has

the right to modify the terms applicable to covered code created

under this License.

6. Redistributions of any form whatsoever must retain the following

acknowledgment:

"This product includes PHP, freely available from

<http://www.php.net/>".

THIS SOFTWARE IS PROVIDED BY THE PHP DEVELOPMENT TEAM ``AS IS'' AND

ANY EXPRESSED OR IMPLIED WARRANTIES, INCLUDING, BUT NOT LIMITED TO,

THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A

PARTICULAR PURPOSE ARE DISCLAIMED. IN NO EVENT SHALL THE PHP

DEVELOPMENT TEAM OR ITS CONTRIBUTORS BE LIABLE FOR ANY DIRECT,

INDIRECT, INCIDENTAL, SPECIAL, EXEMPLARY, OR CONSEQUENTIAL DAMAGES

(INCLUDING, BUT NOT LIMITED TO, PROCUREMENT OF SUBSTITUTE GOODS OR

SERVICES; LOSS OF USE, DATA, OR PROFITS; OR BUSINESS INTERRUPTION)

HOWEVER CAUSED AND ON ANY THEORY OF LIABILITY, WHETHER IN CONTRACT,

STRICT LIABILITY, OR TORT (INCLUDING NEGLIGENCE OR OTHERWISE)

ARISING IN ANY WAY OUT OF THE USE OF THIS SOFTWARE, EVEN IF ADVISED

OF THE POSSIBILITY OF SUCH DAMAGE.

--------------------------------------------------------------------

This software consists of voluntary contributions made by many individuals on behalf of the PHP Group.

The PHP Group can be contacted via Email at [email protected].

For more information on the PHP Group and the PHP project, please see <http://www.php.net>.

This product includes the Zend Engine, freely available at

<http://www.zend.com>.

9.4 OpenSSL

Huge thanks from software development to the OpenSSL Project.

OpenSSL License

---------------

/* ====================================================================

* Copyright (c) 1998-2006 The OpenSSL Project. All rights reserved.

*

* Redistribution and use in source and binary forms, with or without

* modification, are permitted provided that the following conditions

* are met:

* 1. Redistributions of source code must retain the above copyright

* notice, this list of conditions and the following disclaimer.

* 2. Redistributions in binary form must reproduce the above copyright

* notice, this list of conditions and the following disclaimer in

* the documentation and/or other materials provided with the

* distribution.

* 3. All advertising materials mentioning features or use of this

* software must display the following acknowledgment:

* "This product includes software developed by the OpenSSL Project

* for use in the OpenSSL Toolkit. (http://www.openssl.org/)"

* 4. The names "OpenSSL Toolkit" and "OpenSSL Project" must not be used to

* endorse or promote products derived from this software without

* prior written permission. For written permission, please contact

* [email protected].

* 5. Products derived from this software may not be called "OpenSSL"

* nor may "OpenSSL" appear in their names without prior written

* permission of the OpenSSL Project.

* 6. Redistributions of any form whatsoever must retain the following

* acknowledgment:

* "This product includes software developed by the OpenSSL Project

* for use in the OpenSSL Toolkit (http://www.openssl.org/)"

* THIS SOFTWARE IS PROVIDED BY THE OpenSSL PROJECT ``AS IS'' AND ANY

* EXPRESSED OR IMPLIED WARRANTIES, INCLUDING, BUT NOT LIMITED TO, THE

* IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR

* PURPOSE ARE DISCLAIMED. IN NO EVENT SHALL THE OpenSSL PROJECT OR

* ITS CONTRIBUTORS BE LIABLE FOR ANY DIRECT, INDIRECT, INCIDENTAL,

* SPECIAL, EXEMPLARY, OR CONSEQUENTIAL DAMAGES (INCLUDING, BUT

Network Shutdown Module V3 – User Manual Page 51/53

Network Shutdown Module V3

User guide

* NOT LIMITED TO, PROCUREMENT OF SUBSTITUTE GOODS OR SERVICES;

* LOSS OF USE, DATA, OR PROFITS; OR BUSINESS INTERRUPTION)

* HOWEVER CAUSED AND ON ANY THEORY OF LIABILITY, WHETHER IN CONTRACT,

* STRICT LIABILITY, OR TORT (INCLUDING NEGLIGENCE OR OTHERWISE)

* ARISING IN ANY WAY OUT OF THE USE OF THIS SOFTWARE, EVEN IF ADVISED

* OF THE POSSIBILITY OF SUCH DAMAGE.

* ====================================================================

*

* This product includes cryptographic software written by Eric Young

* ([email protected]). This product includes software written by Tim

* Hudson ([email protected]).

*

*/

Original SSLeay License

-----------------------

/* Copyright (C) 1995-1998 Eric Young ([email protected])

* All rights reserved.

*

* This package is an SSL implementation written

* by Eric Young ([email protected]).

* The implementation was written so as to conform with Netscapes SSL.

* This library is free for commercial and non-commercial use as long as

* the following conditions are aheared to. The following conditions

* apply to all code found in this distribution, be it the RC4, RSA,

* lhash, DES, etc., code; not just the SSL code. The SSL documentation

* included with this distribution is covered by the same copyright terms

* except that the holder is Tim Hudson ([email protected]).

* Copyright remains Eric Young's, and as such any Copyright notices in

* the code are not to be removed.

* If this package is used in a product, Eric Young should be given attribution

* as the author of the parts of the library used.

* This can be in the form of a textual message at program startup or

* in documentation (online or textual) provided with the package.

*

* Redistribution and use in source and binary forms, with or without

* modification, are permitted provided that the following conditions

* are met:

* 1. Redistributions of source code must retain the copyright

* notice, this list of conditions and the following disclaimer.

* 2. Redistributions in binary form must reproduce the above copyright

* notice, this list of conditions and the following disclaimer in the

* documentation and/or other materials provided with the distribution.

* 3. All advertising materials mentioning features or use of this software

* must display the following acknowledgement:

* "This product includes cryptographic software written by

* Eric Young ([email protected])"

* The word 'cryptographic' can be left out if the rouines from the library

* being used are not cryptographic related :-).

* 4. If you include any Windows specific code (or a derivative thereof) from

* the apps directory (application code) you must include an acknowledgement:

* "This product includes software written by Tim Hudson ([email protected])"

*

* THIS SOFTWARE IS PROVIDED BY ERIC YOUNG ``AS IS'' AND

* ANY EXPRESS OR IMPLIED WARRANTIES, INCLUDING, BUT NOT LIMITED TO, THE

* IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE

* ARE DISCLAIMED. IN NO EVENT SHALL THE AUTHOR OR CONTRIBUTORS BE LIABLE

* FOR ANY DIRECT, INDIRECT, INCIDENTAL, SPECIAL, EXEMPLARY, OR CONSEQUENTIAL

* DAMAGES (INCLUDING, BUT NOT LIMITED TO, PROCUREMENT OF SUBSTITUTE GOODS

* OR SERVICES; LOSS OF USE, DATA, OR PROFITS; OR BUSINESS INTERRUPTION)

* HOWEVER CAUSED AND ON ANY THEORY OF LIABILITY, WHETHER IN CONTRACT, STRICT

* LIABILITY, OR TORT (INCLUDING NEGLIGENCE OR OTHERWISE) ARISING IN ANY WAY

* OUT OF THE USE OF THIS SOFTWARE, EVEN IF ADVISED OF THE POSSIBILITY OF

* SUCH DAMAGE.

*

* The licence and distribution terms for any publically available version or

* derivative of this code cannot be changed. i.e. this code cannot simply be

* copied and put under another distribution licence

* [including the GNU Public Licence.]

*/

Network Shutdown Module V3 – User Manual Page 52/53

Network Shutdown Module V3

User guide

9.5 Lighttpd

Huge thanks from the software development to the Lighttpd Project.

Copyright (c) 2004, Jan Kneschke, incremental

All rights reserved.

Redistribution and use in source and binary forms, with or without modification, are permitted provided that the following conditions are met:

- Redistributions of source code must retain the above copyright notice, this

list of conditions and the following disclaimer.

- Redistributions in binary form must reproduce the above copyright notice,

this list of conditions and the following disclaimer in the documentation

and/or other materials provided with the distribution.

- Neither the name of the 'incremental' nor the names of its contributors may

be used to endorse or promote products derived from this software without

specific prior written permission.

THIS SOFTWARE IS PROVIDED BY THE COPYRIGHT HOLDERS AND CONTRIBUTORS "AS IS"

AND ANY EXPRESS OR IMPLIED WARRANTIES, INCLUDING, BUT NOT LIMITED TO, THE

IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE

ARE DISCLAIMED. IN NO EVENT SHALL THE COPYRIGHT OWNER OR CONTRIBUTORS BE

LIABLE FOR ANY DIRECT, INDIRECT, INCIDENTAL, SPECIAL, EXEMPLARY, OR

CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT LIMITED TO, PROCUREMENT OF

SUBSTITUTE GOODS OR SERVICES; LOSS OF USE, DATA, OR PROFITS; OR BUSINESS

INTERRUPTION) HOWEVER CAUSED AND ON ANY THEORY OF LIABILITY, WHETHER IN

CONTRACT, STRICT LIABILITY, OR TORT (INCLUDING NEGLIGENCE OR OTHERWISE)

ARISING IN ANY WAY OUT OF THE USE OF THIS SOFTWARE, EVEN IF ADVISED OF

THE POSSIBILITY OF SUCH DAMAGE.

9.6 WxWidget

Huge thanks from software development to the WxWidget Project. wxWindows Library Licence, Version 3.1

======================================

Copyright (C) 1998-2005 Julian Smart, Robert Roebling et al

Everyone is permitted to copy and distribute verbatim copies

of this licence document, but changing it is not allowed.

WXWINDOWS LIBRARY LICENCE

TERMS AND CONDITIONS FOR COPYING, DISTRIBUTION AND MODIFICATION

This library is free software; you can redistribute it and/or modify it

under the terms of the GNU Library General Public Licence as published by

the Free Software Foundation; either version 2 of the Licence, or (at

your option) any later version.

This library is distributed in the hope that it will be useful, but

WITHOUT ANY WARRANTY; without even the implied warranty of

MERCHANTABILITY or FITNESS FOR A PARTICULAR PURPOSE. See the GNU Library

General Public Licence for more details.

You should have received a copy of the GNU Library General Public Licence

along with this software, usually in a file named COPYING.LIB. If not,

write to the Free Software Foundation, Inc., 59 Temple Place, Suite 330,

Boston, MA 02111-1307 USA.

EXCEPTION NOTICE

1. As a special exception, the copyright holders of this library give permission for additional uses of the text contained in this release of the library as licenced under the wxWindows

Library Licence, applying either version 3.1 of the Licence, or (at your option) any later version of the Licence as published by the copyright holders of version 3.1 of the Licence document.

2. The exception is that you may use, copy, link, modify and distribute under your own terms, binary object code versions of works based on the Library.

3. If you copy code from files distributed under the terms of the GNU General Public Licence or the

GNU Library General Public Licence into a copy of this library, as this licence permits, the exception does not apply to the code that you add in this way. To avoid misleading anyone as to the status of such modified files, you must delete this exception notice from such code and/or adjust the licensing conditions notice accordingly.

4. If you write modifications of your own for this library, it is your choice whether to permit this exception to apply to your modifications. If you do not wish that, you must delete the exception notice from such code and/or adjust the licensing conditions notice accordingly.