TP-BC Series

DATA SHEET

High Power Battery Charge Controller

Features

300W Total Power

Regulated 12VDC or 24VDC or 48VDC

Output Voltage

Seamless Switchover From AC to Battery

Power when AC Power Fails.

Load Control to Prevent Battery

Overdischarge. Automatic Recovery.

Smart Charge program for GEL/AGM or WET type batteries

Wide temperature operation

Applications

Wireless Base Stations, Cellular Base Stations

Surveillance Systems

Battery Backup Systems

Description

The TP-BC series of smart battery chargers provide up to 300W of total power. Part of the power is allocated to the regulated load output and remaining power is allocated to battery charging. The smart battery charger is compatible with GEL/AGM type sealed lead acid batteries and also WET type lead acid batteries (like car batteries).

The load output is regulated so that output voltage does not exceed 12.5VDC on the 12V model and 24.5VDC on the

24V model and 48.5VDC on the 48V model. Also the load output will turn off when the battery voltage is low to prevent over discharge of the batteries which can shorten the useable life of the batteries. Load output will turn back on automatically when batteries have sufficient charge. The TP-BC series provides seamless switchover from AC power to battery power so there is no interruption whic h could reset a user’s electronics. The charger auto-recovers from a power failure so no user action is necessary.

The charger has various protections for short circuit, overvoltage protection, overcurrent and reverse battery. It operates over a wide temperature range making it suitable for industrial applications.

The battery charger will not work without a battery connected.

A solar panel and solar charge controller can be added to the system if supplemental power from solar is desired. A

Wind Turbine can be added if wind power is available.

There are various LEDS on the front panel to see status-at-a-glance of the Load Output, Charging Condition and AC

Power Condition.

LED Indicators LOAD (Load Power is Turned On = Green)

PWR (AC Power On = Yellow)

BATT ( Battery is Connected = Green)

CHD ( Battery is Fully Charged = Green)

CHG ( Battery is Charging = Yellow)

WET / GEL

– Switch is positioned to WET(Green) or GEL(Yellow)

Notes:

All shipments F.O.B. Draper, UT 84020

Tycon Power Systems POE Midspan Injectors carry a 1 year warranty

TP-BC Series

Page 2

Specifications

Total Power Available (for

Load and Battery charging)

Nominal Battery Voltage

Load Output Min Current

Load Output Max Current

Overdischarge Protection

TP-BC12-300

300W

12VDC

1A

12A

TP-BC24-300

300W

24VDC

1A

8A

TP-BC48-300

300W

48VDC

1A

6A

Battery Charge Max Current

Battery Charger Voltage

10.7V Load off / 12.6V Load on

12A

WET Equalize = 14.6V, Float =

13.2V

GEL Equalize = 14.2V, Float =

13.5V

21.5V Load off / 25.2V Load on

12A*

* if load current is 8A then battery charge current is 4.5A. If load current 6A then battery charge current is 6.5A

WET Equalize = 28.8V, Float =

26.4V

GEL Equalize = 28.4V, Float =

27V

5%

40V Load off / 51V Load on

6A*

* if load current is 3A then battery charge current is 3A. If load current 1A then battery charge current is 5A

WET Equalize = 58V, Float =

53V

GEL Equalize = 56.8V, Float =

54V

Load Regulation

Line Regulation / Ripple

Noise

Efficiency

Self Consumption

Load and Batt Connections

EMC Standards

Safety Standards

AC Power Input (+-10%)

AC Input Current

Fuse

Operating Temperature

Operating Humidity (RH)

Cooling

Storage Temperature

1%

2%

75% Minimum

<5W

Screw Wire Terminal, 10 AWG MAXIMUM

FCC Class A , NE55022 Class A

UL1950, CSA 22.2, TUV EN60950

Selector Switch 120VAC / 240VAC , 50/60Hz

3.5A @ 115VAC / 1.8A @ 240VAC

6A Internal

-20 to +60C (-4 to +140°F)

Up to 90% (non condensing)

Temperature Controlled Fan

-25 to +85°C (-13 to +185°F)

Up to 90% (non-condensing) Storage Humidity

250 x 185 x 55mm (9.8 x 7.3 x 2.2”) Dimensions (LxWxH)

2.4kg (5.2lb) Weight

System Ordering:

TP-BC12-300

300W Smart Battery Charger with regulated 12VDC load output with US Power Cord*

TP-BC24-300

TP-BC48-300

300W Smart Battery Charger with regulated 24VDC load output with US Power Cord*

300W Smart Battery Charger with regulated 48VDC load output with US Power Cord*

*Add an “E” suffix for Euro power cord

Notes:

All shipments F.O.B. Bluffdale, UT 84065

TP-BC Series carry a 1 year warranty

For further information contact:

Tyconpower.com

14641 S 800 W Suite A

Bluffdale, UT 84065

PH: 801-432-0003

FAX: 801-618-4220

TP-BC Series Spec Rev 3 6-Dec-12 Specifications Subject to Change Without Notice