Honeywell NetAXS-4 Installation Guide


Add to my manuals
73 Pages

advertisement

Honeywell NetAXS-4 Installation Guide | Manualzz
NetAXS™
NX4S1
Access Control Unit
Installation Guide
June 2015
© 2015 Honeywell. All rights reserved.
800-00008V3
Copyright © 2015 Honeywell. All rights reserved.
All product and brand names are the service marks, trademarks, registered trademarks,
or registered service marks of their respective owners. Printed in the United States of
America. Honeywell reserves the right to change any information in this document at
any time without prior notice.
Ordering Information
Please contact your local Honeywell representative or visit us on the web at
www.honeywellaccess.com for information about ordering.
Feedback
Honeywell appreciates your comments about this manual. Please visit us on the web at
www.honeywellaccess.com to post your comments.
CONTENTS
NetAXS™ NX4S1 Installation
1.0 Notices .................................................................................................................................................
1.1 Warnings and Cautions ...................................................................................................
1.2 Product Liability, Mutual Indemnification .....................................................................
1.3 Limited Warranty............................................................................................................
1.4 Federal Communications Commission...........................................................................
1.5 Industry Canada ..............................................................................................................
1.6 Underwriters Laboratories Incorporated.........................................................................
1
1
2
2
3
3
4
2.0 Introduction ......................................................................................................................................... 5
2.1 Access Control Overview ............................................................................................... 5
2.2 NetAXS™ Access Overview.......................................................................................... 5
3.0 Panel Components and Descriptions...............................................................................................
3.1 NetAXS™ Access Control Unit .....................................................................................
Real-Time Clock Protection ...........................................................................................
Memory Protection .........................................................................................................
Reader and AUX Power .................................................................................................
3.2 Power Supply ..................................................................................................................
3.3 Battery.............................................................................................................................
3.4 Enclosure ........................................................................................................................
6
7
7
7
7
8
8
8
4.0 Installation........................................................................................................................................... 9
4.1 Cabinet Mounting ......................................................................................................... 10
4.2 Reader Wiring............................................................................................................... 14
4.3 Supervised Input Wiring ............................................................................................... 14
4.4 NX4S1 Control Output Wiring..................................................................................... 16
4.5 Communications ........................................................................................................... 16
RS-232 Communications ............................................................................................. 16
RS-485 Communications ............................................................................................. 18
Ethernet TCP/IP Communications ............................................................................... 19
4.6 DIP Switch Settings ...................................................................................................... 21
4.7 Jumper Settings............................................................................................................. 23
4.8 Downstream I/O............................................................................................................ 23
NetAXS Access Control Unit NX4S1 Installation Guide, Document 800-00008V3
iii
5.0 System Configuration ......................................................................................................................
5.1 RS-485 Connection via PCI-2 ......................................................................................
5.2 RS-485 Connection via NetAXS™ ..............................................................................
5.3 RS-485 Connections with Multidrop Panels at Both Ends of the Cable ......................
5.4 RS-232 Connection.......................................................................................................
5.5 Ethernet Connection .....................................................................................................
5.6 LANSRLU1 Connection...............................................................................................
5.7 RS-485 Short Haul Modem Connection via PCI-2 ......................................................
5.8 RS-485 Short Haul Modem Connection via NetAXS™ ..............................................
5.9 RS-232 Short Haul Modem Connection .......................................................................
5.10 M-56K Dial-up Modem, RS-485 Connection via Hub...............................................
5.11 M-56K Dial-up Modem, RS-485 Connection via NetAXS™....................................
5.12 Fiber Converter to RS-485 Connection via PCI-2......................................................
5.13 Fiber Converter to RS-485 Connection via NetAXS™..............................................
5.14 N-485-PCI-2/NetAXS™ Access Controller Panel Connection Detail.......................
5.15 NetAXS™/NetAXS™ Access Controller Panel Connection Detail ..........................
26
26
27
28
30
31
32
33
34
35
36
37
38
39
40
41
6.0 NetAXS™ Startup ........................................................................................................................... 42
6.1 LED Operation.............................................................................................................. 42
7.0 Hardware Specifications .................................................................................................................
7.1 Relay Contacts ..............................................................................................................
7.2 Reader Interface ............................................................................................................
7.3 NX4S1 Wire Requirements ..........................................................................................
7.4 Maximum Output Loading ...........................................................................................
7.5 Common Connections...................................................................................................
7.6 Mechanical....................................................................................................................
7.7 Environment..................................................................................................................
7.8 Communications and Wiring ........................................................................................
7.9 Reader Wiring...............................................................................................................
7.10 NX4S1 Wiring Diagram .............................................................................................
44
44
44
44
44
45
45
45
46
46
47
8.0 Maintenance ...................................................................................................................................... 48
9.0 Troubleshooting ............................................................................................................................... 48
10.0 Technical Support .......................................................................................................................... 49
10.1 Normal Support Hours................................................................................................ 49
10.2 Web ............................................................................................................................. 49
iv
www.honeywell.com
NetAXS™ Standalone Operation
A.1 Basic Standalone Operations......................................................................................................... 51
A.1.1 Card Read / Door Lock Operation ............................................................................ 51
A.1.2 Door Egress / Door Lock / Door Status Operation ................................................... 51
A.2 Standalone Settings.........................................................................................................................
A.2.1 NetAXS™ Panel Hardware Settings ........................................................................
A.2.2 Communication Settings...........................................................................................
A.2.3 Emulation Settings ....................................................................................................
A.2.4 Verifying Communications.......................................................................................
52
52
52
52
52
A.3 Standalone Commands ...................................................................................................................
A.3.1 T (Time) Command ..................................................................................................
A.3.2 D (Date) Command...................................................................................................
A.3.3 L (Time Zone) Command .........................................................................................
A.3.4 C (Card Add) Command ...........................................................................................
A.3.5 C (Card Delete) Command .......................................................................................
A.3.6 W (Input) Command .................................................................................................
A.3.7 P (Interlock) Command.............................................................................................
A.3.8 Flow Control Disable/Enable....................................................................................
53
53
54
55
56
56
57
57
58
A.4 NetAXS™ Panel Defaults .............................................................................................................
A.4.1 Reader Ports ..............................................................................................................
A.4.2 Reader LED Outputs ................................................................................................
A.4.3 Reader Tamper Inputs...............................................................................................
A.4.4 Door Egress Inputs....................................................................................................
A.4.5 Door Status Inputs.....................................................................................................
A.4.6 ACFAIL and Panel Tamper Inputs ...........................................................................
A.4.7 Additional Generic Outputs ......................................................................................
59
59
59
60
60
61
61
62
NetAXS Access Control Unit NX4S1 Installation Guide, Document 800-00008V3
v
vi
www.honeywell.com
LIST OF FIGURES
Figure 1: NX4S1 Panel Components ............................................................................ 6
Figure 2: NetAXS™ NX4S1 Panel Cabinet, Front View ........................................... 10
Figure 3: NetAXS™ NX4S1 Panel Cabinet, Top View ............................................. 11
Figure 4: NetAXS™ NX4S1 Panel Cabinet, Bottom View ....................................... 11
Figure 5: NetAXS™ Panel Cabinet, Left View .......................................................... 12
Figure 6: NetAXS™ NX4S1Panel Cabinet, Right View ........................................... 13
Figure 7: Typical Supervised Input Wiring Diagram ................................................. 15
Figure 8: RJ-45 Serial Port ......................................................................................... 17
Figure 9: RS-232 Configuration ................................................................................. 17
Figure 10: RS-485 Configuration via N-485-PCI-2 or PCI-3 .................................... 18
Figure 11: RS-485 Configuration via NetAXS™ Gateway ....................................... 19
Figure 12: Ethernet TCP/IP Configuration ................................................................. 19
Figure 13: Ethernet MAC Address Location .............................................................. 20
Figure 14: DIP Switch and Jumper Locations ............................................................ 21
Figure 15: Default Downstream I/O Configuration with Wiring ............................... 25
Figure 16: RS-485 Connection via PCI-2 ................................................................... 26
Figure 17: RS-485 Connection via NetAXS™ ........................................................... 27
Figure 18: RS-485 Connection via NetAXS™ with Multidrop Panels at Both Ends 28
Figure 19: RS-485 Connection via PCI-2 with Multidrop Panels at Both Ends ........ 29
Figure 20: RS-232 Connection ................................................................................... 30
Figure 21: Ethernet Connection .................................................................................. 31
Figure 22: LANSRLU1 Connection ........................................................................... 32
Figure 23: RS-485 Short Haul Modem Connection via PCI-2 ................................... 33
Figure 24: RS-485 Short Haul Modem Connection via NetAXS™ ........................... 34
Figure 25: RS-232 Short Haul Modem Connection ................................................... 35
Figure 26: M-56K Dial-up Modem, RS-485 Connection via Hub ............................. 36
Figure 27: M-56K Dial-up Modem, RS-485 Connection via NetAXS™ .................. 37
Figure 28: Fiber Converter to RS-485 Connection via PCI-2 .................................... 38
Figure 29: Fiber Converter to RS-485 Connection via NetAXS™ ............................ 39
Figure 30: N-485-PCI-2/NetAXS™ Access Controller Panel Connection Detail ..... 40
Figure 31: NetAXS™/NetAXS™ Access Controller Panel Connection Detail ......... 41
Figure 32: System, Relay and Power LEDs ............................................................... 42
Figure 33: NX4S1 Panel Wiring Diagram .................................................................. 47
NetAXS Access Control Unit NX4S1 Installation Guide, Document 800-00008V3
vii
viii
www.honeywell.com
LIST OF TABLES
Table 1
Table 2
Table 3
Table 4
Table 5
Table 6
Table 7
Table 8
Reader Wiring .............................................................................................................
Default Supervised Input Assignments .......................................................................
DIP Switch Settings ....................................................................................................
MIRO 32/0 DIP Switch and Jumper Settings .............................................................
LED Status ..................................................................................................................
Communications and Wiring ......................................................................................
Reader Wiring .............................................................................................................
Troubleshooting Problems and Solutions ...................................................................
NetAXS Access Control Unit NX4S1 Installation Guide, Document 800-00008V3
14
14
22
23
43
46
46
48
ix
x
www.honeywell.com
NetAXS™ NX4S1 Installation
1.0 Notices
1.1 Warnings and Cautions
Warning: Fire Safety and Liability Notice: Never connect card readers to any critical
entry, exit door, barrier, elevator or gate without providing an alternative exit in
accordance with all fire and life safety codes pertinent to the installation. These fire
and safety codes vary from city to city and you must get approval from local fire
officials whenever using an electronic product to control a door or other barrier. Use of
egress buttons, for example, may be illegal in some cities. In most applications, single
action exit without prior knowledge of what to do is a life safety requirement. Always
make certain that any required approvals are obtained in writing. Verbal approvals are
not valid.
Warning: Honeywell Access
Systems (HAS) never recommends using WIN-PAK or
related products for use as a primary warning or monitoring system. Primary warning
or monitoring systems should always meet local fire and safety code requirements.
The installer must also test the system on a regular basis by instructing the end user in
appropriate daily testing procedures. Failure to test a system regularly could make
installer liable for damages to the end user if a problem occurs.
Warning: Earth
ground all enclosures for proper installation.
Warning: Personal
injury or death could occur, and the equipment could be damaged
beyond repair, if this precaution is not observed!
• Before installation, turn off the external circuit breaker which supplies power
to the system, including door locks.
• Before connecting the device to the power supply, verify that the output
voltage is within specifications of the power supply.
• Do not apply power to the system until after the installation has been
completed.
Caution: If
any damage to the shipment is noticed, a claim must be filed with the
commercial carrier responsible.
Caution: Electro-static
discharge (ESD) can damage CMOS integrated circuits and
modules. To prevent damage always follow these procedures:
• Use static shield packaging and containers to transport all electronic
components, including completed reader assemblies.
NetAXS Access Control Unit NX4S1 Installation Guide, Document 800-00008V3
1
NetAXS™ NX4S1 Installation
Notices
• Handle all ESD sensitive components at an approved static controlled
workstation. These workstations consist of a desk mat, floor mat and an ESD
wrist strap. Workstations are available from various vendors.
1.2 Product Liability, Mutual Indemnification
In the event that a Customer receives a claim that a Product or any component thereof
has caused personal injury or damage to property of others, the Customer shall
immediately notify Honeywell in writing of all such claims. Honeywell shall defend
or settle such claims and shall indemnify and hold the Customer harmless for any
costs or damages including reasonable attorneys’ fees which the Customer may be
required to pay as a result of the defective Product or the negligence of Honeywell, its
agents or its employees.
The Customer shall hold harmless and indemnify Honeywell from and against all
claims, demands, losses and liability arising out of damage to property or injury to
persons occasioned by or in connection with the acts or omissions of the Customer
and its agents and employees, and from and against all claims, demands, losses and
liability for costs of fees, including reasonable attorneys’ fees in connection therewith.
1.3 Limited Warranty
All Products sold or licensed by Honeywell Access Systems (HAS) include a
warranty registration card which must be completed and returned to Honeywell by or
on behalf of the end user in order for Honeywell to provide warranty service, repair,
credit or exchange. All warranty work shall be handled through the Customer which
shall notify Honeywell and apply for a Return Merchandise Authorization (RMA)
number prior to returning any Product for service, repair, credit or exchange.
Honeywell warrants that its Products shall be free from defects in materials and
workmanship for a period of one year from date of shipment of the Product to the
Customer. The warranty on Terminals, Printers, Communications Products and
Upgrade kits is 90 days from date of shipment. Satisfaction of this warranty shall be
limited to repair or replacement of Products which are defective or defective under
normal use.
Honeywell’s warranty shall not extend to any Product which, upon examination, is
determined to be defective as a result of misuse, improper storage, incorrect
installation, operation or maintenance, alteration, modification, accident or unusual
deterioration of the Product due to physical environments in excess of the limits set
forth in Product manuals.
2
www.honeywell.com
NetAXS™ NX4S1 Installation
Notices
THERE ARE NO WARRANTIES THAT EXTEND BEYOND THIS PROVISION.
THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES WHETHER
EXPRESS, IMPLIED OR STATUTORY, INCLUDING IMPLIED WARRANTIES
OF MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE. NO
REPRESENTATION OR WARRANTY OF THE DISTRIBUTOR SHALL EXTEND
THE LIABILITY OR RESPONSIBILITY OF THE MANUFACTURER BEYOND
THE TERMS OF THIS PROVISION. IN NO EVENT SHALL HONEYWELL BE
LIABLE FOR ANY RE-PROCUREMENT COSTS, LOSS OF PROFITS, LOSS OF
USE, INCIDENTAL, CONSEQUENTIAL OR SPECIAL DAMAGES TO ANY
PERSON RESULTING FROM THE USE OF HONEYWELL PRODUCTS.
1.4 Federal Communications Commission
This equipment has been tested and found to comply with the limits for a Class B
digital device, pursuant to part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful interference in a residential installation.
This equipment generates, uses, and can radiate radio frequency energy, and if not
installed and used in accordance with the instructions, may cause harmful interference
to radio communications. However, there is no guarantee that interference will not
occur in a particular installation. If this equipment does cause harmful interference to
radio or television reception, which can be determined by turning the equipment off
and on, the user is encouraged to try to correct the interference by one or more of the
following measures:
• Re-orient or re-locate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which
the receiver is connected.
• Consult the dealer or an experienced radio/TV technician for help.
The user shall not make any changes or modifications to the equipment unless
authorized by the Installation Instructions or User’s Manual. Unauthorized changes or
modifications could void the user’s authority to operate the equipment.
For panels using the Ethernet connection, the cable clamp (HAS part number
3-000342) must be used for the panel to pass the FCC Part 15 Class B requirements.
See “Installation“ on page 9 for clamp installation instructions.
1.5 Industry Canada
This Class B digital apparatus meets all requirements of the Canadian
Interference-Causing Equipment Regulations.
Cet appareil numérique de la classe B respecte toutes les exigences du Réglement sur
le matériel brouilleur du Canada.
NetAXS Access Control Unit NX4S1 Installation Guide, Document 800-00008V3
3
NetAXS™ NX4S1 Installation
Notices
1.6 Underwriters Laboratories Incorporated
The NetAXS™ panel was reviewed by Underwriters Laboratories Incorporated for
Access Control System Units - Category ALVY, UL294 standard. The NetAXS™
panel was reviewed as a stand alone system. The input points only monitor the door
position. The NetAXS™ panel is not intended as a Proprietary Alarm Unit - Category
APOU, UL1076 standard.
The NetAXS™ panel was reviewed using the following Honeywell readers:
OmniAssure (TM) OT30, OmniClass (TM) OM40 and OM55, and OmniProx (TM)
OP30 and OP40.
Notes:
• All field wiring, except the battery backup/charger wiring, is Class 2
power-limited.
• UL has not evaluated communication with panels that are not NetAXS™
panels.
• Underwriters Laboratories (UL) has reviewed only the configurations shown
in “RS-485 Connection via PCI-2“ on page 26, “RS-485 Connection via
NetAXS™“ on page 27, and “RS-232 Connection“ on page 30 of this guide.
Because UL has reviewed the NetAXS™ panel only as a standalone system,
the computer terminal, NetAXS™ gateway panel, and N-485_PCI-2 adapter
appear in these sections only to illustrate the installation and programming of
the NetAXS™ panel.
• UL has not evaluated the compatibility of downstream I/O devices (see
“Downstream I/O“ on page 23) with the NetAXS™ panel.
4
www.honeywell.com
NetAXS™ NX4S1 Installation
Introduction
2.0 Introduction
2.1 Access Control Overview
An access control system protects and preserves an enterprise’s resources by
providing authentication, authorization, and administration services. Authentication is
a process that verifies a user’s identity. If the user is verified, the system then either
grants or denies access to specific areas and resources. Administration includes the
creation and modification of user accounts and access privileges.
An access control system consists of hardware and software, usually configured in a
network environment over a standard network protocol. Access control units, readers,
door strikes, and video and other devices, for example, are configured to control and
monitor the access to a company site.
2.2 NetAXS™ Access Overview
A NetAXS™ access control system consists of a host system and NetAXS™ access
control units that meet existing N-1000-III/IV specifications and that communicate
with each other and with a variety of input and output devices over the RS-232 and
RS-485 network protocols. See “System Configuration“ on page 26 to view
illustrations of the supported NetAXS™ system configurations. A NetAXS™ access
control system is configured and maintained via either the host system or a web server
using RS-232, RS-485, or Ethernet network protocols.
This document describes how to install and configure the NX4L1 access control unit.
NetAXS Access Control Unit NX4S1 Installation Guide, Document 800-00008V3
5
NetAXS™ NX4S1 Installation
Panel Components and Descriptions
3.0 Panel Components and Descriptions
The NX4S1 access control unit consists of a NetAXS™ panel control board and battery. The
components are enclosed in a pre-wired cabinet. The 16.5 VAC power supply (Basler Electric Model
BE156250CAA0004, M&G Electronics Model MGT1650, or Honeywell Access Systems part number
X-4) provides power for the panel control board, which is a four-reader panel providing access control
for up to four doors. The following figure shows the NX4S1 panel components.
Figure 1:
NX4S1 Panel Components
Enclosure Tamper
Switch
Enclosure
Grounding
Studs
Enclosure
Grounding
Studs
AC Power
LED
B
Enclosure Grounding Stud
NetAXS Access
Control Panel
Pb
Battery
6
www.honeywell.com
Pb
B
NetAXS™ NX4S1 Installation
Panel Components and Descriptions
Maintain at least a .25-inch distance between the non-power limited wiring
battery backup/charger wiring) and all other wiring, which is power-limited
Class 2 wiring.
Note:
3.1 NetAXS™ Access Control Unit
The NetAXS™ panel is a four-reader board that controls up to four doors by
providing up to 14 inputs and 8 outputs. The NetAXS™ panel may be used as a
stand-alone panel with independent card and transaction storage or, with a host
software upgrade, as a fully monitored online access control device. The NetAXS™
panel also supports up to 30 downstream panels in a variety of network
configurations. See Communications, page 16, for descriptions and illustrations.
Fourteen inputs are capable of four state supervision: Normal, Alarm, Short and Open.
Eight inputs are used as door control with one input used for request to exit on each
door and one input used for door status on each door. Supervised inputs for Tamper,
External Power Fail and four Reader Tampers are supplied as well, and they can be
used as additional inputs when not required for their default purpose.
Caution: The
NetAXS™ board must not be used to power locks. Only through the
relay board can the common power supply be used for the NetAXS™ and locking
devices.
Real-Time Clock Protection
The panel RTC is backed up using a super capacitor. The super capacitor will power
the real-time clock for one week in the absence of primary power or backup battery.
Memory Protection
The NetAXS™ panel continuously saves database and event information in
non-volatile FLASH memory. This activity prevents the panel from losing data when
power is lost.
Reader and AUX Power
Reader power is supplied within the range of 11.2 VDC and 12.4 VDC with a
maximum current of 600 mA. AUX power is supplied within the range of 10.5 VDC
and 12.4 VDC with a maximum current of 500mA. The current can be distributed
throughout the Reader Power or AUX Power in any configuration as long as the
maximum draw is less than 600 mA: Reader 1 + Reader 2 + Reader 3 + Reader 4 +
AUX Power < 600 mA.
Caution: AUX
Power must not be used to power locks.
For NetAXS™ maximum current draw, refer to Hardware Specifications, page 44.
NetAXS Access Control Unit NX4S1 Installation Guide, Document 800-00008V3
7
NetAXS™ NX4S1 Installation
Panel Components and Descriptions
3.2 Power Supply
The NetAXS™ panel is capable of operating on AC or DC input power. UL has not
reviewed the use of a DC power supply with the NX4S1 panel. The AC input must be
supplied at 16.5 VAC utilizing one of the following UL-listed, 50 VA, Class 2
transformers: Basler Electric Model BE156250CAA0004, M&G Electronics Model
MGT1650 (Honeywell Access Systems part number X-4). Use a two-wire, 18 AWG
shielded cable to run the AC power from the wall transformer to the enclosure. The
AC voltage is non-polarized and connects to TB17-1 and TB17-2.
A power-on LED assembly is supplied with the NX4S1. It is required by UL to be
mounted for external viewing. Refer to Installation, page 9 for details. When there is
sufficient AC power, the power-on LED illuminates. If the AC power is off, the LED
is not illuminated.
DC power is also non-polarized. The panel uses 24 VDC at 1.5 Amp wired into
TB17-1 and TB17-2.
The panel includes an input power indicator that illuminates when input voltage is
present. If the indicator is not illuminated, the input voltage is either off or too low to
operate the system.
Caution: De-energize
the unit before servicing it.
3.3 Battery
One CASIL CA1270 12 VDC, 7 A-Hr sealed lead-acid battery (HAS part number
3-000066) provides standby backup power. When the primary power is off, the
NetAXS™ panel automatically switches to the battery for continuous operation. The
battery provides three hours of standby backup power.
The NetAXS™ panel is capable of providing 300 mA at 13.7 VDC for battery
charging. The panel has deep discharge protection built in for the protection of the
battery. If the battery discharges below 10.4 V, the panel disconnects the battery and
ceases operation.
Replace the battery every two to two-and-a-half years, or more often if the panel has a
high rate of backup use.
Refer to Installation, page 9 for battery cable connection information.
3.4 Enclosure
The NX4S1 enclosure ships pre-wired. Its width is 14.5 inches (368.3 mm), its height
is 18.0 inches (457.2 mm), and its depth is 4.4 inches (111.8 mm). The equipped
enclosure, including the 7 A-Hr battery, is 22.1 pounds (10 Kg).
8
www.honeywell.com
NetAXS™ NX4S1 Installation
Installation
4.0 Installation
Perform the following steps to install the NX4S1 panel:
Warning: Use
a static strap whenever touching the panel to ensure protection from
Electrostatic Discharge (ESD).
1. Review the panel layout, cable runs, and power needs.
2. Mount the enclosure at the proper location on the wall. Use appropriate
anchors for the mounting material.
3. Run all I/O wires to the enclosure, and properly mark each wire for its use.
4. Run appropriate length of two-wire, 18 AWG shielded cable from the wall
transformer to the enclosure. The AC input must be supplied at 16.5 VAC
utilizing one of the following UL-listed, 50 VA, Class 2 transformers: Basler
Electric Model BE156250CAA0004, M&G Electronics Model MGT1650, or
Honeywell Access Systems part number X-4. The AC voltage is non-polarized
and connects to TB17-1 and TB17-2. Caution: Do not plug in the wall
transformer at this time, and do not connect to a receptacle controlled by a
switch.
5. Run a 14 AWG green wire from the enclosure to a proper earth ground.
6. Remove each terminal plug one at a time to wire the properly labeled cables.
See the wiring diagram (Figure 33 on page 47). Leave enough shield drain
length to secure to the grounding stud. Also, maintain a distance of at least .25
inches between the non-power limited wiring (battery backup/charger wiring)
and all other wiring, which is power-limited Class 2 wiring. Caution: Do not
plug in the wall transformer at this time.
7. Connect the shield and the green earth ground to the enclosure’s grounding
studs (see Figure 1 on page 6) for the location of the enclosure’s grounding
studs).
8. Set DIP switch settings for the panel address (Table 3 on page 22), and set J36
and J37 for communication termination and biasing (see “System
Configuration“ on page 26 and “Jumper Settings“ on page 23).
9. Check all wiring at this time. Caution: Improper wiring can cause damage to
the NetAXS™ panel at power up resulting in a loss of warranty.
10.Power up the panel. The power-up sequence may take up to two minutes, after
which the RUN LED blinks green. The RUN LED is located near Terminal
Block (TB) 8. After the power-up sequence, check the LEDs to be sure the
panel has powered up properly (see “LED Operation“ on page 42).
11.Configure the panel by following the instructions in the NetAXS™ Access
Control Unit User’s Guide.
12.If you are using a battery backup function, place the 7 A-Hr battery in the
enclosure.
13.Attach the positive (red) Power Supply-to-Battery cable to the positive (red)
battery terminal.
NetAXS Access Control Unit NX4S1 Installation Guide, Document 800-00008V3
9
NetAXS™ NX4S1 Installation
Installation
14.Attach the negative (black) Power Supply-to-Battery cable to the negative (black) battery
terminal.
15.For panels using the Ethernet connection, the cable clamp (HAS part number 3-000342) must
be used for the panel to pass the FCC Part 15 Class B requirements. Snap the clamp around any
portion of the Ethernet cable that is inside of the enclosure.
4.1 Cabinet Mounting
The following five figures show the back, top, bottom, right, and left views of the NetAXS™ panel
cabinet. Each view includes the dimensions and knockout placement that you will need to mount the
cabinet. All dimensions are given in inches. See Table 1 on page 14 for dimensions of the conduit
entries into the cabinet.
Figure 2:
NetAXS™ NX4S1 Panel Cabinet, Front View
14 9/32" (362.5 mm)
7 1/8" (181.25 mm)
0
0
0
31/32" (25 mm)
1/4" (6.25 mm)
2 30/32"" (75 mm)
2 30/32" (75 mm)
3/8" (9.375 mm) diameter
(3 holes)
1 23/32" (43.75 mm) diameter knockout
12 1/16" (306.25 mm)
15 3/4" (400 mm)
1/4" (6.25 mm) Ø
17 23/32" (450 mm)
14 7/32" (362.50
13 3/4" (343.75 mm)
12 9/16" (318.75 mm)
7 1/8" (181.25 mm)
www.honeywell.com
1 23/32" (43.75
3/4" (18.75 mm)
0
10
NetAXS™ NX4S1 Installation
Installation
Back
14 9/32" (362.5 mm)
13 9/32" (337.5 mm)
31/32" (25 mm)
NetAXS™ NX4S1 Panel Cabinet, Top View
0
Figure 3:
0
0
3/4" (18.75 mm)
1 11/32" (34.375 mm)
14/16" (21.875 mm) diameter knockout
1 1/4" (31.875 mm) diameter knockout
4 7/32" (107.5 mm)
Figure 4:
NetAXS™ NX4S1 Panel Cabinet, Bottom View
All knockouts punched through for easy removal without damage to cabinet
0
1 3/32" (28.125 mm) diameter knockout
14/16" ( 21.875 mm) diameter knockout
3/4" (18.75 mm)
1 16/32" (38.275 mm)
Back
NetAXS Access Control Unit NX4S1 Installation Guide, Document 800-00008V3
0
31/32" (25 mm)
13 9/32" (337.5 mm)
14 9/32" (362.5 mm)
0
11
NetAXS™ NX4S1 Installation
Installation
NetAXS™ Panel Cabinet, Left View
0
4 11/32" (110 mm)
Figure 5:
Back
7/8" (21.875 mm)
diameter
knockout
1 15/32" (37.5 mm)
3/4" (18.75 mm)
12
www.honeywell.com
NetAXS™ NX4S1 Installation
Installation
NetAXS™ NX4S1Panel Cabinet, Right View
0
4 11/32" (110 mm)
Figure 6:
Back
7/8" (21.875 mm)
diameter
knockout
0
3/4" (18.75 mm)
4 7/32" (107.5 mm)
NetAXS Access Control Unit NX4S1 Installation Guide, Document 800-00008V3
13
NetAXS™ NX4S1 Installation
Installation
4.2 Reader Wiring
Each reader port supports a single 12-volt reader with Wiegand output format. Power
to the readers is shared with the AUX Power ports TB3 and TB14. The maximum
power draw is 600 mA for readers and AUX Power combined.
To fully utilize each reader port, a shielded 7-conductor cable (18-22 AWG) is
required. The reader buzzer feature is not supported with NetAXS-4. Therefore, you
can use the standard six-conductor cable (HAS part number NC1861-BL). The cable
shield should be grounded at the panel only. Grounding at both ends can cause ground
loops which can be disruptive. The maximum recommended length of wiring is 500
feet per reader.
Table 1 Reader Wiring
Terminal
Wire Color
Wiegand Reader
TB5-1, 6-1, 11-1, 12-1
Brown
LED Control
TB5-2 6-2, 11-2, 12-2
Green
Wiegand Data 0
or Data
TB5-3, 6-3, 11-3, 12-3
White
Wiegand Data 1
or Clock
TB5-4, 6-4, 11-4, 12-4
Black
Common
TB5-5, 6-5, 11-5, 12-5
Red
12VDC Power
TB5-6, 6-6, 11-6, 12-6
Variable
Tamper
TB5-7, 6-7, 11-7, 12-7
Variable
Buzzer
4.3 Supervised Input Wiring
The supervised inputs are located on TB4 and TB13 (Figure 7 on page 15). Input 1
through Input 8 may be configured for normally open or normally closed contacts as
supervised or non-supervised. Inputs 13 and 14 are on TB8. All eight inputs have
default functions, but they can be configured for general purpose inputs.
The following table identifies the default function for each terminal position.
Table 2 Default Supervised Input Assignments
14
Terminal Position
Default Function
TB4-1
Door 1 REX (Egress)
TB4-3
Door 1 Status
TB4-4
Door 2 REX (Egress)
www.honeywell.com
NetAXS™ NX4S1 Installation
Installation
Table 2 Default Supervised Input Assignments (continued)
Terminal Position
Default Function
TB4-6
Door 2 Status
TB8-1
External Power Supply AC FAIL
TB8-3
Panel Tamper
TB13-1
Door 3 REX (Egress)
TB13-3
Door 3 Status
TB13-4
Door 4 REX (Egress)
TB13-6
Door 4 Status
TB 5-6, 6-6, 11-6,
12-6
Optional supervised input if not used
for a reader tamper
Note: If the default Door REX inputs are not properly terminated, their associated
relay outputs energize on restart.
The following figure shows the typical wiring for a supervised input.
Figure 7:
Typical Supervised Input Wiring Diagram
NO
2.2K
NC
2.2K
2.2K
2.2K
TB 4
1
2
3
4
5
6
DOOR 1 EGRESS
COMMON
DOOR 1 STATUS
DOOR 2 EGRESS
COMMON
DOOR 2 STATUS
The figure above shows standard 2,200 ohm resistors. The NetAXS™ panel accepts
1,000, 2,200, 4,700, or 10,000 ohm values. Note that both resistors must have the
same value. See the NetAXS™ Access Control Unit User’s Guide for instructions on
selecting resistor options.
In addition, the Tamper and External Power Fail, as well as the Reader and Panel
tampers can be supervised and capable of being used as additional inputs if the default
functionality is not needed. They also share a single common.
NetAXS Access Control Unit NX4S1 Installation Guide, Document 800-00008V3
15
NetAXS™ NX4S1 Installation
Installation
The wire used for the inputs should be shielded and cannot exceed 30 ohms over the
entire length of the cable. Remember that the distance from the panel to the door must
be doubled to determine the total resistance.
Caution: The
cable shield should be grounded only at the panel earth ground.
Grounding at both ends can cause ground loops which can be disruptive.
Caution: The
system has not been verified for compliance with UL1076 Burglar
Alarm units and systems.
4.4 NX4S1 Control Output Wiring
Relay 1 is defaulted for control of the Door 1 lock, Relay 2 is defaulted for the control
of the Door 2 lock, Relay 3 is defaulted for the control of the Door 3 lock, and Relay 4
is defaulted for the control of the Door 4 lock. Relays 5-8 are used as auxiliary relays.
Refer to the NetAXS™ Access Control Unit User’s Guide for details on controlling the
relay operations.
Each relay also has a green indicator LED, which indicates the relay state. If the relay
is active, the LED is illuminated.
Power for the door locks or auxiliary loads must be supplied from a separate external
power supply.
A UL-listed system’s power supply must also be UL-listed for this application.
Caution: The cable used must be sized for the current load and should be shielded. The
cable shield should be grounded at the panel only. Grounding at both ends can cause
ground loops which can be disruptive. Do not bundle these wires with
communication, reader, or supervised input wiring.
4.5 Communications
Caution: Do
not route communication wires with power or locking devices.
Because UL has reviewed the NetAXS™ panel only as a standalone system, the
computer terminal, NetAXS™ gateway panel, and N-485_PCI-2 adapter appear in this
section’s figures only to illustrate the installation and programming of the NetAXS™
panel.
Note:
RS-232 Communications
The NetAXS™ panel communicates with a PC through a 50-foot RS-232 cable (HAS
part number CBL50). Connect the RJ45 end of the cable to the jack on the NetAXS™
panel.
The cable is used to provide communication to a single panel. A second cable can be
used with another NetAXS™ control panel connected to a second COM
(communication) port, which would enable eight readers to be used, see Figure 9,
RS-232 Configuration. A USB converter is also available that will provide RS-232
communications.
16
www.honeywell.com
NetAXS™ NX4S1 Installation
Installation
Figure 8 on page 17 illustrates the connections for an RS-232, DB9 (9 pin) connector
to the panel’s RJ-45 serial port. Replacement cables can be obtained by contacting
your Honeywell Access System Representative.
Figure 8:
RJ-45 Serial Port
Figure 9:
RS-232 Configuration
Reader 1
COM1
NetAXS
Panel
Reader 4
CBL50
Terminal
Reader 1
COM2
NetAXS
Panel
Reader 4
One NetAXS panel per COM port. Two COM ports possible.
NetAXS Access Control Unit NX4S1 Installation Guide, Document 800-00008V3
17
NetAXS™ NX4S1 Installation
Installation
RS-485 Communications
The NetAXS™ panel can reside on an existing RS-485 drop line hosted by either a
NetAXS™ panel configured as a Gateway, or N-485-PCI-2, PCI-3, or N-485-HUB-2
(see Figure 10 on page 18, Figure 11 on page 19, and Figure 23 on page 33). The
interface allows the wiring of a Multidrop communication network of up to 4,000 feet
(1200 m) in length. Only one host converter device per dropline is supported.
On a Multidrop line, the Gateway panel and the PCI unit can have either
end-point or interior positions. See Figure 18 on page 28 and Figure 19 on page 29 for
illustrations.
Note:
DIP switch position 6 on the NetAXS™ panel selects whether the panel is a Gateway
or Multidrop panel. The switch in the OFF position configures the panel as a
Multidrop panel; ON configures a Gateway. The panel must be power cycled for a
new switch setting to be recognized. DIP switch positions 1-5 are used to select the
panel’s address on the network. Refer to Table 3 for DIP switch setting information.
Connectors J36 and J37 are provided for supplying biasing and end-of-line
termination for the RS-485 network. The board ships with all jumpers open. For a
Multidrop RS-485 line, you must close both J36 and J37 (terminated and biased) at the
two end-point panels. At all other panels, leave J36 and J37 open. Both jumpers on a
given panel must set the same. Note that biasing and termination on both ends are
present. Use the jumpers on both ends of the RS-485 network.
If an RS-485 network has a NetAXS™ Gateway panel, no N1000-II, N1000-III,
or N1000-IV are allowed on the same network. If they are added to a network with a
NetAXS™ Gateway panel, they will not be able to communicate with the host
computer.
Note:
Figure 10:
RS-485 Configuration via N-485-PCI-2 or PCI-3
COM1
N-485-PCI-2/3
Terminal
RS-485 Multidrop Line
N1000 III
N1000 IV
NS2+
Panel
NetAXS
Panel
A combination of N1000 III, N1000 IV, NS2+ and NetAXS panels,
supporting a total of 31 panels per multi-drop line
18
www.honeywell.com
NetAXS™ NX4S1 Installation
Installation
Figure 11:
RS-485 Configuration via NetAXS™ Gateway
COM1
NetAXS
Gateway
Reader 1
Reader 4
Terminal
RS-485 Multidrop Line
Reader 1
Reader 1
Reader 1
NS2+
NetAXS
NetAXS
Reader 2
Reader 4
Reader 4
A combination of NetAXS and NS2+ panels, supporting a total of 31
panels per multi-drop line
Note:
This configuration is supported using WIN-PAK and the panel is set to Host Mode.
Ethernet TCP/IP Communications
Figure 12:
Ethernet TCP/IP Configuration
Network Interface
Card Inside PC
Ethernet
Up to 255 TCP/IP Connections per System
Ethernet
10/100
Terminal
NetAXS
Gateway
Reader 1
Reader 4
RS-485 Multidrop Line
Reader 1
NetAXS
Reader 4
Reader 1
Reader 1
NS2+
NetAXS
Reader 2
Reader 4
A combination of NetAXS and NS2+ panels, supporting a total of 31
panels per multi-drop line
Note:
This configuration is supported using WIN-PAK and the panel is set to Host Mode.
NetAXS Access Control Unit NX4S1 Installation Guide, Document 800-00008V3
19
NetAXS™ NX4S1 Installation
Installation
Each NetAXS™ panel has a port for an Ethernet TCP/IP interface (see Figure 12,
Ethernet TCP/IP Configuration). The Ethernet TCP/IP interface provides 10/100 Mbit
Ethernet support for each panel. Up to 31 panels can be configured on each TCP/IP
connection.
Figure 13 on page 20 shows the location of the panel’s unique MAC ID.
Figure 13:
Ethernet MAC Address Location
Label with Ethernet MAC Address
20
www.honeywell.com
NetAXS™ NX4S1 Installation
Installation
4.6 DIP Switch Settings
Figure 14 on page 21 locates the NX4S1 DIP switch panel and the J36 and J37
(termination and biasing) jumpers.
Figure 14:
DIP Switch and Jumper Locations
J37
J36
DIP
Switches
NetAXS Access Control Unit NX4S1 Installation Guide, Document 800-00008V3
21
NetAXS™ NX4S1 Installation
Installation
Use the following DIP switch configurations to set the panel address.
Table 3 DIP Switch Settings
S1
S2
S3
S4
S5
on
off
on
off
on
off
on
off
on
off
on
off
on
off
on
off
on
off
on
off
on
off
on
off
on
off
on
off
on
off
on
off
on
on
off
off
on
on
off
off
on
on
off
off
on
on
off
off
on
on
off
off
on
on
off
off
on
on
off
off
on
on
off
off
off
on
on
on
on
off
off
off
off
on
on
on
on
off
off
off
off
on
on
on
on
off
off
off
off
on
on
on
on
off
off
off
off
off
off
off
on
on
on
on
on
on
on
on
off
off
off
off
off
off
off
off
on
on
on
on
on
on
on
on
off
off
off
off
off
off
off
off
off
off
off
off
off
off
off
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
Note:
22
S6
Selection
off
on
Address 1 (default)
Address 2
Address 3
Address 4
Address 5
Address 6
Address 7
Address 8
Address 9
Address 10
Address 11
Address 12
Address 13
Address 14
Address 15
Address 16
Address 17
Address 18
Address 19
Address 20
Address 21
Address 22
Address 23
Address 24
Address 25
Address 26
Address 27
Address 28
Address 29
Address 30
Address 31
NetAXS™ Multidrop
NetAXS™ Gateway
Address 0 is not a valid setting for standard operations.
www.honeywell.com
NetAXS™ NX4S1 Installation
Installation
4.7 Jumper Settings
The NX4S1 panel control board includes jumpers 36 and 37, which set end-of-line
termination and biasing for the Multidrop RS-485 line.
The board ships with all jumpers set to OFF. For a Multidrop RS-485 line, you must
set both J36 and J37 to CLOSED (terminated and biased) at the two end-point panels.
At all other panels, leave J36 and J37 at OPEN. Note that both jumpers on a given
panel must either be OPEN or CLOSED.
4.8 Downstream I/O
Note: UL has not evaluated the compatibility of downstream I/O devices with the
NetAXS™ panel.
In some applications, the number of system inputs or outputs exceeds the number that
is standard on the NetAXS™ panel. The solution is to add a combination of
MIRO-2/16 and MIRO-32/0 modules external to the NetAXS™ enclosure on a
dedicated RS-485 Downstream Input/Output (I/O) bus. A maximum of two
MIRO-32/0 and a maximum of four MIRO-2/16 for a total of six MIRO modules can
be added to the downstream bus.
A MIRO-32/0 module has 32 supervised, four-state inputs that are limited to 1,000
ohms resistance. The MIRO-2/16 has two supervised inputs and 16 SPDT relay
outputs; each input is limited to 1,000 ohms resistance. Refer to the individual
installation manuals for I/O wiring details.
The downstream I/O bus is wired into the NetAXS™ TB10 terminal block. The
downstream bus has a fixed baud rate and communicates to the MIRO modules using
a polling technique.
Each MIRO module needs to have a unique address for proper communication. Each
one also has some configuration jumpers that need to be positioned correctly.
The following table lists the DIP switch and jumper settings for the MIRO 32/0 and
2/16 modules.
Table 4 MIRO 32/0 DIP Switch and Jumper Settings
Module
Setting
Value
MIRO 32/0
DIP switches
Address (switches 1-6) - 1 or 2
Baud rate (switches 7 and 8) - 7
= OFF, 8 = ON
OP Mode (switches 9 and 10) - 9
= OFF, 10 = OFF
NetAXS Access Control Unit NX4S1 Installation Guide, Document 800-00008V3
23
NetAXS™ NX4S1 Installation
Installation
Table 4 MIRO 32/0 DIP Switch and Jumper Settings (continued)
Module
Setting
Value
Jumper settings
JP1 - CLOSED (if the module is
the last module on the
downstream bus), OPEN (if the
module is not the last module on
the downstream bus)
JP2 - any setting
JP3 - any setting
JP4 - NORMAL
(Positions 1 and 2)
MIRO 2/16
DIP switches
Address (switches 1-6) - 3
through 6
Baud rate (switches 7 and 8) - 7
= OFF, 8 = ON
OP Mode (switches 9 and 10) - 9
= OFF, 10 = OFF
Jumper settings
JP1 - CLOSED, positions 2 and
3 (if the module is the last
module on the downstream bus);
OPEN, positions 1 and 2 (if the
module is not the last module on
the downstream bus)
JP2 - NORMAL, positions 1
and 2
Note: If a MIRO 32/0 is not required in a system, start addressing the 2/16 modules at
DIP switch 3. If a MIRO 32/0 is configured with an address other than 1 or 2, the
NetAXS™ panel will not communicate with it. Likewise, if a MIRO 2/16 is
configured with an address other than 3 through 6, the NetAXS™ panel will not
communicate with it.
The NetAXS™ board is not intended to provide either module power or module
output load power for downstream I/O. A separate 24VDC supply should be used to
provide power to all downstream modules and output loads. For some installations,
the noise immunity improves if the NetAXS™ common is connected to the 24 VDC
Return wiring for the downstream modules. This connection is not needed for most
installations.
24
www.honeywell.com
NetAXS™ NX4S1 Installation
Installation
The following figure shows the default downstream I/O system configuration with communication and
power wiring. This configuration has not been reviewed by UL.
Figure 15:
Default Downstream I/O Configuration with Wiring
NetAXS Access Control Unit NX4S1 Installation Guide, Document 800-00008V3
25
NetAXS™ NX4S1 Installation
System Configuration
5.0 System Configuration
This section provides wiring diagrams for each of the NetAXS™ system configurations.
5.1 RS-485 Connection via PCI-2
This connection supports thirty-one NetAXS™ Access Controller panels for each drop line. It has
been reviewed by Underwriters Laboratories Incorporated (UL). Note that PCI-2 units can also be
wired anywhere along the drop line. See Figure 18 on page 28 and Figure 19 on page 29. Because UL
has reviewed the NetAXS™ panel only as a standalone system, the computer terminal, NetAXS™
gateway panel, and N-485_PCI-2 adapter appear in this section only to illustrate the installation and
programming of the NetAXS™ panel.
Figure 16:
RS-485 Connection via PCI-2
COM Port
RS-232 (50 Ft. Max.)
RS-485 (4,000 Ft.)
N-485-PCI-2
Terminal
Refer to N-485-PCI-2/NS2/NS2+
Access Controller Panel
Connection Detail diagram
RS-485 Cable
RS485
NetAXS Panels
Red/White
Black/Green
RS-485 COM
TB7-1 (RS485+)
TB7-2 (RS485-)
TB7-3 (RS485 COM)
4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with
shield, 120 ohm, 23 pf (HAS part no. NCP2441-TN)
DIP Switch Settings
S1: ON
S2: ON
S3: ON
S4: ON
S5: ON
S6: ON (Ack/Nak Enable)
S7: ON
S8: OFF (19,200 Baud Rate)
See RS-485
Cable Note
DIP Switch Settings
S1-S5 Panel Address
S6: OFF
J36 OPEN
J37 OPEN
DIP Switch Settings
S1-S5 Panel Address
S6: OFF
J36 CLOSED
J37 CLOSED
It is recommended to Earth Ground (EG) each
NetAXS enclosure individually
NetAXS
Panel
NetAXS
Panel
EG
EG
Only Earth
th Ground
G
d (EG)
one side of cable
EG
26
www.honeywell.com
EG
NetAXS™ NX4S1 Installation
System Configuration
5.2 RS-485 Connection via NetAXS™
This connection supports thirty-one NetAXS™ Access Controller panels for each drop line. It has
been reviewed by UL. However, because UL has reviewed the NetAXS™ panel only as a standalone
system, the computer terminal and NetAXS™ gateway panel appear in this section only to illustrate
the installation and programming of the NetAXS™ panel.
Figure 17:
RS-485 Connection via NetAXS™
COM Port
RS-232 (50 Ft. Max.)
RS-485 (4,000 Ft.)
NetAXS
Getaway
Terminal
Refer to NetAXS / NetAXS
Panel Connection Detail
diagram
DIP Switch Settings
S1-S5: Panel Address
S6: ON
J36: CLOSED
J37: CLOSED
RS-485 Cable
NetAXS Panel
TB7-1 (RS485+)
TB7-2 (RS485-)
TB7-3 (RS485 COM)
4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with shield,
120 ohm, 23 pf (HAS part no. NCP2441-TN)
DIP Switch Settings
S1-S5 Panel Address
S6: OFF
J36 OPEN
J37 OPEN
DIP Switch Settings
S1-S5 Panel Address
S6: OFF
J36 CLOSED
J37 CLOSED
NetAXS
Panel
NetAXS
Panel
EG
EG
See RS-485
Cable Note
Only Earth Ground (EG)
one side of cable
EG
EG
It is recommended to Earth Ground (EG)
each NetAXS enclosure individually
NetAXS Access Control Unit NX4S1 Installation Guide, Document 800-00008V3
27
NetAXS™ NX4S1 Installation
System Configuration
5.3 RS-485 Connections with Multidrop Panels at Both Ends of the Cable
You can connect Multidrop panels at both ends of an RS-485 cable via either a NetAXS™ panel or a
PCI-2 device. These configurations have not been reviewed by UL.
Figure 18:
RS-485 Connection via NetAXS™ with Multidrop Panels at Both Ends
RS-485 (4,000 Ft.)
COM Port
Terminal
Refer to
NetAXS/NetAXS
Panel Connection
Detail diagram
NetAXS
Gateway
RS-485 Cable
NetAXS Panels
TB7-1 (RS485+)
TB7-2 (RS485-)
TB7-3 (RS485 COM)
DIP Switch Settings
S1-S5: Panel Address
S6: ON
J36 OPEN
J37 OPEN
4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with
shield, 120 ohm, 23 pf (HAS part no. NCP2441-TN)
DIP Switch Settings
S1-S5 Panel Address
S6: OFF
J36 OPEN
J37 OPEN
DIP Switch Settings
S1-S5 Panel Address
S6: OFF
J36 CLOSED
J37 CLOSED
NetAXS
Panel
EG
NetAXS
Panel
EG
NetAXS
Panel
EG
EG
Only Earth Ground (EG)
one side of cable
EG
DIP Switch Settings
S1-S5 Panel Address
S6: OFF
J36 OPEN
J37 OPEN
DIP Switch Settings
S1-S5 Panel Address
S6: OFF
J36 CLOSED
J37 CLOSED
NetAXS
Panel
See RS-485
Cable Note
Only Earth Ground (EG)
one side of cable
EG
EG
It is recommended to Earth Ground (EG) each NetAXS enclosure individual
28
www.honeywell.com
EG
NetAXS™ NX4S1 Installation
System Configuration
Figure 19:
RS-485 Connection via PCI-2 with Multidrop Panels at Both Ends
COM Port
RS-232 (50 Ft. Max.)
RS-485 (4,000 Ft.)
N-485-PCI-2
Terminal
Refer to N-485-PCI-2/NetAXS
Access Controller Panel
Connection Detail diagram
DIP Switch Settings
S1: ON
S2: ON
S3: ON
S4: ON
S5: ON
S6: ON (Ack/Nak Enable)
S7: ON
S8: OFF (19,200 Baud Rate)
RS-485 Cable
RS485
NetAXS Panels
Red
Black
RS-485 COM
TB7-1 (RS485+)
TB7-2 (RS485-)
TB7-3 (RS485 COM)
4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with
shield, 120 ohm, 23 pf (HAS part no. NCP2441-TN)
DIP Switch Settings
S1-S5 Panel Address
S6: OFF
J36 CLOSED
J37 CLOSED
DIP Switch Settings
S1-S5 Panel Address
S6: OFF
J36 OPEN
J37 OPEN
DIP Switch Settings
S1-S5 Panel Address
S6: OFF
J36 CLOSED
J37 CLOSED
NetAXS
Panel
NetAXS
Panel
EG
EG
EG
Only Earth
th Ground
G
d (EG)
one side of cable
Only Earth
th Ground
G
d (EG)
one side of cable
EG
DIP Switch Settings
S1-S5 Panel Address
S6: OFF
J36 OPEN
J37 OPEN
NetAXS
Panel
NetAXS
Panel
EG
See RS-485
Cable Note
EG
EG
EG
It is recommended to Earth Ground (EG) each NetAXS enclosure individually
NetAXS Access Control Unit NX4S1 Installation Guide, Document 800-00008V3
29
NetAXS™ NX4S1 Installation
System Configuration
5.4 RS-232 Connection
This connection supports one NetAXS™ Access Controller panel for each COM port. It has been
reviewed by UL. However, because UL has reviewed the NetAXS™ panel only as a standalone
system, the computer terminal and NetAXS™ gateway panel appear in this section only to illustrate
the installation and programming of the NetAXS™ panel.
Figure 20:
RS-232 Connection
CBL50 (RS-232) 50 Ft. Max.
COM 1
COM 2
Terminal
CBL50
(RS-232)
50 Ft. Max.
DIP Switch Settings
S1 - S5: Panel Address
S6: OFF
NetAXS
Panel
NetAXS
Panel
It is recommended to Earth Ground (EG)
each NetAXS enclosure individually
EG
CBL50 (RS-232)
RS-232
(DB9)
8
5
2
3
7
RJ-45
Request To Send (RTS)
Signal Ground (GND)
Receive Data (RXD)
Transmit Data (TXD)
Clear To Send (CTS)
2
3
4
5
7
9-Pin COM 1 or COM 2 to RJ-45 on NetAXS Panel
30
www.honeywell.com
EG
NetAXS™ NX4S1 Installation
System Configuration
5.5 Ethernet Connection
This connection supports a maximum of 255 IP connections per server. It has not been reviewed by
UL.
Figure 21:
Ethernet Connection
NIC
100BaseT (CAT 5) 328 Ft. Max.
HUB/SWITCH
NIC
Terminal
HUB/SWITCH
RS-485 Multidrop
NetAXS
Panel
DIP Switch Settings
S1-S5 Panel Address
S6: ON: Gateway
EG
NetAXS
Panel
NetAXS
Panel
EG
EG
NetAXS
Panel
EG
100BaseT (CAT 5) 328 Ft. Max.
It is
recommended to
Earth Ground (EG)
each NetAXS
enclosure
individually
DIP Switch Settings
S1-S5 Panel Address
S6: OFF
RS-485 Multidrop
DIP Switch Settings
S1-S5 Panel Address
S6: OFF
100BaseT (CAT 5)
328 Ft. Max.
Crossover Cable
NetAXS
Panel
EG
NetAXS Access Control Unit NX4S1 Installation Guide, Document 800-00008V3
NetAXS
Panel
EG
31
NetAXS™ NX4S1 Installation
System Configuration
5.6 LANSRLU1 Connection
This connection supports thirty-one panels for each drop line and a maximum of 255 IP connections. It
has not been reviewed by UL. Note that PCI-2 units can also be wired anywhere along the drop line.
See Figure 18 on page 28 and Figure 19 on page 29.
Figure 22:
LANSRLU1 Connection
NIC
HUB/SWITCH
Terminal
HUB/SWITCH
HUB/SWITC
CH
HUB/SWITCH
RS-485 Cable
RS485
NetAXS Panels
Red/White
Black/Green
RS-485 COM
100BaseT
(CAT 5)
328 Ft. Max.
TB7-1 (RS485+)
TB7-2 (RS485-)
TB7-3 (RS485 COM)
DIP Switch Settings
S1: ON
S2: ON
S3: ON
S4: ON
S5: ON
S6: ON (Ack/Nak ON)
S7: ON
S8: OFF (19,200 Baud Rate)
4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with
shield, 120 ohm, 23 pf (HAS part no. NCP2441-TN)
LANSRLU1
RJ-45
N-485-PCI-2
RS-232 (50 Ft.)
DIP Switch Settings
S1-S5 Panel Address
S6: OFF
J36: OPEN
J37: OPEN
DIP Switch Settings
S1-S5 Panel Address
S6: OFF
J36: CLOSED
J37: CLOSED
NetAXS
Panel
Refer to 485-PCI-2
/ NetAXS Panel
Connection Detail
diagram
NetAXS
Panel
EG
See RS-485 Cable note
EG
It is recommended to Earth Ground (EG)
each NetAXS enclosure individually
EG
32
www.honeywell.com
Only Earth Ground (EG)
one side of cable
EG
NetAXS™ NX4S1 Installation
System Configuration
5.7 RS-485 Short Haul Modem Connection via PCI-2
This connection supports thirty-one NetAXS™ Access Controller panels for each drop line. It has not
been reviewed by UL. Note that PCI-2 units can also be wired anywhere along the drop line. See
Figure 18 on page 28 and Figure 19 on page 29.
Figure 23:
RS-485 Short Haul Modem Connection via PCI-2
RS232 Cable
PC
(DB-9)
RS-232, 50 Ft. Max.
MODEM
DTE
(Straight)
2 TX
3 RX
5 Comm
DCE
(Null)
2 (TX)
2 (RX)
3 (RX) or 3 (TX)
7 (GND) 7 (GND)
Terminal
SHM-B-ASYNCH
Short Haul Modem
(J1 RS-232 Connector)
RS-485 Cable
NetAXS Panels
DCE
DN
RX +
RX -
TX +
TX GROUND
TB7-1 (RS485+)
TB7-2 (RS485-)
TB7-3 (RS485 COM)
(Jumper)
DIS
RTSIDTR
CONTROL
4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with
shield, 120 ohm, 23 pf (HAS part no. NCP2441-TN)
DTE
DIP Switch Settings
S1-S5 Panel Address
S6: OFF
J36: CLOSED
J37: CLOSED
DIP Switch Settings
S1-S5 Panel Address
S6: OFF
J36: OPEN
J37: OPEN
(S2 Loopback)
5279.9
Feet
(S2 Loopback)
EG
NetAXS
Panel
EG
NetAXS
Panel
See RS-485
cable note
RTSIDTR
CONTROL
DN
Only Earth Ground (EG)
one side of cable
EG
(Jumper)
DIS
EG
It is recommended to Earth Ground (EG) each
NetAXS enclosure individually
SHM-B-ASYNCH
Short Haul Modem
(J1 RS-232 Connector)
RS232 Cable
DIP Switch Settings
S1: ON
S2: ON
S3: ON
S4: ON
S5: ON
S6: OFF (Ack/Nak Enable)
S7: ON
S8: OFF )19,200 Baud Rate)
N-485-PCI-2
(RS-232 50 Ft. Max.)
Male 9 Pin
Male 25 Pin
PC
(DB-9)
2 TX
3 RX
5 Comm
MODEM
DTE
(Straight)
DCE
(Null)
2 (TX)
2 (RX)
3 (RX) or 3 (TX)
7 (GND) 7 (GND)
Refer to 485-PCI-2/NetAXS Panel
Connection Detail diagram
NetAXS Access Control Unit NX4S1 Installation Guide, Document 800-00008V3
33
NetAXS™ NX4S1 Installation
System Configuration
5.8 RS-485 Short Haul Modem Connection via NetAXS™
Thirty-one NetAXS™ Access Controller panels for each drop line. It has not been reviewed by UL.
Figure 24:
RS-485 Short Haul Modem Connection via NetAXS™
RS232 Cable
PC
(DB-9)
RS-232, 50 Ft. Max.
MODEM
DTE
(Straight)
2 TX
3 RX
5 Comm
DCE
(Null)
2 (TX)
2 (RX)
3 (RX) or 3 (TX)
7 (GND) 7 (GND)
Terminal
SHM-B-ASYNCH
Short Haul Modem
(J1 RS-232 Connector)
RS-485 Cable
NetAXS Panels
DCE
DN
RX +
RX -
TX +
TX GROUND
TB7-1 (RS485+)
TB7-2 (RS485-)
TB7-3 (RS485 COM)
(Jumper)
DIS
RTSIDTR
CONTROL
4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with
shield, 120 ohm, 23 pf (HAS part no. NCP2441-TN)
DTE
DIP Switch Settings
S1-S5 Panel Address
S6: OFF
J36: CLOSED
J37: CLOSED
DIP Switch Settings
S1-S5 Panel Address
S6: OFF
J36: OPEN
J37: OPEN
(S2 Loopback)
5279.9
Foot
(S2 Loopback)
EG
NetAXS
Panel
EG
NetAXS
Panel
See RS-485
cable note
RTSIDTR
CONTROL
DN
Only earth ground (EG)
one side of cable
EG
(Jumper)
DIS
EG
It is recommended to Earth Ground (EG) each
NetAXS enclosure individually
SHM-B-ASYNCH
Short Haul Modem
(J1 RS-232 Connector)
RS232 Cabl
DIP Switch Settings
S1-S5 Panel Address
S6: ON
J36: CLOSED
J37: CLOSED
34
www.honeywell.com
NetAXS
Panel
(RS-232 50 Ft. Max.)
CBL50
Male 9 Pin
Male 25 Pin
PC
(DB-9)
2 TX
3 RX
5 Comm
MODEM
DTE
(Straight)
DCE
(Null)
2 (TX)
2 (RX)
3 (RX) or 3 (TX)
7 (GND) 7 (GND)
NetAXS™ NX4S1 Installation
System Configuration
5.9 RS-232 Short Haul Modem Connection
One NetAXS™ Access Controller panel for each loop. It has not been reviewed by UL.
Figure 25:
RS-232 Short Haul Modem Connection
RS232 Cable
PC
(DB-9)
RS-232, 50 Ft. Max.
Terminal
MODEM
DTE
(Straight)
2 TX
3 RX
5 Comm
DCE
(Null)
2 (TX)
2 (RX)
3 (RX) or 3 (TX)
7 (GND) 7 (GND)
SHM-B-ASYNCH
Short Haul Modem
DN
(Jumper)
RX +
RX -
TX +
TX GROUND
DCE
DIS
RTSIDTR
CONTROL
(DEC/DTE)
DTE
(S2 Loopback)
DIP Switch Settings
S1-S5 Panel Address
S6: OFF
5279.9
Foot
(S2 Loopback)
EG
NetAXS
Panel
(DEC/DTE)
RTSIDTR
CONTROL
DN
(Jumper)
DIS
CBL50
It is recommended to
Earth Ground (EG) each
NetAXS enclosure
individually
SHM-B-ASYNCH
Short Haul Modem
(J1 RS-232 Connector)
RS232 Cable
(RS-232 50 Ft. Max.)
Male 9 Pin
Male 25 Pin
NetAXS Access Control Unit NX4S1 Installation Guide, Document 800-00008V3
PC
(DB-9)
2 TX
3 RX
5 Comm
MODEM
DTE
(Straight)
DCE
(Null)
2 (TX)
2 (RX)
3 (RX) or 3 (TX)
7 (GND) 7 (GND)
35
NetAXS™ NX4S1 Installation
System Configuration
5.10 M-56K Dial-up Modem, RS-485 Connection via Hub
Thirty-one NetAXS™ Access Controller panels for each drop line. It has not been reviewed by UL.
Figure 26:
M-56K Dial-up Modem, RS-485 Connection via Hub
M-56K
FAX/MODEM
COM Port
Straight Through Cable
Female 9 Pin
Terminal
Male 25 Pin
(RX) 2
(TX) 3
Analog
Phone
Line
Remote DIP Switch Settings
(1, 3, 8 ON) (2, 4, 5, 6, 7 OFF)
3 (RX)
2 (TX)
(Comm) 5
7 (Comm)
N-485-HUB-2
Dedicated
analog
phone
line
recommended
M-56K
FAX/MODEM
RS-232 (50 ft.)
Remote DIP Switch Settings
(1, 3, 8 ON) (2, 4, 5, 6, 7 OFF)
RS-485 (4,000 ft.)
Refer to 485PCI-2 /NetAXS
Panel
Connection
Detail diagram
DIP Switch Settings
S1: ON
S2: ON
S3: ON
S4: ON
S5: ON
S6: ON (Ack/Nak ON)
S7: ON
S8: OFF (19,200 Baud Rate)
DIP Switch Settings
S1-S5 Panel Address
S6: OFF
J36: OPEN
J37: OPEN
DIP Switch Settings
S1-S5 Panel Address
S6: OFF
J36: CLOSED
J37: CLOSED
NetAXS
Panel
NetAXS
Panel
EG
EG
EG
Only Earth Ground (EG)
one side of cable
See RS-485
Cable Note
EG
It is recommended to Earth Ground (EG)
each NetAXS enclosure Individually
RS-485 Cable
DB 9 / DB 25 Connectors
13
Female
1
25
14
5
9
36
www.honeywell.com
1
6
NetAXS Panels
Male
13
1
25
14
5
9
1
6
TB7-1 (RS485+)
TB7-2 (RS485-)
TB7-3 (RS485 COM)
4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with
shield, 120 ohm, 23 pf (HAS part no. NCP2441-TN)
NetAXS™ NX4S1 Installation
System Configuration
5.11 M-56K Dial-up Modem, RS-485 Connection via NetAXS™
Thirty-one NetAXS™ Access Controller panels for each drop line. It has not been reviewed by UL.
Figure 27:
M-56K Dial-up Modem, RS-485 Connection via NetAXS™
M-56K
FAX/MODEM
COM Port
Straight Through Cable
Female 9 Pin
Terminal
Male 25 Pin
(RX) 2
(TX) 3
3 (RX)
2 (TX)
(Comm) 5
CBL50
7 (Comm)
Male 9 Pin
NetAXS
Panel
Analog
Phone
Line
Remote DIP Switch Settings
(1, 3, 8 ON) (2, 4, 5, 6, 7 OFF)
Dedicated
analog
phone
line
recommended
M-56K
FAX/MODEM
Male 25 Pin
RS-232 (50 ft.)
Remote DIP Switch Settings
(1, 3, 8 ON) (2, 4, 5, 6, 7 OFF)
RS-485 (4,000 ft.)
DIP Switch Settings
S1-S5 Panel Address
S6: OFF
J36: OPEN
J37: OPEN
DIP Switch Settings
S1-S5 Panel Address
S6: OFF
J36: CLOSED
J37: CLOSED
DIP Switch Settings
S1-S5 Panel Address
S6: ON
J36: CLOSED
J37: CLOSED
NetAXS
Panel
NetAXS
Panel
EG
EG
It is recommended to
Earth Ground (EG)
each NetAXS enclosure
Individually
EG
DB 9 / DB 25 Connectors
13
Female
1
25
14
5
9
1
6
1
25
14
5
9
EG
RS-485 Cable
Male
13
See RS-485
Cable Note
1
6
NetAXS Panels
TB7-1 (RS485+)
TB7-2 (RS485-)
TB7-3 (RS485 COM)
4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with
shield, 120 ohm, 23 pf (HAS part no. NCP2441-TN)
NetAXS Access Control Unit NX4S1 Installation Guide, Document 800-00008V3
37
NetAXS™ NX4S1 Installation
System Configuration
5.12 Fiber Converter to RS-485 Connection via PCI-2
This connection supports thirty-one NetAXS™ Access Controller panels for each drop line. It has not
been reviewed by UL. Note that PCI-2 units can also be wired anywhere along the drop line. See
Figure 18 on page 28 and Figure 19 on page 29.
Figure 28:
Fiber Converter to RS-485 Connection via PCI-2
Refer to N-485-PCI-2/NetAXS Access
Controller Panel Connection Detail diagram
COM Port
RS-485
(4000 Ft. Max.)
RS-232 (50 Ft. Max.)
N-485-PCI-2
Terminal
NetAXS
Panel
EG
FC485
RS-485 Fiber Converter
DIP Switch Settings
S1 ON
S2 ON
S3 ON
S4 ON
S5 ON
S6 ON
S7 on
S8 OFF
19,200 Baud Rate
RXD
PWR
TXD
RS-485 Comm.
EG
RS-485 Positive (+)
RS-485 Negative (-)
RS-485 Drain Wire Floating
DIP Switch Settings
S1-S5 Panel Address
S6: OFF
J36: CLOSED
J37: CLOSED
Fiber RXD
Fiber TXD
FC485
RS-485 Fiber Converter
RXD
PWR
TXD
RS-485 Comm.
RS-485 Positive (+)
RS-485 Negative (-)
RS-485 Drain Wire to earth ground
Fiber RXD
Fiber TXD
Fiber Cable
10,000 Ft. Max.
FC485
RS-485 Fiber Converter
Fiber Cable
10,000 Ft. Max.
RS-485 Drain
not connected here
(connected at panel side)
RXD
PWR
TXD
FC485
RS-485 Fiber Converter
NetAXS Panel
RS-485 Comm.
RS-485 Positive (+)
TB1-3 (RS485 COM)
TB1-1 (RS485+)
TB1-2 (RS485-)
RS-485 Negative (-)
RXD
PWR
TXD
RS-485 Drain
Only Earth Ground
(EG) one side of
cable
RS-485 Comm.
RS-485 Positive (+)
RS-485 Negative (-)
Fiber RXD
Fiber TXD
Fiber RXD
Fiber TXD
NetAXS
Panel
NetAXS
Panel
EG
EG
It is recommended to
Earth Ground (EG)
each NetAXS enclosure
Individually
EG
DIP Switch Settings
S1-S5 Panel Address
S6: OFF
J36: OPEN
J37: OPEN
38
www.honeywell.com
RS-485 Cable
RS485
EG
Red/White
Black/Green
RS-485 COM
NetAXS Panels
TB7-1 (RS485+)
TB7-2 (RS485-)
TB7-3 (RS485 COM)
4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with
shield, 120 ohm, 23 pf (HAS part no. NCP2441-TN)
NetAXS™ NX4S1 Installation
System Configuration
5.13 Fiber Converter to RS-485 Connection via NetAXS™
This connection supports thirty-one NetAXS™ Access Controller panels for each drop line. It has not
been reviewed by UL.
Figure 29: Fiber Converter to RS-485 Connection via NetAXS™
RS-485
(4000 Ft. Max.)
COM Port
RS-232 (50 Ft. Max.)
Terminal
NetAXS
Panel
NetAXS
Panel
EG
FC485
RS-485 Fiber Converter
DIP Switch Settings
RXD
PWR
TXD
S1 S5 Panel Address
S6 ON
J36 CLOSED
J37 CLOSED
NetAXS Panel
RS-485 Comm.
RS-485 Positive (+)
RS-485 Negative (-)
TB1-3 (RS485 COM)
TB1-1 (RS485+)
TB1-2 (RS485-)
EG
NetAXS Panel
RS-485 Drain Wire Floating
Fiber RXD
Fiber TXD
Fiber Cable
10,000 Ft.
TB1-3 (RS485 COM)
TB1-1 (RS485+)
TB1-2 (RS485-)
DIP Switch Settings
S1-S5 Panel Address
S6: OFF
J36: CLOSED
J37: CLOSED
FC485
RS-485 Fiber Converter
RXD
PWR
TXD
RS-485 Comm.
RS-485 Positive (+)
RS-485 Negative (-)
RS-485 Drain Wire to earth ground
Fiber RXD
Fiber TXD
Fiber Cable
10,000 Ft.
FC485
RS-485 Fiber Converter
RS-485 Drain
not connected here
(connected at panel side)
RXD
PWR
TXD
FC485
RS-485 Fiber Converter
NetAXS Panel
RS-485 Comm.
RS-485 Positive (+)
RS-485 Negative (-)
TB1-3 (RS485 COM)
TB1-1 (RS485+)
TB1-2 (RS485-)
RXD
PWR
TXD
NetAXS Panel
TB1-3 (RS485 COM)
TB1-1 (RS485+)
TB1-2 (RS485-)
Fiber RXD
Fiber TXD
RS-485 Comm.
RS-485 Positive (+)
RS-485 Negative (-)
Fiber RXD
Fiber TXD
NetAXS
Panel
NetAXS
Panel
EG
EG
It is recommended to
Earth Ground (EG)
each NetAXS enclosure
Individually
EG
RS-485 Cable
EG
NetAXS Panels
DIP Switch Settings
S1-S5 Panel Address
S6: OFF
J36: OPEN
J37: OPEN
NetAXS Access Control Unit NX4S1 Installation Guide, Document 800-00008V3
TB7-1 (RS485+)
TB7-2 (RS485-)
TB7-3 (RS485 COM)
4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with
shield, 120 ohm, 23 pf (HAS part no. NCP2441-TN)
39
NetAXS™ NX4S1 Installation
System Configuration
5.14 N-485-PCI-2/NetAXS™ Access Controller Panel Connection Detail
This diagram has not been reviewed by UL. Note that PCI-2 units can also be wired anywhere along
the drop line. See Figure 18 on page 28 and Figure 19 on page 29.
Figure 30:
N-485-PCI-2/NetAXS™ Access Controller Panel Connection Detail
485 Interface Connection Types
DIP Switch Settings
S1: ON
S2: ON
S3: ON
S4: ON
S5: ON
S6: ON
S7: ON
S8: OFF
RS-485
NetAXS Panel
N-485-PCI-2
N-485-HUB-2
N-485-PCI-2L
COM Port
M-56K Modem
LANSRL100 or LANSRLU1
To Serial Connection
See 485 interface
connection note
Ground Shield
DO NOT CONNECT or
GROUND SHIELD
N-485-PCI-2
NetAXS TB7
1
2
3
N
MO
COM
WHITE
GREE
N
BLAC
K
RED
DIP Switch Settings
S1-S5: Panel Address
S6: OFF
J36: CLOSED
J37: CLOSED
485
Common
NetAXS TB7
DIP Switch Settings
S1-S5: Panel Address
S6: OFF
J36: OPEN
J37: OPEN
Ground only one
side of cable shield
X
Shield
485 +
485 4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with
shield, 120 ohm, 23 pf (HAS part no. NCP2441-TN)
40
www.honeywell.com
X
1
2
3
NetAXS™ NX4S1 Installation
System Configuration
5.15 NetAXS™/NetAXS™ Access Controller Panel Connection Detail
Figure 31:
NetAXS™/NetAXS™ Access Controller Panel Connection Detail
Ground Shield
DO NOT CONNECT or
GROUND SHIELD
To Serial Connection
NetAXS TB7
1
2
3
DIP Switch Settings
S1-S5: Panel Address
S6: OFF
J36: CLOSED
J37: CLOSED
DIP Switch Settings
S1-S5: Panel Address
S6: ON
J36: CLOSED
J37: CLOSED
DO NOT
CONNECT
SHIELD
485
Common
NetAXS TB7
1
2
3
DIP Switch Settings
S1-S5: Panel Address
S6: OFF
J36: OPEN
J37: OPEN
Ground only one
side of cable shield
X
NetAXS Panel
X
Shield
3
1
2
NetAXS TB7
485 +
485 4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with
shield, 120 ohm, 23 pf (NCI part no. NCP2441-TN)
NetAXS Access Control Unit NX4S1 Installation Guide, Document 800-00008V3
41
NetAXS™ NX4S1 Installation
NetAXS™ Startup
6.0 NetAXS™ Startup
6.1 LED Operation
When the panel wiring is complete, turn on the power. It might take a few minutes for the panel to
complete the power-up sequence. When the board does initialize, verify that the appropriate LEDs
identified in the following figure are in accord with the descriptions in Table 5 on page 43.
Figure 32:
System, Relay and Power LEDs
RDR 3
Host RS232 and
Downstream LEDs
Ethernet Status
LEDs
Run LED
RS485 LED
RDR 1
RDR 2
Relay
Status
LEDs
Relay Status
LEDs
Power
42
www.honeywell.com
RDR 4
NetAXS™ NX4S1 Installation
NetAXS™ Startup
The following table indicates the status associated with each LED.
Table 5 LED Status
LED
PWR
RUN
H485
H232
DS
COM
LINK
RLY
RDR
GREEN
Power
OK
Blink =
normal
Steady =
malfunction
Multidrop
Receive
Data
RS232
Receive
Data
Downstream
Receive
Data
100Mbit
Link
OK
Relay
Active
Flash at
read
RED
N/A
N/A
Trans-m
it Data
Trans-m
it Data
Trans-m
it Data
N/A
N/A
N/A
N/A
AMBER
N/A
N/A
TX &
RX
Data
TX &
RX
Data
TX &
RX
Data
N/A
TX &
RX
Data
N/A
N/A
OFF
Power
Off
Malfunction
No
Com
No
Com
No
Com
10Mbit
No
Link
Relay
Off
Normal
Note: The Ethernet/COM status LED will be green even if no cable is attached.
NetAXS Access Control Unit NX4S1 Installation Guide, Document 800-00008V3
43
NetAXS™ NX4S1 Installation
Hardware Specifications
7.0 Hardware Specifications
7.1 Relay Contacts
Four Form-C SPDT relays:
• 10 A @ 28 VDC resistive load
• 5 A @ 28 VDC inductive load
7.2 Reader Interface
• Reader Output Voltage ranges from 11.2 VDC to 12.4 VDC. The maximum
Reader Output Current is 600 mA.
• Reader LED Output: Open collector driver capable of sinking up to 8 mA.
• Reader Tamper: Supervised or non-supervised input.
• Reader Data Input: TTL compatible inputs.
• Reader Buzzer Output (not supported with NetAXS-4): Open collector driver
capable of sinking 8 mA at 15 VDC.
7.3 NX4S1 Wire Requirements
• Power: One twisted pair shielded, 18 AWG.
• RS-485: 24 AWG, 4,000 ft. (1,200 m) max, twisted pairs with shield, 120 ohm,
23 pf (HAS part number NC2441-TN).
• RS-232: Use cable supplied with installation kit (HAS part number CBL50).
Maximum distance per COM port is 50 ft.
• Supervised Inputs: One twisted pair per input, shielded 30 ohms maximum.
• Outputs: As required by load.
• Readers: 7 conductors, 18 AWG, shielded, 500 ft. (150 m) max.
7.4 Maximum Output Loading
• Maximum current for any of the four reader outputs is 600 mA.
• Maximum current for each of the two auxiliary outputs on the NetAXS™
panel is 500 mA.
• Maximum battery charge current for the single battery is 350 mA.
• Maximum combined current of the four reader outputs and the two auxiliary
outputs is
600 mA.
• Maximum combined current of the two auxiliary outputs (if used without the
four reader outputs) is 500 mA.
Notes:
• Each of the eight relay output contacts on the panel is rated for either 10 A at
28 VDC (resistive) or 5 A at 28 VDC (inductive). However, they are powered
from a separate power supply.
• A UL-listed system’s power supply must also be UL-listed for this application.
44
www.honeywell.com
NetAXS™ NX4S1 Installation
Hardware Specifications
7.5 Common Connections
Common connections are all connected internally. They are not connected to the panel
chassis.
7.6 Mechanical
• Panel Dimensions
– Width: 8 inches (203.2 mm)
– Length: 9.75 inches (247.65 mm)
– Height: 1.5 inches (38.1 mm)
• Panel Weight: 1.1 pounds (0.5 kg)
• Enclosure Dimension
– Width: 14.5 inches (368.3 mm)
– Length: 18.0 inches (457.2 mm)
– Height: 4.4 inches (111.8 mm)
• Enclosure Weight, including 7 A-Hr battery: 22.1 pounds (10 kg)
7.7 Environment
• Temperature: 0C to 49C operating, -55C to +85C storage.
• Humidity: 5% to 85% RHNC.
NetAXS Access Control Unit NX4S1 Installation Guide, Document 800-00008V3
45
NetAXS™ NX4S1 Installation
Hardware Specifications
7.8 Communications and Wiring
Table 6 Communications and Wiring
Communication Type
Description
Maximum
Panels
Maximum Distance:
Feet (Meters)
Direct to COM Port
CBL50, RS-232 Cable
9-pin to RJ-45
1
50 (15)
N-485-PCI-2
RS-485 9-pin to CPU
31
4,000 (1,220)
SHM-B-ASYNC/
N-485-PCI-2
Short-haul Modem to
RS-485
31
5,280/4,000 (1,610/1,220)
SHM-B-ASYNC/CBL50
Short-haul Modem to
RS-232
1
5,280/50 (1,610/15)
M-56K/N-485-HUB-2
Dial-up Modem to RS-485
31
NA/4,000 (NA/1,220)
Fiber converter to RS-485
31
10,000/4,000 (3,050/1,220)
Modems
Fiber
FC485
7.9 Reader Wiring
Table 7 Reader Wiring
Cable Specifications
Description
AWG
Maximum Distance:
Feet (Meters)
Readers
NC1861-BL
6 Conductor, Shielded
18
500 (153)
Twisted Pair, Shielded
18
2,000 (610)
Twisted Pair, Shielded
18
2,000 (610)
Alarm Input
NC1821-GR
Relay Outputs
NC1821-GR
46
www.honeywell.com
NetAXS™ NX4S1 Installation
Hardware Specifications
7.10 NX4S1 Wiring Diagram
NX4S1 Panel Wiring Diagram
Door 1/2
Outputs*
}
}
1
XPORT
TB5
TB12
TB13
TB4
TB14
TB3
TB15
TB2
TB16
TB1
J20 (+)
J24 (-)
TB17
_
Battery
CASIL CA1270
+
HAS 3-000066
12VDC, 7AHr
NetAXS Access Control Unit NX4S1 Installation Guide, Document 800-00008V3
}
}
}
Expansion
RS-485*
}
}
}
Reader 3*
TB11
TB6
}
Reader 4*
6
Expansion RS485-/B
Expansion RS485+/A
Buzzer/OUT 17
Tamper/IN 11
+12VDC
Common
D1
D0
LED/OUT 13
Buzzer/OUT 16
Tamper/IN 12
+12VDC
Common
D1
D0
LED/OUT 14
DR3 REX/IN 5
Common
DR3 Status/IN 6
DR4 REX/IN 7
Common
DR4 Status/IN 8
Aux Common
Aux + 12VDC
Relay 5 N.C.
Relay 5 Com
Relay 5 N.O.
Relay 6 N.C.
Relay 6 Com
Relay 6 N.O.
Relay 7 N.C.
Relay 7 Com
Relay 7 N.O.
Relay 8 N.C.
Relay 8 Com
Relay 8 N.O.
AC/DC AC/DC +
Door 3/4
Inputs *
DIP switches
RS-232 *
RESERVED FOR
FUTURE USE
TB10
TB7
Aux
12VDC *
Reader 1*
Reader 2*
Door 1/2
Inputs*
Aux
12VDC*
}
TB9
Output 5/6 *
TB8
Host RS485+
Host RS485Common
LED/OUT 11
D0
D1
Common
+12VDC
Tamper/IN 9
Buzzer/OUT 15
LED/OUT 12
D0
D1
Common
+12VDC
Tamper/IN 10
Buzzer/OUT 16
Door1 REX/IN 1
Common
Door1 Status/IN 2
Door2 REX/IN 3
Common
Door2 Status/IN 4
Aux + 12VDC
Aux Common
Relay 1 N.O.
Relay 1 Com
Relay 1 N.C.
Relay 2 N.O.
Relay 2 Com
Relay 2 N.C.
Relay 3 N.O.
Relay 3 Com
Relay 3 N.C.
Relay 4 N.O.
Relay 4 Com
Relay 4 N.C.
}
AC
Output 7/8*
Input *
}
Ethernet
}
}
}
Door 3/4
Outputs*
Tamper Switch
RS-232
Host RS-485*
Ethernet*
Panel Tamper/IN 14
Common
ACFAIL/IN 13
Figure 33:
Power LED
47
NetAXS™ NX4S1 Installation
Maintenance
Notes:
• Maintain at least a .25-inch distance between the non-power limited wiring (battery
backup/charger wiring) and all other wiring, which is power-limited Class 2 wiring.
• If the default Door REX inputs are not properly terminated, their associated relay outputs
energize on restart.
8.0 Maintenance
Perform the following maintenance on the NetAXS™ enclosure:
• Change the CASIL CA1270 lead-acid battery (Honeywell Access Systems part number
3-000066) every two to two and a half years.
Caution: Do
not connect an uncharged battery to the panel.
• Oil the lock once per year.
9.0 Troubleshooting
Table 8 Troubleshooting Problems and Solutions
48
Problem
Solution
The panel
powers up, but it
does not respond
to any
communication,
cards reads, or
input activation.
Ensure that the Address DIP switches are set to a value other than zero.
Turn off the power (including battery), change the settings, and re-apply
the power.
No
communications
exist with the
Ethernet port.
Only a panel set to be a Gateway (DIP switch 6 = ON) will have
communications on the Ethernet port. If you need to use that port to
access the panel, turn off the power (including the battery), change the
switch setting, and reapply the power. Note that if the panel is normally
not a Gateway on a Multidrop communication bus, then the Host
RS-485 connection (TB7) should also be disconnected while DIP
switch 6 is ON. After completion of the Ethernet session, turn off the
power (including the battery), change the switch setting, re-connect the
Host RS-485 terminal block, and re-apply the power.
The IP address is
incorrectly set to
verify the value.
If you are connecting directly to a computer instead of going through a
router or hub, use a cross-over Ethernet cable.
The N1000
panels on the
Multidrop bus
do not report.
N1000 panels will not communicate to a NetAXS™ panel that is
configured as a Gateway. Replace all of the N1000 panels with
NetAXS™, or replace the Gateway panel with an N-485-PCI-2 device.
www.honeywell.com
NetAXS™ NX4S1 Installation
Technical Support
Table 8 Troubleshooting Problems and Solutions
Problem
Solution
The BAD CRC
counter is
incrementing
every minute.
Two or more panels on the Multidrop Bus have the same panel address.
Verify that each panel has a unique address setting on DIP switch
positions 1-5.
A dropline panel
in standalone
mode using
RS-232 may
unexpectedly fill
its buffer.
The preferred solution is to configure the standalone panel through the
Web server as a Gateway and use the board PCI and AckNak communications. This also gives the user a more secure and reliable communications line.
Another solution is to execute a new command that will allow the user
to turn the Tesla flow control off :
_U=<pn>_D (disable flow control)
This prevents the panels from inadvertently filling their buffers.
To turn the Tesla flow control back on:
_U=<pn>_E (enable flow control)
The NetAXS™ EOL network is AC-coupled. There is no resistance difference
between the RS-485 positive and negative terminals if the EOL network is on or off
(J36 and J37).
Note:
10.0 Technical Support
10.1 Normal Support Hours
Monday through Friday, 7:00 a.m. to 7:00 p.m. Central Standard Time (CST), except
company holidays: (800) 323-4576.
10.2 Web
For technical assistance please visit http://www.honeywellaccess.com
NetAXS Access Control Unit NX4S1 Installation Guide, Document 800-00008V3
49
NetAXS™ NX4S1 Installation
Technical Support
50
www.honeywell.com
NetAXS™ Standalone Operation
A
A.1 Basic Standalone Operations
A.1.1 Card Read / Door Lock Operation
1. Present a card to a reader.
2. The reader sends the card number to a reader input on the panel.
3. The panel searches its database and:
• If it is a valid card, then energize the door relay associated with the
particular reader input. The card is valid when it is in the card database
on the panel and the current time and date conforms to the time zone
associated with the card.
• If it is not a valid card, the door relay remains locked.
A.1.2 Door Egress / Door Lock / Door Status Operation
1. Activate the door egress input.
2. The panel energizes the door relay associated with the particular door egress
input for a default time of 10 seconds.
3. If the door status goes from close to open to close again during the 10 second
door open period, the door relay will be immediately de-energized.
NetAXS Access Control Unit NX4L1 Installation Guide, 800-00008V3
51
NetAXS™ Standalone Operation
Standalone Settings
A.2 Standalone Settings
A.2.1 NetAXS™ Panel Hardware Settings
• Configure the system with an RS-232 connection according to Figure 20 on
page 30.
• Set DIP switches 1 through 5 to define the panel number (see Table 3 on
page 22). Panel number 0 is not valid.
• Set DIP switch 6 to the OFF position to place the panel into the Multidrop
mode.
• Use a personal computer’s serial communications port (COM1 or COM2) and
a terminal emulation program to configure the NetAXS™ panel for normal
operation.
A.2.2 Communication Settings
•
•
•
•
•
Baud Rate: 115200
Data Bits: 8
Parity: None
Stop Bits: 1
Flow Control: None
A.2.3 Emulation Settings
• Echo typed characters locally: YES
• Line Delay: 500 milliseconds
A.2.4 Verifying Communications
1. Press the spacebar.
2. Press the carriage return <CR>. “S?” apppear for every online panel and
indicates proper communication between the terminal and panel.
52
www.honeywell.com
NetAXS™ Standalone Operation
Standalone Commands
A.3 Standalone Commands
Use the following commands, in the order they are listed, to configure the NetAXS™
panel.
1. T command: Sets the panel’s Time
2. D command: Sets the panel’s Date
3. L command: Creates Time zones for use by the cards
4. C command: Adds or Deletes cards from the panel
5. W command: Program each input for either NO/NC and Supervised or NON
Supervised operation
6. P command: Sets interlocks between input points and/or output points
In all examples, the underbar “_” indicates a “space” character and <CR>
indicates a carriage return.
Note:
A.3.1 T (Time) Command
_T=pn_hh:mm<CR>
Variables:
pn = panel number (1-31)
hh = hours (0-23) (Military time)
mm = minutes (00-59)
Example #1:
_T=1_08:30<CR>
This command would set panel 1 to a time of 8:30 AM.
Example #2
_T=6_18:15<CR>
This command would set panel 6 to a time of 6:15 PM.
NetAXS Access Control Unit NX4L1 Installation Guide, 800-00008V3
53
NetAXS™ Standalone Operation
Standalone Commands
A.3.2 D (Date) Command
_D=pn_mm/dd/yyyy_day<CR>
Variables:
pn = panel number (1-31)
mm = month number (1-12)
dd = day number (1-31)
yyyy = year number (ex 2007, 1999, etc.)
day = day of week (1-7):
1 = Monday
2 = Tuesday
3 = Wednesday
4 = Thursday
5 = Friday
6 = Saturday
7 = Sunday
The day of week setting is a hold-over from an old command. The panel using
the mm/dd/yyyy information will automatically configure panel to the correct day of
the week, regardless of the setting selected in day of week. But the command still
requires a value to be entered in its place of 1-7.
Note:
Example #1:
_D=1_01/09/2007_5<CR>
This command would set panel 1 to a date of 1/9/2007 and to Tuesday as the day of
the week.
Example #2:
_D=25_12/14/2009_7<CR>
This command would set panel 25 to a date of 12/14/2009 with a day of week being
Monday.
54
www.honeywell.com
NetAXS™ Standalone Operation
Standalone Commands
A.3.3 L (Time Zone) Command
_L=pn_tz_h1:m1-h2:m2_days<CR>
Variables:
pn = panel number (1-31)
tz = time zone number (1-255)
h1 = start time zone: hours (00-23) (Military time)
m1 = start time zone: minutes (00-59)
h2 = end time zone: hours (00-23) (Military time)
m2 = end time zone: minutes (00-59)
days = days of week valid values as listed below:
1 = Monday
2 = Tuesday
3 = Wednesday
4 = Thursday
5 = Friday
6 = Saturday
7 = Sunday
0 = Holiday 1
8 = Holiday 2
9 = Holiday 3
00:00 is the earliest time possible and 23:59 is the latest time possible. A single
time zone cannot be made to span mid-night, through the use of extended commands
we can simulate this. For more information, please seek the guidance of technical
support.
Note:
Example #1:
_L=5_10_08:00-17:00_1_2_3_4_5<CR>
This command would configure panel 5 to add a time zone entry to time zone number
10 ranging from 8AM to 5PM and would be valid during Monday, Tuesday,
Wednesday, Thursday, and Friday.
Example #2:
_L=25_45_16:00-23:59_0_6_7_8_9<CR>
This command would configure panel 25 to add a time zone entry to time zone
number 45 ranging from 4PM to 11:59PM and would be valid during Saturday,
Sunday, Holiday, 1, 2, and 3.
NetAXS Access Control Unit NX4L1 Installation Guide, 800-00008V3
55
NetAXS™ Standalone Operation
Standalone Commands
A.3.4 C (Card Add) Command
_C=pn_code_time zone_dev<CR>
Variables:
pn = panel number (1-31)
code = card number (range depends on card format)
time zone = time zone number the card will follow (1-255)
dev = device numbers card will work with, see below:
1 = card reader #1
2 = card reader #2
3 = card reader #3
4 = card reader #4
Example #1:
_C=6_12345_10_1_2_3_4<CR>
This command would configure panel 6 to add a card entry of 12345 to the panels
database, that will be valid on reader 1, 2, 3, and 4 during the times and days specified
by time zone 10.
Example #2
_C=18_52989_120_1_3<CR>
This command would configure panel 18 to add a card entry of 52989 to the panels
database, that will be valid on reader 1 and 3 during the times and days specified by
time zone 120.
A.3.5 C (Card Delete) Command
_C=pn_code<CR>
Variables:
pn = panel number (1-31)
code = card number (range depends on card format)
Example #1:
_C=6_12345<CR>
This command would remove card 12345 from panel 6.
Example #2
_C=18_52989<CR>
This command would remove card 52989 from panel 18.
56
www.honeywell.com
NetAXS™ Standalone Operation
Standalone Commands
A.3.6 W (Input) Command
_W=pn_input_{SO|SC|NO|NC}<CR>
Variables:
SO: Supervised normally open
SC: Supervised normally closed
NO: Non-supervised normally open
NC: Non-supervised normally closed (default)
Example:
_W=1_9_SO<CR>
Input 9 has been programmed as supervised, normally open on panel 1.
A.3.7 P (Interlock) Command
_P=pn_I/O_[number]_I/O[number]_{D|E|F|N|P}_
{D|E|F|N|P}<CR>
Parameters:
number: for an input number, the range is 1-96; for output, 0-78
D: De-energize
E: Energize
F: Follow
N: No action
P: Pulse
Example:
_P=1_I_5_O_3_E_D
When Input 5 is triggered, Output 3 energizes.
When Input 5 returns to its normal state, Output 3 de-energizes.
NetAXS Access Control Unit NX4L1 Installation Guide, 800-00008V3
57
NetAXS™ Standalone Operation
Standalone Commands
A.3.8 Flow Control Disable/Enable
(Use this command only for a dropline panel using RS-232 in standalone mode)
_U=[panel name]_{D|E}
Parameters:
D: Disable
E: Enable
Example:
_U=30_D
This disables the flow control on panel 30 and prevents the panel’s buffers from
filling. After a hard re-set of the panel, the flow control is re-enabled.
58
www.honeywell.com
NetAXS™ Standalone Operation
NetAXS™ Panel Defaults
A.4 NetAXS™ Panel Defaults
A.4.1 Reader Ports
The panel accepts a Wiegand serial data packet from the card reader. If the card is in
the database, the associated relay is activated. If the card is not in the database, the
relay state is unchanged.
The following are the default reader port to relay associations:
Reader Number
Controls...
1
Relay 1 (Output 1)
2
Relay 2 (Output 2)
3
Relay 3 (Output 3)
4
Relay 4 (Output 4)
A.4.2 Reader LED Outputs
The Reader LED output defaults to toggle the card reader LED from Red to Green for
two seconds when a valid card is presented. No LED color change (other then a
possible momentary change depending on reader used) occurs if the card is not in the
database.
The following are the default reader LED port to output associations:
Reader LED
Controls...
Reader 1
Output 11
Reader 2
Output 12
Reader 3
Output 13
Reader 4
Output 14
NetAXS Access Control Unit NX4L1 Installation Guide, 800-00008V3
59
NetAXS™ Standalone Operation
NetAXS™ Panel Defaults
A.4.3 Reader Tamper Inputs
The card readers have a Tamper signal wired to the NetAXS™ panel. This is a
two-state input configured as a Normally Closed contact.
The following are the default Reader Tamper Input to Panel Input associations:
Tamper LED
Reports as...
Tamper 1
Input 9
Tamper 2
Input 10
Tamper 3
Input 11
Tamper 4
Input 12
A.4.4 Door Egress Inputs
The panel has a Request-To-Exit (Egress) input for each door. The default condition is
a two-state input configured as Normally Closed contact. When the egress input is
active, the associated output relay will be active.
The following are the default egress input associations:
60
Egress input
Controls relay...
Panel input
Reports as...
1
1
SP1
Input 1
2
2
SP3
Input 3
3
3
SP5
Input 5
4
4
SP7
Input 7
www.honeywell.com
NetAXS™ Standalone Operation
NetAXS™ Panel Defaults
A.4.5 Door Status Inputs
The panel has a Door Status input for each door. The default condition is a two-state
input configured as a Normally Closed contact.
The following are the default door status input associations:
Door Status input
Panel input
Reports as...
1
SP2
Input 2
1
SP4
Input 4
1
SP6
Input 6
1
SP8
Input 8
A.4.6 ACFAIL and Panel Tamper Inputs
The panel has the following two additional generic inputs that can be used as generic
inputs or as either External Power Fail or Enclosure Tamper inputs. The default
condition is a two-state input configured as Normally Closed. Input 14 is a special
case, since it reports in as two inputs (inputs 14 and 20). Input 14 can be used as a
generic input, but input 20 is used for the Enclosure Tamper alarm. An active External
Power Fail input indicates that the system is operating from the battery current, not
from the primary input power. An inactive External Power Fail input indicates that the
system is operating from the primary input power.
Generic input
Panel input
Reports as...
Generic/External Power Fail
SP9
Input 13
Generic/Enclosure Tamper
SP10
Inputs 14 and 20
NetAXS Access Control Unit NX4L1 Installation Guide, 800-00008V3
61
NetAXS™ Standalone Operation
NetAXS™ Panel Defaults
A.4.7 Additional Generic Outputs
The panel has the following four additional generic form C relay outputs that can be
programmed using the P command:
62
Relay output
Controls...
5
Output 5
6
Output 6
7
Output 7
8
Output 8
www.honeywell.com
Honeywell Access Systems
135 W. Forest Hill Avenue
Oak Creek, WI 53154
United States
800-323-4576
414-766-1798 Fax
www.honeywellaccess.com
Specifications subject to change
without notice.
© Honeywell. All rights reserved.
Document 800-00008V3

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement