Bosch MX938I Installation instructions


Add to my manuals
4 Pages

advertisement

Bosch MX938I Installation instructions | Manualzz

Installation Instructions for the MX938i

Ceiling Mount Multiplex

PIR Intrusion Detector

1.0

Specifications

Input Power: Connects directly to the Multiplex Bus of the

Control Panel and optionally to an auxiliary

12 VDC source.

Current Draw:

2-Wire:

LED Off: < 350 µA draw on Mux Bus.

In Alarm; LED On: 2 mA draw on Mux Bus.

4-Wire:

LED Off: < 350 µA draw on Mux Bus.;

0 mA draw on Aux. power.

In Alarm; LED On: < 350 µA draw on Mux Bus;

3 mA draw on Aux. power.

Standby Power: There is no internal standby battery. Connect to DC power sources capable of supplying standby power if primary power fails. For each hour of standby time needed, 350 µAh are required. For UL Listed Requirements, four hours (1400 µAh) minimum are required.

Coverage:

Sensitivity:

Tamper:

Temperature:

360° by 60 ft. (18.3 m) diameter coverage when mounted on 8 to 18 ft. (2.4 to 5.5 m) high ceilings. Pattern consists of 64 zones grouped into 16 barriers, with one additional zone looking straight down from the unit

(sabotage). Each barrier is 30 ft. (9.2 m) long and 4.4 ft. (1.3 m) wide at 30 ft. (9.2 m).

Choice of two optical modules depending on ceiling height. For UL Listed

Requirements, the coverage is 360° by 54 ft.

(16.5 m) when mounted 10 to 13 ft. (3.1 m to

4.0 m) using the AR8-13 array and when mounted from 15 to 18 ft. (4.6 m to 5.5 m) using the AR13-18 array.

Selectable for Standard, Intermediate or High.

A tamper condition is signaled through the

Multiplex Bus and displays at the system keypads.

The storage and operating temperature range is -20°F to +120°F (-29°C to +49°C).

For UL Listed Requirements, the temperature range is +32°F to +120°F (0°C to 49°C).

Control Panel

Requirements:

Patents:

DS7400, DS7400X, or DS7400Xi Control

Panel with a DS7430 or DS7436 Multiplex

Expansion Module. DS7400 and DS7400X require ROM version 1.07 or greater. The

9000 Series Control/Communicators with

D8125MUX Module installed.

This device is covered under one or more of the following U.S. patents: #4,764,755,

#5,268,668, and #5,302,941.

2.0

Control Panel Programming

Refer to the multiplex programming section of your Control Panel

Reference Guide for information on programming multiplex zones for this device.

3.0

Mounting

Moving objects

Hot or cold air directed onto sensor

Rear Wire

Entrance

Wire

Tie-Downs (2)

Mounting

Slots (4)

Terminal

Strip

Interface

Pins

Mounting Base

Avoid

Mounting Outdoors

Pets or animals

Module Tabs (2)

AR8-13

Moisture

Direct or reflected sunlight

Walk Test/Alarm

LED Indicator (3)

Terminal

Strip

Sensitivity

Jumper

Signal

Gain

Jumper Optical Module with Cutaway to show Circuit

Board detail

LED

Operation

Jumper

Address

Switches

Top View of Enclosure with Cover Removed

Cover

Tamper

IMPORTANT

The mounting surface should be solid and vibration free

(i.e., drop tiles should be secured if the area above the tiles is used as an air return for HVAC systems).

• Select a location that is most likely to intercept an intruder moving across the coverage pattern. The recommended mounting height range is 8 to 18 ft. (2.4 to 5.5 m).

• Remove the cover by turning counterclockwise.

• Remove the base from the enclosure by pressing the two enclosure release tabs inward while lifting the enclosure away from the base.

Hint: Slightly rock the enclosure side-to-side during removal, to overcome the friction caused by base-to-enclosure terminal pins.

• Route wiring as necessary to the rear of the base and through the center hole.

Be sure all wiring is unpowered (de-energized) before routing.

• Securely attach the base. Depending on local regulations, the base may be directly surface mounted using anchors, mollies or wing-nuts, or may be mounted to standard four-inch octagonal and square electrical boxes.

NOTE: The MX938i base will not completely cover a four-inch square box. Where aesthetics are important, a four-inch octagonal box is recommended.

Hint: Mounting to removable ceiling tiles is not recommended unless a sandwich is made of the base, ceiling tile and a back plate behind the tile. Covers used for four-inch octagonal and square boxes make a suitable back plate

(when used with bolts and wing nuts, as an example).

• Replace the enclosure on the base.

• Select an Optical Module (AR8-13 or AR13-18).

- For ceilings between 8 and 13 ft. (2.4 m and 4.0 m) from the floor, use the optical module marked AR8-13. This marking can be found next to the two optical module tabs. For ceilings between 13 and 18 ft. (4.0 m and 5.5 m) high, use the optical module marked AR13-18.

- To replace an optical module, push the optical module tabs toward the center until the module snaps free of the circuit board. Holding the new module by the tabs, snap the new module into place.

Avoid fingerprints on the mirrored surfaces. If the mirrored surfaces become soiled or otherwise marked, they can be cleaned using a soft, clean cloth and any commonly available mild window cleaner.

4.0

Wiring

Only apply power after all connections have been made and inspected.

MUX

BUS

AUX

POWER

• Connect wiring as shown.

B+

IN

B-

IN

+

IN

-

IN

1 2 3 4

NOTE: Do not coil excess wiring inside unit.

• Seal the Wire Entrance using the foam plug provided.

Terminal Descriptions

1 (B+) and 2 (B-): Connect to the Multiplex Bus of the control panel. Use no smaller than #22 AWG (0.8 mm) wire between the detector and the control panel.

3 (+) and 4 (-): Connect to the AUX Power of the control panel.

This connection is only required if LED operation (other than during the walk test) is required. Use no smaller than #22 AWG

(0.8 mm) wire between the detector and the control panel.

5.0

Configuration Jumpers

Configure the detector using the appropriate Configuration Jumper settings (refer to the following diagram for jumper locations).

Sensitivity

Jumper

Signal

Gain

Jumper

(located under the mirror)

LED

Operation

Jumper

Address

Switches

5.1

LED Operation Jumper

ON: Allows the LED to operate when activated by alarm.

OFF: The LED will not operate on alarm.

On

If the detector is powered by the MUX Bus only,

the LED is for Walk Test purposes only. Disable the LED when Walk Testing is complete. To

OFF

ON

OFF

ON disable the LED, place the jumper in the OFF position.If the detector has AUX Power

Off

supplied, the LED operation may be left ON during normal use.

5.2

Sensitivity Mode

Standard Sensitivity: Recommended setting for maximum false alarm immunity. Tolerates environment extremes on this setting, but requires the largest amount of intruder motion to achieve an alarm.

Standard

H

I

S

Intermediate Sensitivity: Recommended setting for any location where an intruder is expected to cover only a small portion of the protected area. Tolerates normal environments on this setting. This setting will improve your intruder catch performance.

Intermediate

H

I

S

High Sensitivity: Fast response to intruder signals.

For use in quiet environments where thermal and illumination transients are not anticipated.

High

H

I

S

5.3

Signal Gain

NOTE: The MX938i permits selection of the signal gain depending upon the environment to be protected. The gain select jumper is located under the optical module.

High Gain: Recommended for large coverage applications up to 60 ft. (18.3 m) in diameter. The

MX938i is shipped in this setting. If the gain jumper is missing, it will default to high gain.

Low Gain: Recommended for applications where the area to be covered is 40 ft. (12.2 m) or less in diameter and for applications where the High Gain setting may be too sensitive for environmental extremes.

High Gain

HI

LO

Low Gain

HI

LO

NOTE: Setting the MX938i for the LOW Signal Gain setting reduces the Coverage area to 40 ft. (12.2 m) in diameter.

6.0

Address Switch Settings

• Set the address switch settings (see page 3) before connecting the MX938i to the multiplex bus.

IMPORTANT

No two devices may be set to the same address. Having two or more units set to the same address may prevent fault detection or cause multiplex bus failure.

• You can find the Address Switch Settings using the chart on page 3, or by calculating the decimal number of the address.

O

N

1 2 3 4 5 6 7 8

IMPORTANT

128 64 32 16 8 4 2 1

Binary Switch Values (Point 17 shown)

Zone (Point) Addresses 001 through 008 are reserved for

"on board" points on the DS7400(Xi) Series control panels.

Do not set any multiplex devices for Addresses 001-

008 when using a DS7400(Xi) Series control panel.

Page 2 © 2004 Bosch Security Systems MX938i Installation Instructions

ZONE

(POINT)

ADDRESS

= SWITCH ON

(CLOSED)

SWITCH NUMBER

1 2 3 4 5 6 7 8

047

048

049

050

051

052

053

040

041

042

043

044

045

046

034

035

036

037

038

039

027

028

029

030

031

032

033

054

055

056

057

058

059

060

061

062

063

064

020

021

022

023

024

025

026

013

014

015

016

017

018

019

006

007

008

009

010

011

012

001

002

003

004

005

ZONE

(POINT)

ADDRESS

= SWITCH ON

(CLOSED)

SWITCH NUMBER

1 2 3 4 5 6 7 8

111

112

113

114

115

116

117

104

105

106

107

108

109

110

098

099

100

101

102

103

091

092

093

094

095

096

097

118

119

120

121

122

123

124

125

126

127

128

084

085

086

087

088

089

090

077

078

079

080

081

082

083

070

071

072

073

074

075

076

065

066

067

068

069

MX938i Installation Instructions © 2004 Bosch Security Systems

ZONE

(POINT)

ADDRESS

= SWITCH ON

(CLOSED)

SWITCH NUMBER

1 2 3 4 5 6 7 8

175

176

177

178

179

180

181

168

169

170

171

172

173

174

162

163

164

165

166

167

155

156

157

158

159

160

161

182

183

184

185

186

187

188

189

190

191

192

148

149

150

151

152

153

154

141

142

143

144

145

146

147

134

135

136

137

138

139

140

129

130

131

132

133

ZONE

(POINT)

ADDRESS

= SWITCH ON

(CLOSED)

SWITCH NUMBER

1 2 3 4 5 6 7 8

239

240

241

242

243

244

245

232

233

234

235

236

237

238

226

227

228

229

230

231

219

220

221

222

223

224

225

246

247

248

249

250

251

252

253

254

255

212

213

214

215

216

217

218

205

206

207

208

209

210

211

198

199

200

201

202

203

204

193

194

195

196

197

Page 3

7.0

Setup and Walk Testing

Before walk testing, the system should be fully wired, powered, and programmed.

IMPORTANT

• Configure LED Configuration Switch (S1) to LED ON.

• Replace the front cover.

NOTE: All testing must be performed with the front cover in place.

• Wait at least 2 minutes (with no motion in the coverage area) for the detector to setup.

• Walk test across the coverage pattern.

• The edge of the coverage is determined by activation of the LED.

• Walk test the unit from both directions to determine the boundaries.

On 2-wire systems, configure the LED to OFF when finished with walk tests.

IMPORTANT

8.0

Maintenance

• The range and coverage should be checked in accordance with the Walk Testing section (6.0) on a regular basis.

• Consult the Control Panel’s User's Guide for the procedure on performing a zone test. Performing a zone test on a regular basis assures an alarm output prior to arming the system.

• Excessive handling of the mirror surfaces may lead to performance degradation.

9.0

Coverage Patterns

• Refer to the mirror module and pattern drawings for masking information.

• Before masking, be sure the chosen mirror surface is the correct one. When removing masking, remember, many adhesives will either destroy the mirror’s surface or leave residue behind to reduce coverage performance.

30

9 Meters 6 3

TOP VIEW

0 3 6

0

20

10

10

9

30

20

AR13-18 SIDE VIEW (Cross Section of 2 Opposite Zones)

15

9 Meters 6 3 0 3

10

6

10

0

30 Feet 20 10 0 10

0

10

AR8-13 SIDE VIEW (Cross Section of 2 Opposite Zones)

10

9 Meters 6 3 0 3

20

6

9

4.5

3

30

0

9

3

20

30

9 Meters 6 3 0 3 6

20 0

30 Feet 20

9

30

10 0 10 20 30

0

© 2004 Bosch Security Systems

130 Perinton Parkway, Fairport, New York, USA 14450-9199

Customer Service: (800) 289-0096; Technical Support: (888) 886-6189

03/04

MX938i Installation Instructions

P/N: 45988F Page 4

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Frequently Answers and Questions

What is the input power required for the Bosch Appliances MX938i?
The MX938i connects directly to the Multiplex Bus of the Control Panel and optionally to an auxiliary 12 VDC source.
What are the Current Draw specifications for the MX938i?
2-Wire: ≤ 350 µA draw on Mux Bus. 4-Wire: ≤ 350 µA draw on Mux Bus.; 3 mA draw on Aux. power.
What is the Standby Power requirement for the MX938i?
There is no internal standby battery. Connect to DC power sources capable of supplying standby power if primary power fails. For each hour of standby time needed, 350 µAh are required.
What is the Coverage range of the MX938i?
360° by 60 ft. (18.3 m) diameter coverage when mounted on 8 to 18 ft. (2.4 to 5.5 m) high ceilings.
What are the Sensitivity options for the MX938i?
Selectable for Standard, Intermediate or High.
How does the MX938i indicate Tampering?
A tamper condition is signaled through the Multiplex Bus and displays at the system keypads.
What are the Temperature Range requirements for the MX938i?
The storage and operating temperature range is -20°F to +120°F (-29°C to +49°C). For UL Listed Requirements, the temperature range is +32°F to +120°F (0°C to 49°C).
Which Bosch models require the MX938i to be installed?
DS7400, DS7400X, or DS7400Xi Control Panel with a DS7430 or DS7436 Multiplex Expansion Module.

advertisement