The Static Switch Product Line
SSW 230V-6kVA →
SSW 230 V – 20 kVA →
Description:
The static switch product line is a micro-controller driven state-of-the-art switch between the AC mains and the inverter to provide uninterruptible AC power. After an extremely quick detection of a mains fault, the static switch transfers the load almost without cut off to the redundant AC line. A communication and synchronization bus is responsible for the system performance and the
Delta inverters are synchronized to the public AC mains.
Modular UPS configurations in ON LINE or OFF LINE mode can be realized in combination with Delta inverters and DC power systems with battery backup.
Features
Specification
• Two static switch models 6 kVA and 20 kVA
• 230 Vrms / 50 Hz single phase
• ON LINE or OFF LINE mode selection
• High performance AC line quality monitoring
• Quick detection of AC faults
• Configurable switching criteria
• Load transfer of up to 6 kVA or 20 kVA
• Synchronization of the Delta inverter group
• Convection cooled
• Compact and light
• Power connectors on the rear
General
Product name SSW 230 V – 6 kVA
SSW 230 V – 20 kVA
Safety EN 60 950, class I
EMI, radiated compliant with EN 55 022, class B
300
Cooling Convection cooled
Public AC Input
Voltage range 184 ... 276 V rms
Frequency range 45 - 55 Hz
EMI, conducted compliant with EN 55022, class B
Inverter AC Input
Voltage range 230 V rms
± 1%
Frequency 50 Hz
EMI, conducted compliant with EN 55022, class B
AC Output
Voltage, nominal
Frequency, nominal
Maximum power cosφ, range
230 V rms
50 Hz
6 kVA / 20 kVA
0 .. 1 ind. and cap.
EMI, conducted compliant with EN 55022, class B
Mechanics 6kVA ; 20kVA
Width, overall
Depth, overall
Height, overall
Weight
2.8” / 70 mm ; 5.3” / 135 mm
13.8” / 350 mm ; 13.8” / 350 mm
12.2” / 311 mm ; 12.2” / 7U / 311 mm
7.7 lb / 3.5 kg ; 18.0 lb / 8.6 kg
Switching Criteria
According to
Static rms deviation
Dynamic rms deviation
Static freq. deviation
Dynamic freq. deviation
ETS 300 132-1
± 10 %
± 15 % for max. 500 ms
± 2Hz
± 2Hz for 5 s maximum
Environment
Operating temperature 0 ... + 50 °C
Relative humidity 95 % max, non condensing