Emerson CF110BS00 Owner's Manual
Add to my manuals
16 Pages
Emerson CF110BS00 is a 48-inch ceiling fan with a brushed steel finish. It has five reversible blades, which means you can change the direction of the airflow to suit your needs. The fan also comes with a remote control, so you can adjust the speed and direction of the airflow from anywhere in the room. The Emerson CF110BS00 is a great choice for any room in your home, and it's backed by a 1-year warranty. Here are some of the features and benefits of the Emerson CF110BS00:
- Five reversible blades for customizable airflow
- Remote control for easy operation
- Brushed steel finish for a modern look
advertisement
READ AND SAVE THESE INSTRUCTIONS
CALLAN
™
48” Ceiling Fan Owner's Manual
Model Numbers
CF110BS00 -
Brushed Steel
CF110ORB00 -
Oil Rubbed Bronze
Net Weight:
23.7
Lbs.
Part No. F40BP74660000
11/12
Questions, problems, missing parts: Before returning to the store call
Emerson Electric Customer Service
8 a.m. - 6 p.m., EST, Monday-Friday
1-800-654-3545 www.emersonfans.com
Form No. BP7466
ETL Model No.: CF110
READ AND SAVE THESE INSTRUCTIONS
Safety Instructions
!
WARNING
TO REDUCE THE RISK OF FIRE, ELECTRICAL SHOCK,
OR INJURY TO PERSONS, OBSERVE THE
FOLLOWING: a. Use this unit only in a manner intended by the manufacturer. If you have questions, contact the manufacturer.
b. Before servicing or cleaning unit, switch power off at service panel and lock service panel disconnecting means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a warning device, such as a tag, to the service panel.
1. Read your owner’s manual carefully and keep it for future reference.
2. Be careful of the fan and blades when cleaning, painting, or working near the fan. Always turn off the power to the ceiling fan before servicing.
3. Do not put anything into the fan blades while they are turning.
4. Do not operate reversing switch until fan blades have come to a complete stop.
Additional Safety Instructions for Installation
1. To avoid possible shock, be sure electricity is turned off at the fuse box before wiring, and do not operate fan without blades.
2. All wiring must be in accordance with the National
Electrical Code “ANSI/NFPA 70-2011” and Local
Electrical Codes. Use the National Electrical Code if
Local Codes do not exist. The ceiling fan must be grounded as a precaution against possible electrical shock. Electrical installation should be made or approved by a licensed electrician.
3. The outlet box and joist must be securely mounted and capable of reliably supporting at least 50 pounds.
Use only U.L. outlet boxes listed as “Acceptable for
Fan Support of 15.9kg. (35 lbs.) or less”., and use the mounting screws provided with the outlet box. Most outlet boxes commonly used for support of light fixtures are not acceptable for fan support and may need to be replaced. Consult a qualified electrician if in doubt.
4. The downrod furnished with the fan proves the minimum recommended floor to fan blade clearance for an 8 foot ceiling.
5. The fan must be mounted with the fan blades at least 7 feet from the floor to prevent accidental contact with the fan blades.
6. Follow the recommended instructions for the proper method of wiring your ceiling fan. If you do not know enough about electrical wiring, have your fan installed by a licensed electrician.
WARNING: To reduce the risk of electrical shock, this fan must be installed with an isolating wall control/switch.
NOTE: This fan is suitable for use with solid-state speed controls.
WARNING: To reduce the risk of fire or electrical shock, this fan should only be used with fan speed control,
Model No. UC9020, manufactured by Rhine Electric Co.,
Ltd.
WARNING: This product is designed to use only those parts supplied with this product and/or any accessories designated specifically for use this product by Emerson
Electric Co. Substitution of parts or accessories not designated for use with this product by Emerson could result in personal injury or property damage.
WARNING: To reduce the risk of personal injury, do not bend the blade flange when installing the blade flanges, balancing the blades or cleaning the fan. Do not insert foreign objects in between rotating fan blades.
WARNING: To reduce the risk of electrical shock, this fan must be installed with a general use, isolating control/switch.
NOTE: All setscrews must be checked and re-tightened where necessary before installation.
DATE CODE:
The date code of this fan may be found on the box, stamped in ink on a white label. You should record this data above and keep it in a safe place for future use.
2 ETL Model No.: CF110
Unpacking Instructions
!
WARNING
Do not install or use fan if any part is damaged or missing. Call Toll-Free:
1-800-654-3545
!
WARNING
This product is designed to use only those parts supplied with this product and/or any accessories designated specifically for use with this product by
Emerson Electric Co. Substitution of parts or accessories not designated for use with this product by Emerson Electric Co. could result in personal injury or property damage.
PACKAGE CONTENTS
Part Description
A Fan Motor Assembly
B Ceiling Canopy
C Coupler Cover
D Blade Flanges
E Fan Blades
F Hanger Bracket
G Hanger Ball/Downrod Assembly
H Upper Glass Retainer
I Glass Shade
J Lower Glass Retainer
K Finial
L SW46 Wall Control/Cover Plate
1.
Check to see that you have received the following parts:
NOTE: If you are uncertain of part description, refer to exploded view illustration.
HARDWARE CONTENTS
Part Description
1 Threaded Studs, #8-32 x 1-1/4”
2 Knurled Knobs, #8-32
3 Lockwashers, #8
4 Wire Connectors, Type E3
5 Clevis Pin
6 Hairpin Clip
7 Flange Screw (Spare), 1/4-20 x 1/2”
8 Washer, Paper #10
9 #10-32 x 5/16” Slotted Phillips Washer
Head Blade Screws
10 Blade Balance Kit
Quantity
2
2
2
3
1
21
1
1
21
1
B
A
C
D
E
4
3
2
1
0
7
1
4
8
2
5
9
6
3
10
H
I
L
3
NOTE: Place the parts from the loose parts bags in a small container to keep them from being lost. If any parts are missing, contact your local retailer or catalog outlet for replacement before proceeding.
2.
Remove the fan assembly from the protective plastic bag. Place the fan assembly into the upper foam pad with the bottom of the motor facing up.
The upper foam pad serves as a holder for the fan during the first stages of assembly.
emersonfans.com
Please contact 1-800-654-3545 for further assistance
ETL Model No.: CF110
Quantity
1
1
1
5
1
1
5
1
1
1
1
1
K
J
F
G
This Manual Is Designed to Make it as Easy as Possible for You to Assemble,
Install, Operate and Maintain Your Ceiling Fan
Tools Needed for Assembly
One Phillips head screwdriver
One 1/4” blade screwdriver
One stepladder
One wire stripper
Materials
Wiring outlet box and box connectors must be of type required by the local code. The minimum wire would be a 3-conductor (2-wire with ground) of following size:
Installed Wire Length
Up to 50 ft.
50-100 ft.
Wire Size A.W.G.
14
12
!
WARNING
Before assembly your ceiling fan, refer to section on proper method of wiring your fan (page 9). If you feel you do not have enough wiring knowledge or experience, have your fan installed by a licensed electrician.
Ceiling Fan Assembly
1.
Remove one of the motor housing screws and retain for future use. Loosen the remaining three motor housing screws for assembly of the lower glass retainer (Figure 1).
MOTOR HOUSING
MOTOR HOUSING
SCREWS
2.
Place the lower glass retainer onto the motor housing and engage the key holes of the retainer onto the three motor housing screws. Rotate the lower glass retainer clockwise and tighten the three motor housing screws. Reinstall the motor housing screw
(previously removed) into the remaining hole of the lower glass retainer and tighen all screws securely
(Figure 2).
Figure 1
MOTOR HOUSING
SCREWS
LOWER GLASS
RETAINER
!
WARNING
To reduce the risk of personal injury, do not bend the blade flange when installing the blade flanges, balancing the blades or cleaning the fan. Do not insert foreign objects in between rotating fan blades.
3.
Mount blade flange to fan blade using four
#10-32 x 5/16” slotted Phillips washers head screws and four paper washers (Figure 3). Repeat this procedure for the remaining four blades and flanges.
Figure 2
ROTATE LOWER
GLASS RETAINER
CLOCKWISE
#10-32 x 5/16" SLOTTED
PHILIPS WASHER HEAD
SCREWS (4 per blade assembly)
#10 PAPER WASHERS (4 per blade assembly)
FAN BLADE
BLADE
FLANGE
Figure 3
4 ETL Model No.: CF110
NOTE: Take care not to scratch fan housing when installing blades.
4.
Attach the flange/blade assembly to the motor hub using the two pre-installed 1/4-20 x 1/2” flange screws and lockwashers. Make sure the screws are tightened securely (Figure 4). Repeat this procedure for the other four blade assemblies.
5.
Screw the finial onto the center threaded stud of the motor housing until securely tighten (Figure 5).
6.
Carefully turn the partially assembled fan right side up in preparation of final installation. Rest the fan motor housing onto the packing styrofoam, being careful not to bend the blades.
7.
Carefully place the glass shade over the fan motor housing, resting it into the lower glass retainer.
Orintate the glass shade so that the larger lip is resting in the lower glass retainer per Figure 6.
8.
Remove the four knurled retainer screws from the motor housing and retain for future use.
9 . Align the four holes of the upper glass retainer onto the fan motor housing and reinstall the four knurled retainer screws (previously removed). Securely tighten all four screws (Figure 7).
FLANGE/BLADE ASSEMBLY
1/4-20 x 1/2" FLANGE SCREWS WITH
LOCKWASHERS PRE-ASSEMBLED (2)
MOTOR HUB
Figure 4
FINIAL
Figure 5
FAN MOTOR HOUSING
GLASS SHADE
Figure 6
KNURLED RETAINER
SCREW (4)
UPPER GLASS
RETAINER
LOWER GLASS
RETAINER
FAN MOTOR HOUSING
5
Figure 7 emersonfans.com
Please contact 1-800-654-3545 for further assistance
ETL Model No.: CF110
9.
Remove the hanger ball by loosening the setscrew in the hanger ball until the ball falls freely down the downrod (Figure 8). Remove the pin from the downrod, then remove the hanger ball. Retain the pin and hanger ball for reinstallation in Step 14.
10.
Separate, untwist and unkink the two 80” motor leads. Route the motor lead wires through the downrod. Align the clevis pin holes in the downrod with the holes in the motor coupler. Install the clevis pin and secure with the hairpin clip (Figure 9). The clevis pin must go through the holes in the motor coupler and the holes in the downrod. Be sure to push the straight leg of the hairpin clip through the hole near the end of the clevis pin until the curved portion of the hairpin clip snaps around the clevis pin. The hairpin clip must be properly installed to prevent the clevis pin from working loose. Pull on the downrod to make sure the clevis pin is properly installed.
!
WARNING
It is critical that the clevis pin in the motor coupler is properly installed and the setscrew securely tightened.
Failure to verify that the pin and setscrew are properly installed (as shown in Figure 9) could result in the fan falling.
11.
While pulling up on the downrod, securely tighten the two setscrews in the motor coupler.
12.
Make sure the grommet is properly installed in the coupler cover, then slide the coupler cover on the downrod until it rests on the motor housing
(Figure 10).
13.
Place the ceiling cover over the downrod. Be sure that the ceiling cover and the coupler cover are both oriented correctly (Figure 11).
HANGER BALL
Figure 8
SETSCREW
SETSCREW
CLEVIS PIN
JAM NUT
MOTOR
COUPLING
CLEVIS PIN
MOTOR
COUPLING
HAIRPIN
CLIP
Figure 9
UPPER GLASS
RETAINER
DOWNROD
GROMMET
Figure 10
CEILING
COVER
PIN
DOWNROD
DOWNROD
HAIRPIN CLIP
SETSCREW
COUPLER
COVER
DOWNROD
COUPLER
COVER
6
Figure 11
ETL Model No.: CF110
14.
Reinstall the hanger ball (Figure 12) on the downrod as follows. Route the three 80” motor leads through the hanger ball. Position the pin through the two holes in the downrod and align the hanger ball so the pin is captured in the groove in the top of the hanger ball. Pull the hanger ball up tight against the pin and securely tighten the setscrew in the hanger ball. A loose setscrew could create fan wobble.
!
WARNING
It is critical that the pin in the hanger ball is properly installed and the setscrew securely tightened. Failure to verify that the pin and setscrew are properly installed could result in the fan falling.
15.
The fan comes with black and white leads that are
80-inches long. Before installing the fan, measure up approximately 6 to 9-inches above top of hanger ball/downrod assembly. Cut off excess leads and strip back insulation 1/2-inch from end of leads.
16.
You have now completed the assembly of your new ceiling fan. You can now proceed with hanging and wiring your fan.
HANGER
BALL
CEILING
COVER
SETSCREW
Figure 12
PIN
DOWNROD
Electrical Requirements
Your new ceiling fan will require a grounded electrical supply line of 120 volts AC, 60 Hz, 15 amp circuit.
!
WARNING
Turning off wall switch is not sufficient. To avoid possible electrical shock, be sure electricity is turned off at the main fuse box before wiring. All wiring must be in accordance with National and Local codes and the ceiling fan must be properly grounded as a precaution against possible electrical shock.
CAUTION: To reduce the risk of electrical shock, disconnect the electrical supply circuit before installing the fan, light kit or receiver.
The outlet box must be securely anchored and capable of withstanding a load of at least 50 pounds.
If your fan is to replace an existing ceiling light fixture, turn electricity off at the main fuse box at this time and remove the existing light fixture.
!
WARNING
To avoid fire or shock, follow all wiring instructions carefully.
Any electrical work not described in these instructions should be done or approved by a licensed electrician.
!
WARNING
To reduce the risk of fire, electric shock, or personal injury, mount fan to outlet box marked “Acceptable for
Fan Support of 15.9kg. (35 lbs.) or less”, and use screws supplied with outlet box. Most outlet boxes commonly used for support of light fixtures are not acceptable for fan support and may need to be replaced. Consult a qualified electrician if in doubt.
7 emersonfans.com
Please contact 1-800-654-3545 for further assistance
ETL Model No.: CF110
How to Hang Your Ceiling Fan
!
WARNING
Turning off wall switch is not sufficient. To avoid possible electrical shock, be sure electricity is turned off at the main fuse box before wiring. All wiring must be in accordance with National and Local codes and the ceiling fan must be properly grounded as a precaution against possible electrical shock.
CAUTION: To reduce the risk of electrical shock, disconnect the electrical supply circuit before installing the fan, light kit or receiver.
!
WARNING
The fan must be hung with at least 7' of clearance from floor to blades (Figure 13).
AT LEAST
7'
Figure 13
CEILING
FLOOR
!
WARNING
The outlet box and joist must be securely mounted and capable of supporting at least 50 lbs. Use only a U.L.
outlet box listed as “Acceptable for Fan Support of
15.9kg. (35 lbs.) or less”.
!
WARNING
To reduce the risk of fire, electric shock, or personal injury, mount fan to outlet box marked “Acceptable for
Fan Support of 15.9kg. (35 lbs.) or less”, and use screws supplied with outlet box. Most outlet boxes commonly used for support of light fixtures are not acceptable for fan support and may need to be replaced. Consult a qualified electrician if in doubt.
1.
Securely attach the hanger bracket to the outlet box using the two screws supplied with the outlet box.
(Figure 14.)
!
WARNING
Hanger bracket must seat firmly against outlet box. If the outlet box is recessed, remove wall board until bracket contacts box. If bracket and/or outlet box are not securely attached, the fan could wobble or fall.
2.
Carefully lift the fan and seat the hanger ball/ downrod assembly on the hanger bracket that was just attached to the outlet box (Figure 15). Be sure the groove in the ball is lined up with tab on the hanger bracket (Figure 14).
!
WARNING
Failure to seat tab in groove could cause damage to electrical wires and possible shock or fire hazard.
TWO SCREWS
SUPPLIED WITH
OUTLET BOX
Figure 14
OUTLET
BOX
TAB
HANGER
BRACKET
NOTE: CEILING COVER, SUPPLY WIRES AND FAN WIRES OMITTED
FOR CLARITY.
OUTLET
BOX
HANGER
BRACKET
HANGER BALL/
DOWNROD
ASSEMBLY
Figure 15
!
WARNING
To avoid possible fire or shock, do not pinch wires between the hanger ball/downrod assembly and hanger bracket.
8
ETL Model No.: CF110
How to Wire Your Ceiling Fan
If you feel that you do not have enough electrical wiring knowledge or experience, have your fan installed by a licensed electrician.
1.
Connect the green grounding lead from the hanger ball and the green grounding lead from the hanger bracket to the grounding conductor of supply (this may be a bare wire or wire with green colored insulation). Securely connect wires with wire connectors supplied. (Figure 16.)
GROUND
WIRE
LISTED
WIRE
CONNECTOR (3)
BLACK FAN WIRE
!
WARNING
To avoid possible electrical shock, be sure electricity is turned off at the main fuse box before wiring.
NOTE: If you are not sure if the outlet box is grounded, contact a licensed electrician for advice, as it must be grounded for safe operation.
GREEN WIRE
(GROUND) FROM
HANGER BRACKET
GREEN WIRE
(GROUND) FROM
HANGER BALL
Figure 16
WHITE SUPPLY
(NEUTRAL)
WHITE FAN
WIRE
BLACK SUPPLY
(HOT)
NOTE: CEILING COVER
OMITTED FOR CLARITY.
!
WARNING
This product is designed to use only those parts supplied with this product and/or any accessories designated specifically for use with this product by
Emerson Electric Co. Substitution of parts or accessories not designated for use with this product by Emerson Electric Co. could result in personal injury or property damage.
2.
Securely connect the fan motor white wire to the supply white (neutral) wire using wire connector supplied (Figure 16). Securely connect the fan motor black wire and blue wire to the supply black (hot) wire using wire connector supplied (Figure 16). After connections have been made, turn leads upward and carefully push leads into the outlet box, with the white and green leads on one side of the outlet box and the black lead on the other side of the outlet box.
!
WARNING
Check to see that all connections are tight, including ground, and that no bare wire is visible at the wire connectors, except for the ground wire. Do not operate fan until blades are in place. Noise and fan damage could result.
3.
Screw the two threaded studs (supplied) into the tapped holes in the hanger bracket.
4.
Lift the ceiling cover up to the threaded studs and turn until studs protrude through the holes in the ceiling cover (Figure 17).
CEILING
COVER
LOCKWASHERS (2)
THREADED STUD (2)
KNURLED KNOB (2)
Figure 17
5.
Secure the ceiling cover in place by sliding lockwashers over the threaded studs and installing the two knurled knobs (supplied). (Figure 17.)
Tighten the knurled knobs securely until the ceiling cover fits snugly against the ceiling and the hole in the ceiling cover is clear of the downrod. Your fan is now wired to be turned on and off from the fan switch.
!
WARNING
To avoid possible fire or shock, make sure that the electrical wires are completely inside the outlet box and not pinched between the ceiling cover and the ceiling.
9 emersonfans.com
Please contact 1-800-654-3545 for further assistance
ETL Model No.: CF110
Wall Control Installation
!
WARNING
Turning off wall switch is not sufficient. To avoid possible electrical shock, be sure electricity is turned off at the main fuse box before wiring. All wiring must be in accordance with National and Local codes and the ceiling fan must be properly grounded as a precaution against possible electrical shock.
CAUTION: To reduce the risk of electrical shock, disconnect the electrical supply circuit before installing the fan, light kit or receiver.
This control is designed to operate only one ceiling fan,
(Figure 18). This SW46 speed control is rated for 1.2
amps at 120 volts..
1.
Before disconnecting power, ensure that the fan is set at the highest speed.
NOTE: Electric connections should be in accordance with the National Electrical Codes and all Local Codes. Before starting, disconnect power to the circuit at the fuse box or circuit breaker panel.
2.
Remove the faceplate and screws from the existing wall switch. Pull switch out from wall outlet box.
3.
Disconnect wire from existing fan wall switch (Figure
19).
4.
Slide the SW46 speed control in the OFF position (0).
5.
Connect one BLACK wire from the SW46 speed control to the fan/motor lead with a wire connector
(provided). (Figure 20.)
6.
Connect the other BLACK wire from the SW46 speed control to the 120VAC hot wire with a wire connector
(provided).
NOTE: Use wire connectors (supplied) to secure electrical connections.
7.
Attach the SW46 speed control to the wall outlet box with two 6-32 x 3/4” screws (provided).
Figure 18
Figure 19
TO NEUTRAL
4
3
2
1
0
FACEPLATE
SWITCH
TO FAN MOTOR LOAD
MOTOR LOAD
1.2 AMP MAXIMUM
WALL
OUTLET
BOX
2
1
0
4
3
BLACK
BLACK
Figure 20
TO
120VAC
SOURCE
HOT
10 ETL Model No.: CF110
8.
Position the faceplate (provided) onto the SW46 speed control. Using the two 6-32 x 1/4” screws, screw the faceplate and speed control to the wall outlet box (Figure 21).
9.
Restore power at the main fuse box or circuit breaker panel.
CAUTION
For fans equipped with built-in variable speed devices: These devices must be set at their
MAXIMUM SPEED for proper operation.
Adjustments to their setting must only be made with
Quietslide in the OFF position. Changing or sliding these settings while the fan control is in operation could damage the control.
Set the fan on its HIGH speed pull chain setting. Then use your speed control to select any of the
4-speeds, plus OFF.
NOTE: The “0” position is OFF. The four fan speeds are selected by sliding the bar to the other four speed positions (“1”, “2”, “3” and “4”).
IMPORTANT
Always have the fan switch set to HIGH speed before using the wall control. To avoid accidental pull chain use, shorten chain by cutting it 1” below switch body.
The SW46 speed control turns all Emerson Ceiling Fans into four-speed fans.
SW46 SPEED CONTROL
OUTLET BOX
4
1
0
3
2
6-32 x 3/4" SCREW (2)
Figure 21
6-32 x 1/4" SCREW (2)
FACEPLATE
Using Your Ceiling Fan
1.
Restore electrical power to the outlet box by turning the electricity on at the main fuse box.
2.
All fans are shipped from the factory with the reversing switch positioned to the “left” circulate air downward. If airflow is desired in opposite direction, turn your fan OFF and wait for the blades to stop turning, then slide the reversing switch to the
“right” position, and turn fan on again (Figure 22).
4.
The fan blades will turn in the opposite direction and reverse the airflow.
Season
Summer
Winter
Reverse Switch Information
Rotation Direction
Counter-Clockwise
Clockwise
Switch Position
Left
Right
Figure 22
REVERSING
SWITCH
11 emersonfans.com
Please contact 1-800-654-3545 for further assistance
ETL Model No.: CF110
21
20
4
13
22
2
1
0
4
3
11
10
1
5
Repair Parts
3
2
14
6
7
15
17
16
9
8
18
12
19
12 ETL Model No.: CF110
Repair Parts Listing
Model Numbers
14
19
20
21
22
15
16
17
18
—
5
6
*
4
7
8
9
10
11
12
13
1
2
3
Key
No.
*
Description
Hanger Ball Assembly,
Consisting of:
Hanger Bracket
Hanger Ball
Downrod, 4.5”
Parts Bag Containing:
Wire Connector (3)
Threaded Stud (2)
Lockwasher (2)
Knurled Knob (2)
Pin, Clevis
Clip, Hairpin
Washer, Paper #10 (21)
Screw, #10-32 x 5/16” (21)
Flange Screw, 1/4-20 x 1/2” Spare (1)
Blade Balance Kit
Ceiling Canopy
Coupler Cover
Upper Glass Retainer
Glass Shade
Lower Glass Retainer
Finial
Blade Flange (set of 5)
Fan Blade (set of 5)
SW46 Wall Control/Plate
Owner's Manual
CF110BS00
760750-17
—
—
—
764321-CRM
—
—
—
—
—
—
—
—
—
—
764305-BS
764408-BS
764309-BS
764312-SMK
764311-BS
764319-BS
764315-BS
764317-CH
761971-1
BP7466
CF110ORB00
760750-32
—
—
—
764321-BLOX
—
—
—
—
—
—
—
—
—
—
764305-ORB
764408-ORB
764309-ORB
764312-CMB
764311-ORB
764319-ORB
764315-ORB
764317-WA
761971-1
BP7466
Before discarding packaging material, be certain all parts have been removed.
HOW TO ORDER REPAIR PARTS
WHEN ORDERING REPAIR PARTS, ALWAYS GIVE THE FOLLOWING INFORMATION:
• PART NUMBER • NAME OF ITEM
• PART DESCRIPTION • MODEL NUMBER
The model number of your Fan will be found on a label attached to the top housing.
For repair parts, phone 1-800-654-3545.
13 emersonfans.com
Please contact 1-800-654-3545 for further assistance
ETL Model No.: CF110
Maintenance
IMPORTANT CARE INSTRUCTIONS for your Ceiling Fan
Periodic cleaning of your new ceiling fan is the only maintenance that is needed.
When cleaning, use only a soft brush or lint free cloth to avoid scratching the finish.
Abrasive cleaning agents are not required and should be avoided to prevent damage to finish.
!
WARNING
Do not use water when cleaning your ceiling fan. It could damage the motor or the blades and create the possibility of an electrical shock.
Accessories
1.
Downrod Extension Kits (see store or catalog).
!
WARNING
The use of any other control not specifically approved for this fan could result in fire, shock and personal injury.
!
WARNING
This product is designed to use only those parts supplied with this product and/or any accessories designated specifically for use with this product by
Emerson Electric Co. Substitution of parts or accessories not designated for use with this product by Emerson Electric Co. could result in personal injury or property damage.
Trouble Shooting
!
WARNING: FOR YOUR OWN SAFETY TURN OFF POWER AT FUSE BOX OR CIRCUIT BREAKER BEFORE
TROUBLE SHOOTING YOUR FAN.
TROUBLE PROBABLE CAUSE SUGGESTED REMEDY
1. Fan will not start.
1. Fuse or circuit breaker blown.
1. Check main and branch circuit fuses or circuit breakers.
2. Loose power line connections to the fan, or loose 2. Check line wire connections to fan and switch switch wire switch wire connections in the switch housing.
connections in the switch housing.wire connections in the switch housing.
!
WARNING: Make sure main power is turned off.
3. Reversing switch in neutral position.
2. Fan sounds noisy.
1. Blades not attached to fan.
2. Screws securing fan blade flanges to motor are loose.
3. Make sure reversing switch position is all the way to one side.
1. Attach blades to fan before operating.
2. Check to make sure the screws which attach the fan flanges to the motor are tight.
3. Fan wobbles excessively.
3. Motor noise caused by solid-state variable speed control.
4. Screws holding blades to flanges are loose.
1. Setscrews in motor coupler are not tightened securely.
2. Setscrew in the hangerball/downrod assembly is loose.
3. Screws securing fan blade flanges to motor are .
loose
4. Fan blade flanges not seated properly.
!
WARNING: Make sure main power is turned off.
3. Some fan motors are sensitive to signals from Solid-State variable speed controls. If Solid-State Control is used and motor noise results choose an alternative control method.
4. Tighten screws securely.
1. Raise coupler cover and tighten setscrews securely.
2. Tighten the setscrew in the hangerball/downrod assembly.
5. Hanger bracket and/or ceiling outlet box is not securely fastened
6. Fan blades out of balance.
3. Check to be sure screws which attach the fan blade flanges to the motor are tight.
4. Check to be sure the fan blade flanges seat firmly and uniformly to the surface of the motor. If flanges are seated incorrectly, loosen the flange screws and retighten according to the procedure in the section on "How to Put Your Ceiling
Fan Together".
5. Tighten the hanger bracket screws to the outlet box, and/or secure outlet box.
6. Interchanging an adjacent (side-by-side) blade pair can redistribute the weight and result in smoother operation.
14
ETL Model No.: CF110
Emerson Air Comfort Ceiling Fan Limited Warranty
What The Limited Warranty Covers:
This limited warranty is offered by Air Comfort Products division of Emerson Electric Co. ("Emerson" "we" or "us") located at the address stated below to the original retail purchaser ("you" or "your") of an Emerson Air Comfort Ceiling Fan product ("Emerson Ceiling Fan") and covers the motor and the other components and accessories of the Emerson Ceiling Fan against all defects in workmanship and materials.
What The Period Of Coverage Is:
This limited warranty will cover the Emerson Ceiling Fan motor for the expected lifetime of your Emerson Ceiling Fan (when operated in accordance with your Owner's
Manual or other instructions provided by Emerson to you with the Emerson Ceiling Fan). All other components and accessories of the Emerson Ceiling Fan are covered by this limited warranty for a period of one (1) year from its date of original retail purchase. ANY IMPLIED WARRANTY, INCLUDING WITHOUT LIMITATION, ANY
IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE THAT IS AVAILABLE TO YOU UNDER THE LAWS OF YOUR STATE OR
PROVINCE SHALL COVER THE MOTOR FOR THE EXPECTED LIFETIME OF THE MOTOR (SUBJECT TO PROPER USE), AND FOR ONE YEAR WITH RESPECT TO
COMPONENTS AND ACCESSORIES.
No Other Express or Implied Warranty Applies:
THE LIMITED WARRANTIES PROVIDED ABOVE ARE THE SOLE AND EXCLUSIVE WARRANTIES PROVIDED BY EMERSON TO YOU FOR YOUR EMERSON CEILING
FAN, AND ARE IN LIEU OF ALL OTHER WARRANTIES, WRITTEN OR ORAL, EXPRESS OR IMPLIED, WHETHER ARISING BY OPERATION OF LAW OR OTHERWISE,
WHETHER OR NOT THE PURPOSE HAS BEEN DISCLOSED AND WHETHER OR NOT THE EMERSON CEILING FAN HAS BEEN SPECIFICALLY DESIGNED OR
MANUFACTURED FOR YOUR USE OR PURPOSE. EMERSON HEREBY DISCLAIMS ANY AND ALL IMPLIED WARRANTIES, INCLUDING WITHOUT LIMITATION,
IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE FOR COMPONENTS AND ACCESSORIES AS OF THE EXPIRATION OF THE
ONE YEAR WARRANTY PERIOD FOR SUCH COMPONENTS AND ACCESSORIES. IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR
PURPOSE FOR THE MOTOR PORTION OF THE EMERSON CEILING FAN ARE LIKEWISE DISCLAIMED BY EMERSON AT SUCH TIME THAT THE EXPECTED LIFETIME
OF THE EMERSON CEILING FAN UNDER NORMAL USAGE HAS BEEN REACHED. EXCLUSIONS OR LIMITATIONS OF IMPLIED WARRANTIES MAY VARY FROM
STATE TO STATE AND PROVINCE TO PROVINCE SO THE ABOVE LIMITATIONS MAY NOT APPLY TO YOU.
What We Will Do To Correct Problems:
If during the one (1) year warranty period the motor or any component or accessory of your Emerson Ceiling Fan is defective in materials or workmanship, or if during the expected lifetime of the Emerson Ceiling Fan (when used in accordance with the User Manual or other instructions) the motor is defective in materials or workmanship, you must contact Emerson during the applicable warranty period. If the defect is covered by warranty, Emerson will repair or replace the defective motor, component or other accessory at no charge to you. If repair of the motor, component or accessory is not practical or possible within a reasonable time and no replacement Emerson Ceiling Fan can be provided, Emerson will refund to you the actual purchase price of your Emerson Ceiling Fan. We will ship the repaired or the replacement Emerson Ceiling Fan to you at no charge, but you are responsible for all costs of removal and reinstallation of your Emerson Ceiling Fan.
How You Can Receive Warranty Service:
You must be the original retail purchaser and have proof of your purchase of the Emerson Ceiling Fan to obtain your remedy under this limited warranty. You can return your Emerson Ceiling Fan to your place of purchase, or you can call Emerson Customer Service at 1-800-237-6511 to obtain a return authorization and service identification tag. In order for us to confirm that your Emerson Ceiling Fan is still under warranty, please retain your receipt or other proof of purchase and have that information readily available when returning your Emerson Ceiling Fan to your place of purchase, or upon calling Emerson Customer Service. If you call Emerson
Customer Service, prior to your call please be prepared to provide all model numbers shown on your Emerson Ceiling Fan. Once we have processed your return authorization request, we will provide you with a postage paid return label which should be affixed to the Emerson Ceiling Fan package you ship to the address listed at the end of this limited warranty. The return label will be sent to the mailing address you provide to us by phone.
What Is Not Covered:
This limited warranty does not extend to and expressly excludes:
• The glass globes and light bulbs of your Emerson Ceiling Fan,
• Loss or damage to the motor or any component or accessory caused by normal wear and tear, rather than due to defects in materials or workmanship,
• Loss or damage resulting from conditions beyond our reasonable control, including without limitation, repairs not made at our factory or authorized service center, use of parts or accessories not provided to you as part of this warranty by our factory or authorized service center, mishandling, unreasonable use, misuse, abuse, modifications or other damage caused by you or a third party to your Emerson Ceiling Fan while not in our possession,
• Loss or damage resulting from improper installation, or other failure to comply with instructions in your Owner's Manual.
This limited warranty is deemed null and void upon the occurrence of either of the following events:
• You cease to own the Emerson Ceiling Fan product, or
• The Emerson Ceiling Fan is moved from its original point of installation.
This limited warranty is only valid within the 50 United States, the District of Columbia, and Canada. No other written or oral warranties apply, and no employee, agent, dealer or other person is authorized to give any warranties on behalf of Air Comfort Products or Emerson Electric Co.
Limitation of Liability
REPAIR, REPLACEMENT OR A REFUND ARE THE EXCLUSIVE REMEDIES AVAILABLE TO YOU UNDER THIS LIMITED WARRANTY. TO THE EXTENT PERMITTED BY
LAW, IN NO EVENT SHALL EMERSON OR ANY EMERSON AUTHORIZED DEALER BE LIABLE FOR ANY INCIDENTAL, SPECIAL, INDIRECT, OR CONSEQUENTIAL
DAMAGES, INCLUDING ANY ECONOMIC LOSS, WHETHER RESULTING FROM NONPERFORMANCE, USE, MISUSE OR INABILITY TO USE THE EMERSON CEILING
FAN OR FOR THE NEGLIGENCE OF EMERSON OR AN EMERSON AUTHORIZED DEALER. EMERSON SHALL NOT BE LIABLE FOR DAMAGES CAUSED BY DELAY IN
PERFORMANCE AND IN NO EVENT, REGARDLESS OF THE FORM OF THE CLAIM OR CAUSE OF ACTION (WHETHER BASED IN CONTRACT, INFRINGEMENT,
NEGLIGENCE, STRICT LIABILITY, OTHER TORT OR OTHERWISE), SHALL EMERSON'S OR ANY EMERSON AUTHORIZED AGENT'S LIABILITY TO YOU OR ANY
INDIVIDUAL USING THE EMERSON CEILING FAN EXCEED THE PRICE PAID BY THE ORIGINAL OWNER FOR THE EMERSON CEILING FAN. The term "consequential damages" shall include, but not be limited to, loss of anticipated profits, business interruption, loss of use or revenue, cost of capital or loss or damage to property or equipment.
How State and Provincial Law Relates To The Warranty:
Some states and provinces do not allow the exclusion or limitation of incidental or consequential damages so the above exclusion or limitation may not apply to you.
This limited warranty gives you specific legal rights, and you may also have other rights which vary from state to state or province to province.
15 emersonfans.com
Please contact 1-800-654-3545 for further assistance
ETL Model No.: CF110
Air Comfort Products
DIVISION OF EMERSON ELECTRIC CO.
8100 W. Florissant • St. Louis, MO 63136
Part No. F40BP74660000
11/12
Questions, problems, missing parts: Before returning to the store call
Emerson Electric Customer Service
8 a.m. - 6 p.m., EST, Monday-Friday
1-800-654-3545 www.emersonfans.com
Retain this manual for future use.
Form No. BP7466
ETL Model No.: CF110
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
Frequently Answers and Questions
What safety precautions should be taken when installing the Emerson CF110ORB00 ceiling fan?
What is the recommended wire size for the Emerson CF110ORB00 ceiling fan?
How do I attach the flange/blade assembly to the Emerson CF110ORB00 ceiling fan's motor hub?
How do I install the glass shade on the Emerson CF110ORB00 ceiling fan?
How do I connect the downrod to the Emerson CF110ORB00 ceiling fan?
advertisement