Emerson Liebert UMS02400 Installation Sheet
Add to My manualsadvertisement
U
NIVERSAL
M
ONITOR
Product Specification/Installation Sheet
Description
The Universal
Monitor is a microprocessor with multisensing, remote monitoring and remote control capabilities. Its advanced technology
Universal Monitor
Two sizes of enclosures provides highavailability monitoring around the clock.
The Universal Monitor can operate as an independent, stand-alone controller or in conjunction with Liebert’s SiteScan Web
Enterprise Monitoring System.
The enclosure of the Universal Monitor makes it suited for various applications in both new construction and retrofit jobs. The Universal
Monitor can be mounted on a wall’s surface or recessed within a wall.
The keypad display on the face of the panel is a standard part of the
Universal Monitor.
Features
• Custom configuration for specific applications
• Paging capability—up to four pager numbers
• Preconfigured on-board modem
• Alarm, Event and Trend logs with time and date stamp
• Battery backup to ensure alarm notification
• Backup and download configuration files
• User interface via RS232 or modem connection
• On-board audible alarm
• Configuration data and operating program permanently stored in nonvolatile
Electrically Erasable Programmable Read
Only Memory (EEPROM) for protection against power loss
• Real-time clock
• Status LEDs for verification and diagnostics
Universal Monitor Components and Key Features
Transformer module*
Power On/Off switch
Battery pack
Audible horn
Common alarm connectors
The display, the gateway to all configuration and monitoring, is password-protected.
The Universal Monitor has a standard, on-board modem for remote monitoring via a telephone line.
The modem is preconfigured to work with the panel, eliminating configuration and setup requirements.
24VAC power connector
LCD contrast adjustment
Modem
24VAC connector*
ON Power
On/Off switch*
Power receptacle*
Phone line connector
TB7:
24V INPUT
START
P23:
BATTERY
BATTERY
LCD
CONTRAST
VBATT
J11: PHONE
PIN 3-TIP
PIN 4-RING
MODEM
GND
ON
TP1
ON
S2
OFF
1
DIP
2 3 4 5 6 7 8
MODEM
4 D
DS56
DS54
DS63
DS61
DS60
DS62
DS55
DS57
DS59
DS58
DS53
OUTPUT1
OUTPUT2
OUTPUT3
OUTPUT4
OUTPUT5
OUTPUT6
OUTPUT7
OUTPUT8
CTRLLOCK
SENLOCK
CMN ALR
DS83
DS84
CAN TX
CAN RX
4
R
MOP
F PROG
574 TX
574 RX
485 RX
485 TX
R334
DS70
DS67
DS66
DS65
DS64
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
C71
485
+ —
(BOTTOM)
422
+
—
+
—
+
—
+
—
+
—
AG TB9: ANALOG
GROUND
Serial interface connector (RS232/EIA574)
(TOP)
NO C NC
LS1
+
P11
R40
R2
ENABLE
AUDIBLE
Q11
1-2 TOP
3-4 BOTTOM
NO C NC
(BOTTOM)
TOP
EIA485 connector
TB3:
RELAY
OUTPUTS
(TOP)
4
8
3
7
2
1
6
5
(TOP)
(BOTTOM)
4
8
3
7
2
6
1
5
TB2:
CONTACT
INPUTS
ALL CIRCUITS:
CLASS 2
SiteScan Web connector (EIA422)
*Transformer module comes standard in large enclosure only
Manual override switch
(outputs)
Digital output connectors
Digital input connectors
Analog input connectors
1
Hardware and Components
Two sizes of enclosures provide flexibility and expansion to meet evolving application needs. Both sizes of enclosures come standard with a liquid crystal display (LCD) and controller board. In addition, the large
Universal Monitor has an internal Transformer Module.
The enclosure features a key lock for added security and is made of metal to accommodate secure conduit fittings and protect components against environmental debris. The enclosure is designed for easy wire routing and terminations, with top and bottom access slots for communication cables and network wires. The enclosure is 2-3/4" deep, allowing for recess mounting in a wall.
Keypad Display
The keypad display is a user interface mounted on the enclosure door of each Universal
Monitor. The display provides for complete monitoring and configuration of the panel and is password-protected.
Keypad
The keypad display provides the ability for the
Universal Monitor to operate as a complete standalone panel.
Controller Board
The controller board supports 22 points:
• Eight digital inputs
• Four analog inputs
• Eight digital outputs
• Two Common Alarm outputs
The digital inputs are dry contacts. The analog inputs are 4-20mA inputs. The digital outputs and
Common Alarm outputs are Form C contact relays.
The point terminations are made using removable terminal blocks. This allows for easier access to the terminators, streamlining the process of connecting external devices to the Universal Monitor.
The battery supplies power to the modem for a minimum of 10 minutes, providing the capability to send out a loss-of-power alarm to all configured pagers.
Flash ROM may be easily upgraded at the job site, simplifying the process of installing new firmware as it becomes available.
An RS232 operator terminal port is included with each controller board for easy interface to a laptop or desktop PC for setup and device monitoring.
An integrated on-board modem is included with each controller board for remote access to the Universal
Monitor. An RJ11 phone modem jack is also included. The modem is factory-configured, eliminating field configuration and wiring requirements.
An IGM422 connection is included with each controller to connect the Universal Monitor to Liebert’s
SiteScan Web Enterprise Monitoring System. This connection allows information and alarms to be monitored from a centrally located command center.
Transformer Module
The large Universal Monitor comes with either 115VAC or
230VAC Transformer Module.
• The 115VAC Transformer
Module provides step-down power from 115VAC to
24VAC, two Class 2 24VAC
40VA power terminations and one 115VAC outlet to power accessory devices, such as a Portable Operator’s
Terminal.
115VAC Transformer
• The 230VAC Transformer
230VAC Transformer
Module provides step-down power from 230VAC to 24VAC and two Class 2 24VAC 40VA power terminations. An outlet is not provided on this Transformer Module.
The Transformer Module may be ordered separately as an option for the small Universal Monitor—or any device requiring 24VAC—and mounted outside the enclosure.
I/O Expansion Module
The Universal Monitor I/O Expansion Module, purchased separately, has connectors for 16 digital inputs and eight digital outputs, as shown below.
The board has light emitting diodes (LEDs) to display the status of monitored output devices, communications ports for connection to the Universal
Monitor, power connections and other features necessary to monitor and protect your operation.
I/O Expansion Module Components
& Key Features
24VAC power connector
Digital output connectors (8)
EIA485 + (to UM-)
0V
EIA485 - (to UM+)
POWER INPUT
D6
S4 S3 S2 S1
DEFAULT SETTINGS FOR USE WITH UNIVERSAL MONITOR
EIA485 connector
RELAY OUTPUTS
USE COPPER (CU) CONDUCTORS ONLY.
V1
V2
V3
V4
V5
V6
V7
V8
V9
V10
V11
V12
V13
V14
V15
V16
K1
OUT1
K2
OUT2
K3
OUT3
K4
OUT4
K5
OUT5
K6
OUT6
K7
OUT7
K8
OUT8
Digital output fuses (8)
Digital output
DIP switch
Digital input connectors (16)
2
Dimensions - Enclosures, I/O Expansion Module, Transformer Modules
LARGE ENCLOSURE
18"
(457.2mm)
SMALL ENCLOSURE &
I/O EXPANSION MODULE
TRANSFORMER MODULES
(115V & 230V)
14.25"
(361.95mm)
18"
(457.2mm)
14"
(355.6mm)
12"
(304.8mm)
Front view Front view
3.83"
(97.2mm)
Front view
Top/bottom view
2.85"
(72.39mm)
Top/bottom view
2.85"
(72.39mm)
2.65"
(67.3mm)
Bottom view
Wiring Specifications
Connection
Digital
Input
Supported Wire Type
18-22 AWG Stranded & Unshielded
18 AWG (recommended)
Non Plenum - Belden 9740
Plenum - Belden 89740
Maximum Wire Length
Digital
Output
18-22 AWG Stranded & Unshielded
18 AWG (recommended)
Non Plenum - Belden 9740
Plenum - Belden 89740
18 AWG*
(recommended)
@3A 50 ft. (15m)
@2A 100 ft. (30m)
@1A 200 ft. (60m)
Analog Input
2-Wire
Transducer
Analog Input
4-Wire
Transducer
Common
Alarm
Output
18-22 AWG Stranded & Unshielded
18 AWG (recommended)
Non Plenum - Belden 9740
Plenum - Belden 89740
18-22 AWG Stranded & Unshielded
18 AWG (recommended)
Non Plenum - Belden 8489
Plenum - Belden 88489
18-22 AWG Stranded & Unshielded
18 AWG (recommended)
Non Plenum - Belden 9740
Plenum - Belden 89740
18 AWG*
(recommended)
@3A 50 ft. (15m)
@2A 100 ft. (30m)
@1A 200 ft. (60m)
Communication
RS232
Null Modem Cable
Communication
IGM422
SiteScan
Communication
EIA485
Phone/Modem
Line
18-22 AWG Stranded & Shielded
22 AWG (recommended)
Non Plenum - Belden 9461
Plenum - Belden 88761
18-22 AWG Stranded & Shielded
22 AWG (recommended)
Non Plenum - Belden 9461
Plenum - Belden 88761
4 Wire (Pins 3 & 4)
RJ11 Connector
24VAC Power
Connection
18-22 AWG Stranded & Shielded
18 AWG (recommended)
Non Plenum - Belden 8770
Plenum - Belden 88770
Power Connections (Transformer Module)
115VAC
230VAC
14 AWG Stranded & Unshielded
Non Plenum - Belden 5101UE
14 AWG Stranded & Unshielded
Non Plenum - Belden 5101UE
750 ft. (225m)
20 AWG
750 ft. (225m)
750 ft. (225m)
20 AWG
@3A 40 ft. (12m)
@2A 60 ft. (18m)
@1A 100 ft. (30m)
@3A 25 ft. (7m)
@2A 35 ft. (10m)
@1A 75 ft. (23m)
50 ft. (15m)
1000 ft. (300m)
3000 ft. (900m)
N/A
150 ft. (45m)
150 ft. (45m)
150 ft. (45m)
22 AWG
@3A 40 ft. (12m)
@2A 60 ft. (18m)
@1A 100 ft. (30m)
@3A 25 ft. (7m)
@2A 35 ft. (10m)
@1A 75 ft. (23m)
22 AWG
Rating
Dry Contact
(24VDC, 10 mA)
24VAC @3A
4-20 mA Signal
Input Selectable
Power Source
(12/24VDC)
4-20 mA Signal
Input Selectable
Power Source
(12/24VDC)
24VAC @3A
N/A
N/A
N/A
N/A
24VAC @1.3A
115VAC @5A
230VAC @0.5A
3
Specifications
Input Power
Requirements
Dimensions
W x D x H, in. (mm)
Weight (Assembled)
Enclosure Type
Liquid Crystal Display
Mounting Surface
Ambient Operating
Environment
Modem/Clock Specifics
Modem Type
Clock Type
Clock battery backup type
Clock battery life
Modem battery backup type
Modem battery life
Communications
Local
Remote: Modem
Remote: Supported pagers
SiteScan Web
Expansion Board (optional)
Agency Listings
UL
CSA
CE
FCC Compliance
Inputs & Outputs (Quantity)
Digital Inputs
Analog Inputs
Digital Outputs
Common Alarm Outputs
Small Enclosure
UMS02400
24VAC±10% of nominal; 50/60 Hz,
1.3A, 30VA
14-1/4 x 2-3/4 x 12
(361.95 x 69.85 x 304.8)
7.68 lb. (3.48 kg)
Large Enclosure
115VAC
UML11500
230VAC
UML23000
115VAC±10% of nominal; 60Hz,
4A, 460VA
230VAC±10% of nominal; 50Hz,
0.5A, 115VA
18 x 2-3/4 x 18
(457.2 x 69.85 x 457.2)
20.56 lb. (9.33 kg)
NEMA 1
Four line, 20 character, backlit
Building Wall or Structural Member
32°F to 104°F (0°C to 40°C)
0% RH to 95% RH (non-condensing)
Embedded 14.4K bps
Real-Time Clock
Lithium Cell (non-replaceable)
7 years, constant, no power
Nickel Cadmium (replaceable)
10 minutes at full load
Baud rate 9600 bps; Parity=None; Data bits=8; Stop bits=1
9600 E-7-1 supports TAPI protocol version 1.8
UL3121
C22.2 No. 1010
Yes
CFR 47 Part 15
EIA232
IGM Protocol, EIA422
EIA485
UL1012 UL1585
C22.2 No. 66 and C22.2 No. 107.1
Yes
N/A
Dry Contact Closure
24VDC, 10 mA (8)
4-20mA signal input with selectable power source of 12VDC or 24VDC (4)
24VAC, 3A (8)
24VAC, 3A (2)
I/O Expansion Module
UMEXP
24VAC±10% of nominal; 50/60 Hz,
0.6A, 15VA, Class 2
14-1/4 x 2-3/4 x 12
(361.95 x 69.85 x 304.8)
7.68 lb. (3.48 kg)
NEMA 1
—
—
—
—
—
—
—
—
—
—
—
—
—
EIA485
—
—
—
—
Dry Contact Closure
24VDC, 10 mA (16)
—
240VAC, 2A (8)
—
Ordering Information
Quantity Product #
UMS02400 Universal Monitor small enclosure
Description
UML11500 Universal Monitor large enclosure with 115VAC Transformer Module
UML23000 Universal Monitor large enclosure with 230VAC Transformer Module
TM115
TM230
UMEXP
Transformer Module 115VAC with two 24VAC outputs (40VA each) and 115VAC receptacle
Transformer Module 230VAC with two 24VAC outputs (40VA each)
I/O Expansion Module
Liebert Corporation
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Telephone: 1-800-877-9222
Facsimile: 1-614-841-6022 www.liebert.com
© 2005 Liebert Corporation
All rights reserved throughout the world. Specifications subject to change without notice.
® Liebert and the Liebert logo are registered trademarks of
Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
SL-31061 (2/05) Rev. 1
4
advertisement
Related manuals
advertisement