Emerson Liebert UMS02400 Installation Sheet

Add to My manuals

advertisement

Emerson Liebert UMS02400 Installation Sheet | Manualzz

U

NIVERSAL

M

ONITOR

Product Specification/Installation Sheet

Description

The Universal

Monitor is a microprocessor with multisensing, remote monitoring and remote control capabilities. Its advanced technology

Universal Monitor

Two sizes of enclosures provides highavailability monitoring around the clock.

The Universal Monitor can operate as an independent, stand-alone controller or in conjunction with Liebert’s SiteScan Web

Enterprise Monitoring System.

The enclosure of the Universal Monitor makes it suited for various applications in both new construction and retrofit jobs. The Universal

Monitor can be mounted on a wall’s surface or recessed within a wall.

The keypad display on the face of the panel is a standard part of the

Universal Monitor.

Features

• Custom configuration for specific applications

• Paging capability—up to four pager numbers

• Preconfigured on-board modem

• Alarm, Event and Trend logs with time and date stamp

• Battery backup to ensure alarm notification

• Backup and download configuration files

• User interface via RS232 or modem connection

• On-board audible alarm

• Configuration data and operating program permanently stored in nonvolatile

Electrically Erasable Programmable Read

Only Memory (EEPROM) for protection against power loss

• Real-time clock

• Status LEDs for verification and diagnostics

Universal Monitor Components and Key Features

Transformer module*

Power On/Off switch

Battery pack

Audible horn

Common alarm connectors

The display, the gateway to all configuration and monitoring, is password-protected.

The Universal Monitor has a standard, on-board modem for remote monitoring via a telephone line.

The modem is preconfigured to work with the panel, eliminating configuration and setup requirements.

24VAC power connector

LCD contrast adjustment

Modem

24VAC connector*

ON Power

On/Off switch*

Power receptacle*

Phone line connector

TB7:

24V INPUT

START

P23:

BATTERY

BATTERY

LCD

CONTRAST

VBATT

J11: PHONE

PIN 3-TIP

PIN 4-RING

MODEM

GND

ON

TP1

ON

S2

OFF

1

DIP

2 3 4 5 6 7 8

MODEM

4 D

DS56

DS54

DS63

DS61

DS60

DS62

DS55

DS57

DS59

DS58

DS53

OUTPUT1

OUTPUT2

OUTPUT3

OUTPUT4

OUTPUT5

OUTPUT6

OUTPUT7

OUTPUT8

CTRLLOCK

SENLOCK

CMN ALR

DS83

DS84

CAN TX

CAN RX

4

R

MOP

F PROG

574 TX

574 RX

485 RX

485 TX

R334

DS70

DS67

DS66

DS65

DS64

INPUT1

INPUT2

INPUT3

INPUT4

INPUT5

INPUT6

INPUT7

INPUT8

C71

485

+ —

(BOTTOM)

422

+

+

+

+

+

AG TB9: ANALOG

GROUND

Serial interface connector (RS232/EIA574)

(TOP)

NO C NC

LS1

+

P11

R40

R2

ENABLE

AUDIBLE

Q11

1-2 TOP

3-4 BOTTOM

NO C NC

(BOTTOM)

TOP

EIA485 connector

TB3:

RELAY

OUTPUTS

(TOP)

4

8

3

7

2

1

6

5

(TOP)

(BOTTOM)

4

8

3

7

2

6

1

5

TB2:

CONTACT

INPUTS

ALL CIRCUITS:

CLASS 2

SiteScan Web connector (EIA422)

*Transformer module comes standard in large enclosure only

Manual override switch

(outputs)

Digital output connectors

Digital input connectors

Analog input connectors

1

Hardware and Components

Two sizes of enclosures provide flexibility and expansion to meet evolving application needs. Both sizes of enclosures come standard with a liquid crystal display (LCD) and controller board. In addition, the large

Universal Monitor has an internal Transformer Module.

The enclosure features a key lock for added security and is made of metal to accommodate secure conduit fittings and protect components against environmental debris. The enclosure is designed for easy wire routing and terminations, with top and bottom access slots for communication cables and network wires. The enclosure is 2-3/4" deep, allowing for recess mounting in a wall.

Keypad Display

The keypad display is a user interface mounted on the enclosure door of each Universal

Monitor. The display provides for complete monitoring and configuration of the panel and is password-protected.

Keypad

The keypad display provides the ability for the

Universal Monitor to operate as a complete standalone panel.

Controller Board

The controller board supports 22 points:

• Eight digital inputs

• Four analog inputs

• Eight digital outputs

• Two Common Alarm outputs

The digital inputs are dry contacts. The analog inputs are 4-20mA inputs. The digital outputs and

Common Alarm outputs are Form C contact relays.

The point terminations are made using removable terminal blocks. This allows for easier access to the terminators, streamlining the process of connecting external devices to the Universal Monitor.

The battery supplies power to the modem for a minimum of 10 minutes, providing the capability to send out a loss-of-power alarm to all configured pagers.

Flash ROM may be easily upgraded at the job site, simplifying the process of installing new firmware as it becomes available.

An RS232 operator terminal port is included with each controller board for easy interface to a laptop or desktop PC for setup and device monitoring.

An integrated on-board modem is included with each controller board for remote access to the Universal

Monitor. An RJ11 phone modem jack is also included. The modem is factory-configured, eliminating field configuration and wiring requirements.

An IGM422 connection is included with each controller to connect the Universal Monitor to Liebert’s

SiteScan Web Enterprise Monitoring System. This connection allows information and alarms to be monitored from a centrally located command center.

Transformer Module

The large Universal Monitor comes with either 115VAC or

230VAC Transformer Module.

• The 115VAC Transformer

Module provides step-down power from 115VAC to

24VAC, two Class 2 24VAC

40VA power terminations and one 115VAC outlet to power accessory devices, such as a Portable Operator’s

Terminal.

115VAC Transformer

• The 230VAC Transformer

230VAC Transformer

Module provides step-down power from 230VAC to 24VAC and two Class 2 24VAC 40VA power terminations. An outlet is not provided on this Transformer Module.

The Transformer Module may be ordered separately as an option for the small Universal Monitor—or any device requiring 24VAC—and mounted outside the enclosure.

I/O Expansion Module

The Universal Monitor I/O Expansion Module, purchased separately, has connectors for 16 digital inputs and eight digital outputs, as shown below.

The board has light emitting diodes (LEDs) to display the status of monitored output devices, communications ports for connection to the Universal

Monitor, power connections and other features necessary to monitor and protect your operation.

I/O Expansion Module Components

& Key Features

24VAC power connector

Digital output connectors (8)

EIA485 + (to UM-)

0V

EIA485 - (to UM+)

POWER INPUT

D6

S4 S3 S2 S1

DEFAULT SETTINGS FOR USE WITH UNIVERSAL MONITOR

EIA485 connector

RELAY OUTPUTS

USE COPPER (CU) CONDUCTORS ONLY.

V1

V2

V3

V4

V5

V6

V7

V8

V9

V10

V11

V12

V13

V14

V15

V16

K1

OUT1

K2

OUT2

K3

OUT3

K4

OUT4

K5

OUT5

K6

OUT6

K7

OUT7

K8

OUT8

Digital output fuses (8)

Digital output

DIP switch

Digital input connectors (16)

2

Dimensions - Enclosures, I/O Expansion Module, Transformer Modules

LARGE ENCLOSURE

18"

(457.2mm)

SMALL ENCLOSURE &

I/O EXPANSION MODULE

TRANSFORMER MODULES

(115V & 230V)

14.25"

(361.95mm)

18"

(457.2mm)

14"

(355.6mm)

12"

(304.8mm)

Front view Front view

3.83"

(97.2mm)

Front view

Top/bottom view

2.85"

(72.39mm)

Top/bottom view

2.85"

(72.39mm)

2.65"

(67.3mm)

Bottom view

Wiring Specifications

Connection

Digital

Input

Supported Wire Type

18-22 AWG Stranded & Unshielded

18 AWG (recommended)

Non Plenum - Belden 9740

Plenum - Belden 89740

Maximum Wire Length

Digital

Output

18-22 AWG Stranded & Unshielded

18 AWG (recommended)

Non Plenum - Belden 9740

Plenum - Belden 89740

18 AWG*

(recommended)

@3A 50 ft. (15m)

@2A 100 ft. (30m)

@1A 200 ft. (60m)

Analog Input

2-Wire

Transducer

Analog Input

4-Wire

Transducer

Common

Alarm

Output

18-22 AWG Stranded & Unshielded

18 AWG (recommended)

Non Plenum - Belden 9740

Plenum - Belden 89740

18-22 AWG Stranded & Unshielded

18 AWG (recommended)

Non Plenum - Belden 8489

Plenum - Belden 88489

18-22 AWG Stranded & Unshielded

18 AWG (recommended)

Non Plenum - Belden 9740

Plenum - Belden 89740

18 AWG*

(recommended)

@3A 50 ft. (15m)

@2A 100 ft. (30m)

@1A 200 ft. (60m)

Communication

RS232

Null Modem Cable

Communication

IGM422

SiteScan

Communication

EIA485

Phone/Modem

Line

18-22 AWG Stranded & Shielded

22 AWG (recommended)

Non Plenum - Belden 9461

Plenum - Belden 88761

18-22 AWG Stranded & Shielded

22 AWG (recommended)

Non Plenum - Belden 9461

Plenum - Belden 88761

4 Wire (Pins 3 & 4)

RJ11 Connector

24VAC Power

Connection

18-22 AWG Stranded & Shielded

18 AWG (recommended)

Non Plenum - Belden 8770

Plenum - Belden 88770

Power Connections (Transformer Module)

115VAC

230VAC

14 AWG Stranded & Unshielded

Non Plenum - Belden 5101UE

14 AWG Stranded & Unshielded

Non Plenum - Belden 5101UE

750 ft. (225m)

20 AWG

750 ft. (225m)

750 ft. (225m)

20 AWG

@3A 40 ft. (12m)

@2A 60 ft. (18m)

@1A 100 ft. (30m)

@3A 25 ft. (7m)

@2A 35 ft. (10m)

@1A 75 ft. (23m)

50 ft. (15m)

1000 ft. (300m)

3000 ft. (900m)

N/A

150 ft. (45m)

150 ft. (45m)

150 ft. (45m)

22 AWG

@3A 40 ft. (12m)

@2A 60 ft. (18m)

@1A 100 ft. (30m)

@3A 25 ft. (7m)

@2A 35 ft. (10m)

@1A 75 ft. (23m)

22 AWG

Rating

Dry Contact

(24VDC, 10 mA)

24VAC @3A

4-20 mA Signal

Input Selectable

Power Source

(12/24VDC)

4-20 mA Signal

Input Selectable

Power Source

(12/24VDC)

24VAC @3A

N/A

N/A

N/A

N/A

24VAC @1.3A

115VAC @5A

230VAC @0.5A

3

Specifications

Input Power

Requirements

Dimensions

W x D x H, in. (mm)

Weight (Assembled)

Enclosure Type

Liquid Crystal Display

Mounting Surface

Ambient Operating

Environment

Modem/Clock Specifics

Modem Type

Clock Type

Clock battery backup type

Clock battery life

Modem battery backup type

Modem battery life

Communications

Local

Remote: Modem

Remote: Supported pagers

SiteScan Web

Expansion Board (optional)

Agency Listings

UL

CSA

CE

FCC Compliance

Inputs & Outputs (Quantity)

Digital Inputs

Analog Inputs

Digital Outputs

Common Alarm Outputs

Small Enclosure

UMS02400

24VAC±10% of nominal; 50/60 Hz,

1.3A, 30VA

14-1/4 x 2-3/4 x 12

(361.95 x 69.85 x 304.8)

7.68 lb. (3.48 kg)

Large Enclosure

115VAC

UML11500

230VAC

UML23000

115VAC±10% of nominal; 60Hz,

4A, 460VA

230VAC±10% of nominal; 50Hz,

0.5A, 115VA

18 x 2-3/4 x 18

(457.2 x 69.85 x 457.2)

20.56 lb. (9.33 kg)

NEMA 1

Four line, 20 character, backlit

Building Wall or Structural Member

32°F to 104°F (0°C to 40°C)

0% RH to 95% RH (non-condensing)

Embedded 14.4K bps

Real-Time Clock

Lithium Cell (non-replaceable)

7 years, constant, no power

Nickel Cadmium (replaceable)

10 minutes at full load

Baud rate 9600 bps; Parity=None; Data bits=8; Stop bits=1

9600 E-7-1 supports TAPI protocol version 1.8

UL3121

C22.2 No. 1010

Yes

CFR 47 Part 15

EIA232

IGM Protocol, EIA422

EIA485

UL1012 UL1585

C22.2 No. 66 and C22.2 No. 107.1

Yes

N/A

Dry Contact Closure

24VDC, 10 mA (8)

4-20mA signal input with selectable power source of 12VDC or 24VDC (4)

24VAC, 3A (8)

24VAC, 3A (2)

I/O Expansion Module

UMEXP

24VAC±10% of nominal; 50/60 Hz,

0.6A, 15VA, Class 2

14-1/4 x 2-3/4 x 12

(361.95 x 69.85 x 304.8)

7.68 lb. (3.48 kg)

NEMA 1

EIA485

Dry Contact Closure

24VDC, 10 mA (16)

240VAC, 2A (8)

Ordering Information

Quantity Product #

UMS02400 Universal Monitor small enclosure

Description

UML11500 Universal Monitor large enclosure with 115VAC Transformer Module

UML23000 Universal Monitor large enclosure with 230VAC Transformer Module

TM115

TM230

UMEXP

Transformer Module 115VAC with two 24VAC outputs (40VA each) and 115VAC receptacle

Transformer Module 230VAC with two 24VAC outputs (40VA each)

I/O Expansion Module

Liebert Corporation

1050 Dearborn Drive

P.O. Box 29186

Columbus, OH 43229

Telephone: 1-800-877-9222

Facsimile: 1-614-841-6022 www.liebert.com

© 2005 Liebert Corporation

All rights reserved throughout the world. Specifications subject to change without notice.

® Liebert and the Liebert logo are registered trademarks of

Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.

SL-31061 (2/05) Rev. 1

4

advertisement

Related manuals