Emerson NetSure 211 Series Ordering Guides

Add to my manuals
105 Pages

advertisement

Emerson NetSure 211 Series Ordering Guides | Manualzz

SAG582136600

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

Issue AU, February 21, 2014

Home

SYSTEM OVERVIEW

Description: The NetSure™ 211 NGFB DC Power System is a complete integrated power system containing rectifiers, intelligent control, metering, monitoring, and distribution. This power system consists of the following mounted in a 1RU or 2RU high by 19” or 23” wide shelf.

• 500W or 1000W Rectifier Modules

The 1RU high by 19” wide shelf accommodates two (2) 500W or 1000W Rectifier Modules.

The 1RU high by 23” wide shelf accommodates three (3) 500W or 1000W Rectifier Modules.

The 2RU high by 19” wide shelf accommodates four (4) 500W or 1000W Rectifier Modules.

The 2RU high by 23” wide shelf accommodates six (6) 500W or 1000W Rectifier Modules.

The Rectifier Modules provide load power, battery float current, and battery recharge current during normal operating conditions. The Rectifier Modules are designed to provide constant power. They are designed with the latest patented switch-mode technology using DSP (Digital Signal Processing) functionality for efficient operation.

This means that, within the normal operating ambient temperature range and input voltage range, the maximum available output power is a constant 500W or 1000W.

Within these ranges, the Rectifier Modules operate in one of three modes, depending upon load demands. Transition between modes is completely automatic. If ambient temperature rises above or input voltage falls below acceptable values, Rectifier

Modules continue to operate but at derated output power levels.

1) Constant Voltage Mode: For any initial output voltage setting from 42 to 58 volts, output voltage remains constant regardless of load. This is the normal operating condition, in which loads are being supplied and batteries are float charged. Rectifier Modules operate in the Constant Voltage Mode unless load increases to the point where the product of load current and output voltage is approximately

500W or 1000W.

2) Constant Power Mode: As load increases above approximately 500W or 1000W

(non-adjustable), output current continues to increase, but output voltage decreases as required to maintain constant output power. Rectifier

Modules operate in the

Constant Power Mode unless load continues to increase to the point where the current limit setting is reached.

List 1 (List 2 similar)

3) Constant Current Mode: If load increases above the current limit setting, output voltage decreases linearly to maintain output current at current limit. List 5 (List 6 similar)

Page 1 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

• ACU+ (Advanced Control Unit Plus)

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

Home

The ACU+ provides Rectifier Module and optional Low Voltage Battery Disconnect

(LVBD) or Low Voltage Load Disconnect (LVLD) control, metering functions, monitoring functions, and local/remote alarms as well as PCU control, data acquisition, system alarm management, and advanced battery and energy management. The ACU+ contains an LCD display and keypad for local access. It provides connection for binary inputs, programmable relay outputs, and a charge control function. The controller also supports rectifier temperature compensation if the system is equipped with a temperature probe (or multiple temperature probes connected via a Temperature Concentrator (SM TEMP), and ambient temperature monitoring if equipped with a second temperature probe. The ACU+ provides

Ethernet connection and supports software upgrade via its USB port. It also comes with a comprehensive web page and SNMP capability for remote system management.

SCU+ (Standard Control Unit Plus)

The SCU+ provides Rectifier Module and optional Low Voltage Battery Disconnect

(LVBD) or Low Voltage Load Disconnect (LVLD) control, metering functions, monitoring functions, and local/remote alarms. The SCU+ contains an LCD display and keypad for local access. It provides connection for binary inputs, programmable relay outputs, and a charge control function. The controller also supports rectifier temperature compensation if the system is equipped with a temperature probe (or multiple temperature probes connected via a Temperature Concentrator (SM TEMP), and ambient temperature monitoring if equipped with a second temperature probe.

The SCU+ also provides Ethernet connection and SNMP capability.

Family:

Spec. No.:

Model:

Input Voltage

Output Voltage:

• Distribution Unit

Various Distribution Unit options are available, as described in this document. The

Distribution Unit can be equipped with an optional Low Voltage Battery Disconnect

(LVBD) or Low Voltage Load Disconnect (LVLD) contactor.

NetSure™

582136600

211 NGFB

Nominal 120/208/240 volts AC, single phase, 3-wire, 50/60 Hz, with an operating range of 100 to 250 volts. Acceptable input frequency range is

45 to 65 Hz.

-48 Volts DC

Output Capacity:

Rectifier Module: 500W @ Vout >48Vdc (10.5A @ -48Vdc) or

1000W @ Vout >48Vdc (20.9A @ -48Vdc)

Page 2 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

System: See the following table.

SAG582136600

Issue AU, February 21, 2014

Home

Agency Approval:

Framework Type:

Mounting Width:

Mounting Depth:

Mounting Height:

Access:

Control:

Color:

Environment:

Spec. No.

System DC Output Capability

208/240VAC Input 120VAC Input

+40°C (+104°F) +65°C (+149°F) +40°C (+104°F) +65°C (+149°F)

500W

Rect.

1000W

Rect.

500W

Rect.

1000W

Rect.

500W

Rect.

1000W

Rect.

500W

Rect.

1000W

Rect.

58213660001 20.8A 41.6A 12.6A 25A 20.8A 27.4A 12.6A 16.4A

58213660002 31.2A 62.4A 18.9A 37.5A 31.2A 41.1A 18.9A 24.6A

58213660005 41.6A 83.2A 25.2A

58213660006 62.4A 124.8A 37.8A

50A

75A

41.6A 54.8A 25.2A 32.8A

62.4A 82.2A 37.8A 49.2A

UL 60950 Recognized, CAN/CSA 22.2

Relay Rack Mounted

19” or 23”, nominal

12”

1.75” (1RU) or 3.5” (2RU)

Front for Installation, Operation, and Maintenance

Microprocessor

Front Panels are Gray; Shelf is Galvaneal

-40°C (-40°F) to +65°C (+149°F),

with deratings (see SPECIFICATIONS section)

Page 3 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

58213660001

Side AC Input Connectors

(P/O List 1) and

AC Input Cables/Line Cords

58213660002

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

Home

Rectifier Module

(500W)

or

Rectifier Module

(1000W)

Distribution Unit

SCU+ P/N 1M521BNA

Side AC Input Connectors

(P/O List 2) and

AC Input Cables/Line Cords

Rectifier Module

(500W)

or

Rectifier Module

(1000W)

Distribution Unit

SCU+ P/N 1M521BNA

Page 4 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

58213660001 with P/N 555260

Rear AC Input Connector

( P/O P/N 555260 ) and

AC Input Cables/Line Cords

58213660001 with P/N 556828 Kit

Rectifier Module

(500W)

or

Rectifier Module

(1000W)

Rear AC Input Connector

( P/O P/N 556828 ) and

AC Input Cables/Line Cords

SAG582136600

Issue AU, February 21, 2014

Home

Distribution Unit

SCU+ P/N 1M521BNA

Distribution Unit

SCU+ P/N 1M521BNA

Rectifier Module

(500W)

or

Rectifier Module

(1000W)

Page 5 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

58213660002 with P/N 555261

Rear AC Input Connector

( P/O P/N 555261 ) and

AC Input Cables/Line Cords

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

Home

Rectifier Module

(500W)

or

Rectifier Module

(1000W)

SCU+ P/N 1M521BNA

Distribution Unit

Page 6 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

58213660005

Side AC Input Connectors

(P/O List 5) and

AC Input Cables/Line Cords

58213660006

SAG582136600

Issue AU, February 21, 2014

Home

Rectifier Module

(500W)

or

Rectifier Module

(1000W)

Distribution Unit

SCU+ P/N 1M521BNA

or

ACU+ P/N 1M820BNA

Side AC Input Connectors

(P/O List 6) and

AC Input Cables/Line Cords

Rectifier Module

(500W)

or

Rectifier Module

(1000W)

Distribution Unit

SCU+ P/N 1M521BNA

or

ACU+ P/N 1M820BNA

Page 7 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

DISTRIBUTION UNIT (Lists 1 and 2)

List BG:

(10) GMT Fuse Load Positions

Low Voltage Battery Disconnect (LVBD)

(1) Set Battery Cables

List NG:

(10) GMT Fuse Load Positions

NO Low Voltage Disconnect

(1) Set Battery Cables

System Application Guide

Spec. No. 582136600 (Model 211 NGFB

Home

)

DISTRIBUTION UNIT (Lists 5 and 6)

List BF:

(13) GMT Fuse Load Positions

Low Voltage Battery Disconnect (LVBD)

(3) Battery Landing Points

List LF:

(13) GMT Fuse Load Positions

Low Voltage Load Disconnect (LVLD)

(3) Battery Landing Points

List NF:

(13) GMT Fuse Load Positions

NO Low Voltage Disconnect

(3) Battery Landing Points

List BC:

(5) GMT Fuse Load Positions

(4) Bullet-Nose Circuit Breaker Load Positions

Low Voltage Battery Disconnect (LVBD)

(3) Battery Landing Points

List LC:

(5) GMT Fuse Load Positions

(4) Bullet-Nose Circuit Breaker Load Positions

Low Voltage Load Disconnect (LVLD)

(3) Battery Landing Points

List NC:

(5) GMT Fuse Load Positions

(4) Bullet-Nose Circuit Breaker Load Positions

NO Low Voltage Disconnect

(3) Battery Landing Points

List BA:

(5) GMT Fuse Load Positions

(2) Bullet-Nose Circuit Breaker Load Positions

(2) Bullet-Nose Circuit Breaker Battery Disconnect Positions

Low Voltage Battery Disconnect (LVBD)

List LA:

(5) GMT Fuse Load Positions

(2) Bullet-Nose Circuit Breaker Load Positions

(2) Bullet-Nose Circuit Breaker Battery Disconnect Positions

Low Voltage Load Disconnect (LVLD)

List NA:

(5) GMT Fuse Load Positions

(2) Bullet-Nose Circuit Breaker Load Positions

(2) Bullet-Nose Circuit Breaker Battery Disconnect Positions

NO Low Voltage Disconnect

Page 8 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

SAG582136600

Issue AU, February 21, 2014

Home

Other List Options

List 60: Five (5) Load Lead Assemblies for 10A GMT Fuse Positions

(for use w/ Lists BC, LC, NC, BA, LA, and NA)

List 61: Eight (8) Load Lead Assemblies for 10A GMT Fuse Positions

(for use w/ Lists BF, LF, and NF)

List 62: Five (5) Load Lead Assemblies for 15A GMT Fuse Positions

(for use w/ Lists BF, LF, and NF)

List 65: Shelf Side Battery Cables

(for use w/ Lists BF, LF, NF, BC, LC, and NC)

List 66: Battery Side Battery Cables

(for use w/ Lists BF, LF, NF, BC, LC, and NC)

List 67: Battery Side Battery Cables

(For use with Lists BC, LC, NC, BF, LF, and NF)

List 71: Optional External Battery Cables (8 AWG) with Anderson Connector

for (1) Battery String (for use w/ Lists BG and NG)

List 72: Optional External Battery Cables with Anderson Connector

for (2) Battery Strings (for use w/ Lists BG and NG)

List 73 : Optional External Battery Cables (6 AWG) with Anderson Connector

for (1) Battery String (for use w/ Lists BG and NG)

List 89: Relay Rack Earthquake Anchor Kit

List 90: Temperature Probe (12 ft. total)

List 91: Temperature Probe (33 ft. total)

List 93: Battery Tray (23”)

List 94: Battery Tray (19”)

List KG: GMT Fuse Load Distribution Panel

Accessory Options

Relay Racks

Mounting and Adapter Kits

Distribution Devices

AC Input Cables and Line Cords

Ring & Distribution Module

External Battery Disconnect Unit

SM TEMP Temperature Concentrator

Anderson Battery Connector

Digital Input/Relay Output Cables

Replacement Modules

Wiring Notes

Wiring Illustrations

SEE ALSO

System Overview

Table of Contents

List Descriptions

Specifications

Accessory Descriptions

Physical Size Information

Related Documentation

Page 9 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

TABLE OF CONTENTS

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

System

Overview

Picture

List

Descriptions

Accessory

Descriptions

Specifications

Physical Size

Information

Related

Documentation

SYSTEM OVERVIEW................................................................................................................................................. 1

58213660001 ......................................................................................................................................................... 4

TABLE OF CONTENTS ........................................................................................................................................... 10

LIST DESCRIPTIONS .............................................................................................................................................. 13

List 1: 1RU High by 19” Wide Shelf............................................................................................................... 13

List 2: 1RU High by 23” Wide Shelf............................................................................................................... 14

List 5: 2RU High by 19” Wide Shelf............................................................................................................... 15

List 6: 2RU High by 23” Wide Shelf............................................................................................................... 16

Rectifier Module (500W), P/N 1R48500 ......................................................................................................... 17

Rectifier Module (1000W), P/N 1R481000 ..................................................................................................... 17

ACU+ (Advanced Control Unit Plus), P/N 1M820BNA .................................................................................. 17

SCU+ (Standard Control Unit Plus), P/N 1M521BNA .................................................................................... 18

List 60: Five (5) Load Lead Assemblies (P/N 535206) for 10A GMT Fuse Positions ................................... 18

List 61: Eight (8) Load Lead Assemblies (P/N 535206) for 10A GMT Fuse Positions ................................. 18

List 62: Five (5) Load Lead Assemblies (P/N 540988) for 15A GMT Fuse Positions ................................... 19

List 65: Shelf Side Battery Cables, P/N 540814 ........................................................................................... 19

List 66: Battery Side Battery Cables, P/N 540954 ........................................................................................ 19

List 67: Battery Cable, P/N 545709 ................................................................................................................ 19

List 71: Optional External Battery Cable Assembly with Anderson Connector for (1) Battery String,

P/N 545493 .................................................................................................................................................... 20

List 72: Optional External Battery Cable Assembly with Anderson Connector for (2) Battery

Strings, P/N 535124 ....................................................................................................................................... 20

List 73: Optional External Battery Cable Assembly with Anderson Connector for (1) Battery String,

P/N 555050 .................................................................................................................................................... 20

List 89: Relay Rack Earthquake Anchor Kit, P/N P0987167 ........................................................................ 21

List 90: Optional Temperature Probe, P/N 04118246 (shelf side half) and P/N 04118247 (probe side half, 9 ft. long) ......................................................................................................................................... 21

List 91: Optional Temperature Probe, P/N 04118246 (shelf side half) and P/N 04116740 (probe side half, 30 ft. long) ....................................................................................................................................... 21

List 93: Battery Tray for 23” Relay Rack ....................................................................................................... 22

List 94: Battery Tray for 19” Relay Rack ....................................................................................................... 25

List BF: Distribution Unit with GMT Fuse Load Distribution Positions and with Low Voltage Battery

Disconnect (LVBD) ......................................................................................................................................... 29

List LF: Distribution Unit with GMT Fuse Load Distribution Positions and with Low Voltage Load

Disconnect (LVLD) ......................................................................................................................................... 30

List NF: Distribution Unit with GMT Fuse Load Distribution Positions and w/out Low Voltage

Disconnect ...................................................................................................................................................... 31

List BC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load

Distribution Positions, and with Low Voltage Battery Disconnect (LVBD) ..................................................... 32

List LC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load

Distribution Positions, and with Low Voltage Load Disconnect (LVLD) ......................................................... 33

List NC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load

Distribution Positions, and w/out Low Voltage Disconnect ............................................................................ 34

List BA: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load

Distribution Positions, Circuit Breaker Battery Disconnect Positions, and with Low Voltage Battery

Disconnect (LVBD) ......................................................................................................................................... 35

Page 10 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

SAG582136600

Issue AU, February 21, 2014

List LA: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load

Distribution Positions, Circuit Breaker Battery Disconnect Positions, and with Low Voltage Load

Disconnect (LVLD) ......................................................................................................................................... 36

List NA: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load

Distribution Positions, Circuit Breaker Battery Disconnect Positions, and w/out Low Voltage

Disconnect ...................................................................................................................................................... 37

List BG: Distribution Unit with GMT Fuse Load Distribution Positions and with Low Voltage Battery

Disconnect (LVBD) ......................................................................................................................................... 38

List NG: Distribution Unit with GMT Fuse Load Distribution Positions and w/out Low Voltage

Disconnect ...................................................................................................................................................... 39

List KG: Distribution Panel with (20) GMT Fuse Load Distribution Positions ............................................... 40

ACCESSORY DESCRIPTIONS ............................................................................................................................... 41

Relay Racks ....................................................................................................................................................... 41

Mounting and Adapter Kits .............................................................................................................................. 42

Optional Wall Mount Bracket Kit for Lists 1 and 2, P/N 541285 .................................................................... 42

Optional Wall Mount Bracket Kit for Lists 1, 2, 5 and 6, P/N 553203 ............................................................ 42

Optional 19” to 23” 1RU Rack Adapter Kit, P/N 540993 ................................................................................ 42

Optional 19” to 23” 2RU Rack Adapter Kit, P/N 545728 ................................................................................ 42

Optional 19” Rear Cover Kit, P/N 555260 ...................................................................................................... 43

Optional 3” Projection Mount Kit for List 1, P/N 556828 ................................................................................ 43

Optional 23” Rear Cover Kit, P/N 555261 ...................................................................................................... 43

Rear Battery Cable Exit Kit P/N 547645 ........................................................................................................ 43

Distribution Devices .......................................................................................................................................... 44

GMT Load Distribution Fuses ........................................................................................................................ 44

Bullet Nose-Type Circuit Breakers ................................................................................................................. 45

Optional Bullet Nose 6-Position GMT Fuse Module, P/N 545332 ................................................................. 46

Optional Bulk Output Busbar, P/N 535015 .................................................................................................... 46

AC Input Cables and Line Cords ..................................................................................................................... 47

AC Input Cable Assembly, P/N 535232 ......................................................................................................... 47

AC Input Line Cord, 208/240VAC, P/N 540946 ............................................................................................. 47

AC Input Line Cord, 208/240VAC, P/N 545616 ............................................................................................. 48

AC Input Line Cord, 120VAC, P/N 545252 .................................................................................................... 48

AC Input Line Cord, 120VAC, P/N 545478 .................................................................................................... 49

AC Input Line Cord, 120VAC, P/N 545479 .................................................................................................... 49

AC Input Line Cord, 208/240VAC, P/N 545480 ............................................................................................. 50

AC Input Line Cord, 120VAC, P/N 545481 .................................................................................................... 50

AC Input Line Cord, 208/240VAC, P/N 545553 ............................................................................................. 51

AC Input Line Cord, 120VAC, P/N 547525 .................................................................................................... 51

AC Input Line Cord, 120VAC, P/N 548457 .................................................................................................... 52

AC Input Line Cord, 120/208/240VAC, P/N 548196 ...................................................................................... 52

Special Application Digital Input Cable Kit, P/N 554935................................................................................ 53

AP6C57EA/EB Ring & Distribution Module .................................................................................................... 53

External Battery Disconnect Unit, P/N 535282 ............................................................................................... 55

NetSure™ 211 BC Battery Cabinet (Spec. No. 541434) ................................................................................... 56

NetSure™ 211 BC Battery Cabinet (Spec. No. 545534) ................................................................................... 57

NetSure™ 211 BC Battery Cabinet (Spec. No. 545506) ................................................................................... 58

NetSure™ 211 BC Battery Cabinet (Spec. No. 554631) ................................................................................... 59

SM TEMP Temperature Concentrator (P/N 547490) ....................................................................................... 60

SM Module RS-485 Interface Cable P/N 547674 ............................................................................................. 60

PCU Blank Filler Panel, P/N PSK4820R-1 ....................................................................................................... 60

Anderson Battery Connector ........................................................................................................................... 61

Digital Input and Relay Output Cables ............................................................................................................ 62

Replacement Modules ...................................................................................................................................... 63

Wiring Notes ...................................................................................................................................................... 64

Shelf Frame Grounding Stud ......................................................................................................................... 64

Page 11 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

AC Input Branch Circuit Protection and Wiring .............................................................................................. 64

External Alarm and Monitoring Wiring ........................................................................................................... 64

Load Distribution Wiring (GMT Fuses) (Lists BG and NG only) .................................................................... 65

Load Distribution Wiring (GMT Fuses) (Lists BF, LF, and NF only) .............................................................. 65

Load Distribution Wiring (GMT Fuses) (Lists BC, LC, NC, BA, LA, and NA)................................................. 66

Load Distribution Wiring (Optional Bullet-Nose-Type 6-Position GMT Fuse Module) ................................... 66

Load Distribution Wiring (Circuit Breakers) (Lists BC, LC, NC, BA, LA, and NA) .......................................... 66

Load Distribution Wiring (GMT Fuses) (List KG) ........................................................................................... 68

CO Ground Wiring (Lists BF, LF, NF, BC, LC, NC, BA, LA, and NA) ............................................................ 68

Input Battery Wiring (List BG and NG) ........................................................................................................... 68

Input Battery Wiring (to Battery Disconnect Circuit Breakers) (Lists BA, LA, and NA) .................................. 68

Input Battery Wiring (to Battery Busbars) (Lists BF, LF, NF, BC, LC, and NC) ............................................. 69

Wiring Illustrations ............................................................................................................................................ 70

Shelf Frame Grounding Stud (both 1U and 2U Panels, List 1 and 5 shown) ................................................ 70

AC Input Wiring (Lists 1 and 2) ...................................................................................................................... 71

AC Input Wiring (Lists 5 and 6) ...................................................................................................................... 72

External Alarm and Monitoring Wiring (Lists 1 and 2).................................................................................... 73

External Alarm and Monitoring Wiring (Lists 5 and 6).................................................................................... 74

Load Distribution Wiring (GMT Fuses) (Lists BG and NG installed in a List 1 or 2, List 1 shown) ................ 79

Load Distribution Wiring (GMT Fuses) (Lists BF, LF, and NF installed in a List 5 or 6, List 5 shown) .......... 80

Load Distribution Wiring (GMT Fuses) (Lists BC, LC, NC, BA, LA, and NA installed in a List 5 or 6,

List 5 shown) .................................................................................................................................................. 81

Load Distribution Wiring (Optional Bullet Nose 6-Position GMT Fuse Module) ............................................ 82

Load Distribution Wiring (Circuit Breakers) and CO Ground Wiring (Lists BC, LC, and NC installed in a List 5 or 6, List 5 shown) ......................................................................................................................... 83

Load Distribution Wiring (Circuit Breakers), Input Battery Wiring (Circuit Breakers), and CO Ground

Wiring (Lists BA, LA, and NA installed in a List 5 or 6, List 5 shown) ............................................................ 84

Load Distribution Wiring (GMT Fuses) (List KG) ........................................................................................... 85

Input Battery Wiring (Lists BG and NG installed in a List 1 or 2, List 1 shown) ............................................. 86

Input Battery Wiring (Lists BF, LF, NF, BC, LC, and NC installed in a List 1 or 5, List 5 shown) and

CO Ground Wiring (Lists BF, LF, and NF installed in a List 1 or 5, List 5 shown) ......................................... 87

SPECIFICATIONS .................................................................................................................................................... 88

1.

System ........................................................................................................................................................... 88

1.1

Environmental Ratings ............................................................................................................................. 88

1.2

Compliance Information ........................................................................................................................... 88

1.3

Standard Features .................................................................................................................................... 89

PHYSICAL SIZE INFORMATION ............................................................................................................................ 91

Overall Dimensions – List 1 ............................................................................................................................. 91

Additional Dimensions – List 1 with Wall Mounting Kit (P/N 541285) .......................................................... 92

Additional Dimensions – List 1 with Optional 19” Rear Cover Kit, P/N 555260 .......................................... 93

Additional Dimensions – List 1 with Optional 3” Projection Mount Kit, P/N 556828 .................................. 94

Overall Dimensions – List 2 ............................................................................................................................. 95

Additional Dimensions – List 2 with Wall Mounting Kit (P/N 541285) .......................................................... 96

Additional Dimensions – List 2 with Optional 23” Rear Cover Kit, P/N 555261 .......................................... 97

Overall Dimensions – List 5 ............................................................................................................................. 98

Overall Dimensions – List 6 ............................................................................................................................. 99

Additional Dimensions – Lists 1, 2, 5 and 6 with Wall Mounting Kit (P/N 553203) ................................... 100

Overall Dimensions – List KG ........................................................................................................................ 101

Overall Dimensions – 19” Battery Tray ......................................................................................................... 102

Overall Dimensions – 23” Battery Tray ......................................................................................................... 103

BATTERY MANUFACTURER INFORMATION .................................................................................................... 104

RELATED DOCUMENTATION .............................................................................................................................. 104

REVISION RECORD .............................................................................................................................................. 105

Page 12 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

SAG582136600

Issue AU, February 21, 2014

LIST DESCRIPTIONS

List 1: 1RU High by 19” Wide Shelf

Features

Home

♦ Consists of a 1RU high by 19” wide shelf.

♦ Two (2) 8 AWG 48” long battery cables are factory connected inside the shelf. These cables are terminated at the customer end in a Red SB50 Anderson battery connector. A mating Anderson battery connector is provided [Housing: Emerson P/N 138922, Anderson Power Products P/N 992G1. Contacts

(two provided): Emerson P/N 247109602, Anderson Power Products P/N 5952].

♦ Mounted to the side of the shelf is an AC input housing with plug-in connector for a single AC input feed.

♦ The “Digital Input and Relay Outputs Cable” P/N 545494 (shelf side) is factory connected inside the shelf.

A mating half is available.

♦ The shelf houses up to two (2) Rectifier Modules, one (1) Controller, and one (1) Distribution Unit.

Restrictions

Each List 1 shelf holds up to two (2) Rectifier Modules.

Ordering Notes

1) Order List 1 as required.

Also order the following as required.

2) Order one (1) SCU+ controller (P/N 1M521BNA ) per shelf. Also specify the appropriate configuration file

for your site.

3) Order up to two (2) Rectifier Modules per shelf: P/N 1R48500 (500W) or P/N 1R481000 (1000W).

4) Order AC Input Cables or Line Cords as required. Note that each List 1 shelf requires one (1) AC Input

Cable or Line Cord.

5) Order one (1) Distribution Unit (List BG

or NG ) per shelf.

6) Order Optional External Battery Cables with Anderson Connector for one (1) to two (2) Battery Strings per

List 71 , 72 or 73 .

7) Order Relay Rack Anchor Kit(s) ( List 89 ) as required.

8) Order up to two (2) Temperature Probes ( List 90 or 91 ) as required. One probe is used with the Battery

Charge Temperature Compensation feature, the other to monitor ambient temperature.

9) Order Battery Trays ( List 94 ) as required.

10) Order Relay Racks per ACCESSORY DESCRIPTIONS section.

11) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.

12) Order External Battery Disconnect Unit per ACCESSORY DESCRIPTIONS section.

13) Order Battery Cabinet per ACCESSORY DESCRIPTIONS section.

14) Order Mating Digital Input/Relay Output Cables per ACCESSORY DESCRIPTIONS section.

15) Order Spare Anderson Battery Connector per ACCESSORY DESCRIPTIONS section.

16) Order Special Application Digital Input Cable Kit per ACCESSORY DESCRIPTIONS section.

Page 13 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

List 2: 1RU High by 23” Wide Shelf

Features

♦ Consists of a 1RU high by 23” wide shelf.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB

Home

)

♦ Two (2) 8 AWG 48” long battery cables are factory connected inside the shelf. These cables are terminated at the customer end in a Red SB50 Anderson battery connector. A mating Anderson battery connector is provided [Housing: Emerson P/N 138922, Anderson Power Products P/N 992G1. Contacts

(two provided): Emerson P/N 247109602, Anderson Power Products P/N 5952].

♦ Mounted to the side of the shelf is an AC input housing with plug-in connector for a single AC input feed.

♦ The “Digital Input and Relay Outputs Cable” P/N 545494 (shelf side) is factory connected inside the shelf.

A mating half is available.

♦ The shelf houses up to three (3) Rectifier Modules, one (1) Controller, and one (1) Distribution Unit.

Restrictions

Each List 2 shelf holds up to three (3) Rectifier Modules.

Ordering Notes

1) Order List 2 as required.

Also order the following as required.

2) Order one (1) SCU+ controller (P/N 1M521BNA ) per shelf. Also specify the appropriate configuration file

for your site.

3) Order up to three (3) Rectifier Modules per shelf: P/N 1R48500 (500W) or P/N 1R481000 (1000W).

4) Order AC Input Cables or Line Cords as required. Note that each List 2 shelf requires one (1) AC Input

Cable or Line Cord.

5) Order one (1) Distribution Unit (List BG

or NG ) per shelf.

6) Order Optional External Battery Cables with Anderson Connector for one (1) to two (2) Battery Strings per

List 71 , 72 or 73 .

7) Order Relay Rack Anchor Kit(s) ( List 89 ) as required.

8) Order up to two (2) Temperature Probes ( List 90 or 91 ) as required. One probe is used with the Battery

Charge Temperature Compensation feature, the other to monitor ambient temperature.

9) Order Battery Trays ( List 93 ) as required.

10) Order Relay Racks per ACCESSORY DESCRIPTIONS section.

11) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.

12) Order External Battery Disconnect Unit per ACCESSORY DESCRIPTIONS section.

13) Order Battery Cabinet per ACCESSORY DESCRIPTIONS section.

14) Order Mating Digital Input/Relay Output Cables per ACCESSORY DESCRIPTIONS section.

15) Order Spare Anderson Battery Connector per ACCESSORY DESCRIPTIONS section.

16) Order Special Application Digital Input Cable Kit per ACCESSORY DESCRIPTIONS section.

Page 14 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

SAG582136600

Issue AU, February 21, 2014

List 5: 2RU High by 19” Wide Shelf

Features

♦ Consists of a 2RU high by 19” wide shelf.

Home

♦ Mounted to the side of the shelf is an AC input housing with plug-in connectors for two (2) AC input feeds.

♦ Includes the Customer Interface Board that provides additional Relay Outputs and Digital Inputs.

♦ The “Relay Outputs Cable” P/N 541308 (shelf side) is factory connected inside the shelf. A mating half is available. A “Digital Input Cable” (shelf side and customer side) is also available.

♦ The shelf houses up to four (4) Rectifier Modules, one (1) Controller, and one (1) Distribution Unit.

Restrictions

Each List 5 shelf holds up to four (4) Rectifier Modules.

Ordering Notes

1) Order List 5 as required.

Also order the following as required.

2) Order one (1) SCU+ controller (P/N 1M521BNA

) or (1) ACU+ controller (P/N 1M820BNA ) per shelf. Also

specify the appropriate configuration file for your site.

3) Order up to four (4) Rectifier Modules per shelf: P/N 1R48500 (500W) or P/N 1R481000 (1000W).

4) Order AC Input Cables or Line Cords as required. Note that each List 5 shelf requires two (2) AC Input

Cables or Line Cords.

5) Order one (1) Distribution Unit (List BF ,

LF ,

NF ,

BC ,

LC ,

NC ,

BA ,

LA

, or NA ) per shelf.

6) Order one (1) List 60 for each List BC, LC, NC, BA, LA, or NA ordered.

Each List 60 provides five (5) Load Lead Assemblies for 10A GMT Fuse Positions.

Order one (1) List 61 for each List BF, LF, or NF ordered.

Each List 61 provides eight (8) Load Lead Assemblies for 10A GMT Fuse Positions.

Order one (1) List 62 for each List BF, LF, or NF ordered.

Each List 62 provides five (5) Load Lead Assemblies for 15A GMT Fuse Positions.

7) Order one (1) List KG Distribution Fuse Panel per shelf, as required.

8) Order three (3) sets of Shelf Side and three (3) sets of Battery Side Battery Cables ( List 65 and List 66 )

for each List BC, LC, NC, BF, LF, or NF ordered.

9) Order up to three (3) List 67 for each List BC, LC, NC, BF, LF, and NF ordered.

10) Order Relay Rack Anchor Kit(s) ( List 89 ) as required.

11) Order up to two (2) Temperature Probes ( List 90 or 91 ) as required. One probe is used with the Battery

Charge Temperature Compensation feature, the other to monitor ambient temperature.

12) Order Battery Trays ( List 94 ) as required.

13) Order Relay Racks per ACCESSORY DESCRIPTIONS section.

14) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.

15) Order External Battery Disconnect Unit per ACCESSORY DESCRIPTIONS section.

16) Order Battery Cabinet per ACCESSORY DESCRIPTIONS section.

17) Order Digital Input/Relay Output Cables per ACCESSORY DESCRIPTIONS section.

18) Order lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section.

Page 15 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

List 6: 2RU High by 23” Wide Shelf

Features

♦ Consists of a 2RU high by 23” wide shelf.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB

Home

)

♦ Mounted to the side of the shelf is an AC input housing with plug-in connectors for two (2) AC input feeds.

♦ Includes the Customer Interface Board that provides additional Relay Outputs and Digital Inputs.

♦ The “Relay Outputs Cable” P/N 541308 (shelf side) is factory connected inside the shelf. A mating half is available. A “Digital Input Cable” (shelf side and customer side) is also available.

♦ The shelf houses up to six (6) Rectifier Modules, one (1) Controller, and one (1) Distribution Unit.

Restrictions

Each List 6 shelf holds up to six (6) Rectifier Modules.

Ordering Notes

1) Order List 6 as required.

Also order the following as required.

2) Order one (1) SCU+ controller (P/N 1M521BNA

) or (1) ACU+ controller (P/N 1M820BNA ) per shelf. Also

specify the appropriate configuration file for your site.

3) Order up to six (6) Rectifier Modules per shelf: P/N 1R48500 (500W) or P/N 1R481000 (1000W).

4) Order AC Input Cables or Line Cords as required. Note that each List 6 shelf requires two (2) AC Input

Cables or Line Cords.

5) Order one (1) Distribution Unit (List BF ,

LF ,

NF ,

BC ,

LC ,

NC ,

BA ,

LA

, or NA ) per shelf.

6) Order one (1) List 60 for each List BC, LC, NC, BA, LA, or NA ordered.

Each List 60 provides five (5) Load Lead Assemblies for 10A GMT Fuse Positions.

Order one (1) List 61 for each List BF, LF, or NF ordered.

Each List 61 provides eight (8) Load Lead Assemblies for 10A GMT Fuse Positions.

Order one (1) List 62 for each List BF, LF, or NF ordered.

Each List 62 provides five (5) Load Lead Assemblies for 15A GMT Fuse Positions.

7) Order one (1) List KG GMT Distribution Fuse Panel per shelf, as required.

8) Order three (3) sets of Shelf Side and three (3) sets of Battery Side Battery Cables ( List 65 and List 66 )

for each List BC, LC, NC, BF, LF, or NF ordered.

9) Order up to three (3) List 67 for each List BC, LC, NC, BF, LF, and NF ordered.

10) Order Relay Rack Anchor Kit(s) ( List 89 ) as required.

11) Order up to two (2) Temperature Probes ( List 90 or 91 ) as required. One probe is used with the Battery

Charge Temperature Compensation feature, the other to monitor ambient temperature.

12) Order Battery Trays ( List 93 ) as required.

13) Order Relay Racks per ACCESSORY DESCRIPTIONS section.

14) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.

15) Order External Battery Disconnect Unit per ACCESSORY DESCRIPTIONS section.

16) Order Battery Cabinet per ACCESSORY DESCRIPTIONS section.

17) Order Digital Input/Relay Output Cables per ACCESSORY DESCRIPTIONS section.

18) Order lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section.

Page 16 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

Rectifier Module (500W), P/N 1R48500

Features

♦ Provides one (1) Model R48-500, Spec. No. 1R48500,

500 watt / 48 volt Rectifier Module.

Restrictions

Each List 1 Shelf holds up to two (2) Rectifier Modules.

Each List 2 Shelf holds up to three (3) Rectifier Modules.

Each List 5 Shelf holds up to four (4) Rectifier Modules.

Each List 6 Shelf holds up to six (6) Rectifier Modules.

DO NOT install different wattage Rectifier Modules in same shelf.

Ordering Notes

1) Order by P/N (1R48500) as required.

Rectifier Module (1000W), P/N 1R481000

Features

♦ Provides one (1) Model R48-1000, Spec. No. 1R481000,

1000 watt / 48 volt Rectifier Module.

Restrictions

Each List 1 Shelf holds up to two (2) Rectifier Modules.

Each List 2 Shelf holds up to three (3) Rectifier Modules.

Each List 5 Shelf holds up to four (4) Rectifier Modules.

Each List 6 Shelf holds up to six (6) Rectifier Modules.

DO NOT install different wattage Rectifier Modules in same shelf.

Ordering Notes

1) Order by P/N (1R481000) as required.

ACU+ (Advanced Control Unit Plus), P/N 1M820BNA

Features

♦ Provides the ACU+ Controller.

♦ Factory programmed with the configuration file specified when ordered.

Restrictions

ACU+ is not available in List 1 or List 2 shelves.

Each List 5 or List 6 shelf must contain one (1) SCU+ or one (1) ACU+

Controller.

Ordering Notes

1) Order one (1) ACU+ (P/N 1M820BNA) or one (1) SCU+ Controller (P/N

1M521BNA) or for each shelf.

For the ACU+ controller, specify also one of the following configurations. a) List 5 and 6 with Low Voltage Disconnect: 550166. b) List 5 and 6 without Low Voltage Disconnect: 550167.

Note: For custom ACU+ configurations, contact Emerson.

SAG582136600

Issue AU, February 21, 2014

Home

Page 17 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

SCU+ (Standard Control Unit Plus), P/N 1M521BNA

Features

♦ Provides the SCU+ Controller.

♦ Factory programmed with the configuration file specified when ordered.

Restrictions

Each shelf must contain one (1) SCU+ or one (1) ACU+ Controller.

Ordering Notes

1) Order one (1) SCU+ Controller (P/N 1M521BNA) or one (1) ACU+ (P/N

1M820BNA) for each shelf.

For the SCU+ controller, specify also one of the following configurations. a) List 1 and 2 with Low Voltage Disconnect: 545304. b) List 1 and 2 without Low Voltage Disconnect: 545305. c) List 5 and 6 with Low Voltage Disconnect: 545298. d) List 5 and 6 without Low Voltage Disconnect: 545299.

Note: For custom SCU+ configurations, contact Emerson.

List 60: Five (5) Load Lead Assemblies (P/N 535206) for 10A GMT Fuse Positions

Features

♦ Provides 12’ long, 16 AWG, load and load return leads that are terminated on one end with the appropriate mating connector to plug into the system’s

10A GMT fuse connector on a List BC, LC, NC, BA, LA, or NA Distribution

Unit, and are left un-terminated at the remaining end for connection into customer loads.

Restrictions

For use with List BC, LC, NC, BA, LA, and NA Distribution units only.

Ordering Notes

1) Order one (1) List 60 for each List BC, LC, NC, BA, LA, or NA Distribution Unit.

Each List 60 provides five (5) GMT fuse load lead assemblies, P/N 535206.

List 61: Eight (8) Load Lead Assemblies (P/N 535206) for 10A GMT Fuse

Positions

Features

♦ Provides 12’ long, 16 AWG, load and load return leads that are terminated on one end with the appropriate mating connector to plug into the system’s 10A

GMT fuse connector on a List BF, LF, or NF Distribution Unit, and are left unterminated at the remaining end for connection into customer loads.

Restrictions

For use with List BF, LF, and NF Distribution units only.

Ordering Notes

1) Order one (1) List 61 for each List BF, LF, or NF Distribution Unit.

Each List 61 provides eight (8) GMT fuse load lead assemblies, P/N 535206.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB

Home

)

Page 18 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

SAG582136600

Issue AU, February 21, 2014

Home

List 62: Five (5) Load Lead Assemblies (P/N 540988) for 15A GMT Fuse Positions

Features

♦ Provides 12’ long, 14 AWG, load and load return leads that are terminated on one end with the appropriate mating connector to plug into the system’s 15A GMT fuse connector on a List BF, LF, or NF Distribution Unit, and are left un-terminated at the remaining end for connection into customer loads.

Restrictions

For use with List BF, LF, and NF Distribution units only.

Ordering Notes

1) Order one (1) List 62 for each List BF, LF, or NF Distribution Unit.

Each List 62 provides five (5) GMT fuse load lead assemblies, P/N 540988.

List 65: Shelf Side Battery Cables, P/N 540814

Features

♦ Provides two (2) 3’ long, 2 AWG, battery cables terminated in a 2-position Red

SB120 Anderson connector (mates with the Anderson connector on List 66).

Remaining end terminated in lugs for connection to shelf.

Restrictions

For use with List BF, LF, NF, BC, LC, and NC Distribution units only.

Ordering Notes

1) Order as required. Each shelf provides landings for up to three (3) battery strings.

List 66: Battery Side Battery Cables, P/N 540954

Features

♦ Provides two (2) 12’ long, 2 AWG, battery cables terminated in a 2-position Red SB120 Anderson connector (mates with the Anderson connector on List 65). Remaining end unterminated for connection to batteries.

Restrictions

For use with List BF, LF, NF, BC, LC, and NC only.

Ordering Notes

1) Order as required. Each shelf provides landings for up to three (3) battery strings.

List 67: Battery Cable, P/N 545709

Features

♦ Provides two (2) 4’ long, 8 AWG, battery cables terminated in a 2-position Anderson connector on the battery side. Remaining end terminated in lugs for connection to shelf.

Restrictions

For use with P/N 541434 ,

P/N 545534

, P/N 545506

, or P/N 554631 battery cabinets only.

For use with List BF, LF, NF, BC, LC, and NC Distribution units only.

Ordering Notes

1) Order up to three (3) List 67 for each List BC, LC, NC, BF, LF, and NF ordered.

2) Order one (1) for each battery cabinet feed required.

Page 19 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

List 71: Optional External Battery Cable Assembly with Anderson Connector for (1) Battery String, P/N 545493

Features

♦ Provides two (2) 6’ long, 8 AWG, battery cables terminated in a Red SB50

Anderson connector for connecting one (1) battery string to the system.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB

Home

)

♦ One end of the assembly connects to the Anderson connector factory wired to the shelf’s battery connection points, and the other end contains two (2) unterminated cables for connection into a customer battery string.

Restrictions

For use with List BG and NG only.

Ordering Notes

1) Order if required.

2) Order Spare Anderson Battery Connector per ACCESSORY DESCRIPTIONS section.

List 72: Optional External Battery Cable Assembly with Anderson Connector for (2) Battery Strings, P/N 535124

Features

♦ Provides four (4) 6’ long, 10 AWG, battery cables terminated in a Red SB50

Anderson connector for connecting two (2) battery strings to the system.

♦ One end of the assembly connects to the Anderson connector factory wired to the shelf’s battery connection points, and the other end contains four (4) unterminated cables for connection into customer battery strings.

Restrictions

For use with List BG and NG Distribution units only.

Ordering Notes

1) Order if required.

2) Order Spare Anderson Battery Connector per ACCESSORY DESCRIPTIONS section.

List 73: Optional External Battery Cable Assembly with Anderson Connector for (1) Battery String, P/N 555050

Features

♦ Provides two (2) 6’ long, 6 AWG, battery cables terminated in a Red SB50

Anderson connector for connecting one (1) battery string to the system.

♦ One end of the assembly connects to the Anderson connector factory wired to the shelf’s battery connection points, and the other end contains two (2) unterminated cables for connection into a customer battery string.

Restrictions

For use with List BG and NG only.

Ordering Notes

1) Order if required.

2) Order Spare Anderson Battery Connector per ACCESSORY DESCRIPTIONS section.

Page 20 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

SAG582136600

Issue AU, February 21, 2014

List 89: Relay Rack Earthquake Anchor Kit, P/N P0987167

Features

♦ Provides four (4) sets of hardware for anchoring the relay rack to the floor.

Home

Ordering Notes

1) Order as required.

List 90: Optional Temperature Probe,

P/N 04118246 (shelf side half) and P/N 04118247 (probe side half, 9 ft. long)

Features

♦ Up to two (2) temperature probes can be connected to the Customer Interface (IB2) Board. Either or both probes can be programmed to monitor ambient temperature or battery temperature.

♦ A temperature probe set as a battery probe can also be designated to be used for the battery charge temperature compensation feature. If the system is equipped with the ACU+ Controller, the battery charge temperature compensation feature can be programmed to use one probe or the average or highest value of all probes programmed to monitor battery temperature. The battery charge temperature compensation feature allows the controller to automatically increase or decrease the output voltage of the system to maintain battery float current as battery temperature decreases or increases, respectively. Battery life can be extended when an optimum charge voltage to the battery with respect to temperature is maintained.

♦ If the system is equipped with the ACU+ Controller, a temperature probe set as a battery probe can also be used for controlling against battery thermal runaway (BTRM feature).

♦ The Temperature Probe assembly consists of two pieces that plug together to make a complete probe.

When ordered, P/N 04118246 (3 feet long) is pre-wired to the shelf and P/N 04118247 (9 feet long) is shipped loose. Total length: 12 ft.

Restrictions

A temperature probe programmed to monitor battery temperature should be mounted on the top or side of a battery cell to sense battery temperature. A temperature probe used for battery charge temperature compensation or BTRM (Battery Thermal Runaway Management) should also be mounted on the top or side of a battery cell. A temperature probe programmed to monitor ambient temperature should be mounted in a convenient location, away from direct sources of heat or cold.

Ordering Notes

1) Order up to two (2) Temperature Probes for each shelf, as required.

Each List 90 includes one (1) P/N 04118246 and one (1) P/N 04118247.

2) For a Temperature Probe with a longer cable see List 91.

List 91: Optional Temperature Probe,

P/N 04118246 (shelf side half) and P/N 04116740 (probe side half, 30 ft. long)

Features

♦ See above for description of Temperature Probes.

♦ The Temperature Probe assembly consists of two pieces that plug together to make a complete probe.

When ordered, P/N 04118246 (3 feet long) is pre-wired to the shelf and P/N 04116740 (30 feet long) is shipped loose. Total Length: 33 ft.

Restrictions

See above for restrictions.

Ordering Notes

1) Order up to two (2) Temperature Probes for each shelf, as required.

Each List 91 includes one (1) P/N 04118246 and one (1) P/N 04116740.

Page 21 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

2) For a Temperature Probe with a shorter cable see List 90.

List 93: Battery Tray for 23” Relay Rack

Features

♦ Provides one battery tray that mounts four (4) 12V front terminal

Valve Regulated Lead Acid (VRLA) batteries. Batteries are configured as one (1) 48V string.

♦ Accepts various VRLA batteries. See Ordering Notes below.

See Overall Dimensions - 23” Battery Tray under PHYSICAL SIZE

INFORMATION for battery tray dimensions and typical arrangement. Note that two battery trays are available to accommodate the various size batteries listed in the Ordering

Notes tables.

♦ Trays can be ordered with or without battery disconnect circuit breakers. When circuit breakers are ordered, one is provided in the -48V lead of each battery string (1 circuit breaker per tray).

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

Home

♦ Battery cables are available terminated at the power system end in an Anderson connector. Battery lugs are available for the remaining end.

Restrictions

For 23” relay racks only.

Maximum number of List 93’s per rack is three (3).

A single List 93 must mount at bottom of rack. Multiple List 93’s must mount starting at bottom of rack and working upward.

Ordering Notes

1) Order multiples of List 93 for more than one (1) battery tray. See

Restrictions above.

2) Order one (1) or more P/N 362736700 Cable Bracket(s) as required.

3) Order batteries separately. Tables A, B, and C list the batteries recommended for use with List 93.

4) Specify rack spacing of 6U (10.5”), 7U (12.25”), or 8U (14”) between trays and above top tray as required for battery clearance. See Tables A, B, and C.

5) Battery lugs are provided, as specified from Table D.

6) Specify with or without battery disconnect circuit breakers.

Note: All List 93 trays in a rack will be furnished with or without battery disconnect circuit breakers as specified for the first tray ordered.

7) If ordering List 93 with circuit breakers, order one (1) circuit breaker per List 93 from Table E.

8) If ordering List 93 with circuit breakers, specify breaker mounting on left side of tray, right side of tray, or remote mounting. Circuit breaker mounting kits shown in the Table E will be installed. Kit numbers are provided for reference only

9) If ordering List 93 with circuit breakers, order Alarm Jumper P/N 524384 for each system to connect the alarm terminal of up to three (3) battery disconnect circuit breakers.

Page 22 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

Battery Tray P/N 528496

Manufacturer* Model

Emerson

Network

Power

P/N

GNB Marathon M12V125FT

GNB Marathon M12V155FT

Northstar NSB110FT

--

112795

--

Northstar NSB170FT --

Deka Unigy I 12AVR-150ET 122018

C&D

C&D

FA 12-150F

TEL12-210F

FA12150

554579

Douglas

Douglas

DGS12-150F

DSN12-170F

125453

--

Rated 8-Hr.

Capacity

(Ah)

125

155

110

167

150

150

202

150

170.8

Dimension

W x L x H

(Inches)

4.90 X 22.00 X 11.15

4.90 X 22.00 X 11.15

4.92 X 22.05 X 8.94

4.92 X 22.05 X 12.60

4.90 X 22.00 X 11.75

4.92 X 21.97 X 12.70

4.90 X 22.00 X 12.80

4.90 X 22.00 X 12.70

4.92 X 22.05 X 12.60

SAG582136600

Issue AU, February 21, 2014

Home

Required

Tray

Spacing

7U

7U

7U

8U

8U

8U

8U

8U

8U

Weight

(per battery)

(lbs)

105

119

91

131

115

131

132

137

130

* See Battery Manufacturer Information located at the end of this document.

Table A

Manufacturer*

Northstar

Northstar

Douglas

Douglas

Enersys

Model

NSB40FT**

NSB60FT**

DGS12-25F

DGS12-50F

12TD50F

Battery Tray P/N 540842

Emerson

Network

Power

P/N

--

--

--

--

--

Rated 8-Hr.

Capacity

(Ah)

38.1

57.9

25

50

48

Dimension

W x L x H

(Inches)

3.80 X 9.80 X 8.20

4.20 X 11.30 X 10.40

3.94 X 10.80 X 7.60

3.94 X 10.80 X 11.60

4.2 X 10.9 X 8.7

Required

Tray

Spacing

* See Battery Manufacturer Information located at the end of this document.

** Batteries MUST be equipped with front access terminal option. See Battery Manufacturer for ordering information.

6U

7U

6U

8U

6U

Weight

(per battery)

(lbs)

34

49

27

48

38

Table B

Manufacturer*

Enersys

Model

12TD150F --

Battery Tray P/N 557573

Emerson

Network

Power

P/N

Rated 8-Hr.

Capacity

(Ah)

143

* See Battery Manufacturer Information located at the end of this document.

Dimension

W x L x H

(Inches)

4.3 X 21.7 X 11.3

Table C

Required

Tray

Spacing

8U

Weight

(per battery)

(lbs)

105

Page 23 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

Battery

Specified

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

Home

Battery Lug Kit Part Number

(Kit provides two lugs for one tray.)

Lists 5 and 6 Lists 1 and 2

GNB Marathon M12V125FT

GNB Marathon M12V155FT

Northstar NSB110FT

Northstar NSB170FT

Deka Unigy I 12AVR-150ET

C&D FA 12-150F

C&D TEL12-210F

Douglas DGS12-150F

Douglas DSN12-170F

Northstar NSB40FT

Northstar NSB60FT

Douglas DGS12-25F

Douglas DGS12-50F

Enersys 12TD50F

Enersys 12TD150F

528234

528236

528234

(for use with 10 AWG wire and List 72)

(for use with 8 AWG wire and L ist 71)

555069

(for use with 6 AWG wire and L ist 73)

Table D

Ampere

Rating

Part No., Circuit Breaker,

Electrical/Mechanical Trip 1

(Black Handle)

Part No., Left-Side

Breaker Mtg. Kit

(For Reference Only)

15

20

25

30

1

3

5

10

256690300

256690700

256691100

256691500

256691900

256692300

256692700

256693100

35

40

50

60

256693500

256693900

256694300

256694700

70

75

256695100

256695500

100 256695900

1 Provides an alarm during an electrical or manual trip condition.

Table E

528501

540989

545581

Part No., Right-Side

Breaker Mtg. Kit

(For Reference Only)

528500

Page 24 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

SAG582136600

Issue AU, February 21, 2014

Home

List 94: Battery Tray for 19” Relay Rack

Features

♦ Provides one battery tray that mounts four (4) 12V front terminal

Valve Regulated Lead Acid (VRLA) batteries. Batteries are configured as one (1) 48V string.

♦ Accepts various VRLA batteries. See Ordering Notes below.

See Overall Dimensions - 19” Battery Tray under PHYSICAL SIZE

INFORMATION for battery tray dimensions and typical arrangement. Note that three battery trays are available to accommodate the various size batteries listed in the Ordering

Notes tables.

♦ Trays can be ordered with or without battery disconnect circuit breakers. When circuit breakers are ordered, one is provided in the -48V lead of each battery string (1 circuit breaker per tray).

♦ Battery cables are available terminated at the power system end in an Anderson connector. Battery lugs are available for the remaining end.

Restrictions

For 19” relay racks only.

Maximum number of List 94’s per rack is three (3).

A single List 94 must mount at bottom of rack. Multiple List 94’s must mount starting at bottom of rack and working upward.

Ordering Notes

1) Order multiples of List 94 for more than one (1) battery tray. See

Restrictions above.

2) Order one (1) or more P/N 362736700 Cable Bracket(s) as required.

3) Order batteries separately. Tables F, G, H and I list batteries recommended for use with List 94.

4) Specify rack spacing of 6U (10.5”), 7U (12.25”), or 8U (14”) between trays and above top tray as required for battery clearance. See

Tables F, G, H and I.

5) Battery lugs are provided, as specified from Table J.

6) Specify with or without battery disconnect circuit breakers.

Note: All List 94 trays in a rack will be furnished with or without battery disconnect circuit breakers as specified for the first tray ordered.

7) If ordering List 94 with circuit breakers, order one (1) circuit breaker per List 94 from Table K.

8) If ordering List 94 with circuit breakers, specify breaker mounting on left side of tray, right side of tray, or remote mounting. Circuit breaker mounting kits shown in the Table K will be installed. Kit numbers are provided for reference only.

9) If ordering List 94 with circuit breakers, order Alarm Jumper P/N 524384 for each system to connect the alarm terminal of up to three (3) battery disconnect circuit breakers.

Page 25 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

Manufacturer*

Northstar

Northstar

GNB Marathon

Enersys

Model

NSB90FT

NSB100FT

M12V90FT

12TD100F4

--

--

--

--

Battery Tray P/N 558047

Emerson

Network

Power

P/N

Rated 8-Hr.

Capacity

(Ah)

90

100

90

96

* See Battery Manufacturer Information located at the end of this document.

Dimension

W x L x H

(Inches)

4.25 X 15.59 X 10.04

4.25 X 15.59 X 11.03

4.13 X 15.55 X 10.63

4.3 X 15.5 X 11.3

System Application Guide

Spec. No. 582136600 (Model 211

Required

Tray

Spacing

7U

7U

7U

8U

NGFB

Home

Weight

(per battery)

(lbs)

71

78

70

71

)

Table F

Manufacturer* Model

GNB Marathon M12V105FT

Enersys 12TD100F6

--

--

Battery Tray P/N 541034

Emerson

Network

Power

P/N

Rated 8-Hr.

Capacity

(Ah)

105

97

* See Battery Manufacturer Information located at the end of this document.

Dimension

W x L x H

(Inches)

4.33 X 20.12 X 9.37

4.3 X 20.0 X 9.4

Required

Tray

Spacing

7U

7U

Weight

(per battery)

(lbs)

79

73

Table G

Manufacturer*

Northstar

Northstar

Douglas

Douglas

Enersys

Model

NSB40FT**

NSB60FT**

DGS12-25F

DGS12-50F

12TD50F

Emerson

Network

Power

P/N

--

--

--

--

--

Battery Tray P/N 540841

Rated 8-Hr.

Capacity

(Ah)

38.1

57.9

25

50

48

Dimension

W x L x H

(Inches)

3.80 X 9.80 X 8.20

4.20 X 11.30 X 10.40

3.94 X 10.80 X 7.60

3.94 X 10.80 X 11.60

4.2 X 10.9 X 8.7

Required

Tray

Spacing

* See Battery Manufacturer Information located at the end of this document.

** Batteries MUST be equipped with front access terminal option. See Battery Manufacturer for ordering information.

6U

7U

6U

8U

6U

Table H

Weight

(per battery)

(lbs)

34

49

27

48

38

Page 26 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

Manufacturer*

Enersys

Enersys

Model

12V125F

12TD150F

Battery Tray P/N 548213

Emerson

Network

Power P/N

122009

--

Rated

8-Hr.

Capacit y (Ah)

125

143

Dimension

W x L x H

(Inches)

4.10 X 22.10 X 12.40

4.3 X 21.7 X 11.3

* See Battery Manufacturer Information located at the end of this document.

SAG582136600

Issue AU, February 21, 2014

Home

Required

Tray

Spacing

8U

8U

Weight

(per battery)

(lbs)

124

105

Table I

Battery

Specified

Battery Lug Kit Part Number

(Kit provides two lugs for one tray.)

Lists 5 and 6 Lists 1 and 2

Northstar NSB90FT

Northstar NSB100FT

GNB Marathon M12V90FT

GNB Marathon M12V105FT

Northstar NSB40FT

Northstar NSB60FT

Douglas DGS12-25F

Douglas DGS12-50F

Enersys 12V125F

Enersys 12TD50F

Enersys 12TD100F4

Enersys 12TD100F6

Enersys 12TD150F

528234

540989

(for use with 10 AWG wire and List 72)

545581

(for use with 8 AWG wire and List 71)

555069

(for use with 6 AWG wire and L ist 73)

Table J

Page 27 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

System Application Guide

Spec. No. 582136600 (Model 211

Ampere

Rating

Part No., Circuit Breaker,

Electrical/Mechanical Trip 1

(Black Handle)

Part No., Left-Side

Breaker Mtg. Kit

(For Reference Only)

60

70

75

100

30

35

40

50

10

15

20

25

1

3

5

256690300

256690700

256691100

256691500

256691900

256692300

256692700

256693100

256693500

256693900

256694300

256694700

256695100

256695500

256695900

1 Provides an alarm during an electrical or manual trip condition.

Table K

528501

Part No., Right-Side

Breaker Mtg. Kit

(For Reference Only)

528500

NGFB

Home

)

Page 28 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

SAG582136600

Issue AU, February 21, 2014

List BF: Distribution Unit with GMT Fuse Load Distribution Positions and with Low Voltage Battery Disconnect (LVBD)

Features

♦ Provides a Distribution Unit with Low Voltage

Battery Disconnect (LVBD), a battery shunt, (3) battery connection points, and thirteen (13) GMT fuse load distribution positions.

Home

♦ Five (5) 0A to 15A GMT fuse load distribution positions.

♦ Eight (8) 0A to 10A GMT fuse load distribution positions.

Restrictions

For use with List 5 and 6 only.

The (13) Position GMT Fuse Printed Wiring Board is rated 100A at +40°C (+104°F) and 59.5A at 65°C

(+149°F).

Unless otherwise specified fuses are mounted from bottom to top, starting with the highest capacity and working to the lowest capacity.

In an ambient of 40°C (+104°F):

• Fuseholders F1-F8 are rated for a 10A fuse maximum. An empty space is not required between fuses of any value.

• Fuseholders F9-F13 are rated for a 15A fuse maximum. An empty space is not required between fuses of any value. However, 15A fuses cannot be placed in adjacent fuseholders. 15A fuses must be separated by a smaller fuse or a space.

In an ambient of 65°C (+149°F):

• Fuseholders F1-F8 are rated for a 10A fuse maximum. An empty space is required between 10A fuses.

A fuse greater than 3A cannot be placed in a fuseholder adjacent to a 10A fuse.

• Fuseholders F9-F13 are rated for a 15A fuse maximum. An empty space is required between 15A fuses.

10A fuses cannot be placed in adjacent fuseholders. A fuse greater than 3A cannot be placed in a fuseholder adjacent to a 10A fuse.

See also the

Restrictions under “ GMT Load Distribution Fuses ” in the ACCESSORY DESCRIPTIONS

section.

Ordering Notes

1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf.

Also order the following as required.

2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.

3) Order one (1) List 61 for each List BF. Each List 61 provides eight (8) GMT fuse load lead assemblies for

the 10A fuse blocks.

4) Order one (1) List 62 for each List BF. Each List 62 provides five (5) GMT fuse load lead assemblies for

the 15A fuse blocks.

5) Order Shelf Side, Battery Side Battery Cables or Output Cables ( List 65 , List 66 or List 67 ) as required.

List 65 and List 67 are factory installed.

6) The controller remains powered when the LVBD contactor opens. Specify if you require List BF to be factory configured for the controller not to be powered when the LVBD contactor opens.

Page 29 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

List LF: Distribution Unit with GMT Fuse Load Distribution Positions

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

Home

and with Low Voltage Load Disconnect (LVLD)

Features

♦ Provides a Distribution Unit with Low Voltage Load

Disconnect (LVLD), a battery shunt, (3) battery connection points, and thirteen (13) GMT fuse load distribution positions.

♦ Five (5) 0A to 15A GMT fuse load distribution positions.

♦ Eight (8) 0A to 10A GMT fuse load distribution positions.

Restrictions

For use with List 5 and 6 only.

The (13) Position GMT Fuse Printed Wiring Board is rated

100A at +40°C (+104°F) and 59.5A at 65°C (+149°F).

Unless otherwise specified fuses are mounted from bottom to top, starting with the highest capacity and working to the lowest capacity.

In an ambient of 40°C (+104°F):

• Fuseholders F1-F8 are rated for a 10A fuse maximum. An empty space is not required between fuses of any value.

• Fuseholders F9-F13 are rated for a 15A fuse maximum. An empty space is not required between fuses of any value. However, 15A fuses cannot be placed in adjacent fuseholders. 15A fuses must be separated by a smaller fuse or a space.

In an ambient of 65°C (+149°F):

• Fuseholders F1-F8 are rated for a 10A fuse maximum. An empty space is required between 10A fuses.

A fuse greater than 3A cannot be placed in a fuseholder adjacent to a 10A fuse.

• Fuseholders F9-F13 are rated for a 15A fuse maximum. An empty space is required between 15A fuses.

10A fuses cannot be placed in adjacent fuseholders. A fuse greater than 3A cannot be placed in a fuseholder adjacent to a 10A fuse.

See also the

Restrictions under “ GMT Load Distribution Fuses ” in the ACCESSORY DESCRIPTIONS

section.

Ordering Notes

1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf.

Also order the following as required.

2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.

3) Order one (1) List 61 for each List LF. Each List 61 provides eight (8) GMT fuse load lead assemblies for

the 10A fuse blocks.

4) Order one (1) List 62 for each List LF. Each List 62 provides five (5) GMT fuse load lead assemblies for

the 15A fuse blocks.

5) Order Shelf Side, Battery Side Battery Cables or Output Cables ( List 65 , List 66 or List 67 ) as required.

List 65 and List 67 are factory installed.

Page 30 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

SAG582136600

Issue AU, February 21, 2014

List NF: Distribution Unit with GMT Fuse Load Distribution Positions and w/out Low Voltage Disconnect

Features

♦ Provides a Distribution Unit w/out low voltage disconnect, a battery shunt, (3) battery connection points, and thirteen (13) GMT fuse load distribution positions.

Home

♦ Five (5) 0A to 15A GMT fuse load distribution positions.

♦ Eight (8) 0A to 10A GMT fuse load distribution positions.

Restrictions

For use with List 5 and 6 only.

The (13) Position GMT Fuse Printed Wiring Board is rated 100A at +40°C (+104°F) and 59.5A at 65°C

(+149°F).

Unless otherwise specified fuses are mounted from bottom to top, starting with the highest capacity and working to the lowest capacity.

In an ambient of 40°C (+104°F):

• Fuseholders F1-F8 are rated for a 10A fuse maximum. An empty space is not required between fuses of any value.

• Fuseholders F9-F13 are rated for a 15A fuse maximum. An empty space is not required between fuses of any value. However, 15A fuses cannot be placed in adjacent fuseholders. 15A fuses must be separated by a smaller fuse or a space.

In an ambient of 65°C (+149°F):

• Fuseholders F1-F8 are rated for a 10A fuse maximum. An empty space is required between 10A fuses.

A fuse greater than 3A cannot be placed in a fuseholder adjacent to a 10A fuse.

• Fuseholders F9-F13 are rated for a 15A fuse maximum. An empty space is required between 15A fuses.

10A fuses cannot be placed in adjacent fuseholders. A fuse greater than 3A cannot be placed in a fuseholder adjacent to a 10A fuse.

See also the

Restrictions under “ GMT Load Distribution Fuses ” in the ACCESSORY DESCRIPTIONS

section.

Ordering Notes

1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf.

Also order the following as required.

2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.

3) Order one (1) List 61 for each List NF. Each List 61 provides eight (8) GMT fuse load lead assemblies for

the 10A fuse blocks.

4) Order one (1) List 62 for each List NF. Each List 62 provides five (5) GMT fuse load lead assemblies for

the 15A fuse blocks.

5) Order Shelf Side, Battery Side Battery Cables or Output Cables ( List 65 , List 66 or List 67 ) as required.

List 65 and List 67 are factory installed.

Page 31 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

List BC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker

Load Distribution Positions, and with Low Voltage Battery Disconnect (LVBD)

Home

Features

♦ Provides a Distribution Unit with Low Voltage Battery

Disconnect (LVBD), a battery shunt, (3) battery connection points, four (4) bullet nose-type circuit breaker load distribution positions, five (5) GMT fuse load distribution positions.

♦ Five (5) 0A to 10A GMT fuse load distribution positions.

Restrictions

For use with List 5 and 6 only.

Maximum distribution current is 72A at @ +65°C (+149°F) and 100A @ +40°C (+104°F).

The GMT fuse block has a 35A @ +40°C (+104°F) and a

21A @ +65°C (+149°F) maximum capacity. Maximum GMT fuse size is 10A. At +65°C (+149°F), a space is required between GMT fuses greater than 5A.

Maximum load distribution circuit breaker size is 75A @ +65°C (+149°F).

Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes

SHALL HAVE an empty mounting position between it and any other overcurrent protective device. There are no restrictions in an ambient of +40°C (+104°F).

See also the

Restrictions under “ GMT Load Distribution Fuses

” and “ Bullet Nose-Type Circuit Breakers ” in

the ACCESSORY DESCRIPTIONS section.

Ordering Notes

1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf.

Also order the following as required.

2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.

3) Order one (1) List 60 for each List BC. Each List 60 provides five (5) GMT fuse load lead assemblies for

the 10A fuse blocks.

4) Order Shelf Side, Battery Side Battery Cables or Output Cables ( List 65 , List 66 or List 67 ) as required.

List 65 and List 67 are factory installed.

5) Order circuit breaker load lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section.

6) The controller remains powered when the LVBD contactor opens. Specify if you require List BC to be factory configured for the controller not to be powered when the LVBD contactor opens.

Page 32 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

SAG582136600

Issue AU, February 21, 2014

List LC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker

Load Distribution Positions, and with Low Voltage Load Disconnect (LVLD)

Features

♦ Provides a Distribution Unit with Low Voltage Load

Disconnect (LVLD), a battery shunt, (3) battery connection points, four (4) bullet nose-type circuit breaker load distribution positions, five (5) GMT fuse load distribution positions.

Home

♦ Five (5) 0A to 10A GMT fuse load distribution positions.

Restrictions

For use with List 5 and 6 only.

Maximum distribution current is 72A at @ +65°C (+149°F) and 100A @ +40°C (+104°F).

The GMT fuse block has a 35A @ +40°C (+104°F) and a

21A @ +65°C (+149°F) maximum capacity. Maximum GMT fuse size is 10A. At +65°C (+149°F), a space is required between GMT fuses greater than 5A.

Maximum load distribution circuit breaker size is 75A @ +65°C (+149°F).

Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes

SHALL HAVE an empty mounting position between it and any other overcurrent protective device. There are no restrictions in an ambient of +40°C (+104°F).

See also the

Restrictions under “ GMT Load Distribution Fuses

” and “ Bullet Nose-Type Circuit Breakers ” in

the ACCESSORY DESCRIPTIONS section.

Ordering Notes

1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf.

Also order the following as required.

2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.

3) Order one (1) List 60 for each List LC. Each List 60 provides five (5) GMT fuse load lead assemblies for

the 10A fuse blocks.

4) Order Shelf Side, Battery Side Battery Cables or Output Cables ( List 65 , List 66 or List 67 ) as required.

List 65 and List 67 are factory installed.

5) Order circuit breaker load lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section.

Page 33 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

List NC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker

Load Distribution Positions, and w/out Low Voltage Disconnect

Home

Features

♦ Provides a Distribution Unit w/out low voltage disconnect, a battery shunt, (3) battery connection points, four (4) bullet nose-type circuit breaker load distribution positions, five (5) GMT fuse load distribution positions.

♦ Five (5) 0A to 10A GMT fuse load distribution positions.

Restrictions

For use with List 5 and 6 only.

Maximum distribution current is 72A at @ +65°C (+149°F) and 100A @ +40°C (+104°F).

The GMT fuse block has a 35A @ +40°C (+104°F) and a

21A @ +65°C (+149°F) maximum capacity. Maximum GMT fuse size is 10A. At +65°C (+149°F), a space is required between GMT fuses greater than 5A.

Maximum load distribution circuit breaker size is 75A @ +65°C (+149°F).

Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes

SHALL HAVE an empty mounting position between it and any other overcurrent protective device. There are no restrictions in an ambient of +40°C (+104°F).

See also the

Restrictions under “ GMT Load Distribution Fuses

” and “ Bullet Nose-Type Circuit Breakers ” in

the ACCESSORY DESCRIPTIONS section.

Ordering Notes

1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf.

Also order the following as required.

2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.

3) Order one (1) List 60 for each List NC. Each List 60 provides five (5) GMT fuse load lead assemblies for

the 10A fuse blocks.

4) Order Shelf Side, Battery Side Battery Cables or Output Cables ( List 65 , List 66 or List 67 ) as required.

List 65 and List 67 are factory installed.

5) Order circuit breaker load lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section.

Page 34 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

SAG582136600

Issue AU, February 21, 2014

List BA: Distribution Unit with GMT Fuse Load Distribution Positions,

Circuit Breaker Load Distribution Positions, Circuit Breaker Battery Disconnect Positions, and with Low Voltage Battery Disconnect (LVBD)

Features

♦ Provides a Distribution Unit with Low Voltage Battery

Disconnect (LVBD), a battery shunt, two (2) bullet nose-type circuit breaker load distribution positions, two

(2) bullet nose-type circuit breaker battery disconnect positions, five (5) GMT fuse load distribution positions.

Home

♦ Five (5) 0A to 10A GMT fuse load distribution positions.

Restrictions

For use with List 5 and 6 only.

Maximum distribution current is 72A at @ +65°C (+149°F) and 100A @ +40°C (+104°F).

The GMT fuse block has a 35A @ +40°C (+104°F) and a

21A @ +65°C (+149°F) maximum capacity. Maximum

GMT fuse size is 10A. At +65°C (+149°F), a space is required between GMT fuses greater than 5A.

Maximum load distribution or battery circuit breaker size is 75A @ +65°C (+149°F).

Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes

SHALL HAVE an empty mounting position between it and any other overcurrent protective device. There are no restrictions in an ambient of +40°C (+104°F).

See also the

Restrictions under “ GMT Load Distribution Fuses

” and “ Bullet Nose-Type Circuit Breakers ” in

the ACCESSORY DESCRIPTIONS section.

Ordering Notes

1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf.

Also order the following as required.

2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.

3) Order one (1) List 60 for each List BA. Each List 60 provides five (5) GMT fuse load lead assemblies for

the 10A fuse blocks.

4) Order circuit breaker load lugs and battery input lugs per Wiring Notes under ACCESSORY

DESCRIPTIONS section.

5) The controller remains powered when the LVBD contactor opens. Specify if you require List BA to be factory configured for the controller not to be powered when the LVBD contactor opens.

Page 35 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

List LA: Distribution Unit with GMT Fuse Load Distribution Positions,

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

Home

Circuit Breaker Load Distribution Positions, Circuit Breaker Battery Disconnect Positions, and with Low Voltage Load Disconnect (LVLD)

Features

♦ Provides a Distribution Unit with Low Voltage Load

Disconnect (LVLD), a battery shunt, two (2) bullet nose-type circuit breaker load distribution positions, two (2) bullet nose-type circuit breaker battery disconnect positions, five (5) GMT fuse load distribution positions.

♦ Five (5) 0A to 10A GMT fuse load distribution positions.

Restrictions

For use with List 5 and 6 only.

Maximum distribution current is 72A at @ +65°C (+149°F) and 100A @ +40°C (+104°F).

The GMT fuse block has a 35A @ +40°C (+104°F) and a 21A @ +65°C (+149°F) maximum capacity.

Maximum GMT fuse size is 10A. At +65°C (+149°F), a space is required between GMT fuses greater than

5A.

Maximum load distribution or battery circuit breaker size is 75A @ +65°C (+149°F).

Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes

SHALL HAVE an empty mounting position between it and any other overcurrent protective device. There are no restrictions in an ambient of +40°C (+104°F).

See also the

Restrictions under “ GMT Load Distribution Fuses

” and “ Bullet Nose-Type Circuit Breakers ” in

the ACCESSORY DESCRIPTIONS section.

Ordering Notes

1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf.

Also order the following as required.

2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.

3) Order one (1) List 60 for each List LA. Each List 60 provides five (5) GMT fuse load lead assemblies for

the 10A fuse blocks.

4) Order circuit breaker load lugs and battery input lugs per Wiring Notes under ACCESSORY

DESCRIPTIONS section.

Page 36 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

SAG582136600

Issue AU, February 21, 2014

List NA: Distribution Unit with GMT Fuse Load Distribution Positions,

Circuit Breaker Load Distribution Positions, Circuit Breaker Battery Disconnect Positions, and w/out Low Voltage Disconnect

Features

♦ Provides a Distribution Unit w/out low voltage disconnect, a battery shunt, two (2) bullet nose-type circuit breaker load distribution positions, two (2) bullet nose-type circuit breaker battery disconnect positions, five (5) GMT fuse load distribution positions.

Home

♦ Five (5) 0A to 10A GMT fuse load distribution positions.

Restrictions

For use with List 5 and 6 only.

Maximum distribution current is 72A at @ +65°C (+149°F) and 100A @ +40°C (+104°F).

The GMT fuse block has a 35A @ +40°C (+104°F) and a

21A @ +65°C (+149°F) maximum capacity. Maximum GMT fuse size is 10A. At +65°C (+149°F), a space is required between GMT fuses greater than 5A.

Maximum load distribution or battery circuit breaker size is 75A @ +65°C (+149°F).

Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes

SHALL HAVE an empty mounting position between it and any other overcurrent protective device. There are no restrictions in an ambient of +40°C (+104°F).

See also the

Restrictions under “ GMT Load Distribution Fuses

” and “ Bullet Nose-Type Circuit Breakers ” in

the ACCESSORY DESCRIPTIONS section.

Ordering Notes

1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf.

Also order the following as required.

2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.

3) Order one (1) List 60 for each List NA. Each List 60 provides five (5) GMT fuse load lead assemblies for

the 10A fuse blocks.

4) Order circuit breaker load lugs and battery input lugs per Wiring Notes under ACCESSORY

DESCRIPTIONS section.

Page 37 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

List BG: Distribution Unit with GMT Fuse Load Distribution Positions and with Low Voltage Battery Disconnect (LVBD)

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

Home

Features

♦ Provides a Distribution Unit with Low Voltage Battery

Disconnect (LVBD), battery cables, and ten (10) GMT fuse load distribution positions (15A maximum).

♦ Two (2) 8 AWG 48” long battery cables are factory connected inside the shelf. These cables are terminated at the customer end in a Red SB50

Anderson battery connector. A mating Anderson battery connector is provided [Housing: Emerson P/N

138922, Anderson Power Products P/N 992G1.

Contacts (two provided): Emerson P/N 247109602, Anderson Power Products P/N 5952].

♦ Ten (10) 0A to 15A GMT fuse load distribution positions.

Restrictions

For use with List 1 and 2 only.

The Distribution Unit has a 50A @ +40°C (+104°F) and 40A @ +65°C (+149°F) maximum capacity.

Maximum GMT fuse size is 15A. In an ambient of +65°C (+149°F), an empty space is required between 15A fuses.

See also the

Restrictions under “ GMT Load Distribution Fuses ” in the ACCESSORY DESCRIPTIONS

section.

Ordering Notes

1) Order one (1) Distribution Unit (List BG or NG) for each List 1 or 2 shelf.

Also order the following as required.

2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.

3) Order Optional External Battery Cables with Anderson Connector for one (1) to two (2) Battery Strings per

List 71 , 72 or 73 .

4) Order Spare Anderson Battery Connector per ACCESSORY DESCRIPTIONS section.

Page 38 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

SAG582136600

Issue AU, February 21, 2014

List NG: Distribution Unit with GMT Fuse Load Distribution Positions and w/out Low Voltage Disconnect

Features

♦ Provides a Distribution Unit w/out low voltage disconnect, a battery shunt, battery cables, and ten

(10) GMT fuse load distribution positions (15A maximum).

Home

♦ Two (2) 8 AWG 48” long battery cables are factory connected inside the shelf. These cables are terminated at the customer end in a Red SB50

Anderson battery connector. A mating Anderson battery connector is provided [Housing: Emerson P/N

138922, Anderson Power Products P/N 992G1.

Contacts (two provided): Emerson P/N 247109602, Anderson Power Products P/N 5952].

♦ Ten (10) 0A to 15A GMT fuse load distribution positions.

Restrictions

For use with List 1 and 2 only.

The Distribution Unit has a 50A @ +40°C (+104°F) and 40A @ +65°C (+149°F) maximum capacity.

Maximum GMT fuse size is 15A. In an ambient of +65°C (+149°F), an empty space is required between 15A fuses.

See also the

Restrictions under “ GMT Load Distribution Fuses ” in the ACCESSORY DESCRIPTIONS

section.

Ordering Notes

1) Order one (1) Distribution Unit (List BG or NG) for each List 1 or 2 shelf.

Also order the following as required.

2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.

3) Order Optional External Battery Cables with Anderson Connector for one (1) to two (2) Battery Strings per

List 71 , 72 or 73 .

4) Order Spare Anderson Battery Connector per ACCESSORY DESCRIPTIONS section.

Page 39 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

List KG: Distribution Panel with (20) GMT Fuse Load Distribution Positions

Home

Features

♦ 1U-high GMT fuse panel that provides Single Load

Distribution (-48V)

♦ Provides twenty (20) 0A to 15A GMT fuse load distribution positions.

Caution: At +40°C and +65°C ambient, a fuse with a rating of greater than 10 amperes SHALL

HAVE an empty mounting position between it and any other fuse.

♦ Maximum Capacity: 80A @ +40°C and 80A @ +65°C

♦ Factory mounted and connected to List 5 or 6 shelf.

♦ If the Distribution Unit in the system is equipped with Low Voltage Load Disconnect (LVLD), all List KG loads are disconnected.

♦ If one or more distribution fuses opens, one set of Form-C relay contacts changes state, and resistive battery is provided to an alarm terminal. Alarm circuit is factory connected to activate the Power System

Controller fuse alarm

Restrictions

For use with List 5 and 6 only.

Mounts only immediately above List 5 or 6 shelf.

Maximum distribution current is 80A.

See also the

Restrictions under “ GMT Load Distribution Fuses ” in the ACCESSORY DESCRIPTIONS

section.

Ordering Notes

1) Order one (1) List KG GMT Distribution Fuse Panel Assembly for each List 5 or 6 shelf as required.

Also order the following as required.

2) Order GMT Load Distribution Fuses per ACCESSORY DESCRIPTIONS section.

Page 40 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

SAG582136600

Issue AU, February 21, 2014

ACCESSORY DESCRIPTIONS

Relay Racks

Features

Home

♦ The following relay racks are available.

Restrictions

Customer must mount Power/Distribution Shelf in relay rack. If battery trays are ordered, they are factory mounted in the relay rack.

Ordering Notes

1) Order from relay racks listed in Table 1.

Part

Number

543156

543161

543160

543162

543163

543164

525003

534653

524961

534654

Size

7’0” H x 23” W

Available Mounting

Positions (1RU = 1-3/4”)

23” Relay Racks

51-3/8” H x 23” W

6’0” H x 23” W

28RU

37RU

45RU

7’0” H x 23” W

7’6” H x 23” W

8’0” H x 23” W

45RU

48RU

51RU

19” Relay Racks

51-3/8” H x 19” W 28RU

6’0" H x 19” W

6’0” H x 19” W

6’6” H x 19” W

37RU

37RU

41RU

534651

528183

6’6” H x 19” W

7’0” H x 19” W

41RU

45RU

524988

524963

534652

7’0” H x 19”W

7’6” H x 19” W

8’0" H x 19” W

45RU

48RU

51RU

Note 1: Complies with Bellcore Seismic Zone 4 requirements.

Table 1

Available Relay Racks

Notes

Welded

Welded

Seismic

(Note 1)

Welded

Welded

Welded

Welded

Seismic

(Note 1)

Welded

Seismic

(Note 1)

Welded

Seismic

(Note 1)

Welded

Welded

Welded

Page 41 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

Mounting and Adapter Kits

Optional Wall Mount Bracket Kit for Lists 1 and 2, P/N 541285

Features

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

Home

♦ Allows for horizontal or vertical wall mounting.

See Physical Size Information for mounting dimensions.

Restrictions

For use with List 1 or 2 only.

Customer must supply mounting fasteners for securing the Wall Mount

Bracket to the wall.

This Kit will not support wall-mounting when the 58213660001 and

58213660002 shelves are flush mounted.

Ordering Notes

1) Order P/N 541285, which consists of two (2) P/N 545701 horizontal wall mounting brackets and two (2)

P/N 541284 vertical wall mounting brackets, and eight (8) 12-24 x ½” screws for attaching the brackets to the shelf.

Optional Wall Mount Bracket Kit for Lists 1, 2, 5 and 6, P/N 553203

Features

♦ Allows for vertical wall mounting.

See Physical Size Information for mounting dimensions.

Restrictions

Customer must supply mounting fasteners for securing the Wall Mount Brackets to the wall.

Ordering Notes

1) Order P/N 553203, which consists of two (2) wall brackets (P/N 553058 and 553059) and eight (8) 12-24 x ¾” screws with four (4) ground washers for attaching the brackets to the shelf.

Optional 19” to 23” 1RU Rack Adapter Kit, P/N 540993

Features

♦ Allows for 23” 1RU relay rack mounting

Restrictions

For use with List 1 only.

Ordering Notes

1) Order P/N 540993, which consists of two (2) P/N 540994 adapters and four (4) 12-24 x 1/”2 thread forming screws.

Optional 19” to 23” 2RU Rack Adapter Kit, P/N 545728

Features

♦ Allows for 23” 2RU relay rack mounting

Restrictions

For use with List 5 only.

Ordering Notes

1) Order P/N 545728, which consists of two (2) P/N 545727 adapters and four (4) 12-24 x 1/”2 thread forming screws.

Page 42 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

SAG582136600

Issue AU, February 21, 2014

Optional 19” Rear Cover Kit, P/N 555260

Features

♦ Allows for 19” 1RU flush rack mount configuration

♦ AC input unit is moved to the rear panel

Restrictions

For use with List 1 only.

Ordering Notes

Home

1) Order P/N 555260, which consists of one (1) P/N

553271 19” rear cover assembly, one (1) P/N 29041838 caution label and one (1) P/N PSK04118562 AC input jumper.

Optional 3” Projection Mount Kit for List 1, P/N 556828

Features

♦ Allows for 19" 1RU 3" projection rack mount configuration

Restrictions

For use with List 1 only.

Ordering Notes

1) Order by P/N 556828 as required.

Optional 23” Rear Cover Kit, P/N 555261

Features

♦ Allows for 23” 1RU flush rack mount configuration

♦ AC input unit is moved to the rear panel

Restrictions

For use with List 2 only.

Ordering Notes

1) Order P/N 555261, which consists of one (1) P/N

555113 23” rear cover assembly, one (1) P/N

29041838 caution label and one (1) P/N

PSK04118555 AC input jumper.

Rear Battery Cable Exit Kit P/N 547645

Features

♦ Provides 12” battery cables exiting rear of shelf

Restrictions

For use with List 5 only.

Ordering Notes

1) For use with Battery Cabinets only.

Page 43 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

Distribution Devices

GMT Load Distribution Fuses

Features

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

Home

♦ Each List BF, LF, NF Distribution Unit holds up to five (5) 0-15A GMT load distribution fuses and eight (8)

0-10A GMT load distribution fuses.

♦ Each List BC, LC, NC, BA, LA, NA Distribution Unit holds up to five (5) 0-10A GMT load distribution fuses.

♦ Each List BG and NG Distribution Unit holds up to ten (10) 0-15A GMT load distribution fuses.

♦ Each List KG Distribution Panel holds up to twenty (20) 0-15A GMT load distribution fuses.

Restrictions

When used for power distribution, load should not exceed 80% of device rating, except 10 and 15 ampere fuses, for which load should not exceed 70% of device rating.

See also the Restrictions for each Distribution Unit in the LIST DESCRIPTIONS section.

See also Load Distribution Wiring (GMT Fuses) (Lists BG and NG only) , Load Distribution Wiring (GMT

Fuses) (Lists BF, LF, and NF only)

, and Load Distribution Wiring (GMT Fuses) (Lists BC, LC, NC, BA, LA, and NA) under WIRING NOTES for additional wiring restrictions.

Ordering Notes

1) Order GMT fuses per Table 2.

Ampere Rating

18/100 GMT-A

1/4

1/2

3/4

1-1/3

2

3

P/N

248610301

248610200

248610300

248610500

248610700

248610800

248610900

5

7-1/2

10

15

248611000

248611300

248611200

248611500

Replacement

Dummy Fuse

Replacement Safety

Fuse Cover

Lists BF, LF, NF,

BC, LC, NC,

BA, LA, NA and KG

248872600

102774

Lists BG and NG

Table 2

GMT Fuses

248898700

Fuse Color

--

Violet

Red

Brown

White

Orange

Blue

Green

Black-White

Red-White

Red-Blue

---

--

Page 44 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

SAG582136600

Issue AU, February 21, 2014

Bullet Nose-Type Circuit Breakers

Features

Home

♦ Each List BC, LC, and NC Distribution Unit holds up to four (4) bullet nose-type load distribution circuit breakers.

♦ Each List BA, LA, and NA Distribution Unit holds up to two (2) bullet nose-type battery disconnect circuit breakers and up to two (2) bullet nose-type load distribution circuit breakers.

Restrictions

See also the Restrictions for each Distribution Unit in the LIST DESCRIPTIONS section.

See also Load Distribution Wiring (Circuit Breakers) (Lists BC, LC, NC, BA, LA, and NA)

and Input Battery

Wiring (to Battery Disconnect Circuit Breakers) (Lists BA, LA, and NA) under WIRING NOTES for additional

wiring restrictions.

Ordering Notes

1) Order circuit breakers per Table 3.

60

70

75

80

35

40

45

50

90

100

15

20

25

30

1

3

5

10

Ampere

Rating

P/N

Electrical Trip 1

(White Handle)

Electrical/

Mechanical Trip

(Black Handle)

2

102272

102273

102274

102275

102276

102277

102278

102279

102280

102281

121998

102282

102283

102284

102285

121996

101596

101597

101598

101599

101600

101601

101602

101603

101604

101605

121997

101606

101607

101608

101609

121995

138887

102286

138888

101610

See Table 6 for recommended wire sizes and lugs.

Circuit Breaker Alarm Operation:

2

Provides an alarm during an electrical trip condition only.

Provides an alarm during an electrical or manual trip condition.

Note that Electrical Trip only circuit breakers are not typically used for battery disconnect circuit breakers.

Table 3

Bullet Nose-Type Circuit Breakers

Page 45 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

Optional Bullet Nose 6-Position GMT Fuse Module, P/N 545332

Features

♦ Factory installed in a List BC, LC, NC, BA, LA, and NA Distribution Unit.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB

Home

)

♦ Provides six (6) 0A to 15A GMT fuse load distribution positions.

♦ Screw clamp type load and load return terminals provided.

♦ Includes six (6) dummy fuses equipped with safety fuse covers.

Restrictions

For use with Lists BC, LC, NC, BA, LA, and NA.

Terminal block wire size capacity: 24 to 14 AWG.

Requires two (2) bullet device mounting positions.

Fuse Module has a 30A @ +40°C (+104°F) and +65°C (+149°F) maximum capacity. Maximum GMT fuse size is 15A. Fuses are to be loaded from bottom to top with highest value in the lowest position.

Caution: A fuse with a rating greater than 10 amperes SHALL HAVE an empty mounting position between it and any other overcurrent protective device.

See also the

Restrictions under “ GMT Load Distribution Fuses ” in the ACCESSORY DESCRIPTIONS

section.

Factory installed only.

Ordering Notes

1) Order optional Bullet Nose-Type 6-Position GMT Fuse Module (P/N 545332) as required.

2) Order GMT fuses as required per Table 2.

Optional Bulk Output Busbar, P/N 535015

Features

♦ Each Bulk Output Busbar installs in a single circuit breaker position in a List BC, LC, NC, BA, LA, and NA Distribution Unit.

Restrictions

For use with Lists BC, LC, NC, BA, LA, and NA.

Ordering Notes

1) Order by P/N 535015 as required.

Page 46 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

SAG582136600

Issue AU, February 21, 2014

Home

AC Input Cables and Line Cords

AC Input Cable Assembly, P/N 535232

Features

♦ Provides one (1) 30” long, 8 AWG, AC Input Cable Assembly;

♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf,

♦ and the remaining end un-terminated.

Restrictions

Rated for 30A.

For use with List 1, 2, 5, and 6.

Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord.

Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords.

Ordering Notes

1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 and 2 ordered.

2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 and 6 ordered.

AC Input Line Cord, 208/240VAC, P/N 540946

Features

♦ Provides one (1) 14’ long, 8 AWG, AC Input Line Cord;

♦ terminated on one end with a Molex plug which mates with AC input receptacle on the

Power/Distribution Shelf,

♦ and on the remaining end with a NEMA L6-30P twist-lock plug.

Restrictions

For 208/240 VAC only (rated for 30A at 208/240VAC).

For use with List 1, 2, 5, and 6.

Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord.

Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords.

Ordering Notes

1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 and 2 ordered.

2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 and 6 ordered.

Page 47 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

AC Input Line Cord, 208/240VAC, P/N 545616

Features

♦ Provides one (1) 6’ long, 8 AWG, AC Input Line Cord;

♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf,

System Application Guide

Spec. No. 582136600 (Model 211 NGFB

Home

)

♦ and on the remaining end with a NEMA L6-30P twist-lock plug.

Restrictions

For 208/240 VAC only (rated for 30A at 208/240VAC).

For use with List 1, 2, 5, and 6.

Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord.

Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords.

Ordering Notes

1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 and 2 ordered.

2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 and 6 ordered.

AC Input Line Cord, 120VAC, P/N 545252

Features

♦ Provides one (1) 14’ long, 8 AWG, AC Input Line Cord;

♦ terminated on one end with a Molex plug which mates with AC input receptacle on the

Power/Distribution Shelf,

♦ and on the remaining end with a NEMA L5-30P twist-lock plug.

Restrictions

For 120 VAC only (rated for 30A at 120VAC).

For use with List 1, 2, 5, and 6.

Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord.

Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords.

Ordering Notes

1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 and 2 ordered.

2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 and 6 ordered.

Page 48 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

SAG582136600

Issue AU, February 21, 2014

Home

AC Input Line Cord, 120VAC, P/N 545478

Features

♦ Provides one (1) 14’ long, 14/3 AWG, AC Input Line Cord;

♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf,

♦ and on the remaining end with a NEMA 5-15P plug.

Restrictions

For 120 VAC only (rated for 15A at 120VAC).

For use with List 1 and 5 equipped with R48-500 Rectifier Modules.

Each List 1 requires one (1) AC Input Cable Assembly/Line Cord.

Each List 5 requires two (2) AC Input Cable Assemblies/Line Cords.

Ordering Notes

1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 ordered.

2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 ordered.

AC Input Line Cord, 120VAC, P/N 545479

Features

♦ Provides one (1) 14’ long, 14/3 AWG, AC Input Line Cord;

♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf,

♦ and on the remaining end with a NEMA L5-15P twist-lock plug.

Restrictions

For 120 VAC only (rated for 15A at 120VAC).

For use with List 1 and 5 equipped with R48-500 Rectifier Modules.

Each List 1 requires one (1) AC Input Cable Assembly/Line Cord.

Each List 5 requires two (2) AC Input Cable Assemblies/Line Cords.

Ordering Notes

1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 ordered.

2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 ordered.

Page 49 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

AC Input Line Cord, 208/240VAC, P/N 545480

Features

♦ Provides one (1) 14’ long, 14/3 AWG, AC Input Line Cord;

System Application Guide

Spec. No. 582136600 (Model 211

♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf,

NGFB

Home

)

♦ and on the remaining end with a NEMA L6-15P twist-lock plug.

Restrictions

For 240 VAC only (rated for 15A at 208/240VAC).

For use with List 1 and 5.

For use with List 2 and 6 with R48-500 Rectifiers.

Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord.

Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords.

Ordering Notes

1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 ordered.

2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 ordered.

AC Input Line Cord, 120VAC, P/N 545481

Features

♦ Provides one (1) 14’ long, 12/3 AWG, AC Input Line Cord;

♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf,

♦ and on the remaining end with a NEMA L5-20P twist-lock plug.

Restrictions

For 120 VAC only (rated for 20A at 120VAC).

For use with List 1 and 5.

For use with List 2 and 6 with R48-500 Rectifiers.

Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord.

Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords.

Ordering Notes

1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 ordered.

2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 ordered.

Page 50 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

SAG582136600

Issue AU, February 21, 2014

Home

AC Input Line Cord, 208/240VAC, P/N 545553

Features

♦ Provides one (1) 14’ long, 12/3 AWG, AC Input Line Cord;

♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf,

♦ and on the remaining end with a NEMA L6-20P twist-lock plug.

Restrictions

For 240 VAC only (rated for 20A at 208/240VAC).

For use with List 1, 2, 5, and 6.

Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord.

Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords.

Ordering Notes

1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 and 2 ordered.

2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 and 6 ordered.

AC Input Line Cord, 120VAC, P/N 547525

Features

♦ Provides one (1) 14’ long, 12/3 AWG, AC Input Line Cord;

♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf,

♦ and on the remaining end with a NEMA L5-30P twist-lock plug.

Restrictions

For 120 VAC only (rated for 30A at 120VAC).

For use with List 1, 2, 5, and 6.

Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord.

Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords.

Ordering Notes

1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 and 2 ordered.

2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 and 6 ordered.

Page 51 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

AC Input Line Cord, 120VAC, P/N 548457

Features

♦ Provides one (1) 6’ long, 14/3 AWG, AC Input Line Cord;

♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf,

System Application Guide

Spec. No. 582136600 (Model 211 NGFB

Home

)

♦ and on the remaining end with a NEMA 5-15P plug.

Restrictions

For 120 VAC only (rated for 15A at 120VAC).

For use with List 1 and 5 with R48-500 Rectifiers.

Each List 1 requires one (1) AC Input Cable Assembly/Line Cord.

Each List 5 requires two (2) AC Input Cable Assemblies/Line Cords.

Ordering Notes

1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 ordered.

2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 ordered.

AC Input Line Cord, 120/208/240VAC, P/N 548196

Features

♦ Provides one (1) 6’ long, 12/3 AWG, AC Input Line Cord;

♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf,

♦ and on the remaining end with an IEC320 C20 plug.

Restrictions

For 120/208/240 VAC (rated for 20A at 120/208/240VAC).

For 208/240V use with List 1, 2, 5, and 6 and all Rectifier Modules.

For 120V use with List 1 and 5 and all Rectifier Modules.

For 120V use with List 2 and 6 with 500W Rectifier Module only.

Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord.

Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords.

Per UL 60950-1, 2nd Edition, when this cord is used with this power system, the following restrictions apply:

• The power system must be used “in a location having equipotential bonding (such as a telecommunications centre, a dedicated computer room or a restricted access location).

• “The building installation shall provide a means for connection to protective earth; and

• “The equipment is to be connected to that means; and

• “A service person shall check whether or not the socket-outlet from which the equipment is to be powered provides a connection to the building protective earth. If not, the service person shall arrange for the installation of a protective earthing conductor from the separated protective earthing terminal to the protective earth wire in the building.”

Ordering Notes

1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 and 2 ordered.

2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 and 6 ordered.

Page 52 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

SAG582136600

Issue AU, February 21, 2014

Special Application Digital Input Cable Kit, P/N 554935

Features

♦ Provides an alarm cable kit to add -48VDC to digital input #2.

Home

♦ The kit consists of two pieces that plug together to make a complete connection. One part is pre-wired to the shelf and the other part is shipped loose.

Restrictions

For use with List 1 and 2.

Ordering Notes

1) Order one (1) Special Application Digital Input Cable Kit as required for each List 1 and 2 ordered.

AP6C57EA/EB Ring & Distribution Module

Features

When used with List 6 , this module is designed to

supply a filtered and regulated –48 VDC source and a continuous 20 Hz ringing supply source to imbedded subscriber loop carrier telecommunication systems

(such as SLC-96 or SLC Series-5) requiring up to 45

A of load capacity.

♦ Designed to mount in a 23” relay rack, the module is one rack unit high, with 5” front projection.

♦ Includes two (2) 50VA ringers with automatic transfer capability (N+1 redundancy).

♦ Provides 35 DC distribution fuse positions, configured in five groups of seven, feeding five channel banks.

Includes 35 dummy fuses.

♦ Connectorized cables are available for SLC-96 or SLC Series-5 applications. Required DC distribution fuses are included with each cable assembly ordered.

♦ An Order Wire Option provides a connection interface for an analog communication link over a metallic pair, with surge protection.

♦ See Ring & Distribution Module Installation and User Manuals (IM6C57E and UM6C57E) for complete specifications.

Restrictions

Cannot be used with Distribution units List BF, LF, or NF.

Ordering Notes

1) For a Ring & Distribution Module equipped with two (2) 50VA ringers only, order AP6C57EA (A7000626).

2) For a Ring & Distribution Module equipped with two (2) 50VA ringers and the Order Wire option, order

AP6C57EB (A7000796).

3) Order distribution cable assemblies as required, from the following table. Order up to five (5) cable assemblies (one per channel bank). Required fuses are included with each cable assembly. Cable assemblies can be mixed.

Page 53 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

System Application Guide

Spec. No. 582136600 (Model 211

ORDERING CODE DESCRIPTION

P7000858

P7001139

P7000859

Cable assy for one SLC96 channel bank (8 ft.)

Cable assy for one SLC96 channel bank (20 ft.)

Cable assy for one SLC5 channel bank (8 ft.)

P7001136

P7000937*

Cable assy for one SLC5 channel bank (20 ft.)

Cable assy for one channel bank, generic applications (8 ft.)

*Note: Each channel bank position on the panel has a maximum capacity of 11A.

NGFB

Home

)

4) Order Part No. 547491 DC power cable kit, as required. Provides two (2) 9” long cables to connect between a power shelf and the DC input terminals of one (1) Ring & Distribution Module.

5) For SLC-96 or SLC Series-5 applications, order battery cable kits as required, from the following table.

ORDERING

CODE

DESCRIPTION

547646

547647

Battery cable kit for SLC96 legacy power shelf (Tyco Mate-N-Lock connectors) - for 2 battery strings, Up to 3 cable kits can be installed in the power shelf with Distribution units BC, LC, and NC. Two cable kits can be installed in DU Lists BA, LA, and NA. (Use a flat washer, not provided.)

Battery cable for SLC5 legacy power shelf (Tyco Mate-N-Lock connectors) - for

2 battery strings, Up to 3 cable kits can be installed in the power shelf with Distribution units BC, LC, and NC. Two cable kits can be installed in DU Lists BA, LA, and NA. (Use a flat washer, not provided.)

6) Spare parts for the AP6C57EA/EB Ring & Distribution Module can be ordered as required from the following table.

ORDERING CODE DESCRIPTION

A0885525

A0885530

A0885531

1.33A Alarm SAN-O Fuse

3A Alarm SAN-O Fuse

5A Alarm SAN-O Fuse

A0885532 10A Alarm SAN-O Fuse

A7000627 (AP8C55AA) 50VA Ring Generator

Page 54 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

SAG582136600

Issue AU, February 21, 2014

Home

External Battery Disconnect Unit, P/N 535282

Features

♦ Battery Disconnect Unit with mounting tabs.

♦ Two 1/4-20 studs w/hardware provided for installation of single hole battery lugs.

♦ One (10’ long) alarm lead provided.

Restrictions

Circuit breakers are ordered separately.

Maximum number of Battery Disconnect Units per system is three (3).

Ordering Notes

1) Order by P/N 535282 as required.

2) Order a circuit breaker for each Battery Disconnect Unit from Table 4.

3) Also order the following lug kits for each battery disconnect circuit breaker ordered: 545581(for use with 8 AWG wire and List 71), 540989

(for use with 10 AWG wire and List 72) or 555069 (for use with 6 AWG wire and List 73) and 541031 (wire with lugs for connection from battery disconnect to battery string).

4) Also order P/N 524384 Jumper/Alarm Lead if more than one (1) Battery

Disconnect Units are to be used (daisy-chains the alarm terminal of up to three [3] Battery Disconnect Units). (Section of alarm lead between

Battery Disconnect Units is 30”, section of alarm lead between Battery

Disconnect Unit and system’s alarm terminal is 84”.)

Yellow Jumper/Alarm Lead (P/N 524384)

(for use when more than one Battery

Disconnect Units are ordered)

Ampere

Rating

P/N

Electrical/Mechanical

Trip 1

(Black Handle)

Ampere

Rating

P/N

Electrical/Mechanical

Trip 1

(Black Handle)

1

3

5

10

256690300

256690700

256691100

256691500

35

40

50

60

15

20

25

30

256691900

256692300

256692700

256693100

70

75

100

Circuit Breaker Alarm Operation:

Provides an alarm during an electrical or manual trip condition.

Table 4

Battery Disconnect Unit Circuit Breakers

256693500

256693900

256694300

256694700

256695100

256695500

256695900

Page 55 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

NetSure™ 211

BC

Battery Cabinet (Spec. No. 541434)

Features

♦ The NetSure™ 211 BC Battery Cabinet is rated at

30 amperes, and can be mounted in a 19” or 23” nominal relay rack, or mounted to a suitable wall.

♦ The Battery Cabinet contains one (1) 40 ampere battery disconnect circuit breaker.

♦ Battery circuit breaker alarm leads are provided to tie into the power system’s alarm circuit.

♦ The Battery Cabinet is equipped with a battery cable terminated in an Anderson connector.

♦ Cables to connect the batteries (as specified in the table under Order Notes) into the Battery

Cabinet provided.

♦ Battery Cabinets can be paralleled to provide greater reserve time. Battery cabinets contain a second Anderson battery connector for plugging one cabinet into another.

Ordering Notes

1) Order by Spec. No. 541434 as required.

2) Also order four (4) batteries per Battery Cabinet per the following table.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

Home

Battery

Manufacturer

Hawker

Fiamm

EaglePicher

EaglePicher

Enersys

* 10Hr rate

Manufacturer

P/N

SBS 15

12SLA12

HE-12V7.7FR

HE-12V12.7FR

NP18-12FR

Emerson

P/N

139091

139092

139094

139093

139774

Capacity Amp-Hours

(8Hr rate)

14

12

6.9

11.6*

16 *

Weight (lb) per Battery

12.50

12.35

5.94

9.68

13.60

3) When ordering 139774 batteries, also order 545427 Battery Connection kit.

4) When wall mounted, also order a battery cabinet frame grounding landing point adapter P/N 556872.

This adapter installs in the relay rack mounting bracket holes located on either side of the cabinet.

Frame Grounding Point

(1/4-20 Studs on 5/8” Centers)

Frame Ground Landing

Point Adapter P/N 556872

Attach Frame Ground Landing

Point Adapter to Cabinet

Page 56 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

SAG582136600

Issue AU, February 21, 2014

Home

NetSure™ 211

BC

Battery Cabinet (Spec. No. 545534)

Features

♦ The NetSure™ 211 BC Battery Cabinet is rated at 30 amperes, and can be mounted in a 19” or 23” nominal relay rack, or mounted to a suitable wall.

♦ The Battery Cabinet contains one (1) 40 ampere battery disconnect circuit breaker.

♦ Battery circuit breaker alarm leads are provided to tie into the power system’s alarm circuit.

♦ The Battery Cabinet is equipped with a battery cable terminated in an Anderson connector.

♦ Cables to connect the batteries (as specified in the table under Ordering Notes) into the Battery Cabinet provided.

♦ Battery Cabinets can be paralleled to provide greater reserve time. Battery cabinets contain a second

Anderson battery connector for plugging one cabinet into another.

Ordering Notes

1) Order by Spec. No. 545534 as required.

2) Also order four (4) batteries per Battery Cabinet per the following table.

Battery

Manufacturer

Enersys

C&D / Dynasty

Manufacturer

P/N

SBS B10

TEL12-30

Emerson P/N Capacity Amp-Hours

(8Hr rate)

140553

140455

38

30.5

Weight (lb) per Battery

28.20

26.70

3) When wall mounted, also order a battery cabinet frame grounding landing point adapter P/N 556872.

This adapter installs in the relay rack mounting bracket holes located on either side of the cabinet.

Frame Grounding Point

(1/4-20 Studs on 5/8” Cente

rs)

Frame Ground Landing

Point Adapter P/N 556872

Attach Frame Ground Landing

Point Adapter to Cabinet

Page 57 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

NetSure™ 211

BC

Battery Cabinet (Spec. No. 545506)

Features

♦ The NetSure™ 211 BC Battery Cabinet is rated at 30 amperes, and can be mounted in a 23” nominal relay rack, or mounted to a suitable wall.

♦ The Battery Cabinet contains one (1) 40 ampere battery disconnect circuit breaker.

♦ Battery circuit breaker alarm leads are provided to tie into the power system’s alarm circuit.

♦ The Battery Cabinet is equipped with a battery cable terminated in an Anderson connector.

♦ Cables to connect the batteries (as specified in the table under Ordering Notes) into the Battery Cabinet provided.

♦ Battery Cabinets can be paralleled to provide greater reserve time. Battery cabinets contain a second

Anderson battery connector for plugging one cabinet into another.

Ordering Notes

1) Order by Spec. No. 545506 as required.

2) Also order four (4) batteries per Battery Cabinet per the following table.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

Home

Battery

Manufacturer

Enersys

Enersys

C&D/ Dynasty

C&D/ Dynasty

Manufacturer

P/N

SBS B10

SBS 40

TEL12-30

TEL12-45

Emerson P/N Capacity Amp-Hours

(8Hr rate)

140553

140581

140455

140454

38

38

30.5

46

Weight (lb) per Battery

28.20

28.00

26.70

26.70

3) When wall mounted, also order a battery cabinet frame grounding landing point adapter P/N 556872.

This adapter installs in the relay rack mounting bracket holes located on either side of the cabinet.

Frame Grounding Point

(1/4-20 Studs on 5/8” Centers)

Frame Ground Landing

Point Adapter P/N 55687

2

Attach Frame Ground Landing

Point Adapter to Cabinet

Page 58 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

SAG582136600

Issue AU, February 21, 2014

Home

NetSure™ 211

BC

Battery Cabinet (Spec. No. 554631)

Features

♦ The NetSure™ 211 BC Battery Cabinet is rated at 30 amperes, and can be mounted in a 19” or 23” nominal relay rack, or mounted to a suitable wall.

♦ The Battery Cabinet contains one (1) 40 ampere battery disconnect circuit breaker.

♦ Battery circuit breaker alarm leads are provided to tie into the power system’s alarm circuit.

♦ The Battery Cabinet is equipped with a battery cable terminated in an Anderson connector.

♦ Cables to connect the batteries (as specified in the table under Ordering Notes) into the Battery Cabinet provided.

♦ Battery Cabinets can be paralleled to provide greater reserve time. Battery cabinets contain a second Anderson battery connector for plugging one cabinet into another.

Ordering Notes

1) Order by Spec. No. 554631 as required.

2) Also order four (4) batteries per Battery Cabinet per the following table.

Battery

Manufacturer

GNB

Manufacturer

P/N

M12V40F

Emerson P/N Capacity Amp-Hours

(8Hr rate)

241173815 40

Weight (lb) per Battery

39.00

Note: When wall mounted, a battery cabinet frame grounding landing point adapter, P/N 556872, is provided. This adapter installs in the relay rack mounting bracket holes located on either side of the cabinet.

Frame Grounding Point

(1/4-20 Studs on 5/8” Centers)

Frame Ground Landing

Point Adapter P/N 556872

Attach Frame Ground Landing

Point Adapter to Cabinet

Page 59 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

♦ For interface with SM AC, SM BAT, SM BRC, or SM IO modules.

Restrictions

One (1) RS-485 connector is available in the system.

Ordering Notes

1) Order P/N 547674 as required.

PCU Blank Filler Panel, P/N PSK4820R-1

Features

♦ Provides 1x2U blank filler panel for rectifier module.

Ordering Notes

1) Order P/N PSK4820R-1 as required.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

SM TEMP Temperature Concentrator (P/N 547490)

Features

♦ Allows for multiple temperature probes to be used for temperature compensation. Compensation can be based on highest probe temperature or average probe temperature.

♦ Provides (8) temperature probe inputs per SM TEMP.

♦ Can be cascaded up to (8) SM TEMP modules, connecting up to

64 temperature probes.

♦ Provides analog output for all controllers.

Restrictions

Concentrator needs to plug into analog temp input on IB2 board.

Ordering Notes

1) Order P/N 547490.

2) Order up to (8) 3-meter (P/N 547749) or 10-meter (P/N 547750) temperature probes for each concentrator.

SM Module RS-485 Interface Cable P/N 547674

Features

♦ Provides 4’ cable for connecting SM supervisory modules to the system RS-485 interface connector.

Home

Page 60 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

SAG582136600

Issue AU, February 21, 2014

Home

Anderson Battery Connector

Features

♦ Includes the components necessary to assemble an Anderson connector onto a battery cable.

Restrictions

Appropriate battery post mating lugs must be ordered separately.

Ordering Notes

Order Anderson connector housings and lugs per the following table.

Description

Emerson

P/N

For a single string (spare for List 71).

Consists of two (2) lugs (Anderson P/N 5952) and one (1) Red

Connector (Anderson P/N 992G1). Lugs accept 8 AWG wire.

Allows for the connection of one (1) battery string (both polarities)

(one wire per lug).

For a single string (spare for List 73).

Consists of two (2) lugs (Anderson P/N 5900) and one (1) Red

Connector (Anderson P/N 992G1). Lugs accept 6 AWG wire.

Allows for the connection of one (1) battery string (both polarities)

(one wire per lug).

For a double string (spare for List 72).

Consists of two (2) lugs (Anderson P/N 5900) and one (1) Red

Connector (Anderson P/N 992G1). Lugs accept 6 AWG wires.

Allows for the connection of two (2) battery strings (both polarities)

(two [10 AWG] wires per lug).

Individual Housing and Lugs Part Numbers

(spare for List 1, 2, 71, and 73)

(not available in kit form, order components individually per the second half of this table)

133196

Housing

Single Part Number for a Housing and Lugs

Description

Lug (accepts 8 AWG wire) (2 required per housing)

Lug (accepts 6 AWG wire) (2 required per housing)

Emerson

P/N

138922

247109602

111691

Anderson

P/N

(not available in kit form, order components individually per the second half of this table)

6331G1

Anderson

P/N

992G1

5952

5900

Page 61 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

Digital Input and Relay Output Cables

Features

Home

Lists 1 and 2: Two sets of customer wiring cables are available. One set is for Digital Inputs and Relay outputs. The other set is for an additional -48V digital input. One half of the Digital Inputs and Relay

Outputs cable is provided and factory connected in the shelf. The other half (includes mating connector on one end and un-terminated on the other end) must be ordered separately. The additional -48V digital input cable must be ordered separately. When ordered, one half of the -48V digital input cable is factory connected in the shelf. The other half has a mating connector on one end and is un-terminated on the other end.

Lists 5 and 6: Two sets of customer wiring cables are available. One set is for the Digital Inputs and another set, for the Relay Outputs. One half of the Relay Outputs Cable is provided and factory connected in the shelf. The other half (includes mating connector on one end and un-terminated on the other end) must be ordered separately. Both halves of the Digital Inputs Cable must be ordered separately. When ordered, one half of the Digital Inputs Cable is factory connected in the shelf. The other half has a mating connector on one end and is un-terminated on the other end.

Ordering Notes

1) Lists 1 and 2: For the Digital Inputs and Relay Outputs Cable, P/N 545494 (2 ft.) is provided and factory connected in the List 1 and 2 shelves. The mating cable, P/N 545495 (10 ft.) must be ordered separately.

For additional -48V Digital Input Cable Kit, order P/N 554935.

2) Lists 5 and 6: For the Relay Outputs Cable, P/N 541308 (3 ft.) is provided and factory connected in the

List 5 and 6 shelves. A mating cable, P/N 541309 (10 ft.) or P/N 545644 (50 ft.), must be ordered separately.

For the Digital Inputs Cable, order P/N 541310 (shelf side, 3 ft.) and P/N 541311 (customer side, 10 ft.).

Note: A custom digital input cable and internal wiring kit is available, P/N 545594. This kit is factory installed only.

Page 62 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

SAG582136600

Issue AU, February 21, 2014

Home

Replacement Modules

Ordering Notes

1) Refer to Table 5.

Item

500W Rectifier Module

1000W Rectifier Module

Rectifier Module Fan

SCU+ Controller Module

ACU+ Controller Module

Temperature Probe

Part Number

1R48500

1R481000

32010093

1M521BNA*

* Also specify the appropriate SCU+ configuration file. Refer to the configuration file label on your existing SCU+ Controller.

1M820BNA*

* Also specify the appropriate ACU+ configuration file. Refer to the configuration file label on your existing ACU+ Controller.

Order per List 90 (9 ft. long) or List 91 (30 Ft. long)

(or if only one piece of the two piece probe is needed, see the List 90 or 91 description for part numbers)

Table 5

Replacement Module Part Numbers

Page 63 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

Wiring Notes

Refer also to the next section, Wiring Illustrations .

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

Shelf Frame Grounding Stud

Features

♦ An M5 frame grounding stud with hardware is provided on the rear of the shelf.

Restrictions

Recommended frame ground wire size is 6 AWG.

AC Input Branch Circuit Protection and Wiring

Features

Home

♦ Each shelf contains one (1) or two (2) side mounted plug-in AC input connector(s).

♦ AC Input Cable Assemblies/Line Cords are available that plug into the shelf’s AC input connector.

Restrictions

Lists 1 and 2 require one (1) AC input branch circuit.

The AC input branch circuit feeds two (2) (List 1) or three (3) (List 2) rectifiers.

Refer to the following table for recommended branch circuit protection.

Lists 5 and 6 require two (2) AC input branch circuits.

Each AC input branch circuit feeds two (2) (List 5) or three (3) (List 6) rectifiers.

Refer to the following table for recommended branch circuit protection.

System

AC Input Branch Circuit Protection*

208/240VAC Input 120VAC Input

500W Rect. 1000W Rect. 500W Rect. 1000W Rect.

58213660001

58213660005

(2-Rectifiers per AC Feed)

15A 15A

58213660002

58213660006

(3-Rectifiers per AC Feed)

15A 20A

* Protective devices should be of the time-delay or high inrush type.

15A

20A

20A

25A / 30A

For correct AC input wire size, use the appropriate AC Input Cable Assembly/Line Cord for each AC input branch circuit. Refer to AC Input Cables and Line Cords in the ACCESSORY DESCRIPTIONS section of this document.

External Alarm and Monitoring Wiring

Features

List 5 and 6: Relay output and digital input leads are connected to screw-type terminal blocks located on the Customer Interface Board mounted inside the shelf. One half of a Relay Outputs Cable is factory connected to these terminals. The other half (includes mating connector on one end and un-terminated on the other end) is ordered separately. If ordered, one half of a Digital Input Cable is factory connected to these terminals. The other half includes a mating connector on one end and is un-terminated on the other end.

List 1 and 2: Relay output and digital input leads are connected to screw-type terminals located on the

SCU+ Controller Module mounted inside the shelf. One half of a Digital Input/Relay Output Cable is

Page 64 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

SAG582136600

Issue AU, February 21, 2014 factory connected to these terminals. The other half (includes mating connector on one end and un-terminated on the other end) is ordered separately.

Home

If an additional -48V Digital Input cable is ordered, one half of the cable is factory connected in the shelf.

The other half includes mating connector on one end and is un-terminated on the other end. The additional -48V digital input cable must be ordered separately.

Restrictions

Recommended Wire Size: 22 AWG for Loop Lengths Up to 200 ft.

18-20 AWG for Loop Lengths Over 200 ft.

Load Distribution Wiring (GMT Fuses) (Lists BG and NG only)

Features

♦ Load and load return leads are connected to a screw-type terminal block located on the front of the

Distribution Unit.

Restrictions

The rating of the distribution device determines the wire size requirements. Refer to the American National

Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code

(NEC) and applicable local codes.

Terminal block wire size capacity is 20 to 12 AWG.

Load Distribution Wiring (GMT Fuses) (Lists BF, LF, and NF only)

Features

♦ Load distribution (GMT fuses) and load return leads are connected to receptacles located inside the

Distribution Unit. Load leads are brought into the right side (as viewed from the front) of the shelf and are accessible from the front of the shelf. Note that the GMT distribution fuse block accepts two ranges of fuse amperage sizes, and that two different types of receptacles are provided.

Restrictions

The rating of the distribution device determines the wire size requirements. Refer to the American National

Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code

(NEC) and applicable local codes.

Ordering Notes

1) Lists 61 provides 12’ long, 16 AWG, load and load return leads that are terminated on one end with the appropriate mating connector* to plug into the system’s lower amperage rating GMT fuse connector, and are left un-terminated at the remaining end for connection into customer loads.

* Consists of housing Molex P/N 39-01-2025 and terminals P/N 44476-3112 [loose] or 44476-3111

[reel].

2) Lists 62 provides 12’ long, 14 AWG, load and load return leads that are terminated on one end with the appropriate mating connector* to plug into the system’s higher amperage rating GMT fuse connector, and are left un-terminated at the remaining end for connection into customer loads.

* Consists of housing Tyco P/N 350777-1 and terminals Tyco P/N 350551-3 [loose] or Tyco

350537-3 [reel].

Page 65 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

Load Distribution Wiring (GMT Fuses) (Lists BC, LC, NC, BA, LA, and NA)

Home

Features

♦ Load distribution (GMT fuses) and load return leads are connected to receptacles located inside the

Distribution Unit. Load leads are brought into the right side (as viewed from the front) of the shelf and are accessible from the front of the shelf.

Restrictions

The rating of the distribution device determines the wire size requirements. Refer to the American National

Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code

(NEC) and applicable local codes.

Ordering Notes

1) List 60 provides 12’ long, 16 AWG, load and load return leads that are terminated on one end with the appropriate mating connector* to plug into the system’s GMT fuse connector, and are left un-terminated at the remaining end for connection into customer loads.

* Consists of housing Molex P/N 39-01-2025 and terminals P/N 44476-3112 [loose] or 44476-3111

[reel].

Load Distribution Wiring (Optional Bullet-Nose-Type 6-Position GMT Fuse Module)

Features

♦ Load and load return leads are connected to a screw-type terminal block located on the front of the Fuse

Module.

Restrictions

The rating of the distribution device determines the wire size requirements. Refer to the American National

Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code

(NEC) and applicable local codes.

Terminal block wire size capacity is 24 to 14 AWG.

Load Distribution Wiring (Circuit Breakers) (Lists BC, LC, NC, BA, LA, and NA)

Features

♦ Load distribution (circuit breakers) and load return leads terminated in two-hole lugs are connected to threaded studs located inside the Distribution Unit. Load leads are brought into the right side (as viewed from the front) of the shelf and are accessible from the front of the shelf.

Restrictions

The rating of the distribution device determines the wire size requirements. Refer to the American National

Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code

(NEC) and applicable local codes.

All lugs for customer connections must be ordered separately. Mounting hardware is factory supplied.

Maximum wire size is 6 AWG when all four (4) circuit breaker positions are used. 4 AWG or 2 AWG can be used, but the number of breaker positions will be reduced as follows;

4 AWG: 3 breakers max. (2 load/1 battery or 1 load/2 battery on lists BA, LA, and NA; 3 load on lists BC,

LC, and NC). Use 6 AWG for CO Ground.

2 AWG: 2 breakers max. (1 load/1 battery on lists BA, LA, and NA; 2 load on lists BC, LC, and NC). Use

6 AWG for CO Ground.

For 4 AWG and 2 AWG wire, install a customer supplied flat washer between the lug and the nut supplied on the termination.

Ordering Notes

1) The rating of the distribution device determines the wire size requirements. For wire size and lug selection, refer to Table 6.

2) For other available lugs, refer to drawings 031110100 through 031110300.

Page 66 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

SAG582136600

Issue AU, February 21, 2014

Home

Circuit

Breaker

Amperag e

1, 3, 5,

10A

15A

20A

25A

30A

35A

40A

45A

50A

60A

70A

75A

80A

90A

14 AWG

37 (3, 4, 5)

24 (3, 4)

--

--

--

--

--

--

--

--

12 AWG

58 (3, 4, 5)

39 (3, 4, 5)

29 (3, 4)

--

--

--

--

--

--

--

10 AWG 8 AWG

Loop Length (feet)

6 AWG

(2)

93

62

46

Recm 90°C Wire Size

(3, 4, 5)

(3, 4, 5)

(3, 4, 5)

37 (3, 4,)

31 (3, 4)

--

--

--

--

--

148 (3, 4, 5)

99

74

59

49

(3, 4, 5)

(3, 4, 5)

(3, 4, 5)

(3, 4, 5)

42

37

33

(3, 4)

(3, 4)

(3, 4)

29 (3)

--

(1)

236 (3, 4, 5)

157

118

(3, 4, 5)

(3, 4, 5)

94

78

(3, 4, 5)

(3, 4, 5)

67

59

(3, 4, 5)

(3, 4, 5)

52

47

(3, 4)

(3, 4,)

39 (3, 4)

4 AWG

--

107 (3, 4)

94

83

(3, 4)

(3, 4)

75

62

53

50

(3, 4)

(3, 4)

(3, 4)

(3, 4)

47

--

--

--

--

(3, 4)

41 (3)

2 AWG

--

--

--

--

--

--

--

--

99

85

79

74

--

(3, 4)

(3, 4)

(3, 4)

(3, 4)

66

59

(3, 4)

(3, 4) 100A

2-hole

24539010

0

24539010

0

Recommended Crimp Lug (6)

24539010

0

24534660

0

24534650

0

--

24534680

0

24534690

0

1 Wire sizes are based on recommendations of the American National Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code (NEC). Table 310-16 for wire rated at 90°C conductor temperature operating in ambient temperatures of 40°C, 50°C, and

65°C was used. For other operating ambient temperatures, refer to the NEC. For operation in countries where the NEC is not recognized, follow applicable codes.

2 Recommended wire sizes are sufficient to restrict voltage drop to 1.0 volt or less at listed branch current for the loop lengths shown. Loop length is the sum of the lengths of the positive and negative leads.

3 Wire Size / Loop Length Combination Calculated using 40°C Ambient Operating Temperature.

4 Wire Size / Loop Length Combination Calculated using 50°C Ambient Operating Temperature.

5 Wire Size / Loop Length Combination Calculated using 65°C Ambient Operating Temperature.

6 Two-hole lugs are 10-32 bolt clearance on 5/8" centers. Refer to drawing 031110100 for lug crimping information.

Table 6

Recommended Battery and Load Distribution Wire Size and Lug Selection

(Bullet Nose-Type Circuit Breaker)

Page 67 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

Load Distribution Wiring (GMT Fuses) (List KG)

Features

System Application Guide

Spec. No. 582136600 (Model 211 NGFB

Home

♦ Load distribution (GMT fuses) and load return leads are connected to terminal blocks located on the front of the assembly.

Restrictions

The rating of the distribution device determines the wire size requirements. Refer to the American National

Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code

(NEC) and applicable local codes.

Terminal block wire size capacity is 26 to 14 AWG.

)

CO Ground Wiring (Lists BF, LF, NF, BC, LC, NC, BA, LA, and NA)

Features

♦ Two 10-32 studs on 5/8” centers with hardware are provided on the Return Bus for CO Ground wiring.

Restrictions

Recommended CO ground wire size is 6 AWG.

Recommended lug is 245346500 (2-hole, 10-32 clearance holes, 5/8” centers).

Input Battery Wiring (List BG and NG)

Features

♦ Two (2) 8 AWG 48” long battery cables are factory connected inside the shelf. These cables are terminated at the customer end in a Red SB50 Anderson battery connector. A mating Anderson battery connector is provided [Housing: Emerson P/N 138922, Anderson Power Products P/N 992G1. Contacts

(two provided): Emerson P/N 247109602, Anderson Power Products P/N 5952].

♦ Additional strings of battery may be connected to the system using the available battery cable kits (see

List 71 and List 72).

Restrictions

Battery leads are NOT internally fused.

Input Battery Wiring (to Battery Disconnect Circuit Breakers) (Lists BA, LA, and NA)

Features

♦ Battery and battery return leads terminated in two-hole lugs are connected to threaded studs located inside the Distribution Unit. Battery leads are brought into the right side (as viewed from the front) of the shelf and are accessible from the front of the shelf.

Restrictions

The rating of the distribution device determines the wire size requirements. Refer to the American National

Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code

(NEC) and applicable local codes.

All lugs for customer connections must be ordered separately. Mounting hardware is factory supplied.

Maximum wire size is 6 AWG when all four (4) circuit breaker positions are used. 4 AWG or 2 AWG can be used, but the number of breaker positions will be reduced as follows;

4 AWG: 3 breakers max. (2 load/1 battery or 1 load/2 battery on lists BA, LA, and NA; 3 load on lists BC,

LC, and NC). Use 6 AWG for CO Ground.

2 AWG: 2 breakers max. (1 load/1 battery on lists BA, LA, and NA; 2 load on lists BC, LC, and NC). Use

6 AWG for CO Ground.

For 4 AWG and 2 AWG wire, install a customer supplied flat washer between the lug and the nut supplied on the termination.

Page 68 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

SAG582136600

Issue AU, February 21, 2014

Ordering Notes

1) The rating of the distribution device determines the wire size requirements. For wire size and lug selection, refer to Table 6.

2) For other available lugs, refer to drawings 031110100 through 031110300.

Input Battery Wiring (to Battery Busbars) (Lists BF, LF, NF, BC, LC, and NC)

Features

Home

♦ Battery and battery return leads terminated in two-hole lugs are connected to threaded studs located inside the Distribution Unit. Battery leads are brought into the right side (as viewed from the front) of the shelf and are accessible from the front of the shelf.

Restrictions

All lugs for customer connections must be ordered separately. Mounting hardware is factory supplied.

Maximum size of wire to be connected to a single lug position is 2 AWG.

Maximum lug width, 0.61 inches.

Ordering Notes

1) Battery wire size varies depending on load, therefore no specific information is provided for wire size.

When making connections, observe correct polarity.

2) List 65 and List 66 provide 2 AWG “shelf side” and “battery side” (respectively) battery cables.

Page 69 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

Wiring Illustrations

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

Shelf Frame Grounding Stud (both 1U and 2U Panels, List 1 and 5 shown)

Home

Page 70 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

AC Input Wiring (Lists 1 and 2)

List 1 and List 2 with Side AC Input Connectors

(List 1 shown)

SAG582136600

Issue AU, February 21, 2014

Home

List 1 and List 2 with Rear AC Input Connectors

(List 2 shown)

Front

Rear

AC input connections are made using the supplied AC input cable assemblies/ line cords connected here.

* Rectifiers are numbered left to right as viewed from the front.

AC input connections are made using the supplied AC input cable assemblies/ line cords connected here.

Rear View

Front View

AC Input

Cable Assembly

AC Input

Line Cord

L2-N

Ground

Blue*

Green/Yellow*

White*

Green*

L1

Nominal 120/208/240V

AC Input for Rectifier Module:

List 1 (19” Shelf): #1 and #2

List 2 (23” Shelf): #1, #2, and # 3

Brown* Black*

* color of AC Input Cable

Assembly/Line Cord lead.

Nominal 120/208/240V

AC Input for Rectifier Module:

List 1 (19” Shelf): #1 and #2

List 2 (23” Shelf): #1, #2, and # 3

535232

540946

545252

545478

545479

545480

545481

545553

545616

547525

548457

548196

ENSURE THE PROPER VOLTAGE AC

BRANCH CIRCUIT AND LINE CORDS

WITH THE APPROPRIATE PLUG

ARE USED FOR YOUR APPLICATION.

* AC Input Cable Assembly / Line Cords

Part Number Customer End

500W Rectifier: 120/208/240 VAC Input

1000W Rectifier: 120/208/240 VAC Input unterminated (List 1 & 2)

L6-30P

L5-30P

5-15P

L5-15P

L6-15P

L5-20P

L6-20P

L6-30P

L5-30P

(List 1 & 2)

(List 1 & 2)

(List 1 w/ R48-500)

(List 1 w/ R48-500)

(List 1; List 2 w/ R48-500)

(List 1; List 2 w/ R48-500)

(List 1 & 2)

(List 1 & 2)

(List 1 & 2)

(List 1 w/ R48-500)

“WARNING - HIGH LEAKAGE CURRENT.”

An industrial style plug is required when providing power to three (3) or more Rectifier

Modules with a flexible cord. Plug and outlet types 1-15, 2-15, 2-20, 5-15, and 5-20 as specified in IEC 60083 are considered to be NON-INDUSTRIAL within the meaning of this standard.

5-15P

IEC320 C20 (List 1 120/208/240V & List 2 208/240 w/ R48-500 or R48-1000; List 2 120V w/ R48-500 only.)

Page 71 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

AC Input Wiring (Lists 5 and 6)

List 5

List 6

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

Home

Front

4

3

AC input connections are made using the supplied AC input cable assemblies/ line cords connected here.

2

1

Rectifiers are numbered as shown above

Front View

Front

AC input connections are made using the supplied AC input cable assemblies/ line cords connected here.

6

5

4

2

3

1

Rectifiers are numbered as shown above

ENSURE THE PROPER VOLTAGE AC

BRANCH CIRCUIT AND LINE CORDS

WITH THE APPROPRIATE PLUG

ARE USED FOR YOUR APPLICATION.

500W Rectifier: 120/208/240 VAC Input

1000W Rectifier: 120/208/240 VAC Input

L2-N

Ground

L1

AC Input

Cable Assembly

AC Input

Line Cord

Blue* White*

Green/Yellow* Green*

Brown* Black*

* color of AC Input Cable

Assembly/Line Cord lead.

Nominal 120/208/240V

AC Input for Rectifier Module:

List 5 (19” Shelf): #1 and #2

List 6 (23” Shelf): #1, #2, and #5

Nominal 120/208/240V

AC Input for Rectifier Module:

List 5 (19” Shelf): #3 and #4

List 6 (23” Shelf): #3, #4, and #6

535232

540946

545252

545478

545479

545480

545481

545553

545616

547525

548457

548196

* AC Input Cable Assembly / Line Cords

Part Number Customer End unterminated (List 5 & 6)

L6-30P

L5-30P

5-15P

L5-15P

L6-15P

L5-20P

L6-20P

L6-30P

L5-30P

5-15P

(List 5 & 6)

(List 5 & 6)

(List 5 w/ R48-500)

(List 5 w/ R48-500)

(List 5; List 6 w/ R48-500)

(List 5; List 6 w/ R48-500)

(List 5 & 6)

(List 5 & 6)

(List 5 & 6)

(List 5 w/ R48-500)

“WARNING - HIGH LEAKAGE CURRENT.”

An industrial style plug is required when providing power to three (3) or more Rectifier

Modules with a flexible cord. Plug and outlet types 1-15, 2-15, 2-20, 5-15, and 5-20 as specified in IEC 60083 are considered to be NON-INDUSTRIAL within the meaning of this standard.

IEC320 C20 (List 5 120/208/240V & List 6 208/240 w/ R48-500 or R48-1000; List 6 120V w/ R48-500 only.)

Page 72 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

External Alarm and Monitoring Wiring (Lists 1 and 2)

SAG582136600

Issue AU, February 21, 2014

Home

SCU+

Controller

Notes

Relay Output/Digital Input Cable P/N 545494 is factory connected to terminals. Mating half

(w/ unterminated ends) available, P/N 545495.

When an additional -48V Digital Input Cable Kit

P/N 554935 is ordered, one half of the kit is factory connected in the shelf. The other half has a mating connector on one end and is un-terminated on the other end.

(48/24V)

Digital Inputs

SCU+ Controller

(Top View)

Major

Summary

Alarm

Relay Outputs

Digital Input 1 is factory wired to

Load Breaker / Fuse Alarm.

Digital Input 2 default is External Battery

Disconnect Circuit Breaker Alarm.

A factory-connected jumper supplies +BAT (Battery Return) to the positive side of Digital

Input #2.

When ordered, Temperature Probe leads are factory connected to SCU+ Connector Board located in the Distribution Unit.

These are labeled T1 and T2.

Minor

Summary

Alarm

NC = Normally Closed

COM = Common

NO = Normally Open

All relay contacts are shown with the relay deenergized.

Page 73 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

System Application Guide

Spec. No. 582136600 (Model 211 NGFB

External Alarm and Monitoring Wiring (Lists 5 and 6)

Notes

Home

Note: A custom digital input cable and internal wiring kit is available, P/N 545594. This kit is factory installed only.

)

Relay Output Cable P/N 541308 is factory connected to Relay Output terminals.

Mating half (w/ unterminated ends) available, P/N 541309.

If ordered, Digital Input Cable P/N 541310 is factory connected to Digital Input terminals.

Mating half (w/ unterminated ends) available, P/N 541311.

Digital Input 1 is factory wired to Load Breaker / Fuse Alarm.

Digital Input 2 is reserved for External Battery Breaker Alarm.

A factory connected jumper supplies +BAT (Battery Return) to the positive side of Digital Input 2.

Digital Inputs 3 through 7 are User defined.

Digital Input 8 is reserved for Emergency Stop.

Digital Input 9 is not available in this system.

When ordered, Temperature Probe leads are factory connected to J11 and J12. These are labeled 1 and 2.

NC = Normally Closed

COM = Common

NO = Normally Open

All relay conacts are shown with the relay deenergized.

IB2 Customer

Interface Board

Relay

No.

Relay

No.

J9

Relay Output Term. Blocks

J8 J7 J6

7

NO C NC

5

NO C NC

3

NO C NC

1*

NO C NC

5 3 1

NO C NC

5 3 1

NO C NC

5 3 1

NO C NC

5 3 1

NO C NC

6 4

8

2 6 4

6

2 6 4

4

2 6 4

2

2

Digital Input Term. Blocks

J5 J4 J3

8 7 6 5 4 3 2 1

5 3 1 5 3 1 5 3 1

6 4 2 6 4 2 6 4

8 7 6 5 4 3 2

2

1

Input

No. (

)

Input

No. (+)

J12

J11

RS-485 Connection for SM AC, SM BAT,

SM BRC, or SM IO

Supervisory Modules.

See module data sheets. (Functional with ACU+ only.)

Temp. Probe #2 or

SM TEMP Module

Temp. Probe #1 or

SM TEMP Module

J2

J1

SW1

Switch sections must be set to this position to interface with SCU+/ACU+ controller.

* The relay assigned by the Controller to be the”Major Summary” (SCU+) or “Critical Summary” (ACU+) alarm (relay 1 by default) will operate in the “Fail Safe Mode”. “Fail Safe Mode” means Relay 1 is de-energized during an alarm condition, opening the contacts between the C and NO terminals, and closing the contacts between the C and NC terminals.

The remaining seven (7) alarm relays energize during an alarm condition, closing the contacts between the C and NO terminals, and opening the contacts between the C and NC terminals.

Page 74 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

SAG582136600

Issue AU, February 21, 2014

Yellow Alarm Lead

(P/N 535294)

(factory wired to circuit breaker alarm terminal)

Alarm Wiring to a Single

External Battery Disconnect Unit

Procedure

1. Connect YELLOW lead exiting top of

Battery Disconnect Unit per table below.

Remove quick connect terminal first.

The YELLOW lead is factory connected to circuit breaker “C (Common)” alarm terminal in the Battery Disconnect Unit.

2. There is NO connection to the circuit breaker “NO (Normally Open)” alarm terminal.

3. Connect loose end of Jumper factory connected to bottom terminal on circuit breaker to circuit breaker

“NC (Normally Closed)” alarm terminal.

Torque to 84 in-lbs using supplied hardware

To

Power

System

To

Battery

EXTERNAL BATTERY

DISCONNECT UNIT

(Side cover removed in illustration to show wiring details.)

External Battery Disconnect Circuit Breaker Alarm Input:

A battery disconnect circuit breaker alarm is activated when the circuit breaker is in the OFF position, and provides -48VDC to Digital Input # 2.

Shelf List

1 or 2

5 or 6

Alarm Cable on shelf

545495

NO

YES

541311

NO

YES

Connect to shelf per table below.

Remove quick connect terminal first.

BREAKER ALARM CONNECTION

CONNECT YELLOW WIRE TO:

Must order Cable 545495

R-BK Lead of 545495. Splice and heat shrink tubing included with 545495

Pin 3 of J3 on customer interface BD (negative side of Digital Input # 2)

O-R Lead of 541311. Splice and heat shrink tubing included with 541311

Page 75 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

Yellow Jumper/Alarm

Lead (P/N 524384)

(Ordered separately and supplied loose.

Must be wired by the customer to each circuit breaker

“C (Common)” alarm terminal) see previous page

*

No terminal on 524384 jumper

Connect to shelf per table below.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

Yellow Alarm Lead

(P/N 535294)

(factory wired to circuit breaker alarm terminal)

REMOVE

COMPLETELY

FROM ALL BATTERY

DISCONNECT UNITS

AND DISCARD.

see previous page

1st EXTERNAL BATTERY

DISCONNECT UNIT

(Side cover removed in illustration to show wiring details.)

2nd EXTERNAL BATTERY

DISCONNECT UNIT see previous page

Alarm Wiring to (2) to (3)

External Battery Disconnect Units

3rd EXTERNAL BATTERY

DISCONNECT UNIT

Procedure

1. Completely remove YELLOW lead exiting top of

ALL Battery Disconnect Units and discard.

3. There is NO connection to the circuit breaker “NO (Normally Open)” alarm terminal.

2. Connect separately ordered YELLOW jumper/alarm lead (P/N 524384) to circuit breaker “C (Common)” alarm terminals in ALL Battery Disconnect Units.

Connect remaining end per table below.

4. In ALL Battery Disconnect Units, connect loose end of Jumper factory connected to bottom terminal on circuit breaker to circuit breaker

“NC (Normally Closed)” alarm terminal.

External Battery Disconnect Circuit Breaker Alarm Input:

A battery disconnect circuit breaker alarm is activated when the circuit breaker is in the OFF position, and provides -48VDC to Digital Input # 2.

Shelf List

1 or 2

5 or 6

Alarm Cable on shelf

545495

NO

YES

541311

NO

YES

BREAKER ALARM CONNECTION

CONNECT YELLOW WIRE TO:

Must order Cable 545495

R-BK Lead of 545495. Splice and heat shrink tubing included with 545495

Pin 3 of J3 on customer interface BD (negative side of Digital Input # 2)

O-R Lead of 541311. Splice and heat shrink tubing included with 541311

Page 76 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

Yellow Jumper/Alarm

Lead (P/N 524384)

(Ordered separately and supplied loose.

Must be wired by the customer to each circuit breaker

“C (Common)” alarm terminal)

*

No terminal on 524384 jumper

Connect to shelf per table below.

see previous page

SAG582136600

Issue AU, February 21, 2014

Home

see previous page

1st BATTERY TRAY

BATTERY DISCONNECT

CIRCUIT BREAKER

(Side cover removed in illustration to show wiring details.) see previous page

2nd BATTERY TRAY

BATTERY DISCONNECT

CIRCUIT BREAKER

(if furnished)

Alarm Wiring to Battery Disconnect Circuit

Breakers when (1) to (3) Battery Trays are Used

Procedure

1. Connect kit-supplied YELLOW jumper/alarm lead

(P/N 524384) to circuit breaker “C (Common)” alarm terminals on ALL Battery Disconnect Circuit

Breakers. Connect remaining per table below.

2. There is NO connection to the circuit breaker “NO (Normally Open)” alarm terminal.

3rd BATTERY TRAY

BATTERY DISCONNECT

CIRCUIT BREAKER

(if furnished)

3. On ALL Battery Disconnect circuit breakers, there should be a factory connected Jumper connected from the bottom terminal on the circuit breaker to the circuit breaker “NC

(Normally Closed)” alarm terminal.

External Battery Disconnect Circuit Breaker Alarm Input:

A battery disconnect circuit breaker alarm is activated when the circuit breaker is in the OFF position, and provides -48VDC to Digital Input # 2.

Shelf List

1 or 2

5 or 6

Alarm Cable on shelf

545495

NO

YES

541311

NO

YES

BREAKER ALARM CONNECTION

CONNECT YELLOW WIRE TO:

Must order Cable 545495

R-BK Lead of 545495. Splice and heat shrink tubing included with 545495

Pin 3 of J3 on customer interface BD (negative side of Digital Input # 2)

O-R Lead of 541311. Splice and heat shrink tubing included with 541311

Page 77 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

Yellow Jumper/Alarm

Lead (P/O Cabinet)

Orange Wire on

541434 not used

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

Home

Connect to shelf per table below.

alarm wire alarm wire

1st BATTERY CABINET

BATTERY DISCONNECT

CIRCUIT BREAKER alarm wire

2nd BATTERY CABINET

BATTERY DISCONNECT

CIRCUIT BREAKER

3rd BATTERY CABINET

BATTERY DISCONNECT

CIRCUIT BREAKER

Alarm Wiring to Battery Cabinets

Procedure

1. Remove quick connect terminal from YELLOW battery cabinet alarm lead.

2. Wire per table below.

External Battery Disconnect Circuit Breaker Alarm Input:

A battery disconnect circuit breaker alarm is activated when the circuit breaker is in the OFF position, and provides -48VDC to Digital Input # 2.

Shelf List

1 or 2

5 or 6

Alarm Cable on shelf

545495

NO

YES

541311

NO

YES

BREAKER ALARM CONNECTION

CONNECT YELLOW WIRE TO:

Must order Cable 545495

R-BK Lead of 545495. Splice and heat shrink tubing included with 545495

Pin 3 of J3 on customer interface BD (negative side of Digital Input # 2)

O-R Lead of 541311. Splice and heat shrink tubing included with 541311

Page 78 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

SAG582136600

Issue AU, February 21, 2014

Load Distribution Wiring (GMT Fuses) (Lists BG and NG installed in a List 1 or 2, List 1 shown)

Home

Connect to Front Terminal Block

Load Return

Leads

-48V Distribution

Leads

Fuse

Position

8

9

10

5

6

7

1

2

3

4

Terminal

Load Return Load (-48V)

15

17

19

9

11

13

1

3

5

7

16

18

20

10

12

14

2

4

6

8

Page 79 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

System Application Guide

Spec. No. 582136600 (Model 211

Load Distribution Wiring (GMT Fuses) (Lists BF, LF, and NF installed in a List 5 or 6, List 5 shown)

NGFB

Home

)

Front

Load Distribution

Leads Enter Here

GMT Fuse

Positions

(Max. 15A)

GMT Fuse Load

Distribution Leads

Connect Here

Mating Connectors and 12'

Leads provided with List 62.

-48V on Left (Black Lead),

Return on Right (White Lead)

GMT Fuse

Positions

(Max. 10A)

GMT Fuse Load

Distribution Leads

Connect Here

Mating Connectors and 12'

Leads provided with List 61.

-48V on Left (Black Lead),

Return on Right (White Lead)

Page 80 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

SAG582136600

Issue AU, February 21, 2014

Home

Load Distribution Wiring (GMT Fuses) (Lists BC, LC, NC, BA, LA, and NA installed in a List 5 or 6,

List 5 shown)

Front

GMT Fuse

Positions

Load Distribution

Leads Enter Here

GMT Fuse Load

Distribution Leads

Connect Here

Mating Connectors and 12'

Leads provided with List 60.

-48V on Left (Black Lead),

Return on Right (White Lead); as viewed from side with door closed.

Page 81 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

Load Distribution Wiring (Optional Bullet Nose 6-Position GMT Fuse Module)

System Application Guide

Spec. No. 582136600 (Model 211 NGFB

Home

)

-48V Distribution

Leads

Load Return

Leads

Page 82 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

SAG582136600

Issue AU, February 21, 2014

Home

Load Distribution Wiring (Circuit Breakers) and CO Ground Wiring (Lists BC, LC, and NC installed in a List 5 or 6, List 5 shown)

Front

Load Distribution

Circuit Breakers

Circuit Breaker Load

Distribution and

CO Ground Leads

Enter Here

Front

Portion of shelf removed in illustration for clarity.

Leads are brought into side of shelf, and tools to secure lugs from front of shelf.

-48V Load

Distribution

Leads

Load Return Leads

CO Ground Lead

10-32 studs (w/ hardware) on 5/8" centers for installation of customer provided two hole lugs.

Page 83 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

Load Distribution Wiring (Circuit Breakers), Input Battery Wiring (Circuit Breakers), and CO Ground Wiring (Lists BA, LA, and NA installed in a List 5 or 6, List 5 shown)

Home

Front

Load Distribution

Circuit Breakers

Battery Disconnect

Circuit Breakers

CO Ground, Circuit Breaker

Load Distribution, and Circuit

Breaker Battery Leads

Enter Here

Front

Portion of shelf removed in illustration for clarity.

Leads are brought into side of shelf, and tools to secure lugs from front of shelf.

OBSERVE PROPER

POLARITY WHEN

MAKING BATTERY

CONNECTIONS

-48V Load

Distribution

Leads

-48V Battery

Leads

Battery Return Leads

Load Return Leads

CO Ground Lead

10-32 studs (w/ hardware) on 5/8" centers for installation of customer provided two hole lugs.

Page 84 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

Load Distribution Wiring (GMT Fuses) (List KG)

SAG582136600

Issue AU, February 21, 2014

Home

Inputs for Side “A” and Side “B” are strapped in this system.

Connections are made to screw compression terminal blocks.

Wire size range is 26 to 14 AWG.

Page 85 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

Input Battery Wiring (Lists BG and NG installed in a List 1 or 2, List 1 shown)

System Application Guide

Spec. No. 582136600 (Model 211 NGFB

Home

)

Page 86 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

SAG582136600

Issue AU, February 21, 2014

Home

Input Battery Wiring (Lists BF, LF, NF, BC, LC, and NC installed in a List 1 or 5, List 5 shown) and CO Ground Wiring (Lists BF, LF, and NF installed in a List 1 or 5, List 5 shown)

List NF Distribution

Unit shown. List BF,

LF, BC, LC, and NC similar.

Front

List 65 provides 3' long, 2 AWG, battery cables terminated on one end with lugs to connect to the input battery landings and on the other end with an Anderson connector.

List 66 provides 12' long, 2 AWG, battery cables terminated on one end in an Anderson connector and left unterminated at the remaining end for connection of battery lugs.

Battery: 1/4-20 studs (w/hardware) on 5/8" centers for installation of customer provided two hole lugs.

CO Ground: 10-32 studs (w/hardware) on 5/8" centers for installation of customer provided two hole lugs.

Distribution

Unit

List BC, LC, and NC

Distribution Unit

List BF, LF, and NF

Distribution Unit

Battery, Battery Return, and CO Ground Leads

Enter Here

CO Ground Lead

Right Side

Battery Return Leads -48 Battery Leads

CO Ground Lead

Right Side

Battery Return Leads -48 Battery Leads

OBSERVE PROPER

POLARITY WHEN

MAKING BATTERY

CONNECTIONS

Page 87 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

SPECIFICATIONS

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

Home

Note: For all rectifier specifications, refer to the separate Rectifier User Manual (UM1R48500/UM1R481000) supplied with your Power System.

For all controller specifications, refer to the Controller User Manual (UM1M521B or UM1M820B) supplied with your Power System.

For factory settings of all configurable Controller parameters, refer to the Configuration Drawing (Cdrawing) supplied with your Power System.

1. SYSTEM

1.1 Environmental Ratings

1.1.1 Operating Ambient Temperature Range (Specification Compliant):

(A) -40°C (-40°F) to +65°C (+149°F) with derating output.

(B) -40°C (-40°F) to +40°C (+104°F) with full power performance.

1.1.2 Storage Ambient Temperature Range: -40°C (-40°F) to +75°C (+167°F).

1.1.3 Humidity: This Power System is capable of operating in an ambient relative humidity range of

0% to 90%, non-condensing.

1.1.4 Altitude: 2000 m (6560 ft) at full power (power limited for heights above 2000 m).

1.1.5 Mounting: This product is intended only for installation in a Restricted Access Location on or above a non-combustible surface.

This product must be located in a Controlled Environment with access to Craftspersons only.

This product is intended for installation in Network Telecommunication Facilities (CO, vault, hut, or other environmentally controlled electronic equipment enclosure).

This product is intended to be connected to the common bonding network in a Network

Telecommunication Facility (CO, vault, hut, or other environmentally controlled electronic equipment enclosure).

Typical industry standards recommend minimum aisle space clearance of 2'6" for the front of the relay rack and 2' for the rear of the relay rack.

Separate shelves are available for mounting in either a 19" or 23" wide relay rack (1” or 1-3/4” multiple drillings for the 2U shelf and 1-3/4" multiple drillings for the 1U shelf).

Mounting angles are positioned for a 5-inch front projection mounting only.

Flush mounting is done using optional kits.

1.1.6 Ventilation Requirements: Rectifier and mounting shelf ventilating openings must not be blocked and temperature of air entering rectifiers must not exceed rated Operating Ambient

Temperature Range stated above.

1.2 Compliance Information

1.2.1 Surge Protection: Refer to Paragraphs 2.3.6. and 3.3.6.

Note: This level of protection is a widely used standard for telecommunications power equipment. As with all such equipment, it is the end user's responsibility to provide an adequately sized Surge Suppression Device at the commercial power service entrance of the building that reduces all incoming surges to levels below the classes/categories stated for the equipment.

1.2.2 Safety Compliance:

(A) This unit meets the requirements of UL 60950, Standard for Information Technology

Equipment, and is UL Recognized as a power supply for use in Telephone, Electronic Data

Processing, or Information Processing Equipment.

(B) This unit meets the requirements of CAN/CSA 22.2, No. 60950-00 and is tested and

Certified by UL ("c UR") as a Component Type Power Supply.

Page 88 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

SAG582136600

Issue AU, February 21, 2014

Home

1.2.3 EMC and Safety:

(A) Complies with the Low-Voltage Directive, 73/23/EEC. Complies with Emissions and Immunity requirements as specified in GR-1089-Core Issue 4.

EMC

EN 55022: 1998

CFR 47 – Part 15

GR-1089 Issue 4

Emissions

Conducted

Radiated

Test Level

Class B

Class B

GR-1089 Issue 4

Immunity

EN 61000-4-2 Electrostatic Discharge

EN 61000-4-4 Electric Fast Transients

Radiated Immunity

Conducted Immunity

Surge IEEE C62.41

SAFETY

8kV / 15kV

0.25kV / 0.5kV

8.5V/m

89dBuA

2kV / 6kV

EN 60950-1: 2001

Safety of Information Technology Equipment, including

Electrical Business Equipment

1.2.4 NEBS Compliance: Compliance verified by a Nationally Recognized Testing Laboratory

(NRTL) per GR-1089-CORE and GR-63-CORE. Contact Emerson Network Power for NEBS compliance reports.

For N ET S URE ™ 211 NGFB to remain compliant during a fan failure condition, the backup battery connection must be utilized to provide sufficient power to the loads for up to eight (8) hours when the system is operated at greater than 50% output power. If no backup battery connection is used, the system must operate with a redundant module installed.

1.3 Standard Features

1.3.1 AC Input Connections: AC input cable assemblies and line cords are available.

(A) List 1 and 2: Mounted to the side of the shelf is an AC input housing with one (1) plug-in connector for one (1) AC input feed.

(B) List 5 and 6: Mounted to the side of the shelf is an AC input housing with two (2) plug-in connectors for two (2) AC input feeds.

1.3.2 Battery Connections: Battery cables are available.

(A) List 1 and 2: Battery leads are connected to an Anderson connector exiting the rear of the unit.

(B) Lists 5 and 6: Battery and battery return leads terminated in two-hole lugs are connected to threaded studs located inside the Distribution Unit. Battery leads are brought into the right side (as viewed from the front) of the shelf.

1.3.3 Load Connections:

(A) List 1 and 2: Load and load return leads are connected to a screw-type terminal block located on the front of the shelf.

(B) Lists 5 and 6: Load distribution (circuit breakers, if furnished) and load return leads terminated in two-hole lugs are connected to threaded studs located inside the Distribution

Unit. Load leads are brought into the right side (as viewed from the front) of the shelf and are accessible from the front of the shelf.

Page 89 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

System Application Guide

Spec. No. 582136600 (Model 211 NGFB

Load distribution (GMT fuses) and load return leads are connected to receptacles located inside the Distribution Unit. Load leads are brought into the right side (as viewed from the front) of the shelf and are accessible from the front of the shelf.

)

1.3.4 Alarm and Monitoring Connections: Customer wiring cables are available.

(A) List 1 and 2: Relay output and digital input leads are connected to screw-type terminal blocks located on the SCU+ located inside the shelf. These leads enter the rear of the shelf.

(B) Lists 5 and 6: Relay output and digital input leads are connected to screw-type terminal blocks located on the Customer Interface Board located inside the shelf. These leads enter the right side (as viewed from the front) of the shelf and are accessible from the front of the shelf.

1.3.5 Dimensions and Weights: Refer to the PHYSICAL SIZE INFORMATION section of this document.

Page 90 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

PHYSICAL SIZE INFORMATION

Overall Dimensions – List 1

SAG582136600

Issue AU, February 21, 2014

Home

Left Side View

Top View

17.3

18.3

19.0

Front View

Rear View

0.5

1.25

1.72

5

12

Right Side View

0.23

Bottom View

Notes:

1. All dimensions are in inches, unless otherwise specified.

2. Weight in LBS.

Net: 16

Shipping:

3. Finish: Front Panels are Gray

Shelf is Galvaneal.

Page 91 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

Additional Dimensions – List 1 with Wall Mounting Kit (P/N 541285)

Home

Horizontal Wall Mounting

19.45

18.72

15.34

0.90

Top View

Rear View

Vertical Wall Mounting

Note: All dimensions are in inches.

1.15

18.38

19.87

Top View

2.65

Right Side

View

Page 92 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

SAG582136600

Issue AU, February 21, 2014

Additional Dimensions – List 1 with Optional 19” Rear Cover Kit, P/N 555260

Home

0.6

Top View

16.9

18.3

19.0

Front View

Rear View

0.5

1.25

1.75

12.0

Right Side View

0.25

Page 93 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

Additional Dimensions – List 1 with Optional 3” Projection Mount Kit, P/N 556828

Home

Rear View

Left Side

View

1.25

1.71

0.24

Top View

16.9

18.3

19.0

Front View

12

3

0.5

Right Side

View

Page 94 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

Overall Dimensions – List 2

SAG582136600

Issue AU, February 21, 2014

Home

Page 95 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

Additional Dimensions – List 2 with Wall Mounting Kit (P/N 541285)

Home

Horizontal Wall Mounting

23.41

22.69

15.34

0.90

Top View

Rear View

Vertical Wall Mounting

Note: All dimensions are in inches.

1.15

22.34

23.83

Top View

2.65

Right Side

View

Page 96 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

SAG582136600

Issue AU, February 21, 2014

Additional Dimensions – List 2 with Optional 23” Rear Cover Kit, P/N 555261

Home

0.6

Top View

20.8

22.3

23.0

Front View

Rear View

0.5

1.25

1.75

12.0

Right Side View

0.25

Page 97 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

Overall Dimensions – List 5

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

Home

Left Side View

Top View

17.3

18.3

19.0

19.4

Front View

Rear View

0.5

5

12

Right Side View

3.00

0.23

3.46

Bottom View

Notes:

1. All dimensions are in inches, unless otherwise specified.

2. Weight in LBS.

Net: 30

Shipping:

3. Finish: Front Panels are Gray

Shelf is Galvaneal.

Page 98 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

Overall Dimensions – List 6

SAG582136600

Issue AU, February 21, 2014

Home

Page 99 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

Additional Dimensions – Lists 1, 2, 5 and 6 with Wall Mounting Kit (P/N 553203)

Home

Lists 1 and 2

18.936 (19” Shelf, shown)

22.906 (23” Shelf)

20.543 (19”, shown Shelf)

24.513 (23” Shelf)

Bottom View

Lists 5 and 6

4.625

Right Side View

Note: All dimensions are in inches.

18.936 (19” Shelf, shown)

22.906 (23” Shelf)

20.543 (19” Shelf, shown)

24.513 (23” Shelf)

Bottom View

4.625

Right Side View

Page 100 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

Overall Dimensions – List KG

Notes:

1. Dimensions in inches unless otherwise specified.

2. Finish: Gray

3. Weight:

Net:

Shipping:

See Mounting

Angle Detail

Left Side

View

Top View

17.25

18.25

19.25

22.31

23.25

Front View

SAG582136600

Issue AU, February 21, 2014

Home

5.05

8.31

10.00

0.92

1.75

Right Side

View

R 0.125 (TYP)

0.235

0.125

1.250

0.125

Bottom View

Mounting Angle Detail

0.500

0.500

0.125 0.235

0.125

1.250

Page 101 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

Overall Dimensions – 19” Battery Tray

Optional Battery Disconnect Circuit Breakers

(Shown on Right Side, Available on Either Side)

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

Home

A

See

Note 3

10.50

12.25

14.00

(as ordered)

ISO View

Notes:

1. All dimensions are in inches,

unless otherwise specified.

2. P/N 558047 tray shown.

P/Ns 541034, 540841 and 548213 similar.

3.

Dimension

B

558047

541034

540841

7.78

7.03

6.90

17.60

20.95

12.50

548213 7.28

22.35

4. Weight in LBS.

(per tray, less batteries).

Tray P/Ns

558047

541034

540841

548213

With Circuit

Breaker Option

25.0 lbs

25.3 lbs

18.5 lbs

26.0 lbs

Without Circuit

Breaker Option

23.0 lbs

23.3 lbs

16.5 lbs

24.0 lbs

5. Finish: Gray

6. Maximum trays available per rack is three (3).

Front View B

See Note 3

Right Side View

Page 102 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

Overall Dimensions – 23” Battery Tray

Optional Battery Disconnect Circuit Breakers

(Shown on Right Side, Available on Either Side)

SAG582136600

Issue AU, February 21, 2014

Home

A

See

Note 3

10.50

12.25

14.00

(as ordered)

ISO View

Notes:

1. All dimensions are in inches,

unless otherwise specified.

2. P/N 528496 tray shown.

P/N 540842 and 557573 similar.

3.

Tray P/N

Dimension

A

Dimension

B

528496 9.781

24.437

540842 6.90

557573 10.48

12.50

23.14

4. Weight in LBS.

(per tray, less batteries).

Part No.

With Circuit

Breaker Option

Without Circuit

Breaker Option

528496 33 lbs 29 lbs

540842 20 lbs 18 lbs

557573 25 lbs 23 lbs

5. Finish: Gray

6. Maximum trays available per rack is three (3).

Front View

B

See Note 3

Right Side View

Page 103 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

SAG582136600

Issue AU, February 21, 2014

BATTERY MANUFACTURER INFORMATION

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

Home

Some equipment described in this System Application Guide is designed to accommodate batteries from various manufacturers. The following are referenced in this document.

C&D: C&D Technologies, Inc., Powercom Div., 1400 Union Meeting Road, Blue Bell, PA 19422-0858

Deka ® : East Penn Mfg. Co., Inc., Lyon Station, PA 19536-0147

Douglas ®

Marathon

: Douglas Battery Mfg. Co., 500 Battery Dr., Winston-Salem, NC 27117-2159

TM : GNB Industrial Power, a Division of Exide Technologies, Princeton, NJ 08543.

Northstar: NorthStar Battery Co. LLC, 4000 Continental Way, Springfield, MO 65803

PowerSafe Enersys TM : EnerSys Inc., Reading, PA, 196212-4145

RELATED DOCUMENTATION

Installation Instructions: Section 6031

User Instructions: Section 6032

Battery Cabinet Spec. No. 541434

Installation and User Instructions: Section 6023

Battery Cabinet Spec. No. 545534

Installation and User Instructions: Section 6033

Battery Cabinet Spec. No. 545506

Installation and User Instructions: Section 6036

Battery Cabinet Spec. No. 554631

Installation and User Instructions: UM554631

Rectifier User Instructions: UM1R481000

SCU+ Controller User Instructions: UM1M521BNA

ACU+ Controller User Instructions: UM1M820BNA

Page 104 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

System Application Guide

Spec. No. 582136600 (Model 211 NGFB )

SAG582136600

Issue AU, February 21, 2014

Home

REVISION RECORD

Issue

Change

Number

(ECO)

AN

AP

AR

AS

AT

AU

Description of Change Date Approved

LLP217521

Additional Battery P/N added to Battery Table.

Added optional 19” and 23” rear cover kits P/N

555260 and P/N 555261. Added optional digital input cable kit P/N 554935. Added references to List

73 optional external battery cable assembly P/N

555050. Added PCU blank filler as accessory.

02/20/2013

Shanon

Ravacio

LLP218760 Added Battery Cabinet P/N 554631.

LLP218923

Frame grounding lug adapter P/N 556872 (for use when wall mounted) added.

05/16/2013 John Jasko

09/04/2013 John Jasko

LLP218844 Added optional 3” projection mount kit P/N 556828. 09/19/2013

Khristebelle

Ilagan

LLP219497 Option to not power controller during LVBD added. 11/22/2013 John Jasko

LLP219376

Added 90A Bullet Breaker P/Ns 138887 and

138888. Added battery tray P/N 557573. Replaced battery tray P/N 541036 with 558047.

John Jasko

Feb 28, 2014

Jerry Li

Mar 4, 2014

02/21/2014 John Jasko

Emerson Network Power, Energy Systems, North America, Inc.

4350 Weaver Parkway, Warrenville, IL 60555

Toll Free: 800-800-1280 (USA and Canada)

Telephone: 440-246-6999 Fax: 440-246-4876

Web: EmersonNetworkPower.com/EnergySystems

EnergyNet: Secure.EmersonNetworkPower.com

Page 105 of 105

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement

Table of contents