SAG582136600
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
Issue AU, February 21, 2014
SYSTEM OVERVIEW
Description: The NetSure™ 211 NGFB DC Power System is a complete integrated power system containing rectifiers, intelligent control, metering, monitoring, and distribution. This power system consists of the following mounted in a 1RU or 2RU high by 19” or 23” wide shelf.
• 500W or 1000W Rectifier Modules
The 1RU high by 19” wide shelf accommodates two (2) 500W or 1000W Rectifier Modules.
The 1RU high by 23” wide shelf accommodates three (3) 500W or 1000W Rectifier Modules.
The 2RU high by 19” wide shelf accommodates four (4) 500W or 1000W Rectifier Modules.
The 2RU high by 23” wide shelf accommodates six (6) 500W or 1000W Rectifier Modules.
The Rectifier Modules provide load power, battery float current, and battery recharge current during normal operating conditions. The Rectifier Modules are designed to provide constant power. They are designed with the latest patented switch-mode technology using DSP (Digital Signal Processing) functionality for efficient operation.
This means that, within the normal operating ambient temperature range and input voltage range, the maximum available output power is a constant 500W or 1000W.
Within these ranges, the Rectifier Modules operate in one of three modes, depending upon load demands. Transition between modes is completely automatic. If ambient temperature rises above or input voltage falls below acceptable values, Rectifier
Modules continue to operate but at derated output power levels.
1) Constant Voltage Mode: For any initial output voltage setting from 42 to 58 volts, output voltage remains constant regardless of load. This is the normal operating condition, in which loads are being supplied and batteries are float charged. Rectifier Modules operate in the Constant Voltage Mode unless load increases to the point where the product of load current and output voltage is approximately
500W or 1000W.
2) Constant Power Mode: As load increases above approximately 500W or 1000W
(non-adjustable), output current continues to increase, but output voltage decreases as required to maintain constant output power. Rectifier
Modules operate in the
Constant Power Mode unless load continues to increase to the point where the current limit setting is reached.
List 1 (List 2 similar)
3) Constant Current Mode: If load increases above the current limit setting, output voltage decreases linearly to maintain output current at current limit. List 5 (List 6 similar)
Page 1 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
• ACU+ (Advanced Control Unit Plus)
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
The ACU+ provides Rectifier Module and optional Low Voltage Battery Disconnect
(LVBD) or Low Voltage Load Disconnect (LVLD) control, metering functions, monitoring functions, and local/remote alarms as well as PCU control, data acquisition, system alarm management, and advanced battery and energy management. The ACU+ contains an LCD display and keypad for local access. It provides connection for binary inputs, programmable relay outputs, and a charge control function. The controller also supports rectifier temperature compensation if the system is equipped with a temperature probe (or multiple temperature probes connected via a Temperature Concentrator (SM TEMP), and ambient temperature monitoring if equipped with a second temperature probe. The ACU+ provides
Ethernet connection and supports software upgrade via its USB port. It also comes with a comprehensive web page and SNMP capability for remote system management.
• SCU+ (Standard Control Unit Plus)
The SCU+ provides Rectifier Module and optional Low Voltage Battery Disconnect
(LVBD) or Low Voltage Load Disconnect (LVLD) control, metering functions, monitoring functions, and local/remote alarms. The SCU+ contains an LCD display and keypad for local access. It provides connection for binary inputs, programmable relay outputs, and a charge control function. The controller also supports rectifier temperature compensation if the system is equipped with a temperature probe (or multiple temperature probes connected via a Temperature Concentrator (SM TEMP), and ambient temperature monitoring if equipped with a second temperature probe.
The SCU+ also provides Ethernet connection and SNMP capability.
Family:
Spec. No.:
Model:
Input Voltage
Output Voltage:
• Distribution Unit
Various Distribution Unit options are available, as described in this document. The
Distribution Unit can be equipped with an optional Low Voltage Battery Disconnect
(LVBD) or Low Voltage Load Disconnect (LVLD) contactor.
NetSure™
582136600
211 NGFB
Nominal 120/208/240 volts AC, single phase, 3-wire, 50/60 Hz, with an operating range of 100 to 250 volts. Acceptable input frequency range is
45 to 65 Hz.
-48 Volts DC
Output Capacity:
Rectifier Module: 500W @ Vout >48Vdc (10.5A @ -48Vdc) or
1000W @ Vout >48Vdc (20.9A @ -48Vdc)
Page 2 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
System: See the following table.
SAG582136600
Issue AU, February 21, 2014
Agency Approval:
Framework Type:
Mounting Width:
Mounting Depth:
Mounting Height:
Access:
Control:
Color:
Environment:
Spec. No.
System DC Output Capability
208/240VAC Input 120VAC Input
+40°C (+104°F) +65°C (+149°F) +40°C (+104°F) +65°C (+149°F)
500W
Rect.
1000W
Rect.
500W
Rect.
1000W
Rect.
500W
Rect.
1000W
Rect.
500W
Rect.
1000W
Rect.
58213660001 20.8A 41.6A 12.6A 25A 20.8A 27.4A 12.6A 16.4A
58213660002 31.2A 62.4A 18.9A 37.5A 31.2A 41.1A 18.9A 24.6A
58213660005 41.6A 83.2A 25.2A
58213660006 62.4A 124.8A 37.8A
50A
75A
41.6A 54.8A 25.2A 32.8A
62.4A 82.2A 37.8A 49.2A
UL 60950 Recognized, CAN/CSA 22.2
Relay Rack Mounted
19” or 23”, nominal
12”
1.75” (1RU) or 3.5” (2RU)
Front for Installation, Operation, and Maintenance
Microprocessor
Front Panels are Gray; Shelf is Galvaneal
-40°C (-40°F) to +65°C (+149°F),
with deratings (see SPECIFICATIONS section)
Page 3 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
58213660001
Side AC Input Connectors
(P/O List 1) and
58213660002
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
or
Distribution Unit
Side AC Input Connectors
(P/O List 2) and
or
Distribution Unit
Page 4 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
58213660001 with P/N 555260
Rear AC Input Connector
( P/O P/N 555260 ) and
58213660001 with P/N 556828 Kit
or
Rear AC Input Connector
SAG582136600
Issue AU, February 21, 2014
Distribution Unit
Distribution Unit
or
Page 5 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
58213660002 with P/N 555261
Rear AC Input Connector
( P/O P/N 555261 ) and
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
or
Distribution Unit
Page 6 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
58213660005
Side AC Input Connectors
(P/O List 5) and
58213660006
SAG582136600
Issue AU, February 21, 2014
or
Distribution Unit
or
Side AC Input Connectors
(P/O List 6) and
or
Distribution Unit
or
Page 7 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
DISTRIBUTION UNIT (Lists 1 and 2)
(10) GMT Fuse Load Positions
Low Voltage Battery Disconnect (LVBD)
(1) Set Battery Cables
(10) GMT Fuse Load Positions
NO Low Voltage Disconnect
(1) Set Battery Cables
System Application Guide
Spec. No. 582136600 (Model 211 NGFB
)
DISTRIBUTION UNIT (Lists 5 and 6)
(13) GMT Fuse Load Positions
Low Voltage Battery Disconnect (LVBD)
(3) Battery Landing Points
(13) GMT Fuse Load Positions
Low Voltage Load Disconnect (LVLD)
(3) Battery Landing Points
(13) GMT Fuse Load Positions
NO Low Voltage Disconnect
(3) Battery Landing Points
(5) GMT Fuse Load Positions
(4) Bullet-Nose Circuit Breaker Load Positions
Low Voltage Battery Disconnect (LVBD)
(3) Battery Landing Points
(5) GMT Fuse Load Positions
(4) Bullet-Nose Circuit Breaker Load Positions
Low Voltage Load Disconnect (LVLD)
(3) Battery Landing Points
(5) GMT Fuse Load Positions
(4) Bullet-Nose Circuit Breaker Load Positions
NO Low Voltage Disconnect
(3) Battery Landing Points
(5) GMT Fuse Load Positions
(2) Bullet-Nose Circuit Breaker Load Positions
(2) Bullet-Nose Circuit Breaker Battery Disconnect Positions
Low Voltage Battery Disconnect (LVBD)
(5) GMT Fuse Load Positions
(2) Bullet-Nose Circuit Breaker Load Positions
(2) Bullet-Nose Circuit Breaker Battery Disconnect Positions
Low Voltage Load Disconnect (LVLD)
(5) GMT Fuse Load Positions
(2) Bullet-Nose Circuit Breaker Load Positions
(2) Bullet-Nose Circuit Breaker Battery Disconnect Positions
NO Low Voltage Disconnect
Page 8 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
SAG582136600
Issue AU, February 21, 2014
Other List Options
List 60: Five (5) Load Lead Assemblies for 10A GMT Fuse Positions
(for use w/ Lists BC, LC, NC, BA, LA, and NA)
List 61: Eight (8) Load Lead Assemblies for 10A GMT Fuse Positions
(for use w/ Lists BF, LF, and NF)
List 62: Five (5) Load Lead Assemblies for 15A GMT Fuse Positions
(for use w/ Lists BF, LF, and NF)
List 65: Shelf Side Battery Cables
(for use w/ Lists BF, LF, NF, BC, LC, and NC)
List 66: Battery Side Battery Cables
(for use w/ Lists BF, LF, NF, BC, LC, and NC)
List 67: Battery Side Battery Cables
(For use with Lists BC, LC, NC, BF, LF, and NF)
List 71: Optional External Battery Cables (8 AWG) with Anderson Connector
for (1) Battery String (for use w/ Lists BG and NG)
List 72: Optional External Battery Cables with Anderson Connector
for (2) Battery Strings (for use w/ Lists BG and NG)
List 73 : Optional External Battery Cables (6 AWG) with Anderson Connector
for (1) Battery String (for use w/ Lists BG and NG)
List 89: Relay Rack Earthquake Anchor Kit
List 90: Temperature Probe (12 ft. total)
List 91: Temperature Probe (33 ft. total)
List KG: GMT Fuse Load Distribution Panel
Accessory Options
Mounting and Adapter Kits
AC Input Cables and Line Cords
External Battery Disconnect Unit
SM TEMP Temperature Concentrator
Digital Input/Relay Output Cables
SEE ALSO
System Overview
Page 9 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
TABLE OF CONTENTS
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
System
Overview
List 71: Optional External Battery Cable Assembly with Anderson Connector for (1) Battery String,
List 72: Optional External Battery Cable Assembly with Anderson Connector for (2) Battery
List 73: Optional External Battery Cable Assembly with Anderson Connector for (1) Battery String,
List BF: Distribution Unit with GMT Fuse Load Distribution Positions and with Low Voltage Battery
List LF: Distribution Unit with GMT Fuse Load Distribution Positions and with Low Voltage Load
List NF: Distribution Unit with GMT Fuse Load Distribution Positions and w/out Low Voltage
List BC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load
List LC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load
List NC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load
List BA: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load
Distribution Positions, Circuit Breaker Battery Disconnect Positions, and with Low Voltage Battery
Page 10 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
SAG582136600
Issue AU, February 21, 2014
List LA: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load
Distribution Positions, Circuit Breaker Battery Disconnect Positions, and with Low Voltage Load
List NA: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load
Distribution Positions, Circuit Breaker Battery Disconnect Positions, and w/out Low Voltage
List BG: Distribution Unit with GMT Fuse Load Distribution Positions and with Low Voltage Battery
List NG: Distribution Unit with GMT Fuse Load Distribution Positions and w/out Low Voltage
Page 11 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
Load Distribution Wiring (GMT Fuses) (Lists BC, LC, NC, BA, LA, and NA installed in a List 5 or 6,
Load Distribution Wiring (Circuit Breakers), Input Battery Wiring (Circuit Breakers), and CO Ground
Input Battery Wiring (Lists BF, LF, NF, BC, LC, and NC installed in a List 1 or 5, List 5 shown) and
Page 12 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
SAG582136600
Issue AU, February 21, 2014
LIST DESCRIPTIONS
List 1: 1RU High by 19” Wide Shelf
Features
♦ Consists of a 1RU high by 19” wide shelf.
♦ Two (2) 8 AWG 48” long battery cables are factory connected inside the shelf. These cables are terminated at the customer end in a Red SB50 Anderson battery connector. A mating Anderson battery connector is provided [Housing: Emerson P/N 138922, Anderson Power Products P/N 992G1. Contacts
(two provided): Emerson P/N 247109602, Anderson Power Products P/N 5952].
♦ Mounted to the side of the shelf is an AC input housing with plug-in connector for a single AC input feed.
♦ The “Digital Input and Relay Outputs Cable” P/N 545494 (shelf side) is factory connected inside the shelf.
A mating half is available.
♦ The shelf houses up to two (2) Rectifier Modules, one (1) Controller, and one (1) Distribution Unit.
Restrictions
Each List 1 shelf holds up to two (2) Rectifier Modules.
Ordering Notes
1) Order List 1 as required.
Also order the following as required.
for your site.
3) Order up to two (2) Rectifier Modules per shelf: P/N 1R48500 (500W) or P/N 1R481000 (1000W).
Cable or Line Cord.
5) Order one (1) Distribution Unit (List BG
6) Order Optional External Battery Cables with Anderson Connector for one (1) to two (2) Battery Strings per
7) Order Relay Rack Anchor Kit(s) ( List 89 ) as required.
Charge Temperature Compensation feature, the other to monitor ambient temperature.
9) Order Battery Trays ( List 94 ) as required.
10) Order Relay Racks per ACCESSORY DESCRIPTIONS section.
11) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
12) Order External Battery Disconnect Unit per ACCESSORY DESCRIPTIONS section.
13) Order Battery Cabinet per ACCESSORY DESCRIPTIONS section.
14) Order Mating Digital Input/Relay Output Cables per ACCESSORY DESCRIPTIONS section.
15) Order Spare Anderson Battery Connector per ACCESSORY DESCRIPTIONS section.
16) Order Special Application Digital Input Cable Kit per ACCESSORY DESCRIPTIONS section.
Page 13 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
List 2: 1RU High by 23” Wide Shelf
Features
♦ Consists of a 1RU high by 23” wide shelf.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB
)
♦ Two (2) 8 AWG 48” long battery cables are factory connected inside the shelf. These cables are terminated at the customer end in a Red SB50 Anderson battery connector. A mating Anderson battery connector is provided [Housing: Emerson P/N 138922, Anderson Power Products P/N 992G1. Contacts
(two provided): Emerson P/N 247109602, Anderson Power Products P/N 5952].
♦ Mounted to the side of the shelf is an AC input housing with plug-in connector for a single AC input feed.
♦ The “Digital Input and Relay Outputs Cable” P/N 545494 (shelf side) is factory connected inside the shelf.
A mating half is available.
♦ The shelf houses up to three (3) Rectifier Modules, one (1) Controller, and one (1) Distribution Unit.
Restrictions
Each List 2 shelf holds up to three (3) Rectifier Modules.
Ordering Notes
1) Order List 2 as required.
Also order the following as required.
for your site.
3) Order up to three (3) Rectifier Modules per shelf: P/N 1R48500 (500W) or P/N 1R481000 (1000W).
Cable or Line Cord.
5) Order one (1) Distribution Unit (List BG
6) Order Optional External Battery Cables with Anderson Connector for one (1) to two (2) Battery Strings per
7) Order Relay Rack Anchor Kit(s) ( List 89 ) as required.
Charge Temperature Compensation feature, the other to monitor ambient temperature.
9) Order Battery Trays ( List 93 ) as required.
10) Order Relay Racks per ACCESSORY DESCRIPTIONS section.
11) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
12) Order External Battery Disconnect Unit per ACCESSORY DESCRIPTIONS section.
13) Order Battery Cabinet per ACCESSORY DESCRIPTIONS section.
14) Order Mating Digital Input/Relay Output Cables per ACCESSORY DESCRIPTIONS section.
15) Order Spare Anderson Battery Connector per ACCESSORY DESCRIPTIONS section.
16) Order Special Application Digital Input Cable Kit per ACCESSORY DESCRIPTIONS section.
Page 14 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
SAG582136600
Issue AU, February 21, 2014
List 5: 2RU High by 19” Wide Shelf
Features
♦ Consists of a 2RU high by 19” wide shelf.
♦ Mounted to the side of the shelf is an AC input housing with plug-in connectors for two (2) AC input feeds.
♦ Includes the Customer Interface Board that provides additional Relay Outputs and Digital Inputs.
♦ The “Relay Outputs Cable” P/N 541308 (shelf side) is factory connected inside the shelf. A mating half is available. A “Digital Input Cable” (shelf side and customer side) is also available.
♦ The shelf houses up to four (4) Rectifier Modules, one (1) Controller, and one (1) Distribution Unit.
Restrictions
Each List 5 shelf holds up to four (4) Rectifier Modules.
Ordering Notes
1) Order List 5 as required.
Also order the following as required.
2) Order one (1) SCU+ controller (P/N 1M521BNA
) or (1) ACU+ controller (P/N 1M820BNA ) per shelf. Also
specify the appropriate configuration file for your site.
3) Order up to four (4) Rectifier Modules per shelf: P/N 1R48500 (500W) or P/N 1R481000 (1000W).
Cables or Line Cords.
5) Order one (1) Distribution Unit (List BF ,
6) Order one (1) List 60 for each List BC, LC, NC, BA, LA, or NA ordered.
Each List 60 provides five (5) Load Lead Assemblies for 10A GMT Fuse Positions.
Order one (1) List 61 for each List BF, LF, or NF ordered.
Each List 61 provides eight (8) Load Lead Assemblies for 10A GMT Fuse Positions.
Order one (1) List 62 for each List BF, LF, or NF ordered.
Each List 62 provides five (5) Load Lead Assemblies for 15A GMT Fuse Positions.
7) Order one (1) List KG Distribution Fuse Panel per shelf, as required.
for each List BC, LC, NC, BF, LF, or NF ordered.
9) Order up to three (3) List 67 for each List BC, LC, NC, BF, LF, and NF ordered.
10) Order Relay Rack Anchor Kit(s) ( List 89 ) as required.
Charge Temperature Compensation feature, the other to monitor ambient temperature.
12) Order Battery Trays ( List 94 ) as required.
13) Order Relay Racks per ACCESSORY DESCRIPTIONS section.
14) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
15) Order External Battery Disconnect Unit per ACCESSORY DESCRIPTIONS section.
16) Order Battery Cabinet per ACCESSORY DESCRIPTIONS section.
17) Order Digital Input/Relay Output Cables per ACCESSORY DESCRIPTIONS section.
18) Order lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section.
Page 15 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
List 6: 2RU High by 23” Wide Shelf
Features
♦ Consists of a 2RU high by 23” wide shelf.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB
)
♦ Mounted to the side of the shelf is an AC input housing with plug-in connectors for two (2) AC input feeds.
♦ Includes the Customer Interface Board that provides additional Relay Outputs and Digital Inputs.
♦ The “Relay Outputs Cable” P/N 541308 (shelf side) is factory connected inside the shelf. A mating half is available. A “Digital Input Cable” (shelf side and customer side) is also available.
♦ The shelf houses up to six (6) Rectifier Modules, one (1) Controller, and one (1) Distribution Unit.
Restrictions
Each List 6 shelf holds up to six (6) Rectifier Modules.
Ordering Notes
1) Order List 6 as required.
Also order the following as required.
2) Order one (1) SCU+ controller (P/N 1M521BNA
) or (1) ACU+ controller (P/N 1M820BNA ) per shelf. Also
specify the appropriate configuration file for your site.
3) Order up to six (6) Rectifier Modules per shelf: P/N 1R48500 (500W) or P/N 1R481000 (1000W).
Cables or Line Cords.
5) Order one (1) Distribution Unit (List BF ,
6) Order one (1) List 60 for each List BC, LC, NC, BA, LA, or NA ordered.
Each List 60 provides five (5) Load Lead Assemblies for 10A GMT Fuse Positions.
Order one (1) List 61 for each List BF, LF, or NF ordered.
Each List 61 provides eight (8) Load Lead Assemblies for 10A GMT Fuse Positions.
Order one (1) List 62 for each List BF, LF, or NF ordered.
Each List 62 provides five (5) Load Lead Assemblies for 15A GMT Fuse Positions.
7) Order one (1) List KG GMT Distribution Fuse Panel per shelf, as required.
for each List BC, LC, NC, BF, LF, or NF ordered.
9) Order up to three (3) List 67 for each List BC, LC, NC, BF, LF, and NF ordered.
10) Order Relay Rack Anchor Kit(s) ( List 89 ) as required.
Charge Temperature Compensation feature, the other to monitor ambient temperature.
12) Order Battery Trays ( List 93 ) as required.
13) Order Relay Racks per ACCESSORY DESCRIPTIONS section.
14) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
15) Order External Battery Disconnect Unit per ACCESSORY DESCRIPTIONS section.
16) Order Battery Cabinet per ACCESSORY DESCRIPTIONS section.
17) Order Digital Input/Relay Output Cables per ACCESSORY DESCRIPTIONS section.
18) Order lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section.
Page 16 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
Rectifier Module (500W), P/N 1R48500
Features
♦ Provides one (1) Model R48-500, Spec. No. 1R48500,
500 watt / 48 volt Rectifier Module.
Restrictions
Each List 1 Shelf holds up to two (2) Rectifier Modules.
Each List 2 Shelf holds up to three (3) Rectifier Modules.
Each List 5 Shelf holds up to four (4) Rectifier Modules.
Each List 6 Shelf holds up to six (6) Rectifier Modules.
DO NOT install different wattage Rectifier Modules in same shelf.
Ordering Notes
1) Order by P/N (1R48500) as required.
Rectifier Module (1000W), P/N 1R481000
Features
♦ Provides one (1) Model R48-1000, Spec. No. 1R481000,
1000 watt / 48 volt Rectifier Module.
Restrictions
Each List 1 Shelf holds up to two (2) Rectifier Modules.
Each List 2 Shelf holds up to three (3) Rectifier Modules.
Each List 5 Shelf holds up to four (4) Rectifier Modules.
Each List 6 Shelf holds up to six (6) Rectifier Modules.
DO NOT install different wattage Rectifier Modules in same shelf.
Ordering Notes
1) Order by P/N (1R481000) as required.
ACU+ (Advanced Control Unit Plus), P/N 1M820BNA
Features
♦ Provides the ACU+ Controller.
♦ Factory programmed with the configuration file specified when ordered.
Restrictions
ACU+ is not available in List 1 or List 2 shelves.
Each List 5 or List 6 shelf must contain one (1) SCU+ or one (1) ACU+
Controller.
Ordering Notes
1) Order one (1) ACU+ (P/N 1M820BNA) or one (1) SCU+ Controller (P/N
1M521BNA) or for each shelf.
For the ACU+ controller, specify also one of the following configurations. a) List 5 and 6 with Low Voltage Disconnect: 550166. b) List 5 and 6 without Low Voltage Disconnect: 550167.
Note: For custom ACU+ configurations, contact Emerson.
SAG582136600
Issue AU, February 21, 2014
Page 17 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
SCU+ (Standard Control Unit Plus), P/N 1M521BNA
Features
♦ Provides the SCU+ Controller.
♦ Factory programmed with the configuration file specified when ordered.
Restrictions
Each shelf must contain one (1) SCU+ or one (1) ACU+ Controller.
Ordering Notes
1) Order one (1) SCU+ Controller (P/N 1M521BNA) or one (1) ACU+ (P/N
1M820BNA) for each shelf.
For the SCU+ controller, specify also one of the following configurations. a) List 1 and 2 with Low Voltage Disconnect: 545304. b) List 1 and 2 without Low Voltage Disconnect: 545305. c) List 5 and 6 with Low Voltage Disconnect: 545298. d) List 5 and 6 without Low Voltage Disconnect: 545299.
Note: For custom SCU+ configurations, contact Emerson.
List 60: Five (5) Load Lead Assemblies (P/N 535206) for 10A GMT Fuse Positions
Features
♦ Provides 12’ long, 16 AWG, load and load return leads that are terminated on one end with the appropriate mating connector to plug into the system’s
10A GMT fuse connector on a List BC, LC, NC, BA, LA, or NA Distribution
Unit, and are left un-terminated at the remaining end for connection into customer loads.
Restrictions
For use with List BC, LC, NC, BA, LA, and NA Distribution units only.
Ordering Notes
1) Order one (1) List 60 for each List BC, LC, NC, BA, LA, or NA Distribution Unit.
Each List 60 provides five (5) GMT fuse load lead assemblies, P/N 535206.
List 61: Eight (8) Load Lead Assemblies (P/N 535206) for 10A GMT Fuse
Positions
Features
♦ Provides 12’ long, 16 AWG, load and load return leads that are terminated on one end with the appropriate mating connector to plug into the system’s 10A
GMT fuse connector on a List BF, LF, or NF Distribution Unit, and are left unterminated at the remaining end for connection into customer loads.
Restrictions
For use with List BF, LF, and NF Distribution units only.
Ordering Notes
1) Order one (1) List 61 for each List BF, LF, or NF Distribution Unit.
Each List 61 provides eight (8) GMT fuse load lead assemblies, P/N 535206.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB
)
Page 18 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
SAG582136600
Issue AU, February 21, 2014
List 62: Five (5) Load Lead Assemblies (P/N 540988) for 15A GMT Fuse Positions
Features
♦ Provides 12’ long, 14 AWG, load and load return leads that are terminated on one end with the appropriate mating connector to plug into the system’s 15A GMT fuse connector on a List BF, LF, or NF Distribution Unit, and are left un-terminated at the remaining end for connection into customer loads.
Restrictions
For use with List BF, LF, and NF Distribution units only.
Ordering Notes
1) Order one (1) List 62 for each List BF, LF, or NF Distribution Unit.
Each List 62 provides five (5) GMT fuse load lead assemblies, P/N 540988.
List 65: Shelf Side Battery Cables, P/N 540814
Features
♦ Provides two (2) 3’ long, 2 AWG, battery cables terminated in a 2-position Red
SB120 Anderson connector (mates with the Anderson connector on List 66).
Remaining end terminated in lugs for connection to shelf.
Restrictions
For use with List BF, LF, NF, BC, LC, and NC Distribution units only.
Ordering Notes
1) Order as required. Each shelf provides landings for up to three (3) battery strings.
List 66: Battery Side Battery Cables, P/N 540954
Features
♦ Provides two (2) 12’ long, 2 AWG, battery cables terminated in a 2-position Red SB120 Anderson connector (mates with the Anderson connector on List 65). Remaining end unterminated for connection to batteries.
Restrictions
For use with List BF, LF, NF, BC, LC, and NC only.
Ordering Notes
1) Order as required. Each shelf provides landings for up to three (3) battery strings.
List 67: Battery Cable, P/N 545709
Features
♦ Provides two (2) 4’ long, 8 AWG, battery cables terminated in a 2-position Anderson connector on the battery side. Remaining end terminated in lugs for connection to shelf.
Restrictions
, or P/N 554631 battery cabinets only.
For use with List BF, LF, NF, BC, LC, and NC Distribution units only.
Ordering Notes
1) Order up to three (3) List 67 for each List BC, LC, NC, BF, LF, and NF ordered.
2) Order one (1) for each battery cabinet feed required.
Page 19 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
List 71: Optional External Battery Cable Assembly with Anderson Connector for (1) Battery String, P/N 545493
Features
♦ Provides two (2) 6’ long, 8 AWG, battery cables terminated in a Red SB50
Anderson connector for connecting one (1) battery string to the system.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB
)
♦ One end of the assembly connects to the Anderson connector factory wired to the shelf’s battery connection points, and the other end contains two (2) unterminated cables for connection into a customer battery string.
Restrictions
For use with List BG and NG only.
Ordering Notes
1) Order if required.
2) Order Spare Anderson Battery Connector per ACCESSORY DESCRIPTIONS section.
List 72: Optional External Battery Cable Assembly with Anderson Connector for (2) Battery Strings, P/N 535124
Features
♦ Provides four (4) 6’ long, 10 AWG, battery cables terminated in a Red SB50
Anderson connector for connecting two (2) battery strings to the system.
♦ One end of the assembly connects to the Anderson connector factory wired to the shelf’s battery connection points, and the other end contains four (4) unterminated cables for connection into customer battery strings.
Restrictions
For use with List BG and NG Distribution units only.
Ordering Notes
1) Order if required.
2) Order Spare Anderson Battery Connector per ACCESSORY DESCRIPTIONS section.
List 73: Optional External Battery Cable Assembly with Anderson Connector for (1) Battery String, P/N 555050
Features
♦ Provides two (2) 6’ long, 6 AWG, battery cables terminated in a Red SB50
Anderson connector for connecting one (1) battery string to the system.
♦ One end of the assembly connects to the Anderson connector factory wired to the shelf’s battery connection points, and the other end contains two (2) unterminated cables for connection into a customer battery string.
Restrictions
For use with List BG and NG only.
Ordering Notes
1) Order if required.
2) Order Spare Anderson Battery Connector per ACCESSORY DESCRIPTIONS section.
Page 20 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
SAG582136600
Issue AU, February 21, 2014
List 89: Relay Rack Earthquake Anchor Kit, P/N P0987167
Features
♦ Provides four (4) sets of hardware for anchoring the relay rack to the floor.
Ordering Notes
1) Order as required.
List 90: Optional Temperature Probe,
P/N 04118246 (shelf side half) and P/N 04118247 (probe side half, 9 ft. long)
Features
♦ Up to two (2) temperature probes can be connected to the Customer Interface (IB2) Board. Either or both probes can be programmed to monitor ambient temperature or battery temperature.
♦ A temperature probe set as a battery probe can also be designated to be used for the battery charge temperature compensation feature. If the system is equipped with the ACU+ Controller, the battery charge temperature compensation feature can be programmed to use one probe or the average or highest value of all probes programmed to monitor battery temperature. The battery charge temperature compensation feature allows the controller to automatically increase or decrease the output voltage of the system to maintain battery float current as battery temperature decreases or increases, respectively. Battery life can be extended when an optimum charge voltage to the battery with respect to temperature is maintained.
♦ If the system is equipped with the ACU+ Controller, a temperature probe set as a battery probe can also be used for controlling against battery thermal runaway (BTRM feature).
♦ The Temperature Probe assembly consists of two pieces that plug together to make a complete probe.
When ordered, P/N 04118246 (3 feet long) is pre-wired to the shelf and P/N 04118247 (9 feet long) is shipped loose. Total length: 12 ft.
Restrictions
A temperature probe programmed to monitor battery temperature should be mounted on the top or side of a battery cell to sense battery temperature. A temperature probe used for battery charge temperature compensation or BTRM (Battery Thermal Runaway Management) should also be mounted on the top or side of a battery cell. A temperature probe programmed to monitor ambient temperature should be mounted in a convenient location, away from direct sources of heat or cold.
Ordering Notes
1) Order up to two (2) Temperature Probes for each shelf, as required.
Each List 90 includes one (1) P/N 04118246 and one (1) P/N 04118247.
2) For a Temperature Probe with a longer cable see List 91.
List 91: Optional Temperature Probe,
P/N 04118246 (shelf side half) and P/N 04116740 (probe side half, 30 ft. long)
Features
♦ See above for description of Temperature Probes.
♦ The Temperature Probe assembly consists of two pieces that plug together to make a complete probe.
When ordered, P/N 04118246 (3 feet long) is pre-wired to the shelf and P/N 04116740 (30 feet long) is shipped loose. Total Length: 33 ft.
Restrictions
See above for restrictions.
Ordering Notes
1) Order up to two (2) Temperature Probes for each shelf, as required.
Each List 91 includes one (1) P/N 04118246 and one (1) P/N 04116740.
Page 21 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
2) For a Temperature Probe with a shorter cable see List 90.
List 93: Battery Tray for 23” Relay Rack
Features
♦ Provides one battery tray that mounts four (4) 12V front terminal
Valve Regulated Lead Acid (VRLA) batteries. Batteries are configured as one (1) 48V string.
♦ Accepts various VRLA batteries. See Ordering Notes below.
♦
See Overall Dimensions - 23” Battery Tray under PHYSICAL SIZE
INFORMATION for battery tray dimensions and typical arrangement. Note that two battery trays are available to accommodate the various size batteries listed in the Ordering
Notes tables.
♦ Trays can be ordered with or without battery disconnect circuit breakers. When circuit breakers are ordered, one is provided in the -48V lead of each battery string (1 circuit breaker per tray).
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
♦ Battery cables are available terminated at the power system end in an Anderson connector. Battery lugs are available for the remaining end.
Restrictions
For 23” relay racks only.
Maximum number of List 93’s per rack is three (3).
A single List 93 must mount at bottom of rack. Multiple List 93’s must mount starting at bottom of rack and working upward.
Ordering Notes
1) Order multiples of List 93 for more than one (1) battery tray. See
Restrictions above.
2) Order one (1) or more P/N 362736700 Cable Bracket(s) as required.
3) Order batteries separately. Tables A, B, and C list the batteries recommended for use with List 93.
4) Specify rack spacing of 6U (10.5”), 7U (12.25”), or 8U (14”) between trays and above top tray as required for battery clearance. See Tables A, B, and C.
5) Battery lugs are provided, as specified from Table D.
6) Specify with or without battery disconnect circuit breakers.
Note: All List 93 trays in a rack will be furnished with or without battery disconnect circuit breakers as specified for the first tray ordered.
7) If ordering List 93 with circuit breakers, order one (1) circuit breaker per List 93 from Table E.
8) If ordering List 93 with circuit breakers, specify breaker mounting on left side of tray, right side of tray, or remote mounting. Circuit breaker mounting kits shown in the Table E will be installed. Kit numbers are provided for reference only
9) If ordering List 93 with circuit breakers, order Alarm Jumper P/N 524384 for each system to connect the alarm terminal of up to three (3) battery disconnect circuit breakers.
Page 22 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
Battery Tray P/N 528496
Manufacturer* Model
Emerson
Network
Power
P/N
GNB Marathon M12V125FT
GNB Marathon M12V155FT
Northstar NSB110FT
--
112795
--
Northstar NSB170FT --
Deka Unigy I 12AVR-150ET 122018
C&D
C&D
FA 12-150F
TEL12-210F
FA12150
554579
Douglas
Douglas
DGS12-150F
DSN12-170F
125453
--
Rated 8-Hr.
Capacity
(Ah)
125
155
110
167
150
150
202
150
170.8
Dimension
W x L x H
(Inches)
4.90 X 22.00 X 11.15
4.90 X 22.00 X 11.15
4.92 X 22.05 X 8.94
4.92 X 22.05 X 12.60
4.90 X 22.00 X 11.75
4.92 X 21.97 X 12.70
4.90 X 22.00 X 12.80
4.90 X 22.00 X 12.70
4.92 X 22.05 X 12.60
SAG582136600
Issue AU, February 21, 2014
Required
Tray
Spacing
7U
7U
7U
8U
8U
8U
8U
8U
8U
Weight
(per battery)
(lbs)
105
119
91
131
115
131
132
137
130
* See Battery Manufacturer Information located at the end of this document.
Table A
Manufacturer*
Northstar
Northstar
Douglas
Douglas
Enersys
Model
NSB40FT**
NSB60FT**
DGS12-25F
DGS12-50F
12TD50F
Battery Tray P/N 540842
Emerson
Network
Power
P/N
--
--
--
--
--
Rated 8-Hr.
Capacity
(Ah)
38.1
57.9
25
50
48
Dimension
W x L x H
(Inches)
3.80 X 9.80 X 8.20
4.20 X 11.30 X 10.40
3.94 X 10.80 X 7.60
3.94 X 10.80 X 11.60
4.2 X 10.9 X 8.7
Required
Tray
Spacing
* See Battery Manufacturer Information located at the end of this document.
** Batteries MUST be equipped with front access terminal option. See Battery Manufacturer for ordering information.
6U
7U
6U
8U
6U
Weight
(per battery)
(lbs)
34
49
27
48
38
Table B
Manufacturer*
Enersys
Model
12TD150F --
Battery Tray P/N 557573
Emerson
Network
Power
P/N
Rated 8-Hr.
Capacity
(Ah)
143
* See Battery Manufacturer Information located at the end of this document.
Dimension
W x L x H
(Inches)
4.3 X 21.7 X 11.3
Table C
Required
Tray
Spacing
8U
Weight
(per battery)
(lbs)
105
Page 23 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
Battery
Specified
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
Battery Lug Kit Part Number
(Kit provides two lugs for one tray.)
Lists 5 and 6 Lists 1 and 2
GNB Marathon M12V125FT
GNB Marathon M12V155FT
Northstar NSB110FT
Northstar NSB170FT
Deka Unigy I 12AVR-150ET
C&D FA 12-150F
C&D TEL12-210F
Douglas DGS12-150F
Douglas DSN12-170F
Northstar NSB40FT
Northstar NSB60FT
Douglas DGS12-25F
Douglas DGS12-50F
Enersys 12TD50F
Enersys 12TD150F
528234
528236
528234
(for use with 10 AWG wire and List 72)
(for use with 8 AWG wire and L ist 71)
555069
(for use with 6 AWG wire and L ist 73)
Table D
Ampere
Rating
Part No., Circuit Breaker,
Electrical/Mechanical Trip 1
(Black Handle)
Part No., Left-Side
Breaker Mtg. Kit
(For Reference Only)
15
20
25
30
1
3
5
10
256690300
256690700
256691100
256691500
256691900
256692300
256692700
256693100
35
40
50
60
256693500
256693900
256694300
256694700
70
75
256695100
256695500
100 256695900
1 Provides an alarm during an electrical or manual trip condition.
Table E
528501
540989
545581
Part No., Right-Side
Breaker Mtg. Kit
(For Reference Only)
528500
Page 24 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
SAG582136600
Issue AU, February 21, 2014
List 94: Battery Tray for 19” Relay Rack
Features
♦ Provides one battery tray that mounts four (4) 12V front terminal
Valve Regulated Lead Acid (VRLA) batteries. Batteries are configured as one (1) 48V string.
♦ Accepts various VRLA batteries. See Ordering Notes below.
♦
See Overall Dimensions - 19” Battery Tray under PHYSICAL SIZE
INFORMATION for battery tray dimensions and typical arrangement. Note that three battery trays are available to accommodate the various size batteries listed in the Ordering
Notes tables.
♦ Trays can be ordered with or without battery disconnect circuit breakers. When circuit breakers are ordered, one is provided in the -48V lead of each battery string (1 circuit breaker per tray).
♦ Battery cables are available terminated at the power system end in an Anderson connector. Battery lugs are available for the remaining end.
Restrictions
For 19” relay racks only.
Maximum number of List 94’s per rack is three (3).
A single List 94 must mount at bottom of rack. Multiple List 94’s must mount starting at bottom of rack and working upward.
Ordering Notes
1) Order multiples of List 94 for more than one (1) battery tray. See
Restrictions above.
2) Order one (1) or more P/N 362736700 Cable Bracket(s) as required.
3) Order batteries separately. Tables F, G, H and I list batteries recommended for use with List 94.
4) Specify rack spacing of 6U (10.5”), 7U (12.25”), or 8U (14”) between trays and above top tray as required for battery clearance. See
Tables F, G, H and I.
5) Battery lugs are provided, as specified from Table J.
6) Specify with or without battery disconnect circuit breakers.
Note: All List 94 trays in a rack will be furnished with or without battery disconnect circuit breakers as specified for the first tray ordered.
7) If ordering List 94 with circuit breakers, order one (1) circuit breaker per List 94 from Table K.
8) If ordering List 94 with circuit breakers, specify breaker mounting on left side of tray, right side of tray, or remote mounting. Circuit breaker mounting kits shown in the Table K will be installed. Kit numbers are provided for reference only.
9) If ordering List 94 with circuit breakers, order Alarm Jumper P/N 524384 for each system to connect the alarm terminal of up to three (3) battery disconnect circuit breakers.
Page 25 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
Manufacturer*
Northstar
Northstar
GNB Marathon
Enersys
Model
NSB90FT
NSB100FT
M12V90FT
12TD100F4
--
--
--
--
Battery Tray P/N 558047
Emerson
Network
Power
P/N
Rated 8-Hr.
Capacity
(Ah)
90
100
90
96
* See Battery Manufacturer Information located at the end of this document.
Dimension
W x L x H
(Inches)
4.25 X 15.59 X 10.04
4.25 X 15.59 X 11.03
4.13 X 15.55 X 10.63
4.3 X 15.5 X 11.3
System Application Guide
Spec. No. 582136600 (Model 211
Required
Tray
Spacing
7U
7U
7U
8U
NGFB
Weight
(per battery)
(lbs)
71
78
70
71
)
Table F
Manufacturer* Model
GNB Marathon M12V105FT
Enersys 12TD100F6
--
--
Battery Tray P/N 541034
Emerson
Network
Power
P/N
Rated 8-Hr.
Capacity
(Ah)
105
97
* See Battery Manufacturer Information located at the end of this document.
Dimension
W x L x H
(Inches)
4.33 X 20.12 X 9.37
4.3 X 20.0 X 9.4
Required
Tray
Spacing
7U
7U
Weight
(per battery)
(lbs)
79
73
Table G
Manufacturer*
Northstar
Northstar
Douglas
Douglas
Enersys
Model
NSB40FT**
NSB60FT**
DGS12-25F
DGS12-50F
12TD50F
Emerson
Network
Power
P/N
--
--
--
--
--
Battery Tray P/N 540841
Rated 8-Hr.
Capacity
(Ah)
38.1
57.9
25
50
48
Dimension
W x L x H
(Inches)
3.80 X 9.80 X 8.20
4.20 X 11.30 X 10.40
3.94 X 10.80 X 7.60
3.94 X 10.80 X 11.60
4.2 X 10.9 X 8.7
Required
Tray
Spacing
* See Battery Manufacturer Information located at the end of this document.
** Batteries MUST be equipped with front access terminal option. See Battery Manufacturer for ordering information.
6U
7U
6U
8U
6U
Table H
Weight
(per battery)
(lbs)
34
49
27
48
38
Page 26 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
Manufacturer*
Enersys
Enersys
Model
12V125F
12TD150F
Battery Tray P/N 548213
Emerson
Network
Power P/N
122009
--
Rated
8-Hr.
Capacit y (Ah)
125
143
Dimension
W x L x H
(Inches)
4.10 X 22.10 X 12.40
4.3 X 21.7 X 11.3
* See Battery Manufacturer Information located at the end of this document.
SAG582136600
Issue AU, February 21, 2014
Required
Tray
Spacing
8U
8U
Weight
(per battery)
(lbs)
124
105
Table I
Battery
Specified
Battery Lug Kit Part Number
(Kit provides two lugs for one tray.)
Lists 5 and 6 Lists 1 and 2
Northstar NSB90FT
Northstar NSB100FT
GNB Marathon M12V90FT
GNB Marathon M12V105FT
Northstar NSB40FT
Northstar NSB60FT
Douglas DGS12-25F
Douglas DGS12-50F
Enersys 12V125F
Enersys 12TD50F
Enersys 12TD100F4
Enersys 12TD100F6
Enersys 12TD150F
528234
540989
(for use with 10 AWG wire and List 72)
545581
(for use with 8 AWG wire and List 71)
555069
(for use with 6 AWG wire and L ist 73)
Table J
Page 27 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
System Application Guide
Spec. No. 582136600 (Model 211
Ampere
Rating
Part No., Circuit Breaker,
Electrical/Mechanical Trip 1
(Black Handle)
Part No., Left-Side
Breaker Mtg. Kit
(For Reference Only)
60
70
75
100
30
35
40
50
10
15
20
25
1
3
5
256690300
256690700
256691100
256691500
256691900
256692300
256692700
256693100
256693500
256693900
256694300
256694700
256695100
256695500
256695900
1 Provides an alarm during an electrical or manual trip condition.
Table K
528501
Part No., Right-Side
Breaker Mtg. Kit
(For Reference Only)
528500
NGFB
)
Page 28 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
SAG582136600
Issue AU, February 21, 2014
List BF: Distribution Unit with GMT Fuse Load Distribution Positions and with Low Voltage Battery Disconnect (LVBD)
Features
♦ Provides a Distribution Unit with Low Voltage
Battery Disconnect (LVBD), a battery shunt, (3) battery connection points, and thirteen (13) GMT fuse load distribution positions.
♦ Five (5) 0A to 15A GMT fuse load distribution positions.
♦ Eight (8) 0A to 10A GMT fuse load distribution positions.
Restrictions
For use with List 5 and 6 only.
The (13) Position GMT Fuse Printed Wiring Board is rated 100A at +40°C (+104°F) and 59.5A at 65°C
(+149°F).
Unless otherwise specified fuses are mounted from bottom to top, starting with the highest capacity and working to the lowest capacity.
In an ambient of 40°C (+104°F):
• Fuseholders F1-F8 are rated for a 10A fuse maximum. An empty space is not required between fuses of any value.
• Fuseholders F9-F13 are rated for a 15A fuse maximum. An empty space is not required between fuses of any value. However, 15A fuses cannot be placed in adjacent fuseholders. 15A fuses must be separated by a smaller fuse or a space.
In an ambient of 65°C (+149°F):
• Fuseholders F1-F8 are rated for a 10A fuse maximum. An empty space is required between 10A fuses.
A fuse greater than 3A cannot be placed in a fuseholder adjacent to a 10A fuse.
• Fuseholders F9-F13 are rated for a 15A fuse maximum. An empty space is required between 15A fuses.
10A fuses cannot be placed in adjacent fuseholders. A fuse greater than 3A cannot be placed in a fuseholder adjacent to a 10A fuse.
See also the
Restrictions under “ GMT Load Distribution Fuses ” in the ACCESSORY DESCRIPTIONS
section.
Ordering Notes
1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf.
Also order the following as required.
2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
the 10A fuse blocks.
the 15A fuse blocks.
List 65 and List 67 are factory installed.
6) The controller remains powered when the LVBD contactor opens. Specify if you require List BF to be factory configured for the controller not to be powered when the LVBD contactor opens.
Page 29 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
List LF: Distribution Unit with GMT Fuse Load Distribution Positions
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
and with Low Voltage Load Disconnect (LVLD)
Features
♦ Provides a Distribution Unit with Low Voltage Load
Disconnect (LVLD), a battery shunt, (3) battery connection points, and thirteen (13) GMT fuse load distribution positions.
♦ Five (5) 0A to 15A GMT fuse load distribution positions.
♦ Eight (8) 0A to 10A GMT fuse load distribution positions.
Restrictions
For use with List 5 and 6 only.
The (13) Position GMT Fuse Printed Wiring Board is rated
100A at +40°C (+104°F) and 59.5A at 65°C (+149°F).
Unless otherwise specified fuses are mounted from bottom to top, starting with the highest capacity and working to the lowest capacity.
In an ambient of 40°C (+104°F):
• Fuseholders F1-F8 are rated for a 10A fuse maximum. An empty space is not required between fuses of any value.
• Fuseholders F9-F13 are rated for a 15A fuse maximum. An empty space is not required between fuses of any value. However, 15A fuses cannot be placed in adjacent fuseholders. 15A fuses must be separated by a smaller fuse or a space.
In an ambient of 65°C (+149°F):
• Fuseholders F1-F8 are rated for a 10A fuse maximum. An empty space is required between 10A fuses.
A fuse greater than 3A cannot be placed in a fuseholder adjacent to a 10A fuse.
• Fuseholders F9-F13 are rated for a 15A fuse maximum. An empty space is required between 15A fuses.
10A fuses cannot be placed in adjacent fuseholders. A fuse greater than 3A cannot be placed in a fuseholder adjacent to a 10A fuse.
See also the
Restrictions under “ GMT Load Distribution Fuses ” in the ACCESSORY DESCRIPTIONS
section.
Ordering Notes
1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf.
Also order the following as required.
2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
the 10A fuse blocks.
the 15A fuse blocks.
List 65 and List 67 are factory installed.
Page 30 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
SAG582136600
Issue AU, February 21, 2014
List NF: Distribution Unit with GMT Fuse Load Distribution Positions and w/out Low Voltage Disconnect
Features
♦ Provides a Distribution Unit w/out low voltage disconnect, a battery shunt, (3) battery connection points, and thirteen (13) GMT fuse load distribution positions.
♦ Five (5) 0A to 15A GMT fuse load distribution positions.
♦ Eight (8) 0A to 10A GMT fuse load distribution positions.
Restrictions
For use with List 5 and 6 only.
The (13) Position GMT Fuse Printed Wiring Board is rated 100A at +40°C (+104°F) and 59.5A at 65°C
(+149°F).
Unless otherwise specified fuses are mounted from bottom to top, starting with the highest capacity and working to the lowest capacity.
In an ambient of 40°C (+104°F):
• Fuseholders F1-F8 are rated for a 10A fuse maximum. An empty space is not required between fuses of any value.
• Fuseholders F9-F13 are rated for a 15A fuse maximum. An empty space is not required between fuses of any value. However, 15A fuses cannot be placed in adjacent fuseholders. 15A fuses must be separated by a smaller fuse or a space.
In an ambient of 65°C (+149°F):
• Fuseholders F1-F8 are rated for a 10A fuse maximum. An empty space is required between 10A fuses.
A fuse greater than 3A cannot be placed in a fuseholder adjacent to a 10A fuse.
• Fuseholders F9-F13 are rated for a 15A fuse maximum. An empty space is required between 15A fuses.
10A fuses cannot be placed in adjacent fuseholders. A fuse greater than 3A cannot be placed in a fuseholder adjacent to a 10A fuse.
See also the
Restrictions under “ GMT Load Distribution Fuses ” in the ACCESSORY DESCRIPTIONS
section.
Ordering Notes
1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf.
Also order the following as required.
2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
the 10A fuse blocks.
the 15A fuse blocks.
List 65 and List 67 are factory installed.
Page 31 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
List BC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker
Load Distribution Positions, and with Low Voltage Battery Disconnect (LVBD)
Features
♦ Provides a Distribution Unit with Low Voltage Battery
Disconnect (LVBD), a battery shunt, (3) battery connection points, four (4) bullet nose-type circuit breaker load distribution positions, five (5) GMT fuse load distribution positions.
♦ Five (5) 0A to 10A GMT fuse load distribution positions.
Restrictions
For use with List 5 and 6 only.
Maximum distribution current is 72A at @ +65°C (+149°F) and 100A @ +40°C (+104°F).
The GMT fuse block has a 35A @ +40°C (+104°F) and a
21A @ +65°C (+149°F) maximum capacity. Maximum GMT fuse size is 10A. At +65°C (+149°F), a space is required between GMT fuses greater than 5A.
Maximum load distribution circuit breaker size is 75A @ +65°C (+149°F).
Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes
SHALL HAVE an empty mounting position between it and any other overcurrent protective device. There are no restrictions in an ambient of +40°C (+104°F).
See also the
Restrictions under “ GMT Load Distribution Fuses
” and “ Bullet Nose-Type Circuit Breakers ” in
the ACCESSORY DESCRIPTIONS section.
Ordering Notes
1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf.
Also order the following as required.
2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
the 10A fuse blocks.
List 65 and List 67 are factory installed.
5) Order circuit breaker load lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section.
6) The controller remains powered when the LVBD contactor opens. Specify if you require List BC to be factory configured for the controller not to be powered when the LVBD contactor opens.
Page 32 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
SAG582136600
Issue AU, February 21, 2014
List LC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker
Load Distribution Positions, and with Low Voltage Load Disconnect (LVLD)
Features
♦ Provides a Distribution Unit with Low Voltage Load
Disconnect (LVLD), a battery shunt, (3) battery connection points, four (4) bullet nose-type circuit breaker load distribution positions, five (5) GMT fuse load distribution positions.
♦ Five (5) 0A to 10A GMT fuse load distribution positions.
Restrictions
For use with List 5 and 6 only.
Maximum distribution current is 72A at @ +65°C (+149°F) and 100A @ +40°C (+104°F).
The GMT fuse block has a 35A @ +40°C (+104°F) and a
21A @ +65°C (+149°F) maximum capacity. Maximum GMT fuse size is 10A. At +65°C (+149°F), a space is required between GMT fuses greater than 5A.
Maximum load distribution circuit breaker size is 75A @ +65°C (+149°F).
Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes
SHALL HAVE an empty mounting position between it and any other overcurrent protective device. There are no restrictions in an ambient of +40°C (+104°F).
See also the
Restrictions under “ GMT Load Distribution Fuses
” and “ Bullet Nose-Type Circuit Breakers ” in
the ACCESSORY DESCRIPTIONS section.
Ordering Notes
1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf.
Also order the following as required.
2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
the 10A fuse blocks.
List 65 and List 67 are factory installed.
5) Order circuit breaker load lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section.
Page 33 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
List NC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker
Load Distribution Positions, and w/out Low Voltage Disconnect
Features
♦ Provides a Distribution Unit w/out low voltage disconnect, a battery shunt, (3) battery connection points, four (4) bullet nose-type circuit breaker load distribution positions, five (5) GMT fuse load distribution positions.
♦ Five (5) 0A to 10A GMT fuse load distribution positions.
Restrictions
For use with List 5 and 6 only.
Maximum distribution current is 72A at @ +65°C (+149°F) and 100A @ +40°C (+104°F).
The GMT fuse block has a 35A @ +40°C (+104°F) and a
21A @ +65°C (+149°F) maximum capacity. Maximum GMT fuse size is 10A. At +65°C (+149°F), a space is required between GMT fuses greater than 5A.
Maximum load distribution circuit breaker size is 75A @ +65°C (+149°F).
Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes
SHALL HAVE an empty mounting position between it and any other overcurrent protective device. There are no restrictions in an ambient of +40°C (+104°F).
See also the
Restrictions under “ GMT Load Distribution Fuses
” and “ Bullet Nose-Type Circuit Breakers ” in
the ACCESSORY DESCRIPTIONS section.
Ordering Notes
1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf.
Also order the following as required.
2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
the 10A fuse blocks.
List 65 and List 67 are factory installed.
5) Order circuit breaker load lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section.
Page 34 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
SAG582136600
Issue AU, February 21, 2014
List BA: Distribution Unit with GMT Fuse Load Distribution Positions,
Circuit Breaker Load Distribution Positions, Circuit Breaker Battery Disconnect Positions, and with Low Voltage Battery Disconnect (LVBD)
Features
♦ Provides a Distribution Unit with Low Voltage Battery
Disconnect (LVBD), a battery shunt, two (2) bullet nose-type circuit breaker load distribution positions, two
(2) bullet nose-type circuit breaker battery disconnect positions, five (5) GMT fuse load distribution positions.
♦ Five (5) 0A to 10A GMT fuse load distribution positions.
Restrictions
For use with List 5 and 6 only.
Maximum distribution current is 72A at @ +65°C (+149°F) and 100A @ +40°C (+104°F).
The GMT fuse block has a 35A @ +40°C (+104°F) and a
21A @ +65°C (+149°F) maximum capacity. Maximum
GMT fuse size is 10A. At +65°C (+149°F), a space is required between GMT fuses greater than 5A.
Maximum load distribution or battery circuit breaker size is 75A @ +65°C (+149°F).
Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes
SHALL HAVE an empty mounting position between it and any other overcurrent protective device. There are no restrictions in an ambient of +40°C (+104°F).
See also the
Restrictions under “ GMT Load Distribution Fuses
” and “ Bullet Nose-Type Circuit Breakers ” in
the ACCESSORY DESCRIPTIONS section.
Ordering Notes
1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf.
Also order the following as required.
2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
the 10A fuse blocks.
4) Order circuit breaker load lugs and battery input lugs per Wiring Notes under ACCESSORY
DESCRIPTIONS section.
5) The controller remains powered when the LVBD contactor opens. Specify if you require List BA to be factory configured for the controller not to be powered when the LVBD contactor opens.
Page 35 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
List LA: Distribution Unit with GMT Fuse Load Distribution Positions,
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
Circuit Breaker Load Distribution Positions, Circuit Breaker Battery Disconnect Positions, and with Low Voltage Load Disconnect (LVLD)
Features
♦ Provides a Distribution Unit with Low Voltage Load
Disconnect (LVLD), a battery shunt, two (2) bullet nose-type circuit breaker load distribution positions, two (2) bullet nose-type circuit breaker battery disconnect positions, five (5) GMT fuse load distribution positions.
♦ Five (5) 0A to 10A GMT fuse load distribution positions.
Restrictions
For use with List 5 and 6 only.
Maximum distribution current is 72A at @ +65°C (+149°F) and 100A @ +40°C (+104°F).
The GMT fuse block has a 35A @ +40°C (+104°F) and a 21A @ +65°C (+149°F) maximum capacity.
Maximum GMT fuse size is 10A. At +65°C (+149°F), a space is required between GMT fuses greater than
5A.
Maximum load distribution or battery circuit breaker size is 75A @ +65°C (+149°F).
Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes
SHALL HAVE an empty mounting position between it and any other overcurrent protective device. There are no restrictions in an ambient of +40°C (+104°F).
See also the
Restrictions under “ GMT Load Distribution Fuses
” and “ Bullet Nose-Type Circuit Breakers ” in
the ACCESSORY DESCRIPTIONS section.
Ordering Notes
1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf.
Also order the following as required.
2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
the 10A fuse blocks.
4) Order circuit breaker load lugs and battery input lugs per Wiring Notes under ACCESSORY
DESCRIPTIONS section.
Page 36 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
SAG582136600
Issue AU, February 21, 2014
List NA: Distribution Unit with GMT Fuse Load Distribution Positions,
Circuit Breaker Load Distribution Positions, Circuit Breaker Battery Disconnect Positions, and w/out Low Voltage Disconnect
Features
♦ Provides a Distribution Unit w/out low voltage disconnect, a battery shunt, two (2) bullet nose-type circuit breaker load distribution positions, two (2) bullet nose-type circuit breaker battery disconnect positions, five (5) GMT fuse load distribution positions.
♦ Five (5) 0A to 10A GMT fuse load distribution positions.
Restrictions
For use with List 5 and 6 only.
Maximum distribution current is 72A at @ +65°C (+149°F) and 100A @ +40°C (+104°F).
The GMT fuse block has a 35A @ +40°C (+104°F) and a
21A @ +65°C (+149°F) maximum capacity. Maximum GMT fuse size is 10A. At +65°C (+149°F), a space is required between GMT fuses greater than 5A.
Maximum load distribution or battery circuit breaker size is 75A @ +65°C (+149°F).
Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes
SHALL HAVE an empty mounting position between it and any other overcurrent protective device. There are no restrictions in an ambient of +40°C (+104°F).
See also the
Restrictions under “ GMT Load Distribution Fuses
” and “ Bullet Nose-Type Circuit Breakers ” in
the ACCESSORY DESCRIPTIONS section.
Ordering Notes
1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf.
Also order the following as required.
2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
the 10A fuse blocks.
4) Order circuit breaker load lugs and battery input lugs per Wiring Notes under ACCESSORY
DESCRIPTIONS section.
Page 37 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
List BG: Distribution Unit with GMT Fuse Load Distribution Positions and with Low Voltage Battery Disconnect (LVBD)
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
Features
♦ Provides a Distribution Unit with Low Voltage Battery
Disconnect (LVBD), battery cables, and ten (10) GMT fuse load distribution positions (15A maximum).
♦ Two (2) 8 AWG 48” long battery cables are factory connected inside the shelf. These cables are terminated at the customer end in a Red SB50
Anderson battery connector. A mating Anderson battery connector is provided [Housing: Emerson P/N
138922, Anderson Power Products P/N 992G1.
Contacts (two provided): Emerson P/N 247109602, Anderson Power Products P/N 5952].
♦ Ten (10) 0A to 15A GMT fuse load distribution positions.
Restrictions
For use with List 1 and 2 only.
The Distribution Unit has a 50A @ +40°C (+104°F) and 40A @ +65°C (+149°F) maximum capacity.
Maximum GMT fuse size is 15A. In an ambient of +65°C (+149°F), an empty space is required between 15A fuses.
See also the
Restrictions under “ GMT Load Distribution Fuses ” in the ACCESSORY DESCRIPTIONS
section.
Ordering Notes
1) Order one (1) Distribution Unit (List BG or NG) for each List 1 or 2 shelf.
Also order the following as required.
2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
3) Order Optional External Battery Cables with Anderson Connector for one (1) to two (2) Battery Strings per
4) Order Spare Anderson Battery Connector per ACCESSORY DESCRIPTIONS section.
Page 38 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
SAG582136600
Issue AU, February 21, 2014
List NG: Distribution Unit with GMT Fuse Load Distribution Positions and w/out Low Voltage Disconnect
Features
♦ Provides a Distribution Unit w/out low voltage disconnect, a battery shunt, battery cables, and ten
(10) GMT fuse load distribution positions (15A maximum).
♦ Two (2) 8 AWG 48” long battery cables are factory connected inside the shelf. These cables are terminated at the customer end in a Red SB50
Anderson battery connector. A mating Anderson battery connector is provided [Housing: Emerson P/N
138922, Anderson Power Products P/N 992G1.
Contacts (two provided): Emerson P/N 247109602, Anderson Power Products P/N 5952].
♦ Ten (10) 0A to 15A GMT fuse load distribution positions.
Restrictions
For use with List 1 and 2 only.
The Distribution Unit has a 50A @ +40°C (+104°F) and 40A @ +65°C (+149°F) maximum capacity.
Maximum GMT fuse size is 15A. In an ambient of +65°C (+149°F), an empty space is required between 15A fuses.
See also the
Restrictions under “ GMT Load Distribution Fuses ” in the ACCESSORY DESCRIPTIONS
section.
Ordering Notes
1) Order one (1) Distribution Unit (List BG or NG) for each List 1 or 2 shelf.
Also order the following as required.
2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
3) Order Optional External Battery Cables with Anderson Connector for one (1) to two (2) Battery Strings per
4) Order Spare Anderson Battery Connector per ACCESSORY DESCRIPTIONS section.
Page 39 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
List KG: Distribution Panel with (20) GMT Fuse Load Distribution Positions
Features
♦ 1U-high GMT fuse panel that provides Single Load
Distribution (-48V)
♦ Provides twenty (20) 0A to 15A GMT fuse load distribution positions.
Caution: At +40°C and +65°C ambient, a fuse with a rating of greater than 10 amperes SHALL
HAVE an empty mounting position between it and any other fuse.
♦ Maximum Capacity: 80A @ +40°C and 80A @ +65°C
♦ Factory mounted and connected to List 5 or 6 shelf.
♦ If the Distribution Unit in the system is equipped with Low Voltage Load Disconnect (LVLD), all List KG loads are disconnected.
♦ If one or more distribution fuses opens, one set of Form-C relay contacts changes state, and resistive battery is provided to an alarm terminal. Alarm circuit is factory connected to activate the Power System
Controller fuse alarm
Restrictions
For use with List 5 and 6 only.
Mounts only immediately above List 5 or 6 shelf.
Maximum distribution current is 80A.
See also the
Restrictions under “ GMT Load Distribution Fuses ” in the ACCESSORY DESCRIPTIONS
section.
Ordering Notes
1) Order one (1) List KG GMT Distribution Fuse Panel Assembly for each List 5 or 6 shelf as required.
Also order the following as required.
2) Order GMT Load Distribution Fuses per ACCESSORY DESCRIPTIONS section.
Page 40 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
SAG582136600
Issue AU, February 21, 2014
ACCESSORY DESCRIPTIONS
Relay Racks
Features
♦ The following relay racks are available.
Restrictions
Customer must mount Power/Distribution Shelf in relay rack. If battery trays are ordered, they are factory mounted in the relay rack.
Ordering Notes
1) Order from relay racks listed in Table 1.
Part
Number
543156
543161
543160
543162
543163
543164
525003
534653
524961
534654
Size
7’0” H x 23” W
Available Mounting
Positions (1RU = 1-3/4”)
23” Relay Racks
51-3/8” H x 23” W
6’0” H x 23” W
28RU
37RU
45RU
7’0” H x 23” W
7’6” H x 23” W
8’0” H x 23” W
45RU
48RU
51RU
19” Relay Racks
51-3/8” H x 19” W 28RU
6’0" H x 19” W
6’0” H x 19” W
6’6” H x 19” W
37RU
37RU
41RU
534651
528183
6’6” H x 19” W
7’0” H x 19” W
41RU
45RU
524988
524963
534652
7’0” H x 19”W
7’6” H x 19” W
8’0" H x 19” W
45RU
48RU
51RU
Note 1: Complies with Bellcore Seismic Zone 4 requirements.
Table 1
Available Relay Racks
Notes
Welded
Welded
Seismic
(Note 1)
Welded
Welded
Welded
Welded
Seismic
(Note 1)
Welded
Seismic
(Note 1)
Welded
Seismic
(Note 1)
Welded
Welded
Welded
Page 41 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
Mounting and Adapter Kits
Optional Wall Mount Bracket Kit for Lists 1 and 2, P/N 541285
Features
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
♦ Allows for horizontal or vertical wall mounting.
♦
See Physical Size Information for mounting dimensions.
Restrictions
For use with List 1 or 2 only.
Customer must supply mounting fasteners for securing the Wall Mount
Bracket to the wall.
This Kit will not support wall-mounting when the 58213660001 and
58213660002 shelves are flush mounted.
Ordering Notes
1) Order P/N 541285, which consists of two (2) P/N 545701 horizontal wall mounting brackets and two (2)
P/N 541284 vertical wall mounting brackets, and eight (8) 12-24 x ½” screws for attaching the brackets to the shelf.
Optional Wall Mount Bracket Kit for Lists 1, 2, 5 and 6, P/N 553203
Features
♦ Allows for vertical wall mounting.
♦
See Physical Size Information for mounting dimensions.
Restrictions
Customer must supply mounting fasteners for securing the Wall Mount Brackets to the wall.
Ordering Notes
1) Order P/N 553203, which consists of two (2) wall brackets (P/N 553058 and 553059) and eight (8) 12-24 x ¾” screws with four (4) ground washers for attaching the brackets to the shelf.
Optional 19” to 23” 1RU Rack Adapter Kit, P/N 540993
Features
♦ Allows for 23” 1RU relay rack mounting
Restrictions
For use with List 1 only.
Ordering Notes
1) Order P/N 540993, which consists of two (2) P/N 540994 adapters and four (4) 12-24 x 1/”2 thread forming screws.
Optional 19” to 23” 2RU Rack Adapter Kit, P/N 545728
Features
♦ Allows for 23” 2RU relay rack mounting
Restrictions
For use with List 5 only.
Ordering Notes
1) Order P/N 545728, which consists of two (2) P/N 545727 adapters and four (4) 12-24 x 1/”2 thread forming screws.
Page 42 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
SAG582136600
Issue AU, February 21, 2014
Optional 19” Rear Cover Kit, P/N 555260
Features
♦ Allows for 19” 1RU flush rack mount configuration
♦ AC input unit is moved to the rear panel
Restrictions
For use with List 1 only.
Ordering Notes
1) Order P/N 555260, which consists of one (1) P/N
553271 19” rear cover assembly, one (1) P/N 29041838 caution label and one (1) P/N PSK04118562 AC input jumper.
Optional 3” Projection Mount Kit for List 1, P/N 556828
Features
♦ Allows for 19" 1RU 3" projection rack mount configuration
Restrictions
For use with List 1 only.
Ordering Notes
1) Order by P/N 556828 as required.
Optional 23” Rear Cover Kit, P/N 555261
Features
♦ Allows for 23” 1RU flush rack mount configuration
♦ AC input unit is moved to the rear panel
Restrictions
For use with List 2 only.
Ordering Notes
1) Order P/N 555261, which consists of one (1) P/N
555113 23” rear cover assembly, one (1) P/N
29041838 caution label and one (1) P/N
PSK04118555 AC input jumper.
Rear Battery Cable Exit Kit P/N 547645
Features
♦ Provides 12” battery cables exiting rear of shelf
Restrictions
For use with List 5 only.
Ordering Notes
1) For use with Battery Cabinets only.
Page 43 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
Distribution Devices
GMT Load Distribution Fuses
Features
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
♦ Each List BF, LF, NF Distribution Unit holds up to five (5) 0-15A GMT load distribution fuses and eight (8)
0-10A GMT load distribution fuses.
♦ Each List BC, LC, NC, BA, LA, NA Distribution Unit holds up to five (5) 0-10A GMT load distribution fuses.
♦ Each List BG and NG Distribution Unit holds up to ten (10) 0-15A GMT load distribution fuses.
♦ Each List KG Distribution Panel holds up to twenty (20) 0-15A GMT load distribution fuses.
Restrictions
When used for power distribution, load should not exceed 80% of device rating, except 10 and 15 ampere fuses, for which load should not exceed 70% of device rating.
See also the Restrictions for each Distribution Unit in the LIST DESCRIPTIONS section.
See also Load Distribution Wiring (GMT Fuses) (Lists BG and NG only) , Load Distribution Wiring (GMT
Fuses) (Lists BF, LF, and NF only)
Ordering Notes
1) Order GMT fuses per Table 2.
Ampere Rating
18/100 GMT-A
1/4
1/2
3/4
1-1/3
2
3
P/N
248610301
248610200
248610300
248610500
248610700
248610800
248610900
5
7-1/2
10
15
248611000
248611300
248611200
248611500
Replacement
Dummy Fuse
Replacement Safety
Fuse Cover
Lists BF, LF, NF,
BC, LC, NC,
BA, LA, NA and KG
248872600
102774
Lists BG and NG
Table 2
GMT Fuses
248898700
Fuse Color
--
Violet
Red
Brown
White
Orange
Blue
Green
Black-White
Red-White
Red-Blue
---
--
Page 44 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
SAG582136600
Issue AU, February 21, 2014
Bullet Nose-Type Circuit Breakers
Features
♦ Each List BC, LC, and NC Distribution Unit holds up to four (4) bullet nose-type load distribution circuit breakers.
♦ Each List BA, LA, and NA Distribution Unit holds up to two (2) bullet nose-type battery disconnect circuit breakers and up to two (2) bullet nose-type load distribution circuit breakers.
Restrictions
See also the Restrictions for each Distribution Unit in the LIST DESCRIPTIONS section.
See also Load Distribution Wiring (Circuit Breakers) (Lists BC, LC, NC, BA, LA, and NA)
wiring restrictions.
Ordering Notes
1) Order circuit breakers per Table 3.
60
70
75
80
35
40
45
50
90
100
15
20
25
30
1
3
5
10
Ampere
Rating
P/N
Electrical Trip 1
(White Handle)
Electrical/
Mechanical Trip
(Black Handle)
2
102272
102273
102274
102275
102276
102277
102278
102279
102280
102281
121998
102282
102283
102284
102285
121996
101596
101597
101598
101599
101600
101601
101602
101603
101604
101605
121997
101606
101607
101608
101609
121995
138887
102286
138888
101610
See Table 6 for recommended wire sizes and lugs.
Circuit Breaker Alarm Operation:
2
Provides an alarm during an electrical trip condition only.
Provides an alarm during an electrical or manual trip condition.
Note that Electrical Trip only circuit breakers are not typically used for battery disconnect circuit breakers.
Table 3
Bullet Nose-Type Circuit Breakers
Page 45 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
Optional Bullet Nose 6-Position GMT Fuse Module, P/N 545332
Features
♦ Factory installed in a List BC, LC, NC, BA, LA, and NA Distribution Unit.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB
)
♦ Provides six (6) 0A to 15A GMT fuse load distribution positions.
♦ Screw clamp type load and load return terminals provided.
♦ Includes six (6) dummy fuses equipped with safety fuse covers.
Restrictions
For use with Lists BC, LC, NC, BA, LA, and NA.
Terminal block wire size capacity: 24 to 14 AWG.
Requires two (2) bullet device mounting positions.
Fuse Module has a 30A @ +40°C (+104°F) and +65°C (+149°F) maximum capacity. Maximum GMT fuse size is 15A. Fuses are to be loaded from bottom to top with highest value in the lowest position.
Caution: A fuse with a rating greater than 10 amperes SHALL HAVE an empty mounting position between it and any other overcurrent protective device.
See also the
Restrictions under “ GMT Load Distribution Fuses ” in the ACCESSORY DESCRIPTIONS
section.
Factory installed only.
Ordering Notes
1) Order optional Bullet Nose-Type 6-Position GMT Fuse Module (P/N 545332) as required.
2) Order GMT fuses as required per Table 2.
Optional Bulk Output Busbar, P/N 535015
Features
♦ Each Bulk Output Busbar installs in a single circuit breaker position in a List BC, LC, NC, BA, LA, and NA Distribution Unit.
Restrictions
For use with Lists BC, LC, NC, BA, LA, and NA.
Ordering Notes
1) Order by P/N 535015 as required.
Page 46 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
SAG582136600
Issue AU, February 21, 2014
AC Input Cables and Line Cords
AC Input Cable Assembly, P/N 535232
Features
♦ Provides one (1) 30” long, 8 AWG, AC Input Cable Assembly;
♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf,
♦ and the remaining end un-terminated.
Restrictions
Rated for 30A.
For use with List 1, 2, 5, and 6.
Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord.
Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords.
Ordering Notes
1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 and 2 ordered.
2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 and 6 ordered.
AC Input Line Cord, 208/240VAC, P/N 540946
Features
♦ Provides one (1) 14’ long, 8 AWG, AC Input Line Cord;
♦ terminated on one end with a Molex plug which mates with AC input receptacle on the
Power/Distribution Shelf,
♦ and on the remaining end with a NEMA L6-30P twist-lock plug.
Restrictions
For 208/240 VAC only (rated for 30A at 208/240VAC).
For use with List 1, 2, 5, and 6.
Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord.
Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords.
Ordering Notes
1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 and 2 ordered.
2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 and 6 ordered.
Page 47 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
AC Input Line Cord, 208/240VAC, P/N 545616
Features
♦ Provides one (1) 6’ long, 8 AWG, AC Input Line Cord;
♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf,
System Application Guide
Spec. No. 582136600 (Model 211 NGFB
)
♦ and on the remaining end with a NEMA L6-30P twist-lock plug.
Restrictions
For 208/240 VAC only (rated for 30A at 208/240VAC).
For use with List 1, 2, 5, and 6.
Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord.
Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords.
Ordering Notes
1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 and 2 ordered.
2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 and 6 ordered.
AC Input Line Cord, 120VAC, P/N 545252
Features
♦ Provides one (1) 14’ long, 8 AWG, AC Input Line Cord;
♦ terminated on one end with a Molex plug which mates with AC input receptacle on the
Power/Distribution Shelf,
♦ and on the remaining end with a NEMA L5-30P twist-lock plug.
Restrictions
For 120 VAC only (rated for 30A at 120VAC).
For use with List 1, 2, 5, and 6.
Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord.
Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords.
Ordering Notes
1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 and 2 ordered.
2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 and 6 ordered.
Page 48 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
SAG582136600
Issue AU, February 21, 2014
AC Input Line Cord, 120VAC, P/N 545478
Features
♦ Provides one (1) 14’ long, 14/3 AWG, AC Input Line Cord;
♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf,
♦ and on the remaining end with a NEMA 5-15P plug.
Restrictions
For 120 VAC only (rated for 15A at 120VAC).
For use with List 1 and 5 equipped with R48-500 Rectifier Modules.
Each List 1 requires one (1) AC Input Cable Assembly/Line Cord.
Each List 5 requires two (2) AC Input Cable Assemblies/Line Cords.
Ordering Notes
1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 ordered.
2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 ordered.
AC Input Line Cord, 120VAC, P/N 545479
Features
♦ Provides one (1) 14’ long, 14/3 AWG, AC Input Line Cord;
♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf,
♦ and on the remaining end with a NEMA L5-15P twist-lock plug.
Restrictions
For 120 VAC only (rated for 15A at 120VAC).
For use with List 1 and 5 equipped with R48-500 Rectifier Modules.
Each List 1 requires one (1) AC Input Cable Assembly/Line Cord.
Each List 5 requires two (2) AC Input Cable Assemblies/Line Cords.
Ordering Notes
1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 ordered.
2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 ordered.
Page 49 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
AC Input Line Cord, 208/240VAC, P/N 545480
Features
♦ Provides one (1) 14’ long, 14/3 AWG, AC Input Line Cord;
System Application Guide
Spec. No. 582136600 (Model 211
♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf,
NGFB
)
♦ and on the remaining end with a NEMA L6-15P twist-lock plug.
Restrictions
For 240 VAC only (rated for 15A at 208/240VAC).
For use with List 1 and 5.
For use with List 2 and 6 with R48-500 Rectifiers.
Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord.
Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords.
Ordering Notes
1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 ordered.
2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 ordered.
AC Input Line Cord, 120VAC, P/N 545481
Features
♦ Provides one (1) 14’ long, 12/3 AWG, AC Input Line Cord;
♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf,
♦ and on the remaining end with a NEMA L5-20P twist-lock plug.
Restrictions
For 120 VAC only (rated for 20A at 120VAC).
For use with List 1 and 5.
For use with List 2 and 6 with R48-500 Rectifiers.
Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord.
Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords.
Ordering Notes
1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 ordered.
2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 ordered.
Page 50 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
SAG582136600
Issue AU, February 21, 2014
AC Input Line Cord, 208/240VAC, P/N 545553
Features
♦ Provides one (1) 14’ long, 12/3 AWG, AC Input Line Cord;
♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf,
♦ and on the remaining end with a NEMA L6-20P twist-lock plug.
Restrictions
For 240 VAC only (rated for 20A at 208/240VAC).
For use with List 1, 2, 5, and 6.
Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord.
Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords.
Ordering Notes
1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 and 2 ordered.
2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 and 6 ordered.
AC Input Line Cord, 120VAC, P/N 547525
Features
♦ Provides one (1) 14’ long, 12/3 AWG, AC Input Line Cord;
♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf,
♦ and on the remaining end with a NEMA L5-30P twist-lock plug.
Restrictions
For 120 VAC only (rated for 30A at 120VAC).
For use with List 1, 2, 5, and 6.
Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord.
Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords.
Ordering Notes
1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 and 2 ordered.
2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 and 6 ordered.
Page 51 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
AC Input Line Cord, 120VAC, P/N 548457
Features
♦ Provides one (1) 6’ long, 14/3 AWG, AC Input Line Cord;
♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf,
System Application Guide
Spec. No. 582136600 (Model 211 NGFB
)
♦ and on the remaining end with a NEMA 5-15P plug.
Restrictions
For 120 VAC only (rated for 15A at 120VAC).
For use with List 1 and 5 with R48-500 Rectifiers.
Each List 1 requires one (1) AC Input Cable Assembly/Line Cord.
Each List 5 requires two (2) AC Input Cable Assemblies/Line Cords.
Ordering Notes
1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 ordered.
2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 ordered.
AC Input Line Cord, 120/208/240VAC, P/N 548196
Features
♦ Provides one (1) 6’ long, 12/3 AWG, AC Input Line Cord;
♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf,
♦ and on the remaining end with an IEC320 C20 plug.
Restrictions
For 120/208/240 VAC (rated for 20A at 120/208/240VAC).
For 208/240V use with List 1, 2, 5, and 6 and all Rectifier Modules.
For 120V use with List 1 and 5 and all Rectifier Modules.
For 120V use with List 2 and 6 with 500W Rectifier Module only.
Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord.
Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords.
Per UL 60950-1, 2nd Edition, when this cord is used with this power system, the following restrictions apply:
• The power system must be used “in a location having equipotential bonding (such as a telecommunications centre, a dedicated computer room or a restricted access location).
• “The building installation shall provide a means for connection to protective earth; and
• “The equipment is to be connected to that means; and
• “A service person shall check whether or not the socket-outlet from which the equipment is to be powered provides a connection to the building protective earth. If not, the service person shall arrange for the installation of a protective earthing conductor from the separated protective earthing terminal to the protective earth wire in the building.”
Ordering Notes
1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 and 2 ordered.
2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 and 6 ordered.
Page 52 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
SAG582136600
Issue AU, February 21, 2014
Special Application Digital Input Cable Kit, P/N 554935
Features
♦ Provides an alarm cable kit to add -48VDC to digital input #2.
♦ The kit consists of two pieces that plug together to make a complete connection. One part is pre-wired to the shelf and the other part is shipped loose.
Restrictions
For use with List 1 and 2.
Ordering Notes
1) Order one (1) Special Application Digital Input Cable Kit as required for each List 1 and 2 ordered.
AP6C57EA/EB Ring & Distribution Module
Features
♦
When used with List 6 , this module is designed to
supply a filtered and regulated –48 VDC source and a continuous 20 Hz ringing supply source to imbedded subscriber loop carrier telecommunication systems
(such as SLC-96 or SLC Series-5) requiring up to 45
A of load capacity.
♦ Designed to mount in a 23” relay rack, the module is one rack unit high, with 5” front projection.
♦ Includes two (2) 50VA ringers with automatic transfer capability (N+1 redundancy).
♦ Provides 35 DC distribution fuse positions, configured in five groups of seven, feeding five channel banks.
Includes 35 dummy fuses.
♦ Connectorized cables are available for SLC-96 or SLC Series-5 applications. Required DC distribution fuses are included with each cable assembly ordered.
♦ An Order Wire Option provides a connection interface for an analog communication link over a metallic pair, with surge protection.
♦ See Ring & Distribution Module Installation and User Manuals (IM6C57E and UM6C57E) for complete specifications.
Restrictions
Cannot be used with Distribution units List BF, LF, or NF.
Ordering Notes
1) For a Ring & Distribution Module equipped with two (2) 50VA ringers only, order AP6C57EA (A7000626).
2) For a Ring & Distribution Module equipped with two (2) 50VA ringers and the Order Wire option, order
AP6C57EB (A7000796).
3) Order distribution cable assemblies as required, from the following table. Order up to five (5) cable assemblies (one per channel bank). Required fuses are included with each cable assembly. Cable assemblies can be mixed.
Page 53 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
System Application Guide
Spec. No. 582136600 (Model 211
ORDERING CODE DESCRIPTION
P7000858
P7001139
P7000859
Cable assy for one SLC96 channel bank (8 ft.)
Cable assy for one SLC96 channel bank (20 ft.)
Cable assy for one SLC5 channel bank (8 ft.)
P7001136
P7000937*
Cable assy for one SLC5 channel bank (20 ft.)
Cable assy for one channel bank, generic applications (8 ft.)
*Note: Each channel bank position on the panel has a maximum capacity of 11A.
NGFB
)
4) Order Part No. 547491 DC power cable kit, as required. Provides two (2) 9” long cables to connect between a power shelf and the DC input terminals of one (1) Ring & Distribution Module.
5) For SLC-96 or SLC Series-5 applications, order battery cable kits as required, from the following table.
ORDERING
CODE
DESCRIPTION
547646
547647
Battery cable kit for SLC96 legacy power shelf (Tyco Mate-N-Lock connectors) - for 2 battery strings, Up to 3 cable kits can be installed in the power shelf with Distribution units BC, LC, and NC. Two cable kits can be installed in DU Lists BA, LA, and NA. (Use a flat washer, not provided.)
Battery cable for SLC5 legacy power shelf (Tyco Mate-N-Lock connectors) - for
2 battery strings, Up to 3 cable kits can be installed in the power shelf with Distribution units BC, LC, and NC. Two cable kits can be installed in DU Lists BA, LA, and NA. (Use a flat washer, not provided.)
6) Spare parts for the AP6C57EA/EB Ring & Distribution Module can be ordered as required from the following table.
ORDERING CODE DESCRIPTION
A0885525
A0885530
A0885531
1.33A Alarm SAN-O Fuse
3A Alarm SAN-O Fuse
5A Alarm SAN-O Fuse
A0885532 10A Alarm SAN-O Fuse
A7000627 (AP8C55AA) 50VA Ring Generator
Page 54 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
SAG582136600
Issue AU, February 21, 2014
External Battery Disconnect Unit, P/N 535282
Features
♦ Battery Disconnect Unit with mounting tabs.
♦ Two 1/4-20 studs w/hardware provided for installation of single hole battery lugs.
♦ One (10’ long) alarm lead provided.
Restrictions
Circuit breakers are ordered separately.
Maximum number of Battery Disconnect Units per system is three (3).
Ordering Notes
1) Order by P/N 535282 as required.
2) Order a circuit breaker for each Battery Disconnect Unit from Table 4.
3) Also order the following lug kits for each battery disconnect circuit breaker ordered: 545581(for use with 8 AWG wire and List 71), 540989
(for use with 10 AWG wire and List 72) or 555069 (for use with 6 AWG wire and List 73) and 541031 (wire with lugs for connection from battery disconnect to battery string).
4) Also order P/N 524384 Jumper/Alarm Lead if more than one (1) Battery
Disconnect Units are to be used (daisy-chains the alarm terminal of up to three [3] Battery Disconnect Units). (Section of alarm lead between
Battery Disconnect Units is 30”, section of alarm lead between Battery
Disconnect Unit and system’s alarm terminal is 84”.)
Yellow Jumper/Alarm Lead (P/N 524384)
(for use when more than one Battery
Disconnect Units are ordered)
Ampere
Rating
P/N
Electrical/Mechanical
Trip 1
(Black Handle)
Ampere
Rating
P/N
Electrical/Mechanical
Trip 1
(Black Handle)
1
3
5
10
256690300
256690700
256691100
256691500
35
40
50
60
15
20
25
30
256691900
256692300
256692700
256693100
70
75
100
Circuit Breaker Alarm Operation:
Provides an alarm during an electrical or manual trip condition.
Table 4
Battery Disconnect Unit Circuit Breakers
256693500
256693900
256694300
256694700
256695100
256695500
256695900
Page 55 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
NetSure™ 211
BC
Battery Cabinet (Spec. No. 541434)
Features
♦ The NetSure™ 211 BC Battery Cabinet is rated at
30 amperes, and can be mounted in a 19” or 23” nominal relay rack, or mounted to a suitable wall.
♦ The Battery Cabinet contains one (1) 40 ampere battery disconnect circuit breaker.
♦ Battery circuit breaker alarm leads are provided to tie into the power system’s alarm circuit.
♦ The Battery Cabinet is equipped with a battery cable terminated in an Anderson connector.
♦ Cables to connect the batteries (as specified in the table under Order Notes) into the Battery
Cabinet provided.
♦ Battery Cabinets can be paralleled to provide greater reserve time. Battery cabinets contain a second Anderson battery connector for plugging one cabinet into another.
Ordering Notes
1) Order by Spec. No. 541434 as required.
2) Also order four (4) batteries per Battery Cabinet per the following table.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
Battery
Manufacturer
Hawker
Fiamm
EaglePicher
EaglePicher
Enersys
* 10Hr rate
Manufacturer
P/N
SBS 15
12SLA12
HE-12V7.7FR
HE-12V12.7FR
NP18-12FR
Emerson
P/N
139091
139092
139094
139093
139774
Capacity Amp-Hours
(8Hr rate)
14
12
6.9
11.6*
16 *
Weight (lb) per Battery
12.50
12.35
5.94
9.68
13.60
3) When ordering 139774 batteries, also order 545427 Battery Connection kit.
4) When wall mounted, also order a battery cabinet frame grounding landing point adapter P/N 556872.
This adapter installs in the relay rack mounting bracket holes located on either side of the cabinet.
Frame Grounding Point
(1/4-20 Studs on 5/8” Centers)
Frame Ground Landing
Point Adapter P/N 556872
Attach Frame Ground Landing
Point Adapter to Cabinet
Page 56 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
SAG582136600
Issue AU, February 21, 2014
NetSure™ 211
BC
Battery Cabinet (Spec. No. 545534)
Features
♦ The NetSure™ 211 BC Battery Cabinet is rated at 30 amperes, and can be mounted in a 19” or 23” nominal relay rack, or mounted to a suitable wall.
♦ The Battery Cabinet contains one (1) 40 ampere battery disconnect circuit breaker.
♦ Battery circuit breaker alarm leads are provided to tie into the power system’s alarm circuit.
♦ The Battery Cabinet is equipped with a battery cable terminated in an Anderson connector.
♦ Cables to connect the batteries (as specified in the table under Ordering Notes) into the Battery Cabinet provided.
♦ Battery Cabinets can be paralleled to provide greater reserve time. Battery cabinets contain a second
Anderson battery connector for plugging one cabinet into another.
Ordering Notes
1) Order by Spec. No. 545534 as required.
2) Also order four (4) batteries per Battery Cabinet per the following table.
Battery
Manufacturer
Enersys
C&D / Dynasty
Manufacturer
P/N
SBS B10
TEL12-30
Emerson P/N Capacity Amp-Hours
(8Hr rate)
140553
140455
38
30.5
Weight (lb) per Battery
28.20
26.70
3) When wall mounted, also order a battery cabinet frame grounding landing point adapter P/N 556872.
This adapter installs in the relay rack mounting bracket holes located on either side of the cabinet.
Frame Grounding Point
(1/4-20 Studs on 5/8” Cente
rs)
Frame Ground Landing
Point Adapter P/N 556872
Attach Frame Ground Landing
Point Adapter to Cabinet
Page 57 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
NetSure™ 211
BC
Battery Cabinet (Spec. No. 545506)
Features
♦ The NetSure™ 211 BC Battery Cabinet is rated at 30 amperes, and can be mounted in a 23” nominal relay rack, or mounted to a suitable wall.
♦ The Battery Cabinet contains one (1) 40 ampere battery disconnect circuit breaker.
♦ Battery circuit breaker alarm leads are provided to tie into the power system’s alarm circuit.
♦ The Battery Cabinet is equipped with a battery cable terminated in an Anderson connector.
♦ Cables to connect the batteries (as specified in the table under Ordering Notes) into the Battery Cabinet provided.
♦ Battery Cabinets can be paralleled to provide greater reserve time. Battery cabinets contain a second
Anderson battery connector for plugging one cabinet into another.
Ordering Notes
1) Order by Spec. No. 545506 as required.
2) Also order four (4) batteries per Battery Cabinet per the following table.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
Battery
Manufacturer
Enersys
Enersys
C&D/ Dynasty
C&D/ Dynasty
Manufacturer
P/N
SBS B10
SBS 40
TEL12-30
TEL12-45
Emerson P/N Capacity Amp-Hours
(8Hr rate)
140553
140581
140455
140454
38
38
30.5
46
Weight (lb) per Battery
28.20
28.00
26.70
26.70
3) When wall mounted, also order a battery cabinet frame grounding landing point adapter P/N 556872.
This adapter installs in the relay rack mounting bracket holes located on either side of the cabinet.
Frame Grounding Point
(1/4-20 Studs on 5/8” Centers)
Frame Ground Landing
Point Adapter P/N 55687
2
Attach Frame Ground Landing
Point Adapter to Cabinet
Page 58 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
SAG582136600
Issue AU, February 21, 2014
NetSure™ 211
BC
Battery Cabinet (Spec. No. 554631)
Features
♦ The NetSure™ 211 BC Battery Cabinet is rated at 30 amperes, and can be mounted in a 19” or 23” nominal relay rack, or mounted to a suitable wall.
♦ The Battery Cabinet contains one (1) 40 ampere battery disconnect circuit breaker.
♦ Battery circuit breaker alarm leads are provided to tie into the power system’s alarm circuit.
♦ The Battery Cabinet is equipped with a battery cable terminated in an Anderson connector.
♦ Cables to connect the batteries (as specified in the table under Ordering Notes) into the Battery Cabinet provided.
♦ Battery Cabinets can be paralleled to provide greater reserve time. Battery cabinets contain a second Anderson battery connector for plugging one cabinet into another.
Ordering Notes
1) Order by Spec. No. 554631 as required.
2) Also order four (4) batteries per Battery Cabinet per the following table.
Battery
Manufacturer
GNB
Manufacturer
P/N
M12V40F
Emerson P/N Capacity Amp-Hours
(8Hr rate)
241173815 40
Weight (lb) per Battery
39.00
Note: When wall mounted, a battery cabinet frame grounding landing point adapter, P/N 556872, is provided. This adapter installs in the relay rack mounting bracket holes located on either side of the cabinet.
Frame Grounding Point
(1/4-20 Studs on 5/8” Centers)
Frame Ground Landing
Point Adapter P/N 556872
Attach Frame Ground Landing
Point Adapter to Cabinet
Page 59 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
♦ For interface with SM AC, SM BAT, SM BRC, or SM IO modules.
Restrictions
One (1) RS-485 connector is available in the system.
Ordering Notes
1) Order P/N 547674 as required.
PCU Blank Filler Panel, P/N PSK4820R-1
Features
♦ Provides 1x2U blank filler panel for rectifier module.
Ordering Notes
1) Order P/N PSK4820R-1 as required.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
SM TEMP Temperature Concentrator (P/N 547490)
Features
♦ Allows for multiple temperature probes to be used for temperature compensation. Compensation can be based on highest probe temperature or average probe temperature.
♦ Provides (8) temperature probe inputs per SM TEMP.
♦ Can be cascaded up to (8) SM TEMP modules, connecting up to
64 temperature probes.
♦ Provides analog output for all controllers.
Restrictions
Concentrator needs to plug into analog temp input on IB2 board.
Ordering Notes
1) Order P/N 547490.
2) Order up to (8) 3-meter (P/N 547749) or 10-meter (P/N 547750) temperature probes for each concentrator.
SM Module RS-485 Interface Cable P/N 547674
Features
♦ Provides 4’ cable for connecting SM supervisory modules to the system RS-485 interface connector.
Page 60 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
SAG582136600
Issue AU, February 21, 2014
Home
Anderson Battery Connector
Features
♦ Includes the components necessary to assemble an Anderson connector onto a battery cable.
Restrictions
Appropriate battery post mating lugs must be ordered separately.
Ordering Notes
Order Anderson connector housings and lugs per the following table.
Description
Emerson
P/N
For a single string (spare for List 71).
Consists of two (2) lugs (Anderson P/N 5952) and one (1) Red
Connector (Anderson P/N 992G1). Lugs accept 8 AWG wire.
Allows for the connection of one (1) battery string (both polarities)
(one wire per lug).
For a single string (spare for List 73).
Consists of two (2) lugs (Anderson P/N 5900) and one (1) Red
Connector (Anderson P/N 992G1). Lugs accept 6 AWG wire.
Allows for the connection of one (1) battery string (both polarities)
(one wire per lug).
For a double string (spare for List 72).
Consists of two (2) lugs (Anderson P/N 5900) and one (1) Red
Connector (Anderson P/N 992G1). Lugs accept 6 AWG wires.
Allows for the connection of two (2) battery strings (both polarities)
(two [10 AWG] wires per lug).
Individual Housing and Lugs Part Numbers
(spare for List 1, 2, 71, and 73)
(not available in kit form, order components individually per the second half of this table)
133196
Housing
Single Part Number for a Housing and Lugs
Description
Lug (accepts 8 AWG wire) (2 required per housing)
Lug (accepts 6 AWG wire) (2 required per housing)
Emerson
P/N
138922
247109602
111691
Anderson
P/N
(not available in kit form, order components individually per the second half of this table)
6331G1
Anderson
P/N
992G1
5952
5900
Page 61 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
Digital Input and Relay Output Cables
Features
♦ Lists 1 and 2: Two sets of customer wiring cables are available. One set is for Digital Inputs and Relay outputs. The other set is for an additional -48V digital input. One half of the Digital Inputs and Relay
Outputs cable is provided and factory connected in the shelf. The other half (includes mating connector on one end and un-terminated on the other end) must be ordered separately. The additional -48V digital input cable must be ordered separately. When ordered, one half of the -48V digital input cable is factory connected in the shelf. The other half has a mating connector on one end and is un-terminated on the other end.
♦ Lists 5 and 6: Two sets of customer wiring cables are available. One set is for the Digital Inputs and another set, for the Relay Outputs. One half of the Relay Outputs Cable is provided and factory connected in the shelf. The other half (includes mating connector on one end and un-terminated on the other end) must be ordered separately. Both halves of the Digital Inputs Cable must be ordered separately. When ordered, one half of the Digital Inputs Cable is factory connected in the shelf. The other half has a mating connector on one end and is un-terminated on the other end.
Ordering Notes
1) Lists 1 and 2: For the Digital Inputs and Relay Outputs Cable, P/N 545494 (2 ft.) is provided and factory connected in the List 1 and 2 shelves. The mating cable, P/N 545495 (10 ft.) must be ordered separately.
For additional -48V Digital Input Cable Kit, order P/N 554935.
2) Lists 5 and 6: For the Relay Outputs Cable, P/N 541308 (3 ft.) is provided and factory connected in the
List 5 and 6 shelves. A mating cable, P/N 541309 (10 ft.) or P/N 545644 (50 ft.), must be ordered separately.
For the Digital Inputs Cable, order P/N 541310 (shelf side, 3 ft.) and P/N 541311 (customer side, 10 ft.).
Note: A custom digital input cable and internal wiring kit is available, P/N 545594. This kit is factory installed only.
Page 62 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
SAG582136600
Issue AU, February 21, 2014
Replacement Modules
Ordering Notes
1) Refer to Table 5.
Item
500W Rectifier Module
1000W Rectifier Module
Rectifier Module Fan
SCU+ Controller Module
ACU+ Controller Module
Temperature Probe
Part Number
1R48500
1R481000
32010093
1M521BNA*
* Also specify the appropriate SCU+ configuration file. Refer to the configuration file label on your existing SCU+ Controller.
1M820BNA*
* Also specify the appropriate ACU+ configuration file. Refer to the configuration file label on your existing ACU+ Controller.
Order per List 90 (9 ft. long) or List 91 (30 Ft. long)
(or if only one piece of the two piece probe is needed, see the List 90 or 91 description for part numbers)
Table 5
Replacement Module Part Numbers
Page 63 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
Wiring Notes
Refer also to the next section, Wiring Illustrations .
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
Shelf Frame Grounding Stud
Features
♦ An M5 frame grounding stud with hardware is provided on the rear of the shelf.
Restrictions
Recommended frame ground wire size is 6 AWG.
AC Input Branch Circuit Protection and Wiring
Features
♦ Each shelf contains one (1) or two (2) side mounted plug-in AC input connector(s).
♦ AC Input Cable Assemblies/Line Cords are available that plug into the shelf’s AC input connector.
Restrictions
Lists 1 and 2 require one (1) AC input branch circuit.
The AC input branch circuit feeds two (2) (List 1) or three (3) (List 2) rectifiers.
Refer to the following table for recommended branch circuit protection.
Lists 5 and 6 require two (2) AC input branch circuits.
Each AC input branch circuit feeds two (2) (List 5) or three (3) (List 6) rectifiers.
Refer to the following table for recommended branch circuit protection.
System
AC Input Branch Circuit Protection*
208/240VAC Input 120VAC Input
500W Rect. 1000W Rect. 500W Rect. 1000W Rect.
58213660001
58213660005
(2-Rectifiers per AC Feed)
15A 15A
58213660002
58213660006
(3-Rectifiers per AC Feed)
15A 20A
* Protective devices should be of the time-delay or high inrush type.
15A
20A
20A
25A / 30A
For correct AC input wire size, use the appropriate AC Input Cable Assembly/Line Cord for each AC input branch circuit. Refer to AC Input Cables and Line Cords in the ACCESSORY DESCRIPTIONS section of this document.
External Alarm and Monitoring Wiring
Features
♦ List 5 and 6: Relay output and digital input leads are connected to screw-type terminal blocks located on the Customer Interface Board mounted inside the shelf. One half of a Relay Outputs Cable is factory connected to these terminals. The other half (includes mating connector on one end and un-terminated on the other end) is ordered separately. If ordered, one half of a Digital Input Cable is factory connected to these terminals. The other half includes a mating connector on one end and is un-terminated on the other end.
♦ List 1 and 2: Relay output and digital input leads are connected to screw-type terminals located on the
SCU+ Controller Module mounted inside the shelf. One half of a Digital Input/Relay Output Cable is
Page 64 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
SAG582136600
Issue AU, February 21, 2014 factory connected to these terminals. The other half (includes mating connector on one end and un-terminated on the other end) is ordered separately.
If an additional -48V Digital Input cable is ordered, one half of the cable is factory connected in the shelf.
The other half includes mating connector on one end and is un-terminated on the other end. The additional -48V digital input cable must be ordered separately.
Restrictions
Recommended Wire Size: 22 AWG for Loop Lengths Up to 200 ft.
18-20 AWG for Loop Lengths Over 200 ft.
Load Distribution Wiring (GMT Fuses) (Lists BG and NG only)
Features
♦ Load and load return leads are connected to a screw-type terminal block located on the front of the
Distribution Unit.
Restrictions
The rating of the distribution device determines the wire size requirements. Refer to the American National
Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code
(NEC) and applicable local codes.
Terminal block wire size capacity is 20 to 12 AWG.
Load Distribution Wiring (GMT Fuses) (Lists BF, LF, and NF only)
Features
♦ Load distribution (GMT fuses) and load return leads are connected to receptacles located inside the
Distribution Unit. Load leads are brought into the right side (as viewed from the front) of the shelf and are accessible from the front of the shelf. Note that the GMT distribution fuse block accepts two ranges of fuse amperage sizes, and that two different types of receptacles are provided.
Restrictions
The rating of the distribution device determines the wire size requirements. Refer to the American National
Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code
(NEC) and applicable local codes.
Ordering Notes
1) Lists 61 provides 12’ long, 16 AWG, load and load return leads that are terminated on one end with the appropriate mating connector* to plug into the system’s lower amperage rating GMT fuse connector, and are left un-terminated at the remaining end for connection into customer loads.
* Consists of housing Molex P/N 39-01-2025 and terminals P/N 44476-3112 [loose] or 44476-3111
[reel].
2) Lists 62 provides 12’ long, 14 AWG, load and load return leads that are terminated on one end with the appropriate mating connector* to plug into the system’s higher amperage rating GMT fuse connector, and are left un-terminated at the remaining end for connection into customer loads.
* Consists of housing Tyco P/N 350777-1 and terminals Tyco P/N 350551-3 [loose] or Tyco
350537-3 [reel].
Page 65 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
Load Distribution Wiring (GMT Fuses) (Lists BC, LC, NC, BA, LA, and NA)
Features
♦ Load distribution (GMT fuses) and load return leads are connected to receptacles located inside the
Distribution Unit. Load leads are brought into the right side (as viewed from the front) of the shelf and are accessible from the front of the shelf.
Restrictions
The rating of the distribution device determines the wire size requirements. Refer to the American National
Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code
(NEC) and applicable local codes.
Ordering Notes
1) List 60 provides 12’ long, 16 AWG, load and load return leads that are terminated on one end with the appropriate mating connector* to plug into the system’s GMT fuse connector, and are left un-terminated at the remaining end for connection into customer loads.
* Consists of housing Molex P/N 39-01-2025 and terminals P/N 44476-3112 [loose] or 44476-3111
[reel].
Load Distribution Wiring (Optional Bullet-Nose-Type 6-Position GMT Fuse Module)
Features
♦ Load and load return leads are connected to a screw-type terminal block located on the front of the Fuse
Module.
Restrictions
The rating of the distribution device determines the wire size requirements. Refer to the American National
Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code
(NEC) and applicable local codes.
Terminal block wire size capacity is 24 to 14 AWG.
Load Distribution Wiring (Circuit Breakers) (Lists BC, LC, NC, BA, LA, and NA)
Features
♦ Load distribution (circuit breakers) and load return leads terminated in two-hole lugs are connected to threaded studs located inside the Distribution Unit. Load leads are brought into the right side (as viewed from the front) of the shelf and are accessible from the front of the shelf.
Restrictions
The rating of the distribution device determines the wire size requirements. Refer to the American National
Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code
(NEC) and applicable local codes.
All lugs for customer connections must be ordered separately. Mounting hardware is factory supplied.
Maximum wire size is 6 AWG when all four (4) circuit breaker positions are used. 4 AWG or 2 AWG can be used, but the number of breaker positions will be reduced as follows;
• 4 AWG: 3 breakers max. (2 load/1 battery or 1 load/2 battery on lists BA, LA, and NA; 3 load on lists BC,
LC, and NC). Use 6 AWG for CO Ground.
• 2 AWG: 2 breakers max. (1 load/1 battery on lists BA, LA, and NA; 2 load on lists BC, LC, and NC). Use
6 AWG for CO Ground.
For 4 AWG and 2 AWG wire, install a customer supplied flat washer between the lug and the nut supplied on the termination.
Ordering Notes
1) The rating of the distribution device determines the wire size requirements. For wire size and lug selection, refer to Table 6.
2) For other available lugs, refer to drawings 031110100 through 031110300.
Page 66 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
SAG582136600
Issue AU, February 21, 2014
Circuit
Breaker
Amperag e
1, 3, 5,
10A
15A
20A
25A
30A
35A
40A
45A
50A
60A
70A
75A
80A
90A
14 AWG
37 (3, 4, 5)
24 (3, 4)
--
--
--
--
--
--
--
--
12 AWG
58 (3, 4, 5)
39 (3, 4, 5)
29 (3, 4)
--
--
--
--
--
--
--
10 AWG 8 AWG
Loop Length (feet)
6 AWG
(2)
93
62
46
Recm 90°C Wire Size
(3, 4, 5)
(3, 4, 5)
(3, 4, 5)
37 (3, 4,)
31 (3, 4)
--
--
--
--
--
148 (3, 4, 5)
99
74
59
49
(3, 4, 5)
(3, 4, 5)
(3, 4, 5)
(3, 4, 5)
42
37
33
(3, 4)
(3, 4)
(3, 4)
29 (3)
--
(1)
236 (3, 4, 5)
157
118
(3, 4, 5)
(3, 4, 5)
94
78
(3, 4, 5)
(3, 4, 5)
67
59
(3, 4, 5)
(3, 4, 5)
52
47
(3, 4)
(3, 4,)
39 (3, 4)
4 AWG
--
107 (3, 4)
94
83
(3, 4)
(3, 4)
75
62
53
50
(3, 4)
(3, 4)
(3, 4)
(3, 4)
47
--
--
--
--
(3, 4)
41 (3)
2 AWG
--
--
--
--
--
--
--
--
99
85
79
74
--
(3, 4)
(3, 4)
(3, 4)
(3, 4)
66
59
(3, 4)
(3, 4) 100A
2-hole
24539010
0
24539010
0
Recommended Crimp Lug (6)
24539010
0
24534660
0
24534650
0
--
24534680
0
24534690
0
1 Wire sizes are based on recommendations of the American National Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code (NEC). Table 310-16 for wire rated at 90°C conductor temperature operating in ambient temperatures of 40°C, 50°C, and
65°C was used. For other operating ambient temperatures, refer to the NEC. For operation in countries where the NEC is not recognized, follow applicable codes.
2 Recommended wire sizes are sufficient to restrict voltage drop to 1.0 volt or less at listed branch current for the loop lengths shown. Loop length is the sum of the lengths of the positive and negative leads.
3 Wire Size / Loop Length Combination Calculated using 40°C Ambient Operating Temperature.
4 Wire Size / Loop Length Combination Calculated using 50°C Ambient Operating Temperature.
5 Wire Size / Loop Length Combination Calculated using 65°C Ambient Operating Temperature.
6 Two-hole lugs are 10-32 bolt clearance on 5/8" centers. Refer to drawing 031110100 for lug crimping information.
Table 6
Recommended Battery and Load Distribution Wire Size and Lug Selection
(Bullet Nose-Type Circuit Breaker)
Page 67 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
Load Distribution Wiring (GMT Fuses) (List KG)
Features
System Application Guide
Spec. No. 582136600 (Model 211 NGFB
♦ Load distribution (GMT fuses) and load return leads are connected to terminal blocks located on the front of the assembly.
Restrictions
The rating of the distribution device determines the wire size requirements. Refer to the American National
Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code
(NEC) and applicable local codes.
Terminal block wire size capacity is 26 to 14 AWG.
)
CO Ground Wiring (Lists BF, LF, NF, BC, LC, NC, BA, LA, and NA)
Features
♦ Two 10-32 studs on 5/8” centers with hardware are provided on the Return Bus for CO Ground wiring.
Restrictions
Recommended CO ground wire size is 6 AWG.
Recommended lug is 245346500 (2-hole, 10-32 clearance holes, 5/8” centers).
Input Battery Wiring (List BG and NG)
Features
♦ Two (2) 8 AWG 48” long battery cables are factory connected inside the shelf. These cables are terminated at the customer end in a Red SB50 Anderson battery connector. A mating Anderson battery connector is provided [Housing: Emerson P/N 138922, Anderson Power Products P/N 992G1. Contacts
(two provided): Emerson P/N 247109602, Anderson Power Products P/N 5952].
♦ Additional strings of battery may be connected to the system using the available battery cable kits (see
List 71 and List 72).
Restrictions
Battery leads are NOT internally fused.
Input Battery Wiring (to Battery Disconnect Circuit Breakers) (Lists BA, LA, and NA)
Features
♦ Battery and battery return leads terminated in two-hole lugs are connected to threaded studs located inside the Distribution Unit. Battery leads are brought into the right side (as viewed from the front) of the shelf and are accessible from the front of the shelf.
Restrictions
The rating of the distribution device determines the wire size requirements. Refer to the American National
Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code
(NEC) and applicable local codes.
All lugs for customer connections must be ordered separately. Mounting hardware is factory supplied.
Maximum wire size is 6 AWG when all four (4) circuit breaker positions are used. 4 AWG or 2 AWG can be used, but the number of breaker positions will be reduced as follows;
• 4 AWG: 3 breakers max. (2 load/1 battery or 1 load/2 battery on lists BA, LA, and NA; 3 load on lists BC,
LC, and NC). Use 6 AWG for CO Ground.
• 2 AWG: 2 breakers max. (1 load/1 battery on lists BA, LA, and NA; 2 load on lists BC, LC, and NC). Use
6 AWG for CO Ground.
For 4 AWG and 2 AWG wire, install a customer supplied flat washer between the lug and the nut supplied on the termination.
Page 68 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
SAG582136600
Issue AU, February 21, 2014
Ordering Notes
1) The rating of the distribution device determines the wire size requirements. For wire size and lug selection, refer to Table 6.
2) For other available lugs, refer to drawings 031110100 through 031110300.
Input Battery Wiring (to Battery Busbars) (Lists BF, LF, NF, BC, LC, and NC)
Features
♦ Battery and battery return leads terminated in two-hole lugs are connected to threaded studs located inside the Distribution Unit. Battery leads are brought into the right side (as viewed from the front) of the shelf and are accessible from the front of the shelf.
Restrictions
All lugs for customer connections must be ordered separately. Mounting hardware is factory supplied.
Maximum size of wire to be connected to a single lug position is 2 AWG.
Maximum lug width, 0.61 inches.
Ordering Notes
1) Battery wire size varies depending on load, therefore no specific information is provided for wire size.
When making connections, observe correct polarity.
2) List 65 and List 66 provide 2 AWG “shelf side” and “battery side” (respectively) battery cables.
Page 69 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
Wiring Illustrations
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
Shelf Frame Grounding Stud (both 1U and 2U Panels, List 1 and 5 shown)
Page 70 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
AC Input Wiring (Lists 1 and 2)
List 1 and List 2 with Side AC Input Connectors
(List 1 shown)
SAG582136600
Issue AU, February 21, 2014
List 1 and List 2 with Rear AC Input Connectors
(List 2 shown)
Front
Rear
AC input connections are made using the supplied AC input cable assemblies/ line cords connected here.
* Rectifiers are numbered left to right as viewed from the front.
AC input connections are made using the supplied AC input cable assemblies/ line cords connected here.
Rear View
Front View
AC Input
Cable Assembly
AC Input
Line Cord
L2-N
Ground
Blue*
Green/Yellow*
White*
Green*
L1
Nominal 120/208/240V
AC Input for Rectifier Module:
List 1 (19” Shelf): #1 and #2
List 2 (23” Shelf): #1, #2, and # 3
Brown* Black*
* color of AC Input Cable
Assembly/Line Cord lead.
Nominal 120/208/240V
AC Input for Rectifier Module:
List 1 (19” Shelf): #1 and #2
List 2 (23” Shelf): #1, #2, and # 3
535232
540946
545252
545478
545479
545480
545481
545553
545616
547525
548457
548196
ENSURE THE PROPER VOLTAGE AC
BRANCH CIRCUIT AND LINE CORDS
WITH THE APPROPRIATE PLUG
ARE USED FOR YOUR APPLICATION.
* AC Input Cable Assembly / Line Cords
Part Number Customer End
500W Rectifier: 120/208/240 VAC Input
1000W Rectifier: 120/208/240 VAC Input unterminated (List 1 & 2)
L6-30P
L5-30P
5-15P
L5-15P
L6-15P
L5-20P
L6-20P
L6-30P
L5-30P
(List 1 & 2)
(List 1 & 2)
(List 1 w/ R48-500)
(List 1 w/ R48-500)
(List 1; List 2 w/ R48-500)
(List 1; List 2 w/ R48-500)
(List 1 & 2)
(List 1 & 2)
(List 1 & 2)
(List 1 w/ R48-500)
“WARNING - HIGH LEAKAGE CURRENT.”
An industrial style plug is required when providing power to three (3) or more Rectifier
Modules with a flexible cord. Plug and outlet types 1-15, 2-15, 2-20, 5-15, and 5-20 as specified in IEC 60083 are considered to be NON-INDUSTRIAL within the meaning of this standard.
5-15P
IEC320 C20 (List 1 120/208/240V & List 2 208/240 w/ R48-500 or R48-1000; List 2 120V w/ R48-500 only.)
Page 71 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
AC Input Wiring (Lists 5 and 6)
List 5
List 6
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
Front
4
3
AC input connections are made using the supplied AC input cable assemblies/ line cords connected here.
2
1
Rectifiers are numbered as shown above
Front View
Front
AC input connections are made using the supplied AC input cable assemblies/ line cords connected here.
6
5
4
2
3
1
Rectifiers are numbered as shown above
ENSURE THE PROPER VOLTAGE AC
BRANCH CIRCUIT AND LINE CORDS
WITH THE APPROPRIATE PLUG
ARE USED FOR YOUR APPLICATION.
500W Rectifier: 120/208/240 VAC Input
1000W Rectifier: 120/208/240 VAC Input
L2-N
Ground
L1
AC Input
Cable Assembly
AC Input
Line Cord
Blue* White*
Green/Yellow* Green*
Brown* Black*
* color of AC Input Cable
Assembly/Line Cord lead.
Nominal 120/208/240V
AC Input for Rectifier Module:
List 5 (19” Shelf): #1 and #2
List 6 (23” Shelf): #1, #2, and #5
Nominal 120/208/240V
AC Input for Rectifier Module:
List 5 (19” Shelf): #3 and #4
List 6 (23” Shelf): #3, #4, and #6
535232
540946
545252
545478
545479
545480
545481
545553
545616
547525
548457
548196
* AC Input Cable Assembly / Line Cords
Part Number Customer End unterminated (List 5 & 6)
L6-30P
L5-30P
5-15P
L5-15P
L6-15P
L5-20P
L6-20P
L6-30P
L5-30P
5-15P
(List 5 & 6)
(List 5 & 6)
(List 5 w/ R48-500)
(List 5 w/ R48-500)
(List 5; List 6 w/ R48-500)
(List 5; List 6 w/ R48-500)
(List 5 & 6)
(List 5 & 6)
(List 5 & 6)
(List 5 w/ R48-500)
“WARNING - HIGH LEAKAGE CURRENT.”
An industrial style plug is required when providing power to three (3) or more Rectifier
Modules with a flexible cord. Plug and outlet types 1-15, 2-15, 2-20, 5-15, and 5-20 as specified in IEC 60083 are considered to be NON-INDUSTRIAL within the meaning of this standard.
IEC320 C20 (List 5 120/208/240V & List 6 208/240 w/ R48-500 or R48-1000; List 6 120V w/ R48-500 only.)
Page 72 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
External Alarm and Monitoring Wiring (Lists 1 and 2)
SAG582136600
Issue AU, February 21, 2014
SCU+
Controller
Notes
Relay Output/Digital Input Cable P/N 545494 is factory connected to terminals. Mating half
(w/ unterminated ends) available, P/N 545495.
When an additional -48V Digital Input Cable Kit
P/N 554935 is ordered, one half of the kit is factory connected in the shelf. The other half has a mating connector on one end and is un-terminated on the other end.
(48/24V)
Digital Inputs
SCU+ Controller
(Top View)
Major
Summary
Alarm
Relay Outputs
Digital Input 1 is factory wired to
Load Breaker / Fuse Alarm.
Digital Input 2 default is External Battery
Disconnect Circuit Breaker Alarm.
A factory-connected jumper supplies +BAT (Battery Return) to the positive side of Digital
Input #2.
When ordered, Temperature Probe leads are factory connected to SCU+ Connector Board located in the Distribution Unit.
These are labeled T1 and T2.
Minor
Summary
Alarm
NC = Normally Closed
COM = Common
NO = Normally Open
All relay contacts are shown with the relay deenergized.
Page 73 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
System Application Guide
Spec. No. 582136600 (Model 211 NGFB
External Alarm and Monitoring Wiring (Lists 5 and 6)
Notes
Note: A custom digital input cable and internal wiring kit is available, P/N 545594. This kit is factory installed only.
)
Relay Output Cable P/N 541308 is factory connected to Relay Output terminals.
Mating half (w/ unterminated ends) available, P/N 541309.
If ordered, Digital Input Cable P/N 541310 is factory connected to Digital Input terminals.
Mating half (w/ unterminated ends) available, P/N 541311.
Digital Input 1 is factory wired to Load Breaker / Fuse Alarm.
Digital Input 2 is reserved for External Battery Breaker Alarm.
A factory connected jumper supplies +BAT (Battery Return) to the positive side of Digital Input 2.
Digital Inputs 3 through 7 are User defined.
Digital Input 8 is reserved for Emergency Stop.
Digital Input 9 is not available in this system.
When ordered, Temperature Probe leads are factory connected to J11 and J12. These are labeled 1 and 2.
NC = Normally Closed
COM = Common
NO = Normally Open
All relay conacts are shown with the relay deenergized.
IB2 Customer
Interface Board
Relay
No.
Relay
No.
J9
Relay Output Term. Blocks
J8 J7 J6
7
NO C NC
5
NO C NC
3
NO C NC
1*
NO C NC
5 3 1
NO C NC
5 3 1
NO C NC
5 3 1
NO C NC
5 3 1
NO C NC
6 4
8
2 6 4
6
2 6 4
4
2 6 4
2
2
Digital Input Term. Blocks
J5 J4 J3
8 7 6 5 4 3 2 1
5 3 1 5 3 1 5 3 1
6 4 2 6 4 2 6 4
8 7 6 5 4 3 2
2
1
Input
No. (
–
)
Input
No. (+)
J12
J11
RS-485 Connection for SM AC, SM BAT,
SM BRC, or SM IO
Supervisory Modules.
See module data sheets. (Functional with ACU+ only.)
Temp. Probe #2 or
SM TEMP Module
Temp. Probe #1 or
SM TEMP Module
J2
J1
SW1
Switch sections must be set to this position to interface with SCU+/ACU+ controller.
* The relay assigned by the Controller to be the”Major Summary” (SCU+) or “Critical Summary” (ACU+) alarm (relay 1 by default) will operate in the “Fail Safe Mode”. “Fail Safe Mode” means Relay 1 is de-energized during an alarm condition, opening the contacts between the C and NO terminals, and closing the contacts between the C and NC terminals.
The remaining seven (7) alarm relays energize during an alarm condition, closing the contacts between the C and NO terminals, and opening the contacts between the C and NC terminals.
Page 74 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
SAG582136600
Issue AU, February 21, 2014
Yellow Alarm Lead
(P/N 535294)
(factory wired to circuit breaker alarm terminal)
Alarm Wiring to a Single
External Battery Disconnect Unit
Procedure
1. Connect YELLOW lead exiting top of
Battery Disconnect Unit per table below.
Remove quick connect terminal first.
The YELLOW lead is factory connected to circuit breaker “C (Common)” alarm terminal in the Battery Disconnect Unit.
2. There is NO connection to the circuit breaker “NO (Normally Open)” alarm terminal.
3. Connect loose end of Jumper factory connected to bottom terminal on circuit breaker to circuit breaker
“NC (Normally Closed)” alarm terminal.
Torque to 84 in-lbs using supplied hardware
To
Power
System
To
Battery
EXTERNAL BATTERY
DISCONNECT UNIT
(Side cover removed in illustration to show wiring details.)
External Battery Disconnect Circuit Breaker Alarm Input:
A battery disconnect circuit breaker alarm is activated when the circuit breaker is in the OFF position, and provides -48VDC to Digital Input # 2.
Shelf List
1 or 2
5 or 6
Alarm Cable on shelf
545495
NO
YES
541311
NO
YES
Connect to shelf per table below.
Remove quick connect terminal first.
BREAKER ALARM CONNECTION
CONNECT YELLOW WIRE TO:
Must order Cable 545495
R-BK Lead of 545495. Splice and heat shrink tubing included with 545495
Pin 3 of J3 on customer interface BD (negative side of Digital Input # 2)
O-R Lead of 541311. Splice and heat shrink tubing included with 541311
Page 75 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
Yellow Jumper/Alarm
Lead (P/N 524384)
(Ordered separately and supplied loose.
Must be wired by the customer to each circuit breaker
“C (Common)” alarm terminal) see previous page
*
No terminal on 524384 jumper
Connect to shelf per table below.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
Yellow Alarm Lead
(P/N 535294)
(factory wired to circuit breaker alarm terminal)
REMOVE
COMPLETELY
FROM ALL BATTERY
DISCONNECT UNITS
AND DISCARD.
see previous page
1st EXTERNAL BATTERY
DISCONNECT UNIT
(Side cover removed in illustration to show wiring details.)
2nd EXTERNAL BATTERY
DISCONNECT UNIT see previous page
Alarm Wiring to (2) to (3)
External Battery Disconnect Units
3rd EXTERNAL BATTERY
DISCONNECT UNIT
Procedure
1. Completely remove YELLOW lead exiting top of
ALL Battery Disconnect Units and discard.
3. There is NO connection to the circuit breaker “NO (Normally Open)” alarm terminal.
2. Connect separately ordered YELLOW jumper/alarm lead (P/N 524384) to circuit breaker “C (Common)” alarm terminals in ALL Battery Disconnect Units.
Connect remaining end per table below.
4. In ALL Battery Disconnect Units, connect loose end of Jumper factory connected to bottom terminal on circuit breaker to circuit breaker
“NC (Normally Closed)” alarm terminal.
External Battery Disconnect Circuit Breaker Alarm Input:
A battery disconnect circuit breaker alarm is activated when the circuit breaker is in the OFF position, and provides -48VDC to Digital Input # 2.
Shelf List
1 or 2
5 or 6
Alarm Cable on shelf
545495
NO
YES
541311
NO
YES
BREAKER ALARM CONNECTION
CONNECT YELLOW WIRE TO:
Must order Cable 545495
R-BK Lead of 545495. Splice and heat shrink tubing included with 545495
Pin 3 of J3 on customer interface BD (negative side of Digital Input # 2)
O-R Lead of 541311. Splice and heat shrink tubing included with 541311
Page 76 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
Yellow Jumper/Alarm
Lead (P/N 524384)
(Ordered separately and supplied loose.
Must be wired by the customer to each circuit breaker
“C (Common)” alarm terminal)
*
No terminal on 524384 jumper
Connect to shelf per table below.
see previous page
SAG582136600
Issue AU, February 21, 2014
see previous page
1st BATTERY TRAY
BATTERY DISCONNECT
CIRCUIT BREAKER
(Side cover removed in illustration to show wiring details.) see previous page
2nd BATTERY TRAY
BATTERY DISCONNECT
CIRCUIT BREAKER
(if furnished)
Alarm Wiring to Battery Disconnect Circuit
Breakers when (1) to (3) Battery Trays are Used
Procedure
1. Connect kit-supplied YELLOW jumper/alarm lead
(P/N 524384) to circuit breaker “C (Common)” alarm terminals on ALL Battery Disconnect Circuit
Breakers. Connect remaining per table below.
2. There is NO connection to the circuit breaker “NO (Normally Open)” alarm terminal.
3rd BATTERY TRAY
BATTERY DISCONNECT
CIRCUIT BREAKER
(if furnished)
3. On ALL Battery Disconnect circuit breakers, there should be a factory connected Jumper connected from the bottom terminal on the circuit breaker to the circuit breaker “NC
(Normally Closed)” alarm terminal.
External Battery Disconnect Circuit Breaker Alarm Input:
A battery disconnect circuit breaker alarm is activated when the circuit breaker is in the OFF position, and provides -48VDC to Digital Input # 2.
Shelf List
1 or 2
5 or 6
Alarm Cable on shelf
545495
NO
YES
541311
NO
YES
BREAKER ALARM CONNECTION
CONNECT YELLOW WIRE TO:
Must order Cable 545495
R-BK Lead of 545495. Splice and heat shrink tubing included with 545495
Pin 3 of J3 on customer interface BD (negative side of Digital Input # 2)
O-R Lead of 541311. Splice and heat shrink tubing included with 541311
Page 77 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
Yellow Jumper/Alarm
Lead (P/O Cabinet)
Orange Wire on
541434 not used
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
Connect to shelf per table below.
alarm wire alarm wire
1st BATTERY CABINET
BATTERY DISCONNECT
CIRCUIT BREAKER alarm wire
2nd BATTERY CABINET
BATTERY DISCONNECT
CIRCUIT BREAKER
3rd BATTERY CABINET
BATTERY DISCONNECT
CIRCUIT BREAKER
Alarm Wiring to Battery Cabinets
Procedure
1. Remove quick connect terminal from YELLOW battery cabinet alarm lead.
2. Wire per table below.
External Battery Disconnect Circuit Breaker Alarm Input:
A battery disconnect circuit breaker alarm is activated when the circuit breaker is in the OFF position, and provides -48VDC to Digital Input # 2.
Shelf List
1 or 2
5 or 6
Alarm Cable on shelf
545495
NO
YES
541311
NO
YES
BREAKER ALARM CONNECTION
CONNECT YELLOW WIRE TO:
Must order Cable 545495
R-BK Lead of 545495. Splice and heat shrink tubing included with 545495
Pin 3 of J3 on customer interface BD (negative side of Digital Input # 2)
O-R Lead of 541311. Splice and heat shrink tubing included with 541311
Page 78 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
SAG582136600
Issue AU, February 21, 2014
Load Distribution Wiring (GMT Fuses) (Lists BG and NG installed in a List 1 or 2, List 1 shown)
Connect to Front Terminal Block
Load Return
Leads
-48V Distribution
Leads
Fuse
Position
8
9
10
5
6
7
1
2
3
4
Terminal
Load Return Load (-48V)
15
17
19
9
11
13
1
3
5
7
16
18
20
10
12
14
2
4
6
8
Page 79 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
System Application Guide
Spec. No. 582136600 (Model 211
Load Distribution Wiring (GMT Fuses) (Lists BF, LF, and NF installed in a List 5 or 6, List 5 shown)
NGFB
)
Front
Load Distribution
Leads Enter Here
GMT Fuse
Positions
(Max. 15A)
GMT Fuse Load
Distribution Leads
Connect Here
Mating Connectors and 12'
Leads provided with List 62.
-48V on Left (Black Lead),
Return on Right (White Lead)
GMT Fuse
Positions
(Max. 10A)
GMT Fuse Load
Distribution Leads
Connect Here
Mating Connectors and 12'
Leads provided with List 61.
-48V on Left (Black Lead),
Return on Right (White Lead)
Page 80 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
SAG582136600
Issue AU, February 21, 2014
Load Distribution Wiring (GMT Fuses) (Lists BC, LC, NC, BA, LA, and NA installed in a List 5 or 6,
List 5 shown)
Front
GMT Fuse
Positions
Load Distribution
Leads Enter Here
GMT Fuse Load
Distribution Leads
Connect Here
Mating Connectors and 12'
Leads provided with List 60.
-48V on Left (Black Lead),
Return on Right (White Lead); as viewed from side with door closed.
Page 81 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
Load Distribution Wiring (Optional Bullet Nose 6-Position GMT Fuse Module)
System Application Guide
Spec. No. 582136600 (Model 211 NGFB
)
-48V Distribution
Leads
Load Return
Leads
Page 82 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
SAG582136600
Issue AU, February 21, 2014
Load Distribution Wiring (Circuit Breakers) and CO Ground Wiring (Lists BC, LC, and NC installed in a List 5 or 6, List 5 shown)
Front
Load Distribution
Circuit Breakers
Circuit Breaker Load
Distribution and
CO Ground Leads
Enter Here
Front
Portion of shelf removed in illustration for clarity.
Leads are brought into side of shelf, and tools to secure lugs from front of shelf.
-48V Load
Distribution
Leads
Load Return Leads
CO Ground Lead
10-32 studs (w/ hardware) on 5/8" centers for installation of customer provided two hole lugs.
Page 83 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
Load Distribution Wiring (Circuit Breakers), Input Battery Wiring (Circuit Breakers), and CO Ground Wiring (Lists BA, LA, and NA installed in a List 5 or 6, List 5 shown)
Front
Load Distribution
Circuit Breakers
Battery Disconnect
Circuit Breakers
CO Ground, Circuit Breaker
Load Distribution, and Circuit
Breaker Battery Leads
Enter Here
Front
Portion of shelf removed in illustration for clarity.
Leads are brought into side of shelf, and tools to secure lugs from front of shelf.
OBSERVE PROPER
POLARITY WHEN
MAKING BATTERY
CONNECTIONS
-48V Load
Distribution
Leads
-48V Battery
Leads
Battery Return Leads
Load Return Leads
CO Ground Lead
10-32 studs (w/ hardware) on 5/8" centers for installation of customer provided two hole lugs.
Page 84 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
Load Distribution Wiring (GMT Fuses) (List KG)
SAG582136600
Issue AU, February 21, 2014
Inputs for Side “A” and Side “B” are strapped in this system.
Connections are made to screw compression terminal blocks.
Wire size range is 26 to 14 AWG.
Page 85 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
Input Battery Wiring (Lists BG and NG installed in a List 1 or 2, List 1 shown)
System Application Guide
Spec. No. 582136600 (Model 211 NGFB
)
Page 86 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
SAG582136600
Issue AU, February 21, 2014
Input Battery Wiring (Lists BF, LF, NF, BC, LC, and NC installed in a List 1 or 5, List 5 shown) and CO Ground Wiring (Lists BF, LF, and NF installed in a List 1 or 5, List 5 shown)
List NF Distribution
Unit shown. List BF,
LF, BC, LC, and NC similar.
Front
List 65 provides 3' long, 2 AWG, battery cables terminated on one end with lugs to connect to the input battery landings and on the other end with an Anderson connector.
List 66 provides 12' long, 2 AWG, battery cables terminated on one end in an Anderson connector and left unterminated at the remaining end for connection of battery lugs.
Battery: 1/4-20 studs (w/hardware) on 5/8" centers for installation of customer provided two hole lugs.
CO Ground: 10-32 studs (w/hardware) on 5/8" centers for installation of customer provided two hole lugs.
Distribution
Unit
List BC, LC, and NC
Distribution Unit
List BF, LF, and NF
Distribution Unit
Battery, Battery Return, and CO Ground Leads
Enter Here
CO Ground Lead
Right Side
Battery Return Leads -48 Battery Leads
CO Ground Lead
Right Side
Battery Return Leads -48 Battery Leads
OBSERVE PROPER
POLARITY WHEN
MAKING BATTERY
CONNECTIONS
Page 87 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
SPECIFICATIONS
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
Note: For all rectifier specifications, refer to the separate Rectifier User Manual (UM1R48500/UM1R481000) supplied with your Power System.
For all controller specifications, refer to the Controller User Manual (UM1M521B or UM1M820B) supplied with your Power System.
For factory settings of all configurable Controller parameters, refer to the Configuration Drawing (Cdrawing) supplied with your Power System.
1. SYSTEM
1.1 Environmental Ratings
1.1.1 Operating Ambient Temperature Range (Specification Compliant):
(A) -40°C (-40°F) to +65°C (+149°F) with derating output.
(B) -40°C (-40°F) to +40°C (+104°F) with full power performance.
1.1.2 Storage Ambient Temperature Range: -40°C (-40°F) to +75°C (+167°F).
1.1.3 Humidity: This Power System is capable of operating in an ambient relative humidity range of
0% to 90%, non-condensing.
1.1.4 Altitude: 2000 m (6560 ft) at full power (power limited for heights above 2000 m).
1.1.5 Mounting: This product is intended only for installation in a Restricted Access Location on or above a non-combustible surface.
This product must be located in a Controlled Environment with access to Craftspersons only.
This product is intended for installation in Network Telecommunication Facilities (CO, vault, hut, or other environmentally controlled electronic equipment enclosure).
This product is intended to be connected to the common bonding network in a Network
Telecommunication Facility (CO, vault, hut, or other environmentally controlled electronic equipment enclosure).
Typical industry standards recommend minimum aisle space clearance of 2'6" for the front of the relay rack and 2' for the rear of the relay rack.
Separate shelves are available for mounting in either a 19" or 23" wide relay rack (1” or 1-3/4” multiple drillings for the 2U shelf and 1-3/4" multiple drillings for the 1U shelf).
Mounting angles are positioned for a 5-inch front projection mounting only.
Flush mounting is done using optional kits.
1.1.6 Ventilation Requirements: Rectifier and mounting shelf ventilating openings must not be blocked and temperature of air entering rectifiers must not exceed rated Operating Ambient
Temperature Range stated above.
1.2 Compliance Information
1.2.1 Surge Protection: Refer to Paragraphs 2.3.6. and 3.3.6.
Note: This level of protection is a widely used standard for telecommunications power equipment. As with all such equipment, it is the end user's responsibility to provide an adequately sized Surge Suppression Device at the commercial power service entrance of the building that reduces all incoming surges to levels below the classes/categories stated for the equipment.
1.2.2 Safety Compliance:
(A) This unit meets the requirements of UL 60950, Standard for Information Technology
Equipment, and is UL Recognized as a power supply for use in Telephone, Electronic Data
Processing, or Information Processing Equipment.
(B) This unit meets the requirements of CAN/CSA 22.2, No. 60950-00 and is tested and
Certified by UL ("c UR") as a Component Type Power Supply.
Page 88 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
SAG582136600
Issue AU, February 21, 2014
1.2.3 EMC and Safety:
(A) Complies with the Low-Voltage Directive, 73/23/EEC. Complies with Emissions and Immunity requirements as specified in GR-1089-Core Issue 4.
EMC
EN 55022: 1998
CFR 47 – Part 15
GR-1089 Issue 4
Emissions
Conducted
Radiated
Test Level
Class B
Class B
GR-1089 Issue 4
Immunity
EN 61000-4-2 Electrostatic Discharge
EN 61000-4-4 Electric Fast Transients
Radiated Immunity
Conducted Immunity
Surge IEEE C62.41
SAFETY
8kV / 15kV
0.25kV / 0.5kV
8.5V/m
89dBuA
2kV / 6kV
EN 60950-1: 2001
Safety of Information Technology Equipment, including
Electrical Business Equipment
1.2.4 NEBS Compliance: Compliance verified by a Nationally Recognized Testing Laboratory
(NRTL) per GR-1089-CORE and GR-63-CORE. Contact Emerson Network Power for NEBS compliance reports.
For N ET S URE ™ 211 NGFB to remain compliant during a fan failure condition, the backup battery connection must be utilized to provide sufficient power to the loads for up to eight (8) hours when the system is operated at greater than 50% output power. If no backup battery connection is used, the system must operate with a redundant module installed.
1.3 Standard Features
1.3.1 AC Input Connections: AC input cable assemblies and line cords are available.
(A) List 1 and 2: Mounted to the side of the shelf is an AC input housing with one (1) plug-in connector for one (1) AC input feed.
(B) List 5 and 6: Mounted to the side of the shelf is an AC input housing with two (2) plug-in connectors for two (2) AC input feeds.
1.3.2 Battery Connections: Battery cables are available.
(A) List 1 and 2: Battery leads are connected to an Anderson connector exiting the rear of the unit.
(B) Lists 5 and 6: Battery and battery return leads terminated in two-hole lugs are connected to threaded studs located inside the Distribution Unit. Battery leads are brought into the right side (as viewed from the front) of the shelf.
1.3.3 Load Connections:
(A) List 1 and 2: Load and load return leads are connected to a screw-type terminal block located on the front of the shelf.
(B) Lists 5 and 6: Load distribution (circuit breakers, if furnished) and load return leads terminated in two-hole lugs are connected to threaded studs located inside the Distribution
Unit. Load leads are brought into the right side (as viewed from the front) of the shelf and are accessible from the front of the shelf.
Page 89 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
System Application Guide
Spec. No. 582136600 (Model 211 NGFB
Load distribution (GMT fuses) and load return leads are connected to receptacles located inside the Distribution Unit. Load leads are brought into the right side (as viewed from the front) of the shelf and are accessible from the front of the shelf.
)
1.3.4 Alarm and Monitoring Connections: Customer wiring cables are available.
(A) List 1 and 2: Relay output and digital input leads are connected to screw-type terminal blocks located on the SCU+ located inside the shelf. These leads enter the rear of the shelf.
(B) Lists 5 and 6: Relay output and digital input leads are connected to screw-type terminal blocks located on the Customer Interface Board located inside the shelf. These leads enter the right side (as viewed from the front) of the shelf and are accessible from the front of the shelf.
1.3.5 Dimensions and Weights: Refer to the PHYSICAL SIZE INFORMATION section of this document.
Page 90 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
PHYSICAL SIZE INFORMATION
Overall Dimensions – List 1
SAG582136600
Issue AU, February 21, 2014
Left Side View
Top View
17.3
18.3
19.0
Front View
Rear View
0.5
1.25
1.72
5
12
Right Side View
0.23
Bottom View
Notes:
1. All dimensions are in inches, unless otherwise specified.
2. Weight in LBS.
Net: 16
Shipping:
3. Finish: Front Panels are Gray
Shelf is Galvaneal.
Page 91 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
Additional Dimensions – List 1 with Wall Mounting Kit (P/N 541285)
Horizontal Wall Mounting
19.45
18.72
15.34
0.90
Top View
Rear View
Vertical Wall Mounting
Note: All dimensions are in inches.
1.15
18.38
19.87
Top View
2.65
Right Side
View
Page 92 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
SAG582136600
Issue AU, February 21, 2014
Additional Dimensions – List 1 with Optional 19” Rear Cover Kit, P/N 555260
0.6
Top View
16.9
18.3
19.0
Front View
Rear View
0.5
1.25
1.75
12.0
Right Side View
0.25
Page 93 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
Additional Dimensions – List 1 with Optional 3” Projection Mount Kit, P/N 556828
Rear View
Left Side
View
1.25
1.71
0.24
Top View
16.9
18.3
19.0
Front View
12
3
0.5
Right Side
View
Page 94 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
Overall Dimensions – List 2
SAG582136600
Issue AU, February 21, 2014
Page 95 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
Additional Dimensions – List 2 with Wall Mounting Kit (P/N 541285)
Horizontal Wall Mounting
23.41
22.69
15.34
0.90
Top View
Rear View
Vertical Wall Mounting
Note: All dimensions are in inches.
1.15
22.34
23.83
Top View
2.65
Right Side
View
Page 96 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
SAG582136600
Issue AU, February 21, 2014
Additional Dimensions – List 2 with Optional 23” Rear Cover Kit, P/N 555261
0.6
Top View
20.8
22.3
23.0
Front View
Rear View
0.5
1.25
1.75
12.0
Right Side View
0.25
Page 97 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
Overall Dimensions – List 5
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
Left Side View
Top View
17.3
18.3
19.0
19.4
Front View
Rear View
0.5
5
12
Right Side View
3.00
0.23
3.46
Bottom View
Notes:
1. All dimensions are in inches, unless otherwise specified.
2. Weight in LBS.
Net: 30
Shipping:
3. Finish: Front Panels are Gray
Shelf is Galvaneal.
Page 98 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
Overall Dimensions – List 6
SAG582136600
Issue AU, February 21, 2014
Page 99 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
Additional Dimensions – Lists 1, 2, 5 and 6 with Wall Mounting Kit (P/N 553203)
Lists 1 and 2
18.936 (19” Shelf, shown)
22.906 (23” Shelf)
20.543 (19”, shown Shelf)
24.513 (23” Shelf)
Bottom View
Lists 5 and 6
4.625
Right Side View
Note: All dimensions are in inches.
18.936 (19” Shelf, shown)
22.906 (23” Shelf)
20.543 (19” Shelf, shown)
24.513 (23” Shelf)
Bottom View
4.625
Right Side View
Page 100 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
Overall Dimensions – List KG
Notes:
1. Dimensions in inches unless otherwise specified.
2. Finish: Gray
3. Weight:
Net:
Shipping:
See Mounting
Angle Detail
Left Side
View
Top View
17.25
18.25
19.25
22.31
23.25
Front View
SAG582136600
Issue AU, February 21, 2014
5.05
8.31
10.00
0.92
1.75
Right Side
View
R 0.125 (TYP)
0.235
0.125
1.250
0.125
Bottom View
Mounting Angle Detail
0.500
0.500
0.125 0.235
0.125
1.250
Page 101 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
Overall Dimensions – 19” Battery Tray
Optional Battery Disconnect Circuit Breakers
(Shown on Right Side, Available on Either Side)
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
A
See
Note 3
10.50
12.25
14.00
(as ordered)
ISO View
Notes:
1. All dimensions are in inches,
unless otherwise specified.
2. P/N 558047 tray shown.
P/Ns 541034, 540841 and 548213 similar.
3.
Dimension
B
558047
541034
540841
7.78
7.03
6.90
17.60
20.95
12.50
548213 7.28
22.35
4. Weight in LBS.
(per tray, less batteries).
Tray P/Ns
558047
541034
540841
548213
With Circuit
Breaker Option
25.0 lbs
25.3 lbs
18.5 lbs
26.0 lbs
Without Circuit
Breaker Option
23.0 lbs
23.3 lbs
16.5 lbs
24.0 lbs
5. Finish: Gray
6. Maximum trays available per rack is three (3).
Front View B
See Note 3
Right Side View
Page 102 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
Overall Dimensions – 23” Battery Tray
Optional Battery Disconnect Circuit Breakers
(Shown on Right Side, Available on Either Side)
SAG582136600
Issue AU, February 21, 2014
A
See
Note 3
10.50
12.25
14.00
(as ordered)
ISO View
Notes:
1. All dimensions are in inches,
unless otherwise specified.
2. P/N 528496 tray shown.
P/N 540842 and 557573 similar.
3.
Tray P/N
Dimension
A
Dimension
B
528496 9.781
24.437
540842 6.90
557573 10.48
12.50
23.14
4. Weight in LBS.
(per tray, less batteries).
Part No.
With Circuit
Breaker Option
Without Circuit
Breaker Option
528496 33 lbs 29 lbs
540842 20 lbs 18 lbs
557573 25 lbs 23 lbs
5. Finish: Gray
6. Maximum trays available per rack is three (3).
Front View
B
See Note 3
Right Side View
Page 103 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600
Issue AU, February 21, 2014
BATTERY MANUFACTURER INFORMATION
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
Some equipment described in this System Application Guide is designed to accommodate batteries from various manufacturers. The following are referenced in this document.
C&D: C&D Technologies, Inc., Powercom Div., 1400 Union Meeting Road, Blue Bell, PA 19422-0858
Deka ® : East Penn Mfg. Co., Inc., Lyon Station, PA 19536-0147
Douglas ®
Marathon
: Douglas Battery Mfg. Co., 500 Battery Dr., Winston-Salem, NC 27117-2159
TM : GNB Industrial Power, a Division of Exide Technologies, Princeton, NJ 08543.
Northstar: NorthStar Battery Co. LLC, 4000 Continental Way, Springfield, MO 65803
PowerSafe Enersys TM : EnerSys Inc., Reading, PA, 196212-4145
RELATED DOCUMENTATION
Installation Instructions: Section 6031
User Instructions: Section 6032
Battery Cabinet Spec. No. 541434
Installation and User Instructions: Section 6023
Battery Cabinet Spec. No. 545534
Installation and User Instructions: Section 6033
Battery Cabinet Spec. No. 545506
Installation and User Instructions: Section 6036
Battery Cabinet Spec. No. 554631
Installation and User Instructions: UM554631
Rectifier User Instructions: UM1R481000
SCU+ Controller User Instructions: UM1M521BNA
ACU+ Controller User Instructions: UM1M820BNA
Page 104 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582136600 (Model 211 NGFB )
SAG582136600
Issue AU, February 21, 2014
REVISION RECORD
Issue
Change
Number
(ECO)
AN
AP
AR
AS
AT
AU
Description of Change Date Approved
LLP217521
Additional Battery P/N added to Battery Table.
Added optional 19” and 23” rear cover kits P/N
555260 and P/N 555261. Added optional digital input cable kit P/N 554935. Added references to List
73 optional external battery cable assembly P/N
555050. Added PCU blank filler as accessory.
02/20/2013
Shanon
Ravacio
LLP218760 Added Battery Cabinet P/N 554631.
LLP218923
Frame grounding lug adapter P/N 556872 (for use when wall mounted) added.
05/16/2013 John Jasko
09/04/2013 John Jasko
LLP218844 Added optional 3” projection mount kit P/N 556828. 09/19/2013
Khristebelle
Ilagan
LLP219497 Option to not power controller during LVBD added. 11/22/2013 John Jasko
LLP219376
Added 90A Bullet Breaker P/Ns 138887 and
138888. Added battery tray P/N 557573. Replaced battery tray P/N 541036 with 558047.
John Jasko
Feb 28, 2014
Jerry Li
Mar 4, 2014
02/21/2014 John Jasko
Emerson Network Power, Energy Systems, North America, Inc.
4350 Weaver Parkway, Warrenville, IL 60555
Toll Free: 800-800-1280 (USA and Canada)
Telephone: 440-246-6999 Fax: 440-246-4876
Web: EmersonNetworkPower.com/EnergySystems
EnergyNet: Secure.EmersonNetworkPower.com
Page 105 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 1 SYSTEM OVERVIEW
- 4 58213660001
- 10 TABLE OF CONTENTS
- 13 LIST DESCRIPTIONS
- 13 List 1: 1RU High by 19” Wide Shelf
- 14 List 2: 1RU High by 23” Wide Shelf
- 15 List 5: 2RU High by 19” Wide Shelf
- 16 List 6: 2RU High by 23” Wide Shelf
- 17 Rectifier Module (500W), P/N 1R48500
- 17 Rectifier Module (1000W), P/N 1R481000
- 17 ACU+ (Advanced Control Unit Plus), P/N 1M820BNA
- 18 SCU+ (Standard Control Unit Plus), P/N 1M521BNA
- 18 List 60: Five (5) Load Lead Assemblies (P/N 535206) for 10A GMT Fuse Positions
- 18 List 61: Eight (8) Load Lead Assemblies (P/N 535206) for 10A GMT Fuse Positions
- 19 List 62: Five (5) Load Lead Assemblies (P/N 540988) for 15A GMT Fuse Positions
- 19 List 65: Shelf Side Battery Cables, P/N 540814
- 19 List 66: Battery Side Battery Cables, P/N 540954
- 19 List 67: Battery Cable, P/N 545709
- 20 List 71: Optional External Battery Cable Assemblywith Anderson Connector for (1) Battery String, P/N 545493
- 20 List 72: Optional External Battery Cable Assemblywith Anderson Connector for (2) Battery Strings, P/N 535124
- 20 List 73: Optional External Battery Cable Assemblywith Anderson Connector for (1) Battery String, P/N 555050
- 21 List 89: Relay Rack Earthquake Anchor Kit, P/N P0987167
- 21 List 90: Optional Temperature Probe,P/N 04118246 (shelf side half) and P/N 04118247 (probe side half, 9 ft. long)
- 21 List 91: Optional Temperature Probe,P/N 04118246 (shelf side half) and P/N 04116740 (probe side half, 30 ft. long)
- 22 List 93: Battery Tray for 23” Relay Rack
- 25 List 94: Battery Tray for 19” Relay Rack
- 29 List BF: Distribution Unit with GMT Fuse Load Distribution Positionsand with Low Voltage Battery Disconnect (LVBD)
- 30 List LF: Distribution Unit with GMT Fuse Load Distribution Positionsand with Low Voltage Load Disconnect (LVLD)
- 31 List NF: Distribution Unit with GMT Fuse Load Distribution Positionsand w/out Low Voltage Disconnect
- 32 List BC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit BreakerLoad Distribution Positions, and with Low Voltage Battery Disconnect (LVBD)
- 33 List LC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit BreakerLoad Distribution Positions, and with Low Voltage Load Disconnect (LVLD)
- 34 List NC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit BreakerLoad Distribution Positions, and w/out Low Voltage Disconnect
- 35 List BA: Distribution Unit with GMT Fuse Load Distribution Positions,Circuit Breaker Load Distribution Positions, Circuit Breaker Battery Disconnect Positions,and with Low Voltage Battery Disconnect (LVBD)
- 36 List LA: Distribution Unit with GMT Fuse Load Distribution Positions,Circuit Breaker Load Distribution Positions, Circuit Breaker Battery Disconnect Positions,and with Low Voltage Load Disconnect (LVLD)
- 37 List NA: Distribution Unit with GMT Fuse Load Distribution Positions,Circuit Breaker Load Distribution Positions, Circuit Breaker Battery Disconnect Positions,and w/out Low Voltage Disconnect
- 38 List BG: Distribution Unit with GMT Fuse Load Distribution Positionsand with Low Voltage Battery Disconnect (LVBD)
- 39 List NG: Distribution Unit with GMT Fuse Load Distribution Positionsand w/out Low Voltage Disconnect
- 40 List KG: Distribution Panel with (20) GMT Fuse Load Distribution Positions
- 41 ACCESSORY DESCRIPTIONS
- 41 Relay Racks
- 42 Mounting and Adapter Kits
- 42 Optional Wall Mount Bracket Kit for Lists 1 and 2, P/N 541285
- 42 Optional Wall Mount Bracket Kit for Lists 1, 2, 5 and 6, P/N 553203
- 42 Optional 19” to 23” 1RU Rack Adapter Kit, P/N 540993
- 42 Optional 19” to 23” 2RU Rack Adapter Kit, P/N 545728
- 43 Optional 19” Rear Cover Kit, P/N 555260
- 43 Optional 3” Projection Mount Kit for List 1, P/N 556828
- 43 Optional 23” Rear Cover Kit, P/N 555261
- 43 Rear Battery Cable Exit Kit P/N 547645
- 44 Distribution Devices
- 44 GMT Load Distribution Fuses
- 45 Bullet Nose-Type Circuit Breakers
- 46 Optional Bullet Nose 6-Position GMT Fuse Module, P/N 545332
- 46 Optional Bulk Output Busbar, P/N 535015
- 47 AC Input Cables and Line Cords
- 47 AC Input Cable Assembly, P/N 535232
- 47 AC Input Line Cord, 208/240VAC, P/N 540946
- 48 AC Input Line Cord, 208/240VAC, P/N 545616
- 48 AC Input Line Cord, 120VAC, P/N 545252
- 49 AC Input Line Cord, 120VAC, P/N 545478
- 49 AC Input Line Cord, 120VAC, P/N 545479
- 50 AC Input Line Cord, 208/240VAC, P/N 545480
- 50 AC Input Line Cord, 120VAC, P/N 545481
- 51 AC Input Line Cord, 208/240VAC, P/N 545553
- 51 AC Input Line Cord, 120VAC, P/N 547525
- 52 AC Input Line Cord, 120VAC, P/N 548457
- 52 AC Input Line Cord, 120/208/240VAC, P/N 548196
- 53 Special Application Digital Input Cable Kit, P/N 554935
- 53 AP6C57EA/EB Ring & Distribution Module
- 55 External Battery Disconnect Unit, P/N 535282
- 56 NetSure™ 211bc Battery Cabinet (Spec. No. 541434)
- 57 NetSure™ 211bc Battery Cabinet (Spec. No. 545534)
- 58 NetSure™ 211bc Battery Cabinet (Spec. No. 545506)
- 59 NetSure™ 211bc Battery Cabinet (Spec. No. 554631)
- 60 SM TEMP Temperature Concentrator (P/N 547490)
- 60 SM Module RS-485 Interface Cable P/N 547674
- 60 PCU Blank Filler Panel, P/N PSK4820R-1
- 61 Anderson Battery Connector
- 62 Digital Input and Relay Output Cables
- 63 Replacement Modules
- 64 Wiring Notes
- 64 Shelf Frame Grounding Stud
- 64 AC Input Branch Circuit Protection and Wiring
- 64 External Alarm and Monitoring Wiring
- 65 Load Distribution Wiring (GMT Fuses) (Lists BG and NG only)
- 65 Load Distribution Wiring (GMT Fuses) (Lists BF, LF, and NF only)
- 66 Load Distribution Wiring (GMT Fuses) (Lists BC, LC, NC, BA, LA, and NA)
- 66 Load Distribution Wiring (Optional Bullet-Nose-Type 6-Position GMT Fuse Module)
- 66 Load Distribution Wiring (Circuit Breakers) (Lists BC, LC, NC, BA, LA, and NA)
- 68 Load Distribution Wiring (GMT Fuses) (List KG)
- 68 CO Ground Wiring (Lists BF, LF, NF, BC, LC, NC, BA, LA, and NA)
- 68 Input Battery Wiring (List BG and NG)
- 68 Input Battery Wiring (to Battery Disconnect Circuit Breakers) (Lists BA, LA, and NA)
- 69 Input Battery Wiring (to Battery Busbars) (Lists BF, LF, NF, BC, LC, and NC)
- 70 Wiring Illustrations
- 70 Shelf Frame Grounding Stud (both 1U and 2U Panels, List 1 and 5 shown)
- 71 AC Input Wiring (Lists 1 and 2)
- 72 AC Input Wiring (Lists 5 and 6)
- 73 External Alarm and Monitoring Wiring (Lists 1 and 2)
- 74 External Alarm and Monitoring Wiring (Lists 5 and 6)
- 79 Load Distribution Wiring (GMT Fuses) (Lists BG and NG installed in a List 1 or 2, List 1 shown)
- 80 Load Distribution Wiring (GMT Fuses) (Lists BF, LF, and NF installed in a List 5 or 6, List 5 shown)
- 81 Load Distribution Wiring (GMT Fuses) (Lists BC, LC, NC, BA, LA, and NA installed in a List 5 or 6, List 5 shown)
- 82 Load Distribution Wiring (Optional Bullet Nose 6-Position GMT Fuse Module)
- 83 Load Distribution Wiring (Circuit Breakers) and CO Ground Wiring (Lists BC, LC, and NC installed in a List 5 or 6, List 5 shown)
- 84 Load Distribution Wiring (Circuit Breakers), Input Battery Wiring (Circuit Breakers),and CO Ground Wiring (Lists BA, LA, and NA installed in a List 5 or 6, List 5 shown)
- 85 Load Distribution Wiring (GMT Fuses) (List KG)
- 86 Input Battery Wiring (Lists BG and NG installed in a List 1 or 2, List 1 shown)
- 87 Input Battery Wiring (Lists BF, LF, NF, BC, LC, and NC installed in a List 1 or 5, List 5 shown)and CO Ground Wiring (Lists BF, LF, and NF installed in a List 1 or 5, List 5 shown)
- 88 SPECIFICATIONS
- 91 PHYSICAL SIZE INFORMATION
- 91 Overall Dimensions – List 1
- 92 Additional Dimensions – List 1 with Wall Mounting Kit (P/N 541285)
- 93 Additional Dimensions – List 1 with Optional 19” Rear Cover Kit, P/N 555260
- 94 Additional Dimensions – List 1 with Optional 3” Projection Mount Kit, P/N 556828
- 95 Overall Dimensions – List 2
- 96 Additional Dimensions – List 2 with Wall Mounting Kit (P/N 541285)
- 97 Additional Dimensions – List 2 with Optional 23” Rear Cover Kit, P/N 555261
- 98 Overall Dimensions – List 5
- 99 Overall Dimensions – List 6
- 100 Additional Dimensions – Lists 1, 2, 5 and 6 with Wall Mounting Kit (P/N 553203)
- 101 Overall Dimensions – List KG
- 102 Overall Dimensions – 19” Battery Tray
- 103 Overall Dimensions – 23” Battery Tray
- 104 BATTERY MANUFACTURER INFORMATION
- 104 RELATED DOCUMENTATION