Franklin Water Pump 5870206300 User's Manual

Constant Pressure Water System
SubDrive300
Installation Manual
Contents
Description and Features ................................................................................4
Included Items ..................................................................................................5
How It Works.....................................................................................................6
Pump Sizing and Drive Configuration ............................................................8
Underload Sensitivity for Shallow Wells ........................................................9
Before Getting Started ...................................................................................10
Controller Location Selection ................................................................. 11-12
Circuit Breaker and Wire Sizing ....................................................................13
Quick Reference Guide ............................................................................ 14-15
Pressure Tank .................................................................................................16
Installation Procedure ....................................................................................17
Wiring Connections .................................................................................. 18-20
Start-Up and Operation .................................................................................21
Specifications .................................................................................................22
Mounting Dimensions ....................................................................................23
Diagnostic Fault Codes..................................................................................24
System Troubleshooting Guide .....................................................................25
Underload Smart Reset .................................................................................26
Over Temperature Foldback ..........................................................................26
Tables
1. SubDrive Models .......................................................................................3
2. Breaker Size and Maximum Cable Length ...........................................13
3. Minimum Pressure Tank Size.................................................................16
4. Pressure Tank Precharge .......................................................................16
Figures
1. Shipping and Mounting Screws.............................................................17
2. Motor Lead Connections .......................................................................18
3. Power and Pressure Sensor Connections............................................19
4. Pressure Sensor ......................................................................................20
5. Underload “Smart Reset” Well Recovery Time ....................................26
2
Table 1: SubDrive Models
Model Name
Part Number
Use with Motor Series
SubDrive300
5870206300 (NEMA 4)
234 317 xxxx (5.0 Hp)
3
Description and Features
The Franklin Electric SubDrive300 is a dependable residential and light
commercial water system controller that uses advanced electronics to
enhance the performance of standard submersible pumps. When used with
the specified Franklin Electric motor (see Table 1), the SubDrive eliminates
pressure cycling associated with conventional water well systems and
owners of private water well systems can enjoy “city-like” water pressure.
In addition, the reduced tank size (see Table 3) allows installation in small
spaces. Key features of the SubDrive include:
• Constant water pressure with a wide range of settings (25-80 psi)
• Smaller pressure tank can be used
• Fits the pump to the application – pump speed is controlled to
provide the optimum performance without overloading the motor
• Flexibility – you can use this unit with standard off-the-shelf pumps
• No in-rush (power-on transient) current
• Low motor start-up current (soft-starting)
• Active Power Factor Correction minimizes input RMS current
• Protection features
- Dry well conditions – using smart pump monitoring (see Page 26)
- Bound pump – with auto-reversing torque
- High voltage / lightning surge
- Low line voltage
- Open motor circuit
- Short circuit
4
Included Items
A
B
I
Franklin
Electric
SubDrive
is now
offer
Drive mus 150 and MonoDriv ing an introduct
t be regis
ory
e.
sion.
tered with The extended warranty exte
nsion on
warranty
Franklin
SubDrive
Electric
is free,
• If a
but the
in order
SubDrive
SubDrive/ 75,
to activ
not to excee is registered,
ate the
warranty Monothe warra
d 4 years
nty for that
• The
extenfrom its
regist
manu
unit
•
•
C
ration card
covers
facture
3 years
date.
must be
As with
from the
returned
our stand
date of
to Frank
ship.
ard warra
installation
lin Elect
nty, the
,
ric no later
extended
This Exten
than 30
warranty
days after
ded Warra
covers
installation
defects
nty cover
in mate
.
s only SubD
rial and
rive 75,
workmanSubDrive
150 and
MonoDrive
controllers
.
Cut or fold
here
SubDriv
Term of
warranty:
e Extend
must be
registered 3 Years from date
ed Warran
within 30
of instal
ty Registr
lation
days of
installation , not to excee
ation
Installed
d 4 years
date.
(check
from manu
one):
? SubDrive
facture
date.
75
Product
Installation
Installation
Name /
(587020
3380)
Owner
D
?
SubDrive
150
Address
Installer
Installer
Number (
01000
Warranty
MonoDrive
)
State
Zip
Distributor
Date of
?
(587020
4150)
Phone
City
Address
Phone
City
Installation
onoDrive
Serial
Number
State
SubDrive/M
Number
SubDrive
(examp
Date Code
Phone
(examp
Zip
Number (
)
le: 000451
le: 01A23)
This warran
)
ty card
Street,
must be
Bluffto
Pump Mfg.
returne
n, IN 46714
warranty.
d
/ Model
by mail, to Franklin Electr
or faxed
to 260-82 ic, Attn: Inside
7-5800
. All fields Sales Coordinator
in this form
–
must be SubDrive Produ
filled out
cts, 400
to validat
E.
e the extendSpring
ed
E
F
G
A. Controller Unit
B. Strain Relief Fittings
C. Pressure Shut-off
Sensor and Boot
D. Pressure Sensor and Boot
E.
F.
G.
H.
I.
H
Sensor Adjustment Tool
Sensor Cable
Installation Manual
Installation Guide
Warranty Card
5
How It Works
The Franklin Electric SubDrive300 is designed to be part of a system that
consists of only four components:
A.
B.
C.
D.
E.
Standard Pump and Franklin Electric Motor.
SubDrive Controller.
Small Pressure Tank (for tank size, see Table 3).
Franklin Electric Pressure Sensor (provided).
Franklin Electric Pressure Shut-Off Sensor (provided).
B
C
Pressure
Sensor
Leads
D
Pressure
Shut-off
Sensor
Leads
E
Pressure
Relief Valve
PUMP
MOTOR
Power Supply
From Circuit Breaker
Constant Pressure
The Franklin Electric SubDrive300 provides consistent pressure regulation
using advanced electronics to drive a standard motor and pump according
to the pressure demands indicated by a highly accurate, heavy-duty,
long-life pressure sensor. By adjusting the motor/pump speed, the
SubDrive300 can deliver constant pressure dependably, even as water
demand changes. For example, a small demand on the system, such as
a bathroom faucet, results in the motor/pump running at a relatively low
speed. As greater demands are placed on the system, such as opening
additional faucets or using appliances, the speed increases accordingly to
maintain the desired system pressure.
6
Motor Soft Start
Normally, when there is a demand for water, the SubDrive300 will
be operating to accurately maintain system pressure. Whenever the
SubDrive300 detects that water is being used, the controller always “ramps
up” the motor speed while gradually increasing voltage, resulting in a cooler
motor and lower start-up current compared to conventional water systems.
In those cases where the demand for water is small, the system may cycle
on and off at low speed. Due to the controller’s soft-start feature and
sensor’s robust design, this will not harm the motor or the pressure sensor.
System Diagnostics
In addition to regulating pump pressure and accurately controlling motor
operation, the SubDrive300 continuously monitors system performance and
can detect a variety of abnormal conditions. In many cases, the controller
will compensate as needed to maintain continuous system operation. But
if there is high risk of equipment damage, the controller will protect the
system and display the fault condition. If possible, the controller will try to
restart itself when the fault condition subsides.
Unique Features
SubDrive controllers provide the ultimate in system performance, utilizing
Franklin Electric’s three-phase motor series for maximum starting torque,
high efficiency and smooth operation. SubDrives convert residential singlephase 60Hz power into the variable-frequency three-phase needed by the
motor. In addition, SubDrives can spin a smaller pump slightly faster to
boost output to roughly double its 60Hz horsepower rating. This allows use
of smaller pumps for less system cost. If a smaller pump of the desired flow
rating is not available, the controller can be configured to use larger pumps
up to the horsepower rating of the motor.
7
Pump Sizing
Total Head (ft)
The SubDrive300 is configured at the factory for use with 3 Hp pumps that
are mounted to 5 Hp Franklin Electric three-phase motors. In general, the
SubDrive300 will enhance the performance of a 3 Hp pump to a similar
or better performance than a conventional 5 Hp pump of the same
flowrating (pump series).
Typical SubDrive300 Performance
To select the proper 3 Hp
)Q(1.XJUI4VC%SJWF
700
pump, first choose a 5 Hp
$POWFOUJPOBM)Q(1.1VNQ
$POWFOUJPOBM)Q(1.1VNQ
curve that meets the
application’s head and flow
600
requirements. Use the 3 Hp
500
pump in the same pump
400
series (flow rating). The
SubDrive300 will adjust the
300
speed of this pump to
200
produce the performance
100
of the 5 Hp curve. An
example of this is
5
15
30
45
60
75
illustrated in the graph at right.
Flow GPM
Drive Configuration
The SubDrive300 can also be set up to run a 5 Hp pump if desired, but the
larger pump will still produce to the 5 Hp curve and may only be operated
with a 5 Hp motor. To operate a different pump size, a DIP switch must be
positioned to select the correct pump rating. Otherwise, the SubDrive300
may trigger erroneous faults.
Configuration Switch
1
SW1
OFF
ON
Pump Size
3.0 Hp
5.0 Hp
O
N
To configure the SubDrive300
for a 5 Hp pump, locate the DIP
switch marked “SW1” at the
lower right corner of the main
circuit board. Use a small
screwdriver (provided)
to change the DIP switch
setting according to the chart
as shown.
! WARNING
▲
Serious or fatal electrical shock may result from contact with internal
electrical components. DO NOT, under any circumstances, attempt
to modify DIP switch settings until power has been removed and 5
minutes have passed for internal voltages to discharge!
8
Underload Sensitivity for
Shallow Wells
The SubDrive300 controller is configured at the factory to ensure detection
of Underload faults in a wide variety of pumping applications. In rare cases
(as with certain pumps in shallow wells) this trip level may result in nuisance
faults. If the pump is installed in a shallow well, activate the controller and
observe system behavior. Once the controller begins to regulate pressure,
check operation at several flow rates to make sure the default sensitivity
does not induce nuisance Underload trips.
If it becomes necessary to desensitize the Underload trip level, remove
power and allow the controller to discharge. Once the internal voltages have
dissipated, locate the DIP switch marked “SW1” at the lower right corner
of the main circuit board. Use a small screwdriver (provided) to change
Position 3 to the “ON” position to select the lower Underload sensitivity as
shown in the chart below.
Configuration Switch
POS Underload Sensitivity
O
N
SW1
3
OFF
Normal (default)
ON
Low (shallow wells)
! WARNING
▲
Serious or fatal electrical shock may result from contact with internal
electrical components. DO NOT, under any circumstances, attempt
to modify DIP switch settings until power has been removed and 5
minutes have passed for internal voltages to discharge!
9
Before Getting Started
! WARNING
▲
Serious or fatal electrical shock may result from failure
to connect the ground terminal to the motor, SubDrive
controller, metal plumbing, or other metal near the motor
or cable, using wire no smaller than motor cable wires. To
minimize risk of electrical shock, disconnect power before
working on or around the SubDrive300 system.
CAPACITORS INSIDE THE SUBDRIVE300 CONTROLLER CAN STILL HOLD LETHAL VOLTAGE EVEN AFTER
POWER HAS BEEN DISCONNECTED.
ALLOW 5 MINUTES FOR DANGEROUS INTERNAL
VOLTAGE TO DISCHARGE BEFORE REMOVING
SUBDRIVE300 COVER.
Do not use motor in swimming areas.
! ATTENTION
▲
This equipment should be installed by technically qualified
personnel. Failure to install it in compliance with national
and local electrical codes and within Franklin Electric
recommendations may result in electrical shock or fire
hazard, unsatisfactory performance, or equipment failure.
Installation information is available through pump
manufacturers and distributors, or directly from Franklin
Electric at our toll-free number 1-800-348-2420.
! CAUTION
▲
Use SubDrive300 only with Franklin Electric 4-inch
submersible motors as specified in this manual (see Table
1). Use of this unit with any other Franklin Electric motor or
with motors from other manufacturers may result in damage to both motor and electronics.
10
Controller Location Selection
The SubDrive controller is intended for operation in ambient temperatures
up to 125°F (51°C) at 230 VAC input. The following recommendations will
help in selection of the proper location of the SubDrive unit:
1. A tank tee is recommended for mounting the tank, pressure sensor,
pressure gauge, and pressure relief valve at one junction. If a tank
tee is not used, the pressure sensor should be located within 6 feet
(1.8 meters) of the pressure tank to minimize pressure fluctuations.
There should be no elbows between the tank and pressure sensor.
2. The unit should be mounted on a sturdy supporting structure such as a
wall or supporting post. Please take into account the weight of the unit,
which weighs approximately 34 pounds (15.5 kg).
3. The electronics inside the SubDrive are air-cooled. As a result, there
should be at least 6 inches of clearance above and below the unit to
allow room for air flow.
! CAUTION
▲
There should be at least 6 inches of clearance above and below the
unit to allow room for air flow.
6"
min.
Clearance Pressure
Tank
For
Air Flow
Pressure
Sensor
Pressure
Shut-off
Sensor
6 Feet or Less
PUMP
6"
min.
(Pressure Tank to PressureSensor)*
Pressure
Relief Valve
MOTOR
* NOTE: there should be no elbows between the tank and pressure sensor.
11
Pressure Sensor
Wiring
Wiring
To Motor
Power Supply
From Circuit Breaker
Power Supply
From Circuit Breaker
Wiring
To Motor
Pressure Sensor
Wiring
CORRECT
INCORRECT
4. For indoor or outdoor installations.
5. The SubDrive300 should only be mounted with the wiring end
oriented downward. The controller should not be placed in direct
sunlight or other locations subject to direct rain or snow.
6. The mounting location should have access to 230 VAC electrical
supply and to the submersible motor wiring. To avoid possible
interference with other appliances, please refer to the enclosed
Installation Guide and observe all precautions regarding power
cable routing.
7. To assure maximum weather protection, the unit must be mounted
vertically with the cover properly aligned and secured with all eight
lid screws.
12
Circuit Breaker and Wire Sizing
The minimum circuit breaker size and maximum allowable wire lengths for
connection of motor to the SubDrive300 are given in the following table:
Table 2: Minimum Breaker Size and Maximum Cable Length (in Feet)
AWG Copper Wire Size
Controller
Model
Franklin Electric
Breaker
Motor Model
HP Amps
14
12
10
8
SubDrive300
234 317 xxxx
140
230
370
590
5
40
6
4
920 1430
A 10-foot section of cable is provided with the SubDrive300 to connect
the pressure sensors.
NOTE:
• Maximum allowable wire lengths are measured between the
controller and motor.
• Aluminum wires should not be used with the SubDrive300.
• Wire sizing between the service entrance and the controller must
be sufficient to provide the required maximum input amps to the
controller while conforming to local standards and codes.
• SubDrive300 minimum breaker amps may be lower than AIM
Manual specifications for the motors listed due to the soft-starting
characteristic of the SubDrive300 controller.
13
Quick Reference Guide
P/N 587 020 6300
Configura
SW2
O
N
SW1
1
OFF
ON
From Power Source
Outpu
PRESSURE
SENSOR
INT
FAN
SHUT-OFF
NO
NO
RELAY
COM
PFC
FAN
L1
INV
FAN
L2
(Input)
Sensor Connection
PRESSURE
SENSOR
Red Blk
PRESSURE
SHUT-OFF
Wh Grn
Power Supply
From Circuit Breaker*
Pu
NOTICE
The Safety earth ground connections
are marked at their terminals using
the “ ” symbol
*Note: To avoid possible interference with other appliances,
please refer to the enclosed installation guide and observe all
precautions regarding power cable routing
14
Fra
Ele
Mo
e SubDrive300 (not to scale)
Tank Precharge
Inflation Valve
Sensor Cable
Supplied
Pressure Tank
ation Switch
See Table 3
(page 16) for
recommened
minimum tank size
Pump Size
3.0 Hp
5.0 Hp
ut to Motor
Pressure Gauge
Pressure
Sensor
Pressure
Shut-off
Sensor
Red Yel Blk
(Brn) (Blue) (Blk)
(Output)
Discharge into
drain rated for
max pump output
at relief pressure
ump
anklin
ectric
otor
To Residence
Pressure
Relief Valve
Drain Valve
Pressure Setting Guide
WARNING
Submersible pumps can
develop very high pressure in
some situations. Always
install a pressure relief valve
able to pass full pump flow at
100 PSI. Install the pressure
relief valve between the
pump and pressure tank.
Pressure Switch
Set Point (PSI)
Pressure Tank
Pre-Charge (PSI)
25
30
35
40
45
50 (Factory set)
55
60
65
70
75
80
18
21
25
28
32
35
39
42
46
49
53
56
15
Pressure Tank
The SubDrive needs only a small pressure tank to maintain constant
pressure (see table below for recommended tank size). For pumps rated 12
gpm or more, a slightly larger tank is recommended for optimum pressure
regulation. The SubDrive can also use an existing tank with a much larger
capacity.
Table 3: Minimum Pressure Tank Size (Total Capacity)
Pump Flow Rating
Controller Model
Minimum Tank Size
Less than 12 gpm
SubDrive300
8 gallon
12 gpm and higher
SubDrive300
20 gallon
The pressure tank pre-charge setting should be 70% of the system pressure
sensor setting as indicated in the following table.
Table 4: Pressure Tank Precharge (PSI)
System Pressure
(at Pressure Sensor)
Pressure Tank
Setting (±2 psi)
25
18
30
21
35
25
40
28
45
32
50
35
55
39
60
42
65
46
70
49
75
53
80
56
Factory Setting
NOTE: Check tank precharge regularly to maintain optimum
pressure regulation.
16
Installation Procedure
1. Disconnect electrical power at the main breaker.
2. Drain the system (if applicable).
3. Install the pressure sensor and pressure shut-off sensor at the
pressure tank tee downstream of the pressure tank (the pressure
tank should be between the pressure sensor and the pump). The
sensors have a ¼-18 National Pipe Thread (NPT) connection.
The pressure sensors should not be installed in an inverted
orientation (up-side down). Make sure the pressure sensor and tank
are not located more than 3 feet off the main piping.
4. Install the unit to the wall using four mounting screws (not included) as
shown in Figure 1 below. Remove the SubDrive lid by removing the eight
lid screws.
Lid Screws (Included Quantity 8)
Mounting Screw Locations
(User Supplied Quantity 4)
Figure 1: Mounting Screws
17
Wiring Connections
! WARNING
▲
Serious or fatal electrical shock may result from failure to connect
the motor, the SubDrive300, metal plumbing and all other metal near
the motor, or cable to the power supply ground terminal, using wire
no smaller than motor cable wires. To reduce risk of electrical shock,
disconnect power before working on or around the water system.
Do not use motor in swimming areas.
1. Verify that the power has been shut off at the main breaker.
2. Verify that the dedicated branch circuit for the SubDrive300 is
equipped with a properly-sized circuit breaker. Refer to Table 2
(Page 13) for minimum breaker size.
3. Use the appropriate strain relief or conduit connectors. Type B liquid
tight fittings are recommended for maximum weather protection.
4. Remove the SubDrive300 lid.
SW2
O
N
SW1
5. Feed the motor leads through the opening on the bottom right side
of the unit and connect them to the terminal block positions marked
GND (Green ground wire), Red, Yellow and Black (Figure 2).
Output to Motor
PRESSURE
SENSOR
INT
FAN
SHUT-OFF
NO
NO
RELAY
COM
PFC
FAN
INV
FAN
Red Yel Blk
(Brn) (Blue) (Blk)
(Output)
Figure 2: Motor Lead Connections
18
SW1
O
N
SW2
From Power Source
PRESSURE
SENSOR
INT
FAN
SHUT-OFF
NO
NO
RELAY
Sensor Connection
COM
PFC
FAN
INV
FAN
PRESSURE
SENSOR
L1
L2
Red Blk
(Input)
PRESSURE
SHUT-OFF
Wh Grn
Figure 3: Power and Pressure
Sensor Connections
6. Feed the 230 VAC power leads through the bottom left side of the
SubDrive300 controller and connect them to the terminals marked
L1, L2, and GND (Figure 3).
A 10-foot section of pressure sensor cable is provided with the
controller, but it is possible to use similar 22 AWG wire for distances
up to 100 feet from the pressure sensor. A 100-foot section of
pressure sensor cable is available as an accessory.
7. Feed the pressure sensor leads through the smaller opening located in the
bottom middle of the SubDrive300 unit and press on the quick
connect terminals.
8. Verify that the SubDrive300 unit is properly configured for the
horsepower rating of the motor and pump being used. Please refer to
the section on Pump Sizing for information on drive configuration.
9. Replace the lid. Do not over-tighten the screws.
19
Remove Rubber End Cap To Adjust Pressure
With 7/32" Allen Wrench
Non-Adjustable
Set at 100PSI
Pressure
Sensor
Boot
Quick Connect
lead connect
Figure 4A:
Pressure Sensor
Figure 4B:
Pressure Shut-off Sensor
10A. Connect the other end of the pressure sensor cable with the two
spade terminals to the pressure sensor. The connections are
interchangeable (Figure 4A).
10B. Connect the other end of the pressure sensor cable with the two
¼" quick connect terminals to the pressure shut-off sensor. The
connections are interchangeable (Figure 4B).
11. Set the pressure tank pre-charge at 70% of the desired water
pressure setting. To check the tank’s pre-charge, de-pressurize
the water system by opening a tap. Measure the tank pre-charge
with a pressure gauge at its inflation valve and make the necessary
adjustments.
12. The pressure sensor communicates the system pressure to the
SubDrive300 controller. The sensor is preset at the factory to 50 psi,
but can be adjusted by the installer using the following procedure:
a. Remove the rubber end-cap (Figure 4A).
b. Using a 7/32” Allen wrench (provided), turn the adjusting screw
clockwise to increase pressure and counter-clockwise to
decrease pressure. The adjustment range is between 25 and 80
psi (¼ turn = approximately 3 psi).
c. Replace the rubber end cap.
d. Reset the pressure tank pre-charge to the appropriate pressure.
e. Cover the pressure sensor terminals with the rubber boot
provided (Figure 4A).
! CAUTION
▲
When increasing the pressure, do not exceed the mechanical stop on
the pressure sensor or 80 psi. The pressure sensor may be damaged.
NOTE: Ensure that the system is properly grounded all the way to the service
entrance panel. Improper grounding may result in the loss of voltage surge
protection and interference filtering.
20
Start-Up and Operation
Apply power to the controller. A steady green light indicates that the
SubDrive300 has power but the pump is not running. The green
light will flash continuously when the pump is running.
Leaky Systems
Leaky water systems might keep the controller running due to the accurate
pressure sensing capability of the pressure sensor. Continuous running
or starts and stops do not hurt the controller, pump or motor. However,
to reduce the on-time of the controller/pump/motor, a “Bump-Mode”
procedure is installed. During low flow (or leaky) conditions this feature
periodically increases the speed of the pump several PSI above the set
point and shuts off the pump. This adds some time to bleed off before the
system starts up again.
NOTE: Conventional private water systems intermittently fill a pressure
tank as commanded by a standard pressure switch (e.g. 30 - 50 psi). The
SubDrive300 maintains a constant pressure at the pressure sensor up to the
maximum capability of the motor and pump.
Although the pressure is constant at the pressure sensor, pressure drops
may be noticeable in other areas of the home when additional taps are
opened. This is due to restrictions in the plumbing and will be more
pronounced the farther the taps are from the pressure sensor. This would
be true of any system, and if observed, should not be interpreted as a
failure in the performance of the SubDrive300.
21
Specifications
Input from
Power Source
(single-phase)
Output to Motor
(three-phase)
Pressure Setting
Operating (A)
Conditions
Controller Size (B)
(approximate)
For Use With (C)
NOTES:
Voltage
190-260 VAC
Frequency
50/60 Hz
Current (max)
36 Amps (RMS)
Power Factor
1.0 (constant)
Power (idle)
65 Watts
Power (max)
7200 Watts
Voltage
Adjusts with Frequency
Frequency Range
30-80 Hz (3 Hp pump)
30-60 Hz (5 Hp pump)
Current (max)
17.8 Amps (RMS, each phase)
Factory preset
50 psi
Adjustment range
25-80 psi
NEMA 4 (indoor/outdoor)
Model 5870206300
Temperature (at 230 VAC
input)
-13 to 125°F
(-25 to 51°C)
Relative Humidity
0-100%, non-condensing or
condensing
Outer dimensions
14 ¾” H × 15 ¾” W × 8 ¾” D
Weight
34 lbs (15.5kg)
Pump (60Hz)
3.0 Hp (default)
5.0 Hp
Motor (3-phase)
234317- series (5.0 Hp)
(A) Operating temperature is specified at full output power when installed as
described in Controller Location Selection on Page 11.
(B) Refer to Page 23 for detailed mounting dimensions.
(C) If a pump other than the default rating is used, refer to Page 8 for
drive configuration.
22
Mounting Dimensions
15.34”
8.75”
14.75”
12.00”
4.75”
23
Diagnostic Fault Codes
Should an application or system problem occur, built-in diagnostics will
protect the system. The red “FAULT” light on the front of the SubDrive300
controller will flash a given number of times to indicate the nature of the
fault. In some cases, the system will shut itself off until corrective action has
been taken. Fault codes and the recommended corrective action for each
are listed in the following chart.
# of
Flashes
Fault
Possible Cause
Corrective Action
Motor
Underload
Air-locked pump.
Overpumped or dry well.
Worn pump. Damaged
shaft or coupling. Blocked
pump or screen.
Wait for well to recover and
automatic restart timer to time
out. If the problem does not
correct, check motor and pump.
See description of “Smart Reset”
on Page 26.
2
Undervoltage
Low line voltage.
Misconnected input leads.
Check for loose connections.
Check line voltage. Report low
voltage to the power company.
Unit will start automatically when
the proper power is supplied.
3
Locked
Pump
1
4
5
Reserved for factory use
Open Circuit
Loose connection.
Defective motor or cable.
Check motor wiring. Make certain
all connections are tight. Make
certain proper motor is installed.
Cycle input power** to reset.
Short Circuit
When fault is indicated
immediately after power-up,
short circuit due to loose
connection, defective cable,
splice or motor.
Check motor wiring. Cycle input
power** to reset.
Over Current
When fault is indicated
while motor is running, over
current due to loose debris
trapped in pump.
Check pump.
Overheated
Controller
High ambient temperature.
Direct sunlight. Obstruction
of air-flow.
This fault automaticallyresets
when the temperature returns to a
safe level.
6
7
Motor/pump misaligned.
Unit will attempt to free a locked
Abrasive/Sand-bound pump. pump. If unsuccessful, check the
Dragging pump or motor.
motor and pump.
** “Cycle input power” refers to turning the power off until both lights fade off,
then applying power again.
24
System Troubleshooting Guide
Symptom
Water flow rate
is not as high as
expected.
Possible Cause
Corrective Action
Motor is running backwards.
Verify motor connections.
See Figure 2 in the “Wiring
Connections” section.
Temperature in the controller
is too high. If the controller’s
heat exchanger becomes too
hot, the controller will reduce
the speed of the pump to
lower the power consumption.
Make sure there is at least 6” of room
around the controller for movement
of air. Avoid direct sunlight. Reduce
ambient temperature below 125°F
(51°C). Increase input voltage if
below 230 VAC.
Pump capacity cannot supply
the demand.
Use pump with higher flow rating
(if head requirement is still satisfied).
Check tank for bladder damage.
Replace if necessary.
Excessive
pressure
fluctuations.
Waterlogged tank.
Pressure tank is too small for
flow rating of the pump.
Leak in the pitless adapter.
Motor runs
continuously with
no flow demand. Leak in the household or
outdoor plumbing
Reset the tank pre-charge pressure
(should be 70% of pressure sensor
setting).
Use larger tank
(refer to Table 3 on Page 16 for
minimum Pressure Tank size).
Re-seat the pitless adapter. Replace
seal as needed.
Check for leaky faucets, valves
and/or pipe fittings and repair.
25
Underload Smart Reset
If a motor Underload fault condition occurs, the most likely cause is an
overpumped or dry well. To allow the well to recover, the SubDrive300
controller will wait 30 seconds to 5 minutes, determined by duration of
the previous run time, before restarting the motor. For example, the first
time the fault occurs, the controller will wait 30 seconds before attempting
to restart the pump. If the system would then run for 1 minute and an
Underload fault recurs, the controller will wait 4 minutes before attempting
to restart the pump. This schedule allows for the minimum off-time possible
based on the recovery time of the well.
Figure 5: “Smart Reset” Well Recovery Time
Off Time (Min.)
6.0
5.0
4.0
3.0
2.0
1.0
0.0
0
1
2
3
4
5
6
7
8
Run Time (Min.)
Over-Temperature Foldback
The SubDrive300 controller is designed for full power operation in ambient
temperatures up to 125°F (51°C) as long as the input voltage is kept at 230
VAC. Under extreme thermal conditions, the controller will reduce output
power in an attempt to avoid shutdown. Full pump output is restored when
the controller temperature cools to a safe level.
26