- Home
- Home security & automation
- Security device components
- DPS Telecom
- Omega Temperature and Humidity Sensor HX93A
- Owner's manual
DPS Telecom | Omega Temperature and Humidity Sensor HX93A | Owner's manual | DPS Omega HX93A
Add to My manuals12 Pages
advertisement
DPS Telecom
“Your Partners in Network Alarm Monitoring”
Omega HX93A
Operation Guide
Fig. 1 – The Omega HX93A can be used in conjunction with the NetGuardian or the KDA.
1.1
Summary of Features
• Measures temperature and relative humidity of a network site
• ABS plastic watertight enclosure
• Easy connection to the NetGuardian or the KDA
1.2
Description
The Omega HX93A, used in conjunction with the NetGuardian or the KDA(with an analog card), allows a network manager to monitor the environmental status of a network site. The unit measures the temperature and relative humidity of the immediate network area, thus providing pertinent environmental information from equipment sites.
The Omega HX93A measures temperatures between –4 degrees and +167 degrees Fahrenheit (–20 to +75 degrees
Celsius). It also gauges relative humidity between the range of 3% to 95%. The NetGuardian or KDA(with an analog card) send alarm notifications to the network managers, via analog alarm inputs, if either the temperature or the relative humidity approaches levels that are too high or too low. Proper equipment operation thresholds are determined by the user, which when exceeded, will trigger an alarm condition.
See figure 1.2 below for a typical Omega HX93A installation.
NetGuardian
OR
Omega
HX93A
KDA
September 14, 2004
(800) 622-3314
Fig. 1.2 - The Omega HX93A can be connected to the NetGuardian or the KDA.
1
OG00B.14130
www.dpstelecom.com
Table of Contents
1.1 Summary of Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.3 Shipping List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.4 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.1 Omega HX93A connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.1.1 DC to DC converter power connection . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.1.2 Determining Alarm Threshold Values . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.1.2.1 Converting Volts to meaningful measurements . . . . . . . . . . . . . . . . 4
2.2 NetGuardian connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.2.1 Power connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.2.2 NetGuardian communication lines . . . . . . . . . . . . . . . . . . . . . . . . . . .6
2.2.3 NetGuardian analog jumper settings . . . . . . . . . . . . . . . . . . . . . . . . . .6
2.2.4 Software configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
2.3 KDA connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.3.1 Power connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.3.1.1 Power connection without a DC to DC Converter . . . . . . . . . . . . . . 9
2.3.2 KDA communication lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.3.3 KDA analog jumper settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
2.3.4 KDA software configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
1.3
Shipping List:
Package D-PK-280-10A-00
Omega HX93A
D-PR-591-10A-00
“Y ou r Pa rtn
DPS T ers in Networ elecom k Ala rm ing
”
Omega HX93A
Oper ation Gu ide
1.1
Fig. 1 –
The Omega HX93A
Summary of Features
• ABS plastic watertight enclosure
can be used in conjunction with the NetGuardian or
1.2
Description
immediate network area, thus providing pertinent environmental information from equipment sites.
Celsius). It also gauges relative humidity between the range of 3% to 95%. send alarm notifications to the network managers, via analog alarm inputs, if either the temperature or the relative humidity approaches levels that are too high or too low when exceeded, will trigger an alarm condition.
See figure 1.2 below for a typical Omega HX93A
the KDA.
The unit measures the temperature and relative humidity of the
NetGuardian
. Proper equipment operation thresholds are determined by the user installation.
The NetGuardian or KDA(with an analog card)
OR
September 14, 2004
(800) 622-3314
Fig. 1.2 -
KDA
The Omega HX93A
, which
can be connected to the NetGuardian or
1
Omega
HX93A the KDA.
www
Omega HX93A Operation Guide
OG00B.14130
September 14, 2004
(800) 622-3314
Mounting screws
–48 VDC to +12 VDC Converter
D-PC-766-10A-00
OG00B.14130
www.dpstelecom.com
1.4
Specifications
HX93A (D-PR-591-10A-00)
A. Mechanical
Dimensions:
Weight:
3.14" (80mm) x 3.22"
(82mm) x 2.16” (55mm)
8 oz. (227 grams) max.
Connectors: Liquid-tight nylon with neoprene gland, for .09" to .265" diameter cables. Internal 4-pin terminal block accepts # 14-22 AWG wires.
B. Relative Humidity
Input Voltage Range:
RH Range:
Accuracy:
RH Temperature
Compensation Range:
HX93A RH Output:
RH Time Constant:
6 to 30 VDC
(polarity protected)
3% RH to 95% RH
±2% RH
–4°F to +167°F
(–20°C to +75°C)
4 to 20mA for 0 to 100% RH
(for 90% response at 25°C; in moving air, 1M/sec.)
Less than 10 seconds, 10% RH to 90% RH
Less than 15 seconds, 90% RH to 10% RH
±1% RH Repeatability:
C. Temperature
Input Voltage Range:
Temperature Range:
Accuracy:
HX93A Temperature
Output:
Temperature Time Constant:
Repeatability:
Total current draw:
6 to 30 VDC (polarity protected)
–4°F to +167°F (–20°C to +75°C)
±1°F (±0.6°C)
4 to 20mA for -20°C to +75°C
(for 63.2% response) Less than 9 seconds in moving air (1M/sec); Less than 30 seconds in still air.
±0.5°F (±0.3°C)
30mA
DC to DC converter (D-PC-766-10A-00)
Input Voltage Range:
Output Voltage Range:
Output Current:
Internal Input Fuse:
–36 to –72VDC (polarity protected)
+12 VDC
250mA
250mA
September 14, 2004
(800) 622-3314
OG00B.14130
www.dpstelecom.com
Installation
Chapter 2
2.1
Omega HX93A connections
The Omega HX93A can be connected to the NetGuardian or the KDA. The installation section is broken up into two sections, one for installation with a NetGuardian, and one for installation with a KDA.
The Omega HX93A is a current output device. It measures Temperature from –4 to 167º F and Relative Humidity from 3 to 95% RH and outputs 4 to 20 mA of current for each of its measurements. Each hosts installation section details the hardware and software setup for using the sensor.
2.1.1 DC to DC converter power connection
The Omega sensor can be powered by an optional DC to DC converter (See figure 2.1.1). The converter supplies a +12
VDC output from a –48 VDC input. Up to 250mA are output so multiple sensors can be connected to the same converter.
Refer to the individual host sections in this manual for specific connection information to the DC to DC converter.
Fig. 2.1.1 - The Omega HX93A can be powered by a –48 VDC to +12 VDC converter.
September 14, 2004
(800) 622-3314
OG00B.14130
www.dpstelecom.com
2.2
Installing with a NetGuardian
2.2.1 NetGuardian analog jumper settings
1. Carefully open the NetGuardian case by removing the outer screws.
2. Lift the lid of the NetGuardian to reveal the PC board as shown in figure 2.2.1a.
3. Locate the 8 analog input jumpers underneath the daughter board (See figure 2.2.1a).
4. Refer to Table 2.2.1 to determine which jumpers correspond the analog inputs to be used by the Omega HX93A.
Switch the jumpers for the analog channel you are using from the un-jumpered/open position measuring voltage
(default), to the jumpered/closed position (See figure 2.2.1b).
5. Close the lid and replace the 4 case screws and 4 hex jack screws.
Underneath the daughter board
J15, J16, J18, J20, J21, J22, J23, J24
Fig. 2.2.1a - The jumper default position is unjumpered/open to measure voltage. Switch the jumpers for the inputs used by the Omega HX93A to the jumpered/closed position.
Fig. 2.2.1b - A jumper in the jumpered/closed position.
Tbl. 2.2.1 - Analog alarm jumper numbers
Analog Alarm #
1 2 3 4 5 6 7 8
Jumper PCB Ref. #
J15 J16 J18 J20 J21 J22 J24 J23
September 14, 2004
(800) 622-3314
OG00B.14130
www.dpstelecom.com
2.2.2 Wiring Connections
1. Power down the the NetGuardian (remove the fuse).
2. Remove the cover of the Omega HX93A by removing the 4 screws from the face plate.
3. Connect wires from both screw-lug terminals #1 to the positive terminal of a 6-30 VDC power supply (Output of the
DC to DC converter).
4. Connect wires from both screw-lug terminals #3 to the positive input pins of the desired analog alarms. In the figure below, terminal 1 connects to Amphenol pin 19 for analog channel 1B, and terminal 3 connects to Amphenol pin 20 for analog channel 2B. Refer to Table 2.2.2 for pin numbers for each analog alarm input.
5. Connect wires from the ground or negative output of the 6-30 VDC power supply (GND of the DC to DC converter) to the negative inputs of the analog alarms being used.In the figure below, pins 44 and 45 are used for analog alarms
1 and 2. Refer to Table 2.2.2a and b for pin numbers for each analog alarm input
6. If using the DC to DC converter, connect it to a 48 VDC power supply.
7. Power up the NetGuardian when all connections have been made and proceed to provision the NetGuardian software for the Omega HX93A.
Precautions
• Always observe electrostatic discharge (ESD) precautions.
Rel. Humid.
ADC 1A
ADC 1B
-
J15 pin 44
R s
+
= 250 pin 19
+
1
Omega HX93
Sensor
2 3 Temp.
Net Guardian
ADC 2A
Temp.
ADC 2B
pin 45
J16
R s
+
= 250 pin 20
1 2 3
+
Rel. Humid.
GND
-48VDC
INPUT
GND
DC to DC Converter
-48V IN
+12V OUT
+12VDC OUTPUT
+
Fig. 2.2.2 - Functional schematic of connection to the NetGuardian.
Tbl. 2.2.2a - Analogs 1-6
Amphenol pins
Analog Alarm # 1 2 3 4 5 6
Positive (+) Pin
Number
Negative (–) Pin
Number
NetGuardian
Jumper #
19
44
20
45
21
46
22
47
23
48
24
49
J15 J16 J18 J20 J21 J22
Tbl. 2.2.2b - Analogs 7-8
Screw lug
Analog Alarm # 7 8
Positive (+) Pin
Number
Negative (–) Pin
Number
NetGuardian
Jumper#
B
A
B
A
J23 J24
September 14, 2004
(800) 622-3314
OG00B.14130
www.dpstelecom.com
2.2.4 NetGuardian Software configuration
1. Open a web browser and go to the IP address of the NetGuardian to be configured. (See NetGuardian Manual for details on using the web interface. The text interface may also be used to configure the analog alarms.)
2. Login to the NetGuardian, then click on the “Edit” menu link in the left frame of the window.
3. Click on the Analogs link to bring up the Analogs screen.
4. Enter a Description for the inputs being used such as “Temperature” or “ Relative Humidity.” Wait to enter the thresholds until you have setup the scaling for that input.
5. Check mark the Trap check box to send SNMP traps for that alarm. then set the Primary and Secondary pager IDs. Refer to the NetGuardian manual for detailed field descriptions and web browser interface details.
6. Click on the Unit link to configure the scale and offset for each alarm.
3. Click on the
“Unit” abbreviation to configure the reference and native unit settings
1.
2.
Fig. 2.2.4a - Provision the NetGuardian with the Omega HX93A information.
Native Unit 1 and 2
Fig. 2.2.4b - The Analog Units menu sets the volts to native units conversion scale from two reference points.
2.2.4.1 Units conversion from Volts
1. Each alarm must have its conversion scale from volts to the units being measured configured before alarm thresholds be set. This is done from the Analog Units screen which is reached by clicking on the Units abbreviation in the
Analog alarms menu.
2. In the Reference 1 and 2 sections, enter the units being measured by that channel (for example, F for Fahrenheit, C for Celsius, RH for Relative Humidity). (See figure 2.2.4b)
The Omega HX93A measures temperature in the range of -4 to 167º F (-20 to 75º C), and relative humidity from 3 to 95%
RH. these are the values that are entered in the Native Unit fields to establish the correct scale and the offset to convert from Volts or milliamps to meaningful units.
3a. For temperature in degrees Fahrenheit, set ‘Native Unit 1’ to -4 and ‘Native Unit 2’ to 167.
For temperature in degrees Celsius, set ‘Native Value 1’ to -20 and ‘Native Value 2’ to 75.
3b. For relative humidity, set ‘Native Value 1’ to 3 and ‘Native Value 2’ to 95.
VDC reference 1 and 2 correspond to the electrical output of the sensor in volts . The Omega HX93A outputs from 4 to
20mA of current to indicate the temperature and the relative humidity. Since a 250 ž shunt is inserted by the jumper, as described in section 2.2.1, 1 to 5 volts will correspond to 4 to 20mA of current. This is determined using Ohms law
(E=IR: .004A x 250ž = 1 V and .020A x 250ž = 5 V).
4. Click the “Submit Data” button to enter the changes.
5. Now enter the Thresholds at which an alarm will be triggered. Threshold values will be rounded to the nearest measurable value and might not be the exact numbers entered.
6.
After all data has been entered, Logout of the NetGuardian by clicking the Logout link in the upper right corner.
September 14, 2004
(800) 622-3314
OG00B.14130
www.dpstelecom.com
2.3
Installing with a KDA
The Omega HX93A can only be used in conjunction with an 8 or 16 Channel Analog card in the expansion slot of the KDA. The pinouts and connections are the same whether the 8 or 16 Channel Analog card is being used.
2.3.1 Wiring connections
1. Power down the KDA.
2. Remove the cover of the Omega HX93A by removing the 4 screws from the face plate.
3. Connect wires from both screw-lug terminals #1 to the positive terminals of a 6-30 VDC power supply (Output of DC to
DC converter). (See figure 2.3.1)
4. Connect wires from both screw-lug terminals #3 to the positive input of the analog Alarm channels being used. (Refer to the
Expansion card operation guide for the pinouts of the various connectorization options).
5. Connect the ground or negative output of a 6-30 VDC power supply (GND of the DC to DC converter) to the negative input of the analog Alarm channels being used. (Refer to the Expansion card operation guide for the pinouts of the various
connectorization options).
6. If using the DC to DC converter, connect it to a -48 VDC power supply. (See figure 2.3.1)
7. Do not power up the KDA until all of the hardware installation procedures in this manual are complete.
Rel. Humid.
–
J5
R s
= 250
+
KDA Analog
Expansion Card
Temp.
–
J4
R s
= 250
+
+
Omega HX93
Sensor
1 2
3
Temp.
1 2
3
+
Rel. Humid.
48VDC
INPUT
+
GND
DC to DC Converter
48V IN
12V OUT
12VDC OUTPUT
+
Fig. 2.3.1 - Functional schematic of connection to a KDA.
September 14, 2004
(800) 622-3314
OG00B.14130
www.dpstelecom.com
2.3.3 Analog card jumper settings
The Omega HX93A outputs temperature and relative humidity as current readings. The analog alarms measure voltage by default, however they may be individually configured to measure current with a circuit board jumper. For the analog inputs being connected to the Omega HX93A, the jumper corresponding to that input must be switched to the closed position.
1. Remove the 8 or 16 Channel Analog Monitor from the KDA.
2. Refer to Table 2.3.3 to see which jumpers correspond to the analog alarm channels to be used for the
Omega HX93A.
3. Place those jumpers in the jumpered/closed position.
3. Reinsert the 8 or 16 Channel Analog Monitor into the KDA.
J4 -J17,
J19 -J20
Fig. 2.3.3a - The jumper default position is unjumpered/open to measure voltage. Switch the jumpers for the inputs used by the Omega HX93A to the jumpered/closed position.
Fig. 2.3.3b - A jumper in the closed position.
Tbl. 2.3.3 - Analog channel jumper numbers. The grey portion applies only to the 16 Ch. Analog card.
Analog Channel #
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Jumper
PCB Ref. #
J4 J5 J6 J7 J8 J9 J10 J11 J12 J13 J14 J15 J16 J17 J19 J20
September 14, 2004
(800) 622-3314
OG00B.14130
www.dpstelecom.com
2.3.4 T/KdaW software configuration.
After the hardware has been installed and the jumper settings properly configured, proceed to configure the analog channels connected to the Omega HX93A from T/KdaW. For further software details, please refer to the T/KdaW manual.
1. From the main menu, select ‘Hardware Setup’.(See figure 2.3.4a)
2. Verify that the Analog card installed in the KDA is listed in the appropriate Expansion Card field.
3. Click “OK.”
Fig. 2.3.4a - The ‘Hardware Setup’ menu can be accessed from the main menu.
4. Select the ‘Base Unit’ menu by clicking on the button.
5. From the ‘Base Unit’ pop-up menu, select the ‘Expansion Analogs’ tab. (See figure 2.3.4b)
6. Enable the expansion analog(check mark the ‘Enabled” box) and enter a description (for example,. Rel. Humidity and Temperature). (See figure 2.3.4b)
Fig. 2.3.4b - The Expansion Analogs tab is only available is an analog expansion card has been selected in the
Hardware setup menu
September 14, 2004
(800) 622-3314
OG00B.14130
www.dpstelecom.com
7. Click on the ‘...’ (ellipsis) next to the number you have enabled to bring up the scaling worksheet. (See figure 2.3.4b)
8. At the ‘Native Units’ section enter the units being measured by that channel (for example, F for Fahrenheit, C for
Celsius, RH for Relative Humidity). (See figure 2.3.4c)
Native value 1 and Native value 2 correspond to the measurement range of the sensor. The Omega HX93A measures temperature in the range of -4 to 167º F (-20 to 75º C), and relative humidity from 3 to 95% RH. these are the values that are entered in the Native Value fields to establish the correct scale and the offset to convert from Volts or milliamps to meaningful units.
9a. For temperature in degrees Fahrenheit, set ‘Native Value 1’ to -4 and ‘Native Value 2’ to 167.
For temperature in degrees Celsius, set ‘Native Value 1’ to -20 and ‘Native Value 2’ to 75.
9b. For relative humidity, set ‘Native Value 1’ to 3 and ‘Native Value 2’ to 95.
Analog value 1 and analog value 2 correspond to the electrical output of the sensor in volts or milliamps. The Omega
HX93A outputs from 4 to 20mA of current to indicate the temperature and the relative humidity.
10. Set the ‘Analog Units’ to Milliamps, the ‘Analog Value 1’ to 4 and the ‘Analog Value 2’ to 20.
11. Click ‘O.K.’(See figure 2.3.4c)
Fig. 2.3.4c - Clicking on the ‘...’ next to an enabled channel brings up the scaling worksheet shown here.
12. Set the thresholds at which an alarm condition will be triggered by entering the numbers in the space provided (see figure
2.3.4b). The Omega measures temperature between -4 and +167 degrees Fahrenheit (-20 to +75 degrees Celsius) and relative humidity between 3% and 95%.
Note: The thresholds are automatically rounded up or down to the nearest measurable value.
13. Select other Analog channel parameters as necessary. (Dial Alarms, Qualifying time, etc.) Refer to the T/KdaW manual for in depth T/KdaW information.
September 14, 2004
(800) 622-3314
OG00B.14130
www.dpstelecom.com
“We protect your network like your business depends on it.”™
September 14, 2004
(800) 622-3314
www.dpstele.com
4955 E. Yale Avenue • Fresno, CA 93727
(559) 454-1600 • (800)622-3314 • (559) 454-1688 fax
OG00B.14130
www.dpstelecom.com
advertisement
Related manuals
advertisement
Table of contents
- 1 1.1 Summary of Features
- 1 1.2 Description
- 2 1.3 Shipping List
- 3 1.4 Specifications
- 4 2.1 Omega HX93A connections
- 4 2.1.1 DC to DC converter power connection
- 4 2.1.2 Determining Alarm Threshold Values
- 4 2.1.2.1 Converting Volts to meaningful measurements
- 5 2.2 NetGuardian connection
- 5 2.2.1 Power connection
- 6 2.2.2 NetGuardian communication lines
- 6 2.2.3 NetGuardian analog jumper settings
- 7 2.2.4 Software configuration
- 9 2.3 KDA connection
- 9 2.3.1 Power connection
- 9 2.3.1.1 Power connection without a DC to DC Converter
- 10 2.3.2 KDA communication lines
- 10 2.3.3 KDA analog jumper settings
- 11 2.3.4 KDA software configuration