F111 (Series 1,2,3)

In Ceiling Media Air Cleaner

APPLICATION

The F111 (Series 1,2,3) Ceiling Media Air Cleaner is a media air cleaner that uses either a single-speed or three-speed direct drive forward curve blower motor with particle filter.

When equipped with CPZ™ modules (2), gases and odors are adsorbed from the air passing through the unit. The air cleaner removes airborne particles such as dust, soot, mold spores, pollen and some cooking smoke from the air circulated through the filter.

PRODUCT DATA

FEATURES

• High Efficiency Particulate Air (HEPA) filter models are

99.97% efficient and the hospital grade particle filter models are 95% efficient at 0.3 micron particles. Both models are more efficient on particles smaller and larger. There is also a 95% ASHRAE model.

• Circulates up to 1250 cfm.

• Designed to overcome the increase in air flow resistance normally caused by filter loading.

• White or black color cover to complement the ceiling.

• CPZ™ module removes up to 95% of the space odors for up to 24 months.

• 3-Speed remote wall switch ( 3-speed models only)

• READ AND SAVE THESE

INSTRUCTIONS

The Honeywell Trademark is used under license from Honeywell International

Inc. by Air-Pure Systems.

Honeywell International Inc. makes no representations or warranties with respect to this product.

Contents

Application.........................................................................1

Features ............................................................................1

Specifications ....................................................................2

Ordering Information .........................................................2

Planning the Installation ....................................................3

Installation .........................................................................4

Operation...........................................................................7

Service ..............................................................................8

Parts List ...........................................................................9

Limited Two-Year Warranty ...............................................12

68-0198-2

F111 (SERIES 1,2,3) IN CEILING MEDIA AIR CLEANER

SPECIFICATIONS

IMPORTANT

The specifications given in this publication do not include normal manufacturing tolerances. Therefore, this unit may not exactly match the listed specifications. Also, this product is tested and calibrated under closely controlled conditions, and some minor differences in performance can be expected if those conditions are changed.

Models: Refer to Table 1 for model descriptions.

Grill Color: White (standard) or Black (add ‘B’ to end of model number).

Blower/Motor: Single speed (standard) or three speed ( add

‘-3S’ to the end of the model number) direct drive forward curve.

Dimensions: See Fig. 1 for dimensions.

Model

F111A1253W-3S

F111A1063W-3S

F111C1073W-3S

F111C1003W-3S

F111C1012W-3S

F111A2253W-3S

F111A2007W-3S

F111C2073W-3S

F111C2003W-3S

F111C1053W-3S

F111C1061 b

Voltage

120 Vac, 60 Hz, 8.5A

120 Vac, 60 Hz, 7.2A

120 Vac, 60 Hz, 7.5A

120 Vac, 60 Hz, 7.0A

120 Vac, 60 Hz, 8.0A

230 Vac, 50 Hz, 4.2A

230 Vac, 50 Hz, 3.5A

230 Vac, 50 Hz, 4.0A

230 Vac, 50 Hz, 3.2A

230 Vac, 50 Hz, 3.5A

Table 1. F111 (Series 3) Description.

Particulates at

0.3 Micron

(DOP Test)

Efficiency

V.O.C./Odor

(Most Gases/

Odors First Pass

Average)

Gas, V.O.C. and

Odor Control

Modules (2)

95% ASHRAE

99.97% HEPA

N/A

N/A

N/A

N/A

Air Volume a in cfm

(m

3

/hr)

1250 (2120)

950 (1610)

95% ASHRAE

99.97% HEPA

85%

85%

95% at 0.3 micron 85%

95% ASHRAE N/A

CPZ™ modules 1150 (1950)

CPZ™ modules 825 (1400)

CPZ™ modules 1125 (1910)

N/A 1125 (1910)

99.97% HEPA

95% ASHRAE

N/A

85%

99.97% HEPA 85%

95% at 0.3 micron 85%

N/A 900 (1530)

CPZ™ modules 1025 (1740)

CPZ™ modules 825 (1400)

CPZ™ modules 950 (1610) same as F111C1012B-3S

N/A = not applicable.

a

For single-speed and three-speed systems (set to High) b

F111C1061 has a new model number : F111C1012B

To Order F111 with a Black Grill

Replace the ‘W’ with a ‘B’ to any model number in Table 1.

ORDERING INFORMATION

If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:

1.

Your local Honeywell Commercial Air Products Distributor.

2. Air-Pure Systems

16873 Fish Point Rd. SE

Prior Lake, MN 55372

www.cleanairfacility.com

Phone: (800) 998-1919

Fax: (800) 221-3248

68-0198-2 Release 5-09 2

F111 (SERIES 1,2,3) IN CEILING MEDIA AIR CLEANER

Model

Table 2. F111 Air Volume Specifications for 3 Speed Models (Series 3).

Voltage

F111A1253W-3S 120 Vac, 60 Hz, 8.5A

F111A1063W-3S 120 Vac, 60 Hz, 7.2A

F111C1073W-3S 120 Vac, 60 Hz, 7.5A

F111C1003W-3S 120 Vac, 60 Hz, 7.0A

F111C1012W-3S 120 Vac, 60 Hz, 8.0A

F111A2253W-3S 230 Vac, 50 Hz, 4.2A

F111A2007W-3S 230 Vac, 50 Hz, 3.5A

F111C2073W-3S 230 Vac, 50 Hz, 4.0A

F111C2003W-3S 230 Vac, 50 Hz, 3.2A

F111C1053W-3S 230 Vac, 50 Hz, 3.5A

.

a

Same for Single Speed Models (Series 1 & 2).

Particulates at

0.3 Micron

(DOP Test)

95% ASHRAE

99.97% HEPA

Gas, V.O.C. and

Odor Control

Modules (2)

N/A

N/A

High a in cfm

(m

3

/hr)

Medium in cfm

(m

3

/hr)

Low in cfm

(m

3

/hr)

1250 (2120) 800 (1360) 450 (760)

950 (1610) 775 (1310) 450 (760)

95% ASHRAE

99.97% HEPA

CPZ™ modules 1150 (1950) 825 (1400) 450 (760)

CPZ™ modules 825 (1400) 700 (1190) 450 (760)

95% at 0.3 micron CPZ™ modules 1125 (1910) 825 (1400) 450 (760)

95% ASHRAE N/A 1125 (1910) 700 (1190) 475 (810)

99.97% HEPA

95% ASHRAE

N/A 900 (1530) 600 (1020) 400 (680)

CPZ™ modules 1025 (1740) 675 (1150) 450 (760)

99.97% HEPA CPZ™ modules 825 (1400) 550 (930) 375 (640)

95% at 0.3 micron CPZ™ modules 950 (1610) 625 (1060) 425 (720)

TOP VIEW

Accessories:

Black Color Grill

Remote 3-Speed Wall Switch

3/8 X 16

INTERNAL

THREAD (4)

Replacement Parts See Parts List, Table 5.

PLANNING THE INSTALLATION

48 (1219)

46-3/4 (1187)

POWER CONNECTION

POINT

17-1/4

(438)

24 (610)

22-1/2 (572)

The number of F111 (series 1,2,3) air cleaners that are needed is determined by taking into account the number of occupants and the volume of the space. Type of contamination, outdoor air quality and use of the area are also factors. Refer to Table

3 for general guidelines when determining how many air cleaners are needed.

4-1/2

(114)

Fig. 1. Approximate dimensions of F111

(Series 1,2,3) in in. (mm).

CEILING

LINE

M11996A

EXAMPLE: One air cleaner can provide 2.5 air changes per hour in a 24,000 cubic feet (720 cubic meters) no smoking area. Table 3 suggests two air cleaners for a 24,000 cubic feet area because most areas have contaminants that require more units to

provide quality air.

Installation Weight:

Approximately 115 lb to 155 lb (kg) depending on the filter configuration. Refer to Table 3.

Table 3. Sorbent Module Weight.

Media

CPZ™ modules (2) 43 (20)

Weight in lb (kg)

Sound Level at 3.3 ft (1m):

Low speed: 53 dBA (3 speed models only).

Medium speed: 57 dBA (3 speed models only)

High speed: 61 dBA.

Grille Type: Perforated metal.

Mounting: Recesses into opening on the ceiling.

Approvals:

Underwriters Laboratories Inc.: Listed.

Canadian Standards Association: Listed.

If any questions should arise concerning determining the number of air cleaners needed for an area, consult your distributor or local Honeywell Commercial Air Cleaner

Distributor.

Table 4. Determining the Minimum Number of

Air Cleaners Needed for a Space.

Space Volume

(L x W x H) in Cubic

Feet (Cubic Meter)

12000 to 18000

(360 to 540)

18001 to 35000

(540 to 1050)

Number of

Persons Present

30 to 60

Minimum

Number of Air

Cleaners

1

61 to 90 2

3 68-0198-2

F111 (SERIES 1,2,3) IN CEILING MEDIA AIR CLEANER

Space Volume

(L x W x H) in Cubic

Feet (Cubic Meter)

35001 to 51000

(1050 to 1530)

51001 to 65000

(1530 to 1950)

65001 to 80000

(1950 to 2400)

80001 to 95000

(2400 to 2850)

Number of

Persons Present

91 to 120

Minimum

Number of Air

Cleaners

3

121 to 180

181 to 240

241 to 300

4

5

6

CLEANING FOOTPRINT

F111

(SERIES

11000)

1

2

CORRECT INCORRECT

CEILING

FLOOR

WARNING

TO REDUCE THE RISK OF FIRE,ELECTRICAL

SHOCK, OR INJURY TO PERSONS,OBSERVE THE

FOLLOWING:

1.

Installation Work And Electrical Wiring Must Be Done

By Qualified Person(s) In Accordance With All Applicable Codes And Standard, Including Fire Rated Constructions.

2.

When Cutting Or Drilling Into The Wall Or Ceiling, Do

Not Damage Electrical Wiring And Other Hidden Utilities.

3.

Never Place A Switch Where It Can Be Reached From

A Tub Or Shower.

4.

Use This Unit Only In The Manner Intended By The

Manufacturer. If You have Questions, Contact The Manufacturer.

5.

Before Servicing Or Cleaning Unit, Switch Power Off At

Service Panel And Lock Service Panel To Prevent

Power From Being Switched on Accidentally.

6.

If This Unit Is To Be Installed Over A Tub Or Shower, It

Must Be Marked As appropriate For The Application and be connected to a GFCI (Ground Fault Circuit Interrupter) - protected branch circuit.

Choose Location

Choosing the correct location for the air cleaner affects the overall performance of the unit. The bidirectional airflow pattern must flow into the longest reaches of the zone being cleaned. See Fig. 2

NOTE: The F111 Has Not Been Investigated

For Use In Fire Resistance Rated

Construction.

Fig. 2. Correct positioning of the air cleaner for optimum cleaning.

The air cleaner is designed to be suspended centrally in a space and mounted into or on a ceiling. The cleaning footprint of the air cleaner is rectangular with air patterns that move clean air to the corners of the area while drawing contaminated air up from the center of the area. See Fig. 2.

When multiple air cleaners are installed, the allotted areas to be cleaned should be equal. The air throw in one direction is approximately 55 ft (17m). Air velocity at 90 ft per minute

(27m per minute) is considered end of throw.

M12652A

IMPORTANT

Never hang the air cleaner higher than 16 ft (5m) above the floor.

INSTALLATION

WARNING

Explosion Hazard Possible.

Can cause personal injury or equipment damage.

Do not install or use the F111 (series 11000) air cleaner where there is any danger of gas, vapor or dust explosion.

IMPORTANT

This air cleaner has not been investigated for use in the ceilings of fire-resistant assemblies.

CAUTION

Electrical Hazard.

Can cause personal injury or equipment damage.

Turn off power before installing or servicing the air cleaner.

IMPORTANT

Stand on a stable platform when working with the air cleaner.

When Installing this Product…

1.

Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.

2.

Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.

3.

Installer must be a trained, experienced service technician.

4.

After installation is complete, check out product operation as provided in these instructions.

Unpack the Air Cleaner

Check that all components are included. The unit consists of:

• cabinet and grille/door assembly,

• media modules,

• literature.

68-0198-2 Revised 5-09 4

F111 (SERIES 1,2,3) IN CEILING MEDIA AIR CLEANER

• latches (2)

• 3-speed switch module ( 3 Series only)

Make Opening (if Mounting in a Drop Ceiling)

1.

Size the opening to fit the air cleaner cabinet as closely as possible.

2.

Frame the opening to provide adequate support for the cabinet. The cabinet must fit snugly in the opening; allow no more than 1/4 in. (6 mm) from the opening to each side of the cabinet.

3.

Cover the framing and any unused portion of the opening with wallboard, plywood, or other material and finish to match the ceiling.

Electrical Hookup

All wiring must comply with applicable codes and ordinances.

The power source must agree with the model type: 120V,

60 Hz or 230V, 50 Hz.

1.

Locate the prepunched hole in the side of the cabinet.

2.

Remove the air cleaner lid.

3.

For Series 1 and 2 only.Remove the connection box cover plate in the center cavity of the air cleaner.

4.

For Series 3 only. Remove the connection box cover plate on the bottom, underneath the tray.

5.

Refer to Fig. 3 and 4 for typical electrical diagrams.

WARNING

Risk of Fire or Electric Shock.

Can cause personal injury or equipment damage.

Use only Honeywell 190097C Remote Speed Switch

(3-speed models only) to regulate air cleaner speed.

Using a different speed switch may void the warranty.

IMPORTANT

• Be sure the air cleaner is grounded for correct operation and safety.

• Canadian installation: NEVER install in ceilings with thermal insulation value greater than R-40.

EXTERNAL

WIRING BY

INSTALLER

FACTORY WIRING

BLACK

BROWN

MOTOR

WHITE

GREEN

M12657

Fig. 3. Typical F111 (series 1 & 2) 120V, 60 Hz or

208/230V, 50/60 Hz wiring diagram.

FACTORY WIRING

BLACK BLACK

EXTERNAL

WIRING BY

INSTALLER

BROWN

MOTOR

RED

BLUE

VIOLET

WHITE

GREEN

A100002

Fig. 4. Typical F111 Series 3 only 120V, 60 Hz or

230V, 50 Hz wiring diagram.

Mount Air Cleaner Cabinet

The air cleaner can be mounted in a drop ceiling system or hung in an open area. Both mounting methods require the air cleaner to be level and positioned facing downward for correct operation.

1.

Remove the door/grille from the carton and set it aside.

2.

Remove all filters.

3.

Fit the cabinet into the prepared ceiling opening or position on the ceiling.

4.

Use the four 3/8 x 16T internal nuts (one at each corner) to fasten the cabinet to a structural support (bar joist, concrete slab or timber framing). See Fig. 5.

NOTES:

• All external hardware is furnished by the installer.

• When using the suspension system of mounting, be sure to include a means for leveling adjustment after installation.

• Never rest the air cleaner on the T-bar.

5.

Level the air cleaner.

6.

Turn the air cleaner power on and check for proper operation for 2 to 3 minutes. There should be a smooth, powerful blower sound and air discharging from both ends of the air cleaner.

7.

Turn off the power.

8.

Install the particle filter. Note airflow direction arrows if present. Install the filter with the direction arrow pointing towards the motor.

9.

For Series 1 and 2 only. Fasten the filter tabs. Be sure there is a snapping sound when fastened. The tabs are commercial Velcro and require more force than lightly pushing them together.

10.

For Series 3 only. Lock and secure the particle filter into place by closing both latches.

5 68-0198-2

F111 (SERIES 1,2,3) IN CEILING MEDIA AIR CLEANER

TOP OF METAL CABINET

THREADED

ROD

JAM

NUT

CHAIN

EYEBOLT

JAM NUT

3/8 IN. X 16T

OR USING OPTIONAL "Z" BRACKETS

TOP OF METAL CABINET

HEX BOLT

LOCK

WASHER

CAUTION

• This installation to be performed only by a qualified installer.

• All wiring to comply with local electrical codes.

• Disconnect power to air cleaner at fuse or breaker before beginning work. Failure to do so can result in shock hazard endangering equipment and personal safety of installer.

• Only one air cleaner can be connected to a remote switch

1.

Disconnect power to air cleaner.

2.

Mount 4” x 4” outlet box at desired remote location.

3.

Attach 3/4” extension ring to outlet box.

4.

Run five conductor, color-coded, 18-gauge wires from the remote switch location to the air cleaner.

5.

Use three wire nuts to connect three color-coded, lead wires on the remote switch to three color-coded wires from the air cleaner. (Red, Blue, Violet)

6.

Use one wire nut to connect white color-coded, lead wire from the air cleaner to single color-coded wire from the power supply. (White)

BOTTOM FLANGE AGAINST

UNDERSIDE OF TEES

"Z" BRACKET (4)

NOTE:

FASTEN SECURELY TO STRUCTURAL

SUPPORT SYSTEM, I.E. BAR JOIST,

CONCRETE SLAB OR TIMBER FRAMING.

CEILING

TEE

BLACK

BOTTOM VIEW OF

UNIT WITHOUT

LID ASSEMBLY

M10892

Fig. 5. Fasten cabinet to a structural support.

IMPORTANT

Do not touch the pleated filter media. Handle only the filter frame to prevent damage to the filter media.

11.

Remove CPZ™ sorbent modules (select models) from their packaging and install one module into each cavity.

12.

For Series 1 only. Be sure the fastener tabs are facing downward and fasten them.

13.

For Series 2 and 3 only. Be sure both catches are turned down and filter rests firmly on catches.

14.

Install the prefilter in the air cleaner lid. Position the metal screen mesh so it is facing upward when the lid is closed.

Remote 3 Speed Wall Switch (3 Speed Models only)

The 190097C Remote Wall Switch Assembly allows control of the F111 model air cleaners from a a location separate from the air cleaner. The assembly includes a remote switch with an outlet box cover, outlet box, extension ring, and a wire harness. Wiring to connect the remote switch and air cleaner must be furnished separately.

A100001

Fig. 6. Wiring 3-Speed Remote Switch

7.

Connect the ground wire from the power supply to a ground stud of the outlet box.(Green)

8.

Connect the ground wire from the air cleaner to the ground stud of the outlet box.(Green)

9.

Use one wire nut to connect the black color-coded, lead wire on the remote switch to the black color-coded wire from the power supply.

10.

Fold wires into box and mount remote switch on outlet box. Leave switch in OFF position.

11.

On the air cleaner remove two screws on wiring compartment cover and open

12.

Run five conductor, color coded, 18 gauge wires from the remote switch through the air cleaner access opening into the wiring compartment. Strip ends of remote switch lead wires

13.

Connect three wires on air cleaner to remote switch lead wires with wire nuts following color code used at remote switch. (Red, Blue, Violet)

68-0198-2 Revised 5-09 6

F111 (SERIES 1,2,3) IN CEILING MEDIA AIR CLEANER

14.

Connect one wire on air cleaner to power supply wire with a wire nut following color code used at remote switch. (White)

15.

Connect the ground wire from the remote switch to a ground stud of the wiring compartment cover.(Green)

16.

Fold wires into wiring compartment. Replace wiring compartment cover.

17.

Turn on power to air cleaner at fuse or breaker.

18.

Check operation by turning air cleaner at HIGH,

MEDIUM, and LOW. Note that only the remote switch will operate the air cleaner.

Lid Assembly

The F111 lid is held in place by two separable hinges and two spring loaded plungers. To install the spring loaded plungers on the lid follow these steps:

1.

Pull the plunger back and twist a quarter turn to reveal the wrench flat on the body of the spring loaded plunger

(see Fig 7.)

2.

Turn the threaded barrel out of the spring plunger.

3.

Insert the threaded barrel through the hole in the lid and turn the spring loaded plunger onto it.

4.

Tighten the assembly with wrenches.

5.

Repeat steps 1 through 4 for the second plunger.

Removing /Replacing the Lid

IMPORTANT

The lid is heavy. Make sure that it is supported before removing.

To remove the lid, swing it into the open position. Slide safety catch to off position. Move the lid to the side to disengage the hinge pins. Reverse the procedure to replace the lid. Make sure safety catch is in safe position.

OPERATION

The F111 (series 1,2,3) in Ceiling Media Air Cleaner has been engineered to improve indoor air quality for commercial and industrial applications. The filters are the most practical and effective filtering system for removing atmospheric dust, pollens, bacteria, viruses, mold spores, smoke, fumes, mists and aerosols. Refer to Fig. 8.

WRENCH

FLAT

WRENCH FLAT

THREADED

BARREL

SPRING

LOADED

PLUNGER

M11994

Fig. 7. Lid assembly.

Opening/Closing the Lid

To open the lid, pull the spring loaded plungers back to disengage the plunger. Carefully swing the lid open on the hinges while supporting the filter and/or adsorbent modules as required. To close, swing the lid into the closed position and engage the plungers.

CPZ™

SORBENT

FILTER

MODULE

BLOWER

MOTOR

AIR VENTS CPZ™

SORBENT

FILTER

MODULE

CEILING LINE

CLEAN AIR

DISCHARGE

AIR IN

INTAKE

PARTICLE FILTER

PREFILTER

CEILING LINE

AIR IN

CLEAN AIR

DISCHARGE

M12651A

Fig. 8. F111 (series 1,2,3) air cleaner operation.

The air cleaner is either operating (power on) or off (power off). There are no other operational options available. Even when the area is unoccupied, the air cleaner can be operated continuously to prevent buildup of airborne contaminants.

Operate the air cleaner only when the area is occupied when specific activities produce contaminants.

The CPZ™ sorbent module has the ability to collect and hold gas-phase compounds and vapors typically found in commercial and light industrial facilities. These gases and vapors frequently appear as odors that, at times, can be annoying and irritating. The modules become saturated after collecting 25% to 50% of their weight in gaseous odors. The quantity of CPZ™ material provides adequate dwell time to ensure up to 95% collection efficiency in the first pass. This also provides a long maintenance-free service life.

The minimum recommended air exchange rate is 2.5 times per hour. In a heavily contaminated area, up to 15 air exchanges per hour can be necessary. The factors that determine what the rate of air exchange should be are:

• generation rates of the various pollutants;

• concentration level of the pollutants;

• desired contamination reduction level.

Airborne contaminants will always be present in the air where contaminant generations take place. Air cleaning systems and ventilators do not eliminate airborne contaminants, they reduce the excessive accumulation of the contaminants. To eliminate the contamination, the source of contamination must be removed.

7 68-0198-2

F111 (SERIES 1,2,3) IN CEILING MEDIA AIR CLEANER

Local, Federal and professional ventilation engineering standards and codes prescribe minimum ventilation rates to dilute air contamination in specific applications. The ventilation rates usually assume the injection of outdoor air measured as air exchange rate. The use of the F111 (series

1,2,3) air cleaner to comply with ventilation requirements is an acceptable alternative to ventilation with outdoor air. However, at least 20% of a specified ventilation rate or code must be derived from outdoor air. The F111 (series 1,2,3) air cleaner filtered and recirculated air can be the remaining 80%.

SERVICE

CAUTION

Electrical Hazard.

Can cause personal injury or equipment damage.

Turn off power before installing or servicing the air cleaner.

IMPORTANT

Be sure to change filters as recommended to prevent reduced airflow in the air cleaner.Stand on a stable platform when working with the air cleaner.

The useful life of the CPZ™ sorbent modules may vary from 4 to 24 months, depending on the application. In most applications, the sorbent media life ranges from 12 to 18 months. The particle filter life ranges from 6 to 24 months with

12 to 24 months as an average. The modules and filters need to be changed more frequently in facilities that operate 24 hours a day.

Prefilter

The disposable prefilter collects large dust particulates and lint- type airborne fibers. Check the filter every two weeks to determine the replacement frequency:

1.

Slowly open the lid, supporting the lid so the filters do not fall out.

2.

Remove the dirty prefilter.

3.

Install the new prefilter in the air cleaner lid. Position the metal screen mesh so it is facing upward when the lid is closed.

4.

Close and latch the lid.

Particle Filter

The particle filter collects particulates that pass through the prefilter. The filter life is typically from 1 to 2 years. There is decreased air quality and a pulsing sound when the filter is filled with contaminants. The filter must be replaced when the pulsing sound is noticed.

NOTE: The filter must be replaced. Washing, vacuuming or reverse air blasting does not clean it.

1.

Slowly open lid, supporting it so the filters do not fall out.

2.

Open the securing strips and with both hands. Slide the filter toward you.

3.

Place spent filter in a plastic trash bag and dispose of properly.

4.

Inspect the motor brackets for loose fasteners and tighten as necessary.

5.

Install the new filter noting the direction of airflow arrow.

6.

For Series 1 and 2 only. Fasten the filter tabs. Be sure there is a snapping sound when they are fastened. The tabs are commercial Velcro and require more force to fasten.

7.

For Series 3 only. Lock and secure the particle filter into place by closing both latches

IMPORTANT

Do not touch the pleated filter media. Handle only the filter frame to prevent damage to the filter media.

8.

Close and latch the lid.

CPZ™ Adsorbent Module

The CPZ™ adsorbent module is used to collect gases, vapors, odors and volatile organic compounds (V.O.C.) from the air that passes through the air cleaner. Adsorbents collect and hold 25% to 50% of their weight in odorous gases and vapors. The impurities are collected until the adsorbents reach saturation. At saturation, the adsorbents emit a continuous strong pungent odor. If the air cleaner is turned off for 8 to 10 hours, there will a temporary odor when it is turned back on. If the odor persists for 30 minutes, it is time to replace the filters.

NOTE: When tobacco smoke is a contaminant, both the particle filter and the adsorbent filter will need to be serviced at the same time.

1.

Slowly open the lid, supporting the lid so the filters do not fall out.

2.

For Series 1 only. Support the adsorbent module with one hand and release the fastener.

3.

For Series 2 and 3. Support the adsorbent module with one hand and turn open the catches.

4.

Use two hands and slide the filter from the housing.

IMPORTANT

The module weighs about 26 lb (12 kg) and can be hard to handle.

5.

Place the spent module in a plastic trash bag and dispose of properly.

6.

Remove CPZ™ sorbent modules from their packaging and install.

7.

For Series 1 only. Be sure the fastener tabs are facing downward and fasten them.

8.

For Series 2 and 3 only. Be sure both catches are turned down and filter rests firmly on catches.

9.

Install 1 startup-filter in each end of grill.

10.

Close and latch the lid.

On initial startup, a small amount of dust can blow from the air cleaner. This is normal and stops a few minutes after startup.

The startup-filters will catch all the dust. The startup-filters are placed in the two exit outlets on the grill. After running the unit for 5 minutes, turn off the unit. Remove and discard the two start-up filters.

68-0198-2 Revised 5-09 8

F111 (SERIES 1,2,3) IN CEILING MEDIA AIR CLEANER

PARTS LIST

Refer to Fig. 9 and Table 5 for replacement part information.

Fig.

Reference No.

1

2

3

4

5

Table 5. Replacement Parts.

Description

CPZ™ sorbent module (requires 2)—used with only

95% HEPA or 95% ASHRAE particle filters

Charcoal sorbent module (requires 2)—used with only

95% HEPA or 95% ASHRAE particle filters

Zeolite sorbent module (requires 2)—used with only

95% HEPA or 95% ASHRAE particle filters

Permanganate sorbent module (requires 2)—used with only 95% HEPA or 95% ASHRAE particle filters

Blower wheel, Series 1

Blower wheel, Series 2, and 3

Motor capacitor; 120V, 60 Hz, Series 1,2, and 3

Motor capacitor; 208/230V, 50/60 Hz, Series 1, 2

Motor capacitor; 230V, 50 Hz, Series 3

Motor; 120 V, 60 Hz, Series 1

Motor; 208/230V, 50/60 Hz, Series 1

Motor; 120 V, 60 Hz, Series 2

Motor; 208/230V, 50/60 Hz, Series 2

Motor; 120 V, 3-Speed, 60 Hz, Series 3

Motor; 230V, 3-Speed, 50Hz, Series 3

99.97% HEPA media filter, 3”, Series 1 and 2

99.97% HEPA media filter, 4.5”, Series 3

95% hospital grade filter

6

7

95% ASHRAE particle filter

Prefilter (disposable)

Lid assembly with hinges and latches in White Color

OPTIONAL Parts not shown in Fig. 9.

Remote Wall 3-Speed Switch, Series 3

Motor mount bracket

Motor maintenance grommet set

Snap-loc Tabs; Series 1

Snap-loc Tabs; Series 2

Z Sidemount Bracket Kit

Spring Loaded Plunger

Lid assembly with hinges and latches in Black Color

Pack Qty

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

2

1

1

4

3

1

1

1

Order Number

32004078-001

32004078-002

32004078-003

32004078-004

32000236

32002285

32000265

32000549

32000265

32000270

32000263

32002415-001

32002415-002

32002415-004

32002415-005

32000204-001

32000204-002

32000203

50004739-001

32002307

32002308-002

190097C

32000260

32000261

32000262-001

32000262-002

32002353

32002278

32002308-003

NOTE: All replacement filters must be provided by Air-Pure Systems to maintain U.L. Certification and Warranty.

9 68-0198-2

F111 (SERIES 1,2,3) IN CEILING MEDIA AIR CLEANER

CABINET

ASSEMBLY

1

SORBENT MEDIA MODULE

(2 REQUIRED)

2 BLOWER WHEEL

3 MOTOR CAPACITOR

4 MOTOR

5 MEDIA FILTER

6

PREFILTER

7

LID ASSEMBLY WITH

HINGES AND LATCHES

M11995E

Fig. 9. Exploded view of F111 (series 1,2,3) in Ceiling Media Air Cleaner components.

68-0198-2 Revised 5-09 10

NOTES

F111 (SERIES 1,2,3) IN CEILING MEDIA AIR CLEANER

11 68-0198-2

LIMITED TWO-YEAR WARRANTY

Air-Pure Systems warrants its air cleaner products to be free from defects in workmanship or materials under normal use and service, for a period of two (2) years from the date of purchase by the original end-user. If at anytime during the warranty period the product is defective or malfunctions, Air-Pure Systems, through the distributor or dealer, from which the product was purchased, or through an authorized warranty repair station, shall at Air-Pure Systems option, replace or repair the defective product or component.

This warranty does not cover removal or installation costs. This warranty shall not apply if it is shown that the defect or malfunction was caused by damage which occurred during handling or shipment, improper electrical connections, improper use of the product or abuse.

Air-Pure Systems sole responsibility shall be to repair or replace the product within the terms stated above. AIR-PURE SYSTEMS SHALL NOT

BE LIABLE FOR ANY LOSS OR DAMAGE OF ANY KIND, INCLUDING ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING,

DIRECTLY OR INDIRECTLY, FROM ANY BREACH OF WARRANTY, EXPRESS OR IMPLIED, OR ANY OTHER FAILURE OF THIS PROD-

UCT. (Some states do not allow the exclusion or limitation of incidental or consequential damages, so this limitation may not apply to you.) THE

WARRANTIES SET FORTH HEREIN ARE EXCLUSIVE AND AIR-PURE SYSTEMS’ EXPRESSLY DISCLAIMS ALL OTHER WARRANTIES,

WHETHER WRITTEN OR ORAL, IMPLIED OR STATUTORY, INCLUDING BUT NOT LIMITED TO ANY WARRANTIES OF MERCHANTABIL-

ITY, WORKMANSHIP, OR FITNESS FOR A PARTICULAR USE.

This warranty gives you specific legal rights and you may have other rights which vary from state to state.

How to make a warranty claim or have questions answered:

Should you have a warranty claim or questions about the warranty policy, contact the distributor or dealer from which you purchased the product or the authorized warranty repair stations nearest your location.

NOTE: Do not return any products or parts to the factory without a factory issued “Returned Warranty Goods Label” issued by Air Pure Systems.

In the event you or other persons, have any questions concerning the use and care of this product or this warranty please call or write the factory.

Air-Pure Systems

16873 Fish Point Rd. SE

Prior Lake, MN 55372-1714

Phone: (800) 998-1919

Fax: (800) 221-3248

Air-Pure Systems

16873 Fish Point Rd. SE

Prior Lake, MN 55372-1714

Phone (800) 998-1919

Fax: (800) 221-3248

68-0198-2 Revised 5-09 www.cleanairfacility.com

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

advertisement