Honeywell HE225A Product data

Add to my manuals
12 Pages

advertisement

Honeywell HE225A Product data | Manualzz

HE225A,B and HE265A,B

Bypass Flow-Through

Humidifier

whole-house air quality system

APPLICATION

The Enviacaire Elite HE225A,B and HE265A,B Bypass Flowthrough Humidifiers use the warm air furnace blower to provide humidification for the whole house.

PRODUCT DATA

FEATURES/BENEFITS

• Antimicrobial coating on pad prevents the surface growth and migration of bacteria, mold, fungus and algae on the humidifier pad.

• Bold new look with blue and white styling.

• Proven technology used for high performance humidification and enhanced comfort.

• Preassembled for quicker installation.

• Small footprint, light weight and reversible components allow easy mounting on either warm air supply or return air duct of any forced air furnace.

• Interior components designed for quick maintenance and service.

• Includes easy-to-use humidity control that mounts on the wall or duct for more flexible installation.

• Continuous flushing reduces the frequency of maintenance in a hard water installation.

• AIRWATCH™ Indicator can be installed to remind homeowner to change humidifier pad.

• Five-year warranty.

® U.S. Registered Trademark

Copyright © 2000 Honeywell • All Rights Reserved 68-0244

HE225A,B AND HE265A,B BYPASS FLOW-THROUGH HUMIDIFIER

SPECIFICATIONS

Capacity:

At 120

°

F (49

°

C) plenum temperature and 0.20 static pressure drop across supply and return:

HE225A,B: 12 gallons per day (gpd) or 46 liters per day (lpd).

HE265A,B: 17 gallons per day (gpd) or 65 liters per day (lpd).

Electrical Ratings:

24 Vac, 60 Hz, 0.5A.

Humidified Area:

See Table 1.

House Description

Loose

Average

Tight

Humidifier Pad Dimensions:

See Table 2.

Plenum Opening Dimensions (Height x Width):

See Table 3.

Summer Shut-off Damper Dimensions (Height x Width):

See Table 4.

Bypass Duct Opening (Diameter):

6 in. (152 mm).

Dimensions:

Refer to Fig. 1 and 2.

Table 1. Size Of Area That Can Be Humidified.

Air Changes Per Hour

Two

One

One-half

Drain Connection:

1/2 in. (13 mm) I.D. plastic hose connected directly to drain fitting on unit.

HE225 Area (Up To)

Sq ft Sq m

750

1,500

3,000

70

140

280

HE265 Area (Up To)

Sq ft

1,000

2,000

4,000

Sq m

93

186

372

Table 2. Dimensions Of Humidifier Pads In In. (mm).

Model

HE225

HE265

Height

13 (330)

Width

9-13/16 (249) 9-1/2 (241)

10 (254)

Depth

1-1/2 (38)

1-1/2 (38)

Table 3. Dimensions Of Plenum Opening In In. (mm).

Model

HE225

HE265

Height

9-7/16 (241)

12-5/8 (321)

Width

9-5/16 (238)

9-3/4 (248)

Table 4. Dimensions Of Summer Shut-off Damper

In In. (mm).

Model

HE225

HE265

Height

9-3/16 (234)

12-3/8 (314)

Width

8-7/8 (226)

9-5/16 (236)

ORDERING INFORMATION

When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the

TRADELINE® Catalog or price sheets for complete ordering number.

If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:

1.

Your local Home and Building Control Sales Office (check white pages of your phone directory).

2.

Home and Building Control Customer Relations

Honeywell, 1985 Douglas Drive North, MN10-1461

Golden Valley, Minnesota 55422-4386 1-800-468-1502

In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarbouorgh, Ontario M1V 4Z9.

International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,

Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.

68-0244 2

9-1/8 (232)

12 (3

05)

13-9/16

(345)

6 (152)

DIAMETER

M14818

Fig. 1. Dimensions of HE225A,B in in. (mm).

9-1/4 (235)

13-9/16 (345)

11-7

/16 (29

0)

12 (305)

HE225A,B AND HE265A,B BYPASS FLOW-THROUGH HUMIDIFIER

12-7/16

(316)

15-5/16

(390)

16-3/4

(425)

6 (152)

DIAMETER

M14819

Fig. 2. Dimensions of HE265A,B in in. (mm).

Approvals:

Underwriters Laboratories Inc. Listing: 56 BL.

Canadian Underwriters Laboratories Inc. Listing: 56 BL.

Standard:

Air Conditioning and Refrigeration Institute Tested:

Standard 610.

Models:

HE225A TRADELINE® and HE265A TRADELINE®

Bypass Flow-through Humidifier package includes humidifier pad, mounting template, self-piercing saddle valve, 24 Vac transformer, H8908B Convertible

Humidity Control.

HE225B TRADELINE® and HE265B TRADELINE®

Bypass Flow-through Humidifier package includes humidifier pad, mounting template, self-piercing saddle valve, 24 Vac transformer, H1008A Automatic Humidity

Control with HumidiCalc™ Software.

Accessories:

Current Sensor Relay, part no. 32001754-001.

C7089H Outdoor Temperature Sensor.

H8908B Convertible Humidity Control.

H1008A Automatic Humidity Control with HumidiCalc+™

Software (software calculates dewpoint to prevent moisture condensation).

HC22E Antimicrobial Humidifier Pad (HE225A,B only).

HC26E Antimicrobial Humidifier Pad (HE265 A,B only).

HumidiCalc+™ Humidifier Sizing Software (software calculates required humidifier capacity for application).

PC8900 Control.

S688 Sail Switch.

INSTALLATION

WARNING

Hazardous Voltage.

Can cause personal injury or equipment damage.

Do not cut or drill into any air conditioning line or electrical accessory.

CAUTION

Freezing Water, Flooding or

Static Pressure Hazard.

Can cause water damage to home or permanent equipment damage.

• The humidifier must be located where the ambient temperature is above 32

°

F and below 160

°

F (0

°

C and 71

°

C).

• Be sure supply plenum static pressure is no greater than 0.3 in. w.c. and water pressure is no greater than 125 psi.

IMPORTANT

To assure optimal product performance, be sure the template is level before marking location.

1. Determine the best location for the humidifier and draw a level line on the plenum. See Fig. 3.

68-0244

3

HE225A,B AND HE265A,B BYPASS FLOW-THROUGH HUMIDIFIER

HORIZONTAL

11. Reinstall the humidifier pad assembly in the humidifier housing.

NOTE: Be sure the water feed tube is not pinched or kinked.

12. Hinge the cover in place and secure with the thumbscrew located at the bottom of the cover.

WATER

FEED NOZZLE

HIGHBOY

DOWN

FLO

LOWBOY

HUMIDIFIER

PAD ASSEMBLY

FRAME

M12248C

Fig. 3. Typical humidifier installation locations.

COVER

SIDEWALL

IMPORTANT

Mount the humidifier at least 3 in. (76 mm) above the furnace jacket to allow adequate space for the solenoid valve and drain line. Check that there is adequate space above the humidifier to remove and install the humidifier cover.

2. Tape the template in position and trace around the template.

3. Remove the template and carefully cut the rectangular opening.

4. Disassemble the humidifier; remove the cover and take out the humidifier pad assembly. See Fig. 4.

NOTE: Sidewalls are interchangeable for either left or right by-pass installation. To change direction, remove the screws holding each sidewall, switch sidewall locations and reinstall the screws.

5. Position the humidifier housing in the opening (be sure it is level), so the locking tabs are in place on the lower sheet metal edge of the opening.

6. Secure the humidifier housing to the opening at the top and bottom using sheet metal screws.

7. Locate the other plenum and cut an opening for a 6 in.

(152 mm) collar.

8. Install the 6 in. (152 mm) collar.

NOTE: Be sure to install a duct damper for summer shutoff on systems with air conditioning.

9. Install a 6 in. (152 mm) diameter duct from the collar to the humidifier.

NOTE: Some installations require a 90

°

elbow attachment to the collar.

10. Seal the duct connections with duct tape.

NOTE: To avoid sagging and stress on the humidifier, add support when ducting is longer than

4 ft (120 cm).

HUMIDIFIER

HOUSING

BY-PASS SIDEWALL

WATER

FEED TUBE

Fig. 4. Humidifier components.

M14672

WIRING THE HUMIDIFIER

CAUTION

Hazardous Voltage.

Can cause personal injury or equipment damage.

• Disconnect the power supply before installing or servicing.

• On multispeed blower applications, do not wire the high voltage side of the transformer to the same power source that services the furnace blower.

Premature transformer burnout may occur.

All wiring must comply with applicable local codes, ordinances and regulations.

1. Mount the transformer in a convenient location.

2. Connect wires to the 120V side of the transformer.

3. Wire the humidifier solenoid valve, current sensing relay, or sail switch, humidity control and transformer.

Refer to the humidity control installation instructions for mounting and wiring information.

NOTE: Select models of fan centers include humidifier taps so the current sensing relay or sail switch is not needed.

68-0244 4

HE225A,B AND HE265A,B BYPASS FLOW-THROUGH HUMIDIFIER

PLUMBING THE SADDLE VALVE

Hot or cold water, either hard or softened, can be used in the humidifier.

1. Use the self-piercing saddle valve (included) to tap into the water supply line at an appropriate location.

IMPORTANT

• The saddle valve is not designed to regulate water flow. The valve is either open or closed.

• To prevent debris from clogging the solenoid inline filter, be sure to install the saddle valve handle pointing toward the ceiling.

NOTE: Lightly clean the copper tubing ends with fine sandpaper before making any connections.

2. Use 1/4 in. O.D. copper tubing and connect the saddle valve to the inlet side of the solenoid valve.

CAUTION

Hazardous Voltage.

Can cause personal injury or equipment damage.

Do not use any line connected to an air conditioner.

a.

Place the brass compression nut over the copper tubing.

NOTE: Do not over tighten the compression nut.

Moderate tightness prevents leaking.

b.

Slide the brass ferrule over the tubing.

c.

Insert the tubing into the solenoid valve fitting and support the valve while tightening the compression nut.

3. Connect a 1/2 in. (13 mm) drain tube to the humidifier drain fitting and run to a suitable drain.

NOTE: Slope the drain tube downward for correct drainage.

CHECKING THE INSTALLATION

Use the following procedure to check out the humidifier installation:

1. Open the saddle valve.

2. Set the thermostat setpoint to 10

°

F (6

°

C) above the room temperature.

NOTE: The furnace blower must be on for the humidifier to operate.

3. Set the Convertible Humidity Control to a high setting, or place the H1008A Automatic Humidity Control in the

Test position.

4. Observe the water running out of the drain line to be sure the humidifier is working.

5. Check for leaks.

6. Reset the thermostat and Convertible Humidity Control to a comfortable setting, or the Automatic Humidity

Control to the desired frost factor setting, for automatic operation.

OPERATING THE HUMIDIFIER

The HE225A and HE265A

Humidifiers are controlled by the Convertible Humidity

Control that is installed either on an interior wall in the living area or on the return air duct.

Humidity Control

Régulateur d'humidité

OUTDOOR

TEMPERATURE

-20

-10

°

°

F

F

F

-30

-25

-20

°

° C

C

0

+10

°

F

+20

Over 20

°

°

F

F

-10

-5

Over 0

°

°

C

C

C

HUMIDITY

SETTING

15%

20%

25%

30%

35%

40%

Choose the humidity control setting using the combination relative humidity/outdoor temperature setting scale on the humidity control dial. Match the H8908A dial setting to the outdoor temperature for optimizing the humidity level while reducing the moisture condensation on inside windows. Table 5 can also be used to adjust the humidity control to the recommended setting.

M14694

NOTE: As the outside temperature drops, the recommended setting is lowered to accommodate the effects of dewpoint. These settings should reduce the accumulation of moisture and ice on the windows and in other areas of the house.

Some indoor activities such as cooking, showering and clothes drying can cause excessive levels of humidity and start the accumulation of moisture on the windows.

NOTE: If this condition persists for more than a few hours, set the humidity control to the lowest setting to turn off the humidifier. If the condition does not improve, ventilate your home to remove the moisture.

The Enviracaire Elite HE225B and HE265B Humidifiers are controlled by the Honeywell

H1008A Automatic Humidity

Control with HumidiCalc+

Software. The automatic humidity control is mounted in the return air duct where it can be exposed to the air stream of the return air. The HumidiCalc+

Software inside the automatic humidity control

H1008A

M12817 is designed to automatically adjust the humidity level based on indoor temperature and humidity, inferred or measured outdoor temperature, and the setting of the frost factor dial.

The frost factor allows for variations in furnace size, window insulation and average daily climate temperature.

The Automatic Humidity Control with HumidiCalc+

Software requires an initial adjustment period. Set the frost factor dial on 5 and use Table 6 to adjust the frost factor—only one setting at a time—increasing the dial setting for more humidity, or reducing the setting if moisture develops on inside windows. For more precise humidity adjustment, set the frost factor between dial settings. Allow two days for the humidity level to subside before making further adjustments.

Once the proper setting has been found, no further adjustment is needed. HumidiCalc+

Software takes over and makes any future adjustments caused by varying outdoor temperatures, thus reducing moisture build-up on windows while maintaining the optimal humidity level.

68-0244

5

HE225A,B AND HE265A,B BYPASS FLOW-THROUGH HUMIDIFIER

At Outside Temperature

-20°F (-29°C)

-10°F (-23°C)

0°F (-18°C)

Table 5. Recommended Convertible Humidity Control Settings.

Recommended Setting

15

20

25

At Outside Temperature

+10°F (-12°C)

+20°F (-7°C)

Above 20°F (-7°C)

Recommended Setting

30

35

40

Humidity Level

Insufficient humidity

Condensation on windows

Table 6. Recommended Frost Factor Settings.

Recommended Adjustment

Increase the frost factor dial by one setting.

Decrease the frost factor dial by one setting.

OPERATION

The HE225A,B and HE265A,B Humidifiers use the principle that vapor (evaporated water) is created when warm air blows over a water soaked area. As the vapor circulates, the relative humidity rises.

The humidity control monitors the relative humidity and activates the humidifier accordingly. The humidifier has a water supply that disburses water over an antimicrobial humidifier pad. The warm dry air from the furnace passes over the humidifier pad and collects moisture and them circulates it through the house.

Humidified air feels warmer and more comfortable so the homeowner may be able to lower the thermostat heating setpoint and save money on heating fuel bills. The end result is that the humidifier gives the homeowner a comfortable environment that is also energy efficient.

Every 1 to 3 Months

(Depending on Water Quality)

Use the following procedure to clean the humidifier:

1. Disconnect the power and turn off the humidifier water supply.

2. Remove the humidifier cover. See Fig. 5.

WATER

FEED NOZZLE

HUMIDIFIER

PAD ASSEMBLY

FRAME

COVER

SIDEWALL

MAINTENANCE

A regular maintenance program prolongs the life of the humidifier and provides a more comfortable environment.

Either hard or soft water can be used in the humidifier.

Frequency of cleaning depends on the condition of the water.

CAUTION

Voltage Hazard.

Can cause electrical shock and equipment damage.

Disconnect power supply before installing or servicing.

IMPORTANT

Never oil any part of the humidifier.

HUMIDIFIER

HOUSING

BY-PASS SIDEWALL

WATER

FEED TUBE

Fig. 5. Location of humidifier parts.

M14672

3. Remove the humidifier pad assembly from the humidifier by grasping the tray and pulling it toward you.

4. Pull one side of the humidifier pad assembly frame toward you and remove the tray from the frame.

5. Gently pinch the water nozzle catches inward until the water nozzle can be lifted off the tray.

6. Slide the antimicrobial humidifier pad out of the frame.

7. Carefully scrape any mineral deposits from the tray and frame. Be sure the frame drain hole has nothing blocking it.

68-0244 6

HE225A,B AND HE265A,B BYPASS FLOW-THROUGH HUMIDIFIER

8. Check the humidifier pad and if excessive mineral deposits are present, replace with a new antimicrobial pad.

9. Disconnect the tube from the drain fitting on the bottom of the humidifier housing.

10. Clean the drain fitting, if necessary.

11. Bend the drain tube to loosen any mineral deposits.

12. Flush the drain tube with pressurized water (a running tap) to clean the tube.

13. Reattach the drain tube to the drain fitting.

14. Slide the humidifier pad back into the frame.

IMPORTANT

To maintain the antimicrobial properties of the humidifier, use only a Honeywell HC22E or HC26E

Antimicrobial Pad. See Table 8 List of Replacement

Parts for appropriate pad. Be sure the marked side of the antimicrobial humidifier pad is facing up for proper performance.

15. Snap the water nozzle back on the tray.

16. Reattach the tray to the frame.

17. Place the humidifier pad assembly in the humidifier housing and press until the assembly is completely seated. Be careful not to pinch or kink the water feed tube.

18. Replace the humidifier cover.

19. Verify the humidifier operation by following the steps in the Checkout Procedure section.

End of Humidification Season

At the end of the heating season, follow steps 1 through 18 from the Every 1 To 3 Months section to clean the humidifier and shut if off.

IMPORTANT

Be sure the humidifier power is off.

Beginning of Humidification Season

Refer to the Checkout Procedure section to complete the humidifier startup.

Vacation

When leaving on vacation, turn off the humidifier water supply and the humidity control. When returning from vacation, turn on the humidifier water supply and reset the humidity control to restart the humidifier.

CHECKOUT PROCEDURE

After winter startup or servicing, use the following procedure to check the humidifier operation:

1. Turn on the humidifier power and water supply.

2. Turn the Convertible Humidity Control to the highest setting, or place the H1008A Automatic Humidity

Control in the Test position and set the thermostat to

10 ° F (6 ° C) above the room temperature.

3. Observe that water is flowing out of the drain hose.

NOTE: The furnace blower must be on for the humidifier to operate.

4. Reset the thermostat and Convertible Humidity Control to a comfortable setting, or the H1008A Automatic

Humidity Control to the desired frost factor setting, for automatic operation.

TROUBLESHOOTING

Refer to Table 7 for troubleshooting procedures.

Problem

Low humidity

High humidity

Table 7. Troubleshooting Procedures.

What To Look For

Furnace blower not operating

Rapid air changes. Drafts (cold air is dry and is an added load to the humidifier).

Condensation on walls.

Heavy condensation on windows.

What To Do

• Reset circuit breaker or check for blown fuse.

• Check that the furnace power is on.

• Check all external wiring connections.

• Check the humidity control setting.

• Call a professional heating contractor.

• Keep doors and windows closed.

• Close fireplace damper when not in use.

• Keep exhaust fan running time to a minimum.

• Seal around doors and windows.

• Turn humidity control and water off until condensation is completely evaporated.

• Turn humidity control down low enough to eliminate condensation caused by moisture from bathing, mopping, cooking, etc. If moisture persists, more ventilation is needed.

68-0244

7

HE225A,B AND HE265A,B BYPASS FLOW-THROUGH HUMIDIFIER

REPLACEMENT PARTS

Refer to Fig. 6 and Table 8 when ordering replacement parts.

10

4

9

8

11

20

30 40

10

OFF

50

ON

60

5

6

12

3

1

13

7

8

68-0244

2

Fig. 6. Exploded view of humidifier parts.

8

8

M14820

HE225A,B AND HE265A,B BYPASS FLOW-THROUGH HUMIDIFIER

Table 8. List Of Replacement Parts For HE220A,B, HE260A,B Humidifiers.

Exploded

View Number

1

2

5

6

3

4

7

8

9

10

11

12

13

Description

Side wall

Bypass side wall

Cover Assembly

PerfectFlo™ water distribution tray

Antimicrobial humidifier pad

Frame

Drain fitting

Solenoid valve assembly

(includes water feed tube and nozzle)

Saddle valve assembly

Transformer (10 VA)

Convertible Humidity Control

Automatic Humidity control with

HumidiCalc™+ Software

Base insert assembly, includes no. 8 above

Hardware Kit for Solenoid Assembly (same as Solenoid valve assembly without the solenoid valve)

Current Sensing Relay

HE225 Part Number

32001612-002

32001613-002

32001611-003

32001619-001

HC22E1003

32001621-001

32001615-001

32001639-002

32001616-001

32001652-001

H8908B1002

H1008A1008

32001625-003

32001752-001

32001754-001

HE265 Part Number

32001626-002

32001627-002

32001611-004

32001630-001

HC26E1004

32001632-001

32001615-001

32001639-002

32001616-001

32001652-001

H8908B1002

H1008A1008

32001625-004

32001752-001

32001754-001

9

68-0244

HE225A,B AND HE265A,B BYPASS FLOW-THROUGH HUMIDIFIER

68-0244 10

HE225A,B AND HE265A,B BYPASS FLOW-THROUGH HUMIDIFIER

11

68-0244

HE225A,B AND HE265A,B BYPASS FLOW-THROUGH HUMIDIFIER

IMPROVE YOUR INDOOR AIR WITH A COMPLETE whole-house air quality system

ULTRAVIOLET AIR TREATMENT SYSTEM

• ZAP airborne germs.

• Kill most germs before they recycle through your home.

• Prevent mold spores from growing on your system cooling coils.

F300E ELECTRONIC AIR CLEANER

• TRAP airborne particles.

• Up to 99% efficient at capturing airborne particles.

• Effectively REDUCES fungi, bacteria, mold antigen, cat antigen and ragweed pollen antigen that pass through system.

ENVIRACAIRE ELITE HUMIDIFIERS

• Moisturize parched air.

• Help maintain proper humidity to minimize adverse health effects.

• Features special antimicrobial agent to prevent surface growth and migration of bacteria, mold, fungus and algae on the humidifier pad.

Honeywell offers one of the broadest families of home solutions in the industry - ranging from thermostats, zoning, ventilation, air cleaning, humidification to internet-enabled home control and wireless

WebPAD™ devices for web surfing and more!! Check out our offerings on-line at www.honeywell.com/yourhome/

... only from Honeywell.

M14757

Home and Building Control

Honeywell

1985 Douglas Drive North

Golden Valley, MN 55422

Home and Building Control

Honeywell Limited-Honeywell Limitée

35 Dynamic Drive

Scarborough, Ontario

M1V 4Z9

Printed in U.S.A. on recycled paper containing at least 10% www.honeywell.com/yourhome/