Honeywell PROTECTORELAY R8184G is an oil primary control that operates oil burners, valves, and ignition transformers based on thermostat input. It features a C554 Cad Cell Flame Sensor for flame monitoring and safety shutdown during ignition failure or flame loss. A manual reset button allows for easy system reset after lockout. The R8184G also includes a lockout indicator LED and can be manually opened using a front-mounted lever for maintenance purposes.
advertisement
R8184G PROTECTORELAY
OIL PRIMARY
APPLICATION
The TRADELINE intermittent ignition oil primary control operates the oil burner, oil valve (if desired) and the ignition transformer in response to a call for heat from the thermostat. Through a C554 Cad Cell Flame Sensor, the R8184 monitors the burner flame and shuts down the system on ignition failure or on flame failure during the run cycle. A light emitting diode (LED) on the terminal strip lights when the safety switch opens to provide safety shutdown indication.
A manual reset button is provided to reset the safety switch after lockout.
For convenience in system maintenance, the safety switch can be manually opened using a lever on the front of the control. Clock thermostats that power the clock through the primary control transformer will lose time during lockout unless backup batteries are installed.
R8184G is component recognized by Underwriters Laboratories Inc. and meets their flammability test requirements for a final enclosure.
CAUTION
1. Disconnect power before beginning installation to prevent electrical shock or equipment damage.
2. Make sure combustion chamber is free of oil or vapor before starting system.
RED RESET
BUTTON
2
HOLE OR KNOCKOUT FOR
CAD CELL LEADS
LOW VOLTAGE
TERMINAL STRIP
4 x 4 JUNCTION
BOX
INSTALLATION
WHEN INSTALLING THIS PRODUCT…
1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.
THERMOSTAT
R8184G PROTECTORELAY CONTROL
CAD CELL
T
T
F
R1
2
1K
SAFETY
SWITCH
LOCKOUT
INDICATOR
LED
SAFETY
SWITCH
BILATERAL
SWITCH
SAFETY
SWITCH
HEATER
TRIAC
1K1
R2
CAPACITOR
F
CAD
CELL LEADS
LINE
VOLTAGE LEADS MOUNTING
SCREW HOLE 1
1 STRIP WIRES 3/8 in. (9.5 mm); INSERT FROM SIDE, ABOVE OR BELOW.
2 T-T TERMINALS ON R8184G; T1-T2 TERMINALS ON R8184N.
M1643B
Fig. 1—Mounting the R8184G controls with 130
°
F
[54
°
C] maximum ambient temprature.
LOCATION
1. Mount on a 4 x 4 inch junction box, directly on the main burner, or inside the appliance cabinet. In replacement applications, mount in the same location as the old control.
2. Ensure the operating temperatures are within the ambient temperature range. Ambient temperature ranges are either -40 ° to 130 ° F [-40 ° C to 54 ° C] or -40 ° F to 150 ° F
[-40 ° C to 66 ° C] (Refer to box label).
MAKE WIRING CONNECTIONS AND MOUNT CONTROL
Wiring must comply with all local codes and ordinances.
Before mounting the control, make line voltage connections as shown in Fig. 1 or 2. Splice leads with solderless connectors. Do not exceed load ratings shown on the device label.
If cad cell leads are run with line voltage wires, breakout knockout at the bottom of the low voltage terminal strip and thread can cell leads through the hole.
If necessary use control as a template to mark and drill new mounting holes. Mount using No. 6 screws (obtain locally).
BLACK
JUNCTION BOX
LINE VOLTAGE
THERMOSTAT
2
1K2
ORANGE
WHITE
LIMIT
BURNER
MOTOR
OIL VALVE
(OPTIONAL)
IGNITION
L1
(HOT)
1
L2
D.T.
Rev. 4-91
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2 TO USE R8184 WITH LINE VOLTAGE CONTROLLER, JUMPER T-T TERMINALS AND CONNECT LINE VOLTAGE THERMOSTAT IN
SERIES WITH LIMIT CONTROLLER.
M1635
Fig. 2—Typical hookup for TRADELINE R8184G with indicator light.
Form Number 69-0617—1
© Honeywell Inc. 1991
T87F/Q539A
R
C
G
Y
RH
W
X
FAN
RELAY
COOLING
CONTROL
R8184G PROTECTORELAY CONTROL
COOLING
L1 (HOT)
L2
TRANSFORMER
VIOLET
CAD CELL
T(R)
T(W)
3
2
R1
1K
SAFETY
SWITCH
LOCKOUT
INDICATOR
LED
SAFETY
SWITCH
BILATERAL
SWITCH
SAFETY
SWITCH
HEATER
TRIAC 1K1
1K2
BLACK
1
ORANGE
JUNCTION BOX
LIMIT
BURNER
MOTOR
OIL VALVE
(OPTIONAL)
LINE VOLTAGE
THERMOSTAT
2
L1
(HOT)
L2
1
R2
F
IGNITION
CAPACITOR
WHITE
F
1
2
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
TO USE R8184 WITH LINE VOLTAGE CONTROLLER, JUMPER T-T TERMINALS AND CONNECT LINE
VOLTAGE THERMOSTAT IN SERIES WITH LIMIT CONTROLLER.
3 REMOVE PLUG AND ROUTE VIOLET LEADWIRE THROUGH HOLE IN BASE OF R8184.
M718
Fig. 3—Typical hookup for Tradeline R8184G with indicator light and isolated alarm relay.
Mount control as shown in Fig. 1 or 2. After mounting, make low voltage connections to the screw terminals. Strip leads 3/8 in. [10 mm] and insert under terminal screw. See
Fig. 1 or 2. Connect cad cell leads to F-F terminals and thermostat leads to T-T terminals. See Fig. 3 or 4.
CHECKOUT
START SYSTEM
WARNING
Fire hazard.
Can cause severe burns.
Make sure combustion chamber is free of oil or oil vapor before starting system.
1. Push in and release red reset button.
2. Open hand valve in oil supply line.
3. Make sure system is powered. Check circuit breaker or fuse and close system switch, if provided.
4. Set thermostat to call for heat.
5. Burner should light and operate until call for heat ends.
CHECK SAFETY FEATURES
Simulate flame failure:
1. Follow starting procedure to turn on burner.
2. Close hand valve in oil supply line.
3. Safety switch should lock out approximately in safety switch timing indicated on label. Indicator light should come on. Ignition and motor should stop and oil valve should close.
Simulate ignition failure:
1. Follow starting procedure to turn on burner, except do not open oil supply hand valve.
2. Safety switch should lock out in safety switch timing
(see label). Indicator light should come on. Ignition and motor should stop and oil valve should close.
Simulate power failure:
1. Follow starting procedure to turn on burner.
2. With burner running, trip circuit breaker or remove fuse to turn off power to the system.
3. Burner should stop.
4. Restore power. Burner should restart.
If system does not operate as described, proceed to
Troubleshooting.
TROUBLESHOOTING AND
MAINTENANCE
IMPORTANT
This control contains no field-serviceable parts. Do not attempt to take it apart. Replace entire control if operation is not as described.
PRELIMINARY STEPS
1. Check wiring connections and power supply. Make sure power is on to the controls, burner motor, and ignition transformer.
2. Make sure limit control is closed.
CHECK OIL PRIMARY RELAY
NOTE: You’ll need an insulated jumper wire with both ends stripped.
1. Disconnect cad cell leads from F-F terminals.
2. Reset safety switch and set thermostat to call for heat.
Burner should start.
3. Within safety switch timing, jumper F-F terminals with insulated jumper wire. Burner should continue to run.
4. After safety switch timing, remove jumper. Burner should shut down in safety switch timing.
5. If operation is not as described, replace oil primary control.
2
CHECK CAD CELL
1. Disconnect power at system switch, circuit breaker or fuse.
2. Clean cell face with soft cloth.
3. Make sure cell is seated securely in socket. Be careful not to disturb socket position.
4. Reconnect cad cell leads to F-F terminals.
5. Reset safety switch, turn on power and set thermostat
TRIP SAFETY SWITCH BEFORE PERFORMING
BURNER MAINTENANCE
CAUTION
Tripping the safety switch shuts down the burner but does not disconnect the power supply. Turn off power at system switch or circuit breaker before servicing the control system, burner motor, oil valve or ignition to avoid electric shock.
To trip the safety switch, move the safety switch lever down until the red reset button pops out and the indicator light comes on. See Fig. 5. Burner will not operate until safety switch is reset by pushing in the red reset button.
PUSH LEVER DOWN
TO TRIP SAFETY SWITCH
WHEN SAFETY SWITCH TRIPS
RESET BUTTON POPS OUT
INDICATOR LIGHT COMES ON
(TRADELINE ONLY)
M17882
Fig. 4—Move lever down to trip safety switch.
3 69-0617—1
Automation and Control Solutions
Honeywell International Inc.
Honeywell Limited—Honeywell Limitée
1985 Douglas Drive North
Golden Valley, MN 55422
35 Dynamic Drive
Scarborough, Ontario M1V 4Z9 www.honeywell.com
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement