7900 | LCN ES7982 Series Installation Instructions

Add to my manuals
5 Pages

advertisement

7900 | LCN ES7982 Series Installation Instructions | Manualzz

*23655*

23655

Model ES7982

Control Box

L For closer information see closer installation instruction sheet

Typical Electric & Air Supply Hook Up

120V AC

INPUT

12V DC TO

ACTUATORS

REGULATED AIR FROM

CONTROL BOX TO

AUTO-EQUALIZERS

Installation Instructions

1 Locate box on interior of building within 50 tubing feet of the farthest door to be controlled. Box must be in a clean, dry, well ventilated place where temperatures do not exceed 120°F or fall below

35°F.

2 Mount box to a structurally sound surface using screws provided as shown on page 2 with air fittings on left side as shown. Do not mount box upside down or on a horizontal plane.

3 Refer to instructions packed with actuators and connect leads to terminals 6, 8, 9, and 10 as required.

4 Connect unpowered 120V AC input to terminals 3,

4, and ground screw. (Line side to terminal 3, neutral side to terminal 4 and ground wire to ground screw).

If door control is on a fire door, 120V AC input must be interrupted by the fire alarm panel when in alarm.

When dry auxiliary fire alarm contacts are used, remove shunt from terminals 1 and 2 and connect to dry contacts of fire detector or alarm panel. Terminals

1 and 2 are in series with line side of 120V input.

5 Turn on power. Air valves and compressor will operate one cycle when power is applied.

6 Air pressure output has been preset at factory. If more air pressure is required to adequately open doors, regulate air adjustment valve on pump as shown on page 3.

7 Adjust time delay to keep air valve energized by turning adjustment wheel on timer modules “A” & “B”

(CW to increase - CCW to decrease). The LED (light) on the timer module indicates the valve is energized.

The time can be adjusted from 0-30 seconds. 10 seconds is a “normal” delay.

L TIMER MODULE “A” AND “B” MUST OPERATE LONGER

THAN TIMER MODULE “P”.

8 Adjust timer module “P” to keep compressor activated for the necessary amount of time to open the door.

This can be done by rotating the adjusting wheel.

(CW to increase - CCW to decrease). The LED (light) on the timer module indicates the compressor is energized. The compressor should not run more than

1-3 seconds longer than the time required to open the door.

9 Test actuators to ensure wiring and tubing are properly connected.

1

A

OUTLET B OUTLET A

AIR

FILTER

!

CAUTION

DO NOT MOUNT BOX UPSIDE

DOWN OR IN HORIZONTAL

POSITION. LOCATE WHERE

TEMPERATURES DO NOT

EXCEED 120°F OR FALL

BELOW 35°F

INSTALL BOX WITH SIX TAPCON

CONCRETE SCREWS 3/16 x 1 1/4

DRILL 5/32 HOLE 1 1/4 DEEP

WITH CARBIDE TIPPED

CONCRETE DRILL BIT

TERMINAL "10" IS

COMMON TO ALL

ACTUATORS

12V DC OUTPUT

!

CAUTION

COMPONECTS INSIDE CONTROL

BOX WILL BE HOT TO TOUCH

UNDER NORMAL OPERATION.

ALLOW BOX TO COOL DOWN

BEFORE MAKING ADJUSTMENTS.

AIR FILTER SHOULD BE

INSPECTED EVERY SIX

MONTHS. IF FILTER IS

DAMAGED, CONTACT LCN

FOR REPLACEMENT.

TRIGGER "A"

TRIGGER "B"

!

WARNING

HAZARDOUS VOLTAGE

CAN SHOCK AND

CAUSE SEVERE INJURY

Disconnect power before making any electrical connections or performing maintenance.

!

DANGER

ELECTRICAL DATA

INPUT = 120V AC @ 5 AMPS

POWER CONSUMPTION 600 WATTS

OUTPUT IS 12V DC (250 mA MAX. LOAD)

CONTROL BOX MUST BE CONNECTED TO EARTH GROUND

NEUTRAL 120V AC

LINE

INPUT

TO FIRE

ALARM

SHUNT

*

REMOVE THIS SHUNT

ONLY WHEN CONNECTING

TO NORMALLY CLOSED

FIRE ALARMS CONTACTS

2

Air Pressure Adjustment

A

B

1 Loosen lock nut. (A)

2 Turn outer valve (B) to regulate air pressure.

3 Tighten lock nut.

3

Symptom

No Power Opening.

Does not open or fully open.

Opens too slow or not at all.

Power opening will not time out.

Power opening timing out too soon.

Installation Troubleshooting Chart

Possible Cause Suggested Remedy

No power to control box/blown fuse.

Actuator(s) not connected properly.

Fire alarm system causing open circuit on terminals 1 & 2.

No input to Auto-Equalizer operator.

Air lines obstructed with dirt or ice.

Air valves not working.

Compressor not working.

Verify 120VAC 60HZ power is present at terminals 3 & 4 on control box terminal strip. Check fuse. Replace only with 5 amp

(3AG type) fuse.

Be sure a timer module board is firmly in place in “A,” “B” & “P” slots. Operate actuator(s) LED on timer module should light when actuator is used. The LED on timer “P” should light whenever

“A” or “B” is lit. If not, momentarily short actuator terminals 6 &

10 and 8 & 10 in the control box. If LED lights, check wiring to actuators for an open circuit. If it does not light, check for voltage at terminals 9 & 10. Voltage should read from 11.75 to 13.25V

DC. If there is no reading, disconnect leads from terminals 9 &

10. Short actuator terminals 6 & 10 and 8 & 10. If LED lights, check for short circuit in actuators.

Shunt terminals 1 & 2 with power off. Restore power. If control operates when actuator terminals in the control box are shorted, an open circuit exist in wiring to fire alarm. When Auto-Equalizer is not used with fire alarms, terminals 1 & 2 must be permanently shorted with a shunt.

IMPORTANT! When Auto-Equalizer is connected to fire alarm, make sure shunt is removed from terminals 1 & 2. Terminals 1 &

2 are one leg of 120V line.

Disconnect tubing from Auto-Equalizer operator. Try actuator and verify that air is coming out of tubing. If not, trace tubing to control box, checking for breaks or kinks in air line.

Clean or thaw lines and reroute if necessary. Eliminate dips near cold zones.

Make sure air valve leads are plugged into main board. (Be sure valves in system are plugged into connectors “A” & “B”).

Make sure compressor leads are plugged into main board. (Be sure compressor is plugged into connector “P”).

Control box exhaust restricted.

Exhaust muffler may be clogged by dirty air or accidental painting. Clean in alcohol or mineral spirits.

Inlet filter clogged.

Replace filter element (Contact LCN for replacement).

Scanner maintaining signal to control box.

Switch circuit maintaining contact.

Make sure lenses are clean and there are no obstructions in front of scanner. Model 909 or 939 proximity scanner may “see” an opposite wall. Adjust range as described earlier.

Check for short circuit or error in wiring to switch or scanner.

Air valve blocked open with contaminant.

Air compressor needs readjustment.

Timer cards not set properly.

Cycle valve several times by momentarily shorting actuators in the control box. This should clear valve.

See page 2 for regulation instructions.

Set timer cards “A” & “B” for max. time. Set timer card “P” for min. time. Slowly increase card “P” until “time-out” is 1-3 seconds after door is fully open. Decrease timer card “A” & “B” to achieve desired time delay before closing. (Make sure “P” times out before “A” & “B”).

4

!

WARNING

Model ES7982 for use with Electric Latching Hardware

ES7982 - 2 electric strikes maximum

HAZARDOUS VOLTAGE

CAN SHOCK AND

CAUSE SEVERE INJURY

Disconnect power before making any electrical connections or performing maintenance.

BLK

K1

BLK

BLK K2

BLK

BRN

PINK

POWER SUPPLY

BY OTHERS.

(DO NOT use

LCN 12VDC power

VIO

PINK

WHITE - RED

ELECTRIC STRIKE

DOOR "B"

WHITE - BROWN (N.C.)

WHITE - VIOLET (N.O.)

BROWN (N.C.)

ELECTRIC STRIKE

DOOR "A"

WBRN

WVIO

WRED

VIOLET (N.O.)

VIOLET / WHITE - VIOLET WIRE N.O.

FAIL SECURE STRIKE (N.O. CONTACT)

Strike releases when energized. Remains locked in alarm or power failure. (Manual release hardware required to open door in alarm or power failure.)

BROWN / WHITE - BROWN WIRE N.C.

FAIL SAFE STRIKE (N.C. CONTACT)

Strike releases with alarm or power failure.

Remains lached with power on.

(Not compatible with UL listed fire door.)

Customer Service

1-877-671-7011 www.allegion.com/us

5

© Allegion 2014

Printed in U.S.A.

23655 Rev. 05/14-e

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement