Liebert Network Router micro smart switch User manual
Add to my manuals12 Pages
Liebert Network Router micro smart switch is a 1U rack-mountable power distribution unit with a built-in automatic transfer switch, providing redundant power to connected equipment. It features 12 IEC-320 (10A) receptacles distributed across four circuit breakers, allowing for balanced load distribution and preventing overloads. With dual L6-30P line cords and a total load capacity of 24A, it ensures continuous power to critical equipment, making it ideal for data centers and server rooms.
advertisement
DISCONTINUED
PRODUCT
M
ICRO
S
MART
S
WITCH
D
UAL
I
NPUT
P
OWER
D
ISTRIBUTION
U
SER
M
ANUAL
200 VAC to 240 VAC
50/60 Hz
24 Amps
General Description
The Liebert Micro SmartSwitch (MSS) is a single Phase Dual Input rack mountable Power Distribution Unit (PDU) with a built in Automatic Transfer Switch.
When Input A falls below 168 VAC and Input B is valid, the output is automatically transferred to Input B. The output is transferred back to Input A when Input
A is valid and rises above 178 VAC. This high speed transfer rate ensures that the transfer is transparent to the sensitive equipment.
The two sources are not required to be in phase. This is an effective solution that builds in redundancy and increases the AC power availability of connected equipment. If the dual input power is fed through two independent AC sources, then the system availability is increased and the dual input advantages are fully used.
The Micro SmartSwitch provides 12 receptacles that distribute redundant AC power and may be rack mounted. There are four groups of three IEC-320 (10A) receptacles, where each group is backed up by a 10A magnetic circuit breaker.
The MSS has two attached line cords that are terminated with NEMA L6-30 plugs with a 20A fuse for each. The total load for the MSS cannot exceed 24A of
AC load at 200-240 VAC. Also the load for each of the four groups cannot exceed 10A or the internal breaker may trip or the fuse will blow. The load must be balanced among the four segments such that the total current draw per section does not exceed 10A and a total of 24A for all the four segments of the MSS.
This product provides line-to-line surge protection of 500 Joules.
Glossary of Symbols
Risk of Electrical Shock
!
I
O
Indicates Caution - followed by important instructions
Bonded to Ground
AC Voltage
On
Off
No user servicable parts inside
DISCONTINUED
PRODUCT
About This Device
This guide serves as an outline to assist Qualified personnel with the installation of the Liebert Micro SmartSwitch. The input voltage for this Micro SmartSwitch unit is 200VAC to 240VAC.
This Micro SmartSwitch includes the following features:
• Mounts in 1U of rack space
• Provides 12 receptacles on 4 circuit breakers
• Protects against electrical line surges and spikes
This Micro SmartSwitch is UL and c-UL listed as Information Technology
Equipment.
!
WARNING:
There is a risk of personal injury from electrical shock and hazardous energy levels. The installation of options and routine maintenance and service of the product must be performed by individuals who are knowledgeable about the procedures, precautions, and hazards associated with AC power products (trained service technician).
To reduce the risk of electrical shock and/or equipment damage when installing or servicing the Micro SmartSwitch:
• The Micro SmartSwitch must be disconnected from the product and unplugged from the AC electrical outlet before servicing or repairing product.
• Do not overload the output of the Micro SmartSwitch. The total connected load should not exceed rated input power.
• Do not exceed the leakage current limit for the Micro SmartSwitch in your system. See the “Earth Leakage Current” section later in this document for limits.
Earth Leakage Current
To reduce the risk of electrical shock due to high leakage current, a reliable grounded (earth) connection is essential before connecting Micro SmartSwitch to
AC power. Observe the following limits when connecting the product to AC power distribution devices.
For products that have attached AC power cords directly connected to the building power, the total combined leakage current should not exceed 5 percent of the rated input current for the device.
For products that have detachable AC power cords, the total combined leakage current should not exceed 3.5mA.
Voltage Selection
On connected equipment that have voltage select switches, make sure that the switch is set for the type of voltage you use (208/240 VAC).
DISCONTINUED
PRODUCT
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS.
This manual contains important instructions that should be closely followed during installation and maintenance of this product.
This product is designed for Commercial/Industrial use only. It is not intended for use with life support and other U. S. FDA designated “critical” devices. Maximum load must not exceed that shown on the rating label. See Limited Warranty.
WARNING:
Lethal voltages may be present within this unit even when it is apparently not operating. Observe all cautions and warnings in this manual.
Failure to do so MAY result in serious injury.
This equipment or Micro SmartSwitch is designed for use on a properly grounded (earthed), 208/240 VAC, 50Hz or 60Hz supply.
ELECTROMAGNETIC COMPATIBILITY- The Micro SmartSwitch complies with the limits for a CLASS B digital device, pursuant to part 15 of FCC rules.
These limits provide reasonable protection against harmful interference. If this device is not installed and used in accordance with the instruction manual, it may cause harmful interference to radio communications. Not operating this device in accordance with these instructions may cause harmful interference, which the user must correct at their own expense.
Operate the Micro SmartSwitch in an indoor environment only in an ambient temperature range of 0°C to 50°C (32°F to +122°F). Install it in a clean environment, free from conductive contaminates, moisture, flammable liquids, gasses, or corrosive substances.
Turn the Micro SmartSwitch off and isolate it from other equipment before cleaning. Use a soft cloth, never liquid or aerosol cleaners.
Keep the vents free from dust accumulation that could restrict airflow.
Never block or insert any object into the ventilation holes or other openings.
DISCONTINUED
PRODUCT
Installation
Place rear rail [R] over the studs in the front rail [F]. Tighten nuts finger tight.
The mounting tab [T] will be facing out, so the holes align with the rack sides.
Adjust length of rail assembly to fit inside rack. Tighten either the wing nuts or hex nuts.
Insert cage nut (one on each side) in rack. Set hooks at rear of rail over holes in rack. Use screw [2] (one on each side) to attach rails to rear of rack through cage nut. Use screw [2] (two on each side) to attach rails to front of rack.
R
T
F
OUTSIDE
2
FRONT
Use screws [1] (two on each side) to attach brackets to side of unit. Slide unit into rails and secure by using screws [2] (one on each side) to attach the unit.
1
2
1
DISCONTINUED
PRODUCT
Ground Bonding Screw
A ground bonding screw is provided on the rear of the unit. This feature is provided as an attachment point for conductors the rack may contain for the purpose of functional grounding or bonding of ungrounded metal parts.
Ground cables are not included.
Note:
The Ground Bonding wire must be a minimum of 10 AWG to maintain proper grounding.
Connecting Devices
Make sure that the devices connected do not exceed the unit capabilities.
This Dual Input
Micro Smart-
Switch features
3 output receptacles per circuit breaker, for a total of 12 receptacles.
This model is rated at 10A per breaker.
Each block of 3 receptacles has a maximum output rating of 10A. If the total connected load exceeds 10A, the circuit breaker will trip and interrupt power to all loads attached to that block of receptacles.
The maximum output of this Micro SmartSwitch is 24A. If the total load connected to all load segments exceed 24A, the circuit breaker at the wall could trip and interrupt power to all loads.
DISCONTINUED
PRODUCT
About the Circuit Breakers
Input power can be verified by the illumination of the two LEDs on the front of the unit, marked ~A and ~B.
Output power can be verified by the illumination of the circuit breaker, when in the On position
If connected device is not powered, verify the respective circuit breaker is On and illuminated.
If power is still not restored, see “Contacts” section later in this document.
DISCONTINUED
PRODUCT
Configurations
The Micro SmartSwitch can be configured to fit several power distribution requirements.
Configuration 1
This application shows use of the Micro SmartSwitch in conjunction with singleline cord devices .
Note:
Each segment can accommodate a maximum current draw of 10A, so the individual load connected to it must not exceed 10A or the circuit breaker will trip.
~A:
AC Input A
~B:
AC Input B
1,2,3,4:
Load segments on the
Micro SmartSwitch
Load:
Any server, storage, or other equipment connected to the Micro SmartSwitch
L6-30P
~ A
Dual Input
~ B
L6-30P
P
D
U
1
2
3
4
200-240 VAC
Load
Load
Load
Load
Configuration 2
This configuration shows the use of the Micro SmartSwitch with 3-line cord devices. The figure below shows how three Micro SmartSwitchs can be used to connect with up to four 3-line cord devices.
Note:
Each segment can accommodate a maximum current draw of 10A, so the individual load connected to it must not exceed 10A or the circuit breaker will trip.
~A:
AC Input A
~B:
AC Input B
Load:
Any server, storage, or other equipment connected to the Micro SmartSwitch
L6-30P
~ A
Dual Input
~ B
L6-30P
P
D
U
1
2
3
4
200-240 VAC
Load
Load
Load
Load
DISCONTINUED
PRODUCT
Configuration 3
This configuration shows the use of a Micro SmartSwitch with 2-line cord devices. In this configuration, a server is connected to each of the four segments of the Micro SmartSwitch.
Note:
Each segment can accommodate a maximum current draw of 10A, so the individual load connected to it must not exceed 10A or the circuit breaker will trip.
~A:
AC Input A
L6-30P
~ A
Dual Input
~ B
L6-30P
P
D
U
3
4
1
2
Load
Load
Load
Load
200-240 VAC
~B
: AC Input B
1,2,3,4:
Load segments on the
Micro SmartSwitch
Load:
Any server, storage, or other equipment connected to the Micro SmartSwitch
L6-30P
~ A
Dual Input
~ B
L6-30P
P
D
U
1
2
3
4
Load
Load
200-240 VAC
Configuration 4
If your facility does not have a centralized Uninterruptible Power System, then the following configuration will provide maximum redundancy in a rack environment. The diagram below shows how to use three Micro SmartSwitchs, each connected to a UPS and a server.
Note:
Each segment can accommodate a maximum current draw of 10A, so the individual load connected to it must not exceed 10A or the circuit breaker will trip.
DUAL INPUT
~A:
AC Input A
~B:
AC Input B
~ A
~ B
P
D
U
UPS
Load
Load:
Any server, storage, or other equipment connected to the Micro SmartSwitch
~ A
~ B
~ A
~ B
L6-30P
P
D
U
P
D
U
UPS
UPS
200-240 VAC
Load
Load
DISCONTINUED
PRODUCT
Liebert Model Name
Liebert Micro SmartSwitch Specifications
Micro SmartSwitch
Part Number
Unit Dimensions (H x W x D) in
(mm)
Unit Weight: lbs.(kg)
Shipping Weight: lbs.(kg)
LED Indictors
Nominal Input Voltage Range
On-Line Voltage Range
MSS30A-240
1.72 x 17.00 x 15.25 in
(43.7mm x 432mm x 387mm)
20.0 lbs.(9.7kg)
32.0 lbs.(14.55kg)
Input A (Primary) / Input B (Secondary)
200 – 240VAC
180 – 262VAC
Input Plug
Input Frequency
Input Surge Rating
Output Connectors
Output Circuit Breaker Protection Rating
Output Power (VA) Rating
Maximum Output Current
Transfer Time
(2) Attached x L6-30 Plugs
50/60Hz
500J
(12) x IEC-320-C13
(4) x 10A
4320
24A
<18ms
Environmental
0°C to 50°C (32°F to 122°F) Operating Temperature
Storage Temperature
Relative Humidity
Operating Altitude
Safety Markings
Safety Certifications
-30°C to 60°C (-22°F to 140°F)
10 % to 80 %, non-condensing
0 to 10,000 feet above sea level
Safety and Agency
UL, c-UL
EMC Markings
Emissions
Immunity
UL1950
FCC
FCC Class A,
ANSI C62.41 Cat B (formerly IEEE 587)
DISCONTINUED
PRODUCT
DISCONTINUED
PRODUCT
Micro Smart Switch
The Company Behind the Products
•
•
•
•
•
With over a million installations around the globe,
Liebert is the world leader in computer protection systems. Since its founding in 1965, Liebert has developed a complete range of support and protection systems for sensitive electronics:
Environmental systems—close-control air conditioning from 1 to 60 tons
Power conditioning and UPS with power ranges from 300 VA to more than 1000 kVA
Integrated systems that provide both environmental and power protection in a single, flexible package
Monitoring and control—from systems of any size or location, on-site or remote
Service and support through more than 100 service centers around the world and a 24/7
Customer Response Center
While every precaution has been taken to ensure the accuracy and completeness of this literature,
Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
© 2001 Liebert Corporation
All rights reserved throughout the world.
Specifications subject to change without notice.
® Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
SL-20350 (10/01)
D
UAL
I
NPUT
P
OWER
D
ISTRIBUTION
U
SER
M
ANUAL
Technical Support
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
1-800-222-5877
Outside the United States
+614-888-0246
24 hours a day, 7 days a week
1-800-222-5877
3-Phase UPS
1-800-543-2778
Environmental Control
1-800-543-2778
Italy
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD)
+39 049 9719 111
FAX: +39 049 5841 257
Asia
23F, Allied Kajima Bldg.
138 Gloucester Road
Wanchai
Hong Kong
+852 2 572 2201
FAX: +852 2 831 0114
Web Site
www.liebert.com