LST Triple Input/Output Module 55000-588 User's Manual


Add to my manuals
1 Pages

advertisement

LST Triple Input/Output Module 55000-588 User's Manual | Manualzz

Triple Input/Output Module

55000-588

• ADM loop technology with

Apollo/Discovery protocol

• 3 line-monitored inputs and

3 dry relay outputs

• Setting of module address by means of address switch

• Integrated dual-isolator

• Status LED for each input and output

Description

The addressable Module 55000-588 serves for the line-monitored integration of three contact detectors, such as manual call points, sprinkler system contacts or supervising contacts, into the bidirectional communication on the ADM loop with Apollo/Discovery protocol.

Furthermore, it can be used to actuate external devices by means of three relay outputs, each with a single-pole dry change-over contact, via the ADM loop.

The address is easily selected by means of a built-in DIL switch. Individual status LEDs indicate the condition of every input and output. The module has an integrated dual-isolator and is fi tted into a plastic case.

Specifi cations

Operating voltage

Current consumption

Contact rating

Ambient temperature

Dimensions L × W × H

Colour

Weight

Approval

Order number

Order name

Supply through loop voltage approx. 3mA (quiescent)

1A/30VDC or AC

-20°C to +70°C

250 × 175 × 75 (mm) white

621g

VdS G202052

249077

Module 3xSurv.In 3xRel.Out/Apo 55000-588

Building Safety. Building Security.

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27

[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED