National Instruments NI 9425 is a high-performance 32-channel, 24 V sinking digital input module designed for use in industrial automation applications. It features sourcing-output device connectivity and supports sleep mode for low-power consumption. With its robust design and wide range of safety certifications, the NI 9425 is ideal for use in hazardous environments.
advertisement
OPERATING INSTRUCTIONS AND SPECIFICATIONS
NI 9425
32-Channel, 24 V Sinking Digital Input Module
Français Deutsch
ni.com/manuals
This document describes how to use the National Instruments 9425 and includes specifications and pin assignments for the NI 9425.
Visit ni.com/info and enter rdsoftwareversion to determine which software you need for the modules you are using. For information about installing, configuring, and programming the system, refer to the system documentation. Visit ni.com/info and enter cseriesdoc for information about C Series documentation.
Note The safety guidelines and specifications in this document are specific to the NI 9425. The other components in the system might not meet the same safety ratings and specifications. Refer to the documentation for each component in the system to determine the safety ratings and specifications for the entire system. Visit ni.com/info and enter cseriesdoc for information about C Series documentation.
NI 9425 Operating Instructions and Specifications 2 ni.com
Safety Guidelines
Operate the NI 9425 only as described in these operating instructions.
Hot Surface This icon denotes that the component may be hot. Touching this component may result in bodily injury.
Safety Guidelines for Hazardous Voltages
If hazardous voltages are connected to the module, take the following precautions. A hazardous voltage is a voltage greater than 42.4 V pk
or 60 VDC to earth ground.
Caution Ensure that hazardous voltage wiring is performed only by qualified personnel adhering to local electrical standards.
Caution Do not mix hazardous voltage circuits and human-accessible circuits on the same module.
Caution Make sure that devices and circuits connected to the module are properly insulated from human contact.
© National Instruments Corp. 3 NI 9425 Operating Instructions and Specifications
Caution When module terminals are hazardous voltage
LIVE (>42.4 V pk
/60 VDC), you must ensure that devices and circuits connected to the module are properly insulated from human contact.
Safety Guidelines for Hazardous Locations
The NI 9425 is suitable for use in Class I, Division 2, Groups A, B,
C, D, T4 hazardous locations; Class I, Zone 2, AEx nC IIC T4, and
Ex nC IIC T4 hazardous locations; and nonhazardous locations only. Follow these guidelines if you are installing the NI 9425 in a potentially explosive environment. Not following these guidelines may result in serious injury or death.
Caution Do not disconnect I/O-side wires or connectors unless power has been switched off or the area is known to be nonhazardous.
Caution Do not remove modules unless power has been switched off or the area is known to be nonhazardous.
Caution Substitution of components may impair suitability for Class I, Division 2.
NI 9425 Operating Instructions and Specifications 4 ni.com
Caution For Zone 2 applications, install the system in an enclosure rated to at least IP 54 as defined by
IEC 60529 and EN 60529.
Caution For Zone 2 applications, connected signals must be within the following limit:
Capacitance .......................... 0.03 μF max
Special Conditions for Hazardous Locations Use in Europe
This equipment has been evaluated as EEx nC IIC T4 equipment under DEMKO Certificate No. 03 ATEX 0324020X. Each module is marked II 3G and is suitable for use in Zone 2 hazardous locations. If you are using the NI 9425 in Gas Group IIC hazardous locations or in ambient temperatures of –40 °C ≤ Ta ≤ 70 °C, you must use the device in an NI chassis that has been evaluated as
EEx nC IIC T4, Ex nA IIC T4, or Ex nL IIC T4 equipment.
© National Instruments Corp. 5 NI 9425 Operating Instructions and Specifications
Special Conditions for Marine Applications
Some modules are Lloyd’s Register (LR) Type Approved for marine applications. To verify Lloyd’s Register certification, visit ni.com/certification and search for the LR certificate, or look for the Lloyd’s Register mark on the module.
Caution To meet radio frequency emission requirements for marine applications, use shielded cables and install the system in a metal enclosure. Suppression ferrites must be installed on power supply inputs near power entries to modules and controllers. Power supply and module cables must be separated on opposite sides of the enclosure and must enter and exit through opposing enclosure walls.
NI 9425 Operating Instructions and Specifications 6 ni.com
Connecting the NI 9425
The NI 9425 has a 37-pin DSUB connector that provides connections for 32 simultaneously-sampled digital input channels.
DI25
DI26
DI27
DI28
DI29
DI30
DI31
DI16
DI17
DI18
DI19
DI20
DI21
DI22
DI23
COM
COM
DI24
24
25
26
27
28
29
30
20
21
22
23
31
32
33
34
35
36
37
9
10
11
6
7
8
1
4
5
2
3
12
13
14
15
16
17
18
19
DI0
DI1
DI2
DI3
DI4
DI5
DI6
DI7
COM
COM
DI8
DI9
DI10
DI11
DI12
DI13
DI14
DI15
NC
© National Instruments Corp.
Figure 1. NI 9425 Pin Assignments
7 NI 9425 Operating Instructions and Specifications
Each channel has a DI pin to which you can connect a digital input signal. The NI 9425 has four common pins, COM, that are internally connected to the isolated reference of the module.
The NI 9425 has sinking inputs, meaning that when the device drives a current or applies a voltage to the DI pin, the pin provides a path to COM for the current or voltage. The NI 9425 internally limits current signals connected to DI. For more information about input current levels, refer to the
section.
You can connect 2-, 3-, and 4-wire sourcing-output devices to the NI 9425. A sourcing-output device drives current or applies voltage to the DI pin. An example of a sourcing-output device is an open collector PNP.
Connect the sourcing-output device to the DI pin on the NI 9425.
Connect the common of the external device to the COM pin. Refer
to Figure 2 for an illustration of connecting a device to the
NI 9425.
NI 9425 Operating Instructions and Specifications 8 ni.com
Sourcing-Output
Device
DI
External
Power
Supply
+
_
COM
NI 9425
Figure 2. Connecting a Device to the NI 9425 (Three-Wire Device Shown)
The NI 9425 channel registers as ON when the sourcing-output device applies a voltage or drives a current that is in the input ON range to the DI pin. The channel registers as OFF when the device applies a voltage or drives a current that is in the input OFF range to the DI pin. If no device is connected to the DI pin, the channel registers as OFF. Refer to the
section for more information about the ON and OFF states.
© National Instruments Corp. 9 NI 9425 Operating Instructions and Specifications
Sleep Mode
This module supports a low-power sleep mode. Support for sleep mode at the system level depends on the chassis that the module is plugged into. Refer to the chassis manual for information about support for sleep mode. If the chassis supports sleep mode, refer to the software help for information about enabling sleep mode. Visit ni.com/info and enter cseriesdoc for information about
C Series documentation.
Typically, when a system is in sleep mode, you cannot communicate with the modules. In sleep mode, the system consumes minimal power and may dissipate less heat than it does in normal mode. Refer to the
Specifications section for more
information about power consumption and thermal dissipation.
NI 9425 Operating Instructions and Specifications 10 ni.com
Specifications
The following specifications are typical for the range –40 to 70 °C unless otherwise noted. All voltages are relative to COM unless otherwise noted.
Input Characteristics
Number of channels.......................... 32 digital input channels
Input type .......................................... Sinking
Digital logic levels
OFF state
Input voltage ........................≤5 V
Input current .........................≤150 μA
ON state
Input voltage ........................≥10 V
Input current .........................≥330 μA
Hysteresis
Input voltage ........................ 2 V min
Input current......................... 60 μA min
Input impedance................................ 30 k Ω ± 5%
© National Instruments Corp. 11 NI 9425 Operating Instructions and Specifications
I/O protection
Input voltage
8 channels ............................ 60 VDC max
32 channels .......................... 30 VDC max
Reverse-biased voltage
8 channels ............................ –60 VDC max
32 channels .......................... –30 VDC max
Hold time 1 ......................................... 0 μs min
Setup time 2 ........................................ 1 μs min
Update/transfer time 3 cRIO-9151 R Series
Expansion chassis....................... 8 μs max
All other chassis ......................... 7 μs max
1 Hold time is the amount of time input signals must be stable after initiating a read from the module.
2 Setup time is the amount of time input signals must be stable before reading from the module.
3 The update/transfer time is valid when the module is used in a CompactRIO system.
When used in other systems, driver software and system latencies impact this time.
NI 9425 Operating Instructions and Specifications 12 ni.com
MTBF ............................................... 1,256,699 hours at 25 °C;
Bellcore Issue 2, Method 1,
Case 3, Limited Part Stress
Method
Note Contact NI for Bellcore MTBF specifications at other temperatures or for MIL-HDBK-217F specifications.
Power Requirements
Power consumption from chassis
Active mode ............................... 410 mW max
Sleep mode ................................. 0.5
mW max
Thermal dissipation (at 70 °C)
Active mode ............................... 1.45 W max
Sleep mode ................................. 1 W max
Physical Characteristics
If you need to clean the module, wipe it with a dry towel.
Weight............................................... 147 g (5.2 oz)
© National Instruments Corp. 13 NI 9425 Operating Instructions and Specifications
Safety
Safety Voltages
Connect only voltages that are within the following limits.
Channel-to-COM .............................. 60 VDC max
Isolation
Channel-to-channel .................... None
Channel-to-earth ground
Continuous ........................... 60 VDC,
Measurement Category I
Withstand ............................. 1,000 V rms
, verified by a 5 s dielectric withstand test
Measurement Category I is for measurements performed on circuits not directly connected to the electrical distribution system referred to as MAINS voltage. MAINS is a hazardous live electrical supply system that powers equipment. This category is for measurements of voltages from specially protected secondary circuits. Such voltage measurements include signal levels, special equipment, limited-energy parts of equipment, circuits powered by regulated low-voltage sources, and electronics.
NI 9425 Operating Instructions and Specifications 14 ni.com
Caution Do not connect the NI 9425 to signals or use for measurements within Measurement Categories II,
III, or IV.
Hazardous Locations
U.S. (UL) .......................................... Class I, Division 2,
Groups A, B, C, D, T4;
Class I, Zone 2,
AEx nC IIC T4
Canada (C-UL) ................................. Class I, Division 2,
Groups A, B, C, D, T4;
Class I, Zone 2,
Ex nC IIC T4
Europe (DEMKO)............................. EEx nC IIC T4
Safety Standards
This product meets the requirements of the following standards of safety for electrical equipment for measurement, control, and laboratory use:
• IEC 61010-1, EN 61010-1
• UL 61010-1, CSA 61010-1
© National Instruments Corp. 15 NI 9425 Operating Instructions and Specifications
Note For UL and other safety certifications, refer to the
product label or the Online Product Certification section.
Electromagnetic Compatibility
This product meets the requirements of the following EMC standards for electrical equipment for measurement, control, and laboratory use:
• EN 61326 (IEC 61326): Class A emissions; Basic immunity
• EN 55011 (CISPR 11): Group 1, Class A emissions
• AS/NZS CISPR 11: Group 1, Class A emissions
• FCC 47 CFR Part 15B: Class A emissions
• ICES-001: Class A emissions
Note For the standards applied to assess the EMC of this
product, refer to the Online Product Certification
section.
Note For EMC compliance, operate this device with shielded cabling.
NI 9425 Operating Instructions and Specifications 16 ni.com
CE Compliance
This product meets the essential requirements of applicable
European Directives as follows:
• 2006/95/EC; Low-Voltage Directive (safety)
• 2004/108/EC; Electromagnetic Compatibility Directive
(EMC)
Online Product Certification
Refer to the product Declaration of Conformity (DoC) for additional regulatory compliance information. To obtain product certifications and the DoC for this product, visit ni.com/ certification , search by module number or product line, and click the appropriate link in the Certification column.
Shock and Vibration
To meet these specifications, you must panel mount the system.
Operating vibration
Random (IEC 60068-2-64)......... 5 g rms
, 10 to 500 Hz
Sinusoidal (IEC 60068-2-6) ....... 5 g, 10 to 500 Hz
© National Instruments Corp. 17 NI 9425 Operating Instructions and Specifications
Operating shock
(IEC 60068-2-27).............................. 30 g, 11 ms half sine,
50 g, 3 ms half sine,
18 shocks at 6 orientations
Environmental
National Instruments C Series modules are intended for indoor use only but may be used outdoors if installed in a suitable enclosure.
Refer to the manual for the chassis you are using for more information about meeting these specifications.
Operating temperature
(IEC 60068-2-1, IEC 60068-2-2) ..... –40 to 70 °C
Storage temperature
(IEC 60068-2-1, IEC 60068-2-2) ..... –40 to 85 °C
Ingress protection.............................. IP 40
Operating humidity
(IEC 60068-2-56).............................. 10 to 90% RH, noncondensing
Storage humidity
(IEC 60068-2-56).............................. 5 to 95% RH, noncondensing
NI 9425 Operating Instructions and Specifications 18 ni.com
Maximum altitude............................. 2,000 m
Pollution Degree (IEC 60664) .......... 2
Environmental Management
NI is committed to designing and manufacturing products in an environmentally responsible manner. NI recognizes that eliminating certain hazardous substances from our products is beneficial to the environment and to NI customers.
For additional environmental information, refer to the NI and the
Environment Web page at ni.com/environment . This page contains the environmental regulations and directives with which
NI complies, as well as other environmental information not included in this document.
Waste Electrical and Electronic Equipment (WEEE)
EU Customers At the end of the life cycle, all products
must be sent to a WEEE recycling center. For more information about WEEE recycling centers and National
Instruments WEEE initiatives, visit ni.com/ environment/weee .
© National Instruments Corp. 19 NI 9425 Operating Instructions and Specifications
⬉ᄤֵᙃѻક∵ᶧࠊㅵ⧚ࡲ⊩ ˄Ё
RoHS
˅
Ёᅶ᠋
National Instruments
ヺড়Ё⬉ᄤֵᙃ ѻકЁ䰤ࠊՓ⫼ᶤѯ᳝ᆇ⠽䋼ᣛҸ
(RoHS)
DŽ݇Ѣ
National Instruments
Ё
RoHS
ড়㾘ᗻֵᙃˈ䇋ⱏᔩ ni.com/environment/rohs_china DŽ
(For information about China RoHS compliance, go to ni.com/ environment/rohs_china
.)
Where to Go for Support
The National Instruments Web site is your complete resource for technical support. At ni.com/support you have access to everything from troubleshooting and application development self-help resources to email and phone assistance from
NI Application Engineers.
National Instruments corporate headquarters is located at
11500 North Mopac Expressway, Austin, Texas, 78759-3504.
National Instruments also has offices located around the world to help address your support needs. For telephone support in the
United States, create your service request at ni.com/support and follow the calling instructions or dial 512 795 8248. For
NI 9425 Operating Instructions and Specifications 20 ni.com
telephone support outside the United States, contact your local branch office:
Australia 1800 300 800, Austria 43 662 457990-0,
Belgium 32 (0) 2 757 0020, Brazil 55 11 3262 3599,
Canada 800 433 3488, China 86 21 5050 9800,
Czech Republic 420 224 235 774, Denmark 45 45 76 26 00,
Finland 358 (0) 9 725 72511, France 01 57 66 24 24,
Germany 49 89 7413130, India 91 80 41190000,
Israel 972 3 6393737, Italy 39 02 41309277, Japan 0120-527196,
Korea 82 02 3451 3400, Lebanon 961 (0) 1 33 28 28,
Malaysia 1800 887710, Mexico 01 800 010 0793,
Netherlands 31 (0) 348 433 466, New Zealand 0800 553 322,
Norway 47 (0) 66 90 76 60, Poland 48 22 3390150,
Portugal 351 210 311 210, Russia 7 495 783 6851,
Singapore 1800 226 5886, Slovenia 386 3 425 42 00,
South Africa 27 0 11 805 8197, Spain 34 91 640 0085,
Sweden 46 (0) 8 587 895 00, Switzerland 41 56 2005151,
Taiwan 886 02 2377 2222, Thailand 662 278 6777,
Turkey 90 212 279 3031, United Kingdom 44 (0) 1635 523545
© National Instruments Corp. 21 NI 9425 Operating Instructions and Specifications
National Instruments, NI, ni.com, and LabVIEW are trademarks of National Instruments Corporation. Refer to the Terms
of Use section on ni.com/legal for more information about National Instruments trademarks. Other product and company names mentioned herein are trademarks or trade names of their respective companies. For patents covering
National Instruments products/technology, refer to the appropriate location: Help»Patents in your software, the patents.txt
file on your media, or the National Instruments Patent Notice at ni.com/patents .
© 2004
–
2008 National Instruments Corp. All rights reserved.
373782E-01 Sep08
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 1 NI 9425 Operating Instructions and Specifications
- 3 Safety Guidelines
- 3 Safety Guidelines for Hazardous Voltages
- 4 Safety Guidelines for Hazardous Locations
- 5 Special Conditions for Hazardous Locations Use in Europe
- 6 Special Conditions for Marine Applications
- 7 Connecting the NI 9425
- 7 Figure 1. NI 9425 Pin Assignments
- 9 Figure 2. Connecting a Device to the NI 9425 (Three-Wire Device Shown)
- 10 Sleep Mode
- 11 Specifications
- 11 Input Characteristics
- 13 Power Requirements
- 13 Physical Characteristics
- 14 Safety
- 14 Safety Voltages
- 15 Hazardous Locations
- 15 Safety Standards
- 16 Electromagnetic Compatibility
- 17 CE Compliance
- 17 Online Product Certification
- 17 Shock and Vibration
- 18 Environmental
- 19 Environmental Management
- 20 Where to Go for Support