Omega Speaker Systems Dual Thermocouple Over the Internet iSE-TC User's Manual

Add to my manuals
60 Pages

advertisement

Omega Speaker Systems Dual Thermocouple Over the Internet iSE-TC User's Manual | Manualzz
User’s Guide
Flash Archive
http://192.168.1.200
Input 1:
122
67.8
Flash Archive
SP1_L(below)=044.5 F
F
SP1_H (above)=090.0 F
Archives_Done
Input 2:
77.7
Shop on line at
122
®
omega.com
e-mail: [email protected]
For Latest Product Manuals
omegamanual.info
®
9.0/Div
32
9.0/Div
03/01/2008 09:42:10
1 Day
1 Minute
1 Hour
1 Day
1 Week
1 Month
1 Year
(1 Hour/Div)
Main Menu
03/02/2008 09:42:10
32
Dual Thermocouple over the Internet
It is the policy of OMEGA to comply with all worldwide safety and EMC/EMI regulations that apply.
OMEGA is constantly pursuing certification of its products to the European New Approach Directives. OMEGA will add the CE mark
to every appropriate device upon certification.
The information contained in this document is believed to be correct, but OMEGA Engineering, Inc. accepts no liability for any
errors it contains, and reserves the right to alter specifications without notice.
WARNING: These products are not designed for use in, and should not be used for, patient-connected applications.
This device is marked with the international caution symbol. It is important to read the Setup Guide before installing or
commissioning this device as the guide contains important information relating to safety and EMC.
TABLE OF CONTENTS
Part 1: Introduction
1.1
Safety and EMC Considerations........................................................................2
1.2
Before You Begin ................................................................................................2
1.3
Description ..........................................................................................................2
Part 2: Hardware
2.1
Wall Mounting .....................................................................................................5
2.2
DIP Switches........................................................................................................6
2.3
Parts of the iSE Unit ...........................................................................................7
2.4
Disassembly Instruction ....................................................................................8
2.5
Network Communication Interfaces .................................................................9
2.5.1
10Base-T RJ-45 Pinout.........................................................................9
2.5.2
10Base-T Crossover Wiring.................................................................9
2.6
Relay and I/O Contact Wiring Connections .....................................................9
2.7
DC Power Input Wiring Connections ................................................................9
2.8
Running on Battery Power ..............................................................................10
2.9
Flash Memory Format ......................................................................................11
Part 3: Network Configuration
3.1
Network Protocols ...........................................................................................12
3.2
Ethernet (MAC) Address ..................................................................................12
3.3
DHCP
.............................................................................................................13
3.4
DNS
.............................................................................................................13
3.5
IP Address ........................................................................................................13
3.5.1
Default IP Address..............................................................................14
3.6
Port Number ......................................................................................................14
Part 4: Operations
4.0
Testing the Connection ....................................................................................15
4.1
iConnect Software.............................................................................................16
4.2
Setting a new IP Address over the Network ..................................................18
4.3
Setup and Operation using the iSE Web Page ..............................................19
4.3.1
Read Sensor........................................................................................20
4.3.1.1 Java Runtime Environment 1.4 Setup Instructions.............20
4.3.1.2 Java Runtime Environment 1.5 (5.0) Setup Instructions ....21
4.3.1.3 Browser Proxy Selection ........................................................21
4.3.2
Adjustable Chart .................................................................................22
4.3.3
Retrieving Data from Flash ................................................................23
4.3.4
Access Control ..................................................................................24
4.3.5
Configuration ......................................................................................25
4.3.6
Sensor Parameter ...............................................................................31
4.4
Telnet Setup ......................................................................................................34
4.5
HTTPget Program..............................................................................................34
4.5.1
HTTPget using Port 1000 ...................................................................35
4.5.2
HTTPget and ARP to setup Device IP Address ...............................37
4.6
ARP Protocol .....................................................................................................38
4.7
iLog Software ....................................................................................................39
4.8
Mail Notifier Software .......................................................................................40
4.8.1
Installation...........................................................................................40
4.8.2
Program Options Setup and Configuration ....................................41
4.8.3
Device Setting Setup and Configuration ..........................................42
Part 5: Specifications
.............................................................................................................43
Part 6: Factory Preset Values ......................................................................................................45
Part 7: Approval Information ........................................................................................................46
Appendix A
Glossary.............................................................................................................47
Appendix B
IP Address ........................................................................................................48
Appendix C
IP Netmask.........................................................................................................49
Appendix D
ASCII Chart .......................................................................................................50
ASCII Chart Control Codes .............................................................................51
Appendix E
iLog Error Messages.........................................................................................52
i
LIST OF FIGURES:
Figure 1.1
Figure 2.1
Figure 2.2
Figure 2.3
Figure 2.4
Figure 2.5
Figure 2.6
Figure 2.7
Figure 2.8
Figure 2.9
Figure 2.10
Figure 3.1
Figure 3.2
Figure 3.3
Figure 4.1
Figure 4.2
Figure 4.3
Figure 4.4
Figure 4.5
Figure 4.6
Figure 4.7
Figure 4.8
Figure 4.9
Figure 4.10
Figure 4.11
Figure 4.12
Figure 4.13
Figure 4.14
Figure 4.15
Figure 4.16
Figure 4.17
Figure 4.18
Figure 4.19
iSE and iLD Big Display on the Ethernet Network ..............................4
Mounting ................................................................................................5
Dimensions ............................................................................................5
DIP Switch Location..............................................................................6
Parts of the iSE Unit...............................................................................7
Opening the Unit ....................................................................................8
RJ45 Pinout ............................................................................................9
10Base-T Crossover Cable Wiring .......................................................9
Relay and I/O Contact Connections ....................................................9
Battery and S5 Jumper Location .......................................................10
Chart of Simulated Data.......................................................................11
Labeling ................................................................................................12
DIP Switch on the Bottom Side of iSE................................................13
Telnet Login into the iSE .....................................................................14
Pinging the iSE from MS-DOS Prompt ..............................................15
Assigning an IP Address using iConnect .........................................16
Accessing the iSE’s Home Page Menu ..............................................17
Access Control ...................................................................................18
iSE Home Page ....................................................................................19
LOGIN and ADMINISTRATOR Passwords ........................................19
Read Sensor .........................................................................................20
Adjustable Chart...................................................................................22
iFlash Download Utility........................................................................23
Access Control ....................................................................................24
Configuration ......................................................................................26
Sensor Parameters - Temperature .....................................................31
Sensor Parameters - Input Contact ...................................................32
Remote End Char .................................................................................33
ARP Commands and Responses .......................................................38
iLog Software Logging Data................................................................39
iSE Mail Notifier Main Window ............................................................40
iSE Mail Notifier Profile Setup.............................................................41
iSE Mail Notifier Device Setting .........................................................42
Table 2.1
Parts of iSE Unit.....................................................................................7
LIST OF TABLES:
ii
NOTES, WARNINGS and CAUTIONS
Information that is especially important to note is identified by the following labels:
• NOTE
• WARNING or CAUTION
• IMPORTANT
• TIP
NOTE: Provides you with information that is important to successfully
setup and use the iSE.
CAUTION: Tells you about the risk of electrical shock.
CAUTION: Risk of danger. Tells you of circumstances or practices
that can effect the instrument’s functionality and must refer to
accompanying documents.
TIP: Provides you helpful hints.
•
•
•
•
•
•
•
•
•
•
•
•
•
FEATURES
Two Temperature Channels
Web Server
Virtual Chart Recorder
Two Relay Alarms
Two Contact Closures
Accurate Readings
Password Protection
Email Alarms
Data Logging
2, 4 or 8M bytes Flash Memory Card
Real-Time Clock
LCD Display
UPS / Stand-alone 9Vdc Battery
1
PART 1
INTRODUCTION
1.1 Safety and EMC Considerations
Refer to the CE Approvals Section.
EMC Considerations
• Whenever EMC is an issue, always use shielded cables.
• Never run signal and power wires in the same conduit.
• Use twisted-pair wires for signal connections.
• Install Ferrite Bead(s) on signal wires close to the instrument if EMC problems persist.
Failure to follow all instructions and warnings may result in injury!
1.2 Before You Begin
Inspecting Your Shipment: Remove the packing slip and verify that you have received
everything listed. Inspect the container and equipment for signs of damage as soon as
you receive the shipment. Note any evidence of rough handling in transit. Immediately
report any damage to the shipping agent. The carrier will not honor damage claims
unless all shipping material is saved for inspection. After examining and removing the
contents, save the packing material and carton in the event reshipment is necessary.
Customer Service: If you need assistance, please contact the Customer Service
Department nearest you.
Manuals, Software: The latest Operation Manual as well as free configuration software
(iConnect), datalogging software (iLog), download utility (iFlash), and Mail Notifier are
available at the website listed on the cover page of this manual or on the CD-ROM
enclosed with your shipment.
1.3 Description
Web-based Remote Surveillance of Temperature and Security
The iSE environmental monitor provides Web-based remote surveillance of
environmental conditions in critical HVAC applications such as computer server rooms,
clean rooms, laboratories, museums, warehouses, or any remote facility. View and
record Temperature on two independent thermocouple channels, over an Ethernet
network or the Internet with no special software—just a Web browser.
EMAIL ALARMS -- The device can trigger an alarm if temperature goes above or below
a set point that you determine. Your alarm can be sent by email to a single user or to a
group distribution list, including text messages to cell phones and PDA’s.
PHYSICAL THREATS -- The iSE includes screw terminals for two contact closures that
work with common alarm sensors. You can instruct the iSE monitor to send an alarm if a
door is opened, a window is broken, or a fire sprinkler goes off.
POWER FAILURE -- The iSE monitor can trigger an alarm if the AC power fails. The
iSE monitor will continue to collect data for ten days powered by a standard 9 Volt
alkaline battery (included). The data is stored in nonvolatile flash memory and can later
be downloaded over the Ethernet.
2
LOCAL ALARMS -- The iSE includes two 1.5 Amp output relays that are controlled by
the alarm conditions you select. The relays can trigger flashing lights and a siren for
example to alert personnel near the scene.
With the easy Web-based setup page, the two relays can be programmed for two
temperature inputs, and high or low set points, as well as alarm conditions triggered by
contact closures. The relays can also be programmed to turn off when conditions return
to normal, or programmed to remain latched and require a manual reset.
VIEW CHARTS AND GRAPHS ON THE WEB -- The iSE serves Active Web Pages to
display real time readings, display charts of temperature, or log data in standard data
formats for use in a spreadsheet or data acquisition program such as Excel or Visual
Basic.
The virtual chart viewed on the web page is a JAVA™ Applet that records a chart over
the LAN or Internet in real time. With the iSE, there is no need to invest time and money
learning a proprietary software program to log or chart the data.
Chart scales are fully adjustable on the fly. For example, the chart can display one
minute, one hour, one day, one week, one month or one year. Temperature can be
charted across the full span or within any narrow range.
You can chart temperature from one thermocouple, two thermocouples, and/or the
differential between the two. The iSE can take thermocouple types J, K, T, E, R, S, B, C,
N and L measuring temperatures up to 1,820°C (3,308°F). The iSE can display and chart
absolute measurements in two locations and a differential measurement between the two
locations. The iSE comes with a pair of type K thermocouples.
LINK TO WEB CAM OR IP CAMERA -- The Web page includes a link to a “Web Cam”
or “IP camera” (not included). If you get a message about an alarm condition, you can
quickly click on the link to view the actual scene over the Internet.
FLASH MEMORY -- The iSE records data on a removable 2-MByte Flash Memory card
(included) that can store one full year of readings taken at one-minute intervals (or two
months of readings taken at ten second intervals).
Up to four years of temperature readings can be stored on the optional 8 MByte card.
Even if the Ethernet network fails, data will continuously record on the built-in nonvolatile
flash memory.
Installation and operation of the iSE monitor requires no special training, tools, or
software. The device connects to any Ethernet network with standard cable and is
powered by a universal AC adapter which is supplied with the product.
AWARD-WINNING TECHNOLOGY -- The iSE is simple to install and use, and features
award-winning iServer technology that requires no special software except a Web
Browser.
The iSE connects to an Ethernet Network with a standard RJ45 connector and sends
data in standard TCP/IP packets. It is easily configured with a simple menu using a Web
Browser and can be password protected. From within an Ethernet LAN or over the
Internet, the user simply types its IP address or an easy to remember name such as
"Cleanroom 5" or "Server Room" in any Web Browser, and the iSE serves a Web Page
with the current readings.
3
TYPICAL APPLICATIONS -- The iSE is great for monitoring and recording temperature
in applications such as: clean rooms, computer rooms, HVAC systems, pharmaceutical
and food processing and storage, hospitals, laboratories, semiconductor fabs, electronic
assembly, warehousing, museums, manufacturing, greenhouses, farm animal shelters,
and many more.
The following example illustrates how you can hookup an iSE, a network display (iLD),
and a network camera to your network:
Figure 1.1 iSE and iLD Big Display on the Ethernet Network
4
PART 2 HARDWARE
2.1 Wall Mounting
Position unit where required. Mark and drill the two #4 screw holes.
After bracket is mounted on the wall, align back of unit over the three bracket clips, once
engaged, slide downward, the unit will snap in place.
For extra security, you may screw the unit onto the bracket. Remove cover (see Section
2.4) and screw a #4 x 1/4” long self-tapping screw through the case and bracket.
DRILL 0.125 [3.17]
USE TWO, #4
FLAT HEAD SCREWS
TO MOUNT BRACKET
ADDITIONAL MOUNTING OPTIONTO RETAIN UNIT TO MOUNTING BRACKET
USE #4 X 1/4" LONG SELF-TAPPING SCREW
1.36 [34.4]
3.47 [88.1]
CLIPS (3)
0.59 [14.9]
1.81 [46.1]
UNIT OUTLINE
1.50 [38.1]
5.13 [130.2]
REAR WIRE
ENTRY AREA
1.50 [38.1]
0.94 [23.8]
It is recommended that
you ground your
unit by wrapping a wire
around the case’s
bottom screw or by
connecting a wire to
the Return/Ground
position of the relay
connector (see Figure
2.8 and 3.1).
0.24 [6.1]
Figure 2.1 Mounting
Figure 2.2 Dimensions
5
2.2 DIP Switches
The iSE is shipped with all DIP switches in "OFF" position.
DIP Switch Usage
1) N/C - not used
2) To change to default factory settings
3) To enable/disable DHCP
4) N/C - not used
Figure 2.3 DIP Switch Location
To set the iSE to factory default settings, slide DIP switch #2 to ON position. Power the
iSE on and wait about 10 seconds until the iSE fully boots up. Set the DIP switch #2
back to OFF position (it does not matter if the iSE is powered ON or OFF, just make
sure that the DIP switch is set to OFF, otherwise, every time the unit is power-cycled
the factory settings will take over.
To enable the DHCP, besides using DIP switch #3, set the iSE’s IP address to 0.0.0.0.
An iSE with IP address of 0.0.0.0 will request an IP address, gateway address, and
subnet mask from the DHCP server over the Ethernet
6
2.3 Parts of the iSE Unit
Figure 2.4 Parts of the iSE Unit
Table 2.1 Parts of iSE Unit
ETHERNET
RESET
ACTIVITY
NET LINK
RJ45 interface for 10BASE-T connection.
Button: Used for power reseting the iSE.
LED (Red) Blinking: Indicates network activities (receiving or sending packets).
LED (Green) Solid: Indicates good network link.
DIAGNOSTICS LED (Yellow) Blinking: Indicates transmitting data from iSE to flash memory
card. When DHCP enabled, it remains solid until DHCP IP address is received.
LED (Green) Blinking: Indicates receiving data by the iSE from flash memory.
°C/°F
TIME
BKLT
Button: Change display units of measurement from °C to °F
Button: Change display from DATE and TIME to TEMP
Button: Display Back Light
When using the small push buttons, hold the button until “WAIT” is displayed on the LCD and
then release.
7
2.4 Disassembly Instruction
You will need to open the unit for one of the following reasons:
• To wire relay and I/O contact connectors. (Refer to Section 2.6).
• To connect or replace the battery. (Refer to Section 2.7).
• To change S5 jumper. In the absence of AC power, and if S5 is installed, the LCD
Backlight and iSE board will be on and running on the battery power. (Refer to
Section 2.7).
Disconnect the power supply before proceeding.
Remove cover by removing 2 screws on each side.
COVER
FLASH
CARD
BATTERY &
S5 JUMPER
LOCATION
B
2M
MOUNTING
SCREWS (2)
RELAY
CONNECTOR
I/O CONTACT
CONNECTOR
THERMOCOUPLE
CONNECTORS
TRAY
ETHERNET &
DC POWER
CONNECTORS
Figure 2.5 Opening the Unit
8
2.5 Network Communication Interfaces
2.5.1 10Base-T RJ-45 Pinout
The 10BASE-T Ethernet network
(RJ45) system is used in the iSE for
network connectivity. The 10 Mbps
twisted-pair Ethernet system
operates over two pairs of wires.
One pair is used for receiving data
signals and the other pair is used
for transmitting data signals. This
means that four pins of the eight-pin
connector are used.
Figure 2.6 RJ45 Pinout
Pin
1
2
3
4
5
6
7
8
Name
+Tx
-Tx
+RX
N/C
N/C
-Rx
N/C
N/C
Description
+ Transmit Data
- Transmit Data
+ Receive Data
Not Connected
Not Connected
- Receive Data
Not Connected
Not Connected
2.5.2 10Base-T Crossover Wiring
When connecting the iSE directly to the computer’s network port, the transmit data pins of the
computer should be wired to the receive data pins of the iSE, and vice versa. The 10Base-T
crossover cable with pin connection assignments are shown below.
Use straight through cable for connecting the iSE to an Ethernet hub. The ports on
the hub are already crossed.
2.6 Relay and I/O Contact Wiring Connections
To access the Relay and I/O Contact Connectors you
must remove the cover, refer to Section 2.4.
1
3
4
RTN
NO2
2
It is recommended that you
ground your unit by
connecting a wire to the
Ground/Return position of the
connector or by wrapping a wire
around the case’s bottom screw.
Refer to Figure 3.1 for location.
OUTPUT
6
IN2
5
INPUTS
IN1
4
COM1
3
COM2
2
RTN
9 Vdc
1
RELAY 1
NO1
RELAY 2
Figure 2.7 10Base-T
Crossover Cable Wiring
Figure 2.8 Relay and I/O Contact Connections
2.7 DC Power Input Wiring Connections
A universal ac power adapter with 9 Vdc output is included with your unit. It can be plugged in
at the bottom of unit (See Figure 2.3).
The unit can also be powered on the Relay Connector Pin 1 and Pin 2 (See Figure 2.8).
When using these pins to power the iSE, make sure the power adapter is not used.
9
2.8 Running on Battery Power
To access the Battery and S5 jumper you must remove the cover, refer to Section 2.4.
When you first connect the battery, without the AC power adaptor, the unit will be in “Sleep
Mode”, in order to save power, and the LCD will display “Flash Standby” (provided that S5
jumper is not installed). When battery is installed, plug the AC adaptor into unit and push the
Flash Reset Button (refer to Figure 2.4). Unit is now ready to be configured for recording the
data. Also, if the AC adaptor is unplugged while the unit is recording, the battery will take
over and recording will continue.
Battery and S5 jumper installed: if there is a power outage the iSE board will be fully
functional including Ethernet and the LCD backlight “ON”, for approximately 1 hour.
You need to make sure that the LCD/PWR field on the Configuration page of the iSE is set to
UPS (see Section 4.3.5.F)
Battery installed and S5 jumper in storage position (Factory Default of S5): if there is a power
outage the LCD Backlight and Ethernet will not run, but the unit will be collecting and storing
data for approximately 10 days.
If you want to move the unit to a different location, remove the AC adapter; the
installed battery will keep the recording alive until the AC adapter is plugged
back in.
9VDC BATTERY
INSULATOR COVER
TRAY
S5 PINS
REMOVE BATTERY CLIP
INSULATOR COVER AND
STORE AGAINST BATTERY
WHEN BATTERY IS BEING USED.
KEEP INSULATOR COVER
ON BATTERY CLIP
WHEN BATTERY IS NOT
BEING USED
Figure 2.9 Battery and S5 Jumper Location
10
2.9 Flash Memory Format
A 2 Meg flash memory card is included with your product. This memory card is already
formatted; however, the following procedure describes how to format your memory card.
Once the memory card is formatted, all the data that had previously been
recorded will be replaced by simulated test data (see Figure 2.10).
1)
2)
3)
4)
5)
6)
8)
9)
Unplug the AC adaptor from the unit.
Hold down the ºC/ºF button and connect the AC adaptor back into the unit.
Release the ºC/ºF button.
You will see the following message appear on the LCD: *ºWAITº* *FLASH*.
Wait for about 60 seconds and a new message should appear: *ºWAITº* *OKAY*.
Press the ºC/ºF button once and this message will appear: DATA-RECORD-TEST.
Press the TIME button and this message will appear: DATA RECORD TEST DATA RECORD TEST.
Again, press the ºC/ºF button, the firmware version will appear, followed by
*OKAY*.
Unplug the AC adaptor and plug it back in. The flash memory card is now
formatted. To verify whether the formatting was completed correctly, you should be
able to see the following graph on the WEB server’s “Chart” page.
Figure 2.10 Chart of Simulated Data
11
PART 3
NETWORK CONFIGURATION
3.1 Network Protocols
The iSE can be connected to the network using standard TCP/IP protocols.
It also supports ARP, HTTP (WEB server), DHCP, DNS and Telnet protocols.
3.2 Ethernet (MAC) Address
MAC (Media Access Control) address is your computer's unique hardware number.
When you're connected to the LAN from your computer, a correspondence table relates
your IP address to your computer's physical (MAC) address. The MAC address can be
found on a label attached to your device and contains 6 bytes (12 characters) of
hexadecimal numbers XX:XX:XX:XX:XX:XX hex
For example: 0A:0C:3D:0B:0A:0B
Remove the small label with the default IP address and there will be room to put
your IP address. See Figure 3.1
4 N/C
3 DHCP
2 DEFAULT
1 N/C
1
JTAG CONNECTOR
OFF
ON
SCREW FOR
GROUNDING UNIT
REMOVE DEFAULT IP ADDRESS LABEL
AND PUT NEW CUSTOMER'S IP ADDRESS
iSE’S VERSION #
Figure 3.1 Labeling
12
MICROPROCESSOR
VERSION #
MAC ADDRESS LABEL
IN HEX CODE
3.3 DHCP
DHCP, Dynamic Host Configuration Protocol enables individual computers or devices to
extract their IP configurations from a server (DHCP server). If the DHCP is enabled on
your iSE, as soon as the iSE is connected to the network, there is an exchange of
information between DHCP server and the iSE. During this process the IP address, the
Gateway address, and the Subnet Mask will be assigned to the iSE by the DHCP server.
Note that the DHCP server must be configured correctly to do such assignment.
If fixed or static IP address is desired, the DHCP must be disabled. The iSE is shipped
with DHCP disabled (factory default). The DHCP can be enabled by setting the DIP
switch # 3 to the “ON” position (refer to Figure 3.2).
DIP switch # 3 shown
in “ON” position
OFF
43
2
1
ON
Figure 3.2 DIP Switch on the Bottom Side of iSE
3.4 DNS
DNS, Domain Name System enables individual computers and devices to be recognized
over a network based on a specific name instead of an IP address. For example, instead
of having to use http://192.168.1.200 (IP address), you would use only http://eis03ec or
any eight character name stored as Host Name under the Access Control page in the
iSE Home Page. The default DNS name for an iSE is "eis" followed by the last four
digits of the MAC address of that particular iSE.
1. It is very important to communicate with the network administrator in order to
understand the DHCP and its existing configurations on the host server,
before enabling the DHCP on the iSE.
2. The iSE is shipped with a default static IP address of
192.168.1.200 and Subnet Mask of 255.255.255.0.
3. On Novell networks or Windows 2000 Server where the DCHP is an updated
function of DNS, this feature may be beneficial since a particular name can
be assigned eliminating the need for the IP address, as described in
Section 3.4.
3.5 IP Address
Every active device connected to the TCP/IP network must have a unique IP address.
This IP address is used to build a connection to the iSE. Every computer using TCP/IP
should have a unique 32-bit address. It is divided into two portions, the network ID and
the host ID. For instance, every computer on the same network uses the same network
ID. At the same time, all of them have a different host ID. For more details about the IP
address see Appendix B.
13
3.5.1 Default IP Address
The iSE is shipped with a default IP address set to 192.168.1.200 and Subnet Mask of
255.255.255.0. If you are going to use a Web browser or Telnet program to access the
iSE using its default IP address, make sure that the PC from which you’re establishing
the connection has an IP address that is in the same range as the iSE’s IP address
(192.168.1.x, where x can be any number from 1 to 254.
Your PC’s IP address cannot be the same as the iSE’s IP address).
You also need to make sure that your PC’s Subnet Mask is 255.255.255.0. This is a
good way to access the iSE over the network and make any configuration changes
needed. If 192.168.1.200 is already in use on your network, use an Ethernet crossover
cable between your computer and the iSE to change the IP address or any other settings
within the iSE.
3.6 Port Number
All TCP connections are defined by the IP address and a port number. A port number is
an internal address that provides an interface between an application running on your
computer and the network through the TCP/IP protocol.
There are three default TCP socket port numbers assigned to the iSE:
1. Port (socket) number 1000 when using HTTPget program.
2. Port (socket) number 2000 when trying to access the sensor (probe) connected to
the port of the iSE to receive data.
3. Port (socket) number 2002 when trying to access the iSE itself for Power
Recycling the iSE remotely. This can be done using Windows standard Telnet
application.
Power recycling the iSE can also be done through the iSE’s Web Server (see Section
4.2).
Telnet stands for Telecommunications Network, is a protocol that provides a way for
users (or clients) to connect to computers (or servers) on a network, whether in the next
building or across the world.
Example: C:\>Telnet 192.168.1.200 2002
You will then get the following screen.
Type "reset"
to reboot
the server
The default
Admin. Password
C:\
Telnet 192.168.1.200
Firmware Version x.xx
Admin. Password:00000000
Admin. Login Successful
reset
The unit will reset in 5 seconds
_
Figure 3.3 Telnet Login into the iSE
You can open a Telnet session using other terminal emulation programs like Tera Term
Pro (downloadable from the internet), which is a free software for MS-Windows. It
supports VT100 emulation, Telnet connection and serial com port connections.
14
PART 4
OPERATIONS
This iSE can be used and configured in several ways, depending on user’s preference
and network setup. It can be configured using a Web browser, like Netscape or Internet
Explorer. It can also be configured using the iConnect Configuration Software.
If DHCP and DNS servers are used, the connection is very simple, no need to find the
right IP address or watch for network conflicts, these are all done for you by your network
DHCP and DNS server. All that is left for you to do, is to enable DHCP on the iSE (see
Section 2.2) and use a straight network cable to connect the iSE to a hub and power it
up.
If DHCP is not the preferred method, you can configure your PC’s network connection with
an IP address of 192.168.1.x that is in the same range as the iSE’s default IP address
(192.168.1.200) and connect to the iSE using a cross-over network cable between your
PC’s network port and the iSE. After you’re done with configuring the iSE, you can always
set your PC back to its original settings.
On your computer, from the MS-DOS Prompt window type "ping 192.168.1.200” and
press Enter. If DHCP and DNS servers are used type “ping eisxxxx”, where xxxx are the
last four digits of the iSE’s MAC address, located on the back of the device. You should get
a reply as shown in Figure 4.1.
You can use the iSE host name (eisxxxx) instead of its IP address only if your
DHCP server is configured to communicate with your DNS. Please consult with
your IT department for details.
4.0 Testing the Connection
C:\>ping eis03ec
Pinging eis03ec with 32 bytes of data:
Reply
Reply
Reply
Reply
from
from
from
from
eis03ec:
eis03ec:
eis03ec:
eis03ec:
bytes=32
bytes=32
bytes=32
bytes=32
time=15ms TTL=60
time=8ms TTL=60
time=8ms TTL=60
time=8ms TTL=60
Pinging statistics for eis03ec:
Packets: Sent=4, Received=4, Lost=0 (0% loss)
Approximate round trip times in milli-seconds:
Minimum=8ms, Maximum=15ms, Average=9ms
Figure 4.1 Pinging the iSE from MS-DOS Prompt
This proves that the connection is proper and you can get into configuration or run mode
using the Telnet or Web browser.
15
4.1 iConnect Software
The iSE may also be assigned an IP Address by using the iConnect software.
a) Download the iConnect software from the website listed in this manual.
b) Install iConnect software on a networked PC. This software is compatible with
Windows 95, 98, NT, 2000, and XP.
c) Use iConnect to assign an IP address to the iSE and access its web pages for
configuration. You can also use any standard web browser to access the iSE’s web
pages. Consult with your IT department for obtaining an IP address.
1)
2)
3)
4)
5)
6)
7)
8)
Figure 4.2 Assigning an IP Address using iConnect
Place the IP address in this box.
Take the MAC address from the label attached to the bottom of the iSE and place it
in this box.
Click here to send the above IP address to the iSE.
After the IP address is assigned to the iSE, click here to access it’s web pages.
Click here to Ping the iSE whose IP address is shown in the IP address box.
Click here to find all the iSE’s on your network .
The IP addresses for the iSE’s found by the iConnect will be listed here.
These fields indicate the IP address and the subnet mask of the PC on which the
iConnect is running.
16
4.1 iConnect Software (continued)
d)
To access the iSE for Configuration:
Click on the “View Webpage” button, you will access the iSE’s home page, refer to
Section 4.3 for details.
iSERVER HOME PAGE
Read Sensor
Chart
Access Control
Configuration
Camera Location
Figure 4.3 Accessing the iSE’s Home Page Menu
17
4.2 Setting a New IP Address over the Network
Besides using the iConnect software, you may use the iSE’s default IP address to
access it and assign a new IP address to it.
The iSE is shipped with a default IP address of 192.168.1.200 and Subnet Mask of
255.255.255.0. You can configure your PC’s Network connection with an IP address that
is in the same range as the iSE’s IP address (192.168.1.x) and connect to the iSE using a
crossover network cable between your PC and the iSE.
With this completed, you can go to the DOS-Prompt and ping 192.168.1.200. If you
receive responses back (Figure 4.1), you can go to a Web browser and type in
http://192.168.1.200 and it will take you to the iSE’s main web page.
Select Access Control , button, you’ll be asked for the password. The default LOGIN
password is "12345678" and the ADMINISTRATOR password is "00000000", then you
should be on the Access Control page were you can simply type in the desired Static IP
address, and click Save.
ACCESS CONTROL
Address
http://192.168.1.200
ACCESS CONTROL
Login Password: 12345678
Admin Password: 00000000
Host Name: eis21d9
MAC Address: 00:03:03:00:21:D9
IP Address: 192.168.1.200
Gateway Address: 0.0.0.0
Subnet Mask: 255.255.255.0
Camera IP: 0.0.0.0
Camera Label:
Camera Location
Click the following button to activate the new settings.
Save Reset
Power Recycle
Main Menu
Figure 4.4 Access Control
For the IP address to take effect, the iSE needs to be turned OFF/ON. Clicking the
“Power Recycle” button will turn the iSE OFF and ON. Pressing the physical button
marked “RESET” on the iSE does the same thing.
You can now connect the iSE to an Ethernet hub using a straight through cable, power it
up, and follow the ping routine mentioned in the previous section.
18
4.3 Setup and Operation Using the iSE Web Page
• Start your web browser.
• From the browser you type http://eisxxxx using the last four-digits from the MAC
address label located on the device if DHCP and DNS are used. If a static IP address
is used, then simply type http://x.x.x.x, where x.x.x.x is the iSE’s IP address.
• The Home Page, shown in Figure 4.5, will be displayed.
Figure 4.5 iSE Home Page
In order to access certain menu items of the Home Page, users may be
prompted for a password, as shown in Figure 4.6.
LOGIN
http://192.168.1.200
ADMINISTRATOR
http://192.168.1.200
LOGIN
ADMINISTRATOR
Figure 4.6 LOGIN and ADMINISTRATOR Passwords
There are 2 different access levels:
1. ADMINISTRATOR Password (administrator) allows certain groups and individual users to
access and modify "entire" iSE parameters without any restrictions.
The default password is 00000000. This password can be up to 16 alphanumeric casesensitive characters.
2. LOGIN Password (operator) allows users to access and modify all of the iSE’s
parameters, except “Access Control” which requires an Administrator
password. The "Read Sensor" does not require a password.
The default password is 12345678. This password can be up to 16 alphanumeric
case-sensitive characters.
19
4.3.1 Read Sensor
• Click on Read Sensor . In a few seconds the following page (Figure 4.7) will appear
with all default values of 100.00. Then the actual readings of Temperature will display.
• This page automatically updates the Temperature readings as well as the Differential
values.
• Click on Main Menu to return to Home Page.
While accessing the Read Sensor page, If a blank screen appears without any
“java application running” or image of a “Java logo”, please verify you have the
latest Java Runtime Environment installed and configured according to the
following instructions. If you do not have Java Runtime Environment, you may
download it from our website or contact the Customer Service Department
nearest you.
Read Sensor
http://192.168.1.200
Engineering
Temperature 1
Temperature 2
Differential
76.37 F
39.66 %
36.71 F
Input Contact 1
Input Contact 2
Output Signal
Main Menu
Both
Both
Ch 1
Ch 2
Active
Normal
Active High
Figure 4.7 Read Sensor
4.3.1.1 Java Runtime Environment 1.4 Setup instructions
1. Go to your computer's Control Panel. Open the Java Plug-in
2. Select the "Cache" Tab
Un-check the "Enable Caching" box
3. Select the "Proxy" Tab. Follow these Browser Proxy Selection instructions
below. (Generally, un-check the box if accessing an iSE on your local network
and check the box for access from your internal network to the internet.)
4. Refresh or restart the webpage.
20
4.3.1.2 Java Runtime Environment 1.5 (5.0) Setup instructions
1. Go to your computer's Control Panel. Open the Java Plug-in
2. Click on "Settings" & "View Applets" in the "General" tab.
3. Select the "Settings" button on the General Tab
Un-check the "Enable Caching" box. Then close dialog box to show the General Tab
again
4. Select the "Network Settings" button on the General Tab.
Proceed to the Browser tab. Follow the Browser Proxy Selection instructions
below.You should either select the "Use Browser Settings" option or the "Direct
Connection" option depending on the network connections between your computer
and the iSE product. (Generally, select "Direct Connection" if accessing an iSE on
your local network and select "Use Browser Settings" option for access from your
internal network to the internet.)
5. Refresh or restart the webpage.
4.3.1.3 Browser Proxy Selection
Accessing iSE units within your internal network
• Usually when the computer and iSE are on an internal network, you will not use Proxy
server access.
• You should un-check the "Use Browser Settings" option on the "Proxy" tab.
Accessing iSE units using the internet
• Often the web browser will use Proxy server access to the internet. In such cases, the
default Java runtime settings on the "Proxy" tab should suffice. The default setting is the
"Use Browser Settings" option.
• If the default proxy setting doesn't work, then you may have a situation where the proxy
settings of the web browser are incorrect.
Diagnostics:
If the web page of the iSE appears, then the HTTP Proxy is working fine.
If the data isn't updated on the iSE upon selecting the Read Sensor web page, there may be a
problem with access through a winsock proxy server. In such cases your network administrator
will need to provide the winsock proxy server and port #s. (If the administrator requires
knowledge of the port # required on the iSE, the value is 2003).
These values should be entered into the Socks line on the "Proxy" tab (of the Java Plugin control
panel) or into the "connections" tab on the View,Internet Options dialog and make sure that the
Proxy tab shows that the "Use Browser Settings" option is not selected (i.e. when you specify
proxy connections in the Java Plugin control panel.
Accessing iSE units over Peer-to-Peer network
A simple peer-to-peer network is setup by disconnecting from the main network (as users will
often do when trying to do initial setup of the iSE) and then connecting the iSE to another
computer using a ethernet hub, an ethernet switch, or a Cross-over cable connection.
Often when using a peer-to-peer network, the Java plugin and the web browser (such as Internet
Explorer) have internet connections configured to connect through proxy servers. In such case,
you will need to simply assign the final IP address on this peer to peer network and then view the
iSE charts after connecting the iSE into the regular network. Otherwise you can disable the Java
plug-in's "Use Browser Settings" temporarily and then reconfigure the Java plug-in settings for
regular network access after testing the iSE chart access on your peer-to-peer network.
The "Use Browser Settings" should not be selected. And the HTTP and Socks proxy entries
should be blank. Also, setup the internet browser so that proxy servers are disabled.
Java and the Java Coffee Cup Logo are trademarks or registered trademarks of Sun Microsystems, Inc. in the U.S. and other countries."
21
4.3.2 Adjustable Chart
• Click on Chart , the following page (Figure 4.8) should appear. The Java™ Applet
graph displays Temperature values which can be charted across the full span or within
any narrow range (such as 20 to 30ºC). The time-base can display one minute, one
hour, one day, one week, one month or one year.
If a blank screen appears without any “java application running” or image of a
“Java logo”, please verify you have the latest Java Runtime Environment
installed and configured according to the instructions (refer to Section 4.3.1.1).
If you do not have Java Runtime Environment, you may download it from our
website or contact the Customer Service Department nearest you.
User selectable
temperature units: F or C
Actual Input 1
Temperature
User selectable
temperature range
Number of degrees
per division
based on
temperature range
User selectable
temperature range
Archives_Inactive:
1minute or 1hour
Archives_Enable:
1Day, 1Week, 1Month, or 1Year
Archives_Done:
charting starts for the “time” selected in the
lower pull down menu
Title
Flash Archive
http://192.168.1.200
Input 1:
122
67.8
Actual Input 2
Temperature
Flash Archive
SP1_L(below)=044.5 F
SP1_H (above)=090.0 F
F
Archives_Done
Input 2:
77.7
9.0/Div
32
03/01/2008 09:42:10
Start Time
User selectable time base
1 minute, 1 hour, 1 day,
1 week, 1 month, or 1 year
122
Setpoint boundary
9.0/Div
1 Day
1 Minute
1 Hour
1 Day
1 Week
1 Month
1 Year
(1 Hour/Div)
03/02/2008 09:42:10
Main Menu
32
End Time
Figure 4.8 Adjustable Chart
To avoid any miscommunications when downloading the stored data from the
“Chart” page, it is strongly recommended to let the recording run for a minimum
of 3 minutes if the time interval is 10 seconds (from “Configuration” page), and
15 minutes if the time interval is 1 minute.
22
4.3.3 Retrieving Data from Flash
To retrieve and graph the data that is stored in the Flash Memory, you have two options:
OPTION 1:
You can use the iSE’s WEB interface to chart the data stored in the flash memory.
1. Click on the “Chart” button located on the Server Home Page, see Figure 4.5.
2. Select a time interval of Day, Week, Month or Year (Minute and Hour are not
selectable for data retrieval).
3. As soon as the time interval is selected the “Archives_Inactive” button will change
to “Archives_Enable”.
4. Click on “Archives_Enable” button to graph the stored data.
OPTION 2:
Download the iSE Download Utility iFlash software from the website listed in this manual
and install it on your networked PC. This software is compatible with Windows 95, 98,
NT, 2000, and XP operating systems. After the installation is completed, you can run the
program to obtain the screen shown in Figure 4.9.
To avoid any miscommunications when downloading the stored data using the
iFlash program, it is strongly recommended to let the recording run for a
minimum of 3 minutes if the time interval is 10 seconds (from “Configuration”
page), and 15 minutes if the time interval is 1 minute.
IP Address: Place the IP address of the iSE from which you want to download data, in
this window.
Output Filename: Assign the path and the file name in which the downloaded data will
be placed, in this window.
Model: Select the iSE-TH option.
Latest Data for: This option
allows you to download data for
the last day, week, or month. By
selecting “Full” you can download
the whole data.
Output Format: This option gives
the data in either Excel format
(check the box) or Text format
(uncheck the box).
Header Data: You can choose
what to appear for the header of
the data file either in Excel or Text
format.
Scale: This will give you the
temperature in either Fahrenheit
or Celsius.
Access Log: The completion of
data download will be reported in
this window. You can start
downloading by clicking on the
“Start Download” button.
Figure 4.9 iFlash Download Utility
23
4.3.4 Access Control
This section describes the "Access Control" page of the iSE’s Web interface. This page
allows the users to set up the network and security parameters of the iSE.
At the initial entrance to the “Access Control” page you will be prompted for the LOGIN
Password (see Figure 4.6) prior to an ADMINISTRATOR Password.
The DHCP can be enabled by
setting the dip switch number 3
to ON position.
ACCESS CONTROL
Address
http://192.168.1.200
ACCESS CONTROL
Changes made in the iSE’s
Access Control page can be
saved permanently by pressing
the Save button and power
recycling the iSE.
Login Password: 12345678
Admin Password: 00000000
Host Name: eis21d9
MAC Address: 00:03:03:00:21:D9
IP Address: 192.168.1.200
Gateway Address: 0.0.0.0
Subnet Mask: 255.255.255.0
Camera IP: 0.0.0.0
Camera Label:
If you change a field and press Save,
this message will appear
Camera Location
Click the following button to activate the new settings.
Save Reset
Power Recycle
Main Menu
Figure 4.10 Access Control
Login Password: This allows users to access and modify all of the iSE Home Page menu
items, except “Access Control”, which requires an Administrator password. The default
Login password is 12345678. This password can be up to 16 alpha-numeric case-sensitive
characters. If there is no Login Password assigned (blank box) the iSE will not require a
password to access and modify iSE Home page menu items.
Admin (administrator) Password: This allows users to access and modify the "Access
Control" page. The default password is 00000000. This password can be up to 16 alphanumeric case-sensitive characters. If there is no Administrator Password assigned (blank
box) the iSE will not require password to access and modify "Access Control" page.
Host Name: Refer to Section 3.4, DNS.
MAC Address: This is also called Hardware address or Ethernet address, which is
assigned to the iSE at production. The MAC (Media Access Control) address is the iSE’s
unique hardware number and is not changeable.
IP Address: The IP (Internet Protocol) address is a 32-bit number that identifies each sender
or receiver of information that is sent in packets across the Ethernet or the Internet. The iSE’s
default IP address is 192.168.1.200. The iSE’s IP address should be changed to fit user’s
networking environment. Consult with your IT department for obtaining an IP address.
Gateway Address: A gateway is a network point that acts as an entrance to another
network. A gateway is often associated with a router, which knows where to direct a given
packet of data that arrives at the gateway. If the iSE is sending packets to another network
node that is not on the same network on which the iSE is connected, a gateway address
needs to be given to the iSE. The gateway address should be the IP address of the router
connected to the same LAN to which the iSE is connected. The iSE’s default gateway
address is 0.0.0.0. Consult with your IT department for obtaining a gateway address.
Subnet Mask: It is a 32-bit number that is used to determine which part of the IP address
is the network portion and which part is the host portion. The iSE’s default subnet mask is
255.255.255.0. Consult with your IT department for obtaining a subnet mask.
Camera IP: If there is a networked camera on the LAN, it can be accessed from the iSE’s
Home Page by adding the Camera’s IP address in this field.
24
4.3.4 Access Control (continued)
Camera Label: This is the text field to name the camera button on the iSE Home Page,
the default is “Camera Location”.
Power Recycle: Clicking this button will reset the power on the iSE.
4.3.5 Configuration
Setting up the Flash Memory Card can be done in the Configuration page. From the
Home Page Menu click on Configuration to get to the page (see Figure 4.11).
General Description of the Configuration page: There are two general sections “Flash
Card Memory” and “Server”. Flash Card Memory consists of the following titles: Real
Time Clock (RTC), Title, Alarm Setup, and Flash Recording. Server consists of Terminal
Server and Remote Access.
Title and Flash Recording selections can be editted once by selecting “Activation - Start
Recording” and after that, no modification will take place unless recording is stopped (the
reason for this is to be compliant with the data logging rules). The remaining parameters
can be changed during recording as explained below.
There are several scenarios depending on the state of the Flash Card and the Real Time
Clock (RTC):
#1) RTC is not set and Flash Card is empty.
All the fields must be updated exactly according to the indicated format, “Adjust RTC
Only” check box must be left unchecked, “Activation” selection must set to “Start
Recording” and click the “Update” button. Having done this, it is recommended to
select “Configuration” from “Activation” drop down window, click the “Update” button,
set the “Activation” to “Status/RTC/Alarm” and click the “Update” button one more
time to review/verify that the setup took place as it was intended.
#2) RTC is set, and recording is in progress.
The only possible setups are to update “Date” and “Time” of the Real Time Clock
along with checking “Adjust RTC Only” box. Also, alarms can be updated provided
that “Activation” is set to “Status/RTC/Alarm”. Otherwise, the recording has to be
stopped by selecting “Stop Recording” of the “Activation” drop down window prior to
modifying the Flash Card setup. An alternative way to stop recording is to push
Standby Button (refer to Figure 2.3) of the unit.
#3) RTC is set, recording is stopped, and Flash Card is not empty.
This means that a pre-recorded Flash Card is installed, and by activating the chart the
archived data can be viewed (Refer to Figure 4.8). The chart has the following
selections:
1 Minute, 1 Day, 1 Week, 1 Month, 1 Year
In other words, they are the last specified selection e.g. 1 Day means the last day of
the recorded data. Having done the selection, the “Archives_Enable” button must be
clicked, which will then change to “Archives_Done” and the data will be retrieved
accordingly. Also, the corresponding Start and End dates will reflect the respective
time duration e.g. refer to Figure 4.8 which is the last 1 Day, the dates are:
02/20/2004 09:42:10
to 02/21/2004 09:42:10.
#4) RTC is not set and the Flash Card is not empty.
This is similiar to item 3) above except that at the power-up the installed Flash Card
was not empty. Or, the Flash Card Reset Button (refer to Figure 2.3) was pushed.
25
CONFIGURATION
http://192.168.1.50
No. Sensor Name
1
Temperature 1
3
Differential
2
CONFIGURATION
Reading Command Remote End Char Display Units Remote Format Offset
SRTF
0D
F
T0000.0
0.0
SRDF
0D
F
D0000.0
0.0
Temperature 2
SRHF
4 Input Contact 1
SRT2
5
Input Contact 2
F
0D
0D
T0000.0
0.0
0D
SRH2
Click on Sensor No. on left to modify Sensor Parameters.
Real Time Clock
Date: 03/18/2008 mm/dd/yyyy
Time: 04:26:08 hh:mm:ss
Adjust RTC Only: Time Stamp:
Secured Applet:
2-MegaBytes Flash Card 22 Kbytes Used Space
Flash Card Pre-Recorded AC Power On and Low Battery
Alarm Setup
Input 2 Alarm: High/Low
Input 1 Alarm: Disable
Input 1 Status: Unlatch
SP1_L: 50.0
SP1_H: 80.0
Title: Title
Type: Wrap
nnn.n
nnn.n
Input 2 Status: Unlatch
SP2_L: 60.0
SP2_H: 90.1
Degree Unit: F
Interval: 10_sec
LCD/PWR: OFF
Activation: Status/RTC/Alarm
End Date: 02/16/2008 mm/dd/yyyy
TCP/UDP: TCP
nnn.n
Flash Recording Settings
Start Date: 01/16/2008 mm/dd/yyyy
Contact Input 1: Disable
nnn.n
Time: 12:00:00 hh:mm:ss
Time: 12:00:00 hh:mm:ss
Input Contact Closure
Contact Input 2: Disable
Output Type: Unlatch
Server Type: Command
Terminal Server
Forward CR Disable
Active Contact Output: Active High
Number of Connections 5
Remote Access (Tunneling)
Remote IP Address: 0.0.0.0
Remote Port: 2000 Remote Access: Disable
Update
Main Menu
Figure 4.11 Configuration
26
Port: 2000
4.3.5 Configuration (continued)
Below are the definitions of terms used in the Configuration page.
A) Configuration/Device Setup
Clicking on the No. 1, 2, 3, 4 or 5 allows you to modify the Sensor Parameters (see
Section 4.3.6 for more details).
B) Real Time Clock
RTC Date and Time: The formats are mm/dd/yyyy and hh:mm:ss. The exact formats
are required otherwise an error message will appear in the Title box. Note: time is
military time/24 hour based.
Adjust RTC Only: If checked, the clock will be updated and nothing else, provided
that “Activation” is set to “Status/RTC/Alarm”. To verify the clock, set the “Activation”
to “Configuration”, click Update button, then set “Activation” to “Status/RTC/Alarm”
and click Update button one more time.
Time Stamp: If checked, the Temperature values will be stamped with time and date
using Port 1000 (HTTPget program must be used, see Section 4.5.1).
Secured Applet: If checked, the LOGIN password is required to open “Read Sensor”
and “Chart” pages.
C) Flash Card Size: Reports the Flash Card density and if it is already recorded, how
many locations are filled.
0-Megabytes: Flash Card is not installed or a bad Flash Card
2-Megabytes, 4-Megabytes, 8-Megabytes: available sizes of Flash Cards.
D) Flash Card Message: Describes RTC setup, listed in the previous 4 scenarios.
Flash Card Module Malfunctional
Open Sensor
Flash Card Standby
Flash Card Recording Stopped
Flash Card Pre-Recorded
Flash Card Recording Complete
Flash Card Recording On
Wait Reading Flash
Flash Card Module Not Initialized
Recording Initialized
Flash Card Corrupt Initialization
If the battery is not connected or the voltage is low, the statement “Low Battery” will
be added to the above statements. You may also see a statement “Archive Busy” if
another client is busy receiving archive data. In this case, refrain from activating the
applet, instead keep clicking the Update button and make sure “Activation” is set to
“Status/RTC/Alarm” until the “Archive Busy” statement is no longer displayed.
E) Alarm Setup: There are two alarms which can be assigned to Temperature 1
Temperature 2 (one alarm to each variable). Selection of Input 1 or Input 2 and
Setpoint High (SP_H) or Setpoint Low (SP_L).
Temperature 1 and Temperature 2: Disable, Low, High, High/Low
Disable: Alarm is disabled (no alarm function)
Low: Alarm is enabled only with Low setpoint
High: Alarm is enabled only with High setpoint
High/Low: Alarm is enabled only with High and Low setpoints
27
Example: If High/Low is selected, the temperature will be monitored against these two
High and Low values. If temperature goes above High value (082.5), Relay 1 will be
energized, and if temperature goes below Low value (032.5) Relay 1 will be energized.
Input 1 Status: Unlatch, Latch, Clear Latch, Chart SP
Input 2 Status: Unlatch, Latch, Clear Latch, Chart SP
Unlatch: The relay in the iSE will be turned on (closed) when the Temperature 1 and/or
Temperature 2 values fall outside of Setpoint range. When the Temperature 1 and/or
Temperature 2 values are back within the range, the relay will be turned off (opened).
Latch: The relay in the iSE will be turned on (closed) when the Temperature 1 and/or Temperature 2 values fall outside of Setpoint range and will remain on until the user turns it off.
Clear Latch: This option will clear the latch, meaning the activated alarm will be disabled.
Chart SP: Selecting this option will add the setpoints to the ”Chart”.
SP1_L, SP1_H and SP2_L, SP2_H: Editable box for Setpoint values. The format is
nnn.n, it must be followed exactly otherwise the modification will not take place for any
modified item in the Alarm Setup.
F) Flash Recording
Title: Editable field with up to 16 characters long. The given name will display as a title
on the “Chart” and “Read Sensor” pages either for the real-time data or the stored data.
Degree Unit: The unit of temperature either in degree Fahrenheit or degree Centigrade.
LCD/PWR: The selections are “ON ”, “OFF ”, and “UPS”. Selecting “OFF” will cause
the LCD to turn off during a power outage, provided the battery is connected. The
current consumption is about 1.5 mA or 3 mA depending on “OFF ” or “ON ” selection
respectively. If recording is “ON “, depending on the recording interval, the LCD will be
updated every 10 seconds or 1 minute. Therefore, when the LCD is set to “ON ”, it
could take some time before the LCD is turned on. If recording is not “ON “, the LCD
will be updated every 10 seconds.
Selecting “UPS” puts the iSE into full operational mode when it’s running on the battery
(S5 jumper needs to be installed, see Section 2.4 and 2.7). This means that in case of
power outage, sensing, recording, LCD display, and network communication
capabilities of the iSE will all operate on the battery. Due to heavy power consumption
the battery will not last more than an hour.
Type: The selections are: “Limited”, “Wrap”, or “Nonwrap”.
Limited: You must define the Start Date and Time, and End Date and Time in which
you need the recording to be done.
Wrap: You only need to define the Start Date and Time. The iSE will record data until the
Flash is full, then the iSE will continue to record and overwrite the existing data.
Nonwrap: You only need to define the Start Date and Time. The iSE will record data
until the Flash is full, then the iSE will stop recording.
Interval: The recording interval at which the temperature is being stored into the Flash
Card. The selections are “10 seconds“ and “1 minute“.
To avoid any miscommunications when downloading the stored data using the
iFlash program or from the “Chart” page, it is strongly recommended to let the
recording run for a minimum of 3 minutes if the time interval is 10 seconds (from
the “Configuration” page), and 15 minutes if the time interval is 1 minute.
Activation: The selections are “Status/RTC/Alarm”, “Start Recording ”,
“Configuration”, “Stop Recording ”and “Reset”. Refer to previous scenarios #1 and #2
at the beginning of this Section 4.3.5 for more details.
28
4.3.5 Configuration (continued)
Status/RTC/Alarm: Select “Configuration” and “Status/RTC/Alarm”, each followed
by clicking the Update button to retrieve the latest recording settings. By selecting
“Status/RTC/Alarm” only, followed by clicking the “Update” button the iSE will
report back all the settings, but the “Recording” settings.
Start Recording: Select to initiate a recording.
Configuration: Select to retrieve the latest recording settings, followed by
“Status/RTC/Alarm” option.
Stop Recording: Select to stop an ongoing recording.
Reset: Selecting this option will reset the flash memory, LCD, and recording
sections to a fresh start. It is suggested to select “Reset ” followed by clicking the
“Update” button if you experience recording problems.
Start Date, Time: Starting date and time for recording. The format is mm/dd/yyyy
and hh:mm:ss, it must be followed exactly. Entry is required for all Types of Flash
Recording.
End Date, Time: Ending date and time for recording. The format is mm/dd/yyyy and
hh:mm:ss, it must be followed exactly. Entry is required for Limited Type of Flash
Recording only.
NOTE 1: While the recording is in progress, the “Recording ON” will be displayed on
the LCD.
NOTE 2: Downloading data and recording can not be done at the same time. While
downloading data, the writing process to the flash memory will be internally disabled
while the data is being read from the memory flash. For small amounts of data to be
retrieved (1 Day or 1 Week), this is not a significant interruption in the recording data.
However, for large amounts of data (1 Month or 1 Year) it may take 4 to 8 minutes to
download the data. In “Archives_Enabled “ mode, charting remains static, while data
download is taking place.
NOTE 3: The number of temperature values that can be recorded depends on the
memory flash capacity (2 Mbytes, 4 Mbytes or 8 Mbytes) and recording interval time,
e.g: 1 minute interval for 4 Mbytes is 1,081,212 minutes or 750 days. If the flash is
busy sending data to the applet to chart the archive, the iSE will refuse to initiate a call
to provide archived data to the second applet until it has finished with the first one.
NOTE 4: In case of a power outage and no battery backup, if the unit is recording,
the recording will stop but the data that was stored will be saved. Please note, the
last recorded data (30 minutes to an hour, depending on time interval) could be lost,
due to the fact that the data is initially stored to the buffer before it is transferred to the
Flash Memory and loss of power will erase the data in the buffer.
NOTE 5: After you “Start Recording” the flash recording followed by clicking the
“Update” button, if you then need to make any changes in the Flash Recording
section you must either select “Stop Recording” followed by clicking the “Update”
button or push the reset button on the side of the iSE and reconfigure the Flash
Recording section.
NOTE 6: If you stop the recording prematurely, when you download the data, you will
lose the last 256 bytes of the data that was left in the buffer and was not transferred
into the flash card. Therefore, we strongly suggest downloading the data while the
recording is still on and then stop the recording if desired.
29
4.3.5 Configuration (continued)
G) Input Contact Closure
Contact 1: Disable, Normally Open, Normally Close
Contact 2: Disable, Normally Open, Normally Close
Disabled: Contact is dysfunctional.
Normally Open: Contact is open. If the contact is closed, there will be an Output High
or Low, depending on which output is selected. Read Sensor page will display:
Normal.
Normally Close: Contact is closed. If the contact is open, there will be an Output
High or Low, depending on which output is selected. Read Sensor page will display:
Active.
Active Contact Output: Active High, Active Low. The Output can be High or Low
when the status on the input contact is changed.
Output Type: Unlatch, Latch, Clear Latch
H) Terminal Server
TCP/UDP*: The iSE supports TCP and UDP protocols (default is TCP). If UDP is
selected, it can be configured either for Broadcast UDP or Directed UDP. In case of
Broadcast UDP, the iSE will transmit the data to every node on the network. This can
be accomplished if the Remote IP Address is set to 255.255.255.255.
The Broadcast UDP is a practical solution when one iSE needs to communicate with
multiple nodes over the network. In the case of directed UDP, the iSE will transmit
the data to a specific node on the network. This can be accomplished if the Remote
IP Address is set to the IP address of that specific node.
Server Type: Continuous mode sends the temperature to the Ethernet, every two
seconds. It is mainly used to send readings to a remote display.
Command mode (default) needs a command to query the iSE to send the reponse
back to querying device.
Forward CR: Forward CR can be enabled and disabled. If enabled the iSE will
forward a <CR> along with the data to a network host.
Number of Connections: The range is from 0 to 5. If 0 is selected, the Terminal
Server feature is disabled. This means that no network connection can be made to
the sensor connected to the iSE. If 1 is selected, only one network connection can be
made to the iSE’s. Any number more than 1 would allow that number of network
hosts to read from the iSE simultaneously (default is 5).
Port: Port 2000 is the default TCP port for the iSE’s port to which the sensors are
connected. Ports 1000 (used for HTTPget, refer to Section 4.5), 2002, 2003, and
2004 are reserved for internal use.
Terminal Server usually describes a device that exchanges data between
Ethernet/TCPIP networks and RS-232/RS-485 systems. With this iSE, the
data is obtained digitally from the sensor (irrelevant to RS-232 or RS-485
interface) and can be accessed from anywhere on the network.
A computer program, such as Mail Notifier, OPC Server, iLog, iFlash or
HTTPget can send TCP requests and obtain readings using the Terminal
Server feature.
30
4.3.5 Configuration (continued)
I) Remote Access
Remote IP Address: iSE can establish a connection to a remote device (e.g. an iLD
Remote Display with an Ethernet iSE embedded board) with this IP.
Remote Port: (default 2000) the remote port number for the connection. Ports 1000
(used for HTTPget, refer to Section 4.5), 2002, 2003, and 2004 are reserved for
internal use.
Remote Access:** Remote Access can be enabled and disabled. If enabled, the iSE
can send its data to a remote node on the same network (the “Remote IP address”
and “Remote Port” must be entered).
*TCP/UDP: when UDP mode is selected, Remote Access should be disabled
and Remote IP and Port are the UDP remote listening IP and Port. If the
Remote IP is set to 255.255.255.255, the UDP packet becomes a
broadcasting packet which will allow any device listening to the Remote port
to receive the packet.
**If Remote Access is enabled, Terminal Server is automatically disabled.
31
4.3.6 Sensor Parameters
• In the first column of Configuration page (Figure 4.11), click on No. 1 to view and
modify the Sensor Parameters page for Temperature 1.
Sensor Parameters
http://192.168.1.200
SENSOR PARAMETERS
No. 1
Sensor Name: Temperature 1
TC Type: K
Sampling Rate: 4
Remote End Char 0x: 0D
Remote Display Format: T0000.0 Cnnnn.n
Offset: 0.0
C
Cold Junction: Disable
Update
Reset
Cancel
Click on Update button of the Configuration page to finalize updates.
Main Menu
Figure 4.12 Sensor Parameters - Temperature
You may type any ASCII characters in the first two boxes, but you must delete
the leading spaces.
• In the first column of Configuration page (Figure 4.11), click on No. 4 to view and
modify the Sensor Parameters page for Input Contact 1.
Sensor Parameters
http://192.168.1.200
SENSOR PARAMETERS
No. 4
Sensor Name: Input Contact 1
Remote End Char 0x: 0D
Update
Reset
Cancel
Click on Update button of the Configuration page to finalize updates.
Main Menu
Figure 4.13 Sensor Parameters - Input Contact
32
4.3.6 Sensor Parameters (continued)
Below are some definitions of terms used in the Sensor Parameter pages.
Sensor Name: a text field shown on the “Read Sensor” page.
TC Type: a list of thermocouple types to select from J, K, T, E, R, S, B, C, N, and L (J Din).
(See Figure 12).
Sampling Rate: the number of readings per second. The options are: 2, 4, 8, and 12;
if the higher sampling rate is selected, you’ll have a lower accuracy. (See Figure 12).
Remote End Char: The default value is 0D (Hex representation of <CR>). This means
that the iServer sends <CR> after each temperature value. This will be done in
Continuous mode.
Tera Term - 206.29.25.27 VT
This is how the data will appear on the host with 0D
File Edit Setup Control Window Help
assigned:
C1Disable
TA71.34F
C2Disable
TA72.48F
T168.5F
TD-1.19F
T267.4F
If the end character, for instance, is 20 (Hex
D1.1F
representation of space), the data will then appear as:
C1Disable
TA71.34FTA72.48FTD-1.19F
C2Disable
If nothing is set for the “Remote End Char” field, the
T168.5F
iServer will then forward the data to the LAN with no
T267.3F
characters followed.
D1.2F
C1Disable
Remote Display Format: This determines the data
format sent by the iServer to a remote network node
(e.g. iLD Display)
Figure 4.14 Remote End Char
Example: If Channel 1 shows temperature of 71.34°F,
the TA71.34F will be seen on the remote display. If no format is specified (blank), there
is no reading sent out. If temperature is 75.7 and T00.0F is used in temperature setting,
the remote site will show T75.7F.
This format setup was originally made for the iLD Display, which has four or six LEDs.
For six LEDs, T00.00F format, and for four LEDs, 00.0F format are appropriate.
Offset: Since the sensing probe is solid state electronics, there is no need for
calibration. If it’s determined that the readings are slightly off, the user can manually
assign numerical values to adjust the readings for temperature values. The unit must be
in degree C. The Offset value can either be a positive or negative number
Cold Junction: The options are Disable and Comp_1 for sensor 1 and Comp_2 for
sensor 2. Selecting Comp_1 or Comp_2 will allow you to adjust (calibrate) that sensor in
reference to 0°C environment. Cold Junction Compensation is done for type K thermocouple
for both sensors before the product is shipped. If a different type of thermocouple is used, we
strongly recommend to perform Cold Junction Compensation on that sensor.
Input 2: The options are Enable and Disable for the second thermocouple sensor only. If
it is disabled the thermocouple #2 and the “Differential” value will be shown as “N/A” on
the “Read Sensor” and “Chart” pages.
If the second thermocouple channel is not used, it is strongly recommended to
disable “Input 2”, for faster operation.
33
4.4 Telnet Setup
Set the Number of Connections to 1-5 other than 0, using telnet simulation program
connect to iSE. In continuous mode, the telnet teminal will receive continuous messages
from the iSE. In command mode, the command can be sent to query the iSE and get a
response back. Refer to Figure 3.3
Send remote reset: Telnet port 2002 will bring a terminal for admin password. After
typing the password and following with the end character, the message Admin. Login
Successful will be showed on the terminal. Now type "reset" following with return
character to reset the iSE. If no character is received within 20 seconds, the terminal will
be closed automatically.
Initiating the archive chart while Telnet is active will halt Telnet until the archive
chart is done.
4.5 HTTPget Program
The HTTPget software is used to send a single HTTP or TCP request to an iSE product.
In contrast, the telnet or Hyperterminal programs allow a continuous connection with
multiple requests to be sent to the iSE product.
Generally HTTPget is used for simply programming an IP address to the iSE or for
quickly obtaining a reading of from a device.
The iSE product must be configured from the configuration web page so that the "Server
Type" value is set to "Command" (This is positioned under the heading of Terminal
Server). Also the Number of Connections may need to be set to "0" to enable Port 1000
(Port 1000 is for access in a non-standard terminal mode).
To use Port 2000 access (where "2000" is the value stored in "Port"), the Number of
Connections should be set to "2" for general usage. The value of 2 can later be
changed to a value from 1 to 5 depending on needs for secure access or fault tolerance.
Whenever Terminal Server service (using Port 2000 by default) is required, the Number
of Connections must be set to a value from 1 to 5. The Terminal Server mode is the
recommended mode for the most reliable connection when operating with NEWPORT
software or with other programs supporting TCPIP communications.
The Port 1000 access can be used with NEWPORT software and may be needed with
some iSE products when you need to view readings from the web page while
simultaneously collecting data through TCPIP communications.
34
4.5.1 HTTPget using Port 1000
You can setup and read the information from the iSE by using the HTTPget program.
The following program can be used to read data from the embedded server firmware by
using TCP port 1000. The command string is sent to this TCP port, then the response
can be read back from the same socket.
The HTTPget.exe file is used to setup and read information from the iSE. This file will be
automatically installed when you install the MailNotifier software available on our website
and CD.
Notes on using HTTPget :
The HTTPget.exe program is installed to the windows directory (usually c:\winnt or
c:\windows) when installing the Mail Notifier software.
1. Open up a command window (or have a DOS window)
a) Click on start menu
b) Click on "Run"
c) In the dialog box that appears, type "cmd" or "command" and click on "OK"
button.
d) A command window should now appear.
2. If you now type "HTTPget" and press the "enter" key, the program options should be
displayed.
3. Next run HTTPget with the options displayed as shown in the following text
35
4.5.1 HTTPget using Port 1000 (continued)
httpget -r -S “*SRTC\r” 192.168.1.200:2000
where:
-r –S are parameters needed for the command string
*SRTC is the command as the following:
*SRTC
Read the temperature in C (Channel 1)
*SRTF
Read the temperature in F (Channel 1)
*SRHC
Read temperature in C (Channel 2)
*SRHF
Read temperature in F (Channel 2)
*SRDC
Read the differential in C
*SRDF
Read the differential in F
*SRA1
Read temperature setpoints (Channel 1)
*SRA2
Read temperature setpoints (Channel 2)
*SRB
Read the temperature in C, (both Channel 1 and Channel 2)
*SRYS
Indicate AC or DC power and battery status
*SRYRST
Reset Power on iSE
*SR_XD1
Exclude alarm 1 (disable alarm 1 function)
*SR_XD2
Exclude alarm 2 (disable alarm 2 function)
*SR_XC1
Reset relay 1 latch condition
*SR_XC2
Reset relay 2 latch condition
*SR_XE1
Include alarm 1 (enable alarm 1 function)
*SR_XE2
Include alarm 2 (enable alarm 2 function)
*SR_XP1
Close relay 1 for < 200 mSec
*SR_XP2
Close relay 2 for < 200 mSec
*SR_XH1
*SR_XH2
Close relay 1
Close relay 2
*SR_XL1
Open relay 1
*SRT2
Status of Contact 1 (Disable, Normal, Active)
*SR_XL2
*SRH2
*SRD2
Open relay 2
Status of Contact 2 (Disable, Normal, Active)
Status of the Output associated with the Contacts (Active High,
Active Low)
\r is the carriage return termination character
192.168.1.200 is an IP address
2000 is a socket port number
Response:
076.6 (in Deg.F 35)
36
4.5.2 HTTPget and ARP to setup Device IP Address
Use the iConnect software, which may be downloaded from our website, to do
these IP changes whenever possible.
Use ARP first to assign the mac address to a static IP address in computer arp table by
this command:
arp –s 192.168.1.200 00-03-34-00-06-b6
Then use the following command to assign new IP to the device:
httpget –r –S "00000000" 192.168.1.200:1
where:
“00000000” is admin. password. If the password is wrong, the unit will ignore the new IP.
If the new IP is taken, you will get the message " New IP is Assigned" after the HTTPget
command. The device will reset automatically. (TX and RX led is on for 2 seconds).
“192.168.1.200” is an example of an IP adress. It is replaced with an IP address suitable
for your network
“00-03-34-00-06-b6” is replaced with your iSE product MAC address.
37
4.6 ARP Protocol
ARP is the Internet layer protocol responsible for matching or obtaining the MAC
(hardware) address that corresponds to a particular IP address. The ARP command
allows the user to view the current contents of the ARP cache of the local computer
(residing on the same network). Microsoft includes the ARP.EXE utility for viewing and
modifying the ARP cache with its Windows products. The following ARP commands can
be used to view cache entries:
• arp –a Use this command to view all ARP cache entries.
• arp –a plus IP address Use this command to view ARP cache entries associated
with one particular interface on a network with multiple adapters.
• arp –g Same as arp –a.
• arp –N Use this command to display ARP entries for specific network interface.
• arp – s plus IP address plus Physical address Use this command to manually add
a permanent static entry to the ARP cache.
• arp –d Use this command to manually delete a static entry.
Ping the destination computer using IP address first before using the arp -a
command.
The following window shows examples of arp commands and responses.
• Your computer has an IP address of 192.168.1.118
• The destination computer has an IP address of 192.168.1.96
C:\>arp - 192.168.1.96
No ARP Entries Found
C:\>ping 192.168.1.96
Pinging 192.168.1.96 with 32 bytes of data:
Reply
Reply
Reply
Reply
from
from
from
from
192.168.1.96=bytes=32
192.168.1.96=bytes=32
192.168.1.96=bytes=32
192.168.1.96=bytes=32
time=5ms
time=3ms
time=3ms
time=4ms
TTL=32
TTL=32
TTL=32
TTL=32
C:\>arp -a 192.168.1.96
Interface: 192.168.1.118
Internet Address Physical Addresss
Type
192.168.1.96
00-03-34-00-00-23
dynamic
C:\>arp -s 192.168.1.96 00-03-34-00-00-23
C:\>arp -a 192.168.1.96
Interface: 192.168.1.118
Internet Address Physical Addresss
Type
192.168.1.96
00-03-34-00-00-23
static
C:\>arp -d 192.168.1.96
C:\>arp -a 192.168.1.96
No ARP Entries Found
C:\>
Figure 4.15 ARP Commands and Responses
38
4.7 iLog Software
This is an Excel application software that can log temperature 1, temperature 2 and the
differential temperature from the iSE over the local network (Ethernet) or the internet.
a) Download the iLog software from the website listed in this manual.
b) Install iLog software on a networked PC. This software is compatible with Windows
95, 98, NT, 2000, and XP.
c) For complete information of how to use the iLog software, click on the HELP button.
d) There is a list of Error Messages in Appendix E.
Figure 4.16 iLog Software Logging Data
39
4.8 Mail Notifier Software
For complete information of how to use the Mail Notifier software, click on the Help menu
of the main window.
The Mail Notifier software generates email notifications for alarm conditions. Users can
be notified automatically of alarm conditions monitored via internet connections
throughout the world. By use of the email forwarding of alarm conditions, alarm
conditions can be monitored on a network isolated from the internet and forwarded to
connections on the Internet.
The Mail Notifier utility operates under Windows 98, NT 4.0, 2000, and XP in conjunction
with existing email that supports the MAPI messaging interface. If MS Outlook has been
loaded, the MAPI support should be available.
4.8.1 Installation
The Mail Notifier must be loaded on a computer running Microsoft Windows (versions
specified earlier) using an email program that provides MAPI access. Network access
must be available between this computer and the iSE. Network access must also be
available from this computer to the appropriate email server and from the email server to
the recipient’s email server.
iServer Mail Notifier
File Monitor Mail View Help
Status Indicators
Data
Email
Error
Alerts List
Dev1 alarm: 74.6
Dev2 alarm: 89
Dev1 alarm: 74.7
Dev1 alarm: 74.7
Dev2 alarm: 89
Dev1 alarm: 74.7
Dev1 alarm: 74.6
Connected to Email
Complete
Figure 4.17 iSE Mail Notifier Main Window
40
4.8.2 Program Options Setup and Configuration
Complete program setup requires:
•
Entering a recipient for the email
•
Specifying connection details to MAPI services.
•
Defining alarms for devices, and selecting how and when the email will be active.
Options
Send To Email Setup Content Startup General
Mail Server
MAPI
Use Login
Box
Name/Profile
Password
Email Address
Help
MS Outlook
Outlook 2002
OK
Cancel
Figure 4.18 iSE Mail Notifier Profile Setup
Email Address Setup
The email addresses must be entered using individual addresses or alias. Select
“Options” from the “View” menu and enter the email addresses on the “Send To” screen.
This will be the list of email addresses to which alarm notifications will be sent.
Email Setup
The Mail Notifier is compatible with original MS OutlookTM and OutlookTM 2002 to 2005.
The Mail Notifier will attempt to automatically identify whether the Outlook is a newer
version. A red bar appears under the Mail Notifier splash window to confirm that the
detection of the 2002 or newer version is acceptable. With the newer versions, no
additional steps should be taken to enable the connection between the Mail Notifier and
the Email server.
MS Outlook tends to require that the users respond to a “login box” in order for
email access to be activated for Mail Notifier. Some other email clients may
allow for Mail Notifier to gain access without user login, as may be desired for a
system recovering from a power outage. See the Help files for more
information.
41
4.8.3 Device Setting and Configuration
Device setup requires:
• Server IP Address: for iSE device (for example 192.168.1.200).
• Socket Number: (1000 or 2000 depending on iSE settings).
• Bus Address/Device ID: interface address (1 to 199). Enter "0" for RS232 interface
or for iSE.
• Reading Cmd: normally set to SRFT to obtain reading from the devices. If you want to
change this setting, refer to list of commands in Section 4.5.
• Alarm Type: (High/Low, High value, or Low value).
• Info Message: text can be entered to describe the alarm condition.
• Email Interval: the time interval in which the email is sent.
• Monitor Interval: the interval or time resolution in which readings will be obtained from
the device.
• Alarm Hold Time: the time delay of each subsequential alarm notification to be sent.
Alarm Editor
Device Info (1 of 2)
Server IP Address
Socket Number
Bus Address/Device ID
Description
OK
192.168.1.200
1000
2000
Cancel
31
Help
Dev 2
Dev1
Src ID
SRTF
zRdgA
Reading Cmd
Add
Del
Only Monitor Access
to iServer device
Alarm Configuration
Alarm Type
Alarm High
Info Message
Alarm High
73
Email Interval
Alarm Low
0
Monitor Interval 0.5
min.
Alarm Hold Time 0.0
min.
0.05
Figure 4.19 iSE Mail Notifier Device Setting
42
hrs.
PART 5
SPECIFICATIONS
SENSOR SPECIFICATIONS
Thermocouple Input
Temperature Range: refer to Thermocouple Chart
Temperature Accuracy: refer to Thermocouple Chart
Resolution: 1°/0.1°
Temperature Stability: 0.08°C/°C
Thermocouple Cold End Tracking: 0.05°C/°C
Thermocouple Lead Resistance: 100 ohm max.
Thermocouple Type (ITS 90): J, K, T, E, R, S, B, C, N, L
Input Type
Iron - Constantan
CHROMEGA®- ALOMEGA®
Copper - Constantan
CHROMEGA®- Constantan
Pt / 13%Rh-Pt
Pt / 10%Rh-Pt
30%Rh-Pt / 6%Rh-Pt
5%Re-W / 26%Re-W
L
Nicrosil - Nisil
J DIN
Range
-210 to 760°C / -346 to 1400°F
-270 to -160°C / -160 to 1372°C
-454 to -256°F / -256 to 2502°F
-270 to -190°C / -190 to 400°C
-454 to -310°F / -310 to 752°F
-270 to -220°C / -220 to 1000°C
-454 to -364°F / -364 to 1832°F
-50 to 40°C / 40 to 1768°C
-58 to 104°F / 104 to 3214°F
-50 to 100°C / 100 to 1768°C
-58 to 212°F / 212 to 3214°F
100 to 640°C / 640 to 1820°C
212 to 1184°F / 1184 to 3308°F
0 to 2320°C / 32 to 4208°F
-250 to -100°C / -100 to 1300°C
-418 to -148°F / -148 to 2372°F
-200 to 900°C / -328 to 1652°F
43
Accuracy
0.4°C / 0.7°F
1.0°C / 0.4°C
1.8°F / 0.7°F
1.0°C / 0.4°C
1.8°F / 0.7°F
1.0°C / 0.4°C
1.8°F / 0.7°F
1.0°C / 0.5°C
1.8°F / 0.9°F
1.0°C / 0.5°C
1.8°F / 0.9°F
1.0°C / 0.5°C
1.8°F / 0.9°F
0.4°C / 0.7°F
1.0°C / 0.4°C
1.8°F / 0.7°F
0.4°C / 0.7°F
iSE SPECIFICATIONS
INTERFACES
Ethernet:
Sensor:
Supported Protocols:
LED Indicators:
LCD Display:
Processor:
Memory:
Memory Data
Flash Card:
10Base-T (RJ45)
Digital 4-wire (Mini-DIN 6)
TCP/IP, UDP/IP, ARP, ICMP, DHCP, DNS, HTTP, and Telnet
Network Activity, Network Link, and Diagnostics
32 digits, 4.8 x 9.7mm (0.19 x 0.38”)
Enhanced 8051, 22 MHz
512 Kbytes Flash, 16 Kbytes SRAM
2 Mbytes or 2 months of data storage at 10 second logging
intervals, or 1 year at 1 minute logging intervals.
Atmel# AT45DCB002
Optional Flash Cards: 4 Mbyte (2 years at 1 minute intervals), 8 Mbyte (4 years
at 1 minute intervals)
Relay Outputs:
Two relays 1.5A @ 30Vdc
Alarm I/O’s:
2 Contact Inputs, 1 Open Collector Output 150mA @ 30 Vdc
Management:
Device configuration and monitoring through embedded WEB
server
Embedded WEB Server: Serves WEB pages containing real-time data and live updated
charts within definable time intervals.
POWER
Power Input:
9 to 12 Vdc
Consumption:
2.5 W max.
Safety Qualified ac Power Adapter (included):
Nominal Output:
9 Vdc @ 0.5 A
Input:
100 to 240 Vac, 50/60Hz
Battery:
9 Vdc, alkaline approximately 650 mA hours
ENVIRONMENTAL
Operating Temperature: 0 to 60°C (32 to 140°F)
PACKAGING
Material:
Dimensions:
Weight:
GENERAL
SS 304 case with wall mount bracket
88.1H x 130.2W x 35.8D mm
(3.47 x 5.13 x 1.41”) including wall mount bracket
444.5g (0.98 lbs.)
Agency Approvals: FCC-B, CE
Software:
Packages available are--iConnect, iLog, iFlash, and Mail
Notifier; compatible with all Windows operating systems.
44
PART 6
FACTORY PRESET VALUES
PRESET PARAMETERS
Network Interface:
IP Address
Gateway Address
Subnet Mask
Device Host Name
Login Password
Admin Password
DHCP
Terminal Server:
Server Type
Number of Connections
Port #
Forward CR
Remote Access (Tunneling):
Remote Access
Remote Port
Remote IP Address
LCD Backlight
FACTORY DEFAULTS
192.168.1.200
0.0.0.0
255.255.255.0
eis and the last 4 digits from the MAC address
12345678
00000000
Disabled
Command
5
2000
Enable
Disable
2000
0.0.0.0
On
45
PART 7
APPROVALS INFORMATION
7.1 CE APPROVAL
This product conforms to the EMC directive 89/336/EEC amended by 93/68/EEC,
and with the European Low Voltage Directive 72/23/EEC.
Electrical Safety EN61010-1:2001
Safety requirements for electrical equipment for measurement, control and laboratory.
Basic Insulation
Pollution Degree 2
Dielectric withstand Test per 1 min
• Input Power to Ethernet Output:
1500Vac
• Input Power to Relays:
1500Vac
• Ethernet Output to Relays:
1500Vac
Measurement Category I
Category I are measurements performed on circuits not directly connected to the Mains
Supply (power). Unit measures Temperature.
Transients Overvoltage Surge (1.2/50uS Pulse)
• Input Power:
500V Transients Overvoltage
• Ethernet:
1500V Transients Overvoltage
Note: The ac/dc power adaptor must have Safety Qualified Agency Approvals
for CE with Double Insulation rating.
The ac/dc power adaptor is 9Vdc.
The minimum output current rating is 500mA.
EMC EN61000-6-1:2001 (Immunity) and EN61000-6-3:2001 (Emmissions)
Immunity requirements for residential, commercial and light-industrial environments
• EMC Emissions
Table 1, Class B
• EMC Immunity
Table 1: Enclosure
Table 2: Signal Lines Ports
Table 3: Dc input/Dc output Ports
EMC EN61326:1997 + and A1:1998 + A2:2001
Immunity and Emissions requirements for electrical equipment for measurement, control
and laboratory.
• EMC Emissions
Table 4, Class B of EN61326
• EMC Immunity
Table 1 of EN61326
Note:
I/O lines / sensor cables require shielded cables and these cables must be located
on conductive cable trays or in conduits.
Refer to the EMC and Safety installation considerations (Guidelines) of this manual for
additional information.
7.2
FCC
This device complies with Part 15, Subpart B, Class B of the FCC rules.
46
APPENDIX A
GLOSSARY
User of this manual should be familiar with following definitions:
ARP (Address Resolution Protocol) is a protocol for mapping an Internet Protocol
address (IP address) to a physical machine address that is recognized in the local
network. For example, the IP address in use today is an address that is 32-bits long.
In an Ethernet local area network, however, addresses for attached devices are 48-bits
long. (The physical machine address is also known as a Media Access Control or MAC
address.) A table, usually called the ARP cache, is used to maintain a correlation between
each MAC address and its corresponding IP address. ARP provides the protocol rules for
making this correlation and providing address conversion in both directions.
Ethernet is a network protocol defined by the IEEE 802.3 standard. Ethernet-based
networks use MAC Address rather then IP Address to exchange data between computers.
By using ARP and adding TCP/IP support, Ethernet devices may be connected as part of
the Internet. An Ethernet LAN typically uses coaxial cable or special grades of twisted pair
wires. The most commonly installed Ethernet systems are called 10BASE-T and provide
transmission speeds up to 10 Mbps. Devices are connected to the cable and compete for
access using a Carrier Sense Multiple Access with Collision Detection (CSMA/CD)
protocol.
IP (Internet Protocol) is the method or protocol by which data is sent from one computer
to another on the Internet.
IP address (Internet Protocol address) is a 32-bit number that identifies each sender or
receiver of information that is sent in packets across the Internet.
IP Netmask is a 32-bit pattern of bits used to determine which part of the IP address is the
network portion and which part is the host portion.
MAC (Media Access Control) Address is your computer's unique hardware number.
When you're connected to the Internet from your computer, a correspondence table relates
your IP address to your computer's physical (MAC) address on the LAN.
Ping is a utility that tests the network connectivity. It is used to determine if the host is
capable of exchanging information with another host.
Port number/Socket number is a way to identify a specific process to which an Internet
or other network message is to be forwarded when it arrives at a server. It is a predefined
address that serves as a route from the application to the Transport layer or from the
Transport layer to the application of the TCP/IP system.
Sockets are a method for communication between a client program and a server program
in a network and defined as "the endpoint in a connection." Information transferred across
the Internet primarily occurs between sockets.
TCP/IP (Transmission Control Protocol/Internet Protocol) is the basic communication
language or protocol of the Internet. When you are set up with direct access to the
Internet, your computer is provided with a copy of the TCP/IP program just as every other
computer that you may send messages to or get information from also has a copy of
TCP/IP. TCP/IP often is used as a general term to indicate generic access to the Internet.
UDP/IP (User Datagram Protocol/Internet Protocol) is the TCP/IP standard protocol that
allows an application program on one machine to send a datagram to an application
program on another. The UDP can be either in Broadcast or Directed form. The Broadcast
UDP transmits data to every node on the same network. The Directed UDP transmits data
to one node only.
47
Appendix B
IP Address
An IP address is a unique 32-bit address assigned to a computer and includes:
• A network ID number identifying a network.
• A host ID number identifying a computer on the network.
All IP addresses have been divided into three smaller groups (classes) A, B and C
• Class A addresses have 8-bits of network ID and 24-bits of host ID. They can support
a large number of hosts, approximately 2 = 16,777,216 computers per network.
The IP addresses range in binary from 00000001.xxxxxxxx.xxxxxxxx.xxxxxxxx
to 01111111.xxxxxxxx.xxxxxxxx.xxxxxxxx
The IP addresses range in decimal from 1.x.x.x to 127.x.x.x
Class A network ID’s support a very large number of hosts.
• Class B addresses have 16-bits of network ID and 16-bits of host ID. They can
support approximately 216 = 65,536 computers per network.
The IP addresses range in binary from 10000000 00000000.xxxxxxxx.xxxxxxxx
to 10111111 11111111.xxxxxxxx.xxxxxxxx
The IP addresses range in decimal from 128.0.x.x TO 191.255.xxx.xxx
Class B network ID’s support a medium number of hosts.
• Class C addresses have 24-bits of network ID and 8-bits of host ID. They can support
approximately 28 = 256 computers per network.
The IP addresses range in binary from 11000000.00000000.00000000.xxxxxxxx
to 11011111.11111111.11111111.xxxxxxxx
The IP addresses range in decimal from 192.0.0.xxx to 223.255.255.xxx
Class C network ID’s support a small number of hosts.
The rest of the addresses are divided into two classes, D and E.
Class D networks are not assigned to the host. They are used for multicasting.
The address range from 224.x.x.x to 239.x.x.x
Class E networks are experimental or reserved addresses.
The address range from 240.x.x.x to 247.x.x.x
48
Appendix C
IP Netmask
IP Netmask or Subnet Mask is a 32-bit pattern of ones and zeros used to determine
network portion of an IP address from the host portion of the IP address. Subnet mask is
a network ID that is created by borrowing bits from host portion of IP address and using
them as part of a network ID. The table below shows a default subnet mask for address
Classes A, B, and C. Each bit that is set to "1" in the subnet mask corresponds to the bit
in the IP address that is to be used as the network ID. Each bit that is set to "0" in the
subnet mask corresponds to a bit in the IP address that is to be used as the host ID.
Address Class
Class A
Class B
Class C
Mask Binary Value
11111111 00000000 00000000 00000000
11111111 11111111 00000000 00000000
11111111 11111111 11111111 00000000
Mask Decimal Value
or Dotted Notation
255.0.0.0
255.255.0.0
255.255.255.0
If your network requires more network ID’s, you can extend the default subnet mask to
include additional bits from the host ID. This allows for additional network ID’s within the
network. The table below shows some examples of subnet masks and bits moved from
the hosts ID to create a new subnet.
Mask Dotted Notation
255.0.0.0 (Default)
255.192.0.0
255.224.0.0
255.240.0.0
255.248.0.0
255.252.0.0
255.254.0.0
255.255.0.0
255.255.128.0
255.255.192.0.0
…………….........
255.255.255.252
255.255.0.0 (Default)
255.255.192.0
…………….........
255.255.255.252
255.255.255.0 (Default)
255.255.255.192
………………….
255.255.255.254
11111111
11111111
11111111
11111111
11111111
11111111
11111111
11111111
11111111
11111111
........
11111111
11111111
11111111
........
11111111
11111111
11111111
........
11111111
Mask Binary
Class A
00000000 00000000
11000000 00000000
11100000 00000000
11110000 00000000
11111000 00000000
11111100 00000000
11111110 00000000
11111111 00000000
11111111 10000000
11111111 11000000
........ ........
11111111 11111111
Class B
11111111 00000000
11111111 11000000
........ ........
11111111 11111111
Class C
11111111 11111111
11111111 11111111
........ ........
11111111 11111111
00000000
00000000
00000000
00000000
00000000
00000000
00000000
00000000
00000000
00000000
........
11111100
00000000
00000000
........
11111100
00000000
11000000
........
11111100
Mask Bits
0
2
3
4
5
6
7
8
9
10
.
22
0
2
.
14
0
2
.
6
To determine the number of valid hosts ID’s remaining after subnetting, use the following
equation: 2n – 2, where n is the number of octet digits left after the subnet mask.
49
Appendix D
ASCII
Char
NUL
SOH
STX
ETX
EOT
ENQ
ACK
BEL
BS
HT
LF
VT
FF
CR
SO
SI
DLE
DC1
DC2
DC3
DC4
NAK
SYN
ETB
CAN
EM
SUB
ESC
FS
GS
RS
US
SP
!
"
#
$
%
&
‘
(
)
*
+
,
.
Dec
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
Hex
00
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
0F
10
11
12
13
14
15
16
17
18
19
1A
1B
1C
1D
1E
1F
20
21
22
23
24
25
26
27
28
29
2A
2B
2C
2D
2E
ASCII Chart
Binary
No Parity
00000000
00000001
00000010
00000011
00000100
00000101
00000110
00000111
00001000
00001001
00001010
00001011
00001100
00001101
00001110
00001111
00010000
00010001
00010010
00010011
00010100
00010101
00010110
00010111
00011000
00011001
00011010
00011011
00011100
00011101
00011110
00011111
00100000
00100001
00100010
00100011
00100100
00100101
00100110
00100111
00101000
00101001
00101010
00101011
00101100
00101101
00101110
ASCII
Char
@
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
[
\
]
^
_
`
a
b
c
d
e
f
g
h
I
j
k
l
m
n
50
Dec
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
Hex
40
41
42
43
44
45
46
47
48
49
4A
4B
4C
4D
4E
4F
50
51
52
53
54
55
56
57
58
59
5A
5B
5C
5D
5E
5F
60
61
62
63
64
65
66
67
68
69
6A
6B
6C
6D
6E
Binary
No parity
01000000
01000000
01000010
01000011
01000100
01000101
01000110
01000111
01001000
01001001
01001010
01001011
01001100
01001101
01001110
01001111
01010000
01010001
01010010
01010011
01010100
01010101
01010110
01010111
01011000
01011001
01011010
01011011
01011100
01011101
01011110
01011111
01100000
01100001
01100010
01100011
01100100
01100101
01100110
01100111
01101000
01101001
01101010
01101011
01101100
01101101
01101110
Appendix
/
0
1
2
3
4
5
6
7
8
9
:
;
<
=
>
?
D
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
2F
30
31
32
33
34
35
36
37
38
39
3A
3B
3C
3D
3E
3F
ASCII Chart Continuation
00101111
o
111
p
00110000
112
q
00110001
113
00110010
r
114
00110011
s
115
00110100
t
116
00110101
u
117
00110110
v
118
00110111
w
119
00111000
x
120
y
00111001
121
00111010
z
122
{
00111011
123
|
00111100
124
}
00111101
125
00111110
~
126
00111111
DEL
127
6F
70
71
72
73
74
75
76
77
78
79
7A
7B
7C
7D
7E
7F
01101111
01110000
01110001
01110010
01110011
01110100
01110101
01110110
01110111
01111000
01111001
01111010
01111011
01111100
01111101
01111110
01111111
ASCII Control Codes
ASCII Dec Hex Ctrl Key Definition
ASCII Dec Hex Ctrl Key Definition
Char
Equiv.
Char
Equiv.
NUL 00 00 Crtl @ Null Character DC1
17
11
Crtl Q Data Control 1
- XON
SOH 01 01 Crtl A
Start of
DC2
18
12
Crtl R Data Control 2
Header
STX 02 02 Crtl B
Start of Text
DC3
19
13
Crtl S Data Control 3
- XOFF
ETX 03 03 Crtl C
End of Text
DC4
20
14
Crtl T Data Control 4
EOT 04 04 Crtl D
End of
NAK
21
15
Crtl U
Negative
Transmission
Acknowledge
ENQ 05 05 Crtl E
Inquiry
SYN
22
16
Crtl V Synchronous
Idle
ACK 06 06 Crtl F Acknowledge ETB
23
17
Crtl W End of Trans
Block
BEL 07 07 Crtl G
Bell
CAN
24
18
Crtl X
Cancel
BS
08 08 Crtl H
Back Space
EM
25
19
Crtl Y End of Medium
HT
09 09
Crtl I
Horizontal
SUB
26 1A
Crtl Z
Substitute
Tabulation
LF
10 0A Crtl J
Line Feed
ESC
27 1B
Crtl [
Escape
VT
11 0B Crtl K
Vertical
FS
28 1C
Crtl \ File Separator
Tabulation
FF
12 0C Crtl L
Form Feed
GS
29 1D
Crtl ]
Group
Separator
CR
13 0D Crtl M
Carriage
RS
30 1E
Crtl |
Record
Return
Separator
SO
14 0E Crtl N
Shift Out
US
31 1F
Crtl _ Unit Separator
SI
15 0F Crtl O
Shift In
SP
32
20
Space
DLE 16 10 Crtl P
Data Link
Escape
51
Appendix E
iLog Error Messages
Error # Description
Note
-10005 Failed to find the iSE.
Ethernet cable is disconnected,
iSE is powered off, connections
across the firewall require longer
“connection to socket time out”
setting.
-8003
User stopped logging readings.
-10006 Windows socket was closed.
-10007 Windows socket error.
Wrong IP or wrong Port number
was used.
-10008 The iSE failed to respond to a request.
Wrong IP or wrong Port number
was used.
-10012 Device responded with
"Serial Time Out" string.
Possibly the iLog is configured for
wrong product model.
-10011
Response came empty.
No data was sent.
-10014 Terminal Server Mode when the Port is 1000. Try Port 2000 in iLog configuration.
-15100 Error on obtaining the temperature reading.
52
Possibly the iLog is configured for
wrong product model.
NOTES
NOTES
WARRANTY/DISCLAIMER
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of one (1) year
from the date of purchase. In addition to OMEGA’s standard warranty period, OMEGA Engineering will extend the warranty
period for one (1) additional year if the warranty card enclosed with each instrument is returned to OMEGA.
If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA’s Customer Service Department will issue an
Authorized Return (AR) number immediately upon phone or written request. Upon examination by OMEGA, if the unit is found
to be defective, it will be repaired or replaced at no charge. OMEGA’s WARRANTY does not apply to defects resulting from any
action of the purchaser, including but not limited to mishandling, improper interfacing, operation outside of design limits,
improper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of having been tampered
with or shows evidence of having been damaged as a result of excessive corrosion; or current, heat, moisture or vibration;
improper specification; misapplication; misuse or other operating conditions outside of OMEGA’s control. Components which
wear are not warranted, including but not limited to contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. However, OMEGA neither assumes
responsibility for any omissions or errors nor assumes liability for any damages that result from the use of its
products in accordance with information provided by OMEGA, either verbal or written. OMEGA warrants only that the
parts manufactured by it will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR
REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESS OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL
IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR
PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF LIABILITY: The remedies of purchaser set forth herein are
exclusive, and the total liability of OMEGA with respect to this order, whether based on contract, warranty, negligence,
indemnification, strict liability or otherwise, shall not exceed the purchase price of the component upon which liability
is based. In no event shall OMEGA be liable for consequential, incidental or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic Component”
under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical applications or used on
humans. Should any Product(s) be used in or with any nuclear installation or activity, medical application, used on
humans, or misused in any way, OMEGA assumes no responsibility as set forth in our basic WARRANTY/DISCLAIMER
language, and, additionally, purchaser will indemnify OMEGA and hold OMEGA harmless from any liability or damage
whatsoever arising out of the use of the Product(s) in such a manner.
RETURN REQUESTS/INQUIRIES
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE RETURNING
ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN (AR) NUMBER FROM
OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING DELAYS). The assigned AR
number should then be marked on the outside of the return package and on any correspondence.
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent breakage in
transit.
FOR WARRANTY RETURNS, please have the following
information available BEFORE contacting OMEGA:
1. Purchase Order number under which the product was
PURCHASED,
2. Model and serial number of the product under warranty,
and
3. Repair instructions and/or specific problems relative to
the product.
FOR NON-WARRANTY REPAIRS, consult OMEGA for current
repair charges. Have the following information available
BEFORE contacting OMEGA:
1. Purchase Order number to cover the COST of the repair,
2. Model and serial number of product, and
3. Repair instructions and/or specific problems relative to the
product.
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords our
customers the latest in technology and engineering.
© Copyright 2008 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied, photocopied,
reproduced, translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without the prior
written consent of OMEGA ENGINEERING, INC.
TRADEMARK NOTICE:
, omega.com ®,
®
, and
®
are Trademarks of OMEGA ENGINEERING, INC.
PATENT NOTICE: This product is covered by one or more of the following patents: U.S. Pat. No. Des. 336,895; 5,274,577/
CANADA 2052599; 2052600 / ITALY 1249456; 1250938 / FRANCE BREVET No. 91 12756 / SPAIN 2039150; 2048066 / UK
PATENT No. GB2 249 837; GB2 248 954 / GERMANY DE 41 34398 C2. Other US and International Patents pending or
applied for.
Where Do I Find Everything I Need for
Process Measurement and Control?
OMEGA…Of Course!
Shop on line at omega.com
TEMPERATURE
Thermocouple, RTD & Thermistor Probes, Connectors, Panels & Assemblies
Wire: Thermocouple, RTD & Thermistor
Calibrators & Ice Point References
Recorders, Controllers & Process Monitors
Infrared Pyrometers
Transducers & Strain Gauges
Load Cells & Pressure Gauges
Displacement Transducers
Instrumentation & Accessories
Rotameters, Gas Mass Flowmeters & Flow Computers
Air Velocity Indicators
Turbine/Paddlewheel Systems
Totalizers & Batch Controllers
pH Electrodes, Testers & Accessories
Benchtop/Laboratory Meters
Controllers, Calibrators, Simulators & Pumps
Industrial pH & Conductivity Equipment
Data Acquisition & Engineering Software
Communications-Based Acquisition Systems
Plug-in Cards for Apple, IBM & Compatibles
Datalogging Systems
Recorders, Printers & Plotters
Heating Cable
Cartridge & Strip Heaters
Immersion & Band Heaters
Flexible Heaters
Laboratory Heaters
Metering & Control Instrumentation
Refractometers
Pumps & Tubing
Air, Soil & Water Monitors
Industrial Water & Wastewater Treatment
pH, Conductivity & Dissolved Oxygen Instruments
PRESSURE, STRAIN AND FORCE
FLOW/LEVEL
pH/CONDUCTIVITY
DATA ACQUISITION
HEATERS
ENVIRONMENTAL
MONITORING AND CONTROL
M4422/0908

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement