Split System Submittal Data
System: 30KS72R Indoor/Outdoor: KHS3072R/C3072R
Wall Mounted Air Conditioner
Job Name:
Location:
Engineer:
Submitted to:
Submitted by:
Reference:
Power
Circuit Ampacity
Fuse Size, Max.
Compressor
No. used
R.L. Amps - L.R.
Outdoor Unit
Fan type
Dia. (in.) - No. Speeds
Type Drive - No. Speeds
No. Poles
No. Motors
CFM
F.L. Amps
Coil Type
Fin Type - Pipe Type
Rows - F.P.I.
Face Area
Tube Size
Approval:
Date:
Construction:
Unit #:
Drawing #:
General Data (at 230V)
V/PH/Hz
230/208/1/60
(A)
15-35 Indoor-Outdoor
(A)
15-35 Indoor-Outdoor
DC Rotary Inverter
1
15.5-17.5
(A)
Propeller
18-7/64-1
DC Motor
8 - 800
1 - 90
1942
16.5
(RPM)
(W)
(High)
(A)
(sq.ft.)
(in.)
Aluminum Fin & Copper Pipe
Slit Plate - Inner Riffeled
1 - 14.1
7.26
3/8”
Indoor Unit
Fan type
Dia. & Length (in.) - No. Speeds
No. Speeds
(RPM, High)
No. Poles
(W)
No. Motors
(HI/Med/Lo)
CFM
Indoor Sound Rating
(Hi) (dB-A)
(A)
F.L. Amps
Coil Type
Fin Type - Pipe Type
Rows - F.P.I.
Face Area
Tube Size
Drain Connection Size
Cross Flow
4-13/18 L64 - 1
3 & Auto
4 - 1275
1 - 50
840/740/620
46
0.5
Aluminum Plate Fin & Copper Tube
Slit Plate - Inner Riffeled
2 - 12.7
(sq.ft.)
3.23
(in.)
3/8”
(in.)
1-1/4”
Refrigerant
Lbs. - R410a (outdoor unit)
Control
Connection
Line Length, Max (ft.)
Lift Difference, Max (ft.)
Line Size
Line Size
Dimensions
Indoor Unit
Outdoor Unit
R410A
5.73
Electric Expansion Valve
Flare
165
50 (outdoor lower), 100 (outdoor higher)
(in. O.D. Discharge)
3/8”
(in. O.D. Suction)
5/8”
(in.)
(Uncrated)
(Crated)
(Uncrated)
(Crated)
HxWxD
14-9/16 x 59-1/16 x 9-7/16
18-7/16 x 62-9/16 x 12-9/16
30-23/32 x 37 x 13-3/8
34-31/32 x 39-31/32 x 16-3/32
Weight
Net
Shipping
(lbs.)
(lbs.)
Indoor
63.9
81.6
Outdoor
143
161
Shipping Volume
(cu.ft.)
Indoor
8.4
Outdoor
13.0
Performance Data @ ARI Standard Conditions (230/208V)
Cooling
Total Capacity
(BTU/H)
29,800 (9,500-29,800)
Sensible Capacity
(BTU/H)
17,630
Latent Capacity
(BTU/H)
12,170
SEER
15
Dehumidification
(Pints/H)
9.7
(A)
17.7/19.6
Amps
(W)
3,690/3,690
Power Inputs
Outdoor Sound Rating
(dB-A)
52
Dimensions
Features
Controls
Remote Controller
Temperature Control
Timer
Night Setback
Air Louver
Options
Microprocessor Refrigerant Line Set
LCD Wireless Type, Temp. Sensor Built In Fresh Air Intake
IC Thermostat Airduct Extension
24 Hr. Program Indoor Frame Extension
Dimensional Data for 30K72R
Built-In Condensate Drain Pump
Indoor unit : KH3072R
(Horizontal)
Manual Non-Removeable Remo-con Bracket
(Vertical)
Automatic
Power Failure Automatic Restart
Built-In Operating Range
Dimensional Data for 30K72R
Self-Diagnosis
Built-In
Indoor unit : KH3072R
Air Filter
Maximum
Washable, Anti-Mold Cooling
Minimum
Sanyo Commercial Solutions
A Division of SANYO North America
1300 Michael Drive
Wood Dale, IL 60191 USA
www.sanyohvac.com
Indoor Air Intake Temp.
95F DB/71F WB
67F DB/57F WB
Available
N/A
N/A
N/A
Available
Available
Outdoor Air Intake Temp.
115F DB
0F DB