advertisement
MODEL 5100-02-IT
IT Series
COMBUSTIBLE GAS SENSOR MODULE
Version 2.00a
APPLICABILITY & EFFECTIVITY
Effective for all Model 5100-02-IT Modules manufactured after February 15, 2008.
Instruction Manual Part Number T12019
Rev. B1
Model 5100-02-IT Combustible Gas Sensor Module
FM APPROVAL
ONLY THE FOLLOWING ITEMS, FUNCTIONS AND OPTIONS ARE FM* APPROVED
Model 5100-02-IT Combustible Gas Sensor Module
Sensor Module
Model 5100-02-IT
Model 5100-02-IT-SS
Calibration Equipment
Model 1200-26
Model 1290-02
Model 5358-01
Model 5360-00
Model 1260-02
Model 1260-42
Model 1250-01
Model 1256-01
Model 5394-61
Model 5394-62
Model 5394-64
Model 5394-51
Notes:
Combustible Gas Sensor Module
Combustible Gas Sensor Module, 316SS
Calibration Gas Delivery System
Combustible Gas Cylinder
Calibration Head, Standard
Calibration Gas Delivery Fitting
Combustible 50% LEL Gas Cylinder
Cylinder H2 50% LEL Type A
Gas Sensor Calibrator Kit, Type A
Regulator Type A Calibrator
Auxiliary Connection Option
Auxiliary Relay Option
RS-485 Multidrop Option
Remote Sensor Option – 5100-02-IT
1) FM Approval applies only to conventional (one cable run per sensor module) or multiplexed (multiple sensor modules per cable) installations.
Apparatus must be installed in accordance with National Electrical Code.
* FM Approvals, a subsidiary of FM Global
Project# 3021050
Model 5100-02-IT Combustible Gas Sensor Module
TABLE OF CONTENTS
1.
PRODUCT DESCRIPTION .............................................................................................................................3
1.1
GENERAL........................................................................................................................................................3
1.2
PRODUCT CONFIGURATION........................................................................................................................3
1.3
THEORY OF OPERATION ..............................................................................................................................3
1.4
MODES OF OPERATION................................................................................................................................3
1.4.1
SENTRY INTERFACE..............................................................................................................................3
1.4.2
MODBUS OPERATION............................................................................................................................5
1.4.3
ANALOG OPERATION ............................................................................................................................5
1.4.4
AUXILIARY RELAY OPERATION (Appendix E)......................................................................................5
1.4.5
ENHANCED CONNECTION (Appendix F) ..............................................................................................5
1.4.6
AUXILIARY RS-485 MULTIDROP (Appendix G).....................................................................................5
1.4.7
REMOTE SENSOR (Appendix D)............................................................................................................5
1.4.8
REMOTE ALARM RESET........................................................................................................................5
1.5
MECHANICAL .................................................................................................................................................5
1.5.1
ENCLOSURE ...........................................................................................................................................5
1.5.2
TRANSMITTER ELECTRONICS .............................................................................................................5
1.5.3
SENSOR ASSEMBLY ..............................................................................................................................5
1.6
INTERCONNECT WIRING..............................................................................................................................6
1.7
POWER REQUIREMENTS .............................................................................................................................6
2.
CAUTIONS & WARNINGS .............................................................................................................................7
2.1
INTRODUCTION .............................................................................................................................................7
2.2
IT MODULES GENERAL ..............................................................................................................................7
2.3
WIRING............................................................................................................................................................7
2.3.1
CATALYTIC BEAD SENSOR MODULES................................................................................................8
3.
INSTALLATION ..............................................................................................................................................9
3.1
SENSOR MODULE LOCATIONS...................................................................................................................9
3.2
WIRING............................................................................................................................................................9
3.2.1
ANALOG 4-20 mA OPERATION..............................................................................................................9
3.2.2
MODBUS OPERATION USING RS-485 CONNECTION ........................................................................9
3.2.3
SENTRY OPERATION USING SMC SENTRY CONNECTION ..............................................................9
3.2.4
GENERAL ................................................................................................................................................9
3.3
ENCLOSURE INSTALLATION......................................................................................................................10
3.4
TRANSMITTER AND SENSOR INSTALLATION ..........................................................................................10
3.5
INSTALLATION CONFIGURATION ..............................................................................................................12
4.
INTRODUCTION – HUMAN-MACHINE INTERFACE SYSTEM..................................................................15
4.1
HUMAN-MACHINE INTERFACE ..................................................................................................................15
4.2
MAIN MENU...................................................................................................................................................16
4.3
CONFIGURE SET-POINTS...........................................................................................................................17
4.4
MAINTENANCE FUNCTIONS.......................................................................................................................20
5.
CALIBRATION ..............................................................................................................................................21
5.1
CALIBRATION FREQUENCY .......................................................................................................................21
5.2
CALIBRATION PREPARATION ....................................................................................................................21
5.2.1
CALIBRATION GAS DELIVERY METHODS.........................................................................................21
5.2.2
CALIBRATION PROCEDURE ...............................................................................................................21
5.2.3
SENSOR EXPOSURE TO GAS.............................................................................................................21
6.
SERVICE .......................................................................................................................................................23
6.1
SENSOR MODULE CONFIGURATION ........................................................................................................23
Contents
Model 5100-02-IT Combustible Gas Sensor Module
6.2
ENCLOSURE REPLACEMENT ....................................................................................................................23
6.3
TRANSMITTER REPLACEMENT .................................................................................................................24
6.4
SENSOR REPLACEMENT............................................................................................................................24
6.5
INSTALLATION INSPECTION ......................................................................................................................24
CONTROLLER INSTALLATION ............................................................................................................24
CABLING INSTALLATION .....................................................................................................................24
SENSOR MODULE INSTALLATION .....................................................................................................24
MOISTURE TRAPS AND RAINSHIELDS..............................................................................................25
STANDARD VOLTAGES .......................................................................................................................25
INSPECTION AND TROUBLESHOOTING GUIDE ...............................................................................25
IF MODULE DOES NOT RESPOND TO GAS ......................................................................................25
IF THE MODULE DOES NOT COME OUT OF WARM UP...................................................................25
If the module does not display the correct %LEL...................................................................................25
If the display shows ‘NO SENSR’ –Sensor Failing ................................................................................25
IF THE MODULE SHOWS “***Calibration Required***” ........................................................................25
IF THE MODULE SHOWS “***UNCALIB***” .........................................................................................25
If the display shows ‘H’ (OR l) THEN THE LOCAL HIGH OR LOW ALARM IS ACTIVE ......................25
If the display shows ‘w’ – radio freQuency INTERFERENCE................................................................25
If the display shows “C” – calibration mode ...........................................................................................25
other error messages – call factory........................................................................................................25
7.
APPENDICES ...............................................................................................................................................26
7.1
APPENDIX A: SPECIFICATIONS..................................................................................................................26
7.2
APPENDIX B: MODEL NUMBERS & PARTS LIST .......................................................................................27
7.3
APPENDIX C: LIMITED WARRANTY............................................................................................................28
7.4
APPENDIX D: REMOTE SENSOR/DISPLAY DRAWING 5394-50 ...............................................................29
7.5
APPENDIX E: AUXILIARY RELAY ASSEMBLY 5394-62..............................................................................30
7.6
APPENDIX F: AUXILIARY CONNECTION ASSEMBLY 5394-61 .................................................................31
7.7 APPENDIX G: AUXILIARY RS-485 MULTIDROP ASSEMBLY 5394-64 ……………………………………..32
7.8
APPENDIX H: MODBUS MEMORY MAP......................................................................................................34
7.9
APPENDIX I: COMBUSTIBLE GAS SCALING FACTORS............................................................................35
7.10 APPENDIX J: MENU KEY FOR 5100-02-IT GAS SENSOR MODULE …………………………….…….......36
Contents
Model 5100-02-IT Combustible Gas Sensor Module
1. PRODUCT DESCRIPTION
1.1 GENERAL
The Model 5100-02-IT Catalytic Bead Combustible Gas Sensor Module is a member of the Sentry Information Technology ”IT” family of gas sensor transmitter modules. IT modules offer a broad array of features including:
• Integral Alphanumeric display
• 180 day calibration frequency
• Integral alarm relays (3)
• 4-20 mA output
• Modbus ® RTU interface
• SMC Sentry interface
• 316 Stainless steel enclosure option
• Remote alarm reset
• Auxiliary relay option
• Remote sensor option
• Auxiliary connector option
IT modules are designed, and approved for installation and operation in hazardous locations.
1.2 PRODUCT CONFIGURATION
Various module configuration options are available. Where applicable, these options are factory configured prior to shipment.
1.3 THEORY OF OPERATION
Catalytic bead gas sensors detect gas by comparing the resistance of two heated elements. One element is catalytic to enhance the burning of combustible gases, the other element is passive. Electronic circuits are used to compare the change in the catalytic bead resistance relative to the passive bead. The relative change is calibrated to determine the concentration of the gas of interest.
1.4 MODES OF OPERATION
All IT gas sensor modules can be installed on Sierra Monitor Sentry Model 5000 controllers. Catalytic bead modules communicate as a combustible gas sensor module (Type 2 communication) and are automatically detected by the Sentry controller. When it is installed in a Sentry system the IT module must have a unique address which can be established by setting an address between 1 and 8 on the rotary switch accessible from the cover plate as illustrated in Figure 3-1. Figure 3-4 in this manual provides the wiring terminations for connections to the Sentry controller.
When the module is operated in conjunction with a Sentry controller, the alarm relay setup (See section
4.3) should be set to “Sentry”, allowing the Sentry controller to manage alarm relay action rather than the
5100-02-IT Gas Sensor Module.
An available option, applicable only to Sentry installations, is a connector card which allows daisy chain installation using the Sentry multiplex capability. Use of the connector card reduces costs by avoiding the requirement for wiring junction boxes. The connector card has two sets of connections, allowing for a continuous run to the next module.
®
Registered trademark of Schneider Electric.
Page: 3
Model 5100-02-IT Combustible Gas Sensor Module
Figure 1-1
Model 5100-02-IT Combustible Gas Sensor Module Stainless Steel – Dimensions
Figure 1-2
Model 5100-02-IT Combustible Gas Sensor Module Aluminum – Dimensions
Page: 4
Model 5100-02-IT Combustible Gas Sensor Module
All IT gas sensor modules have a Modbus RTU RS-485 serial interface to allow direct connection to any standard PLC or DCS. The Module Address Switch (section 3.5) allows the user to select Modbus addresses 1 thru 15. Switch position “0” allows the user to set addresses up to 254 using the s Menu (See
Table 4-3). Figure 3-4 provides the wiring terminations for Modbus connections.
All IT gas sensor modules have a 4-20 mA interface to allow direct connection to standard analog indicators or PLCs. The standard Model 5100-02-IT provides a 4-20 mA analog interface which allows power and loop connections. When IT modules are to be operated with analog interface, each module requires individual home run wiring and no unique address is required. Figure 3-3 provides the wiring terminations for 4-20 mA connections.
1.4.4 AUXILIARY RELAY OPERATION (APPENDIX E)
While the 5100-02-IT has three internal 0.25 amp relays (high alarm, low alarm and trouble) as standard, an available option is an Auxiliary Relay Assembly, Part Number 5394-62, which provides 8 amp alarm relays for each of the two conditions, low alarm and high alarm.
1.4.5 ENHANCED CONNECTION (APPENDIX F)
An Auxiliary Connection Assembly, Part Number 5394-61, applicable to Sentry and RS-485 installations only, provides connections capable of accepting 12 AWG wire. Additionally, the enhancement acts as a junction box providing connections for the next module in the run, when utilizing the Sentry multiplexing capability.
1.4.6 AUXILIARY RS-485 MULTIDROP (APPENDIX G)
The Auxiliary RS-485 Multidrop Connection Assembly, Part Number 5394-64, provides the additional terminal connectors to enable the user to connect the In/Out terminations of a RS-485 connection.
1.4.7 REMOTE SENSOR (APPENDIX D)
Extension kit 5394-51 can be used to remotely mount the sensor up to 50’ from the transmitter.
1.4.8 REMOTE ALARM RESET
An input is available for connection of remote alarm reset/acknowledge. Figure 3-5 provides the wiring termination for connecting the remote alarm reset.
1.5 MECHANICAL
The sensor module is comprised of the following three primary components:
1.5.1 ENCLOSURE
Standard on the 5100-02-IT is an explosion-proof, rain-tight cast aluminum electrical housing with three ¾”
FNPT conduit hubs. The 5100-02-IT-SS has a 316 Stainless Steel enclosure. Both enclosure covers have a viewing window. The design of the enclosure allows 3-way mounting choices as shown in figure 1-3. .
Electronic Assembly consisting of one printed circuit board assembly mounted under a cover plate. Wiring connections for power, signal interface and alarm relays are located on the back side of the display.
The sensor assembly includes an explosion proof housing containing the gas sensor and a wiring harness for connection to the transmitter. The sensor assembly threads into one hub of the enclosure. The exposed end of the sensor assembly is threaded to allow connection of a rain-shield or calibration gas delivery fitting.
Page: 5
Model 5100-02-IT Combustible Gas Sensor Module
1.6 INTERCONNECT WIRING
Not supplied with the sensor module, but necessary to the installation and operation is the multi conductor wiring which connects the module to its power source and controller. Before this wiring is installed it is important to read and understand the control system installation instructions to determine wiring requirements and alternatives.
1.7 POWER REQUIREMENTS
IT modules operate on DC power between 10 VDC and 30 VDC. Regulated DC power must be supplied from a separate source, or from an approved Sentry or IT Controller.
Page: 6
Model 5100-02-IT Combustible Gas Sensor Module
2. CAUTIONS & WARNINGS
2.1 INTRODUCTION
Although IT Transmitter Modules are designed and constructed for installation and operation in industrial applications including "hostile" environments, caution should be taken to insure that the installation is made in compliance with this instruction manual and that certain procedures and conditions are avoided. This chapter discusses the necessary cautions. Read the entire chapter prior to installation of the equipment.
2.2 IT MODULES - GENERAL
Avoid installing sensor modules where they will be unnecessarily exposed to wind, dust, water (i.e. direct hose down), shock, or vibration. Observe temperature range limitations.
Sensors may be adversely affected by prolonged exposure to certain materials. Loss of sensitivity, or corrosion, may be gradual if such materials are present in low concentrations. These materials include:
Halides (compounds containing chlorine, fluorine, bromine, iodine), acid vapors, caustic liquids or mists.
Care has been taken by the manufacturer to ship modules in protective packaging to avoid contamination prior to installation. It is recommended that the modules remain protected during installation and that the covering be removed immediately prior to system start-up.
During normal use the sensor is protected from dirt and oil contamination by a sintered metal cover. If this cover becomes clogged, the response of the sensor will be reduced. Protect the sensor from contamination by careful placement, or by use of rain and dust shields.
Sensor modules must not be painted. Paint may contain compounds which will contaminate the sensor. Paint will cause clogging of the sintered metal cover and will cause difficulties during attachment of the calibration head or other maintenance activity. It is recommended that the module be tagged
"DO NOT PAINT"
.
2.3 WIRING
The manufacturer recommends that extra caution be taken where the installation is near any sources of electromagnetic or radio frequency interference. Precautions include:
• Avoid running sensor module cable close to high power cables, radio transmission lines, or cables subject to pulses of high current.
• Avoid running cables near large electric motors or generators.
• When the sensor module is to be operated in analog (4-20mA output) mode shielded cable is required.
• When the risk of interference is present use shielded cables. In conduit installations the shield should be connected to the conduit. In cable applications the shield should be connected to instrument ground.
• All splices must be via either a termination hardware system or soldered. Improperly spliced cable can result in corrosion, resistance changes and system errors.
NOTE
Installation and wiring must be in accordance with the National Electrical Code.
Voltage AC conductors are not to be run in the same conduit as voltage DC conductors.
Page: 7
Model 5100-02-IT Combustible Gas Sensor Module
2.3.1 CATALYTIC BEAD SENSOR MODULES
Model 5100-02-IT Gas Sensor Modules are FM performance approved for detection of Combustible gas
(methane and hydrogen). The sensor is cross sensitive to the combustible gases indicated in Table 2-1.
Risk management planning should take into consideration the potential for the presence of other gases in the monitored area.
Note that the 5100-02-IT has a gas factor scaling feature in which a calibration standard of Methane or
Propane may be used in conjunction with scaling factors to cause alarm function in %LEL scale of another gas. See Appendix I.
Acetaldehyde
Acetic Acid
Acetic Anhydride
Acetone
Acetylene
Alkyl Alcohol
Ammonia n-Amyl Alcohol
Aniline
Benzene
Biphenyl
1,3-Butadiene n-Butane iso-Butane
Butene-1 cis-Butene-2 trans-Butene-2 n-Butyl Alcohol iso-Butyl Alcohol tert-Butyl-Alcohol n-Butyl Benzene iso-Butyl Benzene n-Butyric Acid
Carbon Disulfide
Carbon Monoxide
Carbon Oxysulphide
Chlorobenzene
Cyanogen
Cyclohexane
Cyclopropane n-Decane
Diethylamine
Dimethylamine
2,3-Dimethylpentane
2,3-Dimethylpropane
Dimethylsulphide
1,4-Dioxane
Epichlorohydrin
Ethane
Ethyl Acetate
Ethyl Alcohol
Ethylamine
Ethyl Benzene
Ethyl Bromide
Ethyl Chloride
Ethylcyclopentane
Ethylene
Ethylenedichloride
Ethyleneoxide
Diethyl Ether
Dimethoxyethane
Dimethyl Ether
Dimethylformamide
Ethyl Formate
Ethylmercaptan n-Heptane n-Hexane
Hydrazine
Hydrogencyanide
Hydrogen
Hydrogen Sulfide
Methane
Methyl Actetate
Methyl Alcohol
Methylamine
Methyl Bromide
Methyl Chloride
Methylcyclohexane
Methylenedichloride
Methylethylether
Methylethylketone
Methyl Formate
Methylmercaptan
Methylpropionate
Methyl n-propylketone
Napthalene
Nitromethane n-Nonane n-Octane n-Pentane i-Pentane
Propane n-Propyl Alcohol n-Propylamine n-Propylchloride
Propylene
Propyleneoxide iso-Propylether
Propyne
Toluene
Triethylamine
Trimethylamine
Vinylethylether o-Xylene m-Xylene p-Xylene
JP-4 (Jet Fuel)
Table 2-1
Combustible gases detected by Model 5100-02-IT Combustible Gas Sensor Module
Page: 8
Model 5100-02-IT Combustible Gas Sensor Module
3. INSTALLATION
NOTE
All IT modules are factory pre-configured and calibrated.
All modules are tagged to indicate the configuration including the sensor module number.
Identify all components during unpacking and install using the factory configuration.
3.1 SENSOR MODULE LOCATIONS
Select locations for each sensor module based on the following:
• Modules should be placed close to the potential source of gas.
• Modules should be placed in areas accessible for calibration.
• Sensors should be pointed down and the conduit should include an inverse trap to reduce moisture
(condensation) from accumulating in the electronics enclosure.
• Remote calibration fitting (5360-00) can be used to facilitate calibration gas delivery. Run polyurethane tubing (1/4” O.D. x 1/8” I.D.) from fitting to an accessible location.
3.2 WIRING
3.2.1 ANALOG 4-20 MA OPERATION
The 4-20 mA output for the 5100-02-IT can be either 3-wire (using the 5394-61 Connector Board) or 4-wire operation. If using 3-wire operation, use a minimum of 18 AWG, shielded, 3-conductor cable up to 2000’.
For 4-wire operation, use a minimum of 2 each, 18 AWG, twisted, shielded, pair up to 2000’.
3.2.2 MODBUS OPERATION USING RS-485 CONNECTION
Use a minimum of 18 AWG, 2 conductor for DC power connection. No shield required. In addition use a minimum of 24 AWG, low capacitance, shielded data cable for RS-485 half duplex communication. The installation may be planned in a manner which provides up to 32 sensor modules on a single home run.
3.2.3 SENTRY OPERATION USING SMC SENTRY CONNECTION
Use a minimum of 18 AWG, 3-conductor cable up to 2000’. The cable may or may not be shielded. We recommend shielded cable in circumstances that there could be RF or EM interference present. Shield to be terminated and grounded only at the Sentry controller. Shield must be cut and dressed at the module end so that no part of it comes in contact with the conduit or ground.
NOTE:
Be sure to follow all local electric code and safety requirements when installing the 5100-02-IT Gas Sensor Module
3.2.4 GENERAL
Install conduit as required by local code or construction specifications. When sensor modules are to be multiplexed for Sentry or RS-485 communication two alternatives may be planned:
• Install splice boxes above each sensor module. Use multi-position positive contact terminals to connect daisy chain wiring and provide a pigtail to connect to the sensor module transmitter board.
• Use Auxiliary Connection Assembly, Model 5394-61. The Auxiliary Connection Assembly plugs into the sensor module transmitter and provides daisy chain wiring.
NOTE
The drain wire of shielded cable must NOT be used as one of the conductors.
Installation and wiring must be in accordance with the National Electrical Code. Temperature rating of cable wire must be at least 75 o
C. If cable runs through higher temperature environments, it must be specified for that environment.
Page: 9
Model 5100-02-IT Combustible Gas Sensor Module
3.3 ENCLOSURE INSTALLATION
To protect the transmitter and sensor assembly they should be removed from the enclosure and preserved until final installation and wiring termination.
Prior to installation and wiring.
1. Remove the transmitter from the module housing by:
• Unscrew the two captive panel screws on the face plate.
• Lift the transmitter out of the housing.
• Unplug the sensor cable from transmitter connector J2.
• Remove the sensor assembly from the enclosure hub.
2. Install the module housing onto the end of the supply conduit and/or bolt into position as required.
NOTE
When housing earth grounding is required for the installation a grounding lug is located in the base of the enclosure. Install the earth ground to under the green ground lug.
3.4 TRANSMITTER AND SENSOR INSTALLATION
When all pre-wire is complete:
1. Install sensor assembly in the open hub on the module enclosure. The sensor assembly thread must be fully seated into the hub and tightened to maintain explosion proof assembly.
2. Connect the wires which return to the controller to transmitter connectors P1 and P2 (Figure 3-2) according to Figures 3-3 (Analog Output), 3-4 (Digital Interface), 3-5 (Remote Alarm Reset).
3. Connect the sensor assembly cable to transmitter connector J2.
4. Reconnect any required auxiliary wiring to the applicable terminals according to project requirements and Table 3-2.
5. Connectors P1 and P2 are removable to facilitate wiring termination. When reinstalling the connectors pay attention to the connector orientation. See Figures 3-2, 3-3, 3-4, 3-5, etc.
NOTE
Connectors P1 and P2 are removable for easy wiring termination.
Page: 10
Model 5100-02-IT Combustible Gas Sensor Module
6. Carefully return the transmitter to the enclosure installing it over the two standoffs. Tighten the retaining screws into the standoffs.
P1 F UNCTION
1 High Alarm Relay NC
2 High Alarm Relay NO
3 High Alarm Relay COM
4 Low Alarm Relay NC
5 Low Alarm Relay NO
6 Low Alarm Relay COM
P2
1 Power
F UNCTION
2 Signal
3 Ground
4 N/A
5 N/A
6 4-20 mA output -
7 Trouble Relay NC*
8 Trouble Relay NO*
9 Trouble Relay COM
10 Digital Input SW+
7
8
9
10
4-20 mA output +
RS-485 Ground
RS-485 (-) (B)
RS-485 (+) (A)
11 Digital Input SW-
*Trouble relay is fail safe so it is energized for normal operation. Functions are labeled for normal operation.
Table 3-1
Sensor Module External Interfaces
7. Establish the module address according to section 3.5.
NOTE
The warm-up period is 3 minutes from power on.
Page: 11
Model 5100-02-IT Combustible Gas Sensor Module
3.5 INSTALLATION CONFIGURATION
Table 3-3 and Figures 3-1 through 3-4 provide location and installation details.
P OSITION A DDRESS P OSITION A DDRESS
1
2
3
Sensor 1
Sensor 2
Sensor 3
9
A
B
Sensor 09
Sensor 10
Sensor 11
6
7
Sensor 6
Sensor 7
E
F
Sensor 14
Sensor 15
Table 3-2
Sensor Module Rotary Switch Positions
Figure 3-1
Module Address Rotary Switch
N OTE
For Sentry applications only sensor addresses 1-8 are allowed. If using Modbus output sensor addresses 1-15 are available. Position 0 allows the Modbus or Sentry address to be
set by software menu, in the range 16-254.
Figure 3-2
Connector Locations
Page: 12
Model 5100-02-IT Combustible Gas Sensor Module
Figure 3-3
4-20 mA Connection
Page: 13
Model 5100-02-IT Combustible Gas Sensor Module
Figure 3-4
Digital Interface Connections
Figure 3-5
Remote Alarm Reset
Page: 14
Model 5100-02-IT Combustible Gas Sensor Module
4. INTRODUCTION – HUMAN-MACHINE INTERFACE SYSTEM
The Combustible Gas Sensor utilizes a visual menu system operated by means of a magnet. A magnet stick is supplied for this purpose. The menu system is used to configure alarm set-points, calibrate the sensor module, and for maintenance procedures and alarms acknowledge.
4.1 HUMAN-MACHINE INTERFACE
The module menu system is operated by means of directing the magnet stick toward each of four independent hall-effect magnetic switches. Each switch functions as if it is a manually activated panel key. The keys are located above and below the faceplate display and are labeled M , E , ▲, and ▼as shown in Figure 4-6.
M : MODE
E : ENTER
Mode Enter
Up Down
Figure 4-6
HMI Switch Locations
Page: 15
Model 5100-02-IT Combustible Gas Sensor Module
4.2 MAIN MENU
Table 4-1 describes the primary human-machine interface operation.
M E
S T
M E
S T
M E
S T
M E
S T
M E
S T
M E
S T
M E
S T
Key
M E
S T
M E
S T
M E
S T
M E
S T
Function Display
Mode
Enter
Up
Down
5100-02
1.Xxa
VX.Xxx
Mode
Mode
Mode
Mode
Enter
CALIB:
SETUP:
MAINT:
EXIT-?
0%LEL
0%LEL
Switch [M]
Mode Function - Calibrate
Mode Function - Set Point Adjustments
Mode Function - Maintenance
Exit Mode
Apply Selected Mode (Exit)
Default Display
Description
Switch [E]
Switch [▲] Previous Menu
Switch [▼] Next Menu
First screen at power up-model
Second screen at power up-version
Warm.XXX
Third screen at start up-warm up
0%LEL Normal condition - default display
Mode ALMRSET: Mode Function -Alarms Acknowledge
SSSSSSSS
0%LEL
Banner: Use <M> switch for different menu items. Select <E> to enter menu item.
Default Display
Mode ALMRSET: Mode Function - Alarms Reset
Reference
Table 5-1
Table 4-3
Table 4-4
Table 4-1
Master Menu
Table 4-2 describes the operational display values of the human-machine interface system.
Display
STARTING
##%LEL
L ##%LEL
H ##%LEL
HIGH
NO SENSR
C ##%LEL
ACK
Low Alarm
High Alarm
>100% Full Scale
Sensor Failure
Description
Warm-up at start-up
Concentration
Calibration Mode
Acknowledged Function
Table 4-2
Operation Display Values
ID THE DISPLAY SHOWS “S TART ” INSTEAD OF “S TARTING , THE MODULE MUST BE CALIBRATED BEFORE USING IT .
Page: 16
Model 5100-02-IT Combustible Gas Sensor Module
4.3 CONFIGURE SET-POINTS
The sensor module set-points menu is used to initially set-up the alarm set points, relay actions, gas type and range, 4-20 mA action and RS-485/Sentry address and baud rates (See Menu Key in Appendix J).
• Alarm Set-points: Once the Set-up menu is selected, press [E] to activate the Alarm Set-point screen. Use the [▲] or [▼] keys to select Low Alarm or High Alarm menu. Key [▲] will adjust the setpoint upwards and Key [▼] will adjust the value downwards. Once it reaches the desired setpoint, Key [E] will accept it and ACK will appear. Set-points can be configured using this menu to values between 0 and 60.
• Alarm Relay Set-up: Once the Set-up menu is selected, press key [▼] once and press [E] to activate the Relay Set-up menu. Use the [▲] or [▼] keys to select High Alarm or Low Alarm relay menu and press [E]. Use the [▲] or [▼] keys to select the correct alarm relay action for the application, Latch, Sentry or Non-Latch. Selecting “Sentry” enables the Sentry controller to make all alarm action decisions. * indicates the current selection.
• Gas Factor: A calibration standard of Methane or Propane may be used in conjunction with scaling factors to cause alarm function in %LEL scale of another gas. See Appendix I for a list of the scaling factors. Note that if the 5100-02-IT is interfaced to a Sentry controller that the gas factor can be set in the Sentry or the Gas Sensor Module but NOT IN BOTH. It is recommended that the gas factor be adjusted in the Gas Sensor Module so that the display values on both the Gas Sensor Module and the Sentry are matched. Note that gas factors are not applicable during calibration.
• 4-20mA: Once the Set-up menu is selected, press key [▼] three times and press [E] to activate the
4-20mA Set-up menu. Use the [▲] or [▼] keys to select Calib, or CalibOut TblOut menu and press
[E]. The “Calib” section of the menu allows the user to calibrate the 4 mA and 20 mA outputs. To calibrate the 4 mA and 20 mA outputs it is necessary to have an amp meter connected to the 5100-
28-IT and upon selecting the 4 mA output calibration then the [▲] or [▼] keys can be used to adjust the 4 mA reading on the amp meter until it reads 4 mA. Similar steps can then be performed for the
20 mA output. The CalibOut section allows the user to select the 4-20 mA output action desired during calibration. * indicates the current selected value. Available selections include:
Track – the 4-20mA value tracks the calibration gas exposed to the gas sensor module
Zero – the 4-20mA value is held at 0mA during calibration
C1.50mA – the 4-20mA value is held at 1.50mA during calibration
C4.00mA – the 4-20mA value is held at 4.0mA during calibration.
The Tbl Out menu enables the user to select the mA output value for the Trouble Alarm. Select
“T2.5mA” to choose the 2.5mA default valve. Or select “User mA” and use the [▲] or [▼] keys to select any valve between 0.5mA and 3.7mA.
• RS-485 - Once the Set-up menu is selected, press key [▼] four times and press [E] to activate the
RS-485/Sentry Set-up menu. Use the [▲] or [▼] keys to select Address or Baud rate menu and press [E]. Note that the 5100-28-IT has a rotary switch on the faceplate and it is used to select addresses 1-15. When connected to Sentry the user can select 1-8 and using Modbus RS-485 the user can select addresses 1-15. For Modbus addresses above 15, set the rotary switch to 0 and then use the “Address” menu to select any address between 16 and 254. The Baud rate menu allows the user to select a baud rate of 38400, 19200, 9600, 4800 or 2400. * indicates current selection.
Page: 17
Model 5100-02-IT Combustible Gas Sensor Module
M E
S T
M E
S T
M E
S T
M E
S T
M E
S T
Key Function Display
--0%LELDefault Display
Description
M E
S T
M E
S T
M E
S T
M E
S T
M E
S T
M E
S T
M E
S T
M E
S T
Mode
Mode
Mode
Enter
Down
Down
Down
Down
ALMRSET:
CALIB:--
SETUP:---
Alarms
Relays
GasFactr
4-20mA
RS-485
Mode Function - Alarm Reset
Mode Function - Calibrate
Mode Function - Set Point Adjustments
S.P. Function - Alarm Adjust
S.P. Function - Relays Adjust
S.P. Function - Gas Factor Adjust
S.P. Function - 4-20 mA Adjust
S.P. Function - RS-485/Sentry Output Adjust
High Alarm Set Point Adjustment Example
M E
S T
M E
S T
Enter
Enter
H.Alarm
HASP:60-
S.P. Function - High Alarm Adjust
High Alarm Set Point: current = 60
M E
S T
M E
S T
Down (x5) HASP:55High Alarm Set Point: new = 55
Enter ACK
Use S or T keys to adjust to new set point
Momentary Acknowledge of new Set Point
H.Alarm
S.P. Function - High Alarm Adjust
Enter
Down
Enter
Down
Down
Relays Set Point Adjustment Example
H. Relay S.P. Function - High Alarm Relay Adjust
L.Relay
Latch
Sentry
*Sentry
S.P. Function - Low Alarm Relay Adjust
Use S or T keys to adjust to new relay action
(Latch, Sentry, NonLatc) * indicates current
NOTE: Sentry indicates that Sentry controls relay action and not the IT Sensor Module
High Alarm Relay set to Sentry
Table 4-3A Set-Up Configuration
Reference
* A Below
* B Below
* C pg. 19
* D pg. 19
* E pg. 19
*A
*B
Page: 18
Model 5100-02-IT Combustible Gas Sensor Module
M E
S T
M E
S T
M E
S T
M E
S T
M E
S T
M E
S T
M E
S T
M E
S T
M E
S T
M E
S T
M E
S T
M E
S T
M E
S T
M E
S T
M E
S T
M E
S T
M E
S T
M E
S T
M E
S T
M E
S T
M E
S T
M E
S T
M E
S T
Enter
Enter
Enter
Down
Enter
Enter
Enter
Enter
Gas Factor Example
GasFactr S.P. Function - Gas Factor Adjust
Factr100
ACK
Select [E] to select or S or T to adjust factor number and press [E]
Acknowledgement of new Gas Factor Value
*C
Enter Calib
4-20 mA Adjustment Example
S.P. Function - Calib Adjust
Enter Out: 4mA Use S or T keys to select 4 mA or 20mA
Enter 4mA Selects 4 mA
Enter
Mode
Down
Enter
Enter
*D
ACK
Calib
Momentary Acknowledge of new Set Point
S.P. Function - Calib Adjust
CalibOut S.P. Function - Output during Calibration Adjust
Track
*Track
Use S or T keys to select Track, Zero, C1.50mA, C4.00mA
Track = Output during calibration tracks the calibration gas,
Zero = Output is Zero during calibration,
C1.50mA = Output during calibration is 1.50 mA, C4.00mA =
Output during calibration is 4.0 mA
* = Current selection
Mode Calib S.P. Function - Calib Adjust
Down Tbl Out S.P. Function - output during Trouble Alarm
Enter *T2.50mA
Current Valve 2.5mA for Trouble
Down User mA S.P. Function - User Selectable mA Valve
Enter *T2.50mA
Use S or T keys to select mA Valve between 0.5 and 0.7mA
Enter *T1.75mA
Selctd 1.75mA for volume during trouble
Enter Address
RS-485 Adjustment Example
S.P. Function - RS-485 Address Adjust *E
Addr:016 Use S or T keys to enter new address
ACK
Address
Baud
*38400
New address selected
S.P. Function - RS-485 Address Adjust
S.P. Function - RS-485 Baud Rate Adjust
Press [E] to select or [S] or [T] to select another
Table 4-3B
Set-Up Configuration
Page: 19
Model 5100-02-IT Combustible Gas Sensor Module
4.4 MAINTENANCE FUNCTIONS
The maintenance menu allows the operator to monitor certain Sensor values, and select the required analog or digital communication interface. The maintenance menu operation is described in Table 4-4.
Reference Key Function Display
0%LEL Default Display
M E
S T
M E
S T
M E
S T
M E
S T
M E
S T
Mode
Mode
Mode
Mode
Enter
ALMRSET: Mode Function - Alarm Reset
CALIB:
MAINT:
Mode Function - Calibration
Mode Function - Maintenance
V2.00aA Module Version
Description
SETUP: Mode Function - Set Point Adjustments
Table 4-4
Maintenance Menu
Page: 20
Model 5100-02-IT Combustible Gas Sensor Module
5. CALIBRATION
5.1
CALIBRATION FREQUENCY
The manufacturer specifies that sensor modules must be calibrated every 180 days. Periodic functional tests are advisable for critical applications and hostile environments.
The sensor module microprocessor software includes high level self checking algorithms which provide continuous sensor diagnostic and self adjustment. Users may elect to increase calibration periods based on low drift experience during the first two calibration periods.
5.2
CALIBRATION PREPARATION
Calibration of the sensor is accomplished by simple menu based steps and application of span gas.
N OTE
If an error is made during any stage of the calibration process, hold the magnet stick at the
Switch 1 for 10 seconds. A scrolling display will indicate “Operate Mode” and the sensor module will exit the calibration activity and return to normal operating mode. The calibration procedure can then be restarted.
Calibration must be performed only when the area is known to be clear of combustible gas. If necessary, use a portable instrument to confirm that there is no background combustible gas.
For compliance with Factory Mutual (FM) Approvals, the Sierra Monitor Model 1200-26, 1250-01, 1256-01, 1260 -
02 and 1260-42 are the FM Approved calibration gas delivery devices. Use Model 5358-01 Calibration Adapter or
Model 5360-00 Gas Delivery Fitting.
5.2.1 CALIBRATION GAS DELIVERY METHODS
Calibration gas can be delivered to the sensors via the following delivery devices:
Model 5358-01: Calibration Adapter - use with portable calibrators. See Fig 5-1.
Model 5360-00: Calibration Gas Delivery fitting - permanently installed fitting which allows tubing to be run to a convenient delivery location.
5.2.2 CALIBRATION PROCEDURE
Table 5-1 shows the step by step process of the calibration procedure.
The procedures requires that the menu “keys” be activated using the magnet stick. Each key press steps through the process of setting the zero value for clean air and then setting the span value.
At each of these steps, apply calibration gas of the value corresponding to the setting accepted on the sensor module display.
Figure 5-1
Model 5358-01 Calibration Adapter
5.2.3 SENSOR EXPOSURE TO GAS
Calibration gas must be delivered to the sensor using the flow rate and duration listed in below:
Model Gas Flow
5100-02-IT Combustible 100-300 cc/min
Period
Until Stable (minimum 3 minutes.)
NOTE:
Following calibration, the module counts down for 300 seconds. During this time the module is updating its internal memory and it is very important that its power not be interrupted
Page: 21
Model 5100-02-IT Combustible Gas Sensor Module
Key Function Display
0%LEL
M E
S T
M E
S T
M E
S T
Mode
Mode
Enter
ALMRSET:
CALIB:
CAL-0%
Default Display
Description
Mode Function - Alarms Reset
Mode Function - Calibrate
Banner: Apply zero gas, enter <E> when done
Operation: Confirm area clear of gas, or apply zero air to sensor.
M E
S T
M E
S T
Enter ACK Zero gas setting acknowledged
50%-SPAN Banner: Select span, enter <E> when done
Enter CAL-50% Banner: Apply 50% gas, then enter <E> to calibrate gas sensor
C 0%LEL
Operation: Apply calibration gas.
Reference or Sub Routine A use Sub Routine B
CXX%LEL
Operation: As gas is applied the reading will increase - wait 3 minutes use Sub Routine C
M E
S T
Enter CAL-OK Calibration Passed - now remove gas
WAIT-300
Operation: Five minute time out before sensor is returned to service.
M E
S T
Mode (Any)
Sub-Routine A - Abort Calibration
Operation: Hold magnet over Mode <SW1> for ten seconds to abort calibration
Banner: Operate mode
Default Display 0%LEL
Sub-Routine B - Select Span
M E
S T
M E
S T
M E
S T
M E
S T
Down
50%-SPAN Banner: Select span, enter <E> when done
Down 25%-SPAN
Adj-SPAN
Operation: Change Span Gas Value to 25%
Operation: User adjustable value
Enter 25%-SPAN
Operation: Ready for user adjustment
Up (x5) 30%-SPAN
Operation: User adjustment to new value 30%
M E
S T
Sub-Routine C - Calibration Fail
Enter CAL-FAIL
Operation: No calibration gas applied, or sensor did not respond correctly.
WAIT-300
Operation: Five minute time out before sensor is returned to service.
Table 5-1
Calibration
Page: 22
Model 5100-02-IT Combustible Gas Sensor Module
6. SERVICE
6.1
SENSOR MODULE CONFIGURATION
The gas sensor module is comprised of the following sub-assemblies (Figure 6-1):
5100-02-IT Gas Sensor Module
SPL21810 Alluminum Enclosure (SPL32178 316SS Enclosure)
There are no field serviceable components below the sub assembly level.
6.2
ENCLOSURE REPLACEMENT
The enclosure should be replaced if the cover threads or conduit threads have been damaged, or if the enclosure has been damaged sufficiently that it no longer meets the required NEMA classification.
To replace the enclosure follow the transmitter and sensor assembly removal instructions, remove the damaged enclosure from its conduit, install a new enclosure and continue the transmitter and sensor assembly replacement instructions.
Page: 23
Figure 5-1
Module Components
Model 5100-02-IT Combustible Gas Sensor Module
6.3
TRANSMITTER REPLACEMENT
The transmitter assembly should be replaced when it is determined that it is unreliable, noisy or cannot be calibrated. This may occur due to age, corrosion or failed components.
To replace the transmitter assembly: a. Remove the cover of the main enclosure b. Unscrew the two thumb screws in the top of the cover plate, lift the assembly and rotate 90 o wiring service loop
to relieve the c. Unplug the sensor connector from the transmitter d. Plug connector into new transmitter (be sure to match numbers between connector and socket). e. Restore power and allow a minimum of 3 hours for stabilization before re-calibration
6.4
SENSOR REPLACEMENT
The gas sensor which is located inside the sensor assembly housing can be replaced without replacement of the housing. The gas sensor needs replacement when:
The “CAL-FAIL” message appears after calibration
The sensor output signal is noisy, causing erroneous gas level readings
To replace the sensor: a. Confirm that system power has been removed b. Remove the gas sensor module enclosure cover, c. Unscrew the two thumb screws in the top of the faceplate, lift the transmitter assembly and rotate 90 relieve the wiring service loop. o
to d. Unplug the sensor connector from the transmitter e. Unscrew the old sensor assembly from the enclosure conduit hub. Remove the sensor assembly with its harness f. Unscrew sensor housing cover from the sensor (be sure to loosen the set screw first) g. Carefully pull the old sensor straight up from the socket h. Press the new sensor into the socket. i. Reverse the preceding steps to install the sensor assembly. j. Allow the new sensor to stabilize for a minimum of 3 hours and then calibrate using the procedure in Section
5.
6.5
INSTALLATION INSPECTION
Prior to system start-up or trouble shooting, the entire system should be visually inspected. The following are guidelines for that inspection:
• Controller installed in conformance to instruction manual recommendations.
• AC power is correctly grounded.
• Hot AC and relay connections have safety covers installed.
• All splices are soldered or via terminal block.
• Cabling is away from sources of electrical noise where possible.
• Connector P2, terminals P2 1, 2, 3 on sensor module are connected to Sentry controller as Power, Signal,
Ground, respectively.
6.5.3 SENSOR MODULE INSTALLATION
• Module installation in conformance with this manual.
• Modules accessible for calibration.
Page: 24
Model 5100-02-IT Combustible Gas Sensor Module
• Wiring terminations clean and correct.
6.5.4 MOISTURE TRAPS AND RAINSHIELDS
• Conduit seals and drains installed to avoid moisture build up in electronics enclosure. Water accumulation in sensor module enclosures is a major cause of damage and system failures - take precautions to seal electrical conduits and provide moisture traps and drains to avoid water damage
• Rain-shields installed where applicable.
• Regulated DC Voltage to be applied to the sensor module must be between 10 VDC and 30 VDC.
6.5.6 INSPECTION AND TROUBLESHOOTING GUIDE
The inspection and troubleshooting guide can be used to step through the system start-up and to determine the corrective action if a fault occurs.
6.5.7 IF MODULE DOES NOT RESPOND TO GAS
1. Repeat calibration procedure.
2. Remove the gas and wait for the timer to completely count down.
3. Apply 50%LEL and verify that the sensor sees 50% LEL gas after calibration.
4. If the sensor still does not see gas, power cycle the unit and repeat calibration.
6.5.8 IF THE MODULE DOES NOT COME OUT OF WARM UP
1. Make sure the sensor is placed in an ambient room temperature environment.
2. Power cycle the sensor.
3. Ensure that the sensor is not exposed to combustible gas during warm-up.
6.5.9 IF THE MODULE DOES NOT DISPLAY THE CORRECT %LEL
1. Power cycle the unit.
2. Recalibrate the sensor.
6.5.10 IF THE DISPLAY SHOWS ‘NO SENSR’ –SENSOR FAILING
1. Power down the unit
2. Open the enclosure and unplug the sensor from the transmitter board.
3. Plug the sensor back into the transmitter board carefully and ensure a secure fit.
4. Power up the unit.
6.5.11 IF THE MODULE SHOWS “***CALIBRATION REQUIRED***”
1. Calibrate the module
6.5.12 IF THE MODULE SHOWS “***UNCALIB***”
1. Hold magnet to any key to acknowledge message
2. Calibrate the module
6.5.13 IF THE DISPLAY SHOWS ‘H’ (OR L) THEN THE LOCAL HIGH OR LOW ALARM IS ACTIVE
6.5.14 IF THE DISPLAY SHOWS ‘W’ – RADIO FREQUENCY INTERFERENCE
1. Remove source of interference.
6.5.15 IF THE DISPLAY SHOWS “C” – CALIBRATION MODE
1. Complete calibration or exit to operating mode.
6.5.16 OTHER ERROR MESSAGES – CALL FACTORY
1. E: OSC F1 Oscillator Fail
Page: 25
Model 5100-02-IT Combustible Gas Sensor Module
7. APPENDICES
7.1 APPENDIX A: SPECIFICATIONS
Specifications:
Sensor:
Type:
Range:
Repeatability:
Response time:
Accuracy:
Sensor Life:
Output:
Display:
Relays (Standard):
Relays (Option):
420 mA:
RS485:
Input:
Remote Alarm Reset:
Electrical Data:
Power consumption:
Connection type:
Input voltage:
RFI/EMI Protection:
Operating Range:
Ambient Temperature Range:
0-100% LEL Combustible
LEL
< 12 sec to 60% full scale
+/- 1% for 0-50% LEL range
+/- 2% for 51-100% LEL range
Typically >3 years
Fixed and Scrolling LED
High Alarm, Low Alarm, Trouble (SPDT Form C, 0.25 Amp@ 250VAC)
Signal Output: Sentry Digital Bus
High Alarm, Low Alarm (8 Amp, 250VAC)
3-wire sensor powered analog 4-20 mA or optically isolated (Calibration: 4.0 mA (default) or 1.5 mA. or Normal)
Serial RS-485 Modbus RTU
Normally open digital input
3 watts
3 wire
24 VDC nominal: 10-30VDC
EN50081-2, EN50082-2
-40o to 176 oF(-40o to 80oC)
Enclosure:
Dimensions:
Weight:
Housing:
7.5 x 5.0 x 4.8 inches (H x W x D)
(21.6 x 12.7 x 12.2 cm)
2.7 lb. (1.3 Kg)
Electrical Classification:
Performance: Explosion proof, Class 1, Div. I, Groups B, C, D
Class 1, Zone 1, Group IIB+H2 IP66
Approvals:
FM Approved: Approval Standards: 6320, 3600
Modbus:
Baud: 38400 (Adjustable 2400 to 38400 baud)
Parity: None bit: bits:
1
8
Memory map:
None
Available upon request
Warranty:
Limited warranty: 2 years
Specifications subject to change without notice
Page: 26
Model 5100-02-IT Combustible Gas Sensor Module
7.2 APPENDIX B: MODEL NUMBERS & PARTS LIST
Sensor Module
5100-02-IT-AL Sensor Module, Combustible, Aluminum housing
Options
5311-00
5394-51 Remote Sensor/Display Option
5394-61
5394-62
Auxiliary Connection Assembly
Auxiliary Relay Assembly
Calibration Items
1200-26
1250-01
1256-01
1260-00
1260-02
1260-42
1290-02
Gas Sensor Calibrator w/2 Gas Cylinders
Gas Sensor Calibrator Kit
Regulator Type A Calibrator
Gas Cylinder – Air (Type A), 105 liters
Gas Cylinder – Methane 50% LEL, (type A), 105 liters
Gas Cylinder - Hydrogen, 50% LEL, (Type A), 105 liters
Gas Cylinder - Combustible, CH4, 50% L.E.L.
5358-01 Calibration Adapter - Direct, Standard
Calibration/Configuration Magnetic Tool
Spare Parts
SPL21813
5200-02-IT
Transmitter for 5100-02-IT
Sensor Assy for 5100-02-IT
Page: 27
Model 5100-02-IT Combustible Gas Sensor Module
7.3 APPENDIX C: LIMITED WARRANTY
SIERRA MONITOR CORPORATION warrants its products to be free from defects in workmanship or material under normal use and service for two years after date of shipment. SMC will repair or replace without charge any equipment found to be defective during the warranty period. Final determination of the nature and responsibility for defective or damaged equipment will be made by SMC personnel.
All warranties hereunder are contingent upon proper use in the application for which the product was intended and do not cover products which have been modified or repaired without SMC approval or which have been subjected to accident, improper maintenance, installation or application, or on which original identification marks have been removed or altered. This Limited Warranty also will not apply to interconnecting cables or wires, consumables (i.e. calibration gases, batteries, sensors), nor to any damage resulting from battery leakage.
In all cases SMC’s responsibility and liability under this warranty shall be limited to the cost of the equipment. The purchaser must obtain shipping instructions for the prepaid return of any item under this warranty provision and compliance with such instruction shall be a condition of this warranty.
Except for the express warranty stated above, SMC disclaims all warranties with regard to the products sold hereunder including all implied warranties of merchantability and fitness and the express warranties stated herein are in lieu of all obligations or liabilities on the part of SMC for damages including, but not limited to, consequential damages arising out of/or in connection with the use or performance of the product.
Page: 28
Model 5100-02-IT Combustible Gas Sensor Module
7.4 APPENDIX D: REMOTE SENSOR DRAWING 5394-50
Page: 29
Model 5100-02-IT Combustible Gas Sensor Module
7.5 APPENDIX E: AUXILIARY RELAY ASSEMBLY 5394-62
Page: 30
Model 5100-02-IT Combustible Gas Sensor Module
7.6 APPENDIX F: AUXILIARY CONNECTION ASSEMBLY 5394-61
Page: 31
Model 5100-02-IT Combustible Gas Sensor Module
7.7 APPENDIX G: AUXILIARY RS-485 MULTIDROP ASSEMBLY 5394-64
Page: 32
Model 5100-02-IT Combustible Gas Sensor Module
Page: 33
Model 5100-02-IT Combustible Gas Sensor Module
7.8 APPENDIX H: MODBUS MEMORY MAP
Read Register Table
Register Description
40001 Concentration
40002
40003
Temperature
High Alarm Relay
40004
40005
Low Alarm Relay
Low Alarm Value
40006 High Alarm Value
40007 Reserved
Comments
Gas Concentration multiplied by 100
Temperature in degrees Celsius scalled by a factor of 100
Boolean indicating the High Alarm Status, 0 No Alarm, 1 High Alarm
Boolean indicating the Low Alarm Status, 0 No Alarm, 1 Low Alarm
Low alarm set point, used for activating Alarms
High alarm set point, used for activating High Alarms
40008 Reserved
40009 Reserved
40010 Reserved
40011 Trouble Bits 0 for no trouble
40012
40013
40014
40015
Trouble
High Alarm Immediate Like 40003. but never latched
Low Alarm Immediate
Random ID
1 for any trouble, 0 for no trouble
Like 40004, but never latched
Randomly generated permanent ID of sensor
40016 Restart
40017
40018
Run time – high
Run time – low
40019 Max. gas value
40020 Model
40021
40022
40023
40024
40025
Range
Units
Temperature Units
Gas Scale
Temperature Scale
In minutes
In minutes
*scale ((see 40024)
51002
*scale (see 40024)
1 is %LEL
0 is C, 1 is F
Value like 1 or 100
Value like 1 or 100
Page: 34
Model 5100-02-IT Combustible Gas Sensor Module
7.9 APPENDIX I: COMBUSTIBLE GAS SCALING FACTORS
For combustible gas monitoring, a calibration standard of Methane may be used in conjunction with scaling factors to cause Sentry concentration display and alarm function in %LEL scale of another gas as follows:
GAS METHANE
FACTOR
Acetaldehyde 60
Acetic Acid 54
Acetic Anhydride 46
Acetone 52
Acetylene 57
Alkyl Alcohol 51
Ammonia 126 n-Amyl Alcohol 33
Aniline 39
Benzene 41
Biphenyl 25
1,3-Butadiene 56 n-Butane 58 iso-Butane 52
Butene-1 45 cis-Butene-2 48 trans-Butene-2 51 n-Butyl Alcohol 34 iso-Butyl Alcohol 53 tert-Butyl-Alcohol 74 n-Butyl Benzene 31 iso-Butyl Benzene n-Butyric Acid
Carbon Disulfide
Carbon Monoxide
32
38
18
75
Carbon Oxysulphide 93
Chlorobenzene 34
Cyanogen 89
Cyclohexane 41
Cyclopropane 62 n-Decane 33
Diethylamine 49
Dimethylamine 58
2,3-Dimethylpentane 40
2,3-Dimethylpropane 40
Dimethylsulphide 43
1,4-Dioxane 45
Epichlorohydrin 45
Ethane 68
Ethyl Acetate
Ethyl Alcohol
51
73
Ethylamine 53
Ethyl Benzene
Ethyl Bromide
36
91
Ethyl Chloride 57
Ethylcyclopentane 40
Ethylene 71
Ethylenedichloride 66
Ethyleneoxide 52
NOTES:
GAS METHANE
FACTOR
Diethyl Ether 46
Dimethoxyethane 42
Dimethyl Ether 63
Dimethylformamide 46
Ethyl Formate 44
Ethylmercaptan 56 n-Heptane 39 n-Hexane 37
Hydrazine 45
Hydrogencyanide 48
Hydrogen 77
Hydrogen Sulfide 41
Methane 100
Methyl Actetate 50
Methyl Alcohol 86
Methylamine 77
Methyl Bromide
Methyl Chloride
90
102
Methylcyclohexane 44
Methylenedichloride 93
Methylethylether 44
Methylethylketone 41
Methyl Formate 67
Methylmercaptan 61
Methylpropionate 51
Methyl n-propylketone 40
Napthalene 34
Nitromethane 34 n-Nonane 31 n-Octane 37 n-Pentane 46 i-Pentane 46
Propane 55 n-Propyl Alcohol 47 n-Propylamine 48 n-Propylchloride 50
Propylene 52
Propyleneoxide 46 iso-Propylether 44
Propyne 42
Toluene 40
Triethylamine 40
Trimethylamine 48
Vinylethylether 42 o-Xylene 36 m-Xylene 39 p-Xylene 39
JP-4 (Jet Fuel) 41
1. Scaling factors are not FMRC approved.
2. Base data source: EEV sensor specification catalog. (EEV claims some data is the result of specific tests, other data is empirically derived).
Page: 35
Model 5100-02-IT Combustible Gas Sensor Module
7.10 APPENDIX J: Menu Key for 5100-02-IT Gas Sensor Module
M : MODE
• Key : ENTER
MAIN MENU
Use the M key to access each of the 4 main sections of the menu.
M M M M M
| | | | |
|- ALMRSET: |- : |- : |-
EXIT?
ALARM RESET MENU
ALMRSET:
|
E – RESET (Resets current alarm)
CALIB MENU
CALIB
:
|
E – CAL-0% (Calibrate Zero)
|
E – Ack (Acknowledges Zero)
|
*50%-SPAN (Last span gas used – initially set at 50%)
| |
| ▲ 25%-SPAN
| ▲ 50%-SPAN (Select Span gas value from below)
| ▲ 75%-SPAN
| ▲ Adj-SPAN (To select an alternate span gas value)
| |
|
E
50%-SPAN
| |
| ▲ 51%-SPAN (Change span value to desired, once completed E starts calibration)
|
E C XX%LEL (Reading the value of the calibration gas being applied)
|
|- CAL-OK (if successful) or CAL-FAIL (if unsuccessful)
Page: 36
Model 5100-02-IT Combustible Gas Sensor Module
SETUP MENU
Once in the SETUP menu use the ▲ or ▼ keys to access each of the 5 main sections of the SETUP menu.
▼ ▼ ▼ ▼ ▼
| | | | |
|- Alarms: |- : |- : |- RS-485
SETUP:
|
E
– Alarms (Alarms Set-Point Adjustment)
| |
|
E
– H.Alarm (High Alarm Setup)
| |
| E --------------------------- OR---------------------------------------▼
| | |
| |- HASP: 60 (Current Hi Alarm set-point
| |
|- L. ALARM (Low Alarm Setup)
|
| ▲ or ▼ (To adjust to desired set-point)
| |
| E – Ack (Accepts set-point)
|
|
|
E
LASP:20 (Current Lo Alarm Set-point)
|
▲ or ▼ (To adjust to desired set-point)
|
E – Ack (Accepts set-point)
|
|----▼ Relays (Relay Set Point Adjustment)
| |
|
E
----------------------------- OR-----------------------------------------▼:
| | |
| | - H. Relay (High Relay Setup)
| |
| E – Latch
| |
|
▲ or ▼ (To adjust to desired condition)
|- L. Relay (Low Relay Setup)
|
E – Latch
|
▲ or ▼ (To adjust to desired condition)
| (Selections are Latch, NonLatc, or Senty)
| (* indicates current status, Sentry = Sentry controller controls alarm relay action)
|
|----▼ Gas Factr (Gas Factor Adjustment)
| |
| E
*Factr100 (* = current selection)
| |
| ▲ or ▼ (To adjust to desired factor)
| If USER is selected use the ▲ or ▼ keys to change to desired value
|
Page: 37
Model 5100-02-IT Combustible Gas Sensor Module
|
|----▼ 4-20mA (Verifies 4mA or 20mA output and selects condition of output during calibration)
| |
| ▼ -------or--------------- E Calib
| |
| |
| |
| |
| |
| |
|
|- Out: 4mA
|
▼ --or—E (To calibrate analog output 4mA, |▲ or ▼ to adjust level,
| then t o accept)
| |
| |
| |
| |
▼ --or--E (To calibrate analog output 20mA, |▲ or ▼ to adjust level,
| then to accept)
|- 4mA
▼ --or—E (To calibrate analog input 4mA, |▲ or ▼ to adjust level,
| |
| |
| |
| |
| |
|
|- 20mA
then to accept)
▼--or--E (To calibrate analog input 20mA, |▲ or ▼ to adjust level,
then to accept)
| ▼ -------or--------------- E CalibOut (Adjust 4-20mA output during Calibration)
| |
| |
| |
|
|- Track: (▲ or ▼ (To adjust action/mA value during calibration
Track = mA value tracks Gas value
| |
| |
| |
| |
| |
Hold = holds mA value existing prior to calibration
C1.50mA = 1.50 mA during calibration
C4.00 mA = 4.00 mA during calibration
User mA = |▲ or ▼ to adjust to desired mA value
| ▼ -------or--------------- E Tbl Out (Adjust 4-20mA output during Trouble condition)
| | |
| |
| |
|- T2.50mA: (▲ or ▼ (To select 2.50mA or User mA, * = current value)
User mA = |▲ or ▼ to adjust to desired mA value
| |
| |
|----▼ RS-485 (Select RS-485 address and baud rate)
| |
| | - Address
| |
| ▼ | -------or--------------- E Addr:016 (Use (▲ or ▼ and E to select module address – 016 to 254)
| |
| |- Baud --------------- E *38400 (Use |▲ or ▼ and E to select baud rate, * = current selection)
MAINT MENU
MAINT:
:
|
E – V2.00aB (Software version installed on module)
|
E
– CCC001 (Configuration number)
Page: 38
Model 5100-02-IT Combustible Gas Sensor Module
THIS PAGE INTENTIONALLY LEFT BLANK
Page: 39
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 5 PRODUCT DESCRIPTION
- 5 GENERAL
- 5 CONFIGURATION
- 5 OPERATION
- 5 SENTRY INTERFACE
- 7 MODBUS OPERATION
- 7 ANALOG OPERATION
- 7 AUXILIARY RELAY OPERATION (Appendix E)
- 7 ENHANCED CONNECTION (Appendix F)
- 7 AUXILIARY RS-485 MULTIDROP (Appendix G)
- 7 REMOTE SENSOR (Appendix D)
- 7 REMOTE ALARM RESET
- 7 MECHANICAL
- 7 ENCLOSURE
- 7 TRANSMITTER ELECTRONICS
- 7 SENSOR ASSEMBLY
- 8 WIRING
- 8 REQUIREMENTS
- 9 CAUTIONS & WARNINGS
- 9 INTRODUCTION
- 9 GENERAL
- 9 WIRING
- 10 CATALYTIC BEAD SENSOR MODULES
- 11 INSTALLATION
- 11 LOCATIONS
- 11 WIRING
- 11 ANALOG 4-20 mA OPERATION
- 11 MODBUS OPERATION USING RS-485 CONNECTION
- 11 SENTRY OPERATION USING SMC SENTRY CONNECTION
- 11 GENERAL
- 12 INSTALLATION
- 14 CONFIGURATION
- 17 INTRODUCTION – HUMAN-MACHINE INTERFACE SYSTEM
- 17 INTERFACE
- 19 SET-POINTS
- 22 FUNCTIONS
- 23 CALIBRATION
- 23 FREQUENCY
- 23 PREPARATION
- 23 CALIBRATION GAS DELIVERY METHODS
- 23 CALIBRATION PROCEDURE
- 23 SENSOR EXPOSURE TO GAS
- 25 SERVICE
- 25 CONFIGURATION
- 25 REPLACEMENT
- 26 INSPECTION
- 26 CONTROLLER INSTALLATION
- 26 CABLING INSTALLATION
- 26 SENSOR MODULE INSTALLATION
- 27 MOISTURE TRAPS AND RAINSHIELDS
- 27 STANDARD VOLTAGES
- 27 INSPECTION AND TROUBLESHOOTING GUIDE
- 27 IF MODULE DOES NOT RESPOND TO GAS
- 27 IF THE MODULE DOES NOT COME OUT OF WARM UP
- 27 If the module does not display the correct %LEL
- 27 If the display shows ‘NO SENSR’ –Sensor Failing
- 27 IF THE MODULE SHOWS “***Calibration Required
- 27 IF THE MODULE SHOWS “***UNCALIB
- 27 If the display shows ‘H’ (OR l) THEN THE LOCAL HIGH OR LOW ALARM IS ACTIVE
- 27 If the display shows ‘w’ – radio freQuency INTERFERENCE
- 27 If the display shows “C” – calibration mode
- 27 other error messages – call factory
- 28 APPENDICES
- 28 SPECIFICATIONS
- 30 WARRANTY
- 37 FACTORS