Tripp Lite SU6000RT4UHV User's Manual


Add to my manuals
7 Pages

advertisement

Tripp Lite SU6000RT4UHV User's Manual | Manualzz

Tripp Lite

1111 West 35th Street

Chicago, IL 60609 USA

Telephone: +(773) 869 1234

E-mail: [email protected]

Model #: SU6000RT4UHV

SmartOnline 6kVA On-Line Double-Conversion UPS, 4U Rack/Tower, 200-240V NEMA outlets

Highlights

Completely user hot-swappable—no service call or technician needed

Protects rackmount servers, telecom systems and other networking equipment in high-voltage environments with true on-line operation, pure sine wave output and zero transfer time

4 AC outlets (2 L6-20R; 2 L6-30R) with 200/208/220/230/240V 50/60Hz output

6kVA/5400W capacity in 4U form factor with power module and independent, detachable PDU

Hot-swappable power and battery modules

8.5-minute half-load runtime, 2-minute full-load; expandable runtime with external battery packs

Front panel LEDs with detailed LCD monitoring and control screen

USB, RS232 and SNMP communication ports with included PowerAlert software for complete network power management and control

$250,000 Ultimate Lifetime Insurance; 2-year warranty

Description

Featuring true on-line operation with pure sine wave output, zero transfer time to battery and complete UPS replacement capability with no downtime, the SU6000RT4UHV provides the highest level of protection available for mission-critical equipment from power outages, voltage fluctuations and transient surges. It converts incoming AC power to DC, and re-converts it back to filtered AC output with a pure sine wave, isolating connected components from all power problems in high-voltage environments. The SU6000RT4UHV has a 6kVA/5400W capacity and 4 AC outlets

(2 L6-20R; 2 L6-30R).

With its detachable PDU, the SU6000RT4UHV is easily hot-swappable by a user of any skill set—no need for lengthy and expensive service calls, and no downtime if a repair or battery replacement is needed. In bypass mode, the PDU passes power to equipment without the use of the power and battery modules, allowing them to be removed while keeping your application in operation.

UPS battery backup keeps connected equipment operational through short power failures, and provides time to save data and perform an orderly system shutdown in case of a prolonged blackout. The SU6000RT4UHV‘s runtime can be expanded with optional external battery packs.

The SU6000RT4UHV features a highly efficient (96%) economy mode setting that can significantly reduce a facility's energy costs by minimizing heat output, reducing cooling requirements and consuming less electricity.

An LCD display with LED indicators enables IT personnel to monitor operating modes and conditions. The LCD/LED panel rotates for viewing in horizontal rack or vertical tower installations and includes an audible alarm that signals various conditions.

The SU6000RT4UHV features a USB port and a DB9 port that, when used with Tripp Lite's included PowerAlert software, provide comprehensive network power monitoring and control. An optional SNMPWEBCARD accessory can enable the UPS to operate as an IP managed device.

The unit requires only 4U of rack space in a standard rack enclosure and can be installed in a 2-post rack using the 2POSTRMKITHD accessory, or in a tower configuration with the 2-9USTAND accessory.

The SU6000RT4UHV comes with $250,000 Ultimate Lifetime Insurance coverage for connected equipment and a 2-year warranty.

Features

Tripp Lite SU6000RT4UHV 6000VA / 6kVA / 5400 watt online, double-conversion UPS system in a single 4U rack/tower compatible housing

(at 208V nominal, output is limited to 4992 watts)

Full-time active power conditioning maintains clean, continuous dual-conversion AC output free of voltage fluctuations, power interruptions and line noise

Fault tolerant electronic bypass maintains utility output during a variety of UPS fault conditions

Detachable back panel PDU contains input line cord connection and output receptacles, plus manual bypass switch to support hot-swappable whole UPS replacement with no interruption to connected equipment

hot-swappable whole UPS replacement with no interruption to connected equipment

L6-30P input plug; two L6-30R and two L6-20R outlets

Included rail kit supports 4U 19 inch rackmount installation in 4 post racks

Optional 2POSTRMKITHD supports installation in 2 post 19 inch racks (1 required for SU6000RT4UHV)

Optional 2-9USTAND supports upright tower placement (1 required for SU6000RT4UHV)

Maximum installed rack depth of only 20.7 in. / 52.6cm

Maintains full-time sine wave output within 2% of selected 200/208/220/230/240V nominal in double conversion mode

Corrects brownouts to 156V at full load (100V at 50% load or less)

Corrects overvoltages to 290V at full load (300V at 90% load or less)

Supports 50/60Hz operation for worldwide frequency compatibility

Double-conversion operation offers full-time AC to DC, then DC to AC conversion to maintain perfectly regulated sine wave AC output with enhanced protection from harmonic distortion, fast electrical impulses and other hard-to-solve power problems not addressed by other UPS types

High efficiency ECONOMY MODE operation significantly reduces BTU heat output and operating energy costs

Network-grade AC surge and noise suppression

Supports detailed monitoring of equipment load levels, self-test data and utility power conditions via built-in RS-232, USB and optional

SNMP card slot interfaces

UPS card slot supports one card-based network interface option (part # SNMPWEBCARD) or dry-contact monitoring accessory (part #

RELAYIOCARD)

Optional SNMPWEBCARD offers communications and control via secure remote web and network interfaces

Optional RELAYIOCARD supports six configurable hard contact closure outputs for custom event notification

Optional RELAYIOMINI interface module offers three configurable hard contact closure outputs for custom event notification (requires removal of USB interface module)

HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X

Includes Free PowerAlert monitoring software packages; PowerAlert LOCAL for desktops and small business networks, PowerAlert NSA

(Network Shutdown Agent) for larger networks and PowerAlert NMS (Network Management System) for monitoring up to 250

SNMP-enabled UPS, PDU and other networking devices

Front panel LEDs and LCD readout with scroll controls support front-panel visual monitoring of all major UPS functions with support for a variety of control options to support advanced UPS settings and configurations

LED/LCD display panel rotates for viewing in rackmount or tower configurations

Supports Emergency Power Off (EPO) via built-in interface

Battery independent restart ensures automatic UPS power-up without user interaction after lengthy power outages, even when batteries are expired and require replacement

BP192V12-3U external battery packs are field replaceable and hot swappable

Some external battery configurations require the use of Tripp Lite's External Battery Configuration Software (see manual)

Frequency conversion mode enables conversion of 60Hz to 50Hz or 60Hz to 50Hz (no de-rating)

Specifications

OUTPUT

Output Volt Amp

Capacity (VA)

Output kVA capacity

(kVA)

Output Watt Capacity

(watts)

Output kW capacity

Output power factor

Output Capacity

Details

Crest Factor

Nominal Output

Voltage(s) Supported

6000

6.0

5400

5.4

0.9

Output capacity de-rates to 4992 watts when used at 208V nominal

3:1

200V; 208V; 220V; 230V; 240V

Frequency compatibility

Frequency compatibility details

Output voltage regulation (line mode)

Output voltage regulation (Economy line mode)

Output voltage regulation (Battery mode)

50/60 Hz (auto-selectable)

Output frequency matches input nominal on startup; Frequency conversion mode enables conversion of 60Hz to

50Hz or 50Hz to 60Hz (no de-rating)

+/- 2%

+/- 10%

+/- 2%

Built-in UPS output receptacles

Output receptacle details

2 L6-20R outlet(s); 2 L6-30R outlet(s)

Output receptacles and input line cord are mounted on a detachable PDU backplate with bypass switch to enable hot-swappable power module replacement

Output circuit breaker 20A breaker protects L6-20R outlets, L6-30R outlets are unbreakered

Output AC waveform

(AC mode)

Pure Sine wave

Output AC waveform

(battery mode)

INPUT

Rated input current

(at maximum load)

Pure Sine wave

31.9A (200V), 30.6A (208V), 29A (220V), 27.7A (230V), 26.6A (240V)

200V AC; 208V AC; 220V AC; 230V AC; 240V AC Nominal Input

Voltage(s) Supported

Nominal input voltage description

Factory configured to 208V

UPS input connection type

UPS Input cord length (ft.)

L6-30P

10

UPS Input cord length (m)

Recommended

Electrical Service

BATTERY

Full load runtime

(minutes)

Half load runtime

(minutes)

Expandable battery runtime

External battery pack compatibility

DC system voltage

(VDC)

3

30A

2 minutes (5400 watts)

8.5 minutes (2700 watts)

Runtime is expandable with external battery packs

BP192V12-3U

192

; BP192V557C-1PH ; BP192V787C-1PH ; BP192V1037C-1PH ; BP192V1407C-1PH

Battery recharge rate

(included batteries)

Replacement battery cartridge (internal

UPS battery replacement)

6 hours from 10% to 90% (internal batteries)

RBC5-192

Battery Access Front panel battery access door

Battery replacement description

Hot-swappable, user replaceable internal batteries

VOLTAGE REGULATION

Voltage regulation description

Online, double-conversion power conditioning

Overvoltage correction

Corrects overvoltages as high as 300V (

Undervoltage correction

Corrects undervoltages as low as 100 (

LEDS ALARMS & SWITCHES

LED Indicators 6 LEDs indicate line power, online mode, economy/bypass mode, on-battery, charger and AC output status; LCD screen offers additional information and control options

Alarms Unique audible alarms for all major UPS, environmental and power conditions (see manual)

Alarm cancel operation

Alarm cancel switch

Switches Includes main power off/on switch, plus 2 switches to set and execute scrollable LCD functions. A manual bypass switch featured on the detachable PDU allows for complete removal of the UPS during routine maintenance without disrupting power to connected loads.

SURGE / NOISE SUPPRESSION

UPS AC suppression response time

Instantaneous

Yes EMI / RFI AC noise suppression

PHYSICAL

Installation form factors supported with included accessories

Installation form factors supported with optional accessories

Primary form factor

4 post 19 inch rackmount (mounting rail kit included)

2 post rackmount (2POSTRMKITWM); Tower (2-9USTAND)

Rackmount

6.85 x 17.5 x 20.7

UPS / Power Module dimensions in primary form factor

(height x width x depth / inches)

UPS / Power Module dimensions in primary form factor

(height x width x depth / cm)

17.4 x 44.5 x 52.6

Installed whole system total rack space height (rack spaces)

4U

Secondary form factor Tower

UPS / Power Module weight (lbs)

108

49 UPS / Power Module weight (kg)

UPS Shipping dimensions (height x width x depth / inches)

12.7 x 23.6 x 29.1

UPS Shipping dimensions (height x width x depth / cm)

32.3 x 59.9 x 73.9

Shipping weight (lbs)

Shipping weight (kg)

158

71.7

UPS housing material Steel

Fans Cooling method

ENVIRONMENTAL

Operating

Temperature Range

+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius

+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius Storage Temperature

Range

Relative Humidity 0 to 95%, non-condensing

1767 AC mode BTU / hr.

(full load)

AC economy mode

BTU / hr. (full load)

707

1784 Battery mode BTU / hr. (full load)

AC economy mode efficiency rating

(100% load)

Operating Elevation

(ft)

Audible Noise

96%

0-3000m (0 to 10,000 ft.)

60 dBA at front side 1 meter

0-3000 m Operating Elevation

(m)

COMMUNICATIONS

Communications interface

Network monitoring port description

PowerAlert software

USB (HID enabled); DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface

Additional contact closure support with optional RELAYIOCARD and RELAYIOMINI interface cards. RELAYIOMINI installation requires removal of panel containing USB ports

Included

Communications cable

USB, DB9 serial and EPO cables included

WatchDog compatibility

Yes

LINE / BATTERY TRANSFER

Transfer time No transfer time (0 ms.) in online, double-conversion mode

Transfer time

(economy mode)

8 ms. typical power failure response in optional economy mode

Low voltage transfer to battery power

(setpoint)

High voltage transfer to battery power

(setpoint)

SPECIAL FEATURES

Cold Start (startup in battery mode during a power failure)

156V (full load) / 100V (50% load or less, derates linearly)

280V (full load) / 300V (90% load or less)

Cold-start operation supported

High availability UPS features

Green & high efficiency features

CERTIFICATIONS

UPS Certifications

Automatic inverter bypass; Manual bypass switch; Detachable hot-swap PDU; Hot swappable UPS power module;

Hot swappable batteries

High efficiency economy mode operation; Support for daily startup and shutoff; Schedulable daily hours of economy mode operation

Tested to UL1778 (USA); Tested to CSA (Canada); Meets FCC Part 15 Category A (EMI); ROHS (Restriction of

Hazardous Substances)

IEC 61000-4-5 1995 B Surge Immunity UPS Certification details

WARRANTY

Product Warranty

Period (Worldwide)

2-year limited warranty

Related Items

Optional Products

Related Model

RELAYIOMINI

BP192V12-3U

2POSTRMKITHD

2-9USTAND

SNMPWEBCARD

ENVIROSENSE

RELAYIOCARD

AS400CABLEKIT2

WEXT3-SU6000HV

Description

3 Relay I/O Mini-module

BP192V12-3U - External Battery Pack for UPS System

Enables 2-Post Rackmount Installation of 3U and Larger UPS, Transformer and Battery

Pack Components

Enables Tower Placement of Rackmount UPS Systems

For remote monitoring and control via SNMP, Web, or Telnet.

Monitors temperature, humidity and contact-closure inputs. (Requires SNMPWEBCARD or switched PDU.)

Programmable Relay I/O Card

Power Management Tools - UPS Communication Cable Kit for System i / AS400 / iSeries Servers

3-Year Extended Warranty - For SU6000RT3UHV only

1

1

1

Qty.

1

1

1

1

1

1

WEXT5-SU6000HV 5-Year Extended Warranty - For SU6000RT3UHV only

More information, including related products, owner's manuals, and additional technical specifications, can be found online at www.tripplite.com/en/products/model.cfm?variables.txtModelID=4534 .

1

Copyright © 2013 Tripp Lite. All rights reserved. All trademarks are the sole property of their respective owners. Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice. Photos may differ slightly from final products.

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Key Features

  • 6 kVA 5400 W
  • 4 AC outlet(s)
  • Rackmount Black

Related manuals

advertisement