HT SOLAR I-Ve User manual


Add to my manuals
80 Pages

advertisement

HT SOLAR I-Ve User manual | Manualzz

 Copyright HT ITALIA 2017

Release EN 2.00 - 24/03/2017

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

Table of contents:

1.

 

SAFETY PRECAUTIONS AND PROCEDURES .......................................................... 3

 

1.1.  Preliminary instructions ..................................................................................................... 3 

1.2.  During use ......................................................................................................................... 4 

1.3.  After use ............................................................................................................................ 4 

1.4.  Overvoltage categories - Definitions ................................................................................. 4 

2.

 

GENERAL DESCRIPTION ........................................................................................... 5

 

2.1.  Introduction ........................................................................................................................ 5 

2.2.  Instrument features ........................................................................................................... 5 

3.

 

PREPARATION FOR USE ........................................................................................... 6

 

3.1.  Initial checks ...................................................................................................................... 6 

3.2.  Instrument power supply ................................................................................................... 6 

3.3.  Storage .............................................................................................................................. 6 

4.

 

DESCRIPTION OF PARTS .......................................................................................... 7

 

4.1.  Instrument description ....................................................................................................... 7 

4.2.  Keyboard description ......................................................................................................... 8 

4.3.  Display description ............................................................................................................ 8 

4.4.  Initial screen ...................................................................................................................... 8 

5.

 

MAIN MENU ................................................................................................................. 9

 

5.1.  SET – Instrument settings ................................................................................................. 9 

5.1.1.

5.1.2.

5.1.3.

5.1.4.

5.1.5.

5.1.6.

 

General .................................................................................................................................... 9

 

 

Measurement units ................................................................................................................ 10

 

 

Date/Time ............................................................................................................................... 10

 

 

Remote unit/Solarim. ............................................................................................................. 11

 

 

Irradiance ............................................................................................................................... 12

 

 

DC Clamp (SOLAR I-Vw or SOLAR I-Ve) ............................................................................. 12

 

5.2.  EFF – SETTINGS FOR TESTING PV SYSTEMS (SOLAR I-Vw or SOLAR I-Ve) .......... 13 

5.2.1.

 

Settings for PV systems with single-MPPT inverter - single-phase AC output ..................... 13

 

5.2.1.1.

5.2.1.2.

5.2.2.

5.2.2.1.

  Instrument settings ........................................................................................................................... 13  

  PV plant parameters ........................................................................................................................ 14  

 

Settings for PV with single/multi MPPT inverter – single/three phase AC output .......................... 15

 

  Instrument settings ........................................................................................................................... 15  

5.2.2.2.

5.2.2.3.

  PV plant parameters ........................................................................................................................ 16  

  MPP300 status ................................................................................................................................ 17  

5.2.3.

 

Selection of the compensation relationship of temperature effects ....................................... 18

 

5.3.  DB – Module database .................................................................................................... 19 

5.3.1.

5.3.2.

 

How to define a new PV module ............................................................................................ 20

 

5.3.3.

 

 

How to modify a PV module ................................................................................................... 21

 

How to delete a PV module ................................................................................................... 21

 

6.

 

HOW TO OPERATE ................................................................................................... 22

 

6.1.  Testing PV systems (SOLAR I-Vw or SOLAR I-Ve) ........................................................ 22 

6.1.1.

6.1.2.

 

Testing of PV systems with single-MPPT inverter - single-phase AC output ........................ 23

 

 

Test PV systems with single/multi-MPPT inverter – single/three-phase AC output ................... 27

 

6.2.  I-V curve measurement ................................................................................................... 33 

6.2.1.

6.2.2.

 

I-V curve measurement by use of instrument ........................................................................ 33

 

 

I-V curve measurement by use of remote unit SOLAR-02 .................................................... 37

 

6.2.2.1.

6.2.2.2.

 

I-V curve test by remote unit SOLAR-02 in RF connection .............................................................. 37

 

6.2.3.

  I-V curve test by remote unit SOLAR-02 in synchro recording ......................................................... 41  

 

Meaning of measurement results .......................................................................................... 46

 

6.3.  Quick Check on PV modules and strings (IVCK) ............................................................ 47 

6.3.1.

6.3.2.

6.3.3.

 

General information ............................................................................................................... 47

 

6.3.4.

6.3.5.

 

Preliminary settings ................................................................................................................ 48

 

 

Fast check IVCK without irradiance measurement ................................................................ 49

 

 

Fast check IVCK with irradiance measurement ..................................................................... 51

 

 

Reset Media ........................................................................................................................... 53

 

6.4.  List of display messages ................................................................................................. 54 

7.

 

STORING DATA ......................................................................................................... 55

 

7.1.  Saving test results of PV checks (SOLAR I-Vw or SOLAR I-Ve) .................................... 55 

7.2.  Saving test results of I-V curve test ................................................................................. 55 

EN - 1

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

7.3.  Managing the results ....................................................................................................... 56 

7.3.1.

7.3.2.

 

Recall data of PV checks at display (SOLAR I-Vw or SOLAR I-Ve) ..................................... 56

 

Recall data of I-V curve tests at display ................................................................................. 57

 

7.3.2.1.

7.3.2.2.

7.3.2.3.

 

 

  View data – Numerical screens ........................................................................................................ 58  

View data – Graphic screens of I-V curve ........................................................................................ 59

View data – Graphic screens of power ............................................................................................. 60

7.3.3.

 

Delete data ............................................................................................................................. 61

 

 

 

 

8.

 

CONNECTING THE INSTRUMENT TO A PC ............................................................ 62

 

8.1.  Connecting by optical/USB cable C2006 ........................................................................ 62 

8.2.  Connecting by WiFi ......................................................................................................... 63 

9.

 

MAINTENANCE .......................................................................................................... 64

 

9.1.  General ............................................................................................................................ 64 

9.2.  Battery replacement ........................................................................................................ 64 

9.3.  Instrument cleaning ......................................................................................................... 64 

9.4.  End of life ........................................................................................................................ 64 

10.

 

TECHNICAL SPECIFICATIONS ................................................................................. 65

 

10.1.  Yield test technical feratures (SOLAR I-Vw, SOLAR I-Ve) .............................................. 65 

10.2.  I-V test technical features (I-V and IVCK) ....................................................................... 67 

10.3.  Safety specifications ........................................................................................................ 68 

10.3.1.

 

General .................................................................................................................................. 68

 

10.4.  General characteristics .................................................................................................... 69 

10.5.  Environment conditions ................................................................................................... 69 

10.6.  Accessories ..................................................................................................................... 69 

11.

 

APPENDIX ................................................................................................................. 70

 

11.1.  Testing photovoltaic systems (SOLAR I-Vw, SOLAR I-Ve) ............................................. 70 

11.2.  Notes on MPPT (Maximum Power Point Tracker) .......................................................... 71 

11.3.  Theoretical aspects of the I-V curve measurement ......................................................... 72 

11.3.1.

 

Typical errors on I-V curves and troubleshooting .................................................................. 73

 

12.

 

SERVICE .................................................................................................................... 75

 

12.1.  Warranty conditions ......................................................................................................... 75 

12.2.  Service ............................................................................................................................ 75 

EN - 2

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

1. SAFETY PRECAUTIONS AND PROCEDURES

The word “instrument” in this manual means generically both the models I-V400w, I-V500w,

SOLAR I-Vw or SOLAR I-Ve e SOLAR I-Ve except notation specifically indicated. This instrument has been designed in compliance with directives IEC/EN61010-1 regarding electronic measuring instruments. Before and while measuring, carefully follow the instructions below:

 Do not perform voltage or current measurements in humid environments

 Do not perform measurements near explosive gas or material and fuels or in dusty environments

 Avoid contact with the circuit tested if no measurement is being performed

 Avoid contact with exposed metal parts, test terminals not in use, circuits, etc.

 Do not perform any measurement if instrument anomalies are detected, such as deformations, breaks, leakage of substances, no display reading, etc.

 Only use original HT accessories

In this manual, following symbols are used:

CAUTION: Follow the instructions given in this manual; improper use may damage the instrument, its components or create dangerous situations for the operator

High voltage: risk of electrical shock

Double insulation

DC voltage or current

AC voltage or current

Ground reference

1.1. PRELIMINARY INSTRUCTIONS

 This instrument has been designed for use in the environmental conditions specified in

§ 10.5. Do not use in different environmental conditions.

 The instrument may be used for measuring of VOLTAGE and CURRENT in CAT II

1000V DC or CAT III 300V to ground, maximum voltage 1000V between inputs (I-

V400w and SOLAR I-Vw or SOLAR I-Ve) or 1500V (I-V500w and SOLAR I-Ve) Do not use on systems exceeding the limit values specified in § 10.1 and § 10.2

 We recommend to follow the ordinary safety rules aimed at: your protection against dangerous currents, the instrument’s protection against improper use.

 Only the accessories provided with the instrument guarantee compliance with safety standards. They must be in good conditions and must be replaced, if necessary, with identical models.

 Check that batteries are correctly inserted.

 Before connecting the test cables to the circuit being tested, check that the desired function has been selected.

EN - 3

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

1.2. DURING USE

We recommend to carefully read the following recommendations and instructions:

CAUTION

 Failure to comply with the CAUTIONs and/or instructions may damage the instrument and/or its components or cause dangers to the operator.

 The symbol “

” indicates the charge level. When there are five bars, it means that batteries are fully charged; a decrease in the number of bars down to “ ” indicates that the batteries are almost low. In this case, interrupt tests and replace the batteries according to the indications given in § 9.2. The instrument is capable of keeping data stored even

without batteries.

1.3. AFTER USE

When measuring operations are completed, turn off the instrument by pressing and holding the ON/OFF key for a few seconds. Should the instrument remain unused for a long time, remove batteries and follow the indications given in § 3.3.

1.4. OVERVOLTAGE CATEGORIES - DEFINITIONS

Standard IEC/EN61010-1 (Safety requirements for electrical equipment for measurement, control and laboratory use, Part 1: General requirements) defines what a measurement category (usually called “overvoltage category”) is. At § 6.7.4: Measuring circuits it quotes:

Circuits are divided into the following measurement categories:

Measurement Category IV is for measurements performed at the source of the lowvoltage installation.

Examples are electricity meters and measurements on primary overcurrent protection devices and ripple control units.

Measurement Category III is for measurements performed in the building installation.

Examples are measurements on distribution boards, circuit breakers, wiring, including cables, bus-bars, junction boxes, switches, socket-outlets in the fixed installation, and equipment for industrial use and some other equipment, for example, stationary motors with permanent connection to fixed installation.

Measurement Category II is for measurements performed on circuits directly connected to the low voltage installation.

Examples are measurements on household appliances, portable tools and similar equipment.

Measurement Category I is for measurements performed on circuits not directly connected to MAINS.

Examples are measurements on circuits not derived from MAINS, and specially protected (internal) MAINS-derived circuits. In the latter case, transient stresses are variable; for that reason, the norm requires that the transient withstand capability of the equipment is made known to the user.

EN - 4

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

2. GENERAL DESCRIPTION

2.1. INTRODUCTION

The instrument was designed to perform complete yield test on single-phase (and threephase if combined with optional accessory MPP300) PV installations with calculations of efficiencies (SOLAR I-Vw or SOLAR I-Ve) and to perform all I-V curve tests on single modules (panels) or complete strings of photovoltaic (PV) plants in order to verify the reference parameters given by the manufacturers.

2.2. INSTRUMENT FEATURES

The instrument can perform the following tests:

Check Single phase PV installations (EFF - SOLAR I-Vw and SOLAR I-Ve)

 DC voltage and current measurements (1000V for SOLAR I-Vw 1500V for SOLAR I-Ve)

 AC TRMS voltage and current measurements

 DC/AC power measurement

 Solar irradiation [W/m

2

] measured by use of reference cell connected to unit SOLAR-02

 Module and environ. temp. measurement by means of probe connect to SOLAR-02

 Use of compensation relationships on PDC measurements

 Immediate evaluation of result OK/NO of a test

 Checks with programmable IP from 5s to 60min

Testing single/three-phase PV systems (MPP – SOLAR I-Vw, SOLAR I-Ve + MPP300)

 Measurement of 3 DC voltages and currents

 Measurement of DC string power and total DC power

 Measurement of 3 AC TRMS voltages and currents

 Measurement of total AC power

 Measurement of irradiation [W/m

2

] by means of a reference cell connected to SOLAR-02

 Module and environ. temp. measurement by means of probe connect to SOLAR-02

 Application of compensation relationships to DC efficiency.

 Immediate evaluation of result OK/NO of a test

 Parameter recording of a PV system with 5s to 60min programmable IP

I-V Curve measurement

 Voltage, current, power of PV module/string 1000VDC, 15ADC (SOLAR I-Vw, I-V400w) module/string

 Activation of manual or automatic measurement

 PV module/string temperature measurement

 Irradiance measurement [W/m

2

] by using reference cell

 Numerical and graphical results of I-V curve with 4-wire method

 Comparison of results with standard conditions (STC) and OK/NO final response

 Internal customizable database for definition up to 30 PV modules

 Annual degradation evaluation of PV modules/strings/fields

 Internal memory for saving test and Optical/USB interface for PC connection

Quick Check (IVCK)

 Fast test of open voltage and short circuit current up to 1000V DC, 15A (SOLAR I-Vw,

I-V400w) and up to 1500VDC, 15A (SOLAR I-Ve, I-V500w)

 Activation of manual or automatic measurement

 Immediate evaluation (OK/NO) of test results

The instrument has an innovative electronic function selector to simply set operations with internal parameters, a backlit display, the contrast adjustment and a HELP key in order to give a valid help to the operator during the meter’s connection to the plants. An enable/disable Auto Power OFF feature is available after about 5 minutes of idleness.

EN - 5

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

3. PREPARATION FOR USE

3.1. INITIAL CHECKS

Before shipment, the instrument’s electronics and mechanics have been carefully checked.

All possible precautions have been taken to have the instrument delivered under optimal conditions. However, we recommend to rapidly check the instrument in order to detect possible damage occurred during transport. Should you detect anomalies, please immediately contact the dealer.

It is also recommended to check that the package contains all parts indicated in § 10.6. In case of discrepancies, please contact the dealer. Should it be necessary to return the instrument, please follow the instructions given in § 12.

3.2. INSTRUMENT POWER SUPPLY

The instrument is battery supplied. For battery type and life, see § 10.4.

The symbol “ ” indicates the charge level. When there are five bars next to the battery symbol, it means that batteries are fully charged; a decrease in the number of bars down to “ ” indicates that the batteries are almost low. In this case, interrupt tests and replace the batteries according to the indications given in § 9.2.

The instrument is capable of keeping data stored even without batteries.

The instrument is provided with advanced algorithms to maximize the batteries’ life.

During instrument operation, a further short pressing of the key turns on the display’s backlighting (if battery voltage level is high enough). In order to save battery efficiency, backlighting automatically turns off after approx. 30 seconds.

A frequent use of back lighting reduces the batteries’ life

3.3. STORAGE

In order to guarantee precise measurements, after a long period of the instrument’s storage under extreme environmental conditions, wait until it recovers its normal conditions

(see § 10.5).

EN - 6

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

4. DESCRIPTION OF PARTS

4.1. INSTRUMENT DESCRIPTION

CAPTION:

1. Inputs

2. Display

3. Connector for opto insulated cable

4. Arrows/ENTER key

5. GO/STOP key

6. SAVE key

7. ON/OFF key

8. HELP / key

9. ESC/MENU key

Fig. 1: Description of the front part of the instrument

CAPTION:

1. Input for irradiance probe (I-V) / DC transducer clamp (EFF – SOLAR I-

Vw, SOLAR I-Ve)

2. Input for auxiliary temperature probe

(I-V) / AC transducer clamp (EFF –

SOLAR I-Vw, SOLAR I-Ve) measurement (I-V) / voltage measurement (EFF – SOLAR I-Vw,

SOLAR I-Ve)

P1, P2 inputs for voltage measurement (I-V) / AC voltage

(EFF – SOLAR I-Vw, SOLAR I-Ve)

Fig. 2: Description of the upper part of the instrument

CAPTION:

1. Connector for opto insulated cable connection

Fig. 3: Description of the instrument’s side

EN - 7

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

4.2. KEYBOARD DESCRIPTION

The keyboard includes following keys:

ON/OFF

key to switch on/off the instrument

ESC/MENU

key to exit the selected menu without confirming and to activate menu management

    keys to move the cursor through the different screens in order to select the desired programming parameters

ENTER

key to confirm the modifications and the selected programming parameters and to select the function from the menu

GO/STOP

key to start measurements

SAVE

key to save the measured values

HELP

key (long pressure) to display an indicative outline of the connections between the instrument and the system being tested in the function set

key (short pressure) to turn on the display’s backlighting

4.3. DISPLAY DESCRIPTION

The display is a graphic module with a resolution of 128 x 128 dots. The display’s first line indicates the system date/hour and the battery charge indicator.

In the bottom part the functionality of ENTER key and the active mode is displayed

15/05/10 15:34:26

The symbol indicates the presence of an active radio connection with the selected remote unit (SOLAR-02 or

MPP300).

The flashing symbol indicates that the instrument is currently searching for a radio connection with the selected

Selection remote unit (SOLAR-02 or MPP300).

I – V

4.4. INITIAL SCREEN

When turning on the instrument, the instrument displays the initial screen for a few seconds. It displays the following:

 The instrument’s model

 The manufacturer’s name

 Internal presence of modules for RF (Radio Frequency) and WiFi connection

 The serial number (SN:) of the instrument

 The firmware version (FW:) in the instrument's memory

 The date of the last calibration (Calibration date:)

S O L A R

I - V w

H T

R F - W i S N : 1 5 3 4 5 6 7 8

FW: 7.07 H4

Calibration date:

09/02/2016

Then, the instrument switches to the last function selected.

EN - 8

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

5. MAIN MENU

Pressing the MENU/ESC key in any allowable condition of the instrument displays the main menu screen, in which the instrument may be set, the saved measures can be displayed and the desired measuring function may be set (item EFF only appears for instrument SOLAR I-Vw or SOLAR I-Ve).

Select by cursor the desired options and confirm by pressing

ENTER

15/05/10 15:34:26

I - V

I-V Test

E F F Y i e l d T e s t

S E T

S e t t i n g s

DB

Modules

MEM

Data Recall

PC

PC connection

E N T E R t o s e l e c t .

M E N U

5.1. SET – INSTRUMENT SETTINGS

Move the cursor to SET by means of the arrow keys (,) and confirm with ENTER. Subsequently, the displays shows

15/05/10 15:34:26

G e n e r a l the screen which provides access to the various instrument’s settings.

M e a s . U n i t

The settings will remain valid also after switching off the instrument

D a t e a n d T i m e

R e m o t e U n i t / S o l a r i m .

I r r a d i a n c e

D C C l a m p

E N T E R t o s e l e c t .

S E T

5.1.1. General

1. Move the cursor to “General” by means of the arrow keys

(,) and confirm with ENTER

2. The displays shows the screen which allows:

 Setting the instrument language

 Setting the enable/disable of auto power off

Adjusting the contrast of display

 Enabling the acoustic signal when pressing a key

 Setting the enable/disable of WiFi interface inside each section of main menu for using the instrument with the

HTAnalysis APP (in the PC section the WiFi interface is always on). With WiFi enabled the “ ” symbol is shown in the bottom right side of the display. The enable of

WiFi interface means a higher consumption of the batteries

3. By means of the arrow keys (,) and select the desired option by means of the arrow keys (,)

4. Confirm with SAVE and the “Data saved” message is displayed for a while. Press the ESC/MENU key to exit without saving and to go back to the previous screen

15/05/10 15:34:26

L a n g u a g e :  E n g l i s h 

A U T O P O W E R O F F : N O

C o n t r a s t : 1 0

K e y B e e p : N O

W i F i : N O

S A V E t o s t o r e d a t a

S E T

EN - 9

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

units

This § allows setting the default measurement units of some internal parameters included in the database (DB) for the management of PV modules (§ 5.3)

1. Move the cursor to “Meas. Unit” by means of the arrow keys (,) and confirm with ENTER.

2. The display shows the screen which allows selecting the measurement units of parameters shown by the meter.

3. Press ESC/MENU to exit without saving any setting.

15/05/10 15:34:26

P a r a m e t e r

E N T E R t o s e l e c t

M E N U

4. Move the cursor to “Parameter” by means of the arrow keys (,) and confirm with ENTER.

5. The display shows the screen which allows selecting the measurement units of typical parameters of the modules:

 Alpha  possible selection: “%/°C” and “mA/°C”

 Beta  possible selection: “%/°C” and “mV/°C”

 Gamma  possible selection: “%/°C” and “W/°C”

 Tolerance  possible selection: “%” and “W”

6. Set the desired units by means of the arrow keys (,).

7. Confirm with SAVE and the “Saved data” message is

15/05/10 15:34:26

A l p h a

B e t a

G a m m a

T o l e r a n c e

:  m A / ° C 

: m V / ° C

: W / ° C

: %

SAVE to store data

S E T

displayed for a while. Press ESC/MENU key to exit without saving and to go back to the previous screen.

5.1.3. Date/Time

1. Move the cursor to “Date/Time” by means of the arrow

15/05/10 15:34:26 keys (,) and confirm with ENTER

2. The display shows the screen which allows setting the system date/time both in the European (EU) or USA (US) format.

3. Set the values by means of the arrow keys (,).

4. Confirm with SAVE and the “Saved data” message is

Y e a r

M o n t h

D a y

H o u r

M i n u t e

F o r m a t

:  2 0 0 9 

: 0 6

: 1 5

: 0 9

: 5 3

: E U displayed for a while. Press ESC/MENU key to exit without saving and to go back to the previous screen.

SAVE to store data

S E T

EN - 10

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

unit/Solarim.

This section allows selecting the type of remote unit to be used (if available) and setting the values of typical parameters (Sensitivity and Alpha) of the reference irradiance cell supplied with the meter. The values of these parameters, which are printed on the

back label of the cell, depend on the type of PV modules on test.

1. Move the cursor to “Remote unit” by means of the arrow keys (,) and confirm with ENTER

2. The display shows the screen which allows:

 Select the type of remote unit to be used for testing PV systems (SOLAR I-Vw or SOLAR I-Ve): o

NO: Remote unit disabled o

SOLAR: Use of SOLAR-02 o

MPP300: Use of MPP300 (optional)

 Enable/disable the use of the remote unit SOLAR-02 for

I-V measurements (opt. for I-V400w and I-V500w). In case the use of the remote unit has not been enabled, it will be possible to set the sensitivity values (sens.) of the reference cell provided, expressed in “mV/kW*m-2”, and of the Alpha parameter.

3. Set the value by means of the arrow keys (,)

4. Confirm with SAVE and the “Saved data” message is displayed for a while. Press ESC/MENU key to exit without saving and to go back to the previous screen

15/05/10 15:34:26

R e m o t e U E F F

R e m o t e U I - V :

M P P 3 0 0

:  N O 

S e n s . :  3 1 . 0  m V / k W / m 2

A l p h a : 0 . 0 6 0 % / ° C

S A V E t o s t o r e d a t a

S E T

CAUTION

For EFF measurements (testing of PV systems – SOLAR I-Vw or SOLAR I-

Ve), disabling the remote unit entails:

The impossibility of carrying out Irradiation and Temperature

measurements by means of unit SOLAR-02

The impossibility of using the unit MPP300 (if available)

Consequently, it will be impossible to obtain a result for the test carried out.

EN - 11

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

5.1.5. Irradiance

1. Move the cursor to “Irradiance” by means of the arrow

15/05/10 15:34:26 keys (,) and confirm with ENTER.

2. The display shows the screen with the options: “ Irr min

IV

which allows to set the minimum threshold of measured irradiance expressed in W/m

2

, used by meter as

I r r m i n I V :  0  W / m 2

I r r m i n E F F :  6 0 0  W / m 2 reference during the I-V curve measurements and “Irr min

EFF

” (SOLAR I-Vw or SOLAR I-Ve which allows to set the minimum threshold of measured irradiance expressed in

W/m

2

, used by meter as reference during the check PV

SAVE to store data

S E T

efficiency measurements

3. Set the value by means of the arrow keys (,). The accuracy indicated in this manual is granted under condition indicated in § 10.1 and § 10.2. In I-V curve measurement the value is set within the 0

800 W/m

2

interval while 400

800 W/m

2

for the PV check operations (SOLAR I-Vw or SOLAR I-Ve)

4. Confirm with SAVE and the “Saved data” message is displayed for a while. Press ESC/MENU key to exit without saving and to go back to the previous screen.

CAUTION

The “0 W/m2” setting for parameter “Min Irr IV” allows carrying out I-V measurements without the following conditions being checked:

 Connection of reference cell to input IRR of the instrument

 Unsteady irradiation values

 Number of modules consistent with the measured open circuit voltage

5.1.6. DC Clamp (SOLAR I-Vw or SOLAR I-Ve)

This option allows setting a possible correction factor K for the DC clamp, in order to improve current measurement. If present, the correction factor is indicated on the rear label of the clamp itself, indicated as:

In case no label is present, set k = 1.000

K= X.xxx

1. Move the cursor to “DC Clamp” by means of the arrow keys (,) and confirm with ENTER

15/05/10 15:34:26

2. The item: “DC clamp k” is shown at display to set the corrective factor in a interval within 0.950 and 1.050. Set the value by means of the arrow keys (, )

3. Confirm with SAVE and the “Saved data” message is

D C c l a m p k :  1 . 0 0 0  displayed for a while. Press ESC/MENU key to exit without saving and to go back to the previous screen

SAVE to store data

S E T

EN - 12

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

5.2. EFF – SETTINGS FOR TESTING PV SYSTEMS (SOLAR I-VW OR SOLAR I-VE)

Further in this manual, the acronym MPPT (Multiple Power Point Tracker) shall indicate the characteristic of the DC/AC converter (inverter), capable of maximizing the DC power which can be taken from the photovoltaic field. See § 11.2 for further details.

5.2.1. Settings for PV systems with single-MPPT inverter - single-phase AC output

Check beforehand the settings made in MENUSETRemote Unit and check that you have selected “SOLAR” as setting for parameter “R. unit”.

1. Press MENU key, move the cursor to “EFF” by means of 15/05/10 15:34:26 the arrow keys (,) and confirm with ENTER. The screen with the values of electrical parameters relative to

P r p

I r r

PV generator is displayed

P n o m

T c

T e

P d c

V d c

I d c n d c

- - -

- - -

W / m 2

0 . 0 0 0 k W

- - -

° C

- - -

° C

0 . 0 k W

0 . 0 0 0

V

0 . 0 A

- - -

G O – S t a r t r e c

Select

E F F

2. Press ENTER key. The options Set PV plant and Set

Instrum.

are displayed

3. By means of the arrow keys (,) to select Set Instrum. and confirm with ENTER. The herewith screen is shown:

15/05/10 15:34:26

P R p

I r r

P n o m

T c

T e

P d c

V d c

I d c n d c

- - -

- - -

W / m 2

0 . 0 0 0 k W

- - -

° C

- - -

° C

0 . 0 k W

0 . 0 0 0

V

0 . 0 A

- - -

Set PV plant

S e t I n s t r u m .

Select

E F F

4. By means of the arrow keys (,) the herewith

15/05/10 15:34:26 parameters are set:

 IP (integration period) used by meter during yield test recording. The values I 5s, 10s, 30s, 60s, 120s, 300s,

600s, 900s, 1800s, 3600s

are selectable

I P :  5  s

F S D C c l a m p : 1 0 0 0 A

F S A C c l a m p : 1 0 0 0 A

 The full scale (FS) of DC clamp used on DC current measurement with selectable value within 1A

3000A

 The full scale (FS) of AC clamp used on AC current measurement with selectable value within 1A

3000A

5. Press the SAVE key to save the settings made; the message “Data saved” will be displayed for a few seconds. Press the ESC/MENU key to exit without saving and go back to the previous screen.

SAVE to store data

E F F

EN - 13

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

5.2.1.2. PV plant parameters

1. Press MENU key, move the cursor onto EFF by using the arrow keys (,) and confirm with ENTER. The display shows the values of the output electrical parameters of the photovoltaic generator (DC side).

15/05/10 15:34:26

P R p

I r r

P n o m

T c

T e

P d c

V d c

I d c n d c

- - -

- - -

W / m 2

0 . 0 0 0 k W

- - -

° C

- - -

° C

0 . 0 k W

0 . 0 0 0

V

0 . 0 A

- - -

G O – s t a r t r e c

Select

E F F

2. Press the ENTER key. The instrument shows the 15/05/10 15:34:26 following options: “Set PV plant“ and “Set Instrum“.

3. Use the arrow keys (,) to select “Set PV plant” and confirm with ENTER. The instrument shows the following screen:

P r p

I r r

P n o m

T c

T e

P d c

V d c

I d c n d c

- - -

W / m 2

- - -

W / m 2

0 . 0 0 0 k W

- - -

° C

- - -

° C

0 . 0 k W

0 . 0 0 0

V

0 . 0 A

- - -

Set PV plant

S e t I n s t r u m e n t

4. By means arrow keys ( , ) the herewith parameters

15/05/10 15:34:26 are set:

Pmax  maximum nominal power of the PV installation expressed in kW

Gamma  coefficient of variation of power with the temperature, standard parameter of PV module

(range: -0.3

-0.5%/°C typical)

:  3 . 5 0 0  k W

G a m m a

N o c t

: 0 . 4 5 % / ° C

: 4 5 ° C

T e :

4 5 ° C

T . E n v

Noct  nominal working temperature of a PV cell, standard parameter of PV module (range: 42

 48°C typical)

Select

E F F

SAVE to store data

E F F

Te, Tc  set of default values of environmental temperature and PV module temperature. These values are considered by the meter only without the auxiliary probe connected to emote unit SOLAR-02

Corr. Type  set the corrective term Ptpv for DC efficiency calculation and for maximum DC efficiency visualization (see § 5.2.3)

EN - 14

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

5.2.2. Settings for PV with single/multi MPPT inverter – single/three phase AC output

See § 11.2 for further details about the meaning of MPPT. This mode requires unsing the remote unit MPP300 (optional). Check beforehand the settings made in

MENU

SETRemote Unit and check that you have selected “MPP300” as setting for parameter “R. unit”.

1. Press the MENU key, position the cursor onto EFF by

15/05/10 15:34:26 using the arrow keys (,) and confirm with ENTER.

The display shows the screen here to the side, which contains the global parameters of the system.

P R p

I r r

P n o m

T c

T e

P d c

P a c n d c n a c

- - -

- - -

W / m 2

1 5 0 . 0 k W

- - -

° C

- - -

° C

- - k W

- - k W

- - -

- - -

G O - s t a r t R e c

Select

M P P

2. Press the ENTER key. The instrument shows the 15/05/10 15:34:26 following options: MPP300 status, System Par. and

Instrument settings

3. Use the arrow keys (,) to select “Instrument

settings

the following screen:

.

” and confirm with ENTER. The instrument shows

P R p

I r r

P n o m

T c

T e

P d c

P a c n d c n a c

- - -

- - -

W / m 2

1 5 0 . 0 k W

- - -

° C

- - -

- - -

- - -

- - -

MPP300 Status

- - -

° C k W k W

Set PV plant

S e t I n s t r u m .

Select

M P P

4. By using the arrow keys ( , ) it is possible to set:

15/05/10 15:34:26

 the integration period (IP) which can be used by the instrument when testing the parameters of a PV

 system. The following values can be selected: 5s, 10s,

30s, 60s, 120s, 300s, 600s, 900s, 1800s, 3600s

current with value selectable between 1A

The FS of the DC clamp used for measuring DC

3000A

 The FS of the AC clamp used for measuring AC current with value selectable between 1A

3000A

I P :  5  s

F S D C c l a m p : 1 0 0 0 A

F S A C c l a m p : 1 0 0 0 A

C l a m p T y p e : S T D

D c i n p u t s

A c s y t e m

1 + 2 + 3

3 p h a s e

The type of AC clamp used: STD (standard) or FLEX

(flexible clamp)

S A V E t o s t o r e d a t a

 The number of DC inputs to be used for measuring:

1

, 1+2, 1+2+3

M P P

 The type of AC electrical system: SINGLE, 4 wires

5. Press the SAVE key to save the settings made; the message “Data saved” will be displayed for a few seconds. Press the ESC/MENU key to exit without saving and go back to the previous screen.

EN - 15

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

5.2.2.2. PV plant parameters

1. Press MENU key, position the cursor onto EFF by using

15/05/10 15:34:26 the arrow keys (,) and confirm with ENTER. The display shows the screen here to the side, which contains

P R p

I r r the global parameters of the system.

P n o m

T c

T e

P d c

P a c n d c n a c

- - -

- - -

W / m 2

1 5 0 . 0 k W

- - -

° C

- - -

° C

- - k W

- - k W

- - -

- - -

G O – s t a r t r e c .

Select

M P P

2. Press the ENTER key. The instrument shows the 15/05/10 15:34:26 following options: MPP300 status, Set PV plant. and Set

Instrum.

3. Use the arrow keys (,) to select “Set PV plant” and confirm with ENTER. The instrument shows the following screen:

P R p

I r r

P n o m

T c

T e

P d c

V d c

I d c n d c

- - -

- - -

W / m 2

0 . 0 0 0 k W

- - -

° C

- - -

° C

0 . 0 k W

0 . 0 0 0

V

0 . 0 A

- - -

M P P 3 0 0 s t a t u s

Set PV plant

S e t i n s t r u m .

Select

M P P

4. By using the arrow keys ( , ) it is possible to set:

Range  coefficient of power variation with temperature, characteristic parameter of PV modules

(typically in range: -0.3

-0.5%/C)

15/05/10 15:34:26

Pmax  maximum rated power of PV installation expressed in kW

P m a x

G a m m a

N o c t

:  3 . 5 0 0  k W

: 0 . 4 5 % / ° C

: 4 5 ° C

T e :

4 5 ° C

C o r r . T y p e . :

4 0 ° C

T c :

T . E n v

Noct  rated operating temperature of the cell, characteristic parameter of PV modules (typically in range: 42

 48°C)

S A V E t o s t o r e d a t a

Te, Tc  setting of default values of environmental and PV module temperatures. These values are taken

M P P

into consideration by the instrument only when probe is not connected to unit SOLAR-02

Corr. Type  Setting of the compensation relationship on the calculation of Pdc power and the maximization of DC performance (see § 5.2.3)

EN - 16

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

status

If SOLAR I-Vw or SOLAR I-Ve is near MPP300, the general parameters of MPP300 may be displayed.

1. Position the cursor onto EFF by using the arrow keys

15/05/10 15:34:26

(,) and confirm with ENTER. The display shows the screen here to the side, which contains the global parameters of the system.

P R p

I r r

P n o m

T c

T e

P d c

P a c n d c n a c

- - -

- - -

W / m 2

1 5 0 . 0 k W

- - -

° C

- - -

° C

- - k W

- - k W

- - -

- - -

Select

G O – s t a r t r e c .

Select

M P P

2. Press the ENTER key. The instrument shows the 15/05/10 15:34:26 following options: MPP300 status, Set PV plant and Set

P o w e r s u p p l y P . S u p .

Instrum.

3. Use the arrow keys (,) to select “MPP300 status” and confirm with ENTER. The instrument shows the screen here to the side, which indicates the main general parameters of the instrument.

C h a r g e 9 9 %

S O L A R - 0 2

S I d e t e c t e d

V e r s i o n 1 . 0 1

S N 1 1 0 1 0 0 3 0

MPP300 status

Set PV plant

S e t i n s t r u m .

M E N U

EN - 17

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

5.2.3. Selection of the compensation relationship of temperature effects

This option allows selecting the relationship to be used to correct the measurements performed according to the modules’ temperature. The following correction modes are available:

- T.mod.:

Correction factor Rfv2 related to PV module Temp. (Italian guideline CEI-82-25)

- T.env:

- ndc:

Correction factor Rfv2 related to environment Temp. (Italian guideline CEI-82-25)

PRp (Performance ratio for active power) corrected by PV module Temp.

CAUTION

If it’s performed a test according to Italian guideline it is recommended to select

“T.env.” correction

Corr.

Type

Temperature (Tcel) PRp calculation Ref.

T.mod.

Tcel

Tmodule_Me as

T.amb. Tcel

 Tamb

NOCT

20

Irr

800



R

fv2



1

1 (Tcel 40)

(if

100

(if

Tcel

Tcel

40

C)

40

C)

-

CEI

82-25

PRp

P ca

Rfv

2

G p

G

STC

P n

dc

Tcel

Tmodule_Me as

PRp

G

STC

G p

 

1

100

T cel

25

P ca

P n

- - - where:

G p

G

STC

Irradiance on PV module surface

Standard Irradiance = 1000

2

W/m

2

W/m

Nominal Power = sum of all power module (Pmax ) included in the part of PV plant under test

P n

AC Active Power measured

 

P ca

Rfv

2

NOCT

Thermal Coefficient factor

Absolute value of Pmax thermal coefficient

Normal Operating Cell Temperature (@ 800W/m

2

, 20°C, AM=1.5, vel. Aria =1m/s).

%/

C

%/

C

For further details see § 11.1

EN - 18

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

5.3. DB – MODULE DATABASE

The meter allows defining up to 30 different PV modules, further to a DEFAULT situation

(not editable and not erasable) which can be used as reference case when no piece of information about the module under test is available.

The parameters which can be set, with reference to 1 module, are described below in

Table 1 together with their range, resolution and validity condition.

Symbol Description

Nms Number of modules for string

1

 50

Pmax Maximum nominal power of module

50

 4800W

Vmpp voltage

15.00

 99.99V

100.0

 320.0V

Voltage on point of maximum power

15.00

 99.99V

100.0

 320.0V

Isc Short circuit current

0.5

 15.00A

1

1W

P

max

V mpp

I mpp

P

max

0 .

01

0.01V

0.1V

0.01V

0.1V

0.01A

Voc

Voc

Isc

 Vmpp

 Vmpp

 Impp

Impp Current on point of maximum power

Toll -

Toll +

Alpha

Beta

Gamma

Negative tolerance for Pmax provided by the module manufacturer

Positive tolerance for Pmax provided by the module manufacturer

Isc temperature coefficient

Voc temperature coefficient

Pmax temperature coefficient

0.5

 15.00A

0%

 25.0%

0.01A

0.1%

Isc

 Impp

100*Tol

-

/Pnom< 25

0

 99W

0

 25%

1

0.1%

100*Tol

+

/Pnom< 25

0

 99W

1

-0.100

0.100%/°C 0.001%/°C

-15.00

 15.00mA/°C 0.01mA/°C

-0.99

 -0.01%/°C

0.01%/°C

100*Alpha / Isc

 0.1

100*Beta/Voc

 0.999

-0.999

 -0.001V/°C

0.001V/°C

-0.99

 -0.01%/°C

0.01%/°C

NOCT Nominal working temperature of cell

Tech.

Degr

0

 100°C

1°C

Effects due to PV technology

STD (standard)

CAP(capacitive eff.)

HIT (hybrid techn.)

Percentage of annual performance degradation

0.0

 25.0%/yr

0.1%/yr

Table 1: Typical parameters of PV modules

CAUTION

 The “Tech” item is referred to the choose of the technology of the module on test. Select the “STD” option for test on “STANDARD” PV modules,

“CAP” option for test on higher capacitive effects PV modules or HIT

(modules with HIT/HIP hybrid technology

 A wrong choose of the type of technology can lead to a negative outcome of the final test

 The “Degr” item is referred to the power performance degradation of a PV module/strings/field expressed in annual percentage (maximum limit set =

25%)

EN - 19

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

5.3.1. How to define a new PV module

1. Move the cursor to “DB” by means of the arrow keys

(,) and confirm with ENTER. The display shows the screen with:

 The type of selected module

 The parameter associated to the module (see Table 1)

15/05/10 15:34:26

T y p e :  D E F A U L T 

P m a x = 1 8 5

V o c = 4 4 . 5 V

V m p p = 3 7 . 5

2. Select the “DEFAULT” module by means of the arrow keys (,) and confirm with ENTER.

I m p p = 4 . 9 5

T o l l - =

Select

D B

3. Press ENTER, select the “New” command and confirm again with ENTER. Use the arrow keys (,) to scroll all internal parameters.

15/05/10 15:34:26

T y p e :  D E F A U L T 

P m a x = 1 8 5

V o c = 4 4 . 5 V

V m p p = 3 7 . 5

I m p p = 4 . 9 5

T o l l - =

N e w

Select

D B

4. By using the internal virtual keyboard it is possible to define the name of the module (ex: SUNPOWER 210) by

15/05/10 15:34:26

T y p e :

 means the arrow keys (,,,). Press ENTER to digit the characters of the desired name.

5. Press the SAVE key to save the inserted name of the module as defined or ESC/MENU key to exit without saving.

P m a x = 1 8 5

V o c = 4 4 . 5

K E Y B O A R D

V

S U N P O W E R 2 1 0

A B C D E F G H I J K L M N O P

Q R S T U V W X Y Z - + 0 1 2 3

4 5 6 7 8 9 S P A C E D E L

6. Digit the value of each parameter of the defined module

(see Table 1) based on the manufacturer’s data sheet.

Move the cursor to the row of the parameter by means of the arrow keys (,) and set the value by means of the arrow keys (,). Press and hold (,) for a quick

15/05/10 15:34:26

T y p e : S U N P O W E R 2 1 0

P m a x =

0  W

V o c = 0 . 0 V

V m p p = V

A setting of values.

7. Confirm with SAVE and the “Saved data” message is displayed for a while. Press ESC/MENU key to exit without saving and to go back to the previous screen.

I m p p = 0 . 0 0

T o l l - =

D B

CAUTION

 If the value of any parameter is unknown press and hold the HELP key for some seconds to set the default values

 After pressing the SAVE key, the meter checks all the conditions shown in

Table 1 and, if one or more of these conditions do not occur, some error messages are shown by the display (§ 6.5) and the meter does not save the configuration before any error is solved. Solve the error condition before saving.

EN - 20

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

5.3.2. How to modify a PV module

1. Select the PV module to be modified from the internal database by means of arrow keys (,).

2. Press the ENTER key and select the “Modify” command by means the arrow key ().

3. Confirm the selection with ENTER.

15/05/10 15:34:26

T y p e : 

S U N P O W E R 2 1 0 

P m a x = 2 1 0 W

V o c = 4 7 . 7 0 V

V

A

N e w

M o d i f y

D e l e t e

D e l . A l l

S e l e c t

D B

4. By using the internal virtual keyboard it is possible to define a different name of the module by means of arrow keys (,,,). Press ENTER to digit any character of

15/05/10 15:34:26

T y p e : 

S U N P O W E R 2 1 0 

P m a x = 1 8 5 the desired name.

5. Press the SAVE key to save the new name of the module as defined or to access the new setting of parameters.

V o c = 4 4 . 5

K E Y B O A R D

V

S U N P O W E R 2 1 0

A B C D E F G H I J K L M N O P

Q R S T U V W X Y Z - + 0 1 2 3

4 5 6 7 8 9 S P A C E D E L

SAVE/ESC

6. Select the desired parameters to be modified by means of arrow keys (,) and change values by means of arrow displayed for a while. Press ESC/MENU key to exit without saving and to go back to the previous screen.

15/05/10 15:34:26

T y p e : S U N P O W E R 2 1 0

 keys (,). Press and hold the (,) for a quick setting of values. If the value of any parameter is unknown, press and hold the HELP key for some seconds to set the default values.

7. Confirm with SAVE and the “Saved data” message is

P m a x =

2 1 0

W

V o c = 4 7 . 7 0

V m p p = 4 0 . 0 0

V

V

I s c = 5 . 7 5

A

T o l l - =

D B

5.3.3. How to delete a PV module

1. Select the PV module to be deleted from the internal database by means of arrow keys (,).

15/05/10 15:34:26

T y p e : 

S U N P O W E R 2 1 0 

2. Press the ENTER key and select “Delete” command by means of arrow key () to delete the selected module.

P m a x = 2 1 0

V o c = 4 7 . 7 0

W

V

3. Press the ENTER key and select “Del. All” command by

V

A means of arrow key () to delete all modules in the

N e w database (except for “DEFAULT”).

M o d i f y

4. Confirm the selection with ENTER or press ESC/MENU to exit

D e l e t e

D e l . A l l

S e l e c t

D B

CAUTION

It is not possible to modify or delete the “DEFAULT” PV module which is the standard reference factory module.

EN - 21

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

6. HOW TO OPERATE

6.1. TESTING PV SYSTEMS (SOLAR I-VW OR SOLAR I-VE)

For the sake of simplicity, further in this manual, the word “string” will be used, although often the term “photovoltaic field” would be more correct. From the point of view of the instrument, the management of a single string or of more parallel strings (photovoltaic field) is identical. Furthermore, the acronym MPPT (Multiple Power Point Tracker) shall indicate the characteristic of the DC/AC converter (inverter), capable of maximizing the DC power which can be taken from the photovoltaic field (see the § 11.2 for further details), the acronym PRp shall indicated the Performance ratio (evaluated on active powers).

CAUTION

For the evaluation of the PRP only, the measurement of the DC (voltage

and current) is not strictly necessary

Conversely it is necessary if you want to evaluate the performance of the

photovoltaic section (ndc) and DC / AC conversion (nac)

Simbol Description

PRp Performance Ratio (calculated through Active power)

Irr Irradiance

Pnom Total Nominal power of the PV section under test.

Tc Module

Te Environment

Pdc, Pdcx Total DC power measured, DC power of PV field x (x=1,2,3)

Pac, Pacx Total AC power measured, AC power of phase x (x=1,2,3,) ndc DC nac AC efficiency

Vdc, Vdcx DC Voltage, DC voltage of PV field x (x=1,2,3)

Idc, Idcx DC current, DC current of PV field x (x=1,2,3)

Vac, Vacx AC Voltage, AC voltage of PV field x (x=1,2,3)

Iac, Iacx AC current, AC current of PV field x (x=1,2,3)

Symbols description

Unit

W/m

2 kW

°C

°C kW

A

V

A kW

V

EN - 22

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

6.1.1. Testing of PV systems with single-MPPT inverter - single-phase AC output

The SOLAR I-Vw or SOLAR I-Ve meter (master) can perform check tests of efficiencies on single phase PV installations by using the irradiance and temperature probes which are connected to the remote unit SOLAR-02. This remote unit communicates with the master unit (for the synchronization and download data operations) through a wireless radiofrequency (RF) which is active with a maximum distance of about 1m between units.

CAUTION

 The maximum voltage between C1, and C2 inputs is 1000VDC (for SOLAR

I-Vw) or 1500VDC (for SOLAR I-Ve) and between P1 and P2 inputs is 265V

AC rms. Do not measure voltages exceeding the limits prescribed by this manual. Should you exceed the voltage limits you could damage the instrument and/or its components or endanger your safety

 In order to guarantee the operator’s safety, while making the connections, disable the system being measured by means of the switches/breakers upstream and downstream of the DC/AC converter (inverter).

Fig. 4: Connection of meter for check on single phase PV installation

1. Check and, if necessary, set the sensitivity of the reference cell on SOLAR-02 consistently with the type of PV modules which will be measured (please refer to the User Manual of

SOLAR-02)

2. We recommend making a preliminary evaluation of the value of irradiation on the surface of the PV modules being tested by means of unit SOLAR-02 (operating independently) and the reference cell

3. Switch on SOLAR I-Vw or SOLAR I-Ve. Check and if necessary modify the basic settings of meter relative to the minimum irradiance threshold, the FS of DC and AC transducer clamps, the IP and the parameters of the PV installation on test (see § 5.1.1,

§5.1.5 and §5.2)

EN - 23

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

4. In order to guarantee the operator’s safety, disable the system being measured by means of the switches/breakers upstream and downstream of the DC/AC converter (inverter)

5. In case of inverters provided with more than one power tracker (MPPT), only leave the

string corresponding to the first MPPT connected

, as shown in Fig. 4. Then, it will be necessary to repeat the operations described below by only leaving the string corresponding to the second MPPT connected, then to the third, etc.

6. Bring SOLAR I-Vw or SOLAR I-Ve and SOLAR-02 nearer (maximum distance of 1m between them). All instruments must be switched on (see the User Manual of SOLAR-2 for further details)

7. On SOLAR I-Vw or SOLAR I-Ve, press the MENU key, select the function EFF and press

ENTER

; wait for the two units to start communicating with each other. This condition is highlighted by the contemporary presence of the following indicators:

 Symbol steady (not flashing) on the display of SOLAR I-Vw or SOLAR I-Ve

 Symbol steady (not flashing) on the display of SOLAR-02

8.

Connect the C2 and C1 inputs respectively to the positive and negative polarity of the output string. Connect the P1 and P2 inputs to the phase and neutral conductors respecting the colors as shown in Fig. 4

9. Connect the output connector of the DC clamp to the IDC1 input.

CAUTION

BEFORE CONNECTING THE DC CLAMPS TO THE CONDUCTORS

Switch on the clamp, check the LED indicating the status of the clamp’s internal batteries (if present), select the correct range, press the ZERO key on the DC clamp and check on the display of SOLAR I-Vw or SOLAR I-Ve, the actual zeroing of the corresponding Idc value (values up to 0.02A are acceptable).

10. Connect the DC current clamp to the positive string output conductor by respecting

the direction of the arrow

on the clamp itself as indicated in Fig. 4. Position the DC clamp in point so far from the inverter and avoid that the jaws stay close to the negative conductor

11. Connect the AC current clamp to the Phase L1 conductor by respecting the direction

of the arrow

on the clamp itself as indicated in Fig. 4. Position the AC clamp as far as possible from the inverter and avoid that the jaws stay close to the neutral conductor.

Connect the output of the clamp to the IAC input of the instrument

12. Power on the system on test

EN - 24

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

13. The display shows the first screen containing the values of the electrical parameters on the DC side of the inverter.

15/05/10 15:34:26

P R p

I r r

- - -

- - -

P n o m 3 . 5 0 0

W / m 2

T c 4 5

T e 3 0

I d c 8 . 0 1 n d c

- - -

° C

P d c 3 . 1 2 5

V d c 3 8 9

A

G O – s t a r t r e c .

Select

E F F

14. By means of arrow key  to access to the second screen with the values of electrical parameters of the AC side of means the search by the meter of RF connection with the remote unit SOLAR-02

15/05/10 15:34:26

 k W inverter. Before to start the recording:

Verify the symbol “ ” blinking at display which

Verify that the Pac active power should be a positive

I d c 8 . 0 1 n d c - - -

V

° C

P a c 3 . 0 1 2

V

A value. In the opposite case open the AC clamp and rotate of 180 degree on the phase conductor

Verify that the AC efficiency

ac = Pac / Pdc should be a consistent value (e.g.: a situation of

ac > 1 is not physically possible)

Select

G O – s t a r t r e c

E F F

15. With remote unit always close to the main unit press

15/05/10 15:34:26

GO/STOP

key to start the recording. The “Rec. Start

waiting…

” message is shown at display of main unit and the

HOLD” message is shown at display of SOLAR-02 more than the indication of residual time for “00” instance

P d c 3 . 1 2 5

V d c 3 8 9

I d c 8 . 0 1

- - - ° C n d c

P a c 3 . 0 1 2

V

A

R e c . S t a r t w a i t i n g …

Select

E F F

16. When the “00” instant after the press of GO/STOP key is

15/05/10 15:35:00 reached, the recording starts and the units are correctly

 k W synchronized. In these conditions the message “Rec

running…

” is displayed on the main unit and the

Recording…” message is displayed on the SOLAR-02

I d c 8 . 0 1 n d c - - -

V

° C

P a c 3 . 0 1 2

V

A

R e c . R u n n i n g …

Select

E F F

EN - 25

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

15/05/10 15:35:00 recording status by pressing the MENU key. The following information will be shown:

 starting date and time of recording

 the value set for the integration period

 the number of periods elapsed from the beginning of the recording

 the remaining memory capacity for recording

S t a r t

1 4 / 0 2 / 0 0 1 7 : 1 8 : 0 0

P e r i o d : 5 s

I P N u m b e r

R e c . T i m e

6 1

0 d 1 h

R e c . r u n n i n g

Press the ESC key to exit the screen

Select

M P P

18. Now it is possible to bring the unit SOLAR-02 near the PV strings to measure irradiation and temperature by means of the relevant probes. When the distance between unit SOLAR-02 and SOLAR I-Vw or SOLAR I-Ve does not allow the RF connection, on the display of

SOLAR-02, the symbol “ ” flashes for approx. 30s and then disappears, while SOLAR I-

Vw or SOLAR I-Ve continues searching for the connection for approx. 1 minute.

19. Position the reference cell onto the surface of the PV modules. Please refer to the relevant

User Manual for a correct assembly.

20. Put the temperature sensor in contact with the rear side of the module and fasten it with some tape; prevent touching it with your fingers (as this could alter the measure).

21. Wait some seconds in order to permit a stable measure by probes and then connect the irradiation and temperature probes respectively to the inputs PYRA/CELL and TEMP of the SOLAR-02 unit.

22. Wait for “READY” message displayed on SOLAR-02. This event indicates that the instrument has detected some data with solar irradiation > minimum limit threshold (see

§ 5.1.5)

23. Wait at least 1 minute in order to recording more valid samples

24. Disconnect the irradiation and temperature probes from unit SOLAR-02 and bring the unit near SOLAR I-Vw or SOLAR I-Ve (max distance 1m).

25. The main unit SOLAR I-Vw or SOLAR I-Ve must be in EFF mode. If there is no flashing symbol “ ”, press key  to activate the RF connection search again.

26. Press the  key on SOLAR-02 to active the RF connection. On the main unit the message

“ RF connection active” is displayed

27. To stop testing, press the GO/STOP key on instrument

SOLAR I-Vw or SOLAR I-Ve and confirm with ENTER that you want to stop recording.

28. The display of SOLAR I-Vw or SOLAR I-Ve will show the message “DOWNLOAD” to indicate that the data will be

15/05/10 15:35:00

9 7 1

4 5 . 1

3 0 . 5

° C

° C

0 . 9 5

W / m 2

I r r

P n o m 3 . 5 0 0

T c

T e

P d c 3 . 1 2 5

P a c 2 . 9 6 0 n a c k W n d c 0 . 8 6 transferred to the main unit during its various phases.

29. After the automatic data transfer phase, the instrument:

Do not show any results if do not exist on the PV installation a “stable irradiance” condition more than the minimum irradiance threshold.

Select

A n a l y s i s R e s u l t

E F F

 Display the best performance values if during the recording, the Irradiance values reached the “stable” condition and its values were higher than the minimum irradiance threshold.

30. Press SAVE to save the results (see § 7.1) or ESC to exit the screen of the results and go back to the initial screen

EN - 26

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

6.1.2. Test PV systems with single/multi-MPPT inverter – single/three-phase AC output

The instrument SOLAR I-Vw or SOLAR I-Ve, used together with remote units SOLAR-02 and MPP300 (optional), allows testing PV systems characterized by 1 or more strings (with the same direction and inclination) and single-phase or three-phase output.

The remote unit MPP300 is capable of communicating with SOLAR I-Vw or SOLAR I-Ve

(to manage synchronization and data download) and with the remote unit SOLAR-02 (for recording irradiation and temperature values) via a wireless radiofrequency (RF) connection, which is active up to a maximum distance of 1m between the units.

Fig. 5: Connection of MPP300 for testing a single-phase PV system

EN - 27

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

Fig. 6: Connection of MPP300 for testing a three-phase PV system

CAUTION

 When SOLAR I-Vw or SOLAR I-Ve is set in order to use MPP300 as a remote unit, ALL connections relevant to electrical quantities (voltages and currents) must be carried out on unit MPP300. SOLAR I-Vw or SOLAR I-

Ve must have no voltage nor current connected to its inputs.

 The maximum voltage for the inputs of MPP300 is 1000VDC between inputs VDC1, VDC2, VDC3 and 600VAC between inputs VAC1, VAC2,

VAC3. Do not measure voltages exceeding the limits given in this manual.

Exceeding these limits could result in electrical shocks to the user and damage to the instrument.

 In order to guarantee the operator’s safety, while making the connections, disable the system being measured by means of the switches/breakers upstream and downstream of the DC/AC converter (inverter).

1. Check and, if necessary, set the sensitivity of the reference cell on SOLAR-02 consistently with the type of PV modules which will be measured (please refer to the User Manual of

SOLAR-02).

2. We recommend making a preliminary evaluation of the value of irradiation on the surface of the PV modules being tested by means of unit SOLAR-02 (operating independently) and the reference cell

3. Switch on SOLAR I-Vw or SOLAR I-Ve, check and, if necessary, change the settings relevant to the type of remote unit, to the minimum irradiation threshold, to the full scale of the AC and DC clamps, to the integration period and to the parameters of the system being measured (see § 5.1.4, § 5.1.5, § 5.1.6, § 5.2.2).

4. In order to guarantee the operator’s safety, disable the system being measured by means of the switches/breakers upstream and downstream of the DC/AC converter (inverter).

5. Bring SOLAR I-Vw or SOLAR I-Ve, SOLAR-02 and unit MPP300 nearer (maximum distance of 1m between them). All instruments must be switched on (see the User

Manuals of SOLAR-2 and MPP300 for further details).

6. On SOLAR I-Vw or SOLAR I-Ve, press the MENU key, select the function EFF and press

ENTER

; wait for the three units to start communicating with each other. This condition is highlighted by the contemporary presence of the following indicators:

 Symbol steady (not flashing) on the display of SOLAR I-Vw or SOLAR I-Ve

 Symbol steady (not flashing) on the display of SOLAR-02

 MASTER and REMOTE LEDs flashing green on unit MPP300

7. Connect the VDC1(+) and VDC1(-) inputs of unit MPP300 to the output terminals of the string, respecting the polarities and the colours indicated in Fig. 5 or Fig. 6

8. Repeat the operation described in the step above for other possible DC power trackers to be monitored by using the VDC2 and VDC3 inputs according to the number of DC inputs set (see § 5.2.1.1).

EN - 28

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

9. Connect the output connector of the DC clamp to the IDC1 input of unit MPP300.

CAUTION

BEFORE CONNECTING THE DC CLAMPS TO THE CONDUCTORS

Switch on the clamp, check the LED indicating the status of the clamp’s internal batteries (if present), select the correct range, press the ZERO key on the DC clamp and check on the display of SOLAR I-Vw or SOLAR I-Ve the actual zeroing of the corresponding Idc value (values up to 0.02A are acceptable).

10. Insert the DC current clamp onto the positive output conductor of the string, respecting the

direction of the arrow

found on the clamp itself as indicated in Fig. 5 or Fig. 6. Position the clamp toroid as far as possible from the inverter and from the negative output conductor of the string itself.

11. Repeat the operations described in the two steps above for other possible DC power trackers to be monitored by using the IDC2 and IDC3 inputs according to the number of DC inputs set (see § 5.2.1.1).

12. Connect the VAC1 and N inputs of unit MPP300 to the Phase and Neutral conductors respectively, respecting the polarities and the colors indicated in Fig. 5 or Fig. 6. In case of three-phase systems in which no Neutral conductor is available, connect input N to earth.

13. In case of inverter with three-phase output (see settings in § 5.2.1.1), repeat the operation described in the step above for the remaining phases by using the VAC2 and

VAC3

inputs of MPP300.

14. Connect the AC clamp to the Phase L1 conductor, respecting the direction of the arrow found on the clamp itself as indicated in Fig. 5 or Fig. 6. Position the clamp toroid as far as possible from the inverter and from the Neutral conductor. Connect the clamp output to the

IAC1

input of MPP300.

15. In case of inverter with three-phase output (see settings in § 5.2.1.1), repeat the operation described in the step above for the remaining phases by using the IAC2 and IAC3 inputs of

MPP300.

16. Restore the operation of the electrical system being measured.

17. The display of SOLAR I-Vw or SOLAR I-Ve will show the values of the general electrical parameters of the system being measured. In particular, in this screen:

 Pdc = General DC power (sum of the string powers)

 Pac = AC power (if single-phase) or sum of the ac powers (if three-phase)

We recommend checking that the values of the electrical

15/05/10 15:34:26

P R p

I r r

- - -

- - -

W / m 2

k W

T c

T e k W

P a c 2 . 9 6 0 n d c n a c

- - -

- - -

° C

° C

- - -

0 . 9 5 k W

G O – s t a r t r e c parameters (Pnom, Pdc, Pac) and of the ac performance

(

ac) are consistent with the system being measured (e.g.:

ac > 1 is not physically acceptable)

Select

M P P

EN - 29

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

18. On SOLAR I-Vw or SOLAR I-Ve, press key () to access the second screen which contains the values of the output DC parameters of the strings according to the number of DC inputs set (see § 5.2.1.1). In particular, in this screen:

Vdcx = DC voltage of string x

Idcx = DC current of string x

Pdx = DC power of string x.

15/05/10 15:34:26

V d c 1 4 6 0 . 1 k W

V d c 2 4 6 1 . 4

V d c 3 4 6 2 . 5

V

A

I d c 1 2 . 2 5

I d c 2 2 . 3 1 A

I d c 3 2 . 2 1

P d c 1 1 . 0 3 5

P d c 2 1 . 0 6 6

P d c 3 1 . 0 2 4 k W k W

G O – s t a r t r e c

We recommend checking that the values of the electrical

Select

M P P

parameters (Vdc, Idc, Pdc) are consistent with the system being measured.

19. On SOLAR I-Vw or SOLAR I-Ve, press key () to access the third screen which contains the values of the electrical parameters on the AC side of the inverter, consistently with the settings made in § 5.2.2 (single-phase, threephase 4 wires). In particular, in this screen:

 Vacxy = AC voltage between Phase and Neutral (if single-phase) or between Phases x and y (if threephase)

Iacx = AC current of phase x

 Pacx = AC power of phase x

We recommend checking that the values of the electrical parameters (Vac, Iac, Pac) are consistent with the system being measured.

15/05/10 15:34:26

V

V a c 2 3 4 0 1 . 1

V a c 3 1 4 0 0 . 1

I a c 1 4 . 2 6

A

I a c 3 4 . 2 7

P a c 1 9 8 7

W

P a c 2 9 8 6

W

G O – s t a r t r e c

Select

M P P

E x a m p l e o f a s c r e e n f o r

P V s y s t e m s w i t h t h r e e p h a s e o u t p u t

15/05/10 15:34:26 distance approx. 1m), press the GO/STOP key on SOLAR I-

Vw or SOLAR I-Ve to start testing. Consequently:

 The display of SOLAR I-Vw or SOLAR I-Ve shows the message “rec. start waiting

 The display of SOLAR-02 shows the message “HOLD” and the time, expressed in seconds, remaining before the recording is started

P R p

I r r

T c

T e k W

P a c 2 . 9 6 0 n d c n a c

- - -

- - -

- - -

- - -

W / m 2

k W

° C

° C

- - -

0 . 9 5 k W

 On MPP300, the STATUS LED turns on green (not

Select flashing)

R e c . r u n n i n g

M P P

Upon reaching the instant “00” after pressing the

GO/STOP

synchronized with each other. In these conditions:

key, the test is started and the three units are

The display of SOLAR I-Vw or SOLAR I-Ve shows the message “rec. running

Recording…

P R p

I r r

T c

T e k W

P a c 2 . 9 6 0

The display of SOLAR-02 shows the message n a c

- - -

- - -

- - -

- - -

W / m 2

k W

° C

° C

- - -

0 . 9 5 k W

 On MPP300, the STATUS LED flashes green

R e c . r u n n i n g

Select

M P P

EN - 30

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

15/05/10 15:35:00 recording status by pressing the MENU key. The following information will be shown:

 Starting date and time of recording

The value set for the integration period

 The number of periods elapsed from the beginning of the recording

 The remaining memory capacity for recording

S t a r t

1 4 / 0 2 / 0 0 1 7 : 1 8 : 0 0

P e r i o d : 5 s

I P N u m b e r

R e c . T i m e

6 1

0 d 1 h

Select

R e c . R u n n i n g

M P P

Press the ESC key to exit the screen

23. Now it is possible to bring the unit SOLAR-02 near the PV strings to measure irradiation and temperature by means of the relevant probes. When the distance between unit SOLAR-

02 and MPP300 does not allow the RF connection, on the display of SOLAR-02 the symbol “ ” flashes for approx. 30s and then disappears. Unit MPP300 steadily searches for the RF connection with unit SOLAR-02.

24. Position the reference cell onto the surface of the PV modules. Please refer to the relevant

User Manual for a correct assembly.

25. Put the temperature sensor in contact with the rear side of the module and fasten it with some tape; prevent touching it with your fingers (as this could alter the measure).

26. Wait for a few seconds to allow the probes to reach a steady measure and then connect the irradiation probe to input PYRA/CELL and the temperature probe to input TEMP of unit

SOLAR-02.

27. Wait for the message “READY” to appear on the display of SOLAR-02 to indicate that the unit has detected the data with solar irradiation > minimum threshold set (see § 5.1.5).

28. With the message “READY” shown on the display, wait for approximately 1 minute in

order to take a certain number of samples

.

29. Disconnect the irradiation and temperature probes from unit SOLAR-02 and bring the unit near unit MPP300. Bring the main unit SOLAR I-Vw or SOLAR I-Ve near MPP300 too. The three units must be near each other (max distance 1m).

30. The main unit SOLAR I-Vw or SOLAR I-Ve must be in EFF mode; if no flashing symbol

“ ” appears, press key  to activate the RF connection search again.

31. Press key  on SOLAR-02 to activate the RF connection again. Consequently, the main unit will show the message “active radio connection”.

EN - 31

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

32. To stop testing, press the GO/STOP key on instrument

15/05/10 15:35:00

SOLAR I-Vw or SOLAR I-Ve and confirm pressing ENTER that you want to stop recording.

33. The display of SOLAR I-Vw or SOLAR I-Ve will show the message “DATA DOWNLOAD” to indicate that the data will be transferred to the main unit during its various phases.

34. After the automatic data transfer phase, the instrument:

Do not show any results if do not exist on the PV installation a “stable irradiance” condition more than the minimum irradiance threshold.

P R p

I r r

0 . 8 1 5

T c

T e

9 7 1

4 5 . 1

3 0 . 5

k W

° C

° C

0 . 9 4 7

W / m 2 k W

P a c 2 . 9 6 0 n a c k W n d c 0 . 8 0 6

Select

A n a l y s i s R e s u l t

E F F

 Display the best performance values if during the recording, the Irradiance values reached the “stable” condition and its values were higher than the minimum irradiance threshold.

35. Press SAVE to save the results (see § 7.1) or ESC to exit the screen of the results and go back to the initial screen.

EN - 32

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

6.2. I-V CURVE MEASUREMENT

The meter can perform I-V curve tests in automatic or manual activation mode by using one of the herewith modes:

 I-V curve test with Irr/Temp measurement directly performed by the instrument

 I-V curve test with Irr/Temp measurement performed by use of remote unit SOLAR-02

For theoretical information on measurement see the § 11.1

6.2.1. I-V curve measurement by use of instrument

CAUTION

 The maximum voltage among P1, P2, C1, and C2 inputs is 1000V DC (for I-

V400w and SOLAR I-Vw) or 1500VDC (for I-V500w and SOLAR I-Ve). Do not measure voltages exceeding the limits prescribed by this manual

 The maximum current measured by the meter is 15A. Do not perform test on strings of PV modules in parallel with them

 Do not perform test on PV modules or strings connected to DC/AC converter

1. Turn on the meter by pressing ON/OFF key

2. Check that option NO relative to the selection of remote unit SOLAR-02 should be set on the instrument (see § 5.1.4)

3. Check that the values set on the “Remote unit” section (see § 5.1.4) should be consistent with the reference cell depending on the kind of module/string on test

4. Check that the value set on “Irradiance” section (see § 5.1.5) should be consistent with the measurement to perform. It is suggested to perform the measurement with a threshold

 700 W/m

2

in compliance to the IEC/EN60891 guideline

5. Back to the main menu and select the “I-V” option

6. Press ENTER, by means of arrow keys (,) select

15/05/10 15:34:26 item “Meas. Type ”

7. Using the  key, select item “I-V Test” and confirm by pressing ENTER

V d c

I r r

= 0 . 0 V

= 0 W / m 2

T c

= - - - ° C

Module: SUNPOWER 210

I - V T e s t

S e t I V F a s t C h e c k

M e a

Select I - V

8. The instrument displays a screen similar to the one reported here to the side, where:

15/05/10 15:34:26

V d c

= 0 . 0 V

 Vdc = DC output voltage from module measured between C1 and C2 inputs of meter

 Irr = irradiance measured by supplied reference cell

I r r

= - - - W / m 2

T c

= A u t o

 Tc = temperature of module cell. The herewith options are available for this field:

 AUTO  automatic mode of temperature measurement

Number  MAN or AUX mode of temp. measurement

 “ - - - “  AUX mode with no connected probe

 Module = type of selected module

 Temp = measurement mode of module temperature

 Start = measurement activation mode

M o d u l e : P A N E L 0 1

Temp: Auto

Start: Manual

Select I - V

EN - 33

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

9. Press ENTER key, select the “Settings” item and confirm again with ENTER to access the next screen which allows setting the type of PV module and the number of modules relative to the PV string under test.

15/05/10 15:34:26

V d c

= 0 . 0 V

I r r

= - - - W / m 2

T c

= - - - ° C

Module: PANEL01

S e t t i n g s

M e a s . T y p e 

Select I - V

10. By means of arrow keys (,) select the type of PV

15/05/10 15:34:26 module included in the database of meter (§ 5.3.1).

11. By means of arrow keys (,) select the item “N. of

Type : SUNPOWER 210

N . o f M o d . : 1 5

O p e r . y r s : 4 . 5

Mod.” and by means of arrow keys (,) set the number of modules of the PV string under test. The maximum number of modules is 50

T e m p : A u t o

S t a r t : M a n u a l

P m a x = 2 1 0

V o c =

12. By means of arrow keys (,) select the “Oper. yrs” item and by means of arrow keys (,) set the service operating years of the PV module/string/field from start installation

V m p p = 4 0 . 0 0

I s c = 5 . 7 5

I m p p = 5 . 2 5

(see § 6.2.3). The maximum set value is 25.0 (0.5 = 6

S E T months)

13. By means of arrow keys (,) select the type of PV module included in the database of meter (§ 5.3.1). By means of arrow keys (,) select the “Temp” item and by means of arrow keys (,) choose the type of module temperature among the modes listed:

Auto”  automatic measurement performed by the meter depending on the measured value of open voltage of the modules (recommended method)

 “Manual”  setting of a module temperature value by the operator on the corresponding “Value” field

Aux”  setting of temperature of module performed by auxiliary probe

14. By means of arrow keys (,) select the “Start” item and by means of arrow keys

(,) choose the type of measurement activation between the modes listed:

Auto”  test automatically activated by the instrument with stable values of voltage among inputs for at least 1s and with values within the measurement range (see §

10.2)

 “Manual”  test activated from the user by press of GO/STOP key

15. Confirm with SAVE key or press ESC/MENU key to exit without saving

16. Mount the M304 (inclinometer) supplied accessory, place and hold it on the plane of module.

Verify that the sun shadow falls on the disc within the “limit internal circle” on the disc itself (see Fig. 7b). If this is not the case, the incidence angle between sun rays and the module surface is too high and not complying with the test conditions declared by the module manufacturer. As a consequence the measurements performed by the meter are not ok and all measurements steps shall be repeated at another daytime

17. Fix the support of the cell to the module by using the supplied set of screws and mount the reference cell on it possibly with output terminals downwards with respect to the

module

. Rotate the cell upwards to lean it on the small wing of the support so as the cell is perfectly parallel to the plane of module, then fix it with the relevant screws supplied

18. Connect the output of reference cell (depending on the type of module under test) of reference cell at the IRR. input of meter by using the cable supplied with the cell

EN - 34

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

19. Connect, if used, the auxiliary temperature probe (optional accessory) to the AUX input of meter and on the rear of module, fixing it with adhesive tape

20. Connect the meter to the module/string under test as shown in Fig. 7a. In particular, connect the negative output pole of module/string to P1, C1 input terminals and the positive output pole of module/string to P2, C2 input terminals. In Auto activation mode is recommended the use of KITKELVIN optional accessory

Fig. 7a: Instrument connection to module/string FV Fig. 7b: Positioning of inclinometer M304

CAUTION

The method used by the instrument meter for output VDC and IDC measurements of PV module/string is the “4-wire”. Therefore, it is possible to use also test cables connected to P1, C1, P2, C2 inputs of different length without performing any calibration of cable resistance. It is recommended to

use cables with a §

4mm

2

21. After connection to the plant, the real time values of

15/05/10 15:34:26 parameters are shown by meter:

 Vdc = DC output voltage of PV module/string

 Irr = Irradiance value measured by sensor

 Tc = Value of module temperature

V d c

I r r

= 3 6 7 V

= 1 0 4 5 W / m 2

T c

= 4 5 ° C

Module: SUNPOWER 210

Select

I - V

CAUTION

At the press of GO/STOP key some different error messages can be displayed by the meter (see § 6.4) and, due of this, the test cannot start.

Check and remove, if possible, this error message before start the test

22. Press GO/STOP key (in Manual activation mode) to start power during test.

15/05/10 15:34:26 the test. If none of the previous error messages are

V d c

= 3 6 7 V detected, the message “Measuring…” is shown on the display for some seconds, depending on the level of

I r r

= 1 0 4 5 W / m 2

Tc

= 45 °C

Module: SUNPOWER 210

Select

Measuring…

I - V

EN - 35

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

23. At the end of test, the values of typical parameters (all referred to a single module in standard conditions STC)

15/05/10 15:34:26 are shown by the meter together with the final response (§

6.2.3) based on the automatic calculation performed and relevant to:

I m p p = 4 . 7 A

 Translation of I-V curve to STC condition

 Verification of tolerance % of the maximum power declared by the manufacturer.

P m a x = 2 0 0

F F =

D P m a x = 2 . 1

Results @ STC – Response: OK

Select I - V

CAUTION

 The instrument refer all the values of parameters to one only module at the STC condition

 The total voltage of the string, obtained at OPC, is divided for the number of module of it. Considering this “average” value, together with the measured current, the instrument perform the I-V curve @ OPC calculation which is the translated at the STC condition

24. Press ENTER for the display of measurement results both in numeric and graphical mode referred to STC or OPC conditions (see § 6.2.3).

25. Use the arrow key  for the selection of table or graph

15/05/10 15:34:26

I m p p = 4 . 7 A visualization.

26. Press SAVE key to store the result of test (see § 7.2) or

P m a x = 2 0 0

F F =

ESC/MENU

key to exit without saving and to go back to the main menu

D P m a x = 2 . 1

T a b l e 

27. The “Auto” activation mode require to disconnect and

G r a p h 

– Response: OK

Select reconnect the test leads in order to start automatically a

I - V new measurement

EN - 36

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

6.2.2. I-V curve measurement by use of remote unit SOLAR-02

The I-V curve test with Irr/Temp measurement by use of remote unit SOLAR-02 can be performed in one of the herewith mode:

 Remote unit SOLAR-02 in RF connection with main unit

 Remote unit SOLAR-02 in synchro recording (no RF connection with main unit)

6.2.2.1. I-V curve test by remote unit SOLAR-02 in RF connection

This mode is possible ONLY if the distance between the main unit and the remote unit

SOLAR-02 can establish always a stable RF connection. This distance limit is influenced by obstacles, air humidity, etc., so it is considered valid about some meters.

CAUTION

 The maximum voltage among P1, P2, C1, and C2 inputs is 1000V DC (for I-

V400w and SOLAR I-Vw) or 1500VDC (for I-V500w and SOLAR I-Ve). Do not measure voltages exceeding the limits prescribed by this manual

 The maximum current measured by the meter is 15A. Do not perform test on strings of PV modules in parallel with them

 Do not perform test on PV modules or strings connected to DC/AC converter

1. Turn on the meter by pressing ON/OFF key

2. Check that option YES relative to the selection of remote unit SOLAR-02 should be set on the instrument (see § 5.1.4)

3. Check that the values set on the “Remote unit” section (see § 5.1.4) should be consistent with the reference cell depending on the kind of module/string on test

4. Check that the value set on “Irradiance” section (see § 5.1.5) should be consistent with the measurement to perform. It is suggested to perform the measurement with a threshold

 700 W/m

2

in compliance to the IEC/EN60891 guideline

5. Back to the main menu and select the “I-V” option

6. Press ENTER, by means of arrow keys (,) select item “Meas. Type ”

7. Using the  key, select item “I-V Test” and confirm by

15/05/10 15:34:26

V d c

= 0 . 0 V pressing ENTER

I r r

= 0 W / m 2

T c

= - - - ° C

Modulo: SUNPOWER 210

I - V T e s t

S e t I V F a s t C h e c k

M e a

Select I - V

8. Switch on the remote unit SOLAR-02 and wait that “Radio connection active” message is displayed

EN - 37

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

9. The instrument displays :

 Vdc = DC output voltage from module/string

 Irr = irradiance measured by supplied reference cell

 Tc = temperature of module. The herewith options are available for this field:

 AUTO  automatic mode

 Number  MAN or AUX mode

“ - - - “  AUX mode with no connected probe

 Module = type of selected module

 Temp = measurement mode of module temperature

 Start = measurement activation mode

 The symbol “

fixed at display means that a stable

RF connection is established with the remote unit

10. Press ENTER key, select the “Settings” item and confirm again with ENTER to access the next screen which allows setting the type of PV module and the number of modules relative to the PV string under test.

15/05/10 15:34:26

V d c

= 0 . 0 V

I r r

= - - - W / m 2

T c

= A u t o ° C

Module: PANEL01

Temp: Auto

Start: Manual

Select

I – V

15/05/10 15:34:26

V d c

= 0 . 0 V

I r r

= - - - W / m 2

T c

= - - - ° C

Module: PANEL01

S e t t i n g s

M e a s . T y p e

Select

I - V

11. By means of arrow keys (,) select the type of PV

15/05/10 15:34:26 module included in the database of meter (§ 5.3.1)

Type : SUNPOWER 210

12. By means of arrow keys (,) select the item “N. of

Mod.” and by means of arrow keys (,) set the number

N . o f M o d . : 1 5

O p e r . y r s 4 . 5 of modules of the PV string under test. The maximum

T e m p : A u t o

S t a r t : M a n u a l number of modules is 50

P m a x = 2 1 0

V o c =

13. By means of arrow keys (,) select the “Oper. yrs” item and by means of arrow keys (,) set the service operating years of the PV module/string/field from start installation

V m p p = 4 0 . 0 0

I s c = 5 . 7 5

I m p p = 5 . 2 5

(see § 6.2.3). Maximum set value is 25.0 (0.5 = 6 months)

S E T

14. By means of arrow keys (,) select the type of PV module included in the database of meter (§ 5.3.1). By means of arrow keys (,) select the “Temp” item and by means of arrow keys (,) choose the type of module temperature among the modes:

Auto”  automatic measurement performed by the meter depending on the measured value of open voltage of modules (recommended method)

 “Manual”  setting of a module temperature value by the operator on the corresponding “Value” field

 “Aux”  setting of temperature of module performed by auxiliary probe

15. By means of arrow keys (,) select the “Start” item and by means of arrow keys

(,) choose the type of measurement activation between the modes listed:

Auto”  test automatically activated by the instrument with stable values of voltage among inputs for at least 1s and with values within the measurement range (see §

10.2)

Manual”  test activated from the user by press of GO/STOP key

16. Confirm with SAVE key or press ESC/MENU key to exit without saving

EN - 38

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

17. Mount the M304 (inclinometer) supplied accessory, place and hold it on the plane of module.

Verify that the sun shadow falls on the disc within the “limit internal circle” on the disc itself (see Fig. 8). If this is not the case, the incidence angle between sun rays and the module surface is too high and not complying with the test conditions declared by the module manufacturer. As a consequence the measurements performed by the meter are not ok and all measurements steps shall be repeated at another daytime

18. Fix the support of the cell to the module by using the supplied set of screws and mount the reference cell on it possibly with output terminals downwards with respect to the

module

. Rotate the cell upwards to lean it on the small wing of the support so as the cell is perfectly parallel to the plane of module, then fix it with the relevant screws supplied

19. Connect the output of reference cell (depending on the type of module under test) at the PYRA/CELL input of remote unit SOLAR-02 by using the supplied cable

20. Connect, if used, the auxiliary temperature probe to the TEMP input of remote unit

SOLAR-02 and on the rear of module, fixing it with adhesive tape

21. Connect the meter to the module/string under test as shown in Fig.9. In particular, connect the negative output pole of module/string to P1, C1 input terminals and the positive output pole of module/string to P2, C2 input terminals. In Auto activation mode is recommended the use of KITKELVIN optional accessory

Fig. 8: Positioning the M304 inclinometer

Fig. 9: Connection of units to the PV module/string

EN - 39

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

22. The instrument displays:

 Vdc = DC output voltage from module/string.

 Irr = irradiance measured by supplied reference cell

 Tc = temperature of module. The herewith options are available for this field:

 AUTO  automatic mode of temperature measurement

 Number  MAN or AUX mode of temp. measurement

“ - - - “  AUX mode with no connected probe

 Module = type of selected module

 Temp = measurement mode of module temperature

 Start = measurement activation mode

 The symbol “

fixed at display means that a stable

RF connection is established with the SOLAR-02

15/05/10 15:34:26

V d c

= 3 6 7 V

I r r

= 1 0 4 5 W / m 2

T c

= 4 5 ° C

Module: SUNPOWER 210

Temp: Auto

Start: Manual

Select

I – V

CAUTION

At the press of GO/STOP key some different error messages can be displayed by the meter (see § 6.3) and, due of this, the test cannot start.

Check and remove, if possible, this error message before start the test

23. Press GO/STOP key (in Manual activation mode) to start

15/05/10 15:34:26 the test. If none of the previous error messages are

V d c

= 3 6 7 V detected, the message “Measuring…” is shown on the display for some seconds, depending on the level of

I r r

= 1 0 4 5 W / m 2 power during test.

Tc

= 45 °C

Module: SUNPOWER 210

Measuring…

Select I - V

24. At the end of test, the values of typical parameters (all referred to a single module in standard conditions STC) are shown by the meter together with the final response (§

6.2.3) based on the automatic calculation performed and

15/05/10 15:34:26

I m p p = 4 . 7 A relevant to:

 Translation of I-V curve to STC condition

P m a x = 2 0 0

F F =

 Verification of tolerance % of the maximum power

D P m a x = 2 . 1 declared by the manufacturer.

Results @ STC – Response: OK

Select

I - V

25. Press ENTER for the visualization of measurement results referred at STC or OPC conditions both in numeric and graphical mode (§ 6.2.3)

26. Use the arrow key  for the selection of table or graph

15/05/10 15:34:26

I m p p = 4 . 7 A visualization

27. Press SAVE key to store the result of test (see § 7.2) or

ESC/MENU

key to exit without saving and to go back to

P m a x = 2 0 0

F F =

D P m a x = 2 . 1

T a b l e  the main menu

28. The “Auto” activation mode require to disconnect and

G r a p h 

– Response: OK

Select I - V reconnect the test leads in order to start automatically a new measurement

EN - 40

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

6.2.2.2. I-V curve test by remote unit SOLAR-02 in synchro recording

This mode, which consists in an independent recording of the irradiance and temperature parameters by the remote unit SOLAR-02, permits to perform I-V curve test also with wide distance between the instrument and SOLAR-02 without any connection between them.

On the other hand, due to the impossibility for the meter to have immediately the values of irradiance/temperature, it is necessary wait the transfer of data from remote unit SOLAR-

02 to main unit in order to have all the available results.

CAUTION

 The maximum voltage among P1, P2, C1, and C2 inputs is 1000V DC (for I-

V400w and SOLAR I-Vw) or 1500VDC (for I-V500w and SOLAR I-Ve). Do not measure voltages exceeding the limits prescribed by this manual

 The maximum current measured by the meter is 15A. Do not perform test on strings of PV modules in parallel with them

 Do not perform test on PV modules or strings connected to DC/AC converter

1. Turn on the meter by pressing ON/OFF key

2. Check that option YES relative to the selection of remote unit SOLAR-02 should be set on the instrument (see § 5.1.4)

3. Check that the value set on “Irradiance” section (see § 5.1.5) should be consistent with the measurement to perform. It is suggested to perform the measurement with a threshold

 700 W/m

2

in compliance to the IEC/EN60891 guideline

4. Back to the main menu and select the “I-V” measurement mode

5. Press ENTER, by means of arrow keys (,) select item “Meas. Type ”

15/05/10 15:34:26

V d c

= 0 . 0 V

6. Using the  key, select item “I-V Test” and confirm by pressing ENTER

I r r

= 0 W / m 2

T c

= - - - ° C

Module: SUNPOWER 210

I - V T e s t

S e t I V F a s t C h e c k

M e a

Select

I - V

7. Switch on the remote unit SOLAR-02 and wait that “Radio connection active” is displayed

8. Check the status of internal batteries of SOLAR-02 (the “ displayed)

” symbol should be not

9. Check that the values of sensitivity and temperature coefficient set on the SOLAR-02 section should be consistent with the reference cell depending on the kind of module/string on test (see user manual of SOLAR-02)

EN - 41

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

10. The instrument displays:

 Vdc = DC output voltage from module/string

 Irr = irradiance measured by supplied reference cell

 Tc = temperature of module. The herewith options are available for this field:

 AUTO  automatic mode of temperature measurement

 Number  MAN or AUX mode of temp. measurement

“ - - - “  AUX mode with no connected probe

 Module = type of selected module

 Temp = measurement mode of module temperature

 Start = measurement activation mode

 The symbol “

fixed at display means that a stable

RF connection is established with the SOLAR-02

11. Press ENTER key, select the “Settings” item and confirm again with ENTER to access the next screen which allows setting the type of PV module and the number of modules relative to the PV string under test.

15/05/10 15:34:26

V d c

= 0 . 0 V

I r r

= - - - W / m 2

T c

= A u t o ° C

Module: PANEL01

Temp: Auto

Start: Manual

Select

I – V

15/05/10 15:34:26

V d c

= 0 . 0 V

I r r

= - - - W / m 2

T c

= - - - ° C

Module: PANEL01

S e t t i n g s

M e a s . T y p e 

Select

I - V

12. By means of arrow keys (,) select the type of PV

15/05/10 15:34:26 module included in the database of meter (§ 5.3.1)

Type : SUNPOWER 210

13. By means of arrow keys (,) select the item “N. of

Mod.” and by means of arrow keys (,) set the number

N . o f M o d . : 1 5

O p e r . y r s 4 . 5

T e m p : A u t o of modules of the PV string under test. The maximum

S t a r t : : M a n u a l

P m a x = 2 1 0 number of modules is 50

14. By means of arrow keys (,) select the “Oper. yrs” item and by means of arrow keys (,) set the service operating years of the PV module/string/field from start installation

4 7 . 7 0

V m p p = 4 0 . 0 0

I s c = 5 . 7 5

I m p p = 5 . 2 5

(see § 6.2.3). Maximum set value is 25.0 (0.5 = 6 months)

S E T

15. By means of arrow keys (,) select the type of PV module included in the database of meter (§ 5.3.1). By means of arrow keys (,) select the “Temp” item and by means of arrow keys (,) choose the type of module temperature among the modes:

Auto”  automatic measurement performed by the meter depending on the measured value of open voltage of modules (recommended method)

 “Manual”  setting of a module temperature value by the operator on the corresponding “Value” field

 “Aux”  setting of temperature of module performed by auxiliary probe

16. By means of arrow keys (,) select the “Start” item and by means of arrow keys

(,) choose the type of measurement activation between the modes listed:

Auto”  test automatically activated by the instrument with stable values of voltage among inputs for at least 1s and with values within the measurement range (see §

10.2)

 “Manual”  test activated from the user by press of GO/STOP key

17. Confirm with SAVE key or press ESC/MENU key to exit without saving

EN - 42

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

18. Mount the M304 (inclinometer) supplied accessory, place and hold it on the plane of module.

Verify that the sun shadow falls on the disc within the “limit internal circle” on the disc itself (see Fig. 10). If this is not the case, the incidence angle between sun rays and the module surface is too high and not complying with the test conditions declared by the module manufacturer. As a consequence the measurements performed by the meter are not ok and all measurements steps shall be repeated at another daytime

19. Fix the support of the cell to the module by using the supplied set of screws and mount the reference cell on it possibly with output terminals downwards with respect to the

module

. Rotate the cell upwards to lean it on the small wing of the support so as the cell is perfectly parallel to the plane of module, then fix it with the relevant screws supplied

20. Connect the output of reference cell (depending on the type of module under test) at the PYRA/CELL input of remote unit SOLAR-02 by using the supplied cable

21. Connect, if used, the auxiliary temperature probe to the TEMP input of remote unit

SOLAR-02 and on the rear of module, fixing it with adhesive tape

22. Connect the meter to the module/string under test as shown in Fig.11. In particular, connect the negative output pole of module/string to P1, C1 input terminals and the positive output pole of module/string to P2, C2 input terminals. In Auto activation mode is recommended the use of KITKELVIN optional accessory

Fig. 10: Positioning the M304 inclinometer

Fig.11: Connection of units to the PV module/string

EN - 43

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

23. The instrument displays:

 Vdc = DC output voltage from module/string

 Irr = irradiance measured by supplied reference cell

 Tc = temperature of module. The herewith options are available for this field:

15/05/10 15:34:26

V d c

I r r

= 3 6 7 V

= 1 0 4 5 W / m 2

T c

= 4 5 ° C

 AUTO  automatic mode of temperature measurement

 Number  MAN or AUX mode of temp. measurement

“ - - - “  AUX mode with no connected probe

 Module = type of selected module

 Temp = measurement mode of module temperature

 Start = measurement activation mode

 The symbol “

fixed at display means that a stable

RF connection is established with the remote unit

SOLAR-02

Module: SUNPOWER 210

Temp: Auto

Start: Manual

Select

I – V

24. Press ENTER key, select the “Activate Rec.” item and 15/05/10 15:34:26 confirm with ENTER. The message “Remote unit in

V d c

= 0 . 0 V recording…” is displayed on the meter. In this condition is possible to start the I-V curve tests always considering

I r r

= - - - W / m 2 that the complete results will be available only after the stop of recording of SOLAR-02 and transfer them from the same remote unit

T c

= - - - ° C

A c t i v a t e R e c .

S e t t i n g s

M e a s . T y p e 

Select

I – V

CAUTION

At the press of GO/STOP key some different error messages can be displayed by the meter (see § 6.4) and, due of this, the test cannot start.

Check and remove, if possible, this error message before start the test

25. Press GO/STOP key (in Manual activation mode) to start power during test.

15/05/10 15:34:26 the test. If none of the previous error messages are

V d c

= 3 6 7 V detected, the message “Measuring…” is shown on the display for some seconds, depending on the level of

I r r

= - - - W / m 2

Tc

= Auto °C

Module: SUNPOWER 210

Select

Measuring…

I - V

EN - 44

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

26. At the end of test, based on the descriptions of previous

15/05/10 15:34:26 points, the message “STC Data available after Stop rec” is displayed and then the results at OPC conditions are displayed

1 5 . 2

V

I m p p = 4 . 7

I s c =

F F =

I r r =

T c =

A

P m a x = 2 0 0

7 7 . 1

- - - W / m

2

Select

Results @ OPC

I - V

27. Press ENTER for the visualization of measurement results both in numeric and graphical mode (§ 6.2.3)

28. Use the arrow key  for the selection of table or graph

15/05/10 15:34:26 visualization

29. Press SAVE key to store the result of test or ESC/MENU key to exit without saving and to go back to the main screen

30. The “Auto” activation mode require to disconnect and reconnect the test leads in order to start automatically a new measurement

I m p p = 4 . 7

I s c =

P m a x = 2 0 0

F F =

I r r

=

T a b l e 

- - -

%

W / m

2

G r a p h 

Select I - V

31. At the end of I-V test, press the ENTER key, select the

15/05/10 15:34:26

Stop recording” item and confirm with ENTER. The messages “Wait…” and then “STC Data available in MEM” are displayed

V d c

= 0 . 0 V

I r r

= - - - W / m 2

32. In this conditions, for the I-V tests performed with irradiance values over the limit threshold and stable, the correspondent STC results will be available inside memory

T c

= A u t o ° C

S t o p R e g .

S e t t i n g s

M e a s . T y p e 

Select I - V

33. The message “Download data” is displayed on the instrument and, at the same time, the message “Send” is displayed on SOLAR-02 which means the transfer of irradiance values and, if necessary, the module temperature values on the main unit

34. At the end of data transfer the instrument automatically join the average value of irradiance (detected with IP = 5s) to each I-V test performed and, correspondingly, will calculate the results translated to STC conditions and the Yes/No response for each test. The complete results are recalled at display as described in § 7.3.2. See the §

6.2.3 for the meaning of measurement results

EN - 45

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

6.2.3. Meaning of measurement results

The parameter measured and calculated by meter have the following meaning:

Parameter Description

Pmax Maximum power of module measured by the meter

DPmax

FF

Difference % of maximum measured power from nominal power (@ STC)

Fill Factor %

Vmpp Voltage on point of maximum power

Isc Short circuit current

Impp Current on point of maximum power

Table 2: List of parameter measured by the meter

Where:

DP

MAX

%

100 

P

MAX

Nom

P

Age

Nom

P

Age

 check parameter which defines the final test response

P

Nom

Age

P

Nom

1

Oper

.

Yrs

YearDegr

100

%

P

Nom

= nominal power of module

FF = 100 x [(Vmpp x Impp ) / (Voc x Isc)] = Fill Factor  represents a kind of “efficiency” of module/string as it is a ratio between the maximum power measured and the open power

The meter gives the following final response:

Response Condition Note

OK

- Tol

(-)

+

Meter

 

Meas

Tol

(+)

-

Meter

(1)

OK*

NO OK*

The previous relation (1) is not verified but the following is valid:

- Tol

(-)

 

Meas

Tol

(+)

The relations (1) and (2) are not verified but the following is valid:

- Tol

(-)

-

Meter

 

Meas

Tol

(+)

+

Meter

(2)

(3)

NO OK

None of the relations (1), (2) and (3) are verified (4) where:

Tol

(-)

= Tol

(-)

(%)*Pnom

 Negative tolerance in absolute value, declared by manufacturer

Tol

(+)

= Tol

(+)

(%)*Pnom

 Positive tolerance in absolute value, declared by manufacturer

Meas

= Pmax – Pnom  DPmax which defines the difference between measured values and declared values

Meter

 Absolute error of the measurement chain (meter + transducers in the point of measure) considering the error % and the declared dgt

(1) OK  Positive response of test also considering the error of measurement chain

(2) OK*  Response of test positive less than the error of measurement chain

(3) NO OK*  Response of test negative less than the error of measurement chain

(4) NO OK  Negative response of test also considering the error of measurement chain

EN - 46

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

6.3. QUICK CHECK ON PV MODULES AND STRINGS (IVCK) information

This function permits to carry out a quick Test of a panel/string just measuring open circuit voltage and short circuit current in compliance with IEC/EN62446. Consequently both irradiance and temperature module values can be measured (using corresponding probes).

Irradiation measurement can be executed only adopting one of the following modes:

 Irradiance sensor directly connected to I-V400w, I-V500w , SOLAR I-Vw or SOLAR I-Ve

 Irradiance sensor connected to SOLAR-02 through RF to I-V400w, I-V500w , SOLAR I-

Vw or SOLAR I-Ve

Irradiance measurements are always effected in real time, it is impossible to start a “remote” recording of irradiance values through SOLAR-02

If minimum IV irradiance threshold is set (see § 5.1.5):

 =

the instrument does not control the presence of cell, irradiance changes, number of modules and does not display error messages should it be impossible to calculate Voc and Isc values transposed to Voc and Isc under STC. This mode is suitable to effect a test session on a considerable number of strings as quickly as possible.

 > 0 (suggested > 700)  the instrument carries out all tests provided for I-V, manages all conditions and error messages for I-V test (wrong num. Mod., Temp. out of range, cell presence, Min Irr, etc..) and calculates values of Voc and Isc under STC. This mode is recommended whenever thorough tests are to be effected on modules/strings under test.

In general the result page will include:

 Description of the module

 Irradiance and temperature values (if available)

 Average values of Voc and Isc calculated as average of the corresponding values under

OPC on the last 10 tests saved into memory. If the number of tests is < 10 the average is calculated on the number of available tests. The first test will display dashes in the field

“average values” as there are no previous tests on which average can be calculated.

 The values of Voc and Isc measured under OPC as well as any partial outcome (the latter available only if STC values are not available) obtained through comparison with average values.

 The values of Voc and Isc calculated under STC (if available) and any partial outcome obtained comparing the values calculated under STC with the nominal ones (inserted in

DB modules).

 The overall test outcome (OK(NO). The overall result will be calculated based on the partial results.

 Based on partial outcome under STC (if these are available)

 Based on partial outcome under OPC (if STC values are not available)

The instrument will not display any overall outcome if no partial result is available.

In case of negative outcome it is advisable to effect measurement of I-V feature (see § 6.2) in order to thoroughly analysis of the module/string under test.

EN - 47

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

settings

1. Turn the instrument on by pressing ON/OFF key.

2. Press ESC/MENU to display the main menu.

3. Select “I-V” and press ENTER to enter the FV module performance measurement section.

15/05/10 15:34:26 4. In case the current mode is not IVCK, press ENTER, select “Measurement ” by means of arrow keys

(,).Use the arrow key  to enter the internal submenu, select “IV Check” and confirm by ENTER to start up the initial screen of rapid test IVCK.

V d c

I r r

T c

= 0 . 0 V

= 0 W / m 2

= - - - ° C

Module: SUNPOWER 210

S e t R s T e s t

M e a I - V F a s t C h e c k

Select I - V

5. Press ENTER, select “Settings” and confirm by pressing ENTER again to enter the following screen where it is possible to set module type and number of modules making the string under test.

A v g R e s e t

S e t t i n g s

M e a s T y p e 

I r r 9 8 0 W / m 2

T c ( A U T O ) 4 9 ° C

V o c M e d @ O P C

I s c M e d @ O P C

V o c @ O P C

I s c @ O P C

6 4 7

V

5 . 4 3

A

6 4 6

V

- - -

A

V

A

M o d u l e : S U N P W R 2 1 0

Select

I V C K

6. Use the arrow keys ( , ) to select the module type among the ones stored inside the instrument’s database (see § 5.3.1)

7. Use the arrow keys (,), select “Mod. per Str” and use the arrow keys ( , ) to enter the number of

15/05/10 15:34:26

Tipo : SUNPOWER 210

M o d . x S t r : 1 5

T e m p :

V a l u e

T o l V o c

T o l I s c

: 5 1 ° C

:

:

3 % ( + 4 % )

3 % ( + 4 % ) modules for the string under test. The maximum number of modules to be set is 50

8. Use the arrow keys (,), select “Temp” and use the arrow keys ( , ) to select the measurement type of

V o c

I s c

=

=

6 4 . 7 %

6 . 2 0 %

S E T T I N G

the module temperature among the modes:

Auto”  automatic measurement carried out according to the measured open circuit voltage value of modules (recommended method)

Manual  entering the value of module temperature in the corresponding field “Value

Aux  temperature measurement with probe

9. Use the arrow keys (,), select “Tol Voc” and “Tol Isc” then use the arrow keys ( , ) to set the tolerance values for open circuit voltage (Voc) and short circuit current (Isc) provided by the module manufacturer (values allowed: +0% .. +25%). Please note that the instrument’s uncertainty is indicated in brackets beside the above mentioned values and it will be added to the value entered to get the outcome (OK/NO).

10. By means of arrow keys (,) select the “Start” item and by means of arrow keys

(,) choose the type of measurement activation between the modes listed:

 “Auto”  test automatically activated by the instrument with stable values of voltage among inputs for at least 1s and with values within range (see § 10.2)

 “Manual”  test activated from the user by press of GO/STOP key

11. Press SAVE to store the measurements effected or ESC/MENU to quit without saving.

EN - 48

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

6.3.3. Fast check IVCK without irradiance measurement

CAUTION

 The maximum voltage among inputs P1, P2, C1 and C2 is 1000V DC (for I-

V400w and SOLAR I-Vw) or 1500V (for I-V500w and SOLAR I-Ve). Do not measure voltages exceeding the limits expressed in § 10.2

 The maximum current allowable for the instrument is 15A. Do not effect tests in parallel on FV module strings.

 Never effect tests on modules or FV strings connected to DC/AC converter.

1. Turn on the instrument pressing ON/OFF

2. Check that remote unit SOLAR-02 is not selected (see § 5.1.4– setting NO)

3. Check that the value of minimum irradiance set in the section “Irradiance” (see §5.1.5) is equal to 0

4. Go back to main MENU and select “I-V

5. Select “I-V” and press ENTER to enter the section of FV module performance measurement. Generally when selecting I-V on general menu the instrument automatically shows the last mode under use (I-V or IVCK).

6. In case the current mode is not IVCK, press ENTER,

ENTER

to start up the initial screen of fast check IVCK.

15/05/10 15:34:26 select “Measurement ” by means of arrow keys

(,). Use the arrow key  to enter the internal

V d c

= 0 . 0 V submenu, select “IV Check” and confirm pressing

I r r

= 0 W / m 2

T c

= - - - ° C

Module: SUNPOWER 210

I m p I V C h e c k

M i s

Selection

7. Check the preliminary settings based on descriptions of § 6.3.2

I - V

8. Connect the instrument to the module/string under test as shown in the following picture. In particular connect the negative pole of the module/string to terminals P1, C1 and it positive pole to terminals P2, C2. In Auto activation mode is recommended the use of KITKELVIN optional accessory

CAPTION:

P1: Black cable

P2: Blue cable

C1: Green cable

C2: Red cable

1: Module or FV string

Fig. 10: Connection to module/FV string for IVCK tests without irradiance measurement

EN - 49

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

9. The initial screen under IVCK mode displays the values of:

Module under use

 The average values of Voc and Isc under OPC conditions.

 The value of Voc measured under OPC conditions

15/05/10 15:34:26

M o d u l e :

S U N P W R 2 1 0

I r r . - - - W / m 2

T c ( A U T O ) - - - ° C

V o c M e d @ O P C 6 4 7 V

I s c M e d @ O P C 5 . 4 3 A

V o c @ O P C 6 4 6 V

I s c @ O P C - - - A

V o c @ S T C - - - V

I s c @ S T C - - - A

Selection

I V C K

CAUTION

When pressing the GO/STOP key the instrument can provide different error messages (see §6.3) and, as direct consequence, not carry out the test. Check and eliminate, if possible, causes of the problems before continuing the test.

10. Press GO/STOP (in Manual activation mode) to start the test. In case of no error conditions, the instrument displays the screen with results as shown sideways. It displays as follows:

The module under use

The average values of Voc and Isc under OPC conditions

15/05/10 15:34:26

M o d u l e :

I r r - - - W / m 2

T c ( A U T O )

V o c M e d @ O P C

I s c M e d @ O P C

V o c @ O P C

- - ° C

6 4 7

5 . 4 3

6 4 7

5 . 3 5

V

A

V O K

A O K

I s c @ S T C - - A

S U N P W R 2 1 0

I s c @ O P C

V o c @ S T C - - - V

 The values of Voc and Isc measured under OPC and relative partial outcome resulting after comparing the average values. In general:

Selection

OUTCOME: OK

I V C K

O

utcome

Voc

@

OPC

OK

if 100

VocAvg

@

OPC

Voc

@

OPC

VocAvg

@

OPC

Tol Voc

4%

O

utcome

Isc

@

OPC

OK

if 100

IsAvg

@

OPC

Isc

@

OPC

Tol Isc

4%

IscAvg

@

OPC

 The overall value of outcome: o

OK: if all results under OPC are OK, o

NO if one of the results under OPC is NO

11. Press SAVE to store the test result into the instrument’s memory (see §7.2) or press

ESC/MENU

to quit without saving and go back to main measurement screen

12. The “Auto” activation mode require to disconnect and reconnect the test leads in order to start automatically a new measurement

NOTES on displayed AVERAGE VALUES

The average values of Voc and Isc are displayed on the outcome page. Such values include the average values of Voc and Isc under OPC conditions calculated as mean of the last 10 tests previously saved. If the user effected and saved a number of tests <10 or he reset the average values (see 6.3.5) the average value displayed during test N+1 will be calculated on N available values.

EN - 50

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

6.3.4. Fast check IVCK with irradiance measurement

CAUTION

 The maximum voltage among inputs P1, P2, C1 and C2 is 1000V DC (for I-

V400w and SOLAR I-Vw) or 1500V (for I-V500w and SOLAR I-Ve). Do not measure voltages exceeding the limits expressed in § 10.2

 The maximum current allowable for the instrument is 15A. Do not effect tests in parallel on FV module strings.

 Never effect tests on modules or FV strings connected to DC/AC converter.

1. Turn on the instrument pressing ON/OFF

2. Irradiance measurement can be carried out just through the following modes:

 Measurement through reference cell directly connected to I I-V400w, I-V500w, SOLAR

I-Vw or SOLAR I-Ve

 Measurement through reference cell connected to SOLAR-02 under RF to I-V400w, I-

V500w, SOLAR I-Vw or SOLAR I-Ve

Check that the remote unit SOLAR-02 setting is consistent with the type of measurement to be effected (see §5.1.4).

3. Check the minimum irradiance value set in the “irradiance” section (see § 5.1.5).

4. Go back to main MENU and select “I-V

5. Select “I-V” and press ENTER to enter the FV module performance measurement section.

Generally when selecting I-V on general menu the instrument automatically shows the last mode under use (I-V or IVCK).

6. In case the current mode is not IVCK, press ENTER,

ENTER

to start up the initial screen of fast check IVCK

15/05/10 15:34:26 select “Measurement ” by means of arrow keys

(,). Use the arrow key  to enter the internal

V d c

= 0 . 0 V submenu, select “IV Check” and confirm pressing

I r r

= 0 W / m 2

T c

= - - - ° C

Module: SUNPOWER 210

I m p I V C h e c k

M i s

Selezione

7. Check the preliminary settings based on descriptions of § 6.3.2

I - V

8. Connect the instrument to the module/string under test as shown in the following picture. In particular connect the negative pole of the module/string to terminals P1, C1 and it positive pole to terminals P2, C2. In Auto activation mode is recommended the use of KITKELVIN optional accessory

Caption:

P1: Black

P2: Blue cable cable

C1: Green cable

Fig. 14: Instrument’s connection for

IVCK tests with direct measurement of Irrad/Temp

Fig. 15: Instrument’s connection for

IVCK tests with measurement of

Irrad/Temp through SOLAR-02

C2: Red cable

1: Module or FV string

2: Reference cell

3: Temp probe (if required)

4 Remote unit SOLAR-02

EN - 51

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

9. Connect irradiance probes and temperature probe (if necessary) according to previous pictures and to effected settings (see § 6.3.2).

10. In the initial screen of IVCK mode the following values are

 displayed:

Module under use

Irradiance (through direct measurement or SOLAR_02 under

RF connection)

The temperature value (if mode MAN or AUX) and corresponding measurement mode. If mode AUTO ”- - -“

The average values of Voc and Isc under OPC conditions

15/05/10

15:34:26

M o d u l e :

S U N P W R 2 1 0

I r r . 9 8 0 W / m 2

T c ( A U T O )

V o c M e d @ O P C

I s c M e d @ O P C

V o c @ O P C

I s c @ O P C

V o c @ S T C

I s c @ S T C

- - ° C

6 4 7

5 . 4 3

6 4 6

- - -

- - -

- - -

V

A

V

A

V

A

The following values acquired in real time are also displayed:

 Open circuit voltage

Selection I V C K

 Any symbol of RF connection with SOLAR-02

CAUTION

When pressing the GO/STOP key the instrument can provide different error messages (see §6.3) and, as direct consequence, not carry out the test. Check and eliminate, if possible, causes of the problems before continuing the test.

11. Press GO/STOP (in Manual activation mode) to start up the

 test. In case of no error conditions, the instrument displays the screen with the following results:

The module under use

The irradiance value

The cell temperature value

The average values of Voc and Isc under OPC

 The values of Voc and Isc measured under OPC

15/05/10 15:34:26

M o d u l e :

I r r 9 3 2 W / m 2

T c ( A U T O )

V o c M e d @ O P C

I s c M e d @ O P C

V o c @ O P C

I s c @ O P C

V o c @ S T C

I s c @ S T C

S U N P W R 2 1 0

5 7 ° C

6 4 7

V

5 . 4 3

A

6 4 7

V

5 . 3 5

7 8 7

5 . 7 2

A

V O K

A O K

OUTCOME: OK

 The values of Voc and Isc measured under STC and relative

Selection I V C K partial outcome resulting after comparing the rated values.

In general:

Outcome Voc

@

STC

OK

if 100

VocNom

@

STC

Voc

@

STC

VocNom

@

STC

Tol Voc

4%

Outcome Isc

@

STC

OK

if 100

IscNom

@

STC

Isc

@

STC

Tol Isc

4%

IscNom

@

STC

The rated values of Voc and Isc are the values of the DB built-in modules (see §5.3)

 The overall value of outcome: o

OK: if all results under STC are OK, o

NO if one of the results under STC is NO

12. Press SAVE to store the test result into the instrument’s memory (see §7.2) or press

ESC/MENU

to quit without saving and go back to main measurement screen

13. The “Auto” activation mode require to disconnect and reconnect the test leads in order to start automatically a new measurement

EN - 52

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

Media

If irradiance values are measured the instrument provides an outcome comparing the measured values with the average values calculated according to previously saved measurements.

Therefore in this case the average values calculated by the instrument play an important role.

In case you start a new set of measurements with significant variations in irradiance and temperature it is advisable to set the reference average values to zero in order to recalculate based on new measurements.

To reset the average values keep to the following steps:

1. Under mode IVCK, press ENTER key, select “Reset

Media

” and confirm by pressing ENTER to zero the average values calculated till then.

15/05/10 15:34:26

M o d u l e : S U N P W R 2 1 0

I r r 9 8 0 W / m 2

T c ( A U T O ) 4 9 ° C

V o c M e d @ O P C - - - V

I s c M e d @ O P C - - - A

V o c @ O P C 6 4 6 V

I s c @ O P C - - - A

R e s e t M e d i a

S e t t i n g s

M e a s u r e m e n t 

V

A

Selection I V C K

The average values are automatically reset even modifying and saving one of the following parameters:

 FV module type

 Number of modules per string

The average values are not reset if the operator changes working mode (for example he goes to the overall detection of the I-V curve to effect string analysis in deep) and go back to this mode.

EN - 53

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

6.4. LIST OF DISPLAY MESSAGES

MESSAGE DESCRIPTION

Voltage too low

Vin > 1000

Irradiance too low

NTC Error

Please wait for cooling…

Memory full

Pulse width too long

Current too low

Vdc wrong connection

Negative voltage

Data base full

Data @ STC unavailable

Irradiance too high

Data unavailable

Isc too high

Wrong date

Error 1/2/3/4/5: contact Assistance

Error EEPROM : contact Assistance

Error FLASH : contact Assistance

Error RTC : contact Assistance

Battery low

Error: Vmpp >= Voc

Error: Impp >= Isc

Error: Vmpp * Impp >= Pmax

Error: alpha too high

Error: beta too high

Error: Toll too high

Error: gamma too high

Module already present

Delta-Irrad. too high. Retry

Voltage not steady

Unsteady Current

Firmware mismatch

Ref. Cell temp over range

PV module temp over range

Voc out of range. Continue (ENTER/ESC)?

Ref. Cell temp not detected (ENTER/ESC)

Error during memory writing

Error Radio: contact Assistance

Error Radio transmission

Error during download

Recording downloaded

Radio connection activated

Wait data analysis

Unable execute analysis

I < Lim

CAUTION: internal short

Remote unit not detected Enter/Esc

Rem. Unit in rec

STC Data available after Stop rec.

STC Data available in MEM

Verify connect. P1

Error in data download from SOLAR-02

SOLAR-02 not detected. Stop Rec.?

MPP300 not detected

SOLAR-02 not detected.

MPP300: negative AC power

MPP300: inverted AC and DC voltages

No power supply to MPP. Continue? Enter/Esc

C1 C2 not connected

C1 C2 not connected or fuse blown

Fuse blown

Incorrect language version

C1/C2: neg. voltage.

Check the voltage between C1 and C2 input terminals

DC output voltage from module/string > 1000V (I-V400w, SOLAR I-Vw)

Irradiance value lower than threshold limit

Internal NTC damaged. Contact service dpt

Instrument overheated. Wait before starting the tests again

Internal memory full. Download data to PC

Anomalous condition. Repeat test with more modules

Measured current lower than the minimum detectable

Check the voltage between C1 and C2 input terminals

Check the polarity of input terminals

The number of modules defined is > 30

The meter does not calculate the date at STC conditions

Irradiance value higher than the maximum range

Generic error. Repeat the test

Output current higher than maximum range

Set a correct date/hour on meter

Contact service dpt

Contact service dpt

Contact service dpt

Contact service dpt

Low battery indication. Fit new batteries inside meter

Check the settings of module inside DB

Check the settings of module inside DB

Check the settings of module inside DB

Check the settings of module inside DB

Check the settings of module inside DB

Check the settings of module inside DB

Check the settings of module inside DB

Name of module just used inside DB

Unstable condition on irradiance. Repeat the test

Anomalous condition. Repeat test with more modules

Difference between 2 consec. Instant. values of current is > 0.13A

Problem with internal FW. Contact service dpt

Temperature measured by reference cell is too high

Temperature of module over maximum range

Voc measured not compliance with the set number of modules

(check also the Voc and Beta parameters values in the module’s data sheet)

Measure on the cell of module not performed

Problem with the access to internal memory

Contact service dpt

Contact service dpt

Contact service dpt

Recording corrected downloaded on the instrument

Corrected RF connection with remote unit SOLAR-02

Download data from SOLAR-02 and wait for response

Problem on downloaded data from SOLAR-02. Verify settings

Output current lower that the minimum measurable

Contact service dpt

Unit SOLAR-02 do not RF connected to the instrument

Unit SOLAR-02 in recording parameters Irr/Temp

Stop the recording to obtain STC data

Data STC condition save on memory

Check the proper insertion of test cable in the input P1

SOLAR I-Vw/SOLAR I-Ve used with MPP300. Download error from SOLAR-02.

SOLAR I-Vw or SOLAR I-Ve used with MPP300. SOLAR-02 not detected when stop Rec.

SOLAR I-Vw or SOLAR I-Ve set for use together with MPP300. MPP300 not detected

SOLAR I-Vw or SOLAR I-Ve set for use together with MPP300. SOLAR-02 not detected.

MPP300 has detected negative AC powers.

MPP300 has detected inverted AC and DC voltages

MPP300 has not detected the presence of the external power supply.

Check the connections of the instrument to module/string on test

Check the connections of the instrument and repeat the test. If there is problem again contact service dpt

Update the language file of the instrument

Check the polarity of the connections

EN - 54

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

7. STORING DATA

The meter allows storing 99 results of PV checks (only SOLAR I-Vw or SOLAR I-Ve) and

249 tests of I-V curve in its internal memory. In the PV check operation it’s also possible to save the instantaneous values at display. The saved data can be recalled at display and deleted in each moment, and can be associated (for I-V curve test) to reference numerical markers relevant to the installation name, the PV string and the PV module (max 255 markers).

7.1. SAVING TEST RESULTS OF PV CHECKS (SOLAR I-VW OR SOLAR I-VE)

1. Press SAVE key with a measured result shown at display or for saving the instantaneous values. The right screen with a virtual keyboard is displayed by the meter

2. Use the arrow keys (,) and ( , ) to fit a short description (max 12 chars) relative to the PV check

3. Press SAVE key to store the result of test or ESC/MENU key to exit without saving

15/05/10 15:34:26

P R p

I r r

P n o m

T c

0 . 8 5 1

8 2 7

W / m 2

3 . 5 0 0 k W

4 5

° C

T e

3 0

° C

K E Y B O A R D

A B C D E F G H I

A B C D E F G H I J K L M N O P

Q R S T U V W X Y Z - + 0 1 2 3

4 5 6 7 8 9 S P A C E D E L

SAVE for store data

7.2. SAVING TEST RESULTS OF I-V CURVE TEST

1. Press SAVE key with a measured result shown at display.

The following screen is displayed where the herewith items are shown:

 The first memory location available (“Measurement”)

 The numerical marker “Installation”

 The numerical marker “String”

 The numerical marker “Module”

 The field “Comment” where the operator can include a short description (max 14 char) by using virtual keyboard

15/05/10 15:34:26

M e a s u r e m e n t : 0 0 7

I n s t a l l a t i o n :

0 1 0

S t r i n g : 0 0 9

M o d u l e : 0 0 4

C o m m e n t :

K E Y B O A R D

A B C D E F G H I

A B C D E F G H I J K L M N O P

Q R S T U V W X Y Z - + 0 1 2 3

4 5 6 7 8 9 S P A C E D E L

SAVE for store data

C o m m e n t

MEM – IV

2. Use the arrow keys (,) to select the items and (,) to set the numeric value of the markers and to use the virtual keyboard. “Comments” field modifications are possible only by changing the number of the “Installation” marker inserting one among the available markers

3. Press ENTER to digit any character of the desired name

4. Press SAVE key to store the result of test or ESC/MENU key to exit without saving.

EN - 55

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

7.3. MANAGING THE RESULTS

7.3.1. Recall data of PV checks at display (SOLAR I-Vw or SOLAR I-Ve)

1. Press ESC/MENU key to back to the main menu, select the “MEM” item and confirm with ENTER to access inside the section od saved data

2. Using arrows keys (,) and the arrow key  select the

15/05/10 15:34:26

MEM TYPE

001 IST 08/04/2010 item “Recall”, the item “Yield Test and confirm with

ENTER

for the visualization of PV checks results only

3. Using arrow key  the herewith labels can be displayed:

TYPE  means the type of saved data: “REC” for a complete PV check, “*REC” when the values of

Y i e l d T e s t

V i e

I - V T e s t

R e c a l l

D e l e t e

 irradiance/temperature measured by SOLAR-02 are not available for the meter and “IST” for the saving of

Select

MEM - EFF instantaneous values at display

DATA  means the date/hour od saved data on meter

Comments  means the description gives by the user during the data saved operation

4. Select the “IST” data, the item “View” and confirm with

ENTER

. The herewith screen is displayed:

5. Press the arrow keys (,) to access to the two available screens

6. Press ESC/MENU to back to previous screen

7. Select the “REC” data, the item “View” and confirm with

ENTER

. The herewith screen is displayed:

15/05/10 15:35:00

P d c 3 . 1 2 5

V d c 3 8 9 V

I d c 8 . 0 1 n d c 0 . 8 8

P a c 3 . 0 1 2

V

A

Select

A n a l y s i s r e s u l t s

E F F

8. Press the arrow keys (,) to access to the two available screens

9. The final values of PV check relative to the maximum efficiency condition detected are displayed

10. Press ESC/MENU to back to previous screen

11. Selecting the “*REC” data, the item “View” and confirm with ENTER the message “Unable to execute analysis” is displayed due to the missed of irradiance/temperature

15/05/10 15:35:00

 k W

V

A n d c 0 . 8 8

P a c 3 . 0 1 2

V a c 2 3 1

A n a c 0 . 9 6 values recorded by SOLAR-02. The partial values of

Select

this measurement are only visible after downloading the data onto PC

(see § 8)

E F F

EN - 56

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

7.3.2. Recall data of I-V curve tests at display

1. Press ESC/MENU key to back to the main menu, select the “MEM” item and confirm with ENTER to access inside the section od saved data

2. Using arrows keys (,) and the arrow key  select the

15/05/10 15:34:26

MEM DATA

001

002

08/04/2010 10:38

13/04/2010 12:15 item “Recall”, the item “I-V Test and confirm with ENTER for the visualization of I-C curve results only

3. The “DATA” label means the date/hour od saved data on meter

T e s t

V i e

I - V T e s t

R e c a l l

D e l e t e

Select MEM I - V

4. Use arrow key  to select the “Comments” label 15/05/10

15:34:26

MODULE # 1

MODULE # 2

5. The description gives by the user during the data saved operation (see § 7.2) is displayed

MEM Comments

6. The symbol “*” near the number of measure means that

001 the meter have performed the I-V curve test with recording of irradiance/temperature values by use of remote unit

002*

SOLAR-02, but this values did not transferred or are not available. For this measurements the translated STC

values won’t be available

Select

7. By means of the arrow key , select the “parameters” label.

8. The markers relevant to Installation, String and Module selected by the user during the saving procedure (§ 7.2) are shown on the display.

9. Press ESC/MENU to exit the screen and to go back to the

15/05/10

15:34:26

001

002

0 0 1 0 0 1 0 0 1

0 0 1 0 0 1 0 0 2 main menu.

MEM I - V

Select

MEM – IV

EN - 57

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

7.3.2.1. View data – Numerical screens

1. Select a row corresponding to a saved result and press 15/05/10 15:34:26

ENTER

to access the § for the display of stored data. The herewith screen shows a list of saved tests.

001 001 001 001

2. Select the “View” item and press ENTER to open the section of data visualization in the herewith modes:

002 001

 Numeric screens of parameters measured at the STC conditions and at the operative conditions (OPC)

 Graphic screens relative to the I-V curves saved at STC and OPC conditions

V i e w

D e l e t e

Select

MEM – IV

3. The first screen shows the values of measured parameters, referred to 1 module, translated to the

V o c 4 8 . 0 V standard conditions (STC) according to § 6.2.3

4. Press arrow key , select by means of arrow keys (,)

V m p p 3 9 . 8 the option “OPC – Avg” and press ENTER.

A

A

P m a x W

%

D P m a x S T C

O P C – A v g

D a t a O P C

I - V G r a p h

P W R G r a p h

- O K

Select

I – V

5. The meter shows the values measured on a string at the real operating conditions (OPC). The values are averaged

on a single module

(corresponding to the total values should the string be made of a single module).

6. Press arrow key  in the first screen, select the option

OPC” by means of arrow keys (,) and press ENTER.

15/05/10 15:34:26

V o c

4 . 8 5

I s c

P m a x 1 8 9

F F

9 2 7

T c

R e s u l t s @ O P C – A v g

Select

I – V

7. The meter shows the total values measured at the real operating conditions (OPC) relative to the string under

test.

8. Press ESC/MENU key to exit and go back to the previous screen.

15/05/10 15:34:26

V o c

5 . 2 2

W

0 . 7 7

I r r

T c

R e s u l t s @ O P C

Select

I – V

EN - 58

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

7.3.2.2. View data – Graphic screens of I-V curve

1. With screen of numerical values relative to standard

15/05/10 15:34:26 conditions (STC) select the item “I-V Graph” by means of arrow key  and press ENTER or the arrow key .

2. Select the “STC” option and press ENTER.

3. The herewith screen is shown by the meter.

V o c 4 8 . 0 V

V

I m p p 5 . 2 4

A

I s c

A

P m a x 2 0 8

W

F F

D P m a x

D a t a

S T C

0 . 7 8

O P C – A v g

O P C

I - V G r a p h

P W R G r a p h  - O K

Select

I – V

%

4. The graph is the I-V curve relative to the object under test translated to the standard conditions (STC) and referred to 1 module.

5. Press ESC/MENU key to exit the screen and to go back to the memory section.

15/05/10 15:34:26

I - V G r a p h @ S T C – O K

Select

I – V

6. With screen of numerical values measured by meter

15/05/10 15:34:26 select the item “I-V Graph” by means of arrow key  and press ENTER or the arrow key .

7. Select the option “OPC – Avg” and press ENTER. The I-

V curve graph of a string measured at the real operative conditions (OPC) and displayed by the meter is averaged

on a single module

.

8. Press ESC/MENU key to exit the screen and to go back to the memory section

I - V G r a p h @ O P C - A v g

Select

I – V

9. With screen of numerical values measured by meter

15/05/10 15:34:26 select the item “IV Graph” by means of arrow key  and press ENTER or the arrow key .

10. Select the option “OPC” and press ENTER. The I-V curve graph measured at the real operative conditions (OPC) and displayed by the meter corresponds to the total

value relative to the string under test.

11. Press ESC/MENU key to exit from screen and back to the memory §

I - V G r a p h @ O P C

Select

I – V

EN - 59

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

7.3.2.3. View data – Graphic screens of power

1. With screen of numerical values measured by the meter select the item “PWR Graph” by means of arrow key  and press ENTER or the arrow key .

2. Select the option “STC” and press ENTER.

3. The herewith screen is shown by the meter.

15/05/10 15:34:26

V o c 4 8 . 0 V

V

I m p p 5 . 2 4

A

I s c

A

P m a x 2 0 8

W

F F

D P m a x

D a t a S T C

0 . 7 8

%

0 . 5

%

I - V G O P V – A v g

P W R O P C

Select

4. The graph shows values of output power from module/string translated to the standard conditions (STC).

15/05/10 15:34:26

5. Press ESC/MENU key to exit the screen and to go back to the memory §.

I – V

P W R G r a p h @ S T C – O K

Select

I – V

6. With screen of numerical values measured by meter,

15/05/10 15:34:26 select the item “PWR Graph” by means of arrow key  and press ENTER or the arrow key .

7. Select the option “OPC – Avg” and press ENTER. The meter shows the graph of output power from a single

module of a string

measured at the real operative conditions (OPC).

8. Press ESC/MENU key to exit the screen and to go back to the memory §.

P W R G r a p h @ O P C - A v g

Select

I – V

9. With screen of numerical values measured by the meter select the item “PWR Graph ” by means of arrow key  and press ENTER or the arrow key .

15/05/10 15:34:26

10. Select the option “OPC” and press ENTER. The meter shows the graph of total output power relevant to the

string under test

measured at the real operative conditions (OPC).

11. Press ESC/MENU key to exit the screen and to go back to the memory §.

P W R G r a p h @ O P C

Select

I – V

EN - 60

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

1. Press ENTER key in the memory § to show the submenu

2. Select the “Delete” item and press the arrow key . The options below are shown by the meter:

Del. Last  delete the last measurement saved

Del. All  delete all data in the memory

3. Select the desired option with arrow keys (,) and

15/05/10 15:34:26

MEM DATA

001

1 5 / 0 5 / 1 0

1 2 : 3 2 confirm with ENTER

4. Press ESC/MENU to exit the screen and go back to main menu

V i e w D e l . L a s t

D e l e t e

D e l . A l l

Select

MEM – IV

EN - 61

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

8. CONNECTING THE INSTRUMENT TO A PC

8.1. CONNECTING BY OPTICAL/USB CABLE C2006

CAUTION

 The connection between instrument and PC is realized by means C2006 cable.

 In order to transfer the data onto a PC it is necessary to install the management software Topview in advance and the drivers of cable C2006 on the PC itself.

 Before connecting, it is necessary to select the port to be used and the right baud rate (57600 bps) on the PC. To set these parameters, start the

TopView

software and refer to the program's on-line help.

 The selected port must not be engaged by other devices or applications, e.g. a mouse, a modem, etc.

 Optical port emits invisible LED radiations. Do not bring the beam at eye level. Class 1M LED apparatus according to IEC/EN 60825-1

To transfer the saved data to the PC, keep to the following procedure:

1. Switch on the instrument by pressing ON/OFF key

2. Connect the instrument to the PC via the provided optical/USB cable C2006.

3. Press ESC/MENU key to open the main menu.

4. By means of arrow keys (,) select the item “PC Connection” to access the PC mode section and confirm with ENTER

15/05/10 15:34:26

I - V

I-V Test

EFF Yield Test

SET

Settings

DB

Modules

MEM

Data Recall

PC

PC Connection

E N T E R t o s e l e c t .

M E N U

5. The below screen is displayed by the meter:

15/05/10 15:34:26

PC – RS232

WiFI ON

M E N U

6. Use data management software TopView to transfer the content of the instrument memory to the PC (see on-line help of this software for all details)

EN - 62

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

8.2. CONNECTING BY WIFI

CAUTION

 The connection between instrument and PC is realized by means of WiFi interface which is normally active on the instrument. The WiFi function is not available if in the initial screen of the instrument (see § 4.4) the “WiFi-OFF” message is displayed

 In order to transfer the data onto a PC it is necessary to install the management software Topview in advance, and WiFi interface shall be available on the PC itself

 Before connecting it is necessary to enable WiFi connection on the instrument as below mentioned, and select/connect the “wireless network”

(WiFi) which the instrument makes available

 Before connecting, it is necessary to select the “WiFi” port on the “PC

Instrument Connection” of TopView software and refer to the program online help.

To transfer the saved data to the PC, keep to the following procedure:

1. Switch on the instrument by pressing ON/OFF key

2. Press ESC/MENU key to open the main menu.

3. By means of arrow keys (,) select “PC Connection” to access the PC mode section and confirm by ENTER

15/05/10 15:34:26

I - V

I-V Test

EFF Yield Test

SET

Settings

DB

Modules

MEM

Data Recall

PC

PC Connection

E N T E R t o s e l e c t .

M E N U

4. The below screen is displayed by the meter:

15/05/10 15:34:26

PC – RS232

WiFI ON

M E N U

5. Enable the WiFi connection on the PC (if necessary, it is possible to use a WiFi adaptor). Select and connect the WiFi network which the instrument makes available in

“Network connection  Wireless networks” section

6. Use data management software TopView to transfer the content of the instrument memory to the PC (see software on-line help for all details)

EN - 63

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

9. MAINTENANCE

9.1. GENERAL

The instrument you purchased is a precision instrument. When using and storing it, please observe the recommendations listed in this manual in order to prevent any possible damage or danger. Do not use the instrument in environments with high humidity levels or high temperatures. Do not directly expose it to sunlight. Always switch off the instrument after using it. Should the instrument remain unused for a long time, remove batteries in order to prevent liquids from leaking out of them, and the instrument internal circuits from being damaged.

9.2. BATTERY REPLACEMENT

When the low battery symbol “ ” appears on the LCD display, or if during a test the meter gives the message “low battery”, it is necessary to replace the batteries.

CAUTION

This operation must be carried out by skilled technicians only. Before carrying out this operation, make sure that all cables have been removed from the input leads.

1. Swicth off the instrument by pressing and holding the ON/OFF key.

2. Remove the cables from the input leads.

3. Unscrew the cover fastening screw from the battery compartment and remove it.

4. Remove all the batteries from the battery compartment and replace with new batteries of the same type only (§ 10.4) making sure to respect the indicated polarities.

5. Restore the battery compartment cover into place and fasten it by means of the relevant screw.

6. Do not dispose of the used batteries into the environment. Use relevant containers for disposal.

9.3. INSTRUMENT CLEANING

Use a dry and soft cloth to clean the instrument. Never use wet cloths, solvents, water, etc.

9.4. END OF LIFE

CAUTION

: this symbol indicates that the equipment, the batteries and its accessories must be collected separately and disposed of in the right way.

EN - 64

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

10. TECHNICAL SPECIFICATIONS

10.1. YIELD TEST TECHNICAL FERATURES (SOLAR I-VW, SOLAR I-VE)

Accuracy is calculated as [%reading+(number of dgt) * resolution] at 23°C ± 5°C, <80%HR

VDC Voltage (SOLAR I-Vw)

Range [V]

15.0

 999.9

VDC Voltage (SOLAR I-Ve)

Resolution [V]

0.1

Accuracy

(0.5rdg + 2dgt)

Range [V]

15.0

 99.9

100.0

 1499.0

AC TRMS Voltage

Resolution [V]

0.1

0.3

Range [V]

50.0

 265.0

Max crest factor: 1.5

Resolution [V]

DC Current (by external transducer clamp)

0.1

Accuracy

(0.5rdg + 2dgt)

Accuracy

(0.5rdg + 2dgt)

Range [mV]

-1100

 -5

5

 1100

Resolution [mV]

0.1

Accuracy

(0.5rdg + 0.6mV)

The value of current is ALWAYS displayed with positive sign ; The value of current transduced in voltage less then 5mV is zeroed

AC TRMS Current (by external transducer clamp)

Range [mV]

1

 1200

Resolution [mV]

0.1

Max crest factor: 2.0 ; The value of current transduced in voltage less then 5mV is zeroed

Accuracy

(0.5rdg + 0.6mV)

FS DC and AC clamp [A] Resolution [A]

Minimum read value [A]

DC AC

1< FS

 10

10< FS

 100

100< FS

 1000

DC Power (Vmis > 150V) (SOLAR I-Vw)

Accuracy FS clamp [A]

1< FS

 10

10< FS

 100

Range [W]

0.000k

 9.999k

10.00k

 99.99k

0.000k

 9.999k

10.00k

 99.99k

100< FS

 1000

0.00k

 99.99k

100.0k

 999.9k

Vmis = voltage at which power is measured ; Imis = measured current

Resolution [W]

0.001k

0.01k

0.001k

0.01k

0.01k

0.1k

DC Power (Vmis > 150V) (SOLAR I-Ve)

FS clamp [A]

1< FS

 10

10< FS

100< FS

 100

 1000

Range [W]

0.000k

 9.999k

10.00k

 99.99k

0.000k

 9.999k

10.00k

 99.99k

100.0k

 999.9k

0.00k

 99.99k

100.0k

 999.9k

1000k

 9999k

Resolution [W]

Vmis = voltage at which power is measured ; Imis = measured current

0.001k

0.01k

0.001k

0.01k

0.1k

0.01k

0.1k

1k

(0.7rdg + 3dgt)

(Imis < 10%FS)

(0.7rdg)

(Imis

 10%FS)

Accuracy

(0.7rdg + 3dgt)

(Imis < 10%FS)

(0.7rdg)

(Imis

 10%FS)

EN - 65

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

AC Power (Vmis > 200V, PF=1) (SOLAR I-Vw)

FS clamp [A]

1< FS

 10

10< FS

 100

Range [W]

0.000k

 9.999k

10.00k

 99.99k

0.000k

 9.999k

10.00k

 99.99k

Resolution [W]

100< FS

 1000

0.00k

 99.99k

100.0k

 999.9k

Vmis = voltage at which power is measured ; Imis = measured current

0.001k

0.01k

0.001k

0.01k

0.01k

0.1k

AC Power (Vmis > 200V, PF=1) (SOLAR I-Ve)

FS clamp [A]

1< FS

 10

10< FS

 100

Range [W]

0.000k

 9.999k

10.00k

 99.99k

0.000k

 9.999k

10.00k

 99.99k

100.0k

 999.9k

Resolution [W]

100< FS

 1000

0.00k

 99.99k

100.0k

 999.9k

1000k

 9999k

Vmis = voltage at which power is measured ; Imis = measured current

0.001k

0.01k

0.001k

0.01k

0.1k

0.01k

0.1k

1k

Frequency

Range [Hz]

47.5

 63.0

Resolution [Hz]

0.1

Irradiance (with reference reference cell)

Range [mV]

1.0

 65.0

Temperature (with auxiliary probe)

Range [°C]

-20.0

 100.0

Resolution [mV]

0.1

Resolution [°C]

0.1

Accuracy

(0.7rdg + 3dgt)

(Imis < 10%FS)

(0.7rdg)

(Imis

 10%FS)

Accuracy

(0.7rdg + 3dgt)

(Imis < 10%FS)

(0.7rdg)

(Imis

 10%FS)

Accuracy

(0.2rdg + 1dgt)

Accuracy

(1.0rdg + 5dgt)

Accuracy

(1.0rdg + 1°C)

EN - 66

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

10.2. I-V TEST TECHNICAL FEATURES (I-V AND IVCK)

I-V, IVCK: DC Voltage @ OPC (SOLAR I-Vw, I-V400w)

Range [V] (*)

5.0

 999.9

Resolution [V]

0.1

(*) The I-V curve measurement start for VDC > 15V and the accuracy is defined for VDC > 20V

I-V, IVCK: DC Voltage @ OPC (SOLAR I-Ve, I-V500w)

Range [V] (*)

15.0

 99.9

Resolution [V]

0.1

100.0

 1499.9

0.3

(*) The I-V curve measurement start for VDC > 15V and the accuracy is defined for VDC > 20V

I-V: DC Current @ OPC

Uncertainty (*)

(1.0rdg + 2dgt)

Uncertainty (*)

(0.5rdg + 2dgt)

Range [A]

0.10

 15.00

Resolution [A]

0.01

Uncertainty

(1.0rdg + 2dgt)

(*) Maximum current = 15A for Voc ≤ 1000V, Maximum current = 10A for Voc > 1000V (I-V500w and SOLAR I-Ve)

I-V: DC Power @ OPC (Vmpp > 30V, Impp > 2A)

Range [W] (*)

50

 99999

Resolution [W]

1

Uncertainty

(1.0rdg + 6dgt)

Vmpp = Maximum power voltage, Impp = Maximum Power Current

(*) The value of max measured power is relative to a max FF value of approx. 0.7  Pmax= 1000V x 15A x 0.7 = 10500W

 Pmax= 1500V x 10A x 0.7 = 10500W

I-V, IVCK: DC Voltage @ STC

Uncertainty (*,**)

4.0rdg + 2dgt)

Range [V]

5.0

 999.9

I-V: DC Current @ STC

Resolution [V]

0.1

Range [A]

0.10

 99.00

Resolution [A]

0.01

I-V: DC Power @ STC (Vmpp > 30V, Impp > 2A)

Uncertainty (**)

(4.0 rdg + 2 dgt)

Range [W]

50

 99999

Resolution [W]

1

Global Uncertainty (**)

(5.0 rdg + 1 dgt)

Vmpp = Maximum power voltage, Impp = Maximum Power Current

(*) Measurements of I-V curve start for VDC > 15V and the accuracy is defined for VDC > 20V

(**) Test conditions:

 Test cond.: Steady Irrad.

700W/m

2

, spectrum AM 1.5,solar incidence vs perpendicular.

  25°, Cells Temp. [15..65°C]

 Global accuracy include contribute of solar sensor and its measuring circuit

Irradiance (with reference cell)

Range [mV]

1.0

 100.0

Temperature (with auxiliary probe)

Resolution [mV]

0.1

Accuracy

(1.0rdg + 5dgt)

Range [°C]

-20.0

 100.0

Resolution [°C]

0.1

Accuracy

(1.0rdg + 1°C)

EN - 67

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

10.3. SAFETY SPECIFICATIONS

10.3.1. General

Instrument safety: IEC/EN61010-1

EMC: IEC/EN61326-1

Technical literature: IEC/EN61187

Accessory safety:

Measurements:

IEC / EN61010-031

IEC/EN60891 (I-V curve test)

IEC/EN 60904-5 (Temperature measurement) insulation

Pollution level:

Category of measure:

2

CAT II 1000V DC, CAT III 300V to ground

Max 1000V among inputs P1, P2, C1, C2 (SOLAR I-Vw,

I-V400w)

Max 1500V among inputs P1, P2, C1, C2 (SOLAR I-Ve,

I-V500w)

EN - 68

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

10.4. GENERAL CHARACTERISTICS

Display and memory

Type of display:

Memory capacity:

Saved data:

PC interface:

LCD custom, 128x128 pxl, backlighted

256kbytes

99 yield tests (SOLARI-Vw/I-Ve); 249 I-V, 999IVCK optical/USB and WiFi

RF module specifications

Frequency range:

R&TTE category:

Max transmission power:

Max distance of RF connection

2.400

 2.4835GHz

Class 1

30

W

1m

PV Yield Test (SOLAR I-Vw or SOLAR I-Ve)

Integration period (IP): 5,10,30,60,120,300,600,900,1800,3600s

Memory authonomy SOLAR-02: approx 1.5 hours (@ PI = 5s)

Max distance RF connection: approx 8 days (@ PI = 600s)

1m (3 ft)

Memory of SOLAR-02 - MPP300: approx. 1.5 hours (@ PI = 5s) approx. 8 days (@ PI = 600s)

Power supply

Battery type: 6 x1.5 V alkaline type AA LR06

1W

Low battery indication:

Battery life:

Auto power off: symbol “ “ is displayed approx 120 hours (PV Yield test)

>249 I-V curve test, 999 IVCK test after 5 minutes of idleness

Mechanical data

Dimensions (L x W xH):

Weight (batteries included):

235 x 165 x 75mm ; 9 x 6 x 3in

1.2kg (42 ounces)

10.5. ENVIRONMENT CONDITIONS

Reference temperature:

Working temperature:

Relative humidity allowed:

Storage temperature:

Storage humidity:

Max height of use:

23° ± 5°C (73°F ± 41°F)

0 ÷ 40°C (32°F ÷ 104°F)

<80%RH

-10 ÷ 60°C (14°F ÷ 140°F)

<80%RH

2000m (6562 ft) (*)

CAUTION

(*) Information about the use of meter at altitude from 2000 to 5000m

As for voltage inputs P1, P2, C1, C2 the instrument is to be considered downgraded to overvoltage category CAT I 1000V DC and CAT II 300V to ground, max 1000V among inputs (for SOLAR I-Vw and I-V400w) and max 1500V (for SOLAR I-Ve and I-V500w).

Markings and symbols indicated on the instrument are to be considered valid when using it at altitude lower than 2000m

This instrument complies with the prescriptions of the European directive on low voltage 2014/35/EU (LVD) and EMC 2014/30/EU

This instrument satisfies the requirements of 2011/65/EU (RoHS) directive and

2012/19/EU (WEEE) directive

10.6. ACCESSORIES

See only the standard and optional accessory indicated in the enclosed packing list

EN - 69

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

11. APPENDIX

11.1. TESTING PHOTOVOLTAIC SYSTEMS (SOLAR I-VW, SOLAR I-VE)

According to the requirements of the laws in force, the result of the test depends on settings about Temperature effects compensation and PRp calculations:

Corr.Typ

e

Tcel value PRp calculation

Guidelin e

Tmod

Tcel = PV Module Temp. measured

Tcel = PV module Temp. calculated

Tamb or

Tenv

Tcel

Tamb

NOCT

20

G p

800

PRp

Rfv

2

P ca

G p

G

STC

P n

CEI

82-25

(Italian

Guideline)

nDC

Tcel = PV Module Temp. measured

PRp

G

STC

G p

 

1

100

T cel

25

P ca

P n

- - - where:

G p

Irradiance on PV module surface

W/m

2

G

STC

Standard Irradiance = 1000

2

W/m

 

P n

Nominal Power = sum of all power module (Pmax ) included in the part of PV plant under test

AC Active Power measured

P ca

Rfv

2



1

1 (Tcel 40)

100

(if

(if

Tcel

Tcel

40

C)

40

C)

Thermal Corrective factor

Absolute value of Pmax thermal coefficient

%/

C

NOCT Normal Operating Cell Temperature (@ 800W/m

2

, 20°C,

AM=1.5, vel. Aria =1m/s).

%/

C

Previous relationship are valid if Irradiance > Min Irraddiance value and the Irradiance values are “steady”: if IP

1min (Irr max – Irr min) < 20W/m

2

The final OUTCOME can be:

Non-displayable: if the obtained values are inconsistent (e.g. PRp >1.15) or if irradiation has never reached a steady value > minimum threshold set.

 The maximum performance point (PRp) of the system

The highest performance (maximum value of PRp) is detected according with previous relationships.

EN - 70

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

11.2. NOTES ON MPPT (MAXIMUM POWER POINT TRACKER)

Solar irradiation on a surface such as the surface of a photovoltaic system has extremely variable characteristics, since it depends on the position of the sun with respect to the surface and on atmospheric conditions (typically, on the presence of clouds). A photovoltaic module presents, for different solar irradiation values, and for different temperature values, a range of characteristic curves of the type shown in the following figure. In particular, the figure shows three I-V curves (in bold) which correspond to three values (1000, 800, 600W/m

2

) of solar irradiation.

On each characteristic curve there is one single point in which the power transfer towards a hypothetical charge supplied by the photovoltaic module is maximized. The maximum power point corresponds to the voltage-current pair for which the product V*I is maximum, where V is the value of voltage at the module’s terminals and I is the current which runs in the circuit obtained by closing the module on a hypothetical charge.

With reference to the figure above, the product V*I is represented, for the three solar irradiation values mentioned above, through the three curves in thinner lines.

The figure shows that, as stated above, these curves only have one single maximum point.

For example, for 1000W/m

2

, the maximum power point corresponds to a voltage value of approx. 36V and to a current value of approx. 5.5A.

Obviously, if the power provided by the system is maximized, it is possible to make the most of the system, both in case the system is connected to mains, and in case it is standalone.

MPPT is an inbuilt device in the inverters. It typically reads the voltage and current values at any instant, calculates their product (i.e. the power in Watts) and, by causing small variations in the conversion parameters (duty cycle), it is capable of determining, by comparison, if the photovoltaic module is working in maximum power conditions or not.

According to the result, it operates again on the circuit in order to bring the system to an optimal condition.

EN - 71

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

The reason why MPPTs are used is simple: a photovoltaic system without MPPTs may operate anyway; however, with the same solar irradiation, it provides less energy.

There are inverters with 1, 2 or also 3 inbuilt MPPTs available on the market. Typically, the inverters with more than one MPPT are used in systems where:

- the different photovoltaic systems it consists of “forcibly” have different inclinations or directions. In this way, each single MPPT manages its own photovoltaic field, maximizing its performance for the corresponding irradiation and temperature characteristics (without being influenced by the other photovoltaic fields).

- a greater service continuity is sought. With more MPPTs it is possible to put one single photovoltaic field out of service, while the others continue producing energy towards the remaining MPPTs.

11.3. THEORETICAL ASPECTS OF THE I-V CURVE MEASUREMENT

The I-V curve test is performed as described below:

 The meter performs the I-V curve measurement of the PV module connected to it, further to the real time measurement of irradiance and module temperature

 The results of measurements are automatically “translated” to the standard conditions

(STC) of irradiance at 1000 W/m

2

and module temperature at 25°C. The accuracy indicated in this manual is granted under condition indicated in § 10.2.

 The meter performs a comparison between the maximum nominal power, with the margin of percentage tolerance declared by the module’s manufacturer, which is included in the kind of module selected on the meter from the database (§ 5.3.1), and the measured value

 If the comparison of power is within the declared tolerance, the final response of the meter will be “OK” or will be “NO OK” in the opposite case, and the module will not be complying with the specifications declared by the manufacturer (§ 6.2.3)

EN - 72

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

11.3.1. Typical errors on I-V curves and troubleshooting

Measurement

Good measurement

Event Troubleshooting

 The measured curve extrapolated  No error, save data and to STC (blue) and the curve as declared by the manufacturer

(black) of the modules match. move to next string to test

Low short circuit current

Low open circuit voltage

High short circuit current

 Orient the irradiance sensor differently than the string under test

 sensor properly

 Set the instrument properly

Wrong module selection at configuration of PV system

 Clean the modules

 Remove obstruction

Environmental contaminants on modules (soiling, dirt, snow, debris)

 Far distance obstruction (shading)

 Aging blindness, humidity, etc.

 Replace affected modules

Irradiance sensor oriented differently than the string under test

 Shades on the irradiance sensor

 Orient the irradiance sensor properly

 Clean the irradiance sensor

 Dirt on the irradiance sensor

 configuration of PV system

 Irradiance sensor defect

 Remove obstruction

 Check the irradiance sensor for blindness, humidity, etc.

 Set the instrument properly

 Replace affected sensor

 Low temperature measurement

Wrong numbers of module selection at configuration of PV system

 Shorted bypass diodes

Attach the thermocouple properly to a typical temperature location

 Select the AUTO mode

 Set the instrument properly

 Replace affected modules

Low current ratio Impp/Isc

 Soiling across modules

 Tapered shades

 Small current mismatch

 Degradation of cell shunt resistance

 Clean the modules

 Un-shade the modules

 Check the current match

 Replace affected modules

Low voltage ratio Vmpp/Voc

 Voltage drop on cables to PV module string

 Check cables, connectors, contacts, and string wirings

 Check cable length and cross section

 Check modules for bad connections or oxidation

 Replace affected modules

EN - 73

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

Steps in the I-V curve

 Small or partial shading of one  Remove obstructions module of the string under test

 Reflections

 Random environmental contaminants on modules (soiling, dirt, snow, debris, etc.)

 Strong current mismatch

 Re-test when un-shaded

 Remove reflections

 Clean the modules

 Check the current match

 Replace affected modules

Characteristic curve not linear

 Cracks of cells or glass

 Burn marks

 measurement

 Leopard spot clouds shading the

 Re-test when clouds are gone

 Repeat measurement at an modules

 Low irradiation measurement during irradiation of minimum

700W/m

2

(IEC/EN61829)

EN - 74

I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve

12. SERVICE

12.1. WARRANTY CONDITIONS

This instrument is guaranteed against any defect in material and manufacturing in compliance with the general sales terms and conditions. Throughout the period of guarantee all defective parts may be replaced and the manufacturer reserves the right to repair or replace the product.

If the instrument is to be returned to the after-sales service or to a dealer transportation costs are on the customer’s behalf. Shipment shall be however agreed upon. A report must always be enclosed to a rejected product stating the reasons of its return. To ship the instrument use only the original packaging material; any damage that may be due to nooriginal packing shall be charged to the customer. The manufacturer declines any responsibility for damages caused to persons and/or objects.

Warranty is not applied in the following cases:

 Repair and/or replacement of accessories and battery (not covered by warranty)

 Any repair that might be necessary as a consequence of a misuse of the instrument or of its use with no compatible devices.

 Any repair that might be necessary as a consequence of improper packaging.

 Any repair that might be necessary as a consequence of service actions carried out by unauthorized personnel.

 Any modification of the instrument carried out without the authorization of the manufacturer.

 Use not provided for in the instrument’s specifications or in the instruction manual.

The contents of this manual may not be reproduced in any form whatsoever without the manufacturer’s authorization.

All our products are patented and their trade marks registered. The manufacturer reserves the right to modify the product specifications and prices if this is aimed at technological improvements

.

12.2. SERVICE

If the instrument does not operate properly, before contacting the after-sales service check cables as well as test leads and replace them if necessary. Should the instrument still operate improperly check that the operation procedure is correct and conforms with the instructions given in this manual. If the instrument is to be returned to the after-sales service or to a dealer, transportation costs are on the customer’s behalf. Shipment shall be however agreed upon. A report must always be enclosed to a rejected product stating the reasons of its return. To ship the instrument use only the original packaging material; any damage that may be due to non-original packing shall be charged to the customer.

EN - 75

HT INSTRUMENTS SA

C/ Legalitat, 89

08024 Barcelona - ESP

Tel.: +34 93 408 17 77, Fax: +34 93 408 36 30 eMail: [email protected] eMail: [email protected]

Web: www.htinstruments.es

HT INSTRUMENTS USA LLC

3145 Bordentown Avenue W3

08859 Parlin - NJ - USA

Tel: +1 719 421 9323 eMail: [email protected]

Web: www.ht-instruments.com

HT ITALIA SRL

Via della Boaria, 40

48018 Faenza (RA) - ITA

Tel: +39 0546 621002

Fax: +39 0546 621144 eMail: [email protected]

Web: www.ht-instruments.com

HT INSTRUMENTS GMBH

Am Waldfriedhof 1b

D-41352 Korschenbroich - GER

Tel: +49 (0) 2161 564 581

Fax: + 49 (0) 2161 564 583 eMail: [email protected]

Web: www.ht-instruments.de

HT INSTRUMENTS BRASIL

Rua Aguaçu, 171, bl. Ipê, sala 108

13098321 Campinas SP - BRA

Tel: +55 19 3367.8775

Fax: +55 19 9979.11325 eMail: [email protected]

Web: www.ht-instruments.com.br

HT ITALIA CHINA OFFICE

意大利

HT 中国办事处

Room 3208, 490# Tianhe road, Guangzhou - CHN

地址:广州市天河路

490 号壬丰大厦 3208 室

Tel.: +86 400-882-1983, Fax: +86 (0) 20-38023992 eMail: [email protected]

Web: www.guangzhouht.com

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Key Features

  • Measures irradiance, temperature, and humidity
  • Performs I-V curve measurements
  • Tests PV systems with single or multiple MPPT inverters
  • Generates detailed reports
  • Stores and manages data on your PC

Related manuals

Frequently Answers and Questions

What is the HT SOLAR I-Ve?
The HT SOLAR I-Ve is a powerful and versatile instrument designed for testing and monitoring photovoltaic systems.
What can I do with the HT SOLAR I-Ve?
With the HT SOLAR I-Ve, you can measure irradiance, temperature, and humidity; perform I-V curve measurements; test PV systems with single or multiple MPPT inverters; generate detailed reports; and store and manage data on your PC.
Who is the HT SOLAR I-Ve for?
The HT SOLAR I-Ve is ideal for anyone who needs to test and monitor photovoltaic systems, including solar installers, maintenance technicians, and homeowners.

advertisement

Table of contents