technical guide

Water Source

Heat Pumps

Technical Guide: YK145.00-EG4 (309)

TABLE OF CONTENTS

Water Source Heat Pumps

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

ARI/ISO Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Correction Factors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Blower Performance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

Wiring Diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

2

Johnson Controls

Water Source Heat Pumps

INTRODUCTION

Technical Guide: YK145.00-EG4 (309)

Performance and dependability in a no-nonsense heat pump.

The R-Series units by YORK are completely self-contained heat pumps. This equipment employs a water-torefrigerant heat exchanger to extract (heating cycle) or reject (cooling cycle) heat from/to a circulating water-loop.

The high-quality feature set delivers robust construction and reliable performance that exceeds ASHRAE 90.1 requirements. Available with an insulated refrigerant-circuit, the R-Series is equally suited for water-loop and lowtemperature, geothermal applications.

For commercial installations ranging from schools to multi-story office space, R-Series Water Source Heat Pumps by YORK provide the performance and dependability necessary to suit today’s demanding installation requirements.

Listings / Certifications

PRODUCT OVERVIEW

Refrigerant

R-410A

Sizes

.5 – 6 Tons (1.76 – 21.1 kW)

Model

RSH (Horizontal)

RSV (Vertical)

Johnson Controls

3

Technical Guide: YK145.00-EG4 (309)

SPECIFICATIONS

GENERAL

All R-series models ½ - 6 ton ship as factory-charged packages, complete with R-410A refrigerant. Horizontal

(RSH) units are designed for suspended ceiling mounting. RSH models are shipped with ‘straight-through’ evaporator fan discharge as standard. Fan orientation is field convertible to side discharge.

Vertical (RSV) units are designed for free-standing floor mounting. All units are completely factory wired and pre-piped. Water supply, water outlet, and condensate drain connections are via flush-mounted female pipe thread fittings (no back-up wrench required).

CABINET

All cabinets are completely constructed of corrosion resistant galvanized steel. The RSH units are complete with integral hanger channels. The entire unit interior

(both evaporator and condensing section) is insulated with 1/2 ″ thick, 2 lb density acoustical insulation. Service panels are equipped with lifting handles for ease of removal and handling. All units provide service access to the reversing valve, thermal expansion valve, and compressor with the unit remaining in location. An integral duct collar is provided on the blower discharge opening.

REFRIGERATION CIRCUITS

All models utilize high efficiency rotary, hermetic reciprocating or scroll compressors. Compressors are mounted with rubber isolators on acoustically tuned bases to minimize vibration transmission. Internal overload protection is provided. External high pressure and low pressure cutout switches are included in each compressor control circuit. Each refrigeration circuit includes an adjustable bi-flow thermal expansion valve

(with external equalizer), bi-flow liquid line filter drier, and service gauge ports. The reversing valve is a pilot operated, sliding piston type with a replaceable magnetic solenoid coil.

The refrigerant-to-air heat transfer coils are constructed of internally enhanced copper tubes mechanically bonded to enhanced aluminum plate fins. The evaporator coil is employed in a draw-through configuration.

Large evaporator coil face area minimizes potential water blow-off. A fully-insulated, corrosion resistant condensate drain pan is provided.

• Optional anti-corrosion protective evaporator coil coating.

Water Source Heat Pumps

• Optional stainless steel drain pan.

The coaxial refrigerant-to-water heat exchangers feature a convoluted inner tube design for high heat transfer efficiency. Standard models feature a copper inner tube surrounded by a steel outer tube, and carry a 400 psig water side working pressure rating. Units shall be capable of operation with an entering fluid temperature range of 20°F to 110°F.

• Optional cupro-nickel condenser water coil.

• Optional condenser insulation package for lowwater temperature, geothermal applications.

INDOOR FAN

Forward curved, double inlet and double width, directdrive centrifugal blowers are used for air movement.

Large diameter wheels are employed to provide required airflow performance at minimum noise levels. Blower wheels are fabricated of galvanized steel. Fan motors are PSC type, with minimum three speeds. The PSC motors feature permanently lubricated bearings and internal thermal overload protection.

ELECTRICAL/CONTROLS

All units are completely factory wired with all necessary operating controls. A 24 volt control circuit, with oversized transformer, is provided for field connection. Units are designed to operate with conventional heat pump thermostat control interface. The reversing valve solenoid coil shall be energized in cooling mode only. A manual reset is provided on each compressor control circuit in the event of high/low pressure cutout.

• Optional solid-state electronic condensate overflow switch.

• Optional remote management package allows the unit to be controlled by an external source.

FILTERS

All models are shipped with 1-inch thick throwaway filters, factory installed. Filters are accessible from either side of unit.

FIELD INSTALLED ACCESSORIES

The following options are available field installation:

• 24 ″ braided stainless steel hose kit with fittings.

(qty 2 hoses per kit)

• Manual isolation ball-valves (600 psi full port).

• Thermostat (programmable or non-programmable)

4

Johnson Controls

Water Source Heat Pumps

NOMENCLATURE

Technical Guide: YK145.00-EG4 (309)

WATER SOURCE HEAT PUMP

1,2 3 4,5,6 7 8 9 10 11 12 13 14 15

RS H 018 A 2 E L S A A 0 A

Product Category

RS = Water-Cooled HP R-410A

Miscellaneous Options

A = None

D = Condensate Overflow Switch

Heating Options

0 = None

Product Indentifier

V = Vertical Arrangement (Upflow)

H = Horizontal Arrangment

Nominal Capacity

007 = .5 TON

009 = .75 TON

0 1 2 = 1 T O N

018 = 1.5 TON

024 = 2 TON

030 = 2.5 TON

036 = 3 TON

042 = 3.5 TON

0 4 8 = 4 T O N

0

6

0

=

5 T

O N

0 7 0 = 6 T O N

Design Series

A = C u r r e n t

Waterside Options

A = Std Water coil

B = Insulated Water Coil

N = Cupro-nickel Water Coil

R = Cupro-nickel & Insulation

Airside Options

A = Std Airside coil

C = Corrosion Protective Coating

D = Stainless Steel Drain Pan

F = Coated Coil w/ S-S Drain Pan

Supply Air Options

S = Straight-Thru (Horizontal Only)

B = Back Discharge (Horizontal Only)

T = Top Discharge (Vertical Only)

Voltage

1 = 208/230-60-1

6 = 265-60-1

2 = 208/230-60-3

4 = 460-60-3

5 = 575-60-3

Return Air/Unit Orientation

L = Left Hand

R = Right Hand

Control Options

E = Std Electromechnical Controls

K = Remote Management Relay Kit

Johnson Controls

5

Technical Guide: YK145.00-EG4 (309)

PHYSICAL DATA

Water Source Heat Pumps

Model Series

Nominal Cooling (Ton)

1

Compressor-Type

007

0.5

009

0.75

Rotary

012

1.0

018

1.5

024

2.0

030

2.5

Reciprocating

036

3

042

3.5

048

4

Scroll

060

5

070

6

Air Coil-Type

Face Area(sq ft)

Rows/FPI

1.17

3/13

1.17

3/13

Enhanced Copper tubes, Enhanced Aluminum Fins

1.33

3/15

2.56

3/15

2.88

3/15

2.88

3/15

3.47

3/15

4.44

3/15

4.44

3/15

6.11

3/15

6.11

3/15

Water Coil-Type

Water Connection (in) 1/2 1/2 1/2 3/4

Enhanced Surface Co-Axial

3/4 3/4 3/4 3/4 3/4 1 1

Standard Blower/Motor

Diameter x Width (in)

Motor HP

6x5 6x5

DWDI Forward-Curved Centrifugal / PSC Direct-Drive

6x6 9x7 9x7 10x7T 10x7T 11x8T 11x8T 11x10T 11x10T

0.10/3 0.10/3 0.13/3 0.17/3 0.25/3 0.33/3 0.50/3 0.50/3 0.75/3 1.0/3 1.0/3

RSH Filter

Quantity-Size(in)

1-12x16 1-12x16 1-12x20 1-18x24 1-18x24 1-18x24 2-14x20 2-18x20 2-18x20 2-22x22 2-22x22

RSV Filter

Quantity-Size(in)

1-12x20 1-12x20 1-12x20 1-18x24 1-20x25 1-20x25 1-24x24 2-14x25 2-14x25 2-16x30 2-16x30

RSH Cabinet Weight (lb)

130 135 145 195 210 215 240 310 320

315

370

375

385

390

RSV Cabinet Weight (lb)

120 125 135 185 200 210 230 305

NOTE:

1) Nominal Capacity calculated in accordance with ARI / ISO Standard 13256-1 for Water Loop Application

OPERATING LIMITS*

Min. Entering Water

Max. Entering Water

COOLING

30

110

°

°

F

F

HEATING

20

90

°

°

F

F

*Units are capable of operation with an entering fluid temperature range of 20 ° F to 110 ° F

6

Johnson Controls

Water Source Heat Pumps

ARI/ISO PERFORMANCE DATA

Technical Guide: YK145.00-EG4 (309)

PERFORMANCE DATA - ARI/ISO 13256-1 WATER LOOP CONDITIONS*

Unit Model

Flow Rate

(USGPM)

Air Flow

(SCFM)

Cooling

Capacity (Btuh)

EER

Heating

Capacity (Btuh)

007

009

012

018

024

030

1.8

2.4

3.0

4.8

6.0

7.8

9.0

260

320

400

640

800

1000

1200

6,800

8,900

12,400

19,100

24,600

29,800

36,200

036

042

048

10.4

12.0

1400

1600

42,700

48,300

060

070

15.0

17.5

2000

2200

60,500

67,700

*Water Loop capacities are rated at 86

°

F EWT Cooling, 68

°

F EWT Heating.

12.5

12.4

12.2

13.2

13.5

13.3

13.0

12.7

13.1

13.4

12.9

8,700

11,600

15,600

23,400

29,300

35,300

45,100

50,600

57,200

70,800

79,500

PERFORMANCE DATA - ARI/ISO 13256-1 GROUND WATER CONDITIONS*

Unit Model

007

009

012

018

024

Flow Rate

(USGPM)

1.8

2.4

3.0

4.8

6.0

7.8

Air Flow

(SCFM)

260

320

400

640

800

1000

Cooling

Capacity (Btuh)

7,700

10,100

14,200

22,900

28,700

33,600

EER

030

036

042

048

9.0

10.4

12.0

15.0

1200

1400

1600

2000

39,800

45,800

52,500

66,400

18.8

19.1

19.3

19.8

060

070

17.5

2200 73,600

*Ground Water capacities are rated at 59

°

F EWT Cooling, 50

°

F EWT Heating.

18.7

18.4

18.3

18.1

20.2

20.8

20.0

Heating

Capacity (Btuh)

6,900

9,100

12,900

18,800

23,600

29,100

37,200

42,300

47,400

59,000

66,800

PERFORMANCE DATA - ARI/ISO 13256-1 GROUND LOOP CONDITIONS*

Unit Model

007

009

012

018

Flow Rate

(USGPM)

1.8

2.4

3.0

4.8

6.0

Air Flow

(SCFM)

260

320

400

640

800

Cooling

Capacity (Btuh)

7,100

9,300

13,000

20,600

26,400

024

030

036

042

7.8

9.0

10.4

12.0

1000

1200

1400

1600

31,100

37,500

43,900

49,800

048

060

070

15.0

17.5

2000

2200

62,900

70,100

*Ground Loop capacities are rated at 77

°

F EFT Cooling, 32

°

F EFT Heating.

EER

14.6

14.5

14.3

15.7

16.1

15.3

14.8

14.6

15.0

15.6

14.7

Heating

Capacity (Btuh)

5,500

6,900

10,200

13,900

17,400

22,500

28,600

32,300

37,800

47,200

52,400

NOTE:

1) All Cooling capacities based upon 80.6

°

F DB, 66.2

°

F WB entering air temperature.

2) All Heating capacities based upon 68

°

F DB, 59

°

F WB entering air temperature.

COP

3.9

3.8

3.6

3.9

3.8

3.8

3.9

3.9

3.8

4.0

3.8

COP

3.3

3.3

3.4

3.3

3.4

3.3

3.1

3.4

3.3

3.5

3.3

COP

4.5

4.4

4.2

4.5

4.4

4.5

4.6

4.4

4.5

4.6

4.3

Johnson Controls

7

Technical Guide: YK145.00-EG4 (309)

PERFORMANCE DATA

Water Source Heat Pumps

RS*007 — 320 CFM

20

30

40

50

60

70

80

90

1.0

1.4

1.8

1.0

1.4

1.8

1.0

1.4

1.8

1.0

1.4

1.8

1.0

1.4

1.8

1.0

1.4

1.8

1.8

1.0

1.4

1.8

WPD

3.3

4.3

6.5

3.0

3.9

6.0

4.3

5.6

8.5

3.8

4.9

7.5

2.6

3.5

5.3

2.3

3.1

4.7

FT

11.0

4.9

6.4

9.8

6.8

6.9

7.0

6.4

6.5

6.6

7.4

7.6

7.7

7.0

7.2

7.3

8.5

8.7

8.8

8.1

8.3

8.4

7.7

7.8

8.0

SC

5.3

5.3

5.3

5.1

5.1

5.2

5.4

5.5

5.6

5.2

5.3

5.3

6.0

6.1

6.1

5.8

5.9

6.0

5.5

5.6

5.7

COOLING kW

0.56

0.54

0.53

0.65

0.63

0.60

0.44

0.42

0.42

0.50

0.48

0.47

0.30

0.28

0.26

0.34

0.32

0.31

0.36

0.35

0.34

HR

17.0

17.9

18.4

14.0

15.1

15.6

24.1

25.9

26.8

21.5

22.6

23.4

12.2

12.7

13.1

9.9

10.4

11.0

EER HTG

4.1

28.0

30.8

33.7

5.0

5.3

5.4

9.5

9.9

10.3

10.7

11.0

11.2

7.5

7.7

8.2

8.4

8.8

9.0

5.5

5.7

5.9

6.4

6.6

6.9

8.7

8.8

8.8

8.6

8.6

8.6

8.9

9.0

9.1

8.7

8.8

8.9

9.5

9.7

9.7

9.2

9.4

9.5

8.9

9.0

9.2

HEATING

EWT (F) GPM

1.4

1.8

2.8

1.3

1.7

2.6

1.8

2.4

3.7

1.6

2.1

3.3

1.1

1.5

2.3

1.0

1.3

2.0

PSI

4.8

2.1

2.8

4.2

TC

100

1.0

1.4

1.8

1.0

0.9

1.2

1.8

0.8

2.1

2.7

4.2

1.9

5.9

6.1

6.2

5.4

4.9

5.1

5.1

4.6

0.71

0.69

0.67

0.77

0.7

0.7

0.7

0.8

8.3

8.9

9.2

7.0

110

1.4

1.8

1.1

1.6

2.4

3.7

5.6

5.7

4.7

4.7

0.75

0.73

0.8

0.7

7.5

7.8

Cooling Performance is tabulated at 80.6 F DB and 66.2 F WB entering air. Heating performance tabulated at 68 F EAT

Tabulated data does not include ARI/ISO corrections for fan and pump power.

All capacities are expressed in MBH.

Insulated water circuit is recommended for operation below 60F EWT.

See performance correction tables for conditions beyond what is listed.

Extrapolation is not permissible.

Shaded areas indicate conditions where operation is not recommended.

0.51

0.52

0.54

0.57

0.59

0.59

0.47

0.47

0.48

0.50

0.50

0.52

0.60

0.61

0.63

0.65

0.66

0.66

kW

0.44

0.45

0.47

0.47

5.8

5.9

6.3

6.4

6.8

7.0

3.9

4.1

4.3

4.7

4.9

5.1

7.5

7.8

8.1

8.5

8.8

8.9

HE LAT (F) COP

2.6

80 2.7

3.5

3.7

3.8

82

83

84

3.3

3.3

3.4

95

97

98

99

100

100

90

90

92

92

93

94

84

84

85

87

87

88

4.7

4.7

4.8

4.8

4.9

4.9

4.3

4.4

4.4

4.3

4.4

4.5

3.4

3.5

3.6

3.8

3.9

3.9

8

Johnson Controls

Water Source Heat Pumps

PERFORMANCE DATA

Technical Guide: YK145.00-EG4 (309)

RS*009 — 320 CFM

20

30

40

50

60

70

80

90

1.2

1.8

2.4

1.2

1.8

2.4

1.2

1.8

2.4

1.2

1.8

2.4

1.2

1.8

2.4

1.2

1.8

2.4

2.4

1.2

1.8

2.4

WPD

4.0

6.4

9.3

3.7

5.9

8.5

5.2

8.3

12.1

4.6

7.4

10.7

3.2

5.2

7.5

2.9

4.6

6.7

FT

16.1

6.0

9.6

13.9

8.6

8.9

9.2

8.0

8.2

8.4

9.6

9.9

10.1

9.3

9.5

9.7

12.8

13.1

13.2

12.5

12.7

12.9

10.0

10.4

10.6

SC

6.6

6.8

7.0

6.3

6.4

6.6

7.1

7.2

7.3

6.9

7.0

7.1

9.0

9.1

9.1

8.9

9.0

9.2

7.2

7.4

7.5

COOLING kW

0.69

0.66

0.66

0.74

0.70

0.69

0.57

0.56

0.55

0.65

0.60

0.58

0.47

0.43

0.40

0.54

0.51

0.48

0.52

0.48

0.46

HR

16.7

17.8

18.2

14.4

15.8

16.7

23.0

24.8

26.6

19.2

21.7

23.2

12.5

13.4

14.0

10.8

11.7

12.2

EER HTG

5.6

27.4

30.6

33.0

6.1

6.6

6.8

11.8

12.7

13.3

13.4

14.4

14.7

9.5

10.1

10.6

10.2

11.1

11.8

7.0

7.3

7.6

8.3

8.7

9.1

10.9

11.2

11.4

10.5

10.6

10.7

11.6

11.8

12.0

11.5

11.6

11.7

14.4

14.6

14.6

14.4

14.4

14.6

11.8

12.0

12.2

HEATING

EWT (F) GPM

1.7

2.8

4.0

1.6

2.6

3.7

2.3

3.6

5.2

2.0

3.2

4.6

1.4

2.2

3.3

1.2

2.0

2.9

PSI

7.0

2.6

4.1

6.0

TC

100

1.2

1.8

2.4

1.2

1.1

1.8

2.6

1.0

2.6

4.1

5.9

2.3

7.4

7.6

7.8

8.4

6.2

6.3

6.4

7.1

0.80

0.77

0.76

1.08

10.1

10.2

10.4

12.1

9.2

9.9

10.3

7.8

110

1.8

2.4

1.6

2.3

3.7

5.3

8.7

8.9

7.3

7.4

1.04

1.01

12.2

12.4

8.4

8.8

Cooling Performance is tabulated at 80.6 F DB and 66.2 F WB entering air. Heating performance tabulated at 68 F EAT

Tabulated data does not include ARI/ISO corrections for fan and pump power.

All capacities are expressed in MBH.

Insulated water circuit is recommended for operation below 60F EWT.

See performance correction tables for conditions beyond what is listed.

Extrapolation is not permissible.

Shaded areas indicate conditions where operation is not recommended.

0.71

0.74

0.76

0.71

0.76

0.77

0.62

0.63

0.65

0.68

0.69

0.70

0.77

0.79

0.81

0.80

0.83

0.84

kW

0.57

0.74

0.72

0.62

7.1

7.6

8.0

7.8

8.5

9.2

4.9

5.2

5.4

6.0

6.3

6.7

9.2

10.0

10.5

10.7

11.6

11.8

HE LAT (F) COP

3.7

84 2.9

3.6

4.2

4.7

86

87

88

2.4

2.7

3.2

88

89

90

92

93

94

95

97

99

98

100

102

102

105

106

107

110

111

4.5

4.7

4.8

4.9

5.1

5.1

3.9

4.0

4.1

4.2

4.3

4.5

3.3

3.4

3.4

3.6

3.7

3.8

Johnson Controls

9

Technical Guide: YK145.00-EG4 (309)

PERFORMANCE DATA

Water Source Heat Pumps

RS*012 — 400 CFM

20

30

40

50

60

70

80

90

1.5

2.3

3.0

1.5

2.3

3.0

1.5

2.3

3.0

1.5

2.3

3.0

1.5

2.3

3.0

1.5

2.3

3.0

3.0

1.5

2.3

3.0

WPD

3.0

4.1

5.3

2.8

3.8

4.9

3.9

5.3

6.9

3.5

4.7

6.1

2.4

3.3

4.3

2.2

2.9

3.8

FT

9.0

4.5

6.1

7.9

12.1

12.5

12.8

11.8

12.0

12.2

14.9

15.1

14.2

13.1

13.4

13.5

16.9

17.1

17.2

16.2

16.5

16.6

15.5

15.8

15.9

SC

9.4

9.6

9.8

9.3

9.4

9.6

11.0

11.0

10.3

9.8

9.8

9.9

11.8

11.9

11.9

11.6

11.7

11.8

11.2

11.3

11.3

COOLING kW

0.98

0.96

0.95

1.11

1.08

1.06

0.85

0.81

0.79

0.89

0.86

0.84

0.53

0.49

0.48

0.63

0.60

0.58

0.74

0.71

0.69

HR

17.6

18.6

18.0

14.8

15.6

16.1

25.8

27.6

28.7

21.0

22.3

23.1

12.3

13.0

13.5

10.6

11.1

11.5

EER HTG

8.2

32.0

34.7

36.0

9.0

9.5

9.9

14.8

15.6

16.2

16.1

16.9

17.6

12.0

12.5

12.9

14.6

15.1

15.8

9.8

10.2

10.9

11.7

12.3

12.9

15.5

15.8

16.0

15.6

15.7

15.8

17.8

17.9

16.9

16.1

16.3

16.4

18.7

18.8

18.8

18.3

18.5

18.6

18.0

18.2

18.2

HEATING

EWT (F) GPM

1.3

1.8

2.3

1.2

1.6

2.1

1.7

2.3

3.0

1.5

2.0

2.6

1.1

1.4

1.8

0.9

1.3

1.6

PSI

3.9

2.0

2.6

3.4

TC

100

1.5

2.3

3.0

1.5

0.8

1.1

1.5

0.7

1.9

2.6

3.4

1.7

10.9

11.3

11.5

10.0

9.1

9.4

9.5

8.5

1.21

1.19

1.17

1.32

15.0

15.4

15.5

14.5

9.0

9.5

9.8

7.6

110

2.3

3.0

1.0

1.3

2.3

3.0

10.3

10.6

8.7

8.8

1.29

1.28

14.7

15.0

8.0

8.3

Cooling Performance is tabulated at 80.6 F DB and 66.2 F WB entering air. Heating performance tabulated at 68 F EAT

Tabulated data does not include ARI/ISO corrections for fan and pump power.

All capacities are expressed in MBH.

Insulated water circuit is recommended for operation below 60F EWT.

See performance correction tables for conditions beyond what is listed.

Extrapolation is not permissible.

Shaded areas indicate conditions where operation is not recommended.

0.90

0.92

0.92

1.04

1.03

1.08

0.90

0.91

0.97

1.01

1.03

1.05

0.94

0.97

0.99

0.98

0.99

1.01

kW

0.86

0.91

0.93

0.94

8.9

9.4

9.8

11.0

11.6

12.1

6.7

7.1

7.6

8.3

8.8

9.3

11.6

12.3

12.8

12.7

13.5

14.1

HE LAT (F) COP

5.3

87 2.8

5.9

6.3

6.7

89

90

91

2.9

3.0

3.1

91

92

93

95

96

98

96

97

98

102

103

105

102

104

106

105

107

109

4.6

4.7

4.8

4.8

5.0

5.1

3.9

4.0

4.1

4.1

4.3

4.3

3.2

3.3

3.3

3.4

3.5

3.6

10

Johnson Controls

Water Source Heat Pumps

PERFORMANCE DATA

Technical Guide: YK145.00-EG4 (309)

RS*018 — 640 CFM

20

30

40

50

60

70

80

90

2.4

3.6

4.8

2.4

3.6

4.8

2.4

3.6

4.8

2.4

3.6

4.8

2.4

3.6

4.8

2.4

3.6

4.8

4.8

2.4

3.6

4.8

WPD

4.8

7.5

11.3

4.4

6.9

10.4

6.2

9.8

14.7

5.5

8.7

13.0

3.9

6.1

9.1

3.4

5.4

8.1

FT

19.4

7.1

11.3

16.9

18.6

19.3

19.8

17.4

18.1

18.6

21.3

22.0

22.8

20.2

20.5

21.0

26.6

27.3

27.7

24.9

25.6

25.9

24.3

24.5

24.9

SC

14.4

14.8

15.1

13.7

14.2

14.6

15.7

16.1

16.6

15.0

15.1

15.3

18.6

19.1

19.1

17.7

18.0

18.1

17.5

17.5

17.7

COOLING kW

1.44

1.39

1.37

1.55

1.52

1.50

1.22

1.21

1.13

1.34

1.27

1.24

0.96

0.90

0.87

1.05

1.00

0.96

1.15

1.14

1.09

HR

17.4

18.2

20.2

15.1

16.2

17.0

23.8

25.5

27.0

21.1

21.5

22.8

12.9

13.9

14.5

11.2

11.9

12.4

EER HTG

10.4

27.7

30.2

32.0

12.0

12.4

12.7

23.3

24.6

25.4

25.8

27.0

28.1

19.2

20.1

20.8

22.0

23.1

23.9

14.7

15.2

15.7

17.3

18.0

18.8

23.5

24.0

24.5

22.7

23.3

23.7

25.5

26.1

26.7

24.8

24.8

25.2

29.9

30.4

30.7

28.5

29.0

29.2

28.2

28.4

28.6

HEATING

EWT (F) GPM

2.1

3.3

4.9

1.9

3.0

4.5

2.7

4.3

6.4

2.4

3.8

5.6

1.7

2.6

4.0

1.5

2.3

3.5

PSI

8.4

3.1

4.9

7.3

TC

100

2.4

3.6

4.8

2.4

1.3

2.1

3.1

1.2

3.1

4.8

7.2

2.7

16.6

17.2

17.7

15.1

13.8

14.3

14.6

13.1

1.84

1.82

1.79

1.91

22.9

23.4

23.8

21.6

9.7

10.3

10.6

8.4

110

3.6

4.8

1.9

2.8

4.3

6.5

15.8

16.1

13.5

13.5

1.87

1.84

22.2

22.4

8.9

9.2

Cooling Performance is tabulated at 80.6 F DB and 66.2 F WB entering air. Heating performance tabulated at 68 F EAT

Tabulated data does not include ARI/ISO corrections for fan and pump power.

All capacities are expressed in MBH.

Insulated water circuit is recommended for operation below 60F EWT.

See performance correction tables for conditions beyond what is listed.

Extrapolation is not permissible.

Shaded areas indicate conditions where operation is not recommended.

1.41

1.44

1.45

1.47

1.50

1.56

1.23

1.27

1.28

1.33

1.35

1.41

1.48

1.50

1.51

1.49

1.52

1.55

kW

1.09

1.17

1.21

1.20

14.4

15.2

15.8

17.0

18.0

18.6

10.5

10.9

11.3

12.7

13.4

14.0

18.2

19.5

20.2

20.7

21.8

22.8

HE LAT (F) COP

6.7

83 2.8

8.0

8.3

8.6

85

86

86

3.0

3.0

3.1

89

90

91

93

94

95

96

97

98

100

101

103

102

104

105

105

107

109

4.6

4.8

4.9

5.1

5.2

5.3

4.0

4.1

4.2

4.4

4.5

4.5

3.5

3.5

3.6

3.8

3.9

3.9

Johnson Controls

11

Technical Guide: YK145.00-EG4 (309)

PERFORMANCE DATA

Water Source Heat Pumps

RS*024 — 800 CFM

20

30

40

50

60

70

80

90

3.0

4.5

6.0

3.0

4.5

6.0

3.0

4.5

6.0

3.0

4.5

6.0

3.0

4.5

6.0

3.0

4.5

6.0

6.0

3.0

4.5

6.0

WPD

5.3

8.0

12.8

4.9

7.4

11.8

6.9

10.5

16.7

6.1

9.2

14.7

4.3

6.5

10.4

3.8

5.8

9.2

FT

22.4

7.9

12.0

19.1

24.8

25.1

26.0

23.1

23.9

24.4

27.8

28.4

29.0

27.2

28.0

28.5

35.1

35.9

36.4

33.4

34.3

34.8

31.4

32.2

32.8

SC

19.2

19.3

19.9

18.2

18.8

19.1

20.4

20.7

21.1

20.3

20.6

20.8

24.6

25.0

25.2

23.9

24.4

24.7

22.6

23.0

23.3

COOLING kW

1.77

1.70

1.70

1.96

1.90

1.86

1.49

1.48

1.45

1.64

1.60

1.56

1.07

1.01

0.99

1.13

1.07

1.04

1.30

1.23

1.21

HR

18.7

19.2

20.0

16.6

17.5

18.3

29.5

32.1

33.4

24.2

26.1

27.0

14.0

14.8

15.3

11.8

12.6

13.1

EER HTG

13.3

32.7

35.4

36.8

15.9

16.4

16.8

31.5

31.8

33.0

32.1

33.9

35.3

25.1

26.4

27.4

27.8

29.3

30.4

18.4

19.1

19.7

21.6

22.6

23.6

30.8

30.9

31.8

29.8

30.4

30.8

32.9

33.4

33.9

32.8

33.5

33.8

38.8

39.4

39.8

37.3

37.9

38.4

35.8

36.4

36.9

HEATING

EWT (F) GPM

2.3

3.5

5.5

2.1

3.2

5.1

3.0

4.5

7.2

2.6

4.0

6.4

1.8

2.8

4.5

1.6

2.5

4.0

PSI

9.7

3.4

5.2

8.3

TC

100

3.0

4.5

6.0

3.0

1.5

2.2

3.5

1.3

3.4

5.1

8.2

3.0

20.6

21.6

22.1

18.7

17.2

17.9

18.3

15.9

2.06

2.04

2.01

2.17

27.6

28.6

29.0

26.1

10.0

10.6

11.0

8.6

110

4.5

6.0

2.0

3.2

4.6

7.3

19.5

20.0

16.4

16.6

2.14

2.13

26.8

27.3

9.1

9.4

Cooling Performance is tabulated at 80.6 F DB and 66.2 F WB entering air. Heating performance tabulated at 68 F EAT

Tabulated data does not include ARI/ISO corrections for fan and pump power.

All capacities are expressed in MBH.

Insulated water circuit is recommended for operation below 60F EWT.

See performance correction tables for conditions beyond what is listed.

Extrapolation is not permissible.

Shaded areas indicate conditions where operation is not recommended.

1.71

1.72

1.78

1.77

1.83

1.86

1.59

1.60

1.60

1.71

1.79

1.82

1.85

1.86

1.90

1.84

1.91

1.95

kW

1.50

1.50

1.50

1.54

19.3

20.5

21.3

21.8

23.1

24.1

13.0

13.6

14.2

15.8

16.5

17.4

25.2

25.4

26.5

25.8

27.4

28.6

HE LAT (F) COP

8.2

83 2.6

10.8

11.3

11.6

86

87

87

3.1

3.2

3.2

89

90

91

93

94

95

97

99

100

100

102

103

104

105

106

105

107

109

5.0

5.0

5.1

5.1

5.2

5.3

4.3

4.5

4.5

4.6

4.7

4.8

3.4

3.5

3.6

3.7

3.7

3.8

12

Johnson Controls

Water Source Heat Pumps

PERFORMANCE DATA

Technical Guide: YK145.00-EG4 (309)

RS*030 — 1000 CFM

20

30

40

50

60

70

80

90

3.9

5.8

7.8

3.9

5.8

7.8

3.9

5.8

7.8

3.9

5.8

7.8

3.9

5.8

7.8

3.9

5.8

7.8

7.8

3.9

5.8

7.8

WPD

6.5

8.3

10.3

6.0

7.6

9.5

8.5

10.8

13.4

7.5

9.5

11.8

5.3

6.7

8.3

4.7

5.9

7.4

FT

18.0

9.8

12.4

15.4

29.0

29.7

30.2

28.0

28.7

29.2

32.1

32.9

33.5

31.0

31.8

32.3

38.6

39.5

40.0

37.1

38.0

38.6

34.4

35.2

35.8

SC

22.4

22.8

23.1

22.1

22.5

22.9

23.6

24.0

24.4

23.1

23.4

23.6

27.0

27.5

27.7

26.5

27.1

27.4

24.8

25.2

25.4

COOLING kW

2.04

2.01

2.00

2.33

2.30

2.28

1.75

1.70

1.70

1.86

1.82

1.80

1.43

1.41

1.39

1.53

1.49

1.48

1.65

1.62

1.55

HR

18.3

19.3

19.7

16.7

17.5

17.9

24.2

25.5

26.1

20.8

21.7

23.1

14.2

14.8

15.1

12.0

12.5

12.8

EER HTG

17.5

26.9

28.0

28.7

19.2

20.3

22.0

36.4

38.2

39.7

40.7

42.8

44.5

29.5

30.9

32.0

33.1

34.7

36.0

22.3

23.2

23.9

27.1

28.2

29.1

36.0

36.5

37.0

36.0

36.5

37.0

38.1

38.7

39.3

37.3

38.0

38.5

43.5

44.3

44.8

42.3

43.1

43.6

40.0

40.7

41.1

HEATING

EWT (F) GPM

2.8

3.6

4.4

2.6

3.3

4.1

3.7

4.7

5.8

3.3

4.1

5.1

2.3

2.9

3.6

2.0

2.6

3.2

PSI

7.8

4.2

5.4

6.7

TC

100

3.9

5.8

7.8

3.9

1.8

2.3

2.9

1.6

4.2

5.3

6.6

3.7

25.8

26.5

27.0

23.6

21.5

22.0

22.3

20.1

2.50

2.45

2.45

2.65

34.3

34.9

35.4

32.7

10.3

10.8

11.0

8.9

110

5.8

7.8

2.1

2.6

4.8

5.9

24.3

24.7

20.5

20.5

2.64

2.63

33.3

33.7

9.2

9.4

Cooling Performance is tabulated at 80.6 F DB and 66.2 F WB entering air. Heating performance tabulated at 68 F EAT

Tabulated data does not include ARI/ISO corrections for fan and pump power.

All capacities are expressed in MBH.

Insulated water circuit is recommended for operation below 60F EWT.

See performance correction tables for conditions beyond what is listed.

Extrapolation is not permissible.

Shaded areas indicate conditions where operation is not recommended.

2.11

2.16

2.18

2.20

2.26

2.34

1.87

1.94

1.95

2.15

2.23

2.24

2.32

2.38

2.42

2.43

2.51

2.56

kW

1.97

1.88

1.92

2.01

22.3

23.5

24.6

25.6

27.0

28.0

15.9

16.6

17.3

19.8

20.6

21.4

28.5

30.1

31.4

32.4

34.2

35.8

HE LAT (F) COP

10.8

84 2.6

12.8

13.8

15.1

86

87

88

3.0

3.1

3.2

89

89

90

93

94

95

95

97

98

99

100

101

102

103

105

106

108

109

4.6

4.7

4.8

4.9

5.0

5.1

4.1

4.2

4.3

4.4

4.5

4.5

3.5

3.5

3.6

3.7

3.7

3.8

Johnson Controls

13

Technical Guide: YK145.00-EG4 (309)

PERFORMANCE DATA

Water Source Heat Pumps

RS*036 — 1200 CFM

20

30

40

50

60

70

80

90

4.5

6.8

9.0

4.5

6.8

9.0

4.5

6.8

9.0

4.5

6.8

9.0

4.5

6.8

9.0

4.5

6.8

9.0

9.0

4.5

6.8

9.0

WPD

5.3

9.8

13.3

4.9

9.0

12.2

6.9

12.8

17.3

6.1

11.3

15.3

4.3

7.9

10.8

3.8

7.0

9.5

FT

23.3

7.9

14.6

19.9

36.1

36.5

37.1

34.9

35.4

35.6

38.0

38.9

39.6

34.4

35.3

36.0

45.6

47.5

48.8

44.0

45.0

45.7

41.7

42.8

43.3

SC

27.9

28.0

28.3

27.5

27.7

27.9

27.9

28.4

28.8

25.6

25.9

26.3

31.9

33.1

33.8

31.5

32.0

32.4

30.0

30.6

30.7

COOLING kW

2.56

2.50

2.69

2.96

2.90

2.87

1.84

1.79

1.77

2.02

1.97

1.96

1.27

1.26

1.26

1.44

1.40

1.38

1.72

1.67

1.64

HR

20.7

21.8

22.4

17.0

17.9

18.4

30.6

32.2

33.1

24.3

25.7

26.4

14.1

14.6

13.8

11.8

12.2

12.4

EER HTG

19.9

35.9

37.8

38.8

23.2

24.0

24.5

46.7

49.1

50.4

50.8

53.6

55.6

37.6

39.5

40.8

41.5

43.7

45.3

28.2

29.4

30.2

34.0

35.6

37.2

44.8

45.0

46.3

45.0

45.2

45.4

44.3

45.0

45.6

41.3

42.0

42.7

49.9

51.8

53.1

48.9

49.8

50.4

47.6

48.5

48.9

HEATING

EWT (F) GPM

2.3

4.2

5.7

2.1

3.9

5.3

3.0

5.5

7.5

2.6

4.9

6.6

1.8

3.4

4.7

1.6

3.0

4.1

PSI

10.1

3.4

6.3

8.6

TC

100

4.5

6.8

9.0

4.5

1.5

2.7

3.7

1.3

3.4

6.3

8.5

3.0

32.8

33.3

33.5

31.7

27.4

27.6

27.6

26.9

3.16

3.11

3.10

3.37

43.6

43.9

44.0

43.2

10.4

10.7

10.8

9.4

110

6.8

9.0

2.4

3.3

5.6

7.6

32.1

32.4

27.1

26.9

3.31

3.30

43.4

43.6

9.7

9.8

Cooling Performance is tabulated at 80.6 F DB and 66.2 F WB entering air. Heating performance tabulated at 68 F EAT

Tabulated data does not include ARI/ISO corrections for fan and pump power.

All capacities are expressed in MBH.

Insulated water circuit is recommended for operation below 60F EWT.

See performance correction tables for conditions beyond what is listed.

Extrapolation is not permissible.

Shaded areas indicate conditions where operation is not recommended.

2.50

2.57

2.66

2.64

2.72

2.77

2.23

2.27

2.33

2.43

2.48

2.58

2.85

2.94

3.04

2.98

3.08

3.13

kW

1.94

2.06

2.13

2.11

29.1

30.7

31.7

32.5

34.4

35.9

20.6

21.7

22.3

25.7

27.1

28.4

37.0

39.1

40.0

40.6

43.1

44.9

HE LAT (F) COP

2.0

83 3.0

16.2

16.7

17.3

86

86

87

3.3

3.3

3.4

90

91

91

94

95

97

97

98

99

100

102

103

104

106

107

107

109

111

4.8

4.9

4.9

5.0

5.1

5.2

4.4

4.5

4.5

4.6

4.7

4.8

3.7

3.8

3.8

4.1

4.2

4.2

14

Johnson Controls

Water Source Heat Pumps

PERFORMANCE DATA

Technical Guide: YK145.00-EG4 (309)

RS*042 — 1400 CFM

20

30

40

50

60

70

80

90

5.2

7.8

10.4

5.2

7.8

10.4

5.2

7.8

10.4

5.2

7.8

10.4

10.4

5.2

7.8

10.4

5.2

7.8

10.4

5.2

7.8

10.4

WPD

6.3

10.3

16.3

5.8

9.5

15.0

8.2

13.4

21.3

7.2

11.8

18.8

5.1

8.3

13.2

4.5

7.4

11.7

FT

28.4

9.4

15.4

24.4

42.7

43.5

44.0

40.5

41.4

41.9

44.3

45.0

45.4

43.5

45.6

46.1

48.6

49.1

50.0

47.2

47.8

48.1

45.8

46.5

46.9

SC

33.0

33.4

33.6

32.0

32.5

32.8

32.6

32.9

33.0

32.4

33.5

33.7

34.0

34.2

34.6

33.7

34.0

34.2

33.0

33.2

33.3

COOLING kW

3.46

3.32

3.23

3.91

3.74

3.64

2.76

2.65

2.58

3.06

2.96

2.89

1.97

1.86

1.80

2.22

2.12

2.05

2.39

2.38

2.31

HR

16.0

17.0

17.6

14.2

15.4

16.0

21.2

22.5

23.4

18.4

19.5

20.3

12.4

13.1

13.6

10.4

11.1

11.5

EER HTG

26.7

24.7

26.4

27.6

31.2

31.9

32.2

55.5

58.1

60.1

61.1

63.6

65.9

44.0

45.7

47.0

48.9

51.1

52.7

35.5

36.5

37.3

39.3

40.7

42.3

54.5

54.8

55.0

53.8

54.2

54.3

53.7

54.0

54.2

53.9

55.7

56.0

55.3

55.4

56.1

54.8

55.0

55.1

54.0

54.6

54.7

HEATING

EWT (F) GPM

2.7

4.4

7.0

2.5

4.1

6.5

3.5

5.8

9.2

3.1

5.1

8.1

2.2

3.6

5.7

1.9

3.2

5.1

PSI

12.3

4.1

6.7

10.6

TC

100

5.2

7.8

10.4

5.2

1.7

2.9

4.5

1.6

4.0

6.6

10.4

3.6

38.1

39.0

39.6

36.2

31.8

32.3

32.7

30.8

4.36

4.17

4.06

4.89

53.0

53.2

53.5

52.9

8.7

9.4

9.8

7.3

110

7.8

10.4

2.6

4.1

5.9

9.4

37.1

37.8

31.3

31.4

4.67

4.54

53.0

53.3

7.8

8.2

Cooling Performance is tabulated at 80.6 F DB and 66.2 F WB entering air. Heating performance tabulated at 68 F EAT

Tabulated data does not include ARI/ISO corrections for fan and pump power.

All capacities are expressed in MBH.

Insulated water circuit is recommended for operation below 60F EWT.

See performance correction tables for conditions beyond what is listed.

Extrapolation is not permissible.

Shaded areas indicate conditions where operation is not recommended.

3.52

3.55

3.57

3.61

3.65

3.68

3.36

3.38

3.39

3.44

3.46

3.48

3.71

3.76

3.80

3.82

3.89

3.94

kW

3.32

3.30

3.31

3.32

32.0

33.6

34.8

36.6

38.6

40.1

24.0

25.0

25.7

27.6

28.9

30.4

42.8

45.3

47.1

48.1

50.3

52.5

HE LAT (F) COP

15.4

86 2.5

19.9

20.6

20.9

89

89

89

2.8

2.8

2.8

91

92

93

94

95

96

97

98

99

100

102

103

105

106

108

108

110

112

4.4

4.5

4.6

4.7

4.8

4.9

3.7

3.8

3.9

4.0

4.1

4.2

3.1

3.2

3.2

3.4

3.4

3.6

Johnson Controls

15

Technical Guide: YK145.00-EG4 (309)

PERFORMANCE DATA

Water Source Heat Pumps

RS*048 — 1600 CFM

20

30

40

50

60

70

80

90

6.0

9.0

12.0

6.0

9.0

12.0

6.0

9.0

12.0

6.0

9.0

12.0

12.0

6.0

9.0

12.0

6.0

9.0

12.0

6.0

9.0

12.0

WPD

6.8

13.0

20.3

6.2

12.0

18.7

8.8

17.0

26.5

7.8

15.0

23.4

5.5

10.6

16.5

4.9

9.4

14.6

FT

34.9

10.1

19.5

30.4

48.1

48.6

49.4

46.4

47.2

47.7

51.1

51.7

52.3

49.8

50.2

50.8

61.3

62.2

62.8

58.0

58.8

59.4

55.4

56.5

57.6

SC

37.2

37.3

37.7

36.7

37.1

37.3

37.6

37.7

38.0

37.1

36.9

37.1

42.9

43.4

43.5

41.5

41.9

42.2

39.9

40.4

40.9

COOLING kW

3.98

3.78

3.66

4.51

4.26

4.12

2.97

2.82

2.73

3.39

3.26

3.11

2.33

2.29

2.27

2.46

2.40

2.37

2.69

2.62

2.50

HR

17.2

18.3

19.2

14.7

15.4

16.3

23.6

24.5

25.1

20.6

21.6

23.0

12.1

12.9

13.5

10.3

11.1

11.6

EER HTG

30.5

26.3

27.2

27.7

33.4

35.6

36.7

63.2

64.6

67.2

70.3

72.4

73.3

51.1

53.1

54.6

58.8

59.8

61.3

39.8

41.5

43.6

44.2

45.8

47.4

61.7

61.5

61.9

61.8

61.7

61.8

61.2

61.3

61.6

61.4

61.3

61.4

69.3

70.0

70.5

66.4

67.0

67.5

64.6

65.4

66.1

HEATING

EWT (F) GPM

2.9

5.6

8.8

2.7

5.2

8.1

3.8

7.4

11.5

3.4

6.5

10.1

2.4

4.6

7.1

2.1

4.1

6.3

PSI

15.1

4.4

8.5

13.2

TC

100

6.0

9.0

12.0

6.0

1.9

3.6

5.6

1.7

4.3

8.4

13.0

3.9

43.6

45.0

45.9

39.9

36.4

37.3

37.9

33.9

5.05

4.76

4.59

5.70

60.8

61.2

61.6

59.4

8.6

9.5

10.0

7.0

110

9.0

12.0

3.2

5.0

7.5

11.7

41.3

42.2

34.8

35.0

5.36

5.16

59.6

59.8

7.7

8.2

Cooling Performance is tabulated at 80.6 F DB and 66.2 F WB entering air. Heating performance tabulated at 68 F EAT

Tabulated data does not include ARI/ISO corrections for fan and pump power.

All capacities are expressed in MBH.

Insulated water circuit is recommended for operation below 60F EWT.

See performance correction tables for conditions beyond what is listed.

Extrapolation is not permissible.

Shaded areas indicate conditions where operation is not recommended.

3.62

3.65

3.70

3.84

3.87

3.90

3.33

3.38

3.55

3.63

3.66

3.68

4.05

4.11

4.16

4.28

4.32

4.34

kW

3.32

3.30

3.32

3.34

3.6

3.7

3.7

3.8

3.9

3.9

3.6

3.6

3.6

3.6

3.7

3.7

4.1

4.1

4.2

4.3

4.3

4.3

HE LAT (F) COP

19.1

86 2.8

3.3

3.3

3.3

88

89

89

3.0

3.1

3.2

91

92

93

94

95

95

97

98

99

100

101

102

103

105

106

107

108

109

4.6

4.6

4.7

4.8

4.9

4.9

4.1

4.3

4.3

4.5

4.5

4.6

3.5

3.6

3.6

3.6

3.7

3.8

16

Johnson Controls

Water Source Heat Pumps

PERFORMANCE DATA

Technical Guide: YK145.00-EG4 (309)

RS*060 — 2000 CFM

20

30

40

50

60

70

80

90

7.5

11.2

15.0

7.5

11.2

15.0

7.5

11.2

15.0

7.5

11.2

15.0

15.0

7.5

11.2

15.0

7.5

11.2

15.0

7.5

11.2

15.0

WPD

9.0

11.5

24.0

8.3

10.6

22.2

11.8

15.1

31.4

10.4

13.3

27.7

7.3

9.3

19.5

6.5

8.3

17.3

FT

41.1

13.5

17.3

36.0

59.4

60.8

61.7

56.9

57.5

58.4

63.3

65.6

66.4

62.5

63.8

64.7

72.6

73.8

74.5

68.9

70.1

71.9

66.2

67.5

68.2

SC

45.9

46.6

47.1

45.0

45.1

45.7

46.5

47.9

48.3

46.6

46.9

47.2

50.8

51.4

51.6

49.3

49.9

51.0

47.7

48.3

48.4

COOLING kW

4.84

4.60

4.46

5.33

5.20

5.05

3.85

3.67

3.35

4.38

4.18

3.90

2.77

2.60

2.48

3.25

3.08

2.96

3.60

3.43

3.32

HR

16.4

17.9

19.8

14.3

15.3

16.6

21.2

22.8

24.3

18.4

19.7

20.5

12.3

13.2

13.8

10.7

11.1

11.6

EER HTG

38.2

26.2

28.4

30.0

43.2

45.2

46.0

73.2

78.1

82.3

84.2

88.6

93.5

61.4

63.4

64.9

66.3

69.8

72.9

50.3

52.0

53.5

54.2

56.8

59.0

75.9

76.5

76.9

75.1

75.2

75.6

76.4

78.1

77.8

77.4

78.1

78.0

82.1

82.7

83.0

80.0

80.6

82.0

78.5

79.2

79.5

HEATING

EWT (F) GPM

3.9

5.0

10.4

3.6

4.6

9.6

5.1

6.5

13.6

4.5

5.8

12.0

3.2

4.0

8.4

2.8

3.6

7.5

PSI

17.8

5.9

7.5

15.6

TC

100

7.5

11.2

15.0

7.5

2.5

3.2

6.7

2.5

5.8

7.4

15.4

5.7

51.9

53.6

54.5

48.6

43.3

44.4

45.0

41.3

6.04

5.75

5.57

6.65

72.5

73.2

73.5

71.3

8.6

9.3

9.8

7.3

110

11.2

15.0

3.2

6.6

7.3

15.2

49.2

50.3

41.5

41.7

6.41

6.21

71.1

71.5

7.7

8.1

Cooling Performance is tabulated at 80.6 F DB and 66.2 F WB entering air. Heating performance tabulated at 68 F EAT

Tabulated data does not include ARI/ISO corrections for fan and pump power.

All capacities are expressed in MBH.

Insulated water circuit is recommended for operation below 60F EWT.

See performance correction tables for conditions beyond what is listed.

Extrapolation is not permissible.

Shaded areas indicate conditions where operation is not recommended.

4.39

4.44

4.47

4.52

4.56

4.62

4.05

4.12

4.17

4.21

4.28

4.35

4.70

4.84

5.01

5.09

5.25

5.37

kW

3.32

3.90

3.96

4.00

46.4

48.2

49.6

50.9

54.2

57.1

36.5

37.9

39.3

39.8

42.2

44.2

57.2

61.6

65.2

66.8

70.7

75.2

HE LAT (F) COP

26.8

86 2.9

29.9

31.7

32.3

88

89

89

3.2

3.3

3.4

91

92

93

93

94

95

96

97

98

99

100

102

102

104

106

107

109

111

4.6

4.7

4.8

4.8

4.9

5.1

4.1

4.2

4.3

4.3

4.5

4.6

3.6

3.7

3.8

3.8

3.9

4.0

Johnson Controls

17

Technical Guide: YK145.00-EG4 (309)

PERFORMANCE DATA

Water Source Heat Pumps

RS*070 — 2200 CFM

20

30

40

50

60

70

80

90

8.8

13.1

17.5

8.8

13.1

17.5

8.8

13.1

17.5

8.8

13.1

17.5

17.5

8.8

13.1

17.5

8.8

13.1

17.5

8.8

13.1

17.5

WPD

12.8

19.3

25.3

11.8

17.8

23.3

16.7

25.2

33.1

14.7

22.2

29.2

10.4

15.6

20.5

9.2

13.9

18.2

FT

48.0

19.1

28.9

37.9

66.7

68.2

69.2

63.5

64.3

65.3

71.4

72.6

73.0

73.1

74.5

75.4

82.7

83.4

83.8

79.0

79.9

80.5

75.1

76.2

76.9

SC

51.6

52.3

52.9

50.2

50.5

51.1

52.5

53.0

53.1

54.5

54.8

55.0

57.9

58.1

58.0

56.5

56.9

57.2

54.1

54.5

54.6

COOLING kW

5.09

4.91

4.81

5.62

5.31

5.27

4.30

4.20

4.01

4.87

4.72

4.71

3.22

3.14

3.14

3.85

3.68

3.56

3.99

3.95

3.85

HR

16.6

17.3

18.2

15.0

15.8

16.0

20.5

21.7

22.6

18.8

19.3

20.0

13.1

13.9

14.4

11.3

12.1

12.4

EER HTG

42.1

25.7

26.6

26.7

47.9

49.4

50.7

82.0

85.8

88.9

90.8

95.4

99.0

67.9

70.6

72.7

75.0

78.3

80.8

54.8

56.6

58.1

62.4

65.2

66.8

84.1

84.9

85.6

82.7

82.4

83.3

86.1

86.9

86.7

89.7

90.6

91.5

93.7

94.1

94.5

92.1

92.5

92.7

88.7

89.7

90.0

HEATING

EWT (F) GPM

5.5

8.3

10.9

5.1

7.7

10.1

7.2

10.9

14.3

6.4

9.6

12.6

4.5

6.8

8.9

4.0

6.0

7.9

PSI

20.8

8.3

12.5

16.4

TC

100

8.8

13.1

17.5

8.8

3.5

5.4

7.0

3.5

8.2

12.4

16.2

8.1

59.0

60.8

61.9

54.7

49.2

50.4

51.1

46.5

6.02

5.79

5.73

6.59

79.5

80.6

81.5

77.2

9.8

10.5

10.8

8.3

110

13.1

17.5

5.3

6.9

12.2

16.0

56.7

57.9

47.8

48.1

6.37

6.29

78.4

79.4

8.9

9.2

Cooling Performance is tabulated at 80.6 F DB and 66.2 F WB entering air. Heating performance tabulated at 68 F EAT

Tabulated data does not include ARI/ISO corrections for fan and pump power.

All capacities are expressed in MBH.

Insulated water circuit is recommended for operation below 60F EWT.

See performance correction tables for conditions beyond what is listed.

Extrapolation is not permissible.

Shaded areas indicate conditions where operation is not recommended.

5.10

5.17

5.33

5.21

5.31

5.44

4.93

5.01

5.08

5.02

5.11

5.16

5.28

5.47

5.54

5.39

5.59

5.69

kW

3.32

4.86

4.92

4.98

50.5

53.0

54.5

57.2

60.2

62.2

38.0

39.5

40.8

45.3

47.8

49.2

64.0

67.1

70.0

72.4

76.3

79.6

HE LAT (F) COP

30.7

86 2.6

31.3

32.6

33.7

88

89

89

2.9

2.9

3.0

91

92

92

94

95

96

97

98

99

100

101

102

103

104

105

106

108

110

4.6

4.6

4.7

4.9

5.0

5.1

3.9

4.0

4.0

4.2

4.3

4.4

3.3

3.3

3.4

3.6

3.7

3.8

18

Johnson Controls

Water Source Heat Pumps

CORRECTION FACTORS

ANTIFREEZE CORRECTION TABLE

Ethylene Glycol

Propylene Glycol

Methanol

Cooling

Heating

PD

Cooling

Heating

PD

Cooling

Heating

PD

5%

0.998

0.995

1.040

0.995

0.989

1.035

0.999

0.989

1.050

10%

0.995

0.990

1.055

0.992

0.982

1.055

0.995

0.985

1.072

Technical Guide: YK145.00-EG4 (309)

Antifreeze Concentration

15%

0.993

0.985

1.080

0.987

0.975

1.100

0.990

0.979

1.094

20%

0.991

0.980

1.105

0.983

0.967

1.145

0.986

0.971

1.116

25%

0.989

0.974

1.135

0.979

0.958

1.200

0.982

0.963

1.140

30%

0.987

0.969

1.165

0.975

0.951

1.260

0.980

0.954

1.165

40%

0.984

0.964

1.210

0.970

0.943

1.320

0.978

0.946

1.196

AIRFLOW CORRECTION TABLE

Cooling

Airflow %

90

95

100

105

110

70

75

80

85

115

TC

0.931

0.941

0.950

0.966

0.977

0.989

1.000

1.008

1.018

1.026

SC

0.847

0.872

0.896

0.923

0.948

0.974

1.000

1.025

1.048

1.070

Power

0.964

0.969

0.979

0.983

0.989

0.995

1.000

1.006

1.013

1.019

THR

0.946

0.956

0.961

0.971

0.981

0.990

1.000

1.010

1.017

1.026

HC

0.942

0.953

0.960

0.970

0.979

0.989

1.000

1.009

1.019

1.029

Heating

Power

1.075

1.059

1.039

1.023

1.015

1.007

1.000

0.994

0.992

0.991

HE

0.940

0.949

0.958

0.969

0.979

0.989

1.000

1.010

1.018

1.028

COOLING PERFORMANCE CORRECTION TABLE

Entering Air

WB (F)

60

65

66.2

70

75

Total Clg

Capacity

0.845

0.948

1

1.061

1.162

70

0.86

0.628

0.539

S = Sensible cooling is equal to Total Cooling

Entering Air DB (F) - Sensible Capacity

75

1.1

0.865

0.777

0.631

80.6

1.305

1.082

1

0.855

0.618

85

S

1.312

1.22

1.081

0.848

90

S

S

1.475

1.331

1.09

95

S

S

S

1.543

1.296

Heat

Rejection

0.904

0.979

1

1.039

1.107

HEATING PERFORMANCE CORRECTION TABLE

EAT DB (F)

45

50

55

60

65

68

70

75

80

Heating Capacity

1.101

1.080

1.059

1.039

1.019

1.000

0.990

0.974

0.951

Johnson Controls

Power

0.785

0.832

0.878

0.926

0.960

1.000

1.028

1.064

1.111

Heat Extraction

1.162

1.125

1.079

1.064

1.023

1.000

0.983

0.957

0.918

19

Technical Guide: YK145.00-EG4 (309)

BLOWER PERFORMANCE

Water Source Heat Pumps

BLOWER PERFORMANCE

Unit

Size

007

009

012

018

024

030

036

042

048

Rated

CFM

260

320

400

640

800

1000

1200

1400

1600

Min.

CFM

182

235

300

495

560

730

865

980

1160

Max.

CFM

299

368

460

736

920

1150

1380

1480

1880

Motor

Speed

High

Med

Low

High

Med

Low

High

Med

Low

High

Med

Low

High

Med

Low

High

Med

Low

High

Med

Low

High

Med

Low

High

Med

Low

High

0

-

-

275

-

340

-

-

470

385

-

690

600

-

925

810

-

1150

980

-

1355

1200

-

1370

1480

-

1880

1495

-

0.1

-

-

260

-

325

-

475

455

370

750

660

570

-

905

795

-

1125

970

1390

1320

1190

1175

1320

1410

-

1860

1490

2320

0.2

-

300

240

380

300

-

450

430

355

710

625

535

-

875

780

1170

1090

955

1330

1270

1170

1160

1275

1350

-

External Static Pressure (in w.g.)

1820

1485

2260

060

2000 1560 2300 Med

Low

High

Med

2040

1760

2400

2040

2030

1750

2320

2030

2005

1730

2260

2005

070

2200 1700 2400

Low -

Units are shipped pre-wired for Medium speed.

All airflow ratings are at lowest voltage rating of dual rating (ie. 208 volt)

Airflow ratings include resistance of wet coil and clean air filters.

0.3

-

270

210

360

270

-

420

400

330

660

585

495

950

840

765

1120

1045

935

1270

1215

1130

1120

1210

1290

1915

1770

1480

2200

1970

1700

2200

1970

-

0.4

1925

1660

2120

1925

-

-

235

180

330

235

-

385

365

300

610

540

-

890

790

725

1060

990

905

1210

1155

1085

1075

1150

1220

1835

1710

1460

2120

0.5

-

200

-

290

-

-

345

325

-

555

490

-

820

730

660

985

925

855

1140

1085

1020

1015

1070

1140

1750

1640

1420

2040

1860

1610

2040

1860

-

925

1050

1660

1550

1360

1920

850

785

1055

1005

950

930

-

-

740

660

590

905

-

-

300

-

-

495

0.6

-

-

-

240

1785

1560

1920

1785

-

-

950

1550

1450

1285

1840

765

-

960

920

-

-

1700

-

1840

1700

-

-

-

650

590

-

820

-

-

-

-

-

-

0.7

-

-

-

-

-

-

1415

1320

1160

1700

865

-

-

-

-

-

1610

-

1700

-

-

-

-

550

-

-

730

-

-

-

-

-

-

0.8

-

-

-

-

20

Johnson Controls

Water Source Heat Pumps

ELECTRICAL DATA

Technical Guide: YK145.00-EG4 (309)

RSH/RSV ELECTRICAL DATA

Unit Size

007

009

012

018

024

030

036

042

048

060

070

QTY

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

SUPPLY

VOLTAGE

208-230/1/60

208-230/1/60

208-230/1/60

265/1/60

208-230/1/60

265/1/60

208-230/1/60

265/1/60

208-230/3/60

208-230/1/60

265/1/60

208-230/3/60

208-230/1/60

265/1/60

208-230/3/60

460/3/60

208-230/1/60

208-230/3/60

460/3/60

575/3/60

208-230/1/60

208-230/3/60

460/3/60

575/3/60

208-230/1/60

208-230/3/60

460/3/60

575/3/60

208-230/3/60

460/3/60

575/3/60

COMPRESSOR

RLA

11.6

8.7

4.3

19.9

13.6

6.1

7.0

6.1

10.1

8.7

7.2

13.5

4.2

23.1

16.0

7.1

5.6

3.4

4.6

5.6

4.6

6.9

6.1

8.2

26.3

15.6

7.8

5.8

19.0

9.7

7.4

@

@

@

@

@

@

@

@

@

@

@

@

@

@

@

@

@

@

@

@

@

@

@

@

@

@

@

@

@

@

@

LRA

79.0

78.0

40.0

109.0

81.0

41.0

44.0

58.0

60.0

58.0

58.0

83.0

33.0

144.0

91.0

46.0

37.0

22.0

28.0

29.0

20.0

48.0

44.0

48.0

134.0

110.0

52.0

38.9

123.0

62.0

50.0

BLOWER

HP

0.50

0.50

0.50

0.50

0.50

0.50

0.25

0.25

0.33

0.33

0.33

0.50

0.50

0.75

0.75

0.75

0.75

0.10

0.10

0.13

0.13

0.17

0.17

0.25

1.00

1.00

1.00

1.00

1.00

1.00

1.00

FLA

2.2

3.2

2.5

3.2

3.2

2.5

1.3

1.3

2.6

1.9

2.6

3.2

1.8

4.9

4.9

2.2

1.8

0.8

0.8

1.0

0.9

1.4

0.8

1.5

5.1

5.1

3.2

2.6

5.1

3.2

2.6

MAX FUSE /

CCT. BKR. AMP

25

20

15

45

30

15

15

15

25

20

15

30

15

50

40

15

15

15

15

15

15

15

15

15

60

40

20

15

45

25

15

MIN. CCT.

AMPACITY

16.70

14.08

7.88

28.08

20.20

10.13

10.05

8.93

15.23

12.78

11.60

20.08

5.05

6.55

8.00

6.65

10.03

8.43

11.75

7.05

33.78

24.90

11.08

8.80

37.98

24.60

12.95

9.85

28.85

15.33

11.85

Johnson Controls

21

Technical Guide: YK145.00-EG4 (309)

DIMENSIONAL DATA

E

B

LEFT HAND RETURN

RETURN

AIR

Ø0.875"

G

RSH SERIES

OPTIONAL

SIDE

DISCHARGE

TOP

VIEW

OPTIONAL

SIDE

DISCHARGE

Water Source Heat Pumps

RIGHT HAND RETURN

RETURN

AIR

G

Ø0.875"

B

E

0.75"

TYP

D

A

SUPPLY

AIR

L K

K L

SUPPLY

AIR

D

A

0.75"

TYP

C

ELEVATION

VIEW

2

C

2

0.75"

2.00"

POWER

CONNECTION

WATER OUT

1.63"

POWER

CONNECTION

WATER OUT

2.00"

0.75"

J

M

FRONT

VIEW

M

1 J

1

1.50"

N

WATER IN

LOW VOLTAGE

CONNECTION

1.81"

Model A B

RSH007

34.00

RSH009

34.00

RSH012

34.00

RSH018

40.00

RSH024

44.00

RSH030

44.00

RSH036

48.00

RSH042

52.00

RSH048

52.00

RSH060

56.00

19.00

19.00

19.00

21.00

21.00

21.00

22.00

26.00

26.00

26.00

RSH070

56.00

26.00

ALL DIMENSIONS IN INCHES

22

3

3/4 FPT

DRAIN

C

13.00

13.00

13.00

19.00

19.00

19.00

21.00

21.00

21.00

23.00

23.00

BACK

VIEW

D

31.75

31.75

31.75

37.75

41.75

41.75

45.75

49.75

49.75

53.75

53.75

E

21.50

21.50

21.50

23.50

23.50

23.50

24.50

28.50

28.50

28.50

28.50

SERVICE DOORS

1 - ELECTRICAL BOX SERVICE DOOR

2 - COMPRESSOR AND CONDENSER

SERVICE DOOR

3 - BLOWER SERVICE DOOR

RETURN AIR

G

16.50

16.50

18.50

23.00

24.50

24.50

27.50

35.50

35.50

43.50

43.50

J

10.50

10.50

10.50

16.50

16.50

16.50

18.50

18.50

18.50

20.50

20.50

WATER IN

LOW VOLTAGE

CONNECTION

1.50"

N

3/4 FPT

DRAIN

3

1.81"

K

5.75

5.75

5.75

6.50

6.50

6.50

6.50

6.50

6.50

6.00

6.00

SUPPLY AIR

L

6.44

6.44

7.44

9.19

9.19

9.69

9.69

10.50

10.50

13.12

13.12

M

4.13

4.13

4.13

10.31

10.31

11.38

11.38

13.63

13.63

13.63

13.63

N

3.75

3.75

3.75

3.75

4.81

4.81

5.88

5.88

5.13

5.13

5.13

Johnson Controls

Water Source Heat Pumps

DIMENSIONAL DATA

RSV SERIES

LEFT HAND RETURN

E F

G

D

G

TOP VIEW

SERVICE DOORS

1 - ELECTRICAL BOX SERVICE DOOR

2 - COMPRESSOR AND CONDENSER

SERVICE DOOR

3 - BLOWER SERVICE DOOR

Technical Guide: YK145.00-EG4 (309)

D

RIGHT HAND RETURN

F

E

G

G

TOP VIEW

AIR SUPPLY AIR SUPPLY

K

2"

1"

2"

3

3

L

RETURN AIR

RETURN AIR

LOW VOLTAGE

CONNECTION

POWER

CONNECTION

1

DRAIN

3/4Ø

WATER OUT

C

2

DRAIN

3/4Ø

WATER OUT

WATER IN

1

LOW VOLTAGE

CONNECTION

WATER IN

B

A

AIR COIL SIDE

B

POWER

CONNECTION

Model A B

RSV007

RSV009

RSV012

RSV018

RSV024

RSV030

21.50

21.50

21.50

25.50

25.50

25.50

25.50

21.50

21.50

21.50

23.00

23.00

23.00

23.00

RSV036

RSV042

RSV048

RSV060

RSV070

28.00

28.00

32.50

32.50

25.50

25.50

27.50

27.50

ALL DIMENSIONS IN INCHES

Johnson Controls

C

31.50

31.50

31.50

40.00

40.00

40.00

44.00

46.00

46.00

50.00

50.00

SUPPLY AIR

D

6.44

6.44

7.44

9.19

9.19

9.69

9.69

10.50

10.50

13.12

13.12

E

4.13

4.13

4.13

10.31

10.31

11.38

11.38

13.63

13.63

13.63

13.63

F

2.00

2.00

2.00

2.00

2.00

2.00

2.00

2.00

2.00

3.00

3.00

G

7.53

7.53

7.03

8.16

8.16

7.91

7.91

8.75

8.75

9.69

9.69

RETURN AIR

K

20.00

20.00

20.00

25.00

25.00

25.00

25.00

25.00

25.00

30.00

30.00

L

10.50

10.50

10.50

16.50

18.50

18.50

22.50

26.00

26.00

30.00

30.00

23

Technical Guide: YK145.00-EG4 (309)

WIRING DIAGRAM

SINGLE PHASE

RS* UNITS: 208-230V/1Ph/60Hz

265V/1PH/60Hz

Water Source Heat Pumps

24

Johnson Controls

Water Source Heat Pumps

WIRING DIAGRAM

3 PHASE

RS* UNITS: 208-230V/3Ph/60Hz

460V/3Ph/60Hz

575V/3Ph/60Hz

Technical Guide: YK145.00-EG4 (309)

Johnson Controls

25

Technical Guide: YK145.00-EG4 (309)

NOTES

Water Source Heat Pumps

26

Johnson Controls

Water Source Heat Pumps

NOTES

Technical Guide: YK145.00-EG4 (309)

Johnson Controls

27

Printed on recycled paper

Technical Guide: YK145.00-EG4 (309) Supersedes: Nothing

© 2008 Johnson Controls, Inc. P.O. Box 423, Milwaukee, WI 53201 Printed in USA www.johnsoncontrols.com