technical guide
Water Source
Heat Pumps
Technical Guide: YK145.00-EG4 (309)
TABLE OF CONTENTS
Water Source Heat Pumps
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
ARI/ISO Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Correction Factors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Blower Performance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Wiring Diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
2
Johnson Controls
Water Source Heat Pumps
INTRODUCTION
Technical Guide: YK145.00-EG4 (309)
Performance and dependability in a no-nonsense heat pump.
The R-Series units by YORK are completely self-contained heat pumps. This equipment employs a water-torefrigerant heat exchanger to extract (heating cycle) or reject (cooling cycle) heat from/to a circulating water-loop.
The high-quality feature set delivers robust construction and reliable performance that exceeds ASHRAE 90.1 requirements. Available with an insulated refrigerant-circuit, the R-Series is equally suited for water-loop and lowtemperature, geothermal applications.
For commercial installations ranging from schools to multi-story office space, R-Series Water Source Heat Pumps by YORK provide the performance and dependability necessary to suit today’s demanding installation requirements.
Listings / Certifications
PRODUCT OVERVIEW
Refrigerant
R-410A
Sizes
.5 – 6 Tons (1.76 – 21.1 kW)
Model
RSH (Horizontal)
RSV (Vertical)
Johnson Controls
3
Technical Guide: YK145.00-EG4 (309)
SPECIFICATIONS
GENERAL
All R-series models ½ - 6 ton ship as factory-charged packages, complete with R-410A refrigerant. Horizontal
(RSH) units are designed for suspended ceiling mounting. RSH models are shipped with ‘straight-through’ evaporator fan discharge as standard. Fan orientation is field convertible to side discharge.
Vertical (RSV) units are designed for free-standing floor mounting. All units are completely factory wired and pre-piped. Water supply, water outlet, and condensate drain connections are via flush-mounted female pipe thread fittings (no back-up wrench required).
CABINET
All cabinets are completely constructed of corrosion resistant galvanized steel. The RSH units are complete with integral hanger channels. The entire unit interior
(both evaporator and condensing section) is insulated with 1/2 ″ thick, 2 lb density acoustical insulation. Service panels are equipped with lifting handles for ease of removal and handling. All units provide service access to the reversing valve, thermal expansion valve, and compressor with the unit remaining in location. An integral duct collar is provided on the blower discharge opening.
REFRIGERATION CIRCUITS
All models utilize high efficiency rotary, hermetic reciprocating or scroll compressors. Compressors are mounted with rubber isolators on acoustically tuned bases to minimize vibration transmission. Internal overload protection is provided. External high pressure and low pressure cutout switches are included in each compressor control circuit. Each refrigeration circuit includes an adjustable bi-flow thermal expansion valve
(with external equalizer), bi-flow liquid line filter drier, and service gauge ports. The reversing valve is a pilot operated, sliding piston type with a replaceable magnetic solenoid coil.
The refrigerant-to-air heat transfer coils are constructed of internally enhanced copper tubes mechanically bonded to enhanced aluminum plate fins. The evaporator coil is employed in a draw-through configuration.
Large evaporator coil face area minimizes potential water blow-off. A fully-insulated, corrosion resistant condensate drain pan is provided.
• Optional anti-corrosion protective evaporator coil coating.
Water Source Heat Pumps
• Optional stainless steel drain pan.
The coaxial refrigerant-to-water heat exchangers feature a convoluted inner tube design for high heat transfer efficiency. Standard models feature a copper inner tube surrounded by a steel outer tube, and carry a 400 psig water side working pressure rating. Units shall be capable of operation with an entering fluid temperature range of 20°F to 110°F.
• Optional cupro-nickel condenser water coil.
• Optional condenser insulation package for lowwater temperature, geothermal applications.
INDOOR FAN
Forward curved, double inlet and double width, directdrive centrifugal blowers are used for air movement.
Large diameter wheels are employed to provide required airflow performance at minimum noise levels. Blower wheels are fabricated of galvanized steel. Fan motors are PSC type, with minimum three speeds. The PSC motors feature permanently lubricated bearings and internal thermal overload protection.
ELECTRICAL/CONTROLS
All units are completely factory wired with all necessary operating controls. A 24 volt control circuit, with oversized transformer, is provided for field connection. Units are designed to operate with conventional heat pump thermostat control interface. The reversing valve solenoid coil shall be energized in cooling mode only. A manual reset is provided on each compressor control circuit in the event of high/low pressure cutout.
• Optional solid-state electronic condensate overflow switch.
• Optional remote management package allows the unit to be controlled by an external source.
FILTERS
All models are shipped with 1-inch thick throwaway filters, factory installed. Filters are accessible from either side of unit.
FIELD INSTALLED ACCESSORIES
The following options are available field installation:
• 24 ″ braided stainless steel hose kit with fittings.
(qty 2 hoses per kit)
• Manual isolation ball-valves (600 psi full port).
• Thermostat (programmable or non-programmable)
4
Johnson Controls
Water Source Heat Pumps
NOMENCLATURE
Technical Guide: YK145.00-EG4 (309)
WATER SOURCE HEAT PUMP
1,2 3 4,5,6 7 8 9 10 11 12 13 14 15
RS H 018 A 2 E L S A A 0 A
Product Category
RS = Water-Cooled HP R-410A
Miscellaneous Options
A = None
D = Condensate Overflow Switch
Heating Options
0 = None
Product Indentifier
V = Vertical Arrangement (Upflow)
H = Horizontal Arrangment
Nominal Capacity
007 = .5 TON
009 = .75 TON
0 1 2 = 1 T O N
018 = 1.5 TON
024 = 2 TON
030 = 2.5 TON
036 = 3 TON
042 = 3.5 TON
0 4 8 = 4 T O N
0
6
0
=
5 T
O N
0 7 0 = 6 T O N
Design Series
A = C u r r e n t
Waterside Options
A = Std Water coil
B = Insulated Water Coil
N = Cupro-nickel Water Coil
R = Cupro-nickel & Insulation
Airside Options
A = Std Airside coil
C = Corrosion Protective Coating
D = Stainless Steel Drain Pan
F = Coated Coil w/ S-S Drain Pan
Supply Air Options
S = Straight-Thru (Horizontal Only)
B = Back Discharge (Horizontal Only)
T = Top Discharge (Vertical Only)
Voltage
1 = 208/230-60-1
6 = 265-60-1
2 = 208/230-60-3
4 = 460-60-3
5 = 575-60-3
Return Air/Unit Orientation
L = Left Hand
R = Right Hand
Control Options
E = Std Electromechnical Controls
K = Remote Management Relay Kit
Johnson Controls
5
Technical Guide: YK145.00-EG4 (309)
PHYSICAL DATA
Water Source Heat Pumps
Model Series
Nominal Cooling (Ton)
1
Compressor-Type
007
0.5
009
0.75
Rotary
012
1.0
018
1.5
024
2.0
030
2.5
Reciprocating
036
3
042
3.5
048
4
Scroll
060
5
070
6
Air Coil-Type
Face Area(sq ft)
Rows/FPI
1.17
3/13
1.17
3/13
Enhanced Copper tubes, Enhanced Aluminum Fins
1.33
3/15
2.56
3/15
2.88
3/15
2.88
3/15
3.47
3/15
4.44
3/15
4.44
3/15
6.11
3/15
6.11
3/15
Water Coil-Type
Water Connection (in) 1/2 1/2 1/2 3/4
Enhanced Surface Co-Axial
3/4 3/4 3/4 3/4 3/4 1 1
Standard Blower/Motor
Diameter x Width (in)
Motor HP
6x5 6x5
DWDI Forward-Curved Centrifugal / PSC Direct-Drive
6x6 9x7 9x7 10x7T 10x7T 11x8T 11x8T 11x10T 11x10T
0.10/3 0.10/3 0.13/3 0.17/3 0.25/3 0.33/3 0.50/3 0.50/3 0.75/3 1.0/3 1.0/3
RSH Filter
Quantity-Size(in)
1-12x16 1-12x16 1-12x20 1-18x24 1-18x24 1-18x24 2-14x20 2-18x20 2-18x20 2-22x22 2-22x22
RSV Filter
Quantity-Size(in)
1-12x20 1-12x20 1-12x20 1-18x24 1-20x25 1-20x25 1-24x24 2-14x25 2-14x25 2-16x30 2-16x30
RSH Cabinet Weight (lb)
130 135 145 195 210 215 240 310 320
315
370
375
385
390
RSV Cabinet Weight (lb)
120 125 135 185 200 210 230 305
NOTE:
1) Nominal Capacity calculated in accordance with ARI / ISO Standard 13256-1 for Water Loop Application
OPERATING LIMITS*
Min. Entering Water
Max. Entering Water
COOLING
30
110
°
°
F
F
HEATING
20
90
°
°
F
F
*Units are capable of operation with an entering fluid temperature range of 20 ° F to 110 ° F
6
Johnson Controls
Water Source Heat Pumps
ARI/ISO PERFORMANCE DATA
Technical Guide: YK145.00-EG4 (309)
PERFORMANCE DATA - ARI/ISO 13256-1 WATER LOOP CONDITIONS*
Unit Model
Flow Rate
(USGPM)
Air Flow
(SCFM)
Cooling
Capacity (Btuh)
EER
Heating
Capacity (Btuh)
007
009
012
018
024
030
1.8
2.4
3.0
4.8
6.0
7.8
9.0
260
320
400
640
800
1000
1200
6,800
8,900
12,400
19,100
24,600
29,800
36,200
036
042
048
10.4
12.0
1400
1600
42,700
48,300
060
070
15.0
17.5
2000
2200
60,500
67,700
*Water Loop capacities are rated at 86
°
F EWT Cooling, 68
°
F EWT Heating.
12.5
12.4
12.2
13.2
13.5
13.3
13.0
12.7
13.1
13.4
12.9
8,700
11,600
15,600
23,400
29,300
35,300
45,100
50,600
57,200
70,800
79,500
PERFORMANCE DATA - ARI/ISO 13256-1 GROUND WATER CONDITIONS*
Unit Model
007
009
012
018
024
Flow Rate
(USGPM)
1.8
2.4
3.0
4.8
6.0
7.8
Air Flow
(SCFM)
260
320
400
640
800
1000
Cooling
Capacity (Btuh)
7,700
10,100
14,200
22,900
28,700
33,600
EER
030
036
042
048
9.0
10.4
12.0
15.0
1200
1400
1600
2000
39,800
45,800
52,500
66,400
18.8
19.1
19.3
19.8
060
070
17.5
2200 73,600
*Ground Water capacities are rated at 59
°
F EWT Cooling, 50
°
F EWT Heating.
18.7
18.4
18.3
18.1
20.2
20.8
20.0
Heating
Capacity (Btuh)
6,900
9,100
12,900
18,800
23,600
29,100
37,200
42,300
47,400
59,000
66,800
PERFORMANCE DATA - ARI/ISO 13256-1 GROUND LOOP CONDITIONS*
Unit Model
007
009
012
018
Flow Rate
(USGPM)
1.8
2.4
3.0
4.8
6.0
Air Flow
(SCFM)
260
320
400
640
800
Cooling
Capacity (Btuh)
7,100
9,300
13,000
20,600
26,400
024
030
036
042
7.8
9.0
10.4
12.0
1000
1200
1400
1600
31,100
37,500
43,900
49,800
048
060
070
15.0
17.5
2000
2200
62,900
70,100
*Ground Loop capacities are rated at 77
°
F EFT Cooling, 32
°
F EFT Heating.
EER
14.6
14.5
14.3
15.7
16.1
15.3
14.8
14.6
15.0
15.6
14.7
Heating
Capacity (Btuh)
5,500
6,900
10,200
13,900
17,400
22,500
28,600
32,300
37,800
47,200
52,400
NOTE:
1) All Cooling capacities based upon 80.6
°
F DB, 66.2
°
F WB entering air temperature.
2) All Heating capacities based upon 68
°
F DB, 59
°
F WB entering air temperature.
COP
3.9
3.8
3.6
3.9
3.8
3.8
3.9
3.9
3.8
4.0
3.8
COP
3.3
3.3
3.4
3.3
3.4
3.3
3.1
3.4
3.3
3.5
3.3
COP
4.5
4.4
4.2
4.5
4.4
4.5
4.6
4.4
4.5
4.6
4.3
Johnson Controls
7
Technical Guide: YK145.00-EG4 (309)
PERFORMANCE DATA
Water Source Heat Pumps
RS*007 — 320 CFM
20
30
40
50
60
70
80
90
1.0
1.4
1.8
1.0
1.4
1.8
1.0
1.4
1.8
1.0
1.4
1.8
1.0
1.4
1.8
1.0
1.4
1.8
1.8
1.0
1.4
1.8
WPD
3.3
4.3
6.5
3.0
3.9
6.0
4.3
5.6
8.5
3.8
4.9
7.5
2.6
3.5
5.3
2.3
3.1
4.7
FT
11.0
4.9
6.4
9.8
6.8
6.9
7.0
6.4
6.5
6.6
7.4
7.6
7.7
7.0
7.2
7.3
8.5
8.7
8.8
8.1
8.3
8.4
7.7
7.8
8.0
SC
5.3
5.3
5.3
5.1
5.1
5.2
5.4
5.5
5.6
5.2
5.3
5.3
6.0
6.1
6.1
5.8
5.9
6.0
5.5
5.6
5.7
COOLING kW
0.56
0.54
0.53
0.65
0.63
0.60
0.44
0.42
0.42
0.50
0.48
0.47
0.30
0.28
0.26
0.34
0.32
0.31
0.36
0.35
0.34
HR
17.0
17.9
18.4
14.0
15.1
15.6
24.1
25.9
26.8
21.5
22.6
23.4
12.2
12.7
13.1
9.9
10.4
11.0
EER HTG
4.1
28.0
30.8
33.7
5.0
5.3
5.4
9.5
9.9
10.3
10.7
11.0
11.2
7.5
7.7
8.2
8.4
8.8
9.0
5.5
5.7
5.9
6.4
6.6
6.9
8.7
8.8
8.8
8.6
8.6
8.6
8.9
9.0
9.1
8.7
8.8
8.9
9.5
9.7
9.7
9.2
9.4
9.5
8.9
9.0
9.2
HEATING
EWT (F) GPM
1.4
1.8
2.8
1.3
1.7
2.6
1.8
2.4
3.7
1.6
2.1
3.3
1.1
1.5
2.3
1.0
1.3
2.0
PSI
4.8
2.1
2.8
4.2
TC
100
1.0
1.4
1.8
1.0
0.9
1.2
1.8
0.8
2.1
2.7
4.2
1.9
5.9
6.1
6.2
5.4
4.9
5.1
5.1
4.6
0.71
0.69
0.67
0.77
0.7
0.7
0.7
0.8
8.3
8.9
9.2
7.0
110
1.4
1.8
1.1
1.6
2.4
3.7
5.6
5.7
4.7
4.7
0.75
0.73
0.8
0.7
7.5
7.8
Cooling Performance is tabulated at 80.6 F DB and 66.2 F WB entering air. Heating performance tabulated at 68 F EAT
Tabulated data does not include ARI/ISO corrections for fan and pump power.
All capacities are expressed in MBH.
Insulated water circuit is recommended for operation below 60F EWT.
See performance correction tables for conditions beyond what is listed.
Extrapolation is not permissible.
Shaded areas indicate conditions where operation is not recommended.
0.51
0.52
0.54
0.57
0.59
0.59
0.47
0.47
0.48
0.50
0.50
0.52
0.60
0.61
0.63
0.65
0.66
0.66
kW
0.44
0.45
0.47
0.47
5.8
5.9
6.3
6.4
6.8
7.0
3.9
4.1
4.3
4.7
4.9
5.1
7.5
7.8
8.1
8.5
8.8
8.9
HE LAT (F) COP
2.6
80 2.7
3.5
3.7
3.8
82
83
84
3.3
3.3
3.4
95
97
98
99
100
100
90
90
92
92
93
94
84
84
85
87
87
88
4.7
4.7
4.8
4.8
4.9
4.9
4.3
4.4
4.4
4.3
4.4
4.5
3.4
3.5
3.6
3.8
3.9
3.9
8
Johnson Controls
Water Source Heat Pumps
PERFORMANCE DATA
Technical Guide: YK145.00-EG4 (309)
RS*009 — 320 CFM
20
30
40
50
60
70
80
90
1.2
1.8
2.4
1.2
1.8
2.4
1.2
1.8
2.4
1.2
1.8
2.4
1.2
1.8
2.4
1.2
1.8
2.4
2.4
1.2
1.8
2.4
WPD
4.0
6.4
9.3
3.7
5.9
8.5
5.2
8.3
12.1
4.6
7.4
10.7
3.2
5.2
7.5
2.9
4.6
6.7
FT
16.1
6.0
9.6
13.9
8.6
8.9
9.2
8.0
8.2
8.4
9.6
9.9
10.1
9.3
9.5
9.7
12.8
13.1
13.2
12.5
12.7
12.9
10.0
10.4
10.6
SC
6.6
6.8
7.0
6.3
6.4
6.6
7.1
7.2
7.3
6.9
7.0
7.1
9.0
9.1
9.1
8.9
9.0
9.2
7.2
7.4
7.5
COOLING kW
0.69
0.66
0.66
0.74
0.70
0.69
0.57
0.56
0.55
0.65
0.60
0.58
0.47
0.43
0.40
0.54
0.51
0.48
0.52
0.48
0.46
HR
16.7
17.8
18.2
14.4
15.8
16.7
23.0
24.8
26.6
19.2
21.7
23.2
12.5
13.4
14.0
10.8
11.7
12.2
EER HTG
5.6
27.4
30.6
33.0
6.1
6.6
6.8
11.8
12.7
13.3
13.4
14.4
14.7
9.5
10.1
10.6
10.2
11.1
11.8
7.0
7.3
7.6
8.3
8.7
9.1
10.9
11.2
11.4
10.5
10.6
10.7
11.6
11.8
12.0
11.5
11.6
11.7
14.4
14.6
14.6
14.4
14.4
14.6
11.8
12.0
12.2
HEATING
EWT (F) GPM
1.7
2.8
4.0
1.6
2.6
3.7
2.3
3.6
5.2
2.0
3.2
4.6
1.4
2.2
3.3
1.2
2.0
2.9
PSI
7.0
2.6
4.1
6.0
TC
100
1.2
1.8
2.4
1.2
1.1
1.8
2.6
1.0
2.6
4.1
5.9
2.3
7.4
7.6
7.8
8.4
6.2
6.3
6.4
7.1
0.80
0.77
0.76
1.08
10.1
10.2
10.4
12.1
9.2
9.9
10.3
7.8
110
1.8
2.4
1.6
2.3
3.7
5.3
8.7
8.9
7.3
7.4
1.04
1.01
12.2
12.4
8.4
8.8
Cooling Performance is tabulated at 80.6 F DB and 66.2 F WB entering air. Heating performance tabulated at 68 F EAT
Tabulated data does not include ARI/ISO corrections for fan and pump power.
All capacities are expressed in MBH.
Insulated water circuit is recommended for operation below 60F EWT.
See performance correction tables for conditions beyond what is listed.
Extrapolation is not permissible.
Shaded areas indicate conditions where operation is not recommended.
0.71
0.74
0.76
0.71
0.76
0.77
0.62
0.63
0.65
0.68
0.69
0.70
0.77
0.79
0.81
0.80
0.83
0.84
kW
0.57
0.74
0.72
0.62
7.1
7.6
8.0
7.8
8.5
9.2
4.9
5.2
5.4
6.0
6.3
6.7
9.2
10.0
10.5
10.7
11.6
11.8
HE LAT (F) COP
3.7
84 2.9
3.6
4.2
4.7
86
87
88
2.4
2.7
3.2
88
89
90
92
93
94
95
97
99
98
100
102
102
105
106
107
110
111
4.5
4.7
4.8
4.9
5.1
5.1
3.9
4.0
4.1
4.2
4.3
4.5
3.3
3.4
3.4
3.6
3.7
3.8
Johnson Controls
9
Technical Guide: YK145.00-EG4 (309)
PERFORMANCE DATA
Water Source Heat Pumps
RS*012 — 400 CFM
20
30
40
50
60
70
80
90
1.5
2.3
3.0
1.5
2.3
3.0
1.5
2.3
3.0
1.5
2.3
3.0
1.5
2.3
3.0
1.5
2.3
3.0
3.0
1.5
2.3
3.0
WPD
3.0
4.1
5.3
2.8
3.8
4.9
3.9
5.3
6.9
3.5
4.7
6.1
2.4
3.3
4.3
2.2
2.9
3.8
FT
9.0
4.5
6.1
7.9
12.1
12.5
12.8
11.8
12.0
12.2
14.9
15.1
14.2
13.1
13.4
13.5
16.9
17.1
17.2
16.2
16.5
16.6
15.5
15.8
15.9
SC
9.4
9.6
9.8
9.3
9.4
9.6
11.0
11.0
10.3
9.8
9.8
9.9
11.8
11.9
11.9
11.6
11.7
11.8
11.2
11.3
11.3
COOLING kW
0.98
0.96
0.95
1.11
1.08
1.06
0.85
0.81
0.79
0.89
0.86
0.84
0.53
0.49
0.48
0.63
0.60
0.58
0.74
0.71
0.69
HR
17.6
18.6
18.0
14.8
15.6
16.1
25.8
27.6
28.7
21.0
22.3
23.1
12.3
13.0
13.5
10.6
11.1
11.5
EER HTG
8.2
32.0
34.7
36.0
9.0
9.5
9.9
14.8
15.6
16.2
16.1
16.9
17.6
12.0
12.5
12.9
14.6
15.1
15.8
9.8
10.2
10.9
11.7
12.3
12.9
15.5
15.8
16.0
15.6
15.7
15.8
17.8
17.9
16.9
16.1
16.3
16.4
18.7
18.8
18.8
18.3
18.5
18.6
18.0
18.2
18.2
HEATING
EWT (F) GPM
1.3
1.8
2.3
1.2
1.6
2.1
1.7
2.3
3.0
1.5
2.0
2.6
1.1
1.4
1.8
0.9
1.3
1.6
PSI
3.9
2.0
2.6
3.4
TC
100
1.5
2.3
3.0
1.5
0.8
1.1
1.5
0.7
1.9
2.6
3.4
1.7
10.9
11.3
11.5
10.0
9.1
9.4
9.5
8.5
1.21
1.19
1.17
1.32
15.0
15.4
15.5
14.5
9.0
9.5
9.8
7.6
110
2.3
3.0
1.0
1.3
2.3
3.0
10.3
10.6
8.7
8.8
1.29
1.28
14.7
15.0
8.0
8.3
Cooling Performance is tabulated at 80.6 F DB and 66.2 F WB entering air. Heating performance tabulated at 68 F EAT
Tabulated data does not include ARI/ISO corrections for fan and pump power.
All capacities are expressed in MBH.
Insulated water circuit is recommended for operation below 60F EWT.
See performance correction tables for conditions beyond what is listed.
Extrapolation is not permissible.
Shaded areas indicate conditions where operation is not recommended.
0.90
0.92
0.92
1.04
1.03
1.08
0.90
0.91
0.97
1.01
1.03
1.05
0.94
0.97
0.99
0.98
0.99
1.01
kW
0.86
0.91
0.93
0.94
8.9
9.4
9.8
11.0
11.6
12.1
6.7
7.1
7.6
8.3
8.8
9.3
11.6
12.3
12.8
12.7
13.5
14.1
HE LAT (F) COP
5.3
87 2.8
5.9
6.3
6.7
89
90
91
2.9
3.0
3.1
91
92
93
95
96
98
96
97
98
102
103
105
102
104
106
105
107
109
4.6
4.7
4.8
4.8
5.0
5.1
3.9
4.0
4.1
4.1
4.3
4.3
3.2
3.3
3.3
3.4
3.5
3.6
10
Johnson Controls
Water Source Heat Pumps
PERFORMANCE DATA
Technical Guide: YK145.00-EG4 (309)
RS*018 — 640 CFM
20
30
40
50
60
70
80
90
2.4
3.6
4.8
2.4
3.6
4.8
2.4
3.6
4.8
2.4
3.6
4.8
2.4
3.6
4.8
2.4
3.6
4.8
4.8
2.4
3.6
4.8
WPD
4.8
7.5
11.3
4.4
6.9
10.4
6.2
9.8
14.7
5.5
8.7
13.0
3.9
6.1
9.1
3.4
5.4
8.1
FT
19.4
7.1
11.3
16.9
18.6
19.3
19.8
17.4
18.1
18.6
21.3
22.0
22.8
20.2
20.5
21.0
26.6
27.3
27.7
24.9
25.6
25.9
24.3
24.5
24.9
SC
14.4
14.8
15.1
13.7
14.2
14.6
15.7
16.1
16.6
15.0
15.1
15.3
18.6
19.1
19.1
17.7
18.0
18.1
17.5
17.5
17.7
COOLING kW
1.44
1.39
1.37
1.55
1.52
1.50
1.22
1.21
1.13
1.34
1.27
1.24
0.96
0.90
0.87
1.05
1.00
0.96
1.15
1.14
1.09
HR
17.4
18.2
20.2
15.1
16.2
17.0
23.8
25.5
27.0
21.1
21.5
22.8
12.9
13.9
14.5
11.2
11.9
12.4
EER HTG
10.4
27.7
30.2
32.0
12.0
12.4
12.7
23.3
24.6
25.4
25.8
27.0
28.1
19.2
20.1
20.8
22.0
23.1
23.9
14.7
15.2
15.7
17.3
18.0
18.8
23.5
24.0
24.5
22.7
23.3
23.7
25.5
26.1
26.7
24.8
24.8
25.2
29.9
30.4
30.7
28.5
29.0
29.2
28.2
28.4
28.6
HEATING
EWT (F) GPM
2.1
3.3
4.9
1.9
3.0
4.5
2.7
4.3
6.4
2.4
3.8
5.6
1.7
2.6
4.0
1.5
2.3
3.5
PSI
8.4
3.1
4.9
7.3
TC
100
2.4
3.6
4.8
2.4
1.3
2.1
3.1
1.2
3.1
4.8
7.2
2.7
16.6
17.2
17.7
15.1
13.8
14.3
14.6
13.1
1.84
1.82
1.79
1.91
22.9
23.4
23.8
21.6
9.7
10.3
10.6
8.4
110
3.6
4.8
1.9
2.8
4.3
6.5
15.8
16.1
13.5
13.5
1.87
1.84
22.2
22.4
8.9
9.2
Cooling Performance is tabulated at 80.6 F DB and 66.2 F WB entering air. Heating performance tabulated at 68 F EAT
Tabulated data does not include ARI/ISO corrections for fan and pump power.
All capacities are expressed in MBH.
Insulated water circuit is recommended for operation below 60F EWT.
See performance correction tables for conditions beyond what is listed.
Extrapolation is not permissible.
Shaded areas indicate conditions where operation is not recommended.
1.41
1.44
1.45
1.47
1.50
1.56
1.23
1.27
1.28
1.33
1.35
1.41
1.48
1.50
1.51
1.49
1.52
1.55
kW
1.09
1.17
1.21
1.20
14.4
15.2
15.8
17.0
18.0
18.6
10.5
10.9
11.3
12.7
13.4
14.0
18.2
19.5
20.2
20.7
21.8
22.8
HE LAT (F) COP
6.7
83 2.8
8.0
8.3
8.6
85
86
86
3.0
3.0
3.1
89
90
91
93
94
95
96
97
98
100
101
103
102
104
105
105
107
109
4.6
4.8
4.9
5.1
5.2
5.3
4.0
4.1
4.2
4.4
4.5
4.5
3.5
3.5
3.6
3.8
3.9
3.9
Johnson Controls
11
Technical Guide: YK145.00-EG4 (309)
PERFORMANCE DATA
Water Source Heat Pumps
RS*024 — 800 CFM
20
30
40
50
60
70
80
90
3.0
4.5
6.0
3.0
4.5
6.0
3.0
4.5
6.0
3.0
4.5
6.0
3.0
4.5
6.0
3.0
4.5
6.0
6.0
3.0
4.5
6.0
WPD
5.3
8.0
12.8
4.9
7.4
11.8
6.9
10.5
16.7
6.1
9.2
14.7
4.3
6.5
10.4
3.8
5.8
9.2
FT
22.4
7.9
12.0
19.1
24.8
25.1
26.0
23.1
23.9
24.4
27.8
28.4
29.0
27.2
28.0
28.5
35.1
35.9
36.4
33.4
34.3
34.8
31.4
32.2
32.8
SC
19.2
19.3
19.9
18.2
18.8
19.1
20.4
20.7
21.1
20.3
20.6
20.8
24.6
25.0
25.2
23.9
24.4
24.7
22.6
23.0
23.3
COOLING kW
1.77
1.70
1.70
1.96
1.90
1.86
1.49
1.48
1.45
1.64
1.60
1.56
1.07
1.01
0.99
1.13
1.07
1.04
1.30
1.23
1.21
HR
18.7
19.2
20.0
16.6
17.5
18.3
29.5
32.1
33.4
24.2
26.1
27.0
14.0
14.8
15.3
11.8
12.6
13.1
EER HTG
13.3
32.7
35.4
36.8
15.9
16.4
16.8
31.5
31.8
33.0
32.1
33.9
35.3
25.1
26.4
27.4
27.8
29.3
30.4
18.4
19.1
19.7
21.6
22.6
23.6
30.8
30.9
31.8
29.8
30.4
30.8
32.9
33.4
33.9
32.8
33.5
33.8
38.8
39.4
39.8
37.3
37.9
38.4
35.8
36.4
36.9
HEATING
EWT (F) GPM
2.3
3.5
5.5
2.1
3.2
5.1
3.0
4.5
7.2
2.6
4.0
6.4
1.8
2.8
4.5
1.6
2.5
4.0
PSI
9.7
3.4
5.2
8.3
TC
100
3.0
4.5
6.0
3.0
1.5
2.2
3.5
1.3
3.4
5.1
8.2
3.0
20.6
21.6
22.1
18.7
17.2
17.9
18.3
15.9
2.06
2.04
2.01
2.17
27.6
28.6
29.0
26.1
10.0
10.6
11.0
8.6
110
4.5
6.0
2.0
3.2
4.6
7.3
19.5
20.0
16.4
16.6
2.14
2.13
26.8
27.3
9.1
9.4
Cooling Performance is tabulated at 80.6 F DB and 66.2 F WB entering air. Heating performance tabulated at 68 F EAT
Tabulated data does not include ARI/ISO corrections for fan and pump power.
All capacities are expressed in MBH.
Insulated water circuit is recommended for operation below 60F EWT.
See performance correction tables for conditions beyond what is listed.
Extrapolation is not permissible.
Shaded areas indicate conditions where operation is not recommended.
1.71
1.72
1.78
1.77
1.83
1.86
1.59
1.60
1.60
1.71
1.79
1.82
1.85
1.86
1.90
1.84
1.91
1.95
kW
1.50
1.50
1.50
1.54
19.3
20.5
21.3
21.8
23.1
24.1
13.0
13.6
14.2
15.8
16.5
17.4
25.2
25.4
26.5
25.8
27.4
28.6
HE LAT (F) COP
8.2
83 2.6
10.8
11.3
11.6
86
87
87
3.1
3.2
3.2
89
90
91
93
94
95
97
99
100
100
102
103
104
105
106
105
107
109
5.0
5.0
5.1
5.1
5.2
5.3
4.3
4.5
4.5
4.6
4.7
4.8
3.4
3.5
3.6
3.7
3.7
3.8
12
Johnson Controls
Water Source Heat Pumps
PERFORMANCE DATA
Technical Guide: YK145.00-EG4 (309)
RS*030 — 1000 CFM
20
30
40
50
60
70
80
90
3.9
5.8
7.8
3.9
5.8
7.8
3.9
5.8
7.8
3.9
5.8
7.8
3.9
5.8
7.8
3.9
5.8
7.8
7.8
3.9
5.8
7.8
WPD
6.5
8.3
10.3
6.0
7.6
9.5
8.5
10.8
13.4
7.5
9.5
11.8
5.3
6.7
8.3
4.7
5.9
7.4
FT
18.0
9.8
12.4
15.4
29.0
29.7
30.2
28.0
28.7
29.2
32.1
32.9
33.5
31.0
31.8
32.3
38.6
39.5
40.0
37.1
38.0
38.6
34.4
35.2
35.8
SC
22.4
22.8
23.1
22.1
22.5
22.9
23.6
24.0
24.4
23.1
23.4
23.6
27.0
27.5
27.7
26.5
27.1
27.4
24.8
25.2
25.4
COOLING kW
2.04
2.01
2.00
2.33
2.30
2.28
1.75
1.70
1.70
1.86
1.82
1.80
1.43
1.41
1.39
1.53
1.49
1.48
1.65
1.62
1.55
HR
18.3
19.3
19.7
16.7
17.5
17.9
24.2
25.5
26.1
20.8
21.7
23.1
14.2
14.8
15.1
12.0
12.5
12.8
EER HTG
17.5
26.9
28.0
28.7
19.2
20.3
22.0
36.4
38.2
39.7
40.7
42.8
44.5
29.5
30.9
32.0
33.1
34.7
36.0
22.3
23.2
23.9
27.1
28.2
29.1
36.0
36.5
37.0
36.0
36.5
37.0
38.1
38.7
39.3
37.3
38.0
38.5
43.5
44.3
44.8
42.3
43.1
43.6
40.0
40.7
41.1
HEATING
EWT (F) GPM
2.8
3.6
4.4
2.6
3.3
4.1
3.7
4.7
5.8
3.3
4.1
5.1
2.3
2.9
3.6
2.0
2.6
3.2
PSI
7.8
4.2
5.4
6.7
TC
100
3.9
5.8
7.8
3.9
1.8
2.3
2.9
1.6
4.2
5.3
6.6
3.7
25.8
26.5
27.0
23.6
21.5
22.0
22.3
20.1
2.50
2.45
2.45
2.65
34.3
34.9
35.4
32.7
10.3
10.8
11.0
8.9
110
5.8
7.8
2.1
2.6
4.8
5.9
24.3
24.7
20.5
20.5
2.64
2.63
33.3
33.7
9.2
9.4
Cooling Performance is tabulated at 80.6 F DB and 66.2 F WB entering air. Heating performance tabulated at 68 F EAT
Tabulated data does not include ARI/ISO corrections for fan and pump power.
All capacities are expressed in MBH.
Insulated water circuit is recommended for operation below 60F EWT.
See performance correction tables for conditions beyond what is listed.
Extrapolation is not permissible.
Shaded areas indicate conditions where operation is not recommended.
2.11
2.16
2.18
2.20
2.26
2.34
1.87
1.94
1.95
2.15
2.23
2.24
2.32
2.38
2.42
2.43
2.51
2.56
kW
1.97
1.88
1.92
2.01
22.3
23.5
24.6
25.6
27.0
28.0
15.9
16.6
17.3
19.8
20.6
21.4
28.5
30.1
31.4
32.4
34.2
35.8
HE LAT (F) COP
10.8
84 2.6
12.8
13.8
15.1
86
87
88
3.0
3.1
3.2
89
89
90
93
94
95
95
97
98
99
100
101
102
103
105
106
108
109
4.6
4.7
4.8
4.9
5.0
5.1
4.1
4.2
4.3
4.4
4.5
4.5
3.5
3.5
3.6
3.7
3.7
3.8
Johnson Controls
13
Technical Guide: YK145.00-EG4 (309)
PERFORMANCE DATA
Water Source Heat Pumps
RS*036 — 1200 CFM
20
30
40
50
60
70
80
90
4.5
6.8
9.0
4.5
6.8
9.0
4.5
6.8
9.0
4.5
6.8
9.0
4.5
6.8
9.0
4.5
6.8
9.0
9.0
4.5
6.8
9.0
WPD
5.3
9.8
13.3
4.9
9.0
12.2
6.9
12.8
17.3
6.1
11.3
15.3
4.3
7.9
10.8
3.8
7.0
9.5
FT
23.3
7.9
14.6
19.9
36.1
36.5
37.1
34.9
35.4
35.6
38.0
38.9
39.6
34.4
35.3
36.0
45.6
47.5
48.8
44.0
45.0
45.7
41.7
42.8
43.3
SC
27.9
28.0
28.3
27.5
27.7
27.9
27.9
28.4
28.8
25.6
25.9
26.3
31.9
33.1
33.8
31.5
32.0
32.4
30.0
30.6
30.7
COOLING kW
2.56
2.50
2.69
2.96
2.90
2.87
1.84
1.79
1.77
2.02
1.97
1.96
1.27
1.26
1.26
1.44
1.40
1.38
1.72
1.67
1.64
HR
20.7
21.8
22.4
17.0
17.9
18.4
30.6
32.2
33.1
24.3
25.7
26.4
14.1
14.6
13.8
11.8
12.2
12.4
EER HTG
19.9
35.9
37.8
38.8
23.2
24.0
24.5
46.7
49.1
50.4
50.8
53.6
55.6
37.6
39.5
40.8
41.5
43.7
45.3
28.2
29.4
30.2
34.0
35.6
37.2
44.8
45.0
46.3
45.0
45.2
45.4
44.3
45.0
45.6
41.3
42.0
42.7
49.9
51.8
53.1
48.9
49.8
50.4
47.6
48.5
48.9
HEATING
EWT (F) GPM
2.3
4.2
5.7
2.1
3.9
5.3
3.0
5.5
7.5
2.6
4.9
6.6
1.8
3.4
4.7
1.6
3.0
4.1
PSI
10.1
3.4
6.3
8.6
TC
100
4.5
6.8
9.0
4.5
1.5
2.7
3.7
1.3
3.4
6.3
8.5
3.0
32.8
33.3
33.5
31.7
27.4
27.6
27.6
26.9
3.16
3.11
3.10
3.37
43.6
43.9
44.0
43.2
10.4
10.7
10.8
9.4
110
6.8
9.0
2.4
3.3
5.6
7.6
32.1
32.4
27.1
26.9
3.31
3.30
43.4
43.6
9.7
9.8
Cooling Performance is tabulated at 80.6 F DB and 66.2 F WB entering air. Heating performance tabulated at 68 F EAT
Tabulated data does not include ARI/ISO corrections for fan and pump power.
All capacities are expressed in MBH.
Insulated water circuit is recommended for operation below 60F EWT.
See performance correction tables for conditions beyond what is listed.
Extrapolation is not permissible.
Shaded areas indicate conditions where operation is not recommended.
2.50
2.57
2.66
2.64
2.72
2.77
2.23
2.27
2.33
2.43
2.48
2.58
2.85
2.94
3.04
2.98
3.08
3.13
kW
1.94
2.06
2.13
2.11
29.1
30.7
31.7
32.5
34.4
35.9
20.6
21.7
22.3
25.7
27.1
28.4
37.0
39.1
40.0
40.6
43.1
44.9
HE LAT (F) COP
2.0
83 3.0
16.2
16.7
17.3
86
86
87
3.3
3.3
3.4
90
91
91
94
95
97
97
98
99
100
102
103
104
106
107
107
109
111
4.8
4.9
4.9
5.0
5.1
5.2
4.4
4.5
4.5
4.6
4.7
4.8
3.7
3.8
3.8
4.1
4.2
4.2
14
Johnson Controls
Water Source Heat Pumps
PERFORMANCE DATA
Technical Guide: YK145.00-EG4 (309)
RS*042 — 1400 CFM
20
30
40
50
60
70
80
90
5.2
7.8
10.4
5.2
7.8
10.4
5.2
7.8
10.4
5.2
7.8
10.4
10.4
5.2
7.8
10.4
5.2
7.8
10.4
5.2
7.8
10.4
WPD
6.3
10.3
16.3
5.8
9.5
15.0
8.2
13.4
21.3
7.2
11.8
18.8
5.1
8.3
13.2
4.5
7.4
11.7
FT
28.4
9.4
15.4
24.4
42.7
43.5
44.0
40.5
41.4
41.9
44.3
45.0
45.4
43.5
45.6
46.1
48.6
49.1
50.0
47.2
47.8
48.1
45.8
46.5
46.9
SC
33.0
33.4
33.6
32.0
32.5
32.8
32.6
32.9
33.0
32.4
33.5
33.7
34.0
34.2
34.6
33.7
34.0
34.2
33.0
33.2
33.3
COOLING kW
3.46
3.32
3.23
3.91
3.74
3.64
2.76
2.65
2.58
3.06
2.96
2.89
1.97
1.86
1.80
2.22
2.12
2.05
2.39
2.38
2.31
HR
16.0
17.0
17.6
14.2
15.4
16.0
21.2
22.5
23.4
18.4
19.5
20.3
12.4
13.1
13.6
10.4
11.1
11.5
EER HTG
26.7
24.7
26.4
27.6
31.2
31.9
32.2
55.5
58.1
60.1
61.1
63.6
65.9
44.0
45.7
47.0
48.9
51.1
52.7
35.5
36.5
37.3
39.3
40.7
42.3
54.5
54.8
55.0
53.8
54.2
54.3
53.7
54.0
54.2
53.9
55.7
56.0
55.3
55.4
56.1
54.8
55.0
55.1
54.0
54.6
54.7
HEATING
EWT (F) GPM
2.7
4.4
7.0
2.5
4.1
6.5
3.5
5.8
9.2
3.1
5.1
8.1
2.2
3.6
5.7
1.9
3.2
5.1
PSI
12.3
4.1
6.7
10.6
TC
100
5.2
7.8
10.4
5.2
1.7
2.9
4.5
1.6
4.0
6.6
10.4
3.6
38.1
39.0
39.6
36.2
31.8
32.3
32.7
30.8
4.36
4.17
4.06
4.89
53.0
53.2
53.5
52.9
8.7
9.4
9.8
7.3
110
7.8
10.4
2.6
4.1
5.9
9.4
37.1
37.8
31.3
31.4
4.67
4.54
53.0
53.3
7.8
8.2
Cooling Performance is tabulated at 80.6 F DB and 66.2 F WB entering air. Heating performance tabulated at 68 F EAT
Tabulated data does not include ARI/ISO corrections for fan and pump power.
All capacities are expressed in MBH.
Insulated water circuit is recommended for operation below 60F EWT.
See performance correction tables for conditions beyond what is listed.
Extrapolation is not permissible.
Shaded areas indicate conditions where operation is not recommended.
3.52
3.55
3.57
3.61
3.65
3.68
3.36
3.38
3.39
3.44
3.46
3.48
3.71
3.76
3.80
3.82
3.89
3.94
kW
3.32
3.30
3.31
3.32
32.0
33.6
34.8
36.6
38.6
40.1
24.0
25.0
25.7
27.6
28.9
30.4
42.8
45.3
47.1
48.1
50.3
52.5
HE LAT (F) COP
15.4
86 2.5
19.9
20.6
20.9
89
89
89
2.8
2.8
2.8
91
92
93
94
95
96
97
98
99
100
102
103
105
106
108
108
110
112
4.4
4.5
4.6
4.7
4.8
4.9
3.7
3.8
3.9
4.0
4.1
4.2
3.1
3.2
3.2
3.4
3.4
3.6
Johnson Controls
15
Technical Guide: YK145.00-EG4 (309)
PERFORMANCE DATA
Water Source Heat Pumps
RS*048 — 1600 CFM
20
30
40
50
60
70
80
90
6.0
9.0
12.0
6.0
9.0
12.0
6.0
9.0
12.0
6.0
9.0
12.0
12.0
6.0
9.0
12.0
6.0
9.0
12.0
6.0
9.0
12.0
WPD
6.8
13.0
20.3
6.2
12.0
18.7
8.8
17.0
26.5
7.8
15.0
23.4
5.5
10.6
16.5
4.9
9.4
14.6
FT
34.9
10.1
19.5
30.4
48.1
48.6
49.4
46.4
47.2
47.7
51.1
51.7
52.3
49.8
50.2
50.8
61.3
62.2
62.8
58.0
58.8
59.4
55.4
56.5
57.6
SC
37.2
37.3
37.7
36.7
37.1
37.3
37.6
37.7
38.0
37.1
36.9
37.1
42.9
43.4
43.5
41.5
41.9
42.2
39.9
40.4
40.9
COOLING kW
3.98
3.78
3.66
4.51
4.26
4.12
2.97
2.82
2.73
3.39
3.26
3.11
2.33
2.29
2.27
2.46
2.40
2.37
2.69
2.62
2.50
HR
17.2
18.3
19.2
14.7
15.4
16.3
23.6
24.5
25.1
20.6
21.6
23.0
12.1
12.9
13.5
10.3
11.1
11.6
EER HTG
30.5
26.3
27.2
27.7
33.4
35.6
36.7
63.2
64.6
67.2
70.3
72.4
73.3
51.1
53.1
54.6
58.8
59.8
61.3
39.8
41.5
43.6
44.2
45.8
47.4
61.7
61.5
61.9
61.8
61.7
61.8
61.2
61.3
61.6
61.4
61.3
61.4
69.3
70.0
70.5
66.4
67.0
67.5
64.6
65.4
66.1
HEATING
EWT (F) GPM
2.9
5.6
8.8
2.7
5.2
8.1
3.8
7.4
11.5
3.4
6.5
10.1
2.4
4.6
7.1
2.1
4.1
6.3
PSI
15.1
4.4
8.5
13.2
TC
100
6.0
9.0
12.0
6.0
1.9
3.6
5.6
1.7
4.3
8.4
13.0
3.9
43.6
45.0
45.9
39.9
36.4
37.3
37.9
33.9
5.05
4.76
4.59
5.70
60.8
61.2
61.6
59.4
8.6
9.5
10.0
7.0
110
9.0
12.0
3.2
5.0
7.5
11.7
41.3
42.2
34.8
35.0
5.36
5.16
59.6
59.8
7.7
8.2
Cooling Performance is tabulated at 80.6 F DB and 66.2 F WB entering air. Heating performance tabulated at 68 F EAT
Tabulated data does not include ARI/ISO corrections for fan and pump power.
All capacities are expressed in MBH.
Insulated water circuit is recommended for operation below 60F EWT.
See performance correction tables for conditions beyond what is listed.
Extrapolation is not permissible.
Shaded areas indicate conditions where operation is not recommended.
3.62
3.65
3.70
3.84
3.87
3.90
3.33
3.38
3.55
3.63
3.66
3.68
4.05
4.11
4.16
4.28
4.32
4.34
kW
3.32
3.30
3.32
3.34
3.6
3.7
3.7
3.8
3.9
3.9
3.6
3.6
3.6
3.6
3.7
3.7
4.1
4.1
4.2
4.3
4.3
4.3
HE LAT (F) COP
19.1
86 2.8
3.3
3.3
3.3
88
89
89
3.0
3.1
3.2
91
92
93
94
95
95
97
98
99
100
101
102
103
105
106
107
108
109
4.6
4.6
4.7
4.8
4.9
4.9
4.1
4.3
4.3
4.5
4.5
4.6
3.5
3.6
3.6
3.6
3.7
3.8
16
Johnson Controls
Water Source Heat Pumps
PERFORMANCE DATA
Technical Guide: YK145.00-EG4 (309)
RS*060 — 2000 CFM
20
30
40
50
60
70
80
90
7.5
11.2
15.0
7.5
11.2
15.0
7.5
11.2
15.0
7.5
11.2
15.0
15.0
7.5
11.2
15.0
7.5
11.2
15.0
7.5
11.2
15.0
WPD
9.0
11.5
24.0
8.3
10.6
22.2
11.8
15.1
31.4
10.4
13.3
27.7
7.3
9.3
19.5
6.5
8.3
17.3
FT
41.1
13.5
17.3
36.0
59.4
60.8
61.7
56.9
57.5
58.4
63.3
65.6
66.4
62.5
63.8
64.7
72.6
73.8
74.5
68.9
70.1
71.9
66.2
67.5
68.2
SC
45.9
46.6
47.1
45.0
45.1
45.7
46.5
47.9
48.3
46.6
46.9
47.2
50.8
51.4
51.6
49.3
49.9
51.0
47.7
48.3
48.4
COOLING kW
4.84
4.60
4.46
5.33
5.20
5.05
3.85
3.67
3.35
4.38
4.18
3.90
2.77
2.60
2.48
3.25
3.08
2.96
3.60
3.43
3.32
HR
16.4
17.9
19.8
14.3
15.3
16.6
21.2
22.8
24.3
18.4
19.7
20.5
12.3
13.2
13.8
10.7
11.1
11.6
EER HTG
38.2
26.2
28.4
30.0
43.2
45.2
46.0
73.2
78.1
82.3
84.2
88.6
93.5
61.4
63.4
64.9
66.3
69.8
72.9
50.3
52.0
53.5
54.2
56.8
59.0
75.9
76.5
76.9
75.1
75.2
75.6
76.4
78.1
77.8
77.4
78.1
78.0
82.1
82.7
83.0
80.0
80.6
82.0
78.5
79.2
79.5
HEATING
EWT (F) GPM
3.9
5.0
10.4
3.6
4.6
9.6
5.1
6.5
13.6
4.5
5.8
12.0
3.2
4.0
8.4
2.8
3.6
7.5
PSI
17.8
5.9
7.5
15.6
TC
100
7.5
11.2
15.0
7.5
2.5
3.2
6.7
2.5
5.8
7.4
15.4
5.7
51.9
53.6
54.5
48.6
43.3
44.4
45.0
41.3
6.04
5.75
5.57
6.65
72.5
73.2
73.5
71.3
8.6
9.3
9.8
7.3
110
11.2
15.0
3.2
6.6
7.3
15.2
49.2
50.3
41.5
41.7
6.41
6.21
71.1
71.5
7.7
8.1
Cooling Performance is tabulated at 80.6 F DB and 66.2 F WB entering air. Heating performance tabulated at 68 F EAT
Tabulated data does not include ARI/ISO corrections for fan and pump power.
All capacities are expressed in MBH.
Insulated water circuit is recommended for operation below 60F EWT.
See performance correction tables for conditions beyond what is listed.
Extrapolation is not permissible.
Shaded areas indicate conditions where operation is not recommended.
4.39
4.44
4.47
4.52
4.56
4.62
4.05
4.12
4.17
4.21
4.28
4.35
4.70
4.84
5.01
5.09
5.25
5.37
kW
3.32
3.90
3.96
4.00
46.4
48.2
49.6
50.9
54.2
57.1
36.5
37.9
39.3
39.8
42.2
44.2
57.2
61.6
65.2
66.8
70.7
75.2
HE LAT (F) COP
26.8
86 2.9
29.9
31.7
32.3
88
89
89
3.2
3.3
3.4
91
92
93
93
94
95
96
97
98
99
100
102
102
104
106
107
109
111
4.6
4.7
4.8
4.8
4.9
5.1
4.1
4.2
4.3
4.3
4.5
4.6
3.6
3.7
3.8
3.8
3.9
4.0
Johnson Controls
17
Technical Guide: YK145.00-EG4 (309)
PERFORMANCE DATA
Water Source Heat Pumps
RS*070 — 2200 CFM
20
30
40
50
60
70
80
90
8.8
13.1
17.5
8.8
13.1
17.5
8.8
13.1
17.5
8.8
13.1
17.5
17.5
8.8
13.1
17.5
8.8
13.1
17.5
8.8
13.1
17.5
WPD
12.8
19.3
25.3
11.8
17.8
23.3
16.7
25.2
33.1
14.7
22.2
29.2
10.4
15.6
20.5
9.2
13.9
18.2
FT
48.0
19.1
28.9
37.9
66.7
68.2
69.2
63.5
64.3
65.3
71.4
72.6
73.0
73.1
74.5
75.4
82.7
83.4
83.8
79.0
79.9
80.5
75.1
76.2
76.9
SC
51.6
52.3
52.9
50.2
50.5
51.1
52.5
53.0
53.1
54.5
54.8
55.0
57.9
58.1
58.0
56.5
56.9
57.2
54.1
54.5
54.6
COOLING kW
5.09
4.91
4.81
5.62
5.31
5.27
4.30
4.20
4.01
4.87
4.72
4.71
3.22
3.14
3.14
3.85
3.68
3.56
3.99
3.95
3.85
HR
16.6
17.3
18.2
15.0
15.8
16.0
20.5
21.7
22.6
18.8
19.3
20.0
13.1
13.9
14.4
11.3
12.1
12.4
EER HTG
42.1
25.7
26.6
26.7
47.9
49.4
50.7
82.0
85.8
88.9
90.8
95.4
99.0
67.9
70.6
72.7
75.0
78.3
80.8
54.8
56.6
58.1
62.4
65.2
66.8
84.1
84.9
85.6
82.7
82.4
83.3
86.1
86.9
86.7
89.7
90.6
91.5
93.7
94.1
94.5
92.1
92.5
92.7
88.7
89.7
90.0
HEATING
EWT (F) GPM
5.5
8.3
10.9
5.1
7.7
10.1
7.2
10.9
14.3
6.4
9.6
12.6
4.5
6.8
8.9
4.0
6.0
7.9
PSI
20.8
8.3
12.5
16.4
TC
100
8.8
13.1
17.5
8.8
3.5
5.4
7.0
3.5
8.2
12.4
16.2
8.1
59.0
60.8
61.9
54.7
49.2
50.4
51.1
46.5
6.02
5.79
5.73
6.59
79.5
80.6
81.5
77.2
9.8
10.5
10.8
8.3
110
13.1
17.5
5.3
6.9
12.2
16.0
56.7
57.9
47.8
48.1
6.37
6.29
78.4
79.4
8.9
9.2
Cooling Performance is tabulated at 80.6 F DB and 66.2 F WB entering air. Heating performance tabulated at 68 F EAT
Tabulated data does not include ARI/ISO corrections for fan and pump power.
All capacities are expressed in MBH.
Insulated water circuit is recommended for operation below 60F EWT.
See performance correction tables for conditions beyond what is listed.
Extrapolation is not permissible.
Shaded areas indicate conditions where operation is not recommended.
5.10
5.17
5.33
5.21
5.31
5.44
4.93
5.01
5.08
5.02
5.11
5.16
5.28
5.47
5.54
5.39
5.59
5.69
kW
3.32
4.86
4.92
4.98
50.5
53.0
54.5
57.2
60.2
62.2
38.0
39.5
40.8
45.3
47.8
49.2
64.0
67.1
70.0
72.4
76.3
79.6
HE LAT (F) COP
30.7
86 2.6
31.3
32.6
33.7
88
89
89
2.9
2.9
3.0
91
92
92
94
95
96
97
98
99
100
101
102
103
104
105
106
108
110
4.6
4.6
4.7
4.9
5.0
5.1
3.9
4.0
4.0
4.2
4.3
4.4
3.3
3.3
3.4
3.6
3.7
3.8
18
Johnson Controls
Water Source Heat Pumps
CORRECTION FACTORS
ANTIFREEZE CORRECTION TABLE
Ethylene Glycol
Propylene Glycol
Methanol
Cooling
Heating
PD
Cooling
Heating
PD
Cooling
Heating
PD
5%
0.998
0.995
1.040
0.995
0.989
1.035
0.999
0.989
1.050
10%
0.995
0.990
1.055
0.992
0.982
1.055
0.995
0.985
1.072
Technical Guide: YK145.00-EG4 (309)
Antifreeze Concentration
15%
0.993
0.985
1.080
0.987
0.975
1.100
0.990
0.979
1.094
20%
0.991
0.980
1.105
0.983
0.967
1.145
0.986
0.971
1.116
25%
0.989
0.974
1.135
0.979
0.958
1.200
0.982
0.963
1.140
30%
0.987
0.969
1.165
0.975
0.951
1.260
0.980
0.954
1.165
40%
0.984
0.964
1.210
0.970
0.943
1.320
0.978
0.946
1.196
AIRFLOW CORRECTION TABLE
Cooling
Airflow %
90
95
100
105
110
70
75
80
85
115
TC
0.931
0.941
0.950
0.966
0.977
0.989
1.000
1.008
1.018
1.026
SC
0.847
0.872
0.896
0.923
0.948
0.974
1.000
1.025
1.048
1.070
Power
0.964
0.969
0.979
0.983
0.989
0.995
1.000
1.006
1.013
1.019
THR
0.946
0.956
0.961
0.971
0.981
0.990
1.000
1.010
1.017
1.026
HC
0.942
0.953
0.960
0.970
0.979
0.989
1.000
1.009
1.019
1.029
Heating
Power
1.075
1.059
1.039
1.023
1.015
1.007
1.000
0.994
0.992
0.991
HE
0.940
0.949
0.958
0.969
0.979
0.989
1.000
1.010
1.018
1.028
COOLING PERFORMANCE CORRECTION TABLE
Entering Air
WB (F)
60
65
66.2
70
75
Total Clg
Capacity
0.845
0.948
1
1.061
1.162
70
0.86
0.628
0.539
S = Sensible cooling is equal to Total Cooling
Entering Air DB (F) - Sensible Capacity
75
1.1
0.865
0.777
0.631
80.6
1.305
1.082
1
0.855
0.618
85
S
1.312
1.22
1.081
0.848
90
S
S
1.475
1.331
1.09
95
S
S
S
1.543
1.296
Heat
Rejection
0.904
0.979
1
1.039
1.107
HEATING PERFORMANCE CORRECTION TABLE
EAT DB (F)
45
50
55
60
65
68
70
75
80
Heating Capacity
1.101
1.080
1.059
1.039
1.019
1.000
0.990
0.974
0.951
Johnson Controls
Power
0.785
0.832
0.878
0.926
0.960
1.000
1.028
1.064
1.111
Heat Extraction
1.162
1.125
1.079
1.064
1.023
1.000
0.983
0.957
0.918
19
Technical Guide: YK145.00-EG4 (309)
BLOWER PERFORMANCE
Water Source Heat Pumps
BLOWER PERFORMANCE
Unit
Size
007
009
012
018
024
030
036
042
048
Rated
CFM
260
320
400
640
800
1000
1200
1400
1600
Min.
CFM
182
235
300
495
560
730
865
980
1160
Max.
CFM
299
368
460
736
920
1150
1380
1480
1880
Motor
Speed
High
Med
Low
High
Med
Low
High
Med
Low
High
Med
Low
High
Med
Low
High
Med
Low
High
Med
Low
High
Med
Low
High
Med
Low
High
0
-
-
275
-
340
-
-
470
385
-
690
600
-
925
810
-
1150
980
-
1355
1200
-
1370
1480
-
1880
1495
-
0.1
-
-
260
-
325
-
475
455
370
750
660
570
-
905
795
-
1125
970
1390
1320
1190
1175
1320
1410
-
1860
1490
2320
0.2
-
300
240
380
300
-
450
430
355
710
625
535
-
875
780
1170
1090
955
1330
1270
1170
1160
1275
1350
-
External Static Pressure (in w.g.)
1820
1485
2260
060
2000 1560 2300 Med
Low
High
Med
2040
1760
2400
2040
2030
1750
2320
2030
2005
1730
2260
2005
070
2200 1700 2400
Low -
Units are shipped pre-wired for Medium speed.
All airflow ratings are at lowest voltage rating of dual rating (ie. 208 volt)
Airflow ratings include resistance of wet coil and clean air filters.
0.3
-
270
210
360
270
-
420
400
330
660
585
495
950
840
765
1120
1045
935
1270
1215
1130
1120
1210
1290
1915
1770
1480
2200
1970
1700
2200
1970
-
0.4
1925
1660
2120
1925
-
-
235
180
330
235
-
385
365
300
610
540
-
890
790
725
1060
990
905
1210
1155
1085
1075
1150
1220
1835
1710
1460
2120
0.5
-
200
-
290
-
-
345
325
-
555
490
-
820
730
660
985
925
855
1140
1085
1020
1015
1070
1140
1750
1640
1420
2040
1860
1610
2040
1860
-
925
1050
1660
1550
1360
1920
850
785
1055
1005
950
930
-
-
740
660
590
905
-
-
300
-
-
495
0.6
-
-
-
240
1785
1560
1920
1785
-
-
950
1550
1450
1285
1840
765
-
960
920
-
-
1700
-
1840
1700
-
-
-
650
590
-
820
-
-
-
-
-
-
0.7
-
-
-
-
-
-
1415
1320
1160
1700
865
-
-
-
-
-
1610
-
1700
-
-
-
-
550
-
-
730
-
-
-
-
-
-
0.8
-
-
-
-
20
Johnson Controls
Water Source Heat Pumps
ELECTRICAL DATA
Technical Guide: YK145.00-EG4 (309)
RSH/RSV ELECTRICAL DATA
Unit Size
007
009
012
018
024
030
036
042
048
060
070
QTY
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
SUPPLY
VOLTAGE
208-230/1/60
208-230/1/60
208-230/1/60
265/1/60
208-230/1/60
265/1/60
208-230/1/60
265/1/60
208-230/3/60
208-230/1/60
265/1/60
208-230/3/60
208-230/1/60
265/1/60
208-230/3/60
460/3/60
208-230/1/60
208-230/3/60
460/3/60
575/3/60
208-230/1/60
208-230/3/60
460/3/60
575/3/60
208-230/1/60
208-230/3/60
460/3/60
575/3/60
208-230/3/60
460/3/60
575/3/60
COMPRESSOR
RLA
11.6
8.7
4.3
19.9
13.6
6.1
7.0
6.1
10.1
8.7
7.2
13.5
4.2
23.1
16.0
7.1
5.6
3.4
4.6
5.6
4.6
6.9
6.1
8.2
26.3
15.6
7.8
5.8
19.0
9.7
7.4
@
@
@
@
@
@
@
@
@
@
@
@
@
@
@
@
@
@
@
@
@
@
@
@
@
@
@
@
@
@
@
LRA
79.0
78.0
40.0
109.0
81.0
41.0
44.0
58.0
60.0
58.0
58.0
83.0
33.0
144.0
91.0
46.0
37.0
22.0
28.0
29.0
20.0
48.0
44.0
48.0
134.0
110.0
52.0
38.9
123.0
62.0
50.0
BLOWER
HP
0.50
0.50
0.50
0.50
0.50
0.50
0.25
0.25
0.33
0.33
0.33
0.50
0.50
0.75
0.75
0.75
0.75
0.10
0.10
0.13
0.13
0.17
0.17
0.25
1.00
1.00
1.00
1.00
1.00
1.00
1.00
FLA
2.2
3.2
2.5
3.2
3.2
2.5
1.3
1.3
2.6
1.9
2.6
3.2
1.8
4.9
4.9
2.2
1.8
0.8
0.8
1.0
0.9
1.4
0.8
1.5
5.1
5.1
3.2
2.6
5.1
3.2
2.6
MAX FUSE /
CCT. BKR. AMP
25
20
15
45
30
15
15
15
25
20
15
30
15
50
40
15
15
15
15
15
15
15
15
15
60
40
20
15
45
25
15
MIN. CCT.
AMPACITY
16.70
14.08
7.88
28.08
20.20
10.13
10.05
8.93
15.23
12.78
11.60
20.08
5.05
6.55
8.00
6.65
10.03
8.43
11.75
7.05
33.78
24.90
11.08
8.80
37.98
24.60
12.95
9.85
28.85
15.33
11.85
Johnson Controls
21
Technical Guide: YK145.00-EG4 (309)
DIMENSIONAL DATA
E
B
LEFT HAND RETURN
RETURN
AIR
Ø0.875"
G
RSH SERIES
OPTIONAL
SIDE
DISCHARGE
TOP
VIEW
OPTIONAL
SIDE
DISCHARGE
Water Source Heat Pumps
RIGHT HAND RETURN
RETURN
AIR
G
Ø0.875"
B
E
0.75"
TYP
D
A
SUPPLY
AIR
L K
K L
SUPPLY
AIR
D
A
0.75"
TYP
C
ELEVATION
VIEW
2
C
2
0.75"
2.00"
POWER
CONNECTION
WATER OUT
1.63"
POWER
CONNECTION
WATER OUT
2.00"
0.75"
J
M
FRONT
VIEW
M
1 J
1
1.50"
N
WATER IN
LOW VOLTAGE
CONNECTION
1.81"
Model A B
RSH007
34.00
RSH009
34.00
RSH012
34.00
RSH018
40.00
RSH024
44.00
RSH030
44.00
RSH036
48.00
RSH042
52.00
RSH048
52.00
RSH060
56.00
19.00
19.00
19.00
21.00
21.00
21.00
22.00
26.00
26.00
26.00
RSH070
56.00
26.00
ALL DIMENSIONS IN INCHES
22
3
3/4 FPT
DRAIN
C
13.00
13.00
13.00
19.00
19.00
19.00
21.00
21.00
21.00
23.00
23.00
BACK
VIEW
D
31.75
31.75
31.75
37.75
41.75
41.75
45.75
49.75
49.75
53.75
53.75
E
21.50
21.50
21.50
23.50
23.50
23.50
24.50
28.50
28.50
28.50
28.50
SERVICE DOORS
1 - ELECTRICAL BOX SERVICE DOOR
2 - COMPRESSOR AND CONDENSER
SERVICE DOOR
3 - BLOWER SERVICE DOOR
RETURN AIR
G
16.50
16.50
18.50
23.00
24.50
24.50
27.50
35.50
35.50
43.50
43.50
J
10.50
10.50
10.50
16.50
16.50
16.50
18.50
18.50
18.50
20.50
20.50
WATER IN
LOW VOLTAGE
CONNECTION
1.50"
N
3/4 FPT
DRAIN
3
1.81"
K
5.75
5.75
5.75
6.50
6.50
6.50
6.50
6.50
6.50
6.00
6.00
SUPPLY AIR
L
6.44
6.44
7.44
9.19
9.19
9.69
9.69
10.50
10.50
13.12
13.12
M
4.13
4.13
4.13
10.31
10.31
11.38
11.38
13.63
13.63
13.63
13.63
N
3.75
3.75
3.75
3.75
4.81
4.81
5.88
5.88
5.13
5.13
5.13
Johnson Controls
Water Source Heat Pumps
DIMENSIONAL DATA
RSV SERIES
LEFT HAND RETURN
E F
G
D
G
TOP VIEW
SERVICE DOORS
1 - ELECTRICAL BOX SERVICE DOOR
2 - COMPRESSOR AND CONDENSER
SERVICE DOOR
3 - BLOWER SERVICE DOOR
Technical Guide: YK145.00-EG4 (309)
D
RIGHT HAND RETURN
F
E
G
G
TOP VIEW
AIR SUPPLY AIR SUPPLY
K
2"
1"
2"
3
3
L
RETURN AIR
RETURN AIR
LOW VOLTAGE
CONNECTION
POWER
CONNECTION
1
DRAIN
3/4Ø
WATER OUT
C
2
DRAIN
3/4Ø
WATER OUT
WATER IN
1
LOW VOLTAGE
CONNECTION
WATER IN
B
A
AIR COIL SIDE
B
POWER
CONNECTION
Model A B
RSV007
RSV009
RSV012
RSV018
RSV024
RSV030
21.50
21.50
21.50
25.50
25.50
25.50
25.50
21.50
21.50
21.50
23.00
23.00
23.00
23.00
RSV036
RSV042
RSV048
RSV060
RSV070
28.00
28.00
32.50
32.50
25.50
25.50
27.50
27.50
ALL DIMENSIONS IN INCHES
Johnson Controls
C
31.50
31.50
31.50
40.00
40.00
40.00
44.00
46.00
46.00
50.00
50.00
SUPPLY AIR
D
6.44
6.44
7.44
9.19
9.19
9.69
9.69
10.50
10.50
13.12
13.12
E
4.13
4.13
4.13
10.31
10.31
11.38
11.38
13.63
13.63
13.63
13.63
F
2.00
2.00
2.00
2.00
2.00
2.00
2.00
2.00
2.00
3.00
3.00
G
7.53
7.53
7.03
8.16
8.16
7.91
7.91
8.75
8.75
9.69
9.69
RETURN AIR
K
20.00
20.00
20.00
25.00
25.00
25.00
25.00
25.00
25.00
30.00
30.00
L
10.50
10.50
10.50
16.50
18.50
18.50
22.50
26.00
26.00
30.00
30.00
23
Technical Guide: YK145.00-EG4 (309)
WIRING DIAGRAM
SINGLE PHASE
RS* UNITS: 208-230V/1Ph/60Hz
265V/1PH/60Hz
Water Source Heat Pumps
24
Johnson Controls
Water Source Heat Pumps
WIRING DIAGRAM
3 PHASE
RS* UNITS: 208-230V/3Ph/60Hz
460V/3Ph/60Hz
575V/3Ph/60Hz
Technical Guide: YK145.00-EG4 (309)
Johnson Controls
25
Technical Guide: YK145.00-EG4 (309)
NOTES
Water Source Heat Pumps
26
Johnson Controls
Water Source Heat Pumps
NOTES
Technical Guide: YK145.00-EG4 (309)
Johnson Controls
27
Printed on recycled paper
Technical Guide: YK145.00-EG4 (309) Supersedes: Nothing
© 2008 Johnson Controls, Inc. P.O. Box 423, Milwaukee, WI 53201 Printed in USA www.johnsoncontrols.com
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 1 YK145.00-EG4
- 1 Water Source Heat Pumps Technical Guide
- 2 TABLE OF CONTENTS
- 3 INTRODUCTION
- 3 PRODUCT OVERVIEW
- 4 SPECIFICATIONS
- 5 NOMENCLATURE
- 6 PHYSICAL DATA
- 7 ARI/ISO PERFORMANCE DATA
- 8 PERFORMANCE DATA
- 8 RS*007 — 320 CFM
- 9 RS*009 — 320 CFM
- 10 RS*012 — 400 CFM
- 11 RS*018 — 640 CFM
- 12 RS*024 — 800 CFM
- 13 RS*030 — 1000 CFM
- 14 RS*036 — 1200 CFM
- 15 RS*042 — 1400 CFM
- 16 RS*048 — 1600 CFM
- 17 RS*060 — 2000 CFM
- 18 RS*070 — 2200 CFM
- 19 CORRECTION FACTORS
- 20 BLOWER PERFORMANCE
- 21 ELECTRICAL DATA
- 22 DIMENSIONAL DATA
- 22 RSH SERIES
- 23 RSV SERIES
- 24 WIRING DIAGRAM
- 24 SINGLE PHASE
- 25 3 PHASE