Model T1905E
PROGRAM TIME SWITCH
FOR UP TO 48 TIMING OPERATIONS
ON 24 HOUR SCHEDULE
SINGLE POLE DOUBLE THROW
LR3730
SWITCH RATING: 20 AMP. 125-480 VOLTS A.C. 1/2 HP-125V 1 HP-250V.
CLOCK MOTOR: 480 VOLTS - 60 HZ.
CLOCK MOTOR VOLTAGE AND CYCLE MUST BE AS SPECIFIED. TO ORDER
REPLACEMENT, INDICATE PART NO. (WG--) ON MOTOR COVER.
CLOCK
MOTOR
TIME
DIAL
MANUAL
LEVER
CAP
NUTS
TIME
N.O.
SUPPLY
N.C.
COM.
CLOCK
N.C.
LOAD
NORMALLY CLOSED CIRCUIT
NO.
LOAD
INSULATOR
NORMALLY OPEN CIRCUIT
FIG. 1 WIRING DIAGRAM
WIRING INSTRUCTIONS
This Time Switch can be wired to control two circuits as Single Pole
Double throw, or to control one circuit as Single Pole Single Throw. Either normally open (NO) or normally closed (NC). To wire switch see wiring diagram above.
1.
2.
TO PROGRAM TIME SWITCH, Depress tripper(s) into dial at desired time(s) operation(s) is/are required.
•
ON TIME: First tripper turns on the load for 16-20 minutes. Each additional tripper will lengthen the on time by 15 minutes.
•
OFF TIME: First tripper in raised position turns off the load for
10-14 minutes.Each additional space will lengthen the of time by 15 minutes.
SET TIME-OF-DAY: Turn dial in clockwise direction only and align the exact time-of-day (the time now when switch is being put into operation) to the “TIME” arrow on insulator.
OPERATING INSTRUCTIONS
TO CONTROL LOADS MANUALLY, Move manual lever (See Figure
1) up. This lever will close normally open circuit and open the normally closed circuit. To return, to automatic control, move lever back to its original position .
IN CASE OF POWER FAILURE, reset dial. See step (2) of programming instructions.
TO REMOVE MECHANISM FROM CASE, Disconnect electricity and all wiring. Depress retainer spring at upper left, or unscrew mounting screws, then grasp dial and pull mechanism out.