New Vers
a IC
Control
Platform
Models 504A thru 2004A
Category I with vertical vent
Models 503A thru 2003A
Models 2503 thru 4003
Category IV Venting
Up to
88.4%
thermal efficiency!
CSA Certified Lead Content
Less Than .25 Pb
Proudly made in the U.S.A
TM
Category I*-up to 85% efficiency
Category IV-up to 88.4% efficiency
Raypak’s Next Generation
Modulating Boiler
Time-honored technologies unite with cutting-edge advancements in
Raypak’s MVB modulating vertical boiler. Never before has a vertical
boiler provided both the installer and building owner such installation
flexibility, ease-of-commissioning, reliability and long-term performance.
Small space, not a problem. The MVB 503A thru 2003A has the smallest
installed footprint of any vertical boiler, only 5.4 square feet. MVB models 2503 thru 4003 are just 11.7 square feet. Raypak’s MVB is built with
commercial-grade components and materials. From our structural steel
base to our stainless steel flue wrapper, you can tell the MVB is built to
last. It’s easy to handle and install, but still user friendly to service. Our
compact design fits through a 32” door opening making it the perfect
choice for those hard to reach retrofit projects. Now is the perfect time
to take a closer look at Raypak.
Flexibility
Small diameter vents and industry-leading vent length allowances
afford greater vent location options, thus reducing wasted space. Vent
versatility is further enhanced by the self-tuning combustion system
which compensates for unusual chimney and vent configurations.
Category I* -CSA-certified 84% boiler and up to 85% water heater
models available (504A-2004A). Our category I solution is the perfect
replacement for your retrofit applications. This reduces the installed
cost by using existing category I venting or chimney. Installation couldn’t be easier; all connections are on the back of the unit. Start-up is a
snap, it’s as close to plug-n-play as a boiler can get.
Category IV -CSA-certified 87% thermal efficiency (503A-2003A) and
85% thermal efficiency (2503-4003) at full fire–the highest possible for
non-condensing boilers (Up to 88.4% at part load!) When the job
requires high efficiency, our category IV solution meets your needs.
At the heart of every Raypak MVB is a unique integral evaporator system - the first defense against harmful condensation. Raypak’s evaporator system collects and re-evaporates condensate which may form during initial start-up or brief periods of cold-water operation, eliminating
the need for a boiler condensate drain. This saves you money on installation costs as well as the inconvenience of dealing with multiple condensate drains.
True Modulation
Modulation is nothing new to Raypak, we have honed our gas modulation experience for over 65 years. The Raypak MVB will precisely track
the heating load with its built-in Versa IC® Integrated Control platform,
eliminating costly overshooting. Utilizing the latest technology for the
blower-gas valve package, the optimum fuel-air ratio is maintained
throughout the entire range of the load-tracking operation. Now with
up to 7:1 turndown (503A thru 4003 Cat IV) ensures efficiency is maintained throughout the firing rate and actually increases during part
load, right when you want it! The MVB automatically self-tunes to
accommodate the widest range of gas supply pressures. The high quality integrated blower-gas valve is self-correcting and allows smooth
operation with fluctuating gas supply pressures. The Raypak MVB is
cutting edge technology with atmospheric simplicity.
Key Features
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
16 models from 500,000 to 4,000,000 BTUH
Up to 85% efficiency (Cat. I*);
Up to 88.4% efficiency (Cat. IV)
No boiler condensate drain required (proprietary design)
Lowest minimum required inlet water temperature (120F)
Modulating gas valve and burner, up to 7:1 (503A thru 4003 Cat. IV)
turndown
Multiple pump outputs - Boiler, System, and Indirect DHW.
0-10 VDC BMS Interface (setpoint or direct drive).
Built-in cascade function for up to 4 boilers.
Built-in outdoor reset functionality.
Modbus BMS port.
Engineered with precisely matched system components
Small installed footprint design fits tight spaces and easily replaces
larger boilers
Advanced diagnostics center, real English fault codes
Indoor/outdoor construction
Complete cabinet protects all controls and wiring
Low NOx combustion system
Suitable for altitudes up to 10,000 ft. (derate above 5,000 ft.)
With all copper and bronze waterways (optional on some
models), the MVB is available in boiler and water heater configurations
Inline combustion air filter (MERV8)
All water heaters are low lead (<.25%) certified.
*Category I with vertical vent, category III with horizontal venting and no extractor.
2
6
5
4
3
2
1
7
8
9
10
11
12
Models 2503 thru 4003
Features and Benefits
1. Control Interface
Large easy to read (3.5”) LCD display. Will continuously
monitor flame strength (μa), sensor temps, BMS signal (0-10V),
set points, DeltaT, all safety signals, full diagnostics and fault history for last 15 events. Simple touch pad settings. Everything you
need from set-up to service is at your fingertips, all in one location.
1a. Versa IC Board (not shown)
The Versa IC, Integrated Control system is CSA listed and certified
as a combined temperature, safety, and ignition control device.
Easy front access to all field wiring. This includes outdoor sensor,
DHW sensor, system alarm, Modbus BMS port and 0-10V DC
input connections. Each unit comes factory equipped with cascade control capability. Simple, quick access daisy chain of up to
4 boilers, link to Raypak Temp Tracker Mod+ Hybrid Master control for up to 16.
1b. Low Voltage Wiring Connections (not shown)
Up front and easy to get to. Makes sensor wiring and external
control wiring simple and clean.
1c. Control Panel (not shown)
Fully enclosed controls and wiring protect against damage or
vandalism. Swing out cabinet design affords easy access to controls for installation and service
2. Status Lights and On/Off Switch
Easy to read and monitor boiler status. Colored lights alert maintenance personnel to power, call for heat, burner on and safety
fault.
3. Gas Valve
Designed to work in perfect harmony with the air blower. The gas
valve delivers the perfect fuel mix based on the amount of combustion air being supplied. The Euro designed gas valve provides
smooth light off and precise flame modulation with up to 7:1
turndown (503A thru 4003 Cat. IV).
4. Combustion Air Blower
Cast aluminum blower housing, non-sparking construction.
Precise PWM speed input allows for instantanous response to the
Versa IC control output. No blower lag associated with real time
water temperature sensing.
5. Vent Pressure Switch
Monitors vent pressure and provides safe shut down if back pressure is excessive.
6. Air Filter
Every MVB comes standard with a rear access, easy to service
Merv 8 media, combustion air filter.
7. Rugged Cast Headers
Bronze headers standard on water heater models. Cast-iron standard on boiler models 503A-2004A, with bronze headers optional. Bronze headers are standard on all models 2503 thru 4003.
8. Tube Sheet Construction
Eliminates the repair & maintenance problems associated with
rolled-tube construction. Easy, cost-effective component replacement.
9. Vertical Heat Exchanger
Cylindrical, multi-pass heat exchanger for models 503A thru
2004A captures all radiant energy, eliminating the need for heavy
refractory. Dual heat exchanger for models 2503 thru 4003.
10. Minimum Clearance Requirements
Only one inch of side clearance is required from
combustible surfaces.
10a. Weather-Proof Jacket
Heavy gauge galvanized steel with a UV-resistant Polytuf powder
coat finish is impervious to weather and corrosion. Raypak has
one of the finest, top-of -the-line powder coat systems on the
west coast regardless of industry. We laugh at a 1000 hour salt
spray test. Independent test documentation available upon
request.
11. Easy Rigging
Steel base allows for forklift/pallet jack use. Models 2503 thru
4003 have factory mounted rigging eyelets for hoist and crane
connections.
12. Drain Valves
Two drain valves are located at the bottom of the heat exchanger. This allows for complete winterizing and drainage of the
heater. Connects to a standard garden hose.
Models
503A thru 2003A
504A thru 2004A
3
503A thru 2003A
504A thru 2004A
Models
PHYSICAL DATA
MVB
MVB
Cat. I* Cat. IV
504A
754A
1104A
1504A
2004A
-
503A
753A
1003A
1253A
1503A
1753A
2003A
2503
3003
3503
4003
Dimensions (inches)
B
Ht.
D
E
43
49
55
61
67
75
81
68-1/4
73-1/4
78-1/4
83-1/4
32
38
44
50
56
62
68
62
67
71
76
35
41
47
53
59
65
71
64-7/8
69-7/8
74-7/8
79-7/8
F
G†
NPT
H
23-3/4
29-3/4
35-3/4
41-3/4
47-3/4
53-3/4
59-3/4
7-5/16
7-5/16
7-5/16
7-5/16
1
1
1-1/4
1-1/4
1-1/4
2
2
2-1/2
2-1/2
2-1/2
2-1/2
2” NPT
2” NPT
2-1/2” NPT
2-1/2” NPT
2-1/2” NPT
2-1/2” NPT
2-1/2” NPT
4” groove
4” groove
4” groove
4” groove
K-Ø
K-Ø
Cat. I* Cat. IV
8
10
10
12
14
-
*Category I with vertical vent, category III with horizontal venting and no extractor.
6
6
6
8
8
8
8
10
10
12
12
Operating
M
M
Cat I*
Cat IV
N
CA Ø
14-1/8
16
16
18-1/8
20-1/8
-
14-1/2
14-1/2
14-1/2
17-3/4
17-3/4
17-3/4
17-3/4
26-3/4
29-1/4
31-3/4
34-1/4
6
6
6
8
8
8
8
10
10
12
12
P
R
V
35
41
47
53
59
68
74
6
6
6
6
6
9
9
2
2
2
2
2
5
5
N/A
N/A
4-13/16
N/A
N/A
4-13/16
N/A
N/A
4-13/16
N/A
N/A
4-13/16
†NPT shown is for Natural Gas. For Propane, NPT= 1” for 503/4 thru 2003/4 and 2-1/2” for 2503 thru 4003 all water heater/boiler sizes.
‡Current draw is for heater only. (Supply breaker must have a delayed trip.)
PHYSICAL DATA
Models
MVB
MVB
Cat. I* Cat. IV
-
2503
3003
3503
4003
Dimensions (inches)
W*
X*
58.22
63.22
68.22
73.22
67.12
72.12
77.12
82.12
*Only one port is to be used. All three ports are
shown for pictorial purposes.
4
Weight Amps‡
(lbs.)
600
660
720
780
840
940
1000
1150
1250
1375
1450
12
12
12
12
12
18
18
12
15
17
20
2503 thru 4003
RATING PLATE
CLEARANCES
Heater
Side
From Combustible
Surfaces (min.)
503/4A thru 2003/4A
For Service
2503 thru 4003
0”
12”
1”
1”
0”
24”
1”
1”
0”
36”
24”**
24”**
Indoor
Outdoor
0”
Unobstructed
10”
Unobstructed
12”
Unobstructed
Indoor
Outdoor
Open
1”
12”
24”
1”
12”
30”
1”
12”
Floor*
Rear
Right Side
Left Side
Top
Front
Vent Stack
Vent Cap
** One side 24” other 1” clearance.
*Do not install on carpeting
Note: Local codes may require increased clearances
PUMP
MVB
Model
All components are contained inside the
cabinet (except PRV), no external fans or
valves to deal with.
503A/504A
753A/754A
1003A/1104A
1253A
1503A/1504A
1753A
2003A/2004A
2503
3003
3503
4003
Soft
HP
Amps
1/4
1/4
1/4
1/2
3/4
1
1-1/2
1-1/2
1-1/2
1-1/2
3
6
6
6
7
11
14
15
8.2
8.2
8.2
16
Note: Current draw (Amps) is for pump only
*Pump selections based on 75ft equivalent length of tubing
** At 230 VAC
For Service
Water Hardness
Medium
HP
Amps
1/4
1/2
1/2
1
1
1-1/2
1-1/2
1-1/2
3
3
5
6
7
7
14
14
15
15
8.2
16
16
23
Hard
HP
Amps
3/4
3/4
1
1
1
1-1/2
1-1/2
3
3
3
5
11
11
14
14
14
15
15
16
16
16
23
Water hardness grains per gallon
Soft = 3-4 • Medium = 5-15 • Hard = 16-25
5
RESET
ITEM
MENU
Versa IC Boiler Control and On-Board
Diagnostic Center
Versa IC merges safety, ignition and temperature control, outdoor reset and
freeze protection, plus system monitoring, alarm and diagnostics, and BMS
transmission all in one Integrated Control Platform. Easy front access to
read, set up and trouble shoot on a 3.5” LCD screen. The entire package is
CSA certified, and listed for each individual function.
Inlet and outlet sensors factory installed in boiler. Remote sensor for system included. BMS all point diagnostics transmission port. 0-10V DC
set point input standard. Also can drive and monitor external motorized auxiliaries such as extractors and louvers. Additional connections for
auxiliary functions, indirect DHW, and dry contact remote alarm relay are provided.
Outdoor Proven
Raypak is no stranger to the outdoor environment. Our touchpad is 100% waterproof and has been proven and perfected on our pool products. No guesswork here, just one tough boiler ready to take on jobs that others have to walk away from.
Diagnostic Information
Control Faults
• Low 24VAC
• Control Setup
• ID Card Fail
• Device Lost
• Device Error
• PIM Error
Ignition Control Faults
• Ignition Lockout
• False Flame
• Ignition Failure
• Low HSI Current
• Blower Speed
MBTUH
Model
503A
753A
1003A
1253A
1503A
1753A
2003A
2503
3003
3503
4003
504A
754A
1104A
1504A
2004A
Boilers
Safety Faults
• Sensor Failure - 6
• Vent Block
• Manual Limit
• Auto Limit
• Water Flow
• Delta T Fault
• Low Water
• Low Gas
• High Gas
• Extra 1
• Options
Water Heaters
Venting
Category
†
Input
Output
Efficiency
Input
Output
Efficiency
Input
Min.
IV
IV
IV
IV
IV
IV
IV
IV
IV
IV
IV
I*
I*
I*
I*
I*
500
750
999
1250
1500
1750
1999
2501
3000
3500
3999
500
750
1100
1500
1999
435
653
869
1088
1305
1523
1739
2126
2550
2975
3399
420
630
924
1260
1679
87%
87%
87%
87%
87%
87%
87%
85%
85%
85%
85%
84%
84%
84%
84%
84%
500
750
999
1250
1500
1750
1999
2501
3000
3500
4000
500
750
1045
1425
1900
435
653
869
1088
1305
1523
1739
2126
2550
2975
3400
420
630
888
1211
1615
87%
87%
87%
87%
87%
87%
87%
85%
85%
85%
85%
84%
84%
85%
85%
85%
71
108
143
179
214
250
286
350
420
490
560
300
450
660
900
1199
*Category I with vertical vent, category III with horizontal venting and no extractor.
†Category IV requires sealed vent with condensate drain. Category I uses conventional B vent.
Note: Ratings are for natural or propane gas and for elevations up to 5,000 ft. above sea level. For higher elevations, consult the factory.
6
Raypak Leadership in Boiler Management
The new modulating or stagefire VERSA ICTM fully integrates temperature
control, ignition, safety, temperature safety and individual fault monitoring.
Field upgradable. Raypak’s unique Cold Water Protection control function
is now built in; simply add the appropriate 3-way valve or variable speed
pump. A Modbus communications port is standard for continuous monitoring, trending, and trouble shooting.
• Cascade up to 4 boilers
• Modbus RTU comm port standard
• All faults and interlocks monitored and reported in plain English
• Building Management System integration via optional gateways
• BACnet MS/TP, BACnet IP, N2 Metasys or Modbus TCP
• LONworks
LONworks®
BACnet®,Metasys®
Modbus®
gateway module
(optional)
gateway module
(optional)
CATEGORY I*
BOILERS
(TYPE H)
Flow Rates
MVB
Model
504A
754A
1104A
1504A
2004A
Pressure Drops
Minimum Flow
Maximum Flow
20°F
30°F
39°F
GPM
⌬P FT
⌬T °F
GPM
⌬P FT
⌬T °F
GPM
⌬P FT
GPM
⌬P FT
GPM
⌬P FT
25
32
47
65
86
1.1
1.8
4.3
8.4
16.7
34
39
39
39
39
100
100
113
113
113
11.3
13.8
18.6
22.2
27.2
8
13
16
22
30
42
63
92
N/A
N/A
2.7
6.0
13.3
N/A
N/A
28
42
62
84
112
1.4
2.9
6.7
13.3
26.9
N/A
32
47
65
86
N/A
1.8
4.3
8.4
16.7
CATEGORY I*
WATER HEATERS
(TYPE WH)
Flow Rates
MVB
Model
504A
754A
1104A
1504A
2004A
Minimum Flow
Maximum Flow
GPM
⌬P FT
⌬T °F
GPM
⌬P FT
⌬T °F
29
44
61
84
113
1.4
2.9
6.7
13.3
27.2
29
29
29
29
29
100
100
113
113
113
11.3
13.8
18.6
22.2
27.2
8
13
16
22
29
Flow Rates
CATEGORY IV BOILERS
& WATER HEATERS
(TYPE H & WH)
MVB
Model
503A
753A
1003A
1253A
1503A
1753A
2003A
2503
3003
3503
4003
Minimum Flow
Pressure Drops
Maximum Flow
20°F
30°F
39°F
GPM
⌬P FT
⌬T °F
GPM
⌬P FT
⌬T °F
GPM
⌬P FT
GPM
⌬P FT
GPM
⌬P FT
25‡
33‡
43‡
54‡
65‡
76‡
87‡
120‡
131‡
153‡
174‡
1.1
1.9
3.7
6.2
9.5
13.4
15.2
4.7
6.3
9.1
13.5
35
40
40
40
40
40
40
35
39
39
39
100
100
113
113
113
113
116
264
264
264
264
11.3
13.8
18.6
22.2
25.5
27.2
30.2
15.7
23.1
26.8
33.5
9
13
15
19
23
27
30
16
19
23
26
43
65
87
109
N/A
N/A
N/A
213
255
N/A
N/A
2.8
6.4
12.0
20.9
N/A
N/A
N/A
11.7
21.7
N/A
N/A
29
43
58
73
87
101
116
142
170
198
227
1.4
3.1
6.0
10.2
16.0
22.5
31.9
6.2
10.3
15.2
23.7
N/A
33
45
56
67
78
89
N/A
131
153
174
N/A
1.9
3.8
6.5
10.0
14.0
19.8
N/A
6.3
9.1
13.5
*Category I with vertical vent, category III with horizontal venting and no extractor.
‡ Use 30° column as minimum flow for hot water supply.
Boiler Only
7
Cascade up to 4 Boilers
The MVB comes standard with a built-in Cascading Boiler
Control. No other controls to buy, just daisy chain the units
together with 2-wire shielded cable (not supplied) that connect to the front mounted low voltage wiring board.
Designate a Cascade Master Boiler and set all the other boilers as Followers. It’s that simple! The MVB has built-in
equal run-time rotation. This allows rotation of the starting
boiler so all boilers in the system remain active and the run
times remain equal on each unit.
Low Voltage Wiring Terminal
Control panel swings open for easy control access.
Cat.
I*
84%
Cat.
I*
84%
85%
Cat.
IV
87%
85%
MVB
Input
(000)
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
500
750
1100
1500
1999
5,091
7,636
11,200
15,273
20,353
2,545
3,818
5,600
7,636
10,177
1,697
2,545
3,733
5,091
6,784
1,273
1,909
2,800
3,818
5,088
1,018
1,527
2,240
3,055
4,071
848
1,273
1,867
2,545
3,392
727
1,091
1,600
2,182
2,908
636
955
1,400
1,909
2,544
566
848
1,244
1,697
2,261
509
764
1,120
1,527
2,035
463
694
1,018
1,388
1,850
424
636
933
1,273
1,850
392
587
862
1,175
1,566
364
545
800
1,091
1,454
339
509
747
1018
1,357
Recovery Rates (GPH) - Boiler
MVB
Input
(000)
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
500
750
1045
1425
1900
5,091
7,636
10,640
14,682
19,576
2,545
3,818
5,320
7,341
9,788
1,697
2,545
3,547
4,894
6,525
1,273
1,909
2,660
3,670
4,894
1,018
1,527
2,128
2,936
3,915
848
1,273
1,773
2,447
3,263
727
1,091
1,520
2,097
2,797
636
955
1,330
1,835
2,447
566
848
1,182
1,631
2,175
509
764
1,064
1,468
1,958
463
694
967
1,335
1,780
424
636
887
1,223
1,631
392
587
818
1,129
1,506
364
545
760
1,049
1,398
339
509
709
979
1,305
Recovery Rates (GPH) - Water Heater
MVB
Input
(000)
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
500
5,273
2,636
1,758
1,318
1,055
879
753
659
586
527
479
439
406
377
352
750
7,909
3,955
2,636
1,977
1,582
1,318
1,130
989
879
791
719
659
608
565
527
999
10,535 5,267
3,512
2,634
2,107
1,756
1,505
1,317
1,171
1,053
958
878
810
752
702
1250
13,182 6,591
4,394
3,295
2,636
2,197
1,883
1,648
1,465
1,318
1,198
1,098
1,014
942
879
1500
15,818 7,909
5,273
3,955
3,164
2,636
2,260
1,977
1,758
1,582
1,438
1,318
1,217
1,130
1,055
1750
18,455 9,227
6,152
4,614
3,691
3,076
2,636
2,307
2,051
1,845
1,678
1,538
1,420
1,318
1,230
1999
21,080 10,540 7,027
5,270
4,216
3,513
3,011
2,635
2,342
2,108
1,916
1,757
1,622
1,506
1,405
2501
25,768 12,884 8,589
6,442
5,154
4,295
3,681
3,221
2,863
2,577
2,343
2,147
1,982
1,841
1,718
3000
30,909 15,455 10,303 7,727
6,182
5,152
4,416
3,864
3,434
3,091
2,810
2,576
2,378
2,208
2,061
3500
36,061 18,030 12,020 9,015
7,212
6,010
5,152
4,508
4,007
3,606
3,278
3,005
2,774
2,576
2,404
4000
41,212 20,606 13,737 10,303 8,242
6,869
5,887
5,152
4,579
4,121
3,747
3,434
3,170
2,944
2,747
Recovery Rates (GPH)
8
Smallest Installed Footprint
The MVB’s compact design allows for easy installation in the most challenging equipment rooms. It’s easy to handle and install, but still user friendly to service. The MVB
503A thru 2003A has the smallest installed footprint of any vertical boiler, only 5.4 square
feet. MVB models 2503 thru 4003 are just 11.7 square feet. The MVB contains all of its
components to the inside of the cabinet, so there won’t be any fans or valves hanging
off the cabinet that need extra clearance. The compact design fits through a 32” door
opening making it the perfect choice for those hard to reach retrofit projects.
Optional Equipment
Cold Water Solutions
Cold Water Start – For applications
that require reliable protection against
harmful condensation caused by frequent,
extended, cold water start-ups. Raypak’s
Cold Water Start protection system utilizes
a proportional valve to bypass water from
the boiler outlet to the inlet during startup, when the system return water temperature is below the
minimum acceptable level.
Cold Water Run – For applications
requiring constant condensation protection. Raypak’s Cold Water Run system utilizes a variable-speed pump to inject just
the right amount of water from the main
system loop into the boiler to maintain
the optimum inlet temperature. This
approach allows the full capacity of the
boiler to be utilized to meet the system load, while at the same
time continuously maintaining the optimum inlet water temperature to prevent condensation.
9
Multi Boiler Solutions
Hybrid Control
BACnet BMS Link
TempTracker Mod+ Hybrid– Controls up
to 16 Raypak boilers with PID logic.
Automatic or manually selectable lead-lag
boiler operation. TempTracker Mod+ Hybrid
monitors and displays supply water temperatures on all applications including outdoor
temperature when outdoor reset mode is
selected. Can also be used to control a mix of
condensing and non condensing boilers using
our Hybrid control algorithm. Now available
with optional BACnet® MS/TP BMS link.
(See Cat. # 5100.22)
MVB
OPERATING CONTROLS
JACKET
HEAT EXCHANGER
ASME, National Board Registered, 160 PSI
Heat Exchanger Tubes
Bronze Headers
Cast Iron Headers
Pressure Relief Valve
HLW Stamp
H Stamp
Copper
Cupro Nickel
Standard on all 2503 thru 4003
Boilers
(Type H)
N/A
N/A
N/A
• 60 PSI
• 125 PSI
• 30, 45, 75, 150 PSI
Fully-Enclosed Controls
Combustible Floor Rated
120V Power Supply With 120V/24V Transformer (503/4 thru 2003/4) • 240V (2503 thru 4003)
On/Off Switch
Programmable Pump Time Delay, Single-Phase
• Included In Controller
Terminal Block Connections
• Enable / Disable
• External Interlocks
• 0-10 VDC Setpoint/Direct Drive Input
Diagnostic LCD Display With Up To 15 Faults
Status Display Lights (4)
Versa IC Control System
• (up to 7:1 Turndown)
(Cascade up to 4 heaters)
• Outdoor Reset Sensor
• DHW Indirect Sensor
Multiple Boiler Controller
• TempTracker Mod+ Hybrid BACnet, Up To 16 boilers
• Multi-Mod Platinum (BACnet)
N/A
N/A
Temperature & Pressure Gauge
Pump
• 120V, Single-Phase (503/4 thru 2003/4)
Indoor/Outdoor Construction
Vent Terminal
• Outdoor
• Through-The-Wall
Hot Surface Ignition System
SAFETIES
•
•
•
•
•
Water Heaters
(Type WH)
High/Low Gas Pressure Switches
Blocked Vent And Air Pressure Switches
High Limit Switch
Manual Reset, Fixed (integral)
Additional Manual Reset, Adjustable
Additional Automatic Reset, Adjustable
With Manual Reset And Test Buttons
GAS TRAIN
•
•
•
•
Modulating Combination Gas Valve
Combustion Air Blower
TruSeal Direct-Vent Ready
Additional Safety Valve
OTHER
Low Water Cut-Off, 24V
Flow Switch
• 1-Try (Standard On Cat. IV)
• 3-Try (Standard On Cat. I)
• Hi Gas Standard on 2503 thru 4003
CSA-Certified Efficiency • Cat. IV - 87% At Full Fire (503A thru 2003A) • 85%At Full Fire (2503 thru 4003)
• Cat. I - 84% to 85% (See MBTUH Table)
Air Filter (Shipped Loose on models 503/4 thru 2003/4)
Alarm System
CSD-1 / GE GAP Control System
Low NOx
• Confirm Local Requirements
Cold Water Start
• Prevents Internal Condensation On Start-Up
Cold Water Run
• Prevents Condensation In Continuous Low-Temp Operation
= Standard
• Motorized (Externally Mounted)
• Solenoid (Externally Mounted)
= Optional
®
LLC
eÉ~íáåÖ=_çáäÉêë=låäó
Raypak, Inc. • 2151 Eastman Avenue, Oxnard, CA 93030 • phone: (805) 278-5300 • fax: (800) 872-8725 • www.raypak.com
10
Cat. No. 3400.11- K Effective 01-01-14