Zurn-Wilkins 1-350XLSHFT Installation Guide
Add to my manuals4 Pages
Zurn-Wilkins 1-350XLSHFT is a Double Check Valve Assembly designed for use on water lines where a health hazard does not exist in the event of a backflow situation. It is suitable for both indoor and outdoor installations, provided that the device is protected against freezing conditions. The 1-350XLSHFT helps prevent contaminated water from flowing back into the clean water supply by utilizing two independently operating check valves. Each check valve features a rubber seal ring and o-ring for a tight seal, and the assembly includes test cocks for easy pressure testing.
advertisement
Model 350
Double Check Valve Assembly (3/4”& 1”)
Installation Testing Maintenance Instructions
INSTALLATION INSTRUCTIONS PLACING THE MODEL 350 IN SERVICE
®
CAUTION: Installation of Backflow Preventers must be performed by qualified, licensed personnel. The installer should be sure the proper device has been selected for the particular installation. Faulty installation could result in an improperly functioning device.
ZURN WILKINS Model 350 Double Check Valve assemblies are for use on water lines where a health hazard does not exist in the event of a backflow situation.
Damage to the device could result wherever water hammer and/or water thermal expansion could create excessive line pressure. Where this could occur, shock arresters, check valves and/or pressure relief valves should be installed downstream of the device.
If installation is in a pit or vault, the Backflow Preventer must never be submerged in water because this could cause a cross-connection. Make sure that the pit or vault always remains dry by providing ample drainage.
1. Start with both shut-off valves closed.
Slowly open the inlet shut-off valve until the backflow preventer is completely pressurized.
2. When the unit has been pressurized, vent any trapped air by slightly opening each of the four test cocks.
3. Slowly open the downstream shut-off valve. The Model 350 Double Check Valve assembly is now in service.
1. Before installing a Model 350 Backflow Preventer, flush the line thoroughly to remove all debris, chips and other foreign matter. If required, a strainer should be placed upstream of the Backflow Preventer. CAUTION: Do not use a strainer in seldom used emergency waterlines such as fire lines.
4. After the Model 350 has been properly installed, test the device (see “TEST PRO-
CEDURES”). If the device fails the test, remove the first and second check valves and thoroughly flush the device. Clean rubber and seats of all debris and place unit back in service.
2. Provide adequate space around the installed unit so that the test cocks will be accessible for testing and servicing.
3. Install valve at least 12 inches above surrounding flood level.
4. Always consult local codes for installation methods, approvals and guidance.
WILKINS 350
DIRECTION OF FLOW
OPTIONAL STRAINER
(MODEL SXL)
PROTECTIVE
ENCLOSURE
WILKINS 350
12" MIN.
30" MAX.
WILKINS 350
DIRECTION OF FLOW
VERTICAL INSTALLATION INDOOR INSTALLATION
DIRECTION OF FLOW
OUTDOOR INSTALLATION
Vertical installation is acceptable in applications where inlet and outlet piping are flowing vertically upwards. All the basic installation instructions apply to such installations.
Consult factory for approval status.
Indoor installation is preferred in areas that are subject to freezing conditions. All the basic installation instructions apply to such installations.
The Model 350 Backflow Preventer may be installed outdoors only if the device is protected against freezing conditions.
Exposure to freezing conditions will result in improper function or damage to the device. The installation location must be kept above 32°F. All the basic installation instructions apply.
Proposition 65 Warning This product contains chemicals known to the State of California to cause cancer or birth defects or other reproductive harm.
In accordance with U.S. Federal Safe Drinking Water Act Lead-Free requirements, as of January 4, 2014, this product can only be used in water systems considered non-potable. Please contact your local water utility for further requirements.
Testing Procedures
MODEL 350 DOUBLE CHECK VALVE ASSEMBLY
Equipment Required: Differential pressure gauge test kit.
TEST NO. 1 - TIGHTNESS OF #1 CHECK VALVE
REQUIREMENT:
The static pressure drop across check valve #1 shall be at least
1.0 psid. If test cock #3 is not at the highest point of the check valve body, then a vertical tube must be installed on test cock #3 so that it rises to the top of the check valve body.
PROCEDURE:
1. Slowly open all 4 test cocks to remove any foreign material
and attach fittings.
2. Attach hose from the high side of the test kit to the #2 test cock.
3. Open test cock #2 and bleed all air from the hose and gauge
by opening the high side bleed needle valve. Close high side
bleed needle valve. If a tube is attached to test cock #3, open
test cock #3 to fill the tube. Close test cock #3. Close #2
shut-off valve then close the #1 shut-off valve.
4. Hold gauge at same level as test cock #3 or water level in
tube. Slowly open test cock #3. Record the static pressure drop
across check valve #1 after gauge reading stabilizes and
water stops running out of test cock #3.
5. Close all test cocks, open shut-off valve #1 and remove test
equipment.
TEST NO. 2 - TIGHTNESS OF #2 CHECK VALVE
REQUIREMENT:
The static pressure drop across check valve #2 shall be at least
1.0 psid. If test cock #4 is not at the highest point of the check valve body, then a vertical tube must be installed on test cock #4 so that it rises to the top of the check valve body.
PROCEDURE:
1. Attach hose from the high side of the test kit to the #3 test cock.
2. Open test cock #3 and bleed all air from the hose and gauge
by opening the high side bleed needle valve. Close high side
bleed needle valve. If a tube is attached to test cock #4,
open test cock #4 to fill the tube. Close test cock #4.
Close #1 shut-off valve.
3. Hold gauge at same level as test cock #4 or water level
in tube. Slowly open test cock #4. Record the static pressure
drop across check valve #2 after gauge reading stabilizes
and water stops running out of test cock #4.
4. Close all test cocks, slowly open shut-off valve #1 & #2 and
remove test equipment.
#2 TEST COCK
#1 TEST COCK
#3 TEST COCK
#4 TEST COCK
#1 SHUT-OFF
VALVE
LOW SIDE BLEED
NEEDLE VALVE
WILKINS 350
HIGH SIDE BLEED
NEEDLE VALVE
#2 SHUT-OFF
VALVE
LOW SIDE HOSE HIGH SIDE HOSE
VENT HOSE
2
ZURN WILKINS
1747 Commerce Way, Paso Robles, CA 93446 Phone:855-663-9876 Fax:805-238-5766 www.zurn.com
®
Maintenance Instructions
Seat
Poppet
Spring
Tailpiece
CHECK ASSEMBLY
All Model 350 Double Check Valve Backflow Preventers must be inspected and maintained by licensed personnel at least once a year or more frequently as specified by local codes. Replacement of worn or damaged parts must only be made with genuine
“ZURN WILKINS” parts.
GENERAL MAINTENANCE
1. Clean all parts thoroughly with water after disassembly.
2. Carefully inspect rubber seal rings and o-rings for damage.
3. Test unit after reassembly for proper operation (refer to
“TESTING PROCEDURES”).
SERVICING CHECK VALVES
1. Close inlet and outlet shut-off valves.
2. Open No. 2, No. 3 and No. 4 test cocks to release pressure
from valve.
3. Unscrew the 4 bolts (1/4-20 UNC Hex Flange) holding the
housing in place.
4. Using a #2 flathead screwdriver, pry loose housing by plac-
ing the screwdriver in the notch between housing and body.
5. Pull housing out of the body and remove checks by sliding
them towards the outlet of housing.
6. Using the same screwdriver, locate the notch between seat
and tailpiece of each check. Insert screwdriver and twist to
“snap” checks apart. CAUTION: Checks are spring loaded.
7. Inspect the rubber seal ring around poppet for cuts or
embedded debris.
8. If the poppet is damaged, replace with a new poppet.
9. Inspect the remaining check parts and seating areas. Re-
move any debris.
10. If necessary, replace any damaged parts with new ones.
11. Lightly grease o-rings on checks and reinstall into housing
following the above procedures in reverse order.
12. Flush body prior to reinstalling housing.
13. Lightly grease o-rings on housing and reinstall into body
following the above procedures in reverse order.
Note: When installing housing, match slight taper on the outlet of the housing with corresponding taper in body.
Hex Flange Bolts
No. 3
Test Cock
No. 1
Test Cock
Inlet
O-ring
No. 2
Test Cock
Outlet
O-ring
Inlet
Ball Valve
No. 4
Test Cock
Housing
Body
Outlet
Ball Valve
FIGURE 1
®
#1 Check
O-ring
#1 Check
Assembly
#2 Check
O-ring
#1 Seat
Poppet
Spring
Tailpiece
#2 Seat
#2 Check
Assembly
FIGURE 2 FIGURE 3
ZURN WILKINS
1747 Commerce Way, Paso Robles, CA 93446 Phone:855-663-9876 Fax:805-238-5766 www.zurn.com
3
Troubleshooting
PROBLEM
1. LEAKING CHECK VALVES
POSSIBLE CAUSES
1. Debris on seat or seal ring
2. Damaged seat
3. Damaged seal ring
4. Damaged check o-ring
2. LOW OR NO FLOW 1. Device installed backwards
2. Shut-off valves or valve upstream
may not be fully open
3. Low supply pressure
Performance Characteristics
15
0.00
10
5
0
0
1.26
FLOW CHARACTERISTICS
MODEL 350 3/4" & 1" (STANDARD & METRIC)
FLOW RATES (l/s)
2.52
3.79
3/4" (20mm)
20 40
FLOW RATES (GPM)
60
CORRECTIVE ACTION
1. Clean seat and seal ring area
2. Replace seat
3. Replace poppet
4. Replace check o-ring
1" (25mm)
5.05
103
80
0
69
34
Capacity thru Schedule 40 Pipe
Pipe size 5 ft/sec 7.5 ft/sec 10 ft/sec 15 ft/sec
1/8"
1/4"
3/8"
1/2"
1
2
3
5
1
2
4
7
2
3
6
9
3
5
9
14
3/4"
1"
1 1/4"
1 1/2"
2"
8
13
23
32
52
12
20
35
48
78
17
27
47
63
105
25
40
70
95
167
SPECIFICATIONS
Maximum working water pressure 175 PSI
Maximum working water temperature 180°F
Hydrostatic test pressure
End connections
350 PSI
Threaded ANSI B1.20.1
Proper performance is dependent upon licensed, qualified personnel performing regular, periodic testing according to ZURN
WILKINS’ specifications and prevailing governmental & industry standards and codes and upon following these installation instructions. Failure to do so releases ZURN WILKINS of any liability that it might otherwise have with respect to that device. Such failure could also result in an improperly functioning device.
®
IS350-34-1 (REV. 4/13)