Capstone
Capstone Turbine Corporation  21211 Nordhoff Street  Chatsworth  CA 91311  USA
Telephone: (818) 734-5300  Facsimile: (818) 734-5320  Website: www.microturbine.com
Product Specification
Model C200 – Capstone MicroTurbine
Summary
This Product Specification describes the Capstone Model C200 MicroTurbine power
generating system (hereafter referred to by Capstone as a MicroTurbine). The MicroTurbine
provides on-site electrical power for primary or standby applications, and for peak shaving,
base loading, and/or capacity additions. MicroTurbine(s) may generate power in parallel
with an electrical utility (Grid Connect mode), or isolated from the utility (Stand Alone
mode). The system consists of a turbine engine, solid-state power electronics, a fuel
system, and an indoor/outdoor-rated NEMA 3R enclosure.
Major turbine engine components include a compressor, a recuperator (exhaust gas heat
exchanger), a combustor, a turbine, and a generator. The turbine engine is air-cooled and
supported on air-lubricated compliant foil bearings. The compressor impeller, turbine rotor,
and generator rotor are mounted on a single shaft, which comprises the only moving part in
the engine. Power electronics are solid-state, double conversion type, producing three-phase
alternating current output power from the high-frequency alternating current engine output.
Available Model Types
Model C200 MicroTurbine systems are available in several versions, depending on fuel type,
certifications, and other characteristics. Table 1 below summarizes the available construction
types covered by this Product Specification.
Table 1. C200 Model Designations
Certifications (1)
Fuel Capability
Dual
Mode
Capable
Natural
Gas
Option
Option
X
Option
Option
X
Option
X
C200 Model
Designations
External Heat
Recovery
Module
HP Natural Gas
Accessory
LP Natural Gas
Accessory
CARB Certified
LP Natural Gas
Included
Landfill
Accessory
Option
Option
Digester
Accessory
Option
Option
CE
CARB (2)
X
Landfill
Gas
Digester
Gas
X (3)
X (3)
Notes:
(1) All versions are planned to be UL Listed except the CE Certified models
(2) Systems are in process of being certified by the California Air Resources Board for exhaust emissions
(3) Operation on these fuels may be limited – see sections below
460045 Rev C (November 2008)
Page 1 of 16
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Capstone Turbine Corporation  21211 Nordhoff Street  Chatsworth  CA 91311  USA
Product Specification: Model C200 - Capstone MicroTurbine
The tables and figures in the sections below may group the performance of these different
construction types. Unless otherwise specified, the designation “C200” will cover all these
construction types, and “All Other C200” will define all other constructions except any
designations that are specifically called out in a given section.
Definitions

ISO conditions are defined as: 15 °C (59 °F), 60% relative humidity, and sea level
pressure of 101.3 kPa (14.696 psia)

HHV: Higher Heating Value

LHV: Lower Heating Value

HPNG: High Pressure Natural Gas

LPNG: Low Pressure Natural Gas

L/DG: Landfill/Digester Gas

SG: Sour Gas

kWth: Kilowatt (thermal)

kWe : Kilowatt (electric)

Scf: Standard cubic feet (standard references ISO temperature and pressure)

SCFM: Standard Cubic Feet per Minute (standard references ISO temperature
and pressure)

SLPM: Standard Liters per Minute (standard references ISO temperature and
pressure)

THD: Total Harmonic Distortion
460045 Rev C (November 2008)
Page 2 of 16
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Capstone Turbine Corporation  21211 Nordhoff Street  Chatsworth  CA 91311  USA
Product Specification: Model C200 - Capstone MicroTurbine
Table of Contents
Summary...................................................................................................................................... 1
Available Model Types ................................................................................................................ 1
Definitions .................................................................................................................................... 2
Performance Specification .......................................................................................................... 5
Performance Ratings at Full Load Power ............................................................................... 5
Electrical Performance Ratings at Full Load Power ............................................................... 5
Performance Derating.............................................................................................................. 6
Fuel Input Requirements at Full Load Power ....................................................................... 11
Exhaust Output Ratings at Full Load Power......................................................................... 11
Air Flow Requirements at Full Load Power........................................................................... 12
Acoustic Emissions Ratings at Full Load Power................................................................... 13
MicroTurbine Dimensions and Weights ................................................................................ 13
MicroTurbine Temperature Ratings ...................................................................................... 13
External Heat Recovery Module ............................................................................................... 14
Certification Information............................................................................................................. 15
Disclaimer Statement ................................................................................................................ 15
Capstone Contact Information .................................................................................................. 16
Capstone Applications ........................................................................................................... 16
Capstone Service................................................................................................................... 16
List of Tables
Table 1. C200 Model Designations............................................................................................ 1
Table 2. Performance Ratings ................................................................................................... 5
Table 3. Electrical Performance Ratings in Grid Connect Mode .............................................. 5
Table 4. Electrical Performance Ratings in Stand Alone Mode................................................ 6
Table 5. Fuel Input Requirements............................................................................................ 11
Table 6. Exhaust Output Ratings............................................................................................. 11
Table 7. Air Flow Requirements at ISO Conditions with Zero Back Pressure ....................... 12
Table 8. Acoustic Emissions Ratings....................................................................................... 13
Table 9. MicroTurbine Dimensions and Weights .................................................................... 13
Table 10. MicroTurbine Temperature Ratings ........................................................................ 13
Table 11. C200 with External Capstone Heat Recovery Module Accessory......................... 14
460045 Rev C (November 2008)
Page 3 of 16
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Capstone Turbine Corporation  21211 Nordhoff Street  Chatsworth  CA 91311  USA
Product Specification: Model C200 - Capstone MicroTurbine
List of Figures
Figure 1. C200 Net Power Output vs. Ambient Temperature................................................... 7
Figure 2. C200 Net Efficiency vs. Ambient Temperature.......................................................... 8
Figure 3. C200 Low Pressure Natural Gas Net Power vs. Ambient Temperature .................. 9
Figure 4. C200 Low Pressure Natural Gas Net Efficiency vs. Ambient Temperature ........... 10
460045 Rev C (November 2008)
Page 4 of 16
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Capstone Turbine Corporation  21211 Nordhoff Street  Chatsworth  CA 91311  USA
Product Specification: Model C200 - Capstone MicroTurbine
Performance Specification
Performance Ratings at Full Load Power
Table 2 summarizes performance ratings at full load power and ISO conditions.
Table 2. Performance Ratings
Parameter
C200 Low Pressure NG
All Other C200
Net Power Output
190 (+0/- 4) kW net
200 (+0/- 4) kW net
Net Efficiency (LHV)
31 (± 2)%
33 (± 2)%
Nominal Net Heat Rate
(LHV)
11,600 kJ/kWh
(11,000 Btu/kWh)
10,900 kJ/kWh
(10,300 Btu/kWh)
Nominal Generator Heat
Rate (LHV)
10,700 kJ/kWh
(10,200 Btu/kWh)
10,200 kJ/kWh
(9,700 Btu/kWh)
Nominal Steady State
Fuel Flow (HHV) (1) (2)
2,400,000 kJ/hr
(2,280,000 BTU/hr)
2,400,000 kJ/hr
(2,280,000 BTU/hr)
Notes:
(1) The ratio of Higher Heating Value (HHV) to Lower Heating Value (LHV) is assumed to be 1.1.
(2) Onload fuel flows can be up to two times higher than the steady state values.
Electrical Performance Ratings at Full Load Power
Table 3 presents the electrical performance ratings for Model C200 MicroTurbines operating
in the Grid Connect mode at ISO conditions with zero back pressure.
Table 3. Electrical Performance Ratings in Grid Connect Mode
Parameter
C200 Low Pressure NG
All Other C200
Net Power Output
190 (+0/- 4) kW
200 (+0/- 4) kW
190 kVA
200 kVA
400 to 480 VAC
400 to 480 VAC
50/60 Hz
50/60 Hz
Max Apparent Power
Output (1)
Nominal Voltage
Operating Range
Nominal Frequency
Operating Range
Output
Voltage Connection (2)
Max Output
Current Steady State
3-phase, 3 or 4 wire wye
3-phase, 3 or 4 wire wye
275 Amps RMS @ 400V
230 Amps RMS @ 480V
290 Amps RMS @ 400V
240 Amps RMS @ 480V
Current THD
IEEE 519 compliant, 5%
IEEE 519 compliant, 5%
Notes:
(1) The microturbine system operates at unity power factor in Grid Connect mode.
(2) The grid connection to the microturbine must be neutral grounded.
460045 Rev C (November 2008)
Page 5 of 16
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Capstone Turbine Corporation  21211 Nordhoff Street  Chatsworth  CA 91311  USA
Product Specification: Model C200 - Capstone MicroTurbine
Table 4 presents the electrical performance ratings for C200 MicroTurbines operating in the
Stand Alone mode at ISO conditions.
Table 4. Electrical Performance Ratings in Stand Alone Mode
Parameter
C200 Low Pressure NG
All Other C200
Net Power Output
190 (+0/- 4) kW
200 (+0/- 4) kW
Max Apparent Power Output (1)
258 kVA at 480 VAC
258 kVA at 480 VAC
Nominal Voltage Operating Range
400 to 480 VAC
400 to 480 VAC
Frequency Operating Range
10 to 60 Hz
10 to 60 Hz
3-phase, 4 wire wye
3-phase, 4 wire wye
Max Output Current (3)
310 Amps RMS
steady state
310 Amps RMS
steady state
Voltage THD
IEEE 519 Compliant, 5%
IEEE 519 Compliant, 5%
Output Voltage Connection
(2)
Notes:
(1) System power factor is limited by maximum current in Stand Alone mode
(2) Neutral must be solidly grounded
(3) Values assume linear load
Performance Derating
Performance is affected by ambient temperature and elevation. The performance ratings
listed above are at full load power at ISO conditions. Performance derating occurs at ambient
temperatures and elevations above ISO conditions and is also affected by air inlet pressure,
back pressure, and system parasitic loads (e.g. fuel gas compressor, battery charging).
Typical derating curves for power output and efficiency based on ambient temperature are
shown in the curves on the following pages. These curves assume no external parasitic loads
no inlet air restrictions, and no exhaust back pressure.
460045 Rev C (November 2008)
Page 6 of 16
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Capstone Turbine Corporation  21211 Nordhoff Street  Chatsworth  CA 91311  USA
Product Specification: Model C200 - Capstone MicroTurbine
Figure 1 presents the nominal rating and minimum/maximum net power output versus
ambient temperature (at sea level) for the standard high pressure natural gas C200
MicroTurbine, without fuel gas compression. For C200 installations with external heat
recovery module, this plot assumes the heat recovery module is in full bypass mode.
C200 HPNG Net Power vs. Ambient Temperature at Sea Level
200
180
160
Nominal
Net Power [kW]
140
Minimum
120
Maximum
100
C200 High Pressure
Natural Gas
80
60
40
20
0
0
10
20
30
40
50
60
70
80
90
100
110
120
Ambient Temperature [°F]
Figure 1. C200 Net Power Output vs. Ambient Temperature
Notes:
(1) Nominal Rating and Min/Max Net Power vs. Ambient Temperature at Sea Level with Zero Back Pressure for
the high pressure natural gas C200 MicroTurbine (without Gas Compression).
(2) All other C200 versions behave according to Figure 1, except the low pressure natural gas versions.
460045 Rev C (November 2008)
Page 7 of 16
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Capstone Turbine Corporation  21211 Nordhoff Street  Chatsworth  CA 91311  USA
Product Specification: Model C200 - Capstone MicroTurbine
Figure 2 presents the nominal rating and minimum/maximum net efficiency versus ambient
temperature (at sea level) for the high pressure natural gas C200 MicroTurbine, without gas
compression. For C200 installations with external heat recovery module, this plot assumes
the heat recovery module is in full bypass mode.
C200 HPNG Net Efficiency vs. Ambient Temperature at Sea Level
40
35
Net Efficiency [%]
30
25
Nominal
C200 High Pressure
Natural Gas
Minimum
20
Maximum
15
10
5
0
0
10
20
30
40
50
60
70
80
90
100
110
120
Ambient Temperature [°F]
Figure 2. C200 Net Efficiency vs. Ambient Temperature
Notes:
(1) Nominal Rating and Min/Max Net Efficiency vs. Ambient Temperature at Sea Level with Zero Back Pressure for
the high pressure natural gas C200 MicroTurbine (without Gas Compression).
(2) All other C200 versions behave according to Figure 2, except the low pressure natural gas versions.
460045 Rev C (November 2008)
Page 8 of 16
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Capstone Turbine Corporation  21211 Nordhoff Street  Chatsworth  CA 91311  USA
Product Specification: Model C200 - Capstone MicroTurbine
Figure 3 presents the nominal rating and minimum/maximum net power output versus
ambient temperature (at sea level) for the C200 low pressure natural gas versions, with the
external heat recovery module in full bypass mode and inlet fuel pressure of .25 psig
(1.7 kPag).
C200 LPNG Net Power vs. Ambient Temperature at Sea Level
200
180
160
Net Power [kW]
140
Nominal
120
Minimum
C200 Low Pressure
Natural Gas
Maximum
100
80
60
40
20
0
0
10
20
30
40
50
60
70
80
90
100
110
120
Ambient Temperature [°F]
Figure 3. C200 Low Pressure Natural Gas Net Power vs. Ambient Temperature
Note:
(1) Nominal Rating and Min/Max Net Power vs. Ambient Temperature at Sea Level with Zero Back Pressure for
the C200 low pressure natural gas versions and inlet fuel pressure of .25 psig (1.7 kPag).
460045 Rev C (November 2008)
Page 9 of 16
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Capstone Turbine Corporation  21211 Nordhoff Street  Chatsworth  CA 91311  USA
Product Specification: Model C200 - Capstone MicroTurbine
Figure 4 presents the nominal rating and minimum/maximum net efficiency versus ambient
temperature (at sea level) for the C200 low pressure natural gas versions, including the
external heat recovery module in full bypass mode and inlet fuel pressure at .25 psig
(1.7 kPag).
C200 LPNG Net Efficiency vs. Ambient Temperature at Sea Level
40
35
Net Efficiency [%]
30
25
Nominal
Minimum
20
C200 Low Pressure
Natural Gas
Maximum
15
10
5
0
0
10
20
30
40
50
60
70
80
90
100
110
120
Ambient Temperature [°F]
Figure 4. C200 Low Pressure Natural Gas Net Efficiency vs. Ambient Temperature
Note:
(1) Nominal Rating and Min/Max Net Efficiency vs. Ambient Temperature at Sea Level with Zero Back
Pressure for the C200 low pressure natural gas versions with inlet fuel pressure at .25 psig (1.7 kPag).
460045 Rev C (November 2008)
Page 10 of 16
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Capstone Turbine Corporation  21211 Nordhoff Street  Chatsworth  CA 91311  USA
Product Specification: Model C200 - Capstone MicroTurbine
Fuel Input Requirements at Full Load Power
Table 5 presents fuel input requirements at full load power and ISO conditions.
Table 5. Fuel Input Requirements
Inlet Pressure
Range
C200 Version
High Pressure NG
Low Pressure NG
Landfill
Digester
75 - 80 psig
(517 – 552 kPaG)
0.25 – 5 psig
(1.8 – 103 kPaG)
75 – 80 psig
(517 – 552 kPaG)
75 – 80 psig
(517 – 552 kPaG)
Fuel Type
Fuel Energy Content
Range [HHV]
Natural Gas
30,700 – 47,500 kJ/m3
(825 – 1,275 Btu/scf)
Landfill Gas
Digester Gas
13,000 – 22,300 kJ/m3
(350 – 600 Btu/scf)
20,500 – 32,600 kJ/m3
(550 – 875 Btu/scf)
Notes:
(1) Minimum power output is 100kW for these fuels. Additional fuel gas conditioning will be required.
Consult Capstone for specific application guidance.
Exhaust Output Ratings at Full Load Power
Table 6 presents nominal exhaust output ratings at full load power and ISO conditions.
Table 6. Exhaust Output Ratings
Parameter
C200 CARB
Natural Gas
All Other C200
Nominal Exhaust Gas Temp (1)
280 °C (535 °F)
280 °C (535 °F)
Nominal Total Exhaust Energy (1)
1,420,000 kJ/hr
(1,350,000 Btu/hr)
1,420,000 kJ/hr
(1,350,000 Btu/hr)
NOx Emissions (2)
<4 ppm V
@ 15% O2
<9 ppm V
@ 15% O2
Exhaust Mass Flow
1.33 kg/s
(2.93 lbm/s)
1.33 kg/s
(2.93 lbm/s)
Notes:
(1) These are the final exhaust temperature and exhaust energy if the external heat recovery module is bypassing
exhaust heat. Temperature and exhaust energy will be lower while recovering heat.
(2) Emissions for standard natural gas at 1,000 BTU/scf (HHV).
460045 Rev C (November 2008)
Page 11 of 16
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Capstone Turbine Corporation  21211 Nordhoff Street  Chatsworth  CA 91311  USA
Product Specification: Model C200 - Capstone MicroTurbine
Air Flow Requirements at Full Load Power
Table 7 summarizes the nominal air flow requirements of the C200 MicroTurbine systems.
Table 7. Air Flow Requirements at ISO Conditions with Zero Back Pressure
Parameter
All C200
Engine Inlet Air Flow
2,600 scfm
(73,600 slpm)
Engine Inlet Air Temp (1) (2)
-20 to 50 °C
(-4 to 122 °F)
Electronics Controller Inlet Air Flow (3)
3,600 scfm
(102,000 slpm)
Electronics Controller Inlet Air Temp (2)
-20 to 50 °C
(-4 to 122 °F)
Notes:
(1) For C200 versions that include the external heat recovery module, minimum operating ambient temperature
may be higher, depending on heat recovery fluid characteristics. For water, minimum ambient temperature is 1.7 °C
(35 °F).
(2) The Electronics Controller inlet air temperature must be within 2 °C (3.6 °F) of the Engine inlet air temperature.
(3) Values are the same for all C200 configurations, including low pressure and dual mode versions with batteries.
460045 Rev C (November 2008)
Page 12 of 16
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Capstone Turbine Corporation  21211 Nordhoff Street  Chatsworth  CA 91311  USA
Product Specification: Model C200 - Capstone MicroTurbine
Acoustic Emissions Ratings at Full Load Power
Table 8 presents nominal acoustic emissions ratings, captured at full rated output power at a
distance of 10 meters (33 feet). Actual sound levels for a given installation depend on many
site factors, so the numbers provided here should only be used as general guidance.
Table 8. Acoustic Emissions Ratings
Parameter
All C200
Acoustic Emissions
(1)
65 dBA
Note:
(1) Average of acoustic emissions measurements taken 10 meters from all sides at a height of 1.4 meters.
MicroTurbine Dimensions and Weights
Table 9 summarizes approximate dimensions and weights of the C200 MicroTurbine
systems.
Table 9. MicroTurbine Dimensions and Weights
Parameter
C200 Low Pressure
Natural Gas
All Other C200
Height (1)
2,490 mm
(98 inches)
2,490 mm
(98 inches)
Width
1,700 mm
(67 inches)
1,700 mm
(67 inches)
Depth
3,660 mm
(144 inches)
3,660 mm
(144 inches)
2,730 kg (6,000 lb)
(Grid Connect)
2,270 kg (5,000 lb)
(Grid Connect)
3,640 kg (8,000 lb)
(Dual Mode)
3,180 kg (7,000 lb)
(Dual Mode)
Weight
Notes:
(1) Height dimensions are to the roof line. Exhaust outlet extends at least 8 inches above the roof line. Rear roof
extension and exhaust outlet can be removed to provide 88 inch height for shipment, if needed.
MicroTurbine Temperature Ratings
Table 10 summarizes the temperature ratings of MicroTurbine systems. The C200 must be
stored dry. For C200 systems with external heat recovery, minimum operating temperature
depends on heat recovery fluid characteristics.
Table 10. MicroTurbine Temperature Ratings
Parameter
C200
Operating Temperature
-20 to 50 °C (-4 to 122 °F)
Storage Temperature
-40 to 65 °C (-40 to 149 °F)
460045 Rev C (November 2008)
Page 13 of 16
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Capstone Turbine Corporation  21211 Nordhoff Street  Chatsworth  CA 91311  USA
Product Specification: Model C200 - Capstone MicroTurbine
External Heat Recovery Module
A Capstone external heat recovery module is available as an accessory for all C200 systems.
Tables 11 shows the heat recovered in full heat recovery mode for water at various inlet
water temperatures. The minimum heat recovery is 5 kWth (17 MBtu/hr) in full bypass mode.
Table 11. C200 with External Capstone Heat Recovery Module Accessory
Water Temperature
Heat Recovery
Inlet
Outlet
30 C (85 F)
37 C (98 F)
284 kWth (970 MBtu/hr)
60 C (140 F)
66 C (151 F)
245 kWth (835 MBtu/hr)
85 C (185 F)
90 C (195 F)
212 kWth (724 MBtu/hr)
Conditions for Table 11:
 ±10% performance range
 9.5 l/s (150 gal/min) water flow
 Full power output @ 200 kWe
 ISO Conditions
460045 Rev C (November 2008)
Page 14 of 16
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Capstone Turbine Corporation  21211 Nordhoff Street  Chatsworth  CA 91311  USA
Product Specification: Model C200 - Capstone MicroTurbine
Certification Information
Please contact Capstone for the latest certification information.
Disclaimer Statement
All information contained in this document is subject to change without notice. The products
described in this document are NOT intended for use in applications where malfunction may
result in injury or death to persons. The information contained in this document does not
affect or change Capstone’s warranties. Nothing in this document shall operate as an
express or implied license or indemnity under the intellectual property rights of Capstone or
third parties. All information contained in this document was obtained in specific environments
and is presented as an illustration. The results obtained in other environments may vary.
THE INFORMATION CONTAINED IN THIS DOCUMENT IS PROVIDED ON AN “AS IS”
BASIS. In no event will Capstone be liable for damages arising directly or indirectly from any
use of the information contained in this document.
460045 Rev C (November 2008)
Page 15 of 16
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Capstone Turbine Corporation  21211 Nordhoff Street  Chatsworth  CA 91311  USA
Product Specification: Model C200 - Capstone MicroTurbine
Capstone Contact Information
If questions arise regarding Model C65 Product Specification, please contact Capstone
Turbine Corporation for assistance and information:
Capstone Applications
Toll Free Telephone: (866) 4-CAPSTONE or (866) 422-7786
Fax: (818) 734-5385
E-mail: applications@capstoneturbine.com
Capstone Service
Capstone Technical Support
Toll Free Telephone: (877) 282-8966
Service Telephone: (818) 407-3600  Fax: (818) 734-1080
E-mail: service@capstoneturbine.com
Capstone Technical Support (Japan)
Service Telephone: (818) 407-3700  Fax: (818) 734-1080
E-mail: servicejapan@capstoneturbine.com
460045 Rev C (November 2008)
Page 16 of 16
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.