Amana PTH123G35AXXX Installation Guide


Add to my manuals
8 Pages

advertisement

Amana PTH123G35AXXX Installation Guide | Manualzz

PTAC A

ir

C

ondiTioners

And

H

eAT

P

umPs

11.7 EER / 3.4 COP P

roduCT

s

PeCifiCATions

Product Features

• Quiet operation: STC of 28

• Assembled in the USA for 30 years

• Increased dehumidification capacity

• 100% run-tested at our plant in Fayetteville, TN, for leaks

• 7⅝” unit front depth: one of the shallowest silhouettes in the industry today

• Removable condenser shroud allows easy access to enable regular cleaning of coils

• Easy pull-out filters that are washable and easy to maintain

• Filter drier for sealed system refrigerant

• 7-Button touch pad provides complete control to guests for in-room comfort while maintaining energy efficiency

• Condensate dispersion system removes condensate from indoor cooling operation and evaporates it into the atmosphere through the condenser

• Digismart™ front desk control & energy management software

• Room freeze protection is activated when the unit senses temperatures of 40°F or below

• Versatile style that blends into any room’s color scheme and decor

• Easy to service with on-board led diagnostics

• Digismart™ wireless remote thermostat is available

• Remote temperature sensing for guest climate control

• Extended heat pump heating down to as low as 24°F outdoor ambient temperature

• Zero floor clearance allows unit to be installed flush to a finished floor

• 30-second fan-off delay

• Compressor lock-in prevents compressor short-cycling

• Constant fan mode

• Hidden ventilation control

• High-pressure switch

Control Board

First-Year Warranty: Parts & Labor on entire unit

Second through Fifth Year: Parts & Labor on certain sealed system components

Second through Fifth Year: on certain functional parts only

* Complete warranty details available at www.amana-ptac.com.

SS-DPTAC www.amana-ptac.com

Amana® is a trademark of Maytag Corporation or its related companies and used under license to Goodman Company, L.P., Houston, Texas.

2/13

Supersedes 9/12

P roduct

S

PecificationS n

omenClATure

 

PTC

1,2,3

07

4,5

3

6

Basic  Model  Type

PTC

PTH

DRY

Standard  Cooler  PTAC

Standard  Heat  Pump  PTHP

Dehumid  Cooler  PTAC

Cooling  Capacity

07

09

10

12

7000  BTU/h

9000  BTU/h

10000  BTU/h

12000  BTU/h

3

4

5

15 14000  BTU/h

Rated  Voltage

2 115V,  60  Hz,  1  Ph

230/208V,  60  Hz,  1  Ph

265V,  60  Hz,  1  Ph

240/220V,  50  Hz,  1  Ph

60  Hz

60  Hz

50  Hz

50  or  60  Hz

60  Hz

Design  Series

G R-­‐410A

Heater  Size

00 No  Electric  Heat

15 1.5  kW

25 2.5  kW

35

50

3.5  kW  (230/208V)

3.7  kW  (265V)

5.0  kW

G

7

35 AXXX AA

8,9 10,11,12,13 14,15

Engineering  

Major  &  Minor  Revisions

Standard  Model

Corrosion  Protec>on  (Seacoast)

Power  Door

Fuse  Holder  (230/208  Only)

Hydronic  Heat-­‐Capable

Condensate  Pump  (PTH  Only)

Quiet  STC  31  Chassis

RF  Antenna

Power  Vent placeholder

Hard-­‐Wired  (PTQC)

Features  Code

Q

R

V

X

W

F

H

P

A

C

D

Use  up  to  4  as  needed  in  alphabe>cal  order

Examples:

PTC123E50AXXX

PTC123E50CXXX

PTC073E35CRXX

PTC073E25CQRW

P roduct

S

PecificationS

2 www.amana-ptac.com SS-DPTAC SS-DPTAC www.amana-ptac.com

3

2

P roduCT

s

PeCifiCATions www.amana-ptac.com SS-DPTAC

P roduCT

s

PeCifiCATions

P

roduCT

s

PeCifiCATions

: PTC m

odels

— C

ooling

/e

leCTriC

H

eAT

230/208 V olts

Model ⁶ , ⁸ , ⁹

Voltage ³

Capacity (BTU/h)

Amps ¹⁰

Watts ¹⁰

EER

Unit without Electric Heater

Min. Circuit Amps ² , ⁴ , ¹⁰

CFM (Cool/Wet Coil)

CFM (Dry Coil)

Ventilated Air, CFM (Fan Only)*

Dehumidification (Pints/Hr.)

Net Weight (lbs.)

Ship Weight (lbs.)

High

Low

High

Low

PTC

073G***XXX

230 / 208

7,700 / 7,700

3.5 / 3.5

670/660

11.5/11.7

4.2

290

264

310

282

65*

1.7

98

113

PTC

093G***XXX

230 / 208

9,000 / 9,000

4.1 / 4.1

805/785

11.2/11.5

4.9

290

264

310

282

65*

2.2

102

117

PTC

123G***XXX

230 / 208

11,700 / 11,500

5.6 / 5.6

1135/1105

10.3/10.4

6.8

290

264

310

282

65*

3.6

102

119

265/277 V olts

Voltage ¹ , ³

Capacity (BTU/h)

Amps ¹⁰

Watts ¹⁰

EER

Model 1, 6, 8

PTC

074G***XXX

265

7,700

3.0

670

11.5

PTC

094G***XXX

265

9,000

3.6

795

11.3

PTC

124G***XXX

265

12,000

4.8

1,165

10.3

PTC

154G***XXX

265

14,800

6.0

1,480

10.0

Unit without Electric Heater

Min. Circuit Amps ² , ⁴ , ¹⁰

CFM (Cool/Wet Coil)

CFM (Dry Coil)

Ventilated Air, CFM (Fan Only)*

Dehumidification (Pints/Hr.)

Net Weight (lbs.)

High

Low

High

Low 282

65*

1.7

98

113

3.6

290

264

310

282

65*

2.2

102

117

4.4

290

264

310

282

65*

3.6

102

119

5.9

290

264

310

332

65*

4.4

113

130

7.4

340

314

360

Ship Weight (lbs.)

* Approximately 95 CFM with optional power vent kit. Actual vent CFM performance will vary due to application and installation conditions. See Notes on following page.

PTC

153G***XXX

230 / 208

15,000 / 14,700

7.0 / 7.0

1500/1470

10.0/10.0

8.5

340

314

360

332

65*

4.4

113

130

SS-DPTAC www.amana-ptac.com

3

P roduCT

s

PeCifiCATions

P

roduCT

s

PeCifiCATions

: PTC / PTH m

odels

— e

leCTriC

H

eAT

P

erformAnCe

(Primary Heating for PTC Models; Auxiliary Heating for PTH Models; See below for Power Cord Configuration)

Voltage

230/208V

230/208V

230/208V

265V

265V

265V

Electric

Heat (kW)

2.5

3.5

5

2.5

3.7

5

1

1

1

1

1

1

No. of

Stages

Nominal Heating (BTU/h)

@ 230V @ 208V @ 265V

8,500

12,000

17,100

- -

- -

- -

6,800

9,900

14,000

- -

- -

- -

- -

- -

- -

8,500

12,600

17,100

Total

Watts 6

Total

Amps

2,570 / 2,115 11.2 / 10.1

3,570 / 2,935 15.5 / 14.1

5,070 / 4,160 22.1 / 20.0

2,570 9.7

3,770

5,070

14.2

19.2

Min. Circuit

Ampacity²

MOP 4

(amps)

14.0

19.4

27.5

12.1

17.8

23.9

15

20

30

15

20

25

Power

Cord

6-15 P

6-20 P

6-30 P

7-20 P

7-20 P

7-30 P

Notes

¹ All 265-volt models must use an Amana® brand sub-base (PTSB4**E) or an Amana® brand hard-wire kit PTPWHWK4 and disconnect switch PSHW04A.

² Minimum Circuit Ampacity (MCA) ratings conform to the National Electric Code; however, local codes should apply.

³ Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts. Minimum voltage on 265-volt models is 239 volts; maximum is 292 volts.

⁴ Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265-volt models must be cartridge-style time-delay fuses (included and factory-installed on all Amana® brand 265-volt chassis). See heater performance

⁵ Heating capacity and efficiency based on unit operation without condensate pump; unit automatically switches to electric heat at approximately 24°F outdoor ambient.

⁶ Specify two-digit heater kW size to complete model number.

⁷ R-410A refrigerant used in all systems.

⁸ All units meet or exceed ASHRAE 90.1 standards.

⁹ All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.

¹⁰ Refer to electric heat performance data for total MCA and recommended overcurrent protection. Amps and Watts notation refers to compressor only.

P roduCT

s

PeCifiCATions

4 www.amana-ptac.com SS-DPTAC SS-DPTAC www.amana-ptac.com

5

4

P roduCT

s

PeCifiCATions www.amana-ptac.com SS-DPTAC

P roduCT

s

PeCifiCATions

P

roduCT

s

PeCifiCATions

: PTH m

odels

— C

ooling

/H

eAT

P

umP

/e

leCTriC

H

eAT

230208 V olts

Model ⁶ , ⁸ , ⁹

Voltage ³

Capacity (BTU/h)

Amps ¹⁰

Watts ¹⁰

EER

Unit without Electric Heater

Min. Circuit Amps ² , ⁴ , ¹⁰

CFM (Cool/Wet Coil)

PTH

073E**AXXX

230 / 208

7,600 / 7,500

3.5 / 3.5

650 / 620

11.3 / 11.4

PTH

093E**AXXX

230 / 208

9,000 / 8,900

4.1 / 4.1

770 / 765

11.1 / 11.1

PTH

123E**AXXX

230 / 208

11,500 / 11,100

5.6 / 5.6

1095 / 1065

10.2 / 10.1

PTH

153E**AXXX

230 / 208

14,000 / 13,900

7.0 / 7.0

1460 / 1465

9.6 / 9.5

CFM (Dry Coil)

Ventilated Air, CFM (Fan Only)*

Dehumidification (Pints/Hr.)

Net Weight (lbs.)

Ship Weight (lbs.)

High

Low

High

Low 282

65*

1.7

108

123

4.2

290

264

310

282

65*

2.2

112

127

5.0

290

264

310

282

65*

3.6

115

132

6.8

290

264

310

332

65*

4.4

126

143

8.5

340

314

360

265,277 V olts

Model ¹ , ⁶ ,

Voltage ¹ , ³

Capacity (BTU/h)

Amps ¹⁰

Watts ¹⁰

EER

Unit without Electric Heater

Min. Circuit Amps ² , ⁴ , ¹⁰

CFM (Cool/Wet Coil)

CFM (Dry Coil)

Ventilated Air, CFM (Fan Only)*

Dehumidification (Pints/Hr.)

Net Weight (lbs.)

Ship Weight (lbs.)

High

Low

High

Low

PTH

074E**AXXX

265

7,500

3.0

635

11.6

3.6

290

264

310

282

65*

1.7

108

123

PTH

094E**AXXX

265

9,000

3.6

780

11.1

4.4

290

264

310

282

65*

2.2

112

127

PTH

124E**AXXX

265

11,500

4.8

1115

10.0

5.9

290

264

310

282

65*

3.6

115

132

PTH

154E**AXXX

265

14,000

6.0

1430

9.7

7.3

340

314

360

332

65*

4.4

125

142

* Approximately 95 CFM with optional power vent kit. Actual vent CFM performance will vary due to application and installation conditions. See Notes on previous page

SS-DPTAC www.amana-ptac.com

5

6

P roduCT

s

PeCifiCATions

P

roduCT

s

PeCifiCATions

: PTH m

odels

— r

everse

-C

yCle

H

eATing

P

erformAnCe

230/208 V olts

Heating Capacity

Voltage ³

BTU/h ⁵

Amps ¹⁰

Watts ¹⁰

COP 5

CFM (Dry)

PTH

073E**AXXX

230 / 208

6,800 / 6,800

3.5 / 3.5

605 / 605

3.3 / 3.3

310

PTH

093E**AXXX

230 / 208

8,300 / 8,100

4.1 / 4.1

735 / 720

3.3 / 3.3

310

PTH

123E**AXXX

PTH

153E**AXXX

230 / 208 230 / 208

10,900 / 10,500 13,500 / 13,300

5.6 / 5.6

1040 /1020

3.1 / 3.1

310

7.0 / 7.0

1365 / 1345

2.9 / 2.9

360

265/277 V olts

Heating Capacity

Voltage ³

BTU/h ⁵

Amps ¹⁰

Watts ¹⁰

COP ⁵

CFM (Dry)

PTH

074E**AXXX

265

6,800

3.0

585

3.4

310

PTH

094E**AXXX

265

8,200

3.6

730

3.3

310

PTH

124E**AXXX

265

11,000

4.8

1040

3.1

310

PTH

154E**AXXX

265

13,500

6.0

1365

2.9

360

COP = Coefficiency of Performance; per ARI test procedures, units are rated for capacities and efficiencies.

Notes:

¹ All 265-volt models must use an Amana® brand sub-base (PTSB4**E) or an Amana® brand hard-wire kit (PTPWHWK4).

² Minimum Circuit Ampacity (MCA) ratings conform to the National Electric Code; however, local codes should apply.

³ Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts.

Minimum voltage on 265-volt models is 238.5 volts; maximum is 291.5 volts.

⁴ Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265-volt models must be cartridge-style time-delay fuses (included and factory-installed on all Amana® brand 265-volt chassis). See heater performance for total MCA.

⁵ Heating capacity and efficiency based on unit operation without condensate pump; unit automatically switches to electric heat at approximately 24°F outdoor ambient.

⁶ Total watts for 12,000 and 15,000 BTU/h models; subtract 70 watts for PT07/09*E**A*

⁷ Specify two-digit heater kW size to complete model number.

⁸ Total amps for 12,000 and 15,000 BTU/h models; subtract 0.2 amps for PT07/09*E*A*.

⁹ R-410A refrigerant used in all systems.

¹⁰ All units meet or exceed ASHRAE 90.1 standards.

¹¹ All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.

¹² Refer to electric heat performance data for total MCA and recommended overcurrent protection. Amps and Watts notation refers to compressor only.

P roduCT

s

PeCifiCATions www.amana-ptac.com SS-DPTAC SS-DPTAC www.amana-ptac.com

7

6

P roduCT

s

PeCifiCATions www.amana-ptac.com SS-DPTAC

P roduCT

s

PeCifiCATions

C

onTrACTor

'

s

b

id

s

HeeT

Furnish and install air-cooled through-the-wall package terminal air conditioners amd heat pumps (assembled in the USA).

Units are rated in accordance with the ARI (Air Conditioning & Refrigeration Institute) Standards 310/380-93, CSA (Canadian

Standards Association) EEV certification programs and listed by U. L. (Underwriters Laboratories). r

ATings

Each unit must meet the following specifications:

ARI rating of _________BTUH cooling (and _________ BTUH reverse cycle heating with a COP of _________ at 47° F O.D.)

Electric resistance heat of _________ BTUH. Total Amp draw must be of ________ and _________ Watts at _________ volts.

The unit must remove a minimum of _________ pints of moisture per hour when operated at rating conditions. The EER must be a minimum of _________ EER.

u niT

C

HAssis

Each unit must be slide out design shipped with room cabinet front installed. Unit chassis must have the ability to be installed with 0 clearance from finished floor. An electrical power cord must be included with chassis and installed by the manufacturer to assure proper NEMA 6 or 7 configuration and UL-approved length. Units less than 250 volts must also have a LCDI power cord.

Unit must be tested for conformance to ASTME water infiltration specification ASTME 331-86, which ensures no water infiltration when tested at 8" rain per hour at 63 mph wind for 15 minutes.

r oom

C

AbineT

The monochromatic front of the room cabinet must be able to be field-secured to chassis to inhibit tampering. Filter must be accessible without removing room front. Cabinet depth must not exceed 7⅝” to minimize unit’s impact on room space.

C oils

Unit’s coils must have rifled copper tubing expanded into rippled-edge louvered aluminum fins. Exterior coil must be of a two-row bent coil design with removable shroud top to allow easy-access for cleaning of the exterior coil.

H eAT

P umPs

Each unit must include a change-over thermistor that senses an outside ambient switch-over temperature as low as 24°F, lockopen refrigerant reversing valve during heat pump operation, temperature-activated defrost drain and automatic emergency heat operation to override the heat pump’s change-over thermostat and bring on electric resistance heaters in the event of a sealed system failure. Unit must not operate compressor and electric heaters simultaneously.

C omPressor

The compressor must be hermetically sealed, internally isolated, rotary-type and permanently mounted on rubber isolators. No removal or adjustment of compressor hold-down bolts is to be required during installation.

W

ArrAnTy

The warranty is for Full One Year on the entire unit; Full 2nd through

5th Year on the entire sealed refrigerant system components;

Limited Second through Fifth Year on functional parts only.

u niT

d igiTAl

C onTrols

The unit’s control must be completely wired and accessible from the top of the chassis. Controls shall be a LED touch-pad design with seven large, easy-to-read and use buttons: Heat – Cool –

Off – Fan – Temp+ (plus) – Temp- (minus) and two red sevensegment LED temperature displays. Unit shall have a green status LED to advise owner of operational diagnostic messages.

Unit shall have one-button activation via membrane touch-pad.

Unit control board shall have an 18-pin low-voltage connector to allow for easy connection to remote wired devices. Unit shall have two serial-port connectors for easy connection to wired or wireless EMS (Energy Management Systems).

Unit must have the ability to easily configure owner-selectable and programmable functions:

• Fan-cycle operation

• Electronic temperature limiting for cooling

• Electronic temperature limiting for heating

• Enhanced dehumidification cooling operation

• Unoccupied 18-hour temperature set-back

• Un-rented temperature set-back

• Multiple unit twinning to one wired thermostat

• Load-shedding operation

• Front-desk on-off or temperature set-back

Unit must be able to connect to approved remote devices:

• Wired thermostat

• Wired door motion sensor

• Wired room motion sensor

• Wired room-to-room transfer fan

• Front Desk Control

• Future RF wireless communications devices

Unit must be able to acquire and display operational temperature data from up to six installed thermistors to include:

• IAT—Indoor air temperature (black)

• ICT—Indoor coil temperature (red )

• IDT—Indoor discharge temperature (yellow)

• OCT—Outdoor coil temperature (blue) (heat pumps & Wireless cooler models)

• OAT— Outdoor Air Temperature (Wireless-ready models only)

• Orange—Miscellaneous thermistor or analog device (optional) e vAPorATor

/C ondenser

f

Ans

Direct drive with a permanent, split-capacitor, two-speed indoor motor. Condensate must be directed onto the back and sides of the coil to aid in evaporation and removal.

A ir

d isCHArge

Must be a sloped surface so that obstructions cannot be placed on the unit. Discharge conditioned air can be directed into the room at an angle of 16 or 56 degrees from the vertical position.

The discharge grille must be of polycarbonate material to resist bending, cracking, rusting and corrosion.

SS-DPTAC www.amana-ptac.com

7

P roduct

S

PecificationS

New installations typically require a minimum of WS900D wall sleeve and an outdoor grille.

W

All

s leeves

(Ws900e)

The wall sleeve must be industry-accepted dimensions:

14⅛” depth x 42” width x 16¹/₁₆” height and constructed of

G90 HDG galvanized steel with a baked corrosion-inhibiting urethane primer and baked-polyester topcoat enamel.

Sleeve must be insulated and shipped with a weather resistant rear closure panel installed.

o uTdoor

G rilles

Outdoor grille must be architecturally extruded, louvered aluminum (AGK01*B), one-piece polymer-blend injection molded louver (PGK01*B) or standard stamped aluminum

(SGK**B). All other grilles must be submitted to the PTAC manufacturer for feasibility, airflow characteristics and compliance with UL regulations, where necessary.

The optional accessories listed below perform specific functions required in some installations.

C ondensATe

d rAin

K iT

(dK900d)

Attaches to the bottom of the wall sleeve for directionalcontrolled internal or external disposal of condensate, defrost or rain water.

s ubbAse

K iT

(PTsb***e)

Necessary for UL listing requirements for 265V units (Hard

Wire Kit may be substituted for Subbase kit). Optional for

230/208V units. Must be pre-wired to facilitate field-electrical connections and include an NEMA 6 or 7 configuration electrical receptacle. It must have two leveling screws for sleeve support and accurate unit leveling during installation.

Locations for field installation of physical disconnect switches, cartridge-style fuse holders and circuit breakers must be provided. Side-skirts must be provided with subbases. (PTSB000E Non-Electrical Subbase available.)

P oWer

v enT

& d

AmPer

Must be provided to maximize ventilation air intake to up to approximately 95 CFM. Power vent must be off and damper door closed when unit fan is de-energized.

f use

H older

( inCluded in

265v

CHAssis

)

Must be installed either in the unit or the subbase and must match the electrical requirements of the chassis.

s eCuriTy

K ey

l oCKs

(Kl03e)

Must be installed to prevent tampering of the unit controls.

Unit room cabinet must also be secured to the chassis with field supplied screws. UL-approved for institutional use only.

d isConneCT

s

WiTCH

Power disconnect switch must be installed in subbase for use as a physical disconnect, where required by local codes.

d uCT

K iTs

(mdK01e, edK02b, TdK02b, PTdK01e, ddK01e)

Three kits must be supplied to provide ducted, conditioned air into a second room: a main duct kit, an extension duct kit and a terminal duct kit.

H ydroniC

H eAT

K iT

Is required for heating functions instead of electric resistance heaters. Unit must retain complete service access with the kit installed. Proper water or steam valves must be used.

C ondensATe

r emovAl

P umP

(H eAT

P umPs only

)

Must be installed to assist in removing the condensate developed by the heat pump operation and transfer it to the indoor coil to dissipate into the room, adding humidity to the room.

C irCuiT

b reAKer

K iT

Must be installed in subbase to provide overcurrent protection for proper 230/208V amperage. Can also be used as a physical disconnect where local codes permit for

230/208 voltage.

H

Ard

W ire

K iT

Must be used to permanently wire chassis for hard wire purposes. (For 265V units, Hard Wire Kit may be substituted with Subbase Kit.)

T

HermosTATs

A manufacturer-approved manual, auto changeover or programmable traditionally wired thermostat must be installed to provide full remote operation of the chassis. A

Remote Escutcheon Kit must be used to indicate remote operation.

8

Amana® is a trademark of Maytag Corporation or its related companies and used under license to Goodman Company, L.P. All rights reserved. Our continuing commitment to quality products may mean a change in specifications without notice. © 2013 • Goodman Company, L.P. • Houston, Texas • Printed in the USA.

www.amana-ptac.com SS-DPTAC SS-DPTAC www.amana-ptac.com

P roduct

S

PecificationS

PB

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Key Features

  • Quiet operation: STC of 28
  • Assembled in the USA for 30 years
  • Increased dehumidification capacity
  • 100% run-tested at our plant in Fayetteville, TN, for leaks
  • Versatile style that blends into any room’s color scheme and decor
  • Easy to service with on-board led diagnostics
  • Digismart™ wireless remote thermostat is available

Related manuals

Frequently Answers and Questions

How many cooling and heating stages does the unit have?
The unit has one cooling stage and one heating stage.
What is the minimum voltage required for the unit to operate?
The minimum voltage required for the unit to operate is 197 volts.
What is the maximum voltage required for the unit to operate?
The maximum voltage required for the unit to operate is 253 volts.
What is the minimum circuit ampacity required for the unit?
The minimum circuit ampacity required for the unit is 14.0 amps.
What is the maximum circuit ampacity required for the unit?
The maximum circuit ampacity required for the unit is 19.4 amps.