Operating instructions Wireless temperature relay type

Add to my manuals
20 Pages

advertisement

Operating instructions Wireless temperature relay type | Manualzz

MINIPAN

®

digital panel meters, temperature- and mains controlling, special purpose instruments for customer requirements www.ziehl.com

Operating instructions

Wireless temperature relay type WR250

potential-free temperature monitoring

Integrated antenna

Input for external antenna when mounted in shielded area (metallic switchgear cabinet) or under difficult radio reception conditions

ATTENTION: No external antenna included within the scope of supply.

Please order extra when required.

datum / name ) : 13.05.2011 Sc

Page 1 of 20

Z. Nr.: 12200-0702-02

Type: WR250

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, e-mail: [email protected]

Table of Contents

1.

Application and brief description ............................................................................ 3

2.

Function overview ..................................................................................................... 3

3.

Connection diagram ................................................................................................. 3

4.

Display and control elements .................................................................................. 4

5.

Important information ............................................................................................... 5

6.

Installation ................................................................................................................. 6

7.

Detailed description .................................................................................................. 6

8.

Starting the wireless system .................................................................................... 7

8.1

General notes on operation ................................................................................... 7

8.2

Display mode ........................................................................................................ 7

8.3

Menu mode ........................................................................................................... 7

8.4

Parametrization mode ........................................................................................... 7

8.5

Operating flowchart ............................................................................................... 8

8.6

Startup overview.................................................................................................... 9

8.7

Configuration ......................................................................................................... 9

8.8

Registration of wireless sensors ............................................................................ 9

8.9

Alarm parametrization ......................................................................................... 10

8.10

Short-circuit monitoring ....................................................................................... 11

8.11

Relay test ............................................................................................................ 11

8.12

RS485 Modbus interface ..................................................................................... 12

8.13

Sensor Simulation ............................................................................................... 12

8.14

Code lock ............................................................................................................ 13

8.15

Notes on operation: ............................................................................................. 13

8.16

Device reaction time – measuring time t

M

........................................................... 14

8.17

Possible values in the display ............................................................................. 14

9.

Factory default settings .......................................................................................... 16

10.

Servicing and maintenance .................................................................................... 17

11.

Troubleshooting ...................................................................................................... 17

11.1

Displaying the software version ........................................................................... 18

12.

Technical data ......................................................................................................... 18

13.

Design V4 ................................................................................................................ 20

datum / name ) : 13.05.2011 Sc

Page 2 of 20

Z. Nr.: 12200-0702-02

Type: WR250

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, e-mail: [email protected]

1. Application and brief description

The WR250 wireless relay is a receiver and evaluation device for WS Pt 100 wireless sensors. Up to 6 wireless sensors transmit temperature values by radio, which are displayed and evaluated by the WR250.

Use:

for overheating protection in high-voltage transformers (also in primary coils)

for measuring temperatures at high potential

where contact-free data transmission by radio is preferred

2. Function overview

evaluation of 1

– 6 WS Pt 100 wireless sensors

 measurement and control range 0 … 180°C

4 relay output ports (1 changeover contact each), 3 alarms fully programmable

switch points and relay function pre-set for transformer control (ventilator, warning and shut-down)

alarm in case of sensor errors at the «sensor alarm» relay

multi-voltage power supply AC/DC 24-240 V

display / store the measured MIN and MAX values

interface RS485 (Modbus) for scanning of temperature and alarms and for parametrization

Feeder clamps pluggable

Intergrated antenna, input for external antenna

3. Connection diagram

1) Links for terminating resistor

2) Connector for external antenna datum / name ) : 13.05.2011 Sc

Page 3 of 20

Z. Nr.: 12200-0702-02

Type: WR250

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, e-mail: [email protected]

4. Display and control elements

1 LEDs relay status

K1, K2, K3 lit yellow = relay engaged

sensor alarm (K4) lit red = relay disengaged

2 Digital display, 4 digits for

temperature

alarms ( 8 Al1 8 , 8 Al2 8 , 8 Al3 8 )

error messages ( 8 Err1 8 … 8 Err9 8 )

menu and parameterization mode

3 Key «Up» (in Display mode, normal state)

Press briefly: Change to menu mode (see operating instructions item 8.3)

Confirmation for > 2 s: Display MAX values measured by the selected sensor.

Additional pressing of the «Set» key for ≥ 2s will erase the stored MIN/MAX values.

4 Key «Set/Reset» (in Display mode, normal state)

Press briefly: Display the next sensor (sensor LED lit) / display the highest temperature measured by all sensors (LEDs for all registered sensors lit)

Confirmation for 10 s: Display the software version (z. B. 8 0-00 8 )

5 Key «Down» (in Display mode, normal state)

Press briefly: Change to Menu mode (see operating instructions item 8.3)

Confirmation for > 2 s: Display the MIN value measured by the selected sensor.

Additional pressing of the «Set» key for ≥ 2s will erase the stored MIN/MAX values.

6 Sensor LEDs

Yellow LEDs on: indicate the wireless sensor currently displayed. If the LEDs for all registered sensors are lit, the warmest is being shown.

Red LEDs on: indicate an error at the wireless sensor. The sensor can be selected using key «Set/Reset», and the display will show an Error Code ( 8 Err 8 ).

The following Error Codes are possible:

8 Err1 8 sensor short-circuited at the WS Pt 100 wireless sensor

8 Err2 8 sensor interruption at the WS Pt 100 wireless sensor

8 Err3 8 no radio contact with the WS Pt 100 wireless sensor

8 Err4 8 illumination of the WS Pt 100 wireless sensor too low

8 Err5 8 energy level of the WS Pt 100 wireless sensor too low datum / name ) : 13.05.2011 Sc

Page 4 of 20

Z. Nr.: 12200-0702-02

Type: WR250

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, e-mail: [email protected]

5. Important information

!

WARNUNG

Dangerous electric voltage!

May cause electric shock and burns.

Before beginning work, disconnect system and device.

Correct and safe operations of any device requires that it has been transported and stored appropriately, installed and commissioned correctly and is being operated according to the instructions.

Only persons familiar with installation, start-up and operations and possessing qualifications appropriate for their work may perform work on the device. They must observe the contents of the operating instructions, the information printed on the device and the relevant safety regulations for construction and operation of electric installations.

The devices are manufactured in accordance with DIN / EN and leave the production site in a condition of safety-related flawlessness.

If in any case the information provided in the operating instructions should be insufficient, please contact us directly, or address your local representative.

When using the device outside the area of applicability of the industrial norms referred to in the present operating instructions and valid in Europe, in their stead comply with the applicable regulations valid in the country of application.

!

Caution!

Do not connect or disconnect the device under power. Before connecting the device to the mains, make sure that the control voltage according to the type plate (on the side of the device) U

C

matches the voltage of the grid which the device is to be connected to!

Caution!

!

If the «operating current» function is programmed for all relays, a failure of control voltage or of the system may remain undetected. When using the device for control, it is the operator's responsibility to detect this error by regular controls. We recommend to program at least one relay in the system for standby current and to evaluate it accordingly.

Caution! Multi-voltage power supply

The device is equipped with a multi-voltage power supply suitable for DC and AC power supply. Before connecting the device to the mains, make sure that the permissible control voltage range according to the type plate (on the side of the device) U

C

matches the voltage of the grid which the device is to be connected to! datum / name ) : 13.05.2011 Sc

Page 5 of 20

Z. Nr.: 12200-0702-02

Type: WR250

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, e-mail: [email protected]

6. Installation

The device can be fastened:

Distributor installation or switching cabinet on 35 mm mounting rail according to EN

60715

Wall-mounting with M4 screws. (additional bar not included in delivery)

Connect in accordance with connection diagram or type plate.

Pay attention to the maximally permissible temperature when installing into a switching cabinet. Provide sufficient distance from other devices or heat sources. If cooling is hampered e. g. by close vicinity of devices with increased surface temperature or by obstruction of the cooling air flow, the permissible ambient temperature is reduced.

7. Detailed description

The WR250 displays and evaluates the temperatures transmitted from the wireless sensors WS Pt 100.

The hottest wireless sensor switches the relay.

For the relays K1 (alarm 1), K2 (alarm 2) and K3 (alarm 3), the following can be selected individually: o alarm value o hysteresis o response and reset delay o operation current or standby current o cyclic relay test (e. g. K1 for ventilator) o alarm in case of error 3 (no radio contact with WS Pt 100)

In case of an error at the WS Pt 100 wireless sensor, the relay will switch off the sensor alarm (K4), and the red LED is lit.

In addition, the MIN and MAX temperature values of each WS Pt 100 wireless sensor are stored.

The device can be polled remotely via a RS485 Modbus interface, and data can be queried.

Under difficult radio reception conditions or unfavorable mounting positions (e.g. shielded switchgear-cabinet) an external antenna can be connected.

For more informations concerning ranges and coverage see „APPLICATION NOTE AN001“ at www.enocean.de

. datum / name ) : 13.05.2011 Sc

Page 6 of 20

Z. Nr.: 12200-0702-02

Type: WR250

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, e-mail: [email protected]

8. Starting the wireless system

8.1 General notes on operation

The decimal point behind the last 7-element display shows the operating mode which the device is in.

8.2 Display mode

Decimal point off (normal state for temperature display)

Display current sensor temperature in °C (sensor LED lit)

LED yellow

K 1, K 2 and K 3

LED red sensor alarm

LED Sensor

WS Pt 100 function key

«Set/Reset»

Display the highest temperature measured by all attached sensors

(LEDs for all active sensors lit)

Display errors at the wireless sensor with error code (only when displaying individual sensors), e. g. 8 Err1 8 , 8 Err2 8 , …

Display alarm messages ( 8 Al1 8 , 8 al2 8 or 8 al3 8 )

AN («on») = relay engaged

AUS («off») = relay disengaged

AN («on») = relay disengaged

AUS («off») = relay engaged yellow = temperature of the selected wireless sensor is being displayed. If the LEDs for all registered sensors are lit, the hottest is being shown. red = error in selected wireless sensor

Press briefly: Display the next sensor (sensor LED lit) and display the highest temperature measured by all sensors (LEDs for all registered sensors lit)

Confirmation for 10 s: Display the software version function keys

«Up» and «Down»

Press briefly: Change to Menu mode

Confirmation for ≥2 s: Display MIN and MAX values measured by the selected sensor. Additional pressing of the «Set» key for ≥ 2s will erase the stored values.

8.3 Menu mode

Decimal point on

Select the menu items for changing parameters function keys

«Up» and «Down»

Press briefly: Select menu item; change to Display mode function keys

«Set/Reset»

Press briefly: Change to Parametrization mode

8.4 Parametrization mode

Decimal point flashing function key

«Up» and «Down»

Press briefly/for a longer time: Change parameter value

(slow/fast) function keys

«Set/Reset»

Press briefly: Accept setting and selection of the next parameter, after the last parameter change to Menu mode

Note: Press the «Set» key for 2 s to return to Display mode from Menu mode /

Parametrization mode. The same thing happens if no key has been pressed for 30 s

(Exception: 15 min in Simulation mode). datum / name ) : 13.05.2011 Sc

Page 7 of 20

Z. Nr.: 12200-0702-02

Type: WR250

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, e-mail: [email protected]

8.5 Operating flowchart

Display mode

normal state

Parametrization mode

Sensor LEDs at the type plate indicate the corresponding input ports.

«Up»/«Down» pressed simultaneously sets values to Zero.

Code reset = 2 s «Set» upon mains power on (Pin = 504)

Error messages:

Err1 = short circuit in sensor

Err2 = sensor interrupted

Err3 = no radio contact

Err4 = sensor illumination too low

Err5 = sensor energy too low

Err8 = internal error

Err9 = parameter error datum / name ) : 13.05.2011 Sc

Page 8 of 20

Z. Nr.: 12200-0702-02

Type: WR250

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, e-mail: [email protected]

8.6 Startup overview required optional

X

X

X

X

Overview

8.7 configuration (basic settings of the device)

8.8 registration of wireless sensors WS Pt 100

8.9 alarm parametrization

8.10 relay test

X

X

8.11

8.12 sensor simulation

RS485 Modbus interface

X 8.13 code lock

8.7 Configuration

The appropriate program must be selected in accordance with the settings of the wireless sensors (see operating instructions for WS Pt 100 wireless sensors). This is done once during commissioning.

switch of control voltage at the WR250

keep «Set» key pressed and switch on control voltage again

after 10 s, 8 Pr 5 8 is shown in the display

release «Set» key

select program in accordance with the wireless sensors, using the «Up»/«Down» keys

(program # see operating instructions for WS Pt 100 wireless sensor)

press «Set» key

device goes through reset and starts

8.8 Registration of wireless sensors

Start in Display mode (return to Display mode by pressing «Set» key for ≥ 2s). After 30 s without input, the device will also return to Display mode.

press «Down» key

display 8 S 1 .

8 / 8 off .

8 (sensor 1 / off) flashes alternatingly

press «Set» key

press «Down» key («Up» key turns off the sensor input port)

display 8 on .

8 (on)

press «Set» key

display 8 adr .

8 / 8 lrn .

8 (address / learn) flashes alternatingly

within 30 s, briefly (approx. 1 s) link contacts 3 and 4 of the sensor plug-in socket at the WS Pt 100 wireless sensor (small wire jumper, or if the sensor plug is plugged in, briefly link the two contacts 3 and 4)

registration OK: Display 8 lrnd.

8 (learned) will flash 4×

registration error: Display 8 Err .

8 (error) will flash 4×

display 8 S 2 .

8 / 8 off .

8 (sensor 2 / off) flashes alternatingly

register sensors 2 to 6 (optional)

after sensor 6, change to next menu item (parametrization of alarms) datum / name ) : 13.05.2011 Sc

Page 9 of 20

Z. Nr.: 12200-0702-02

Type: WR250

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, e-mail: [email protected]

8.9 Alarm parametrization

The following parameters are important: alarm value

8

8

8

AL 1.

AL 2.

AL 3.

8

8

8 limit values for the alarms. alarm 1 for relay K1, alarm 2 for relay K2 and alarm 3 for relay K3. hysteresis 8 H .

8 reset value calculated from alarm value + hysteresis e. g.: 90°C (limit value) + (-5)°C (hysteresis) = 85°C (reset value) alarm delay on alarm delay off

8 dal .

8 alarm will be suppressed for the selected time (seconds) relay

Sensor-

Error

8 dof .

8 alarm will be switched off only after falling below limit (alarm value + hysteresis) and elapse of this time (seconds)

8 rel .

8 standby current 8 r.

8 : In OK state (= alarm value not reached), the relay is engaged, it will be disengaged when reaching the alarm value.

Advantage: errors and failures generally result in alarm

Disadvantage: alarm also when control voltage is switched off. Unfavourable e. g. in transformers, in particular if WR250 control voltage is provided by the transformer to be controlled operating current 8 a.

8 : In OK state, the relay is disengaged, it will by engaged upon reaching the alarm value. No alarm in case of switched-off control voltage and failures.

8 SErr.

8 8 on .

8 alarm if there is no radio contact with the WS Pt 100 wireless sensor ( 8 Err3 8 ).

8 off .

8 no alarm in case of 8 Err3 8

Selection: use the «Up» and «Down» keys to select menu item until …

display 8 AL 1.

8 / 8 90.

8 (alarm 1 / limit value) flashes alternatingly

press «Set» key

display 8 90.

8 (current limit value, value may deviate)

use the «Up» and «Down» keys to select the desired limit value

press «Set» key

display 8 H .

8 / 8 -5.

8 (hysteresis / value) flashes alternatingly

use the «Up» and «Down» keys to select the desired hysteresis

press «Set» key

display 8 dal .

8 / 8 0.

8 (delay alarm / value) flashes alternatingly

use the «Up» and «Down» keys to select the desired value

press «Set» key

display 8 dof .

8 / 8 0.

8 (delay alarm off / value) flashes alternatingly

use the «Up» and «Down» keys to select the desired value

press «Set» key

display 8 rel .

8 / 8 r.

8 (relay / Parameter) flashes alternatingly

use the «Up» and «Down» keys to select the desired value

press «Set» key datum / name ) : 13.05.2011 Sc

Page 10 of 20

Z. Nr.: 12200-0702-02

Type: WR250

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, e-mail: [email protected]

display 8 SERR.

8 / 8 off .

8 (sensor error / value) flashes alternatingly

use the «Up» and «Down» keys to select the desired value

press «Set» key

display 8 AL 2.

8 / 8 100.

8 (alarm 2 / limit value) flashes alternatingly

parametrization of alarm 2 and alarm 3

after parametrization of alarm 3, change to next menu item (RS485 Modbus)

8.10 Short-circuit monitoring

To avoid sensor-alarms at sensor-temperatures <0°C, short-circuit-monitoring can be deactivated. With short-circuit-monitoring de-activated, the WR250 will display -1°C at temperatures <0°C.

Selection: use the «Up» and «Down» keys to select menu item until …

display 8 SESC.

8 / 8 on .

8 (short-circuit monitoring / on) flashes alternatingly

press «Set» key

use the «Up» and «Down» keys to select the desired value

display 8 on .

8 (on/with) / 8 off .

8 (off/without)

press «Set» key (change to next menu item)

8.11 Relay test

Here you can define that after a specified time 8 don 8 , e. g. 2 weeks (= 336 hours), a relay will go to alarm state for a time of 8 dof 8 , e. g. 10 s. This may be required to shortly start a ventilator of a pump to move them and prevent damage to the bearings by long downtimes.

The following parameters are important:

Relay test 8 tst .

8 relay test – Menu alarm #

8

8

8

AL 1.

AL 2.

AL 3.

8

8

8 relay test alarm 1 (relay K1) relay test alarm 2 (relay K2) relay test alarm 3 (relay K3) time of test 8 don .

8 shows after which time (in h) the relay test will be started or repeated, respectively duration of test 8 dof .

8 shows how long (in s) the relay test will run

How to adjust:

Select menu item with «Up»/«Down» keys until …

display shows 8 tst .

8

press «Set» key

display 8 AL .

8 / 8 E .

8 (alarm / exit) flashes alternatingly

Use the «Up» and «Down» keys to select the desired alarm #

8 AL 1.

8 , 8 AL 2.

8 , 8 AL 3.

8 , or press 8 E .

8 (Exit) to leave the menu item

press «Set» key

display 8 don .

8 / 8 off .

8 (time of test / value) flashes alternatingly

use the «Up» and «Down» keys to select the desired time for repetition of the relay test, 8 off .

8 – 8 1.

8 – 8 999.

8 h

press «Set» key datum / name ) : 13.05.2011 Sc

Page 11 of 20

Z. Nr.: 12200-0702-02

Type: WR250

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, e-mail: [email protected]

use the «Up» and «Down» keys to select the duration of the relay test,

8 1.

8 – 8 999.

8 s

press «Set» key

The elapsed test time 8 don 8 is stored persistently in the device.

8.12 RS485 Modbus interface

The following parameters are important:

Modbus 8 mbus.

8 Modbus menu

Address 8 Adr .

8 Address of device, selectable from range 1 to 247 baud rate 8 baud.

8 baud rate, 9600 or 19200 parity 8 pari.

8 parity : 8 even.

8 , 8 odd .

8 , 8 no .

8 (even, odd, none)

Selection: select menu item with «Up»/«Down» keys until …

display 8 Mbus.

8

press «Set» key

display 8 Adr .

8 / 8 1.

8 (address / value) flashes alternatingly

use the «Up» and «Down» keys to select the desired address

press «Set» key

display 8 baud.

8 / 8 9.6.

8 (baud rate / value) flashes alternatingly

use the «Up» and «Down» keys to select the desired baud rate

press «Set» key

display 8 pari.

8 / 8 even.

8 (parity / value) flashes alternatingly

use the «Up» and «Down» keys to select the desired value

press «Set» key

leave menu item RS485 Modbus

change to next menu item (Sensor Simulation)

Further informations relating to Modbus configuration and programming can be found in

Appendix 1 (available for download from www.ziehl.de

).

8.13 Sensor Simulation

Here you can simulate a temperature. All functions of the device will work as if this temperature were actually measured.

If no key has been pressed for 15 minutes, the device automatically returns to Display mode.

Select menu item with keys «Up»/«Down» until …

display 8 Si .

8

press «Set» key

use the «Up» and «Down» keys to select the desired temperature

press «Set» key

leave menu item Simulation

change to next menu item (Code lock) datum / name ) : 13.05.2011 Sc

Page 12 of 20

Z. Nr.: 12200-0702-02

Type: WR250

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, e-mail: [email protected]

8.14 Code lock

Here you can protect the entered parameters by activating code lock.

The device will reject faulty input with 8 Err 8 (flashes 3×).

Select menu item with keys «Up»/«Down» until …

display 8 Cod .

8 / 8 off .

8 (Code lock / off or on) flashes alternatingly

press «Set» key

display 8 Pin .

8 / 8 0.

8 (pin / pin code) flashes alternatingly

use the «Up» and «Down» keys to select the stored pin code (factory

default setting is 8 504.

8 )

press «Set» key

use the «Up» and «Down» keys to select the desired code lock: o 8 off .

8 off, any parameter may be modified o 8 EL .

8 EasyLimit, only alarm values may be modified o 8 on .

8 on, no parameter may be modified

press «Set» key

display 8 Pin .

8 / 8 504.

8 (pin / pin code) flashes alternatingly

use the «Up» and «Down» keys to enter the desired new pin code (Caution: write down pin code)

press «Set» key

Code lock on, display 8 on 8 flashes 3×

Code lock EasyLimit, display 8 EL 8 flashes 3×

Code lock off, display 8 off 8 flashes 3×

leave menu item Code lock and change to Display mode (normal state).

8.15 Notes on operation:

After completion of any program item, the program will continue with the next one.

If the right decimal point of the 7-segment display is lit, you have left the Display mode and may select the individual menu items by pressing «Up»/«Down» (Menu mode).

If the right decimal point flashes, you are in Parametrization mode and may change the settings by pressing «Up»/«Down».

Pressing «Up»/«Down» for longer periods of time accelerates changes in the display.

Pressing «Up»/«Down» simultaneously sets the selected values to zero.

 Reset (pressing «Set/Reset» for 2 s) will take you back to Display mode from any position in Parametrization mode or Menu mode (exception: Simulation), accepting the most recently entered value.

datum / name ) : 13.05.2011 Sc

Page 13 of 20

Z. Nr.: 12200-0702-02

Type: WR250

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, e-mail: [email protected]

8.16 Device reaction time – measuring time t

M

The reaction time of the device depends on the measuring and transmission times of the wireless sensors (see operating instructions WS Pt 100 wireless sensor).

The wireless sensors measure the temperature every 1 s, 10 s or 100 s and transmit it to the WR250 after every single, after every 10 th

or after every 100 th

measurement.

Consequently, there may be delays in sending and evaluating temperature changes.

Temperature changes > 4 °C will be sent immediately after measurement.

The delay times 8 dal .

8 and 8 dof .

8 may be increased by the duration of the transmission intervals (± 20%).

8.17 Possible values in the display

In Display mode (normal state)

8 al1 8 / 8 al2 8 / 8 al3 8 alarm 1, alarm 2, alarm 3 active (relay function dependent on programming for standby or operating current)

8 Err1 8 sensor short-circuited at the WS Pt 100 wireless sensor

8 Err2 8 sensor interruption at the WS Pt 100 wireless sensor

8 Err3 8 no radio contact with the WS Pt 100 wireless sensor

8 Err4 8 illumination of the WS Pt 100 wireless sensor too low

8 Err5 8 energy level of the WS Pt 100 wireless sensor too low

8 Err8 8 WR250 internal error

8 Err9 8 parameter error (illogic configuration of the WR250) sensors, Menu mode / Parametrization mode

8 S 1 8 … 8 S 2 8 sensors 1 to 6

8 on 8 / 8 off 8 sensors on / off

8 Adr 8 / 8 Lrn 8

8 Lrnd 8 flashes alternatingly, ready for registration of a new sensor new sensor registered successfully (learned) alarm values, Menu mode / Parametrization mode

8 al 1 8 / 8 al 2 8 / 8 al 3 8

8 H 8 alarm values hysteresis

8 dal 8 delay until alarm

8 dof 8 delay until alarm reset

8 rel 8

8 r 8 / 8 a 8 relay function relay function

– standby current, operating current

Short-circuit monitoring, Menu mode / Parametrization mode

8 SESC 8 Short-circuit monitoring

8 off 8 / 8 on 8 off (without) / on (with) Short-circuit monitoring datum / name ) : 13.05.2011 Sc

Page 14 of 20

Z. Nr.: 12200-0702-02

Type: WR250

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, e-mail: [email protected]

relay test, Menu mode / Parametrization mode

8 tst 8 relay test

8 AL 8 / 8 E 8 alarm / exit

8 al 1 8 / 8 al 2 8 / 8 al 3 8 relay test on alarm 1 (K1) / alarm 2 (K2) / alarm 3 (K3)

8 don 8 shows after which time (in h) the relay test will be started or repeated, respectively

8 dof 8 shows how long (in s) the relay test has been running

8 Mbus 8

8

8

8

8

8

RS485 interface Modbus, Menu mode / Parametrization mode adr baud

9.6

pari even

8

8

8

8

8

/

/

8

8

19.2

odd 8

8

/ 8 no 8

Modbus (RS485 interface)

Modbus – device address

Modbus – baud rate

Modbus

– baud rate, 9600 or 19200

Modbus – parity

Modbus – parity bit – even / odd / none

Simulation, Menu mode / Parametrization mode

8 Si 8 Simulation

Code lock, Menu mode / Parametrization mode

8 Cod 8 Code lock

8 Pin 8 pin code

8 on 8 / 8 el 8 / 8 off 8 Code lock on / EasyLimit / off datum / name ) : 13.05.2011 Sc

Page 15 of 20

Z. Nr.: 12200-0702-02

Type: WR250

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, e-mail: [email protected]

9. Factory default settings

When switching the program (operating instructions item «Configuration»), all parameters are reset to their factory default settings.

Menu mode

8 S 1 8

Parameter

Factory default settings

8 off 8

My data

8 S 2 8 8 off 8 sensor

1 .. 6

8 S 3 8

8 S 4 8

8 S 5 8

8 off 8

8 off 8

8 off 8

8 S 6 8 8 off 8 alarm 1 relay K1

8 AL 1 8

8 H 8

8 dal 8

8 dof 8

8 rel 8 limit hysteresis delay delay

– alarm

– alarm off relay function

8 90 8 °C

8 -10 8 °C

8 0 8 s

8 999 8

8 a 8 s alarm 2 relay K2

8

8

8

8

8

8

8

8

SErr

AL 2

H dal dof rel

SErr

AL 3

8

8

8

8

8

8

8

8 alarm sensor error 3 limit hysteresis delay delay

– alarm

– alarm off relay function alarm sensor error3 limit alarm 3 relay K3

8 H 8

8 dal 8

8 dof 8

8 rel 8 hysteresis delay delay

– alarm

– alarm off relay function

8 SErr 8

SESC 8 SESC 8 relay test tst

Modbus

Cod alarm sensor error3

Short-circuit monitoring

8 off 8

8 on 8

8

8

8

8

8

8

8

AL 1

AL 2

AL 3 adr baud

Pari on

8

8

8

8

8

8

8 /

8 Pin 8

8

8 don 8 Time of test

8 dof 8 duration of test 8 1 8

8 don 8 Time of test 8 off 8

8 dof 8 duration of test 8 1 8

8 don 8 Time of test 8 off 8

8 dof 8 duration of test 8 1 8

8 1 8

8 9.6

8

8 even 8 el 8 / 8 off 8

8

8 off 8

8 off

504

8

8

8 on 8

8 130 8 °C

8 -5 8 °C

8 0 8 s

8 0 8

8 r 8 s

8 off 8

8 150 8 °C

8 -5 8 °C

8 0 8 s

8 0 8

8 a 8 s datum / name ) : 13.05.2011 Sc

Page 16 of 20

Z. Nr.: 12200-0702-02

Type: WR250

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, e-mail: [email protected]

10. Servicing and maintenance

ZIEHL industrie-elektronik GmbH + Co KG

Daimlerstr.13

D-74523 Schwäbisch Hall

Germany

Phone: +49 791 504-0

Fax: +49 791 504-56

Email: [email protected]

Homepage: http://www.ziehl.de

11. Troubleshooting

8 Err1 8 or 8 Err2 8 shown in the display cause remedy sensor short-circuited or sensor interrupted at the WS Pt 100 wireless sensor please check temperature sensor at the WS Pt 100 wireless sensor for being electrically in order and correctly connected.

(see operating instructions: WS Pt 100 wireless sensor)

8 Err3 8 shown in the display cause remedy no radio contact with the WS Pt 100 wireless sensor

distance from WS Pt 100 wireless sensor too great

storage capacitor in the WS Pt 100 wireless sensor exhaustively discharged

reduce distance between devices

charge storage capacitor, illuminate WS Pt 100 wireless sensor with > 1000 lux for approx. 2 – 3 hours

8 Err4 8 shown in the display cause illumination of the WS Pt 100 wireless sensor too low or failed remedy provide illumination or increase light intensity, respectively

8 Err5 8 shown in the display cause energy level of the WS Pt 100 wireless sensor too low remedy charge storage capacitor, illuminate WS Pt 100 wireless sensor with > 1000 lux for approx. 2

– 3 hours

8 Err8 8 shown in the display cause WR250 internal error remedy send the device in for examination

8 Err9 8 shown in the display cause remedy

Parameter error (implausible configuration of WR250) check alarm parametrization datum / name ) : 13.05.2011 Sc

Page 17 of 20

Z. Nr.: 12200-0702-02

Type: WR250

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, e-mail: [email protected]

Device refuses programming cause Code lock remedy

The code lock provides protection from unauthorized manipulations of the device. When code lock is activated, parameters cannot be changed. The pin can be selected by the user. pin code unknown? → perform code reset:

 Upon activation of the control voltage, keep «Set» key pressed for 2 s

display changes to 8 8888 8 – 8 Cod 8 – 8 off 8 – 8 8888 8

release «Set» key

code lock is deactivated, pin code is «504»

No registration of a WS Pt 100 wireless sensor with the WR250 possible cause

 distance between wireless sensor and WR250 too great

 wireless sensor power too low for work

 wrong registration contacts linked at the wireless sensor or static linkage of remedy the contact

 reduce distance between the devices

 charge storage capacitor, illuminate WS Pt 100 wireless sensor with > 1000 lux for approx. 2 – 3 hours

 link registration contacts at the wireless sensor only briefly (see operating instructions: WS Pt 100 wireless sensor)

11.1 Displaying the software version

In Display mode, press the «Set» key for 10 s

12. Technical data

control voltage U

C limit values measurement range tolerance input for external antenna frequency range antennas: for metal surfaces (e.g.) for other surfaces (e.g.) extension-cable for antenna length

AC/DC 24 – 240 V 0/50/60 Hz <3 W < 6 VA

DC 20.4

– 297 V

AC 20

– 264 V

0 … 180°C

± 4 K

FME plug

868 MHz

MAR-C3G-2F (ZIEHL, Order-no. 101100)

Hirschmann MCA 1890 MH

Hirschmann MCA 1890 MP

Hirschmann MCA 1890 MP

HAMA MiniPlanar 38499

RG58 - FME bushing / plug max. 15m datum / name ) : 13.05.2011 Sc

Page 18 of 20

Z. Nr.: 12200-0702-02

Type: WR250

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, e-mail: [email protected]

relay output port switching voltage switching current switching capacity

Nominal operation current I

E

:

AC15

DC13

Recommended backup fuse service life of contacts mech. service life of contacts electr.

Test conditions

4 × 1 changeover contact max. AC 415 V max. 5 A max. 1250 VA (ohmic load) max. 120 W at DC 24 V

Ie = 3 A

Ie = 2 A

Ie = 0,2 A

Ie = 0,1 A

Ue = AC 250 V

Ue = DC 24 V

Ue = DC 125 V

Ue = DC 250 V

T 3.15 A (gL)

3 x 10

7

switching cycles

1 x 10

5

switching cycles at AC 250 V / 6 A rated impulse withstand voltage degree of soiling rated insulation voltage U

Casing installation depth

I

Uptime permissible ambient temperature

EMC – stability

EMC – interference emissions vibration resistance EN 60068-2-6

EN 50178 / EN 60 947

4000 V

3

300 V

100 %

20 °C … +60 °C

EN 60068-2-2 dry heat

EN 61000-6-2

EN 61000-6-3

2 … 25 Hz ±1,6 mm

25 … 150 Hz 5 g

V4 design, distributor installation

55 mm

4 TE

70 × 90 × 58 mm

1 × 1.5 mm² each width dimensions (B × H × T) line connector, single wire finely stranded with wire end ferrule 1 × 1.0 mm² each

Protection class, casing IP 30

Protection class, clamps fastening weight

IP 20 snap mounting on bearing rail 35 mm according to EN 60 715 or screw fastening M 4 (additional bar not included in delivery) approx. 190 g

Subject to technical modifications datum / name ) : 13.05.2011 Sc

Page 19 of 20

Z. Nr.: 12200-0702-02

Type: WR250

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, e-mail: [email protected]

13. Design V4

Dimensions in mm

58

48

16,5

70

Option

4

5

7

2

6

1 3

4

5

6

7

1

2

3

Oberteil / cover

Unterteil / base

Riegel / bar for snap mounting

Plombenlasche / latch for sealing

Frontplatteneinsatz / front panel

Kennzeichen für unten / position downward

Riegel bei Wandbefestigung mit Schrauben. Riegelbohrung Ø 4,2 mm / for fixing to wall with screws, Ø 4,2 mm

Sie finden diese und weitere Betriebsanleitungen, soweit verfügbar auch in englisch, auf unserer Homepage www.ziehl.de

.

You find this and other operating-manuals on our homepage www.ziehl.de

, as far as available also in English. datum / name ) : 13.05.2011 Sc

Page 20 of 20

Z. Nr.: 12200-0702-02

Type: WR250