- No category
advertisement
Te c h n i k , d i e d e m M e n s c h e n d i e n t .
Installation and operating instructions
Programming module BM
Wolf GmbH · Postfach 1380 · D-84048 Mainburg · Tel. +49-8751/74-0 · Fax +49-8751/741600 · Internet: www.wolf-heiztaechnik.de
30 61 872_0407 Subject to modifications 6 6701 623
2
Index
Safety instructions ............................................................... 3
Standards / Regulations ...................................................... 4
Installation
• Installation / Wall mounting base installation ............... 5
• Electrical connection, remote control ......................... 6
• Remote switching contact ........................................... 6
• Outside temperature sensor ....................................... 7
• Boiler integration .......................................................... 8
• Integration into a gas fired boiler ................................ 9
• Module installation ...................................................... 10
eBUS interface settings .................................................... 11
Overview .............................................................................. 12
Control level 1
• Description l.h. / r.h. rotary selector ......................... 12
• Symbol description ............................................... 12-13
• Function: Flue gas test / temperature selection ....... 14
• Info pushbutton .......................................................... 15
• Single cylinder heating pushbutton ........................... 16
• Heating pushbutton .................................................... 16
• Setback pushbutton ................................................... 16
• Display ................................................................... 17-18
Control level 2
• Control level 2 – Summary ......................................... 19
• Standard settings ...................................................... 20
Parameters overview, standard settings .......... 20
Time ...................................................................... 20
Day ....................................................................... 21
Time program ....................................................... 21
Day temperature .................................................. 22
Setback temperature ........................................... 23
Heating curve .................................................. 24-25
Room influence .................................................... 26
S/W changeover, subject to outside temp. .... 27-28
ECO/RED ......................................................... 29-30
DHW temperature ................................................ 31
Language ............................................................. 31
Pushbutton lock ................................................... 32
• Time program (setting switching times, example) .. 33-34
• Contractor
Code scan ............................................................ 35
Overview, Contractor menu ............................... 36
• Summary – system parameters ................................ 37
Room influence (A00) ......................................... 38
Heat-up optimisation (A01) ................................. 39
Maximum heat-up time (A02) ......................... 39-40
30 61 872_0407
Index / Safety instructions
Required heat-up time (A03) .............................. 40
Adjusted outside temperature (A04) ................. 41
Room temperature sensor matching (A05) ....... 41
External sensor (A06) ......................................... 42
Pasteurisation function (A07) ............................. 43
Maintenance message (A08) ............................. 44
Frost protection limit (A09) ................................. 44
Parallel DHW operation (A10) ............................. 45
Room temp. summer/winter changeover (A11) ... 46
Setback stop (A12) ............................................. 47
Minimum DHW temperature (A13) ...................... 48
• Summary – changing boiler parameters .............. 49-50
• Summary – changing mixer parameters ................... 51
• Summary – changing solar parameters ................... 52
• Summary – changing other parameters ................... 53
Screed drying, direct heating circuit ............. 54-55
Reset ......................................................................... 55
Operating mode status boiler HG ................................... 56
Settings report
• Standard settings parameters ............................. 56-57
• Time programs ....................................................... 58-59
• System parameters ................................................... 60
Safety instructions
NB
NTC sensor resistances ................................................... 61
Fault messages .............................................................. 62-63
Specification ......................................................................... 64
The following symbols are used in conjunction with these important instructions concerning personal safety as well as operational reliability.
"Safety instructions" are instructions with which you must comply exactly, to prevent injury and material losses.
Danger through 'live' electrical components.
NB Switch OFF the ON / OFF switch before removing the casing.
Never touch electrical components or contacts when the
ON / OFF switch is in the ON position. This brings a risk of electrocution, which may result in injury or death.
The main supply terminals are 'live' even when the ON / OFF switch is in the OFF position.
This indicates technical instructions which you must observe to prevent material losses and boiler malfunctions.
30 61 872_0407 3
Standards / Regulations
Installation / Commissioning
- According to DIN EN 50110-1, only qualified electricians may carry out the installation and commissioning of the heating control unit and connected accessories.
- Observe all regulations stipulated by your local power supply utility and all VDE or local regulations.
- DIN VDE 0100 regulations regarding the installation of high voltage systems up to 1000V
- DIN VDE 0105-100 operation of electrical systems
- DIN EN 50165 electrical equipment for non-electrical devices for domestic use and similar purposes
- EN 60335-1 safety equipment of electrical devices for domestic use and similar purposes.
Warnings
- Never remove, bypass or disable safety and monitoring equipment.
- Only operate the system in perfect technical condition.
Immediately remove / remedy any faults and damage that may impact on safety.
- Always ensure that cold water is mixed in with hot water, when the DHW temperature is set above 60 °C or when operating the pasteurisation system at a temperature higher than 60 °C (risk of scalding).
Maintenance / Repair
NB
- Regularly check the perfect function of all electrical equipment.
- Only qualified personnel may remove faults or repair damage.
- Only replace faulty components or equipment with original
Wolf spare parts.
- Always maintain prescribed electrical protection values (see specification).
Any damage or loss resulting from technical modifications to
Wolf control units is excluded from our liability.
4 30 61 872_0407
Remote control
Installation
The BM programming module can be used as remote control (e.g.
in the living room). Using a remote control makes both the walk to the boiler / installation room superfluous and provides additional functions (e.g. room temperature hook-up).
If there are several heating circuits with controllers from the Wolf control unit range, a single BM programming module can operate and adjust all heating circuits.
However, an individual BM programming module can also be allocated as remote control to each heating circuit.
Only a two-wire BUS is required for the use as remote control.
Installation information
- Install the wall mounting base (available as option) on an internal wall at a height of approx. 1.5 m above the floor.
- For an optimum room temperature sensor function, install the
BM programming module in a living room (reference room) that is representative of the entire accommodation or the entire house.
- The BM programming module must not be subject to draughts or direct radiated heat.
- The BM programming module must not be obstructed by furniture or curtains.
- In the reference room, all radiator valves must be fully opened.
Wall mounting base installation
- Remove the wall mounting base from its packing.
- Secure the wall mounting base on a flush-mounting box
(Ø 55 mm) or directly on the wall.
Fixing holes
Fixing holes
Wall mounting base
30 61 872_0407 5
Electrical connection
Remote control
Installation
The electrical connection must only be carried out by a qualified electrician.
Never route sensor leads alongside mains power cables.
- Switch OFF the ON / OFF switch at the boiler.
- Set the rotary temperature selector for central heating and the
DHW selector into their central positions (5).
- Wire the wall mounting base with a two-core cable (minimum cross-section 0.5 mm²) in accordance with the diagram.
Note
Remote switching contact
6
Green plug of the control unit
eBUS
Terminal strip
Wall mounting base
- Connect the optional outside temperature sensor to the wall mounting base.
- Connect the remote switching contact to the wall mounting base.
- Check the eBUS address (see chapter "eBUS interface settings").
- Click the BM programming module into the wall mounting base as shown in the diagram.
- Switch ON the ON / OFF switch at the boiler.
All accessories are connected in parallel to the control unit eBUS when connecting several remote control units or a radio clock module.
A remote switching contact offers the possibility of switching the heating system to enable 24 h central heating and DHW, using a zero-volt contact (e.g. a telecontrol contact). The control unit operates with the set time programs if the remote switching contact remains open.
- Switch OFF the ON / OFF switch at the boiler.
- Wire the remote switching contact with a 2-core cable (minimum cross-section 0.5 mm²) in accordance with the diagram.
Remote switching contact (on site) e.g. telecontrol contact
Green plug of the control unit
eBUS
Terminal strip
Wall mounting base
- Click the BM programming module into the wall mounting base as shown in the diagram.
- Switch ON the ON / OFF switch at the boiler.
30 61 872_0407
Installation
Outside temperature s e n s o r
Installation at the boiler
Outside temperature sensor
ϑ
2
OS at the boiler
Radio clock module with outside temperature sensor
ϑ
The outside temperature sensor can either be connected directly to the boiler (preferred option) or at the BM programming module.
Join the on-site lead of the outside temperature sensor with the plug supplied in the boiler control unit. Insert the plug into the designated location in the plug-in connector strip of the boiler control unit, and secure the lead with its strain relief. Route the lead through the boiler casing cutout. Fit the outside temperature sensor to the north or northeast wall, 2 to 2.5 m above ground level (cable entry pointing down).
A wireless outside temperature sensor can also be used if there is no cable or conduit available on site for the outside temperature sensor.
A wireless outside temperature sensor or a radio clock module with outside temperature sensor is available as optional accessory.
2
1
2 eBUS
External wireless sensor
ϑ
2
1
2 eBUS
Installation at the programming module
- Switch OFF the system ON / OFF switch at the boiler control unit.
- Wire the outside temperature sensor with a 2-core lead (minimum cross-section 0.5 mm²) in accordance with the diagram.
ϑ
Outside temp. sensor
Green plug of the control unit
eBUS
Terminal strip
Wall mounting base
- Click the BM programming module into the wall mounting base as shown in the diagram.
- Switch ON the ON / OFF switch at the boiler.
7 30 61 872_0407
Boiler integration
Installation
The BM programming module can also be integrated into the boiler control unit. That means that all settings are made at the boiler control unit.
In addition, all heating circuits can be controlled and adjusted from the boiler control unit, if there are several heating circuits that are operated with components from the Wolf range of control equipment.
The electrical connection must only be carried out by a qualified electrician.
- Switch OFF the ON / OFF switch at the boiler.
- Set the rotary temperature selector for central heating and the
DHW selector into their central positions (5).
- Check the eBUS address (see chapter "eBUS interface settings").
- Remove the facia or the BM programming module from the boiler control unit as shown in the diagram.
- Click the BM programming module or facia into the boiler control unit as shown in the diagram.
- Switch ON the ON / OFF switch at the boiler.
8 30 61 872_0407
Integration into a gas fired boiler
Installation
The BM programming module can also be integrated into the control unit of gas fired boilers. That means that all settings are made at the control unit of the gas fired boiler.
In addition, all heating circuits can be controlled and adjusted from the control unit of the gas fired boiler, if there are several heating circuits that are operated with components from the Wolf range of control equipment.
The electrical connection must only be carried out by a qualified electrician.
- Switch OFF the ON / OFF switch at the boiler.
- Set the rotary temperature selector for central heating and the
DHW selector into their central positions (5). Check the eBUS address (see chapter "eBUS interface settings").
- Remove the facia from the control unit of the gas fired boiler as shown in the diagram.
- Click the BM programming module into the control unit of the gas fired boiler as shown in the diagram.
- Switch ON the ON / OFF switch at the boiler.
30 61 872_0407 9
Module installation
Installation
The BM programming module can also be integrated into modules
(e.g. mixer module MM, solar module SM). That means that all settings are made at the relevant module.
The electrical connection must only be carried out by a qualified electrician.
- Switch OFF the ON / OFF switch (or system ON / OFF switch) at the module.
- Remove the facia from the module as shown in the diagram.
- Check the eBUS address of the BM programming module and the module (see chapter "eBUS interface settings").
- Click the BM programming module into the module as shown in the diagram.
- Switch ON the ON / OFF switch (or system ON / OFF switch) at the module.
10 30 61 872_0407
Setting eBUS interface
Adresse 0
ON DIP
ON
1 2 3 4
Dip 1-4
OFF
eBUS interface settings
The BM programming module is factory-set so that all connected components of the heating system are controlled from the programming module. You can ignore the following chapter, if only one BM programming module is to be installed as part of the heating system.
In addition, the programming module can be used to provide the complete control of an extension module (see the illustration below as example).
For this, set the DIP switch at the back of the programming module into the correct position (see illustration).
Note:
One BM with address 0 must always be part of the system.
Up to seven extension modules can be connected.
A correct BUS address and consequently the communication of all users with each other is indicated in the display of the connected BM programming module after approx. one minute by symbol (see diagram) or by an LED in the expansion modules.
eBUS connection enabled
30 61 872_0407 1 1
Overview
L.h. rotary selector
Program selection
Status display Display
R.h. rotary selector
Temp. selection
Info pushbutton
Single cylinder heating pushbutton
Program selection
12
Function display
Setback pushbutton
Heating pushbutton
Left-hand rotary selector, program selection
This rotary selector enables programs to be selected. The rotary selector can be moved without end stop, providing a clearly recognisable indexing function. The selected function is indicated by an arrow in the display.
Right-hand rotary selector temperature selection
This rotary selector enables the temperature to be selected. The rotary selector can be moved without end stop, providing a clearly recognisable indexing function. The selected function is indicated by one or two arrow(s) in the display.
In addition, the r.h. rotary selector enables all programming to be accomplished. Pressing the r.h. rotary selector confirms the programming step.
You can select the following programs by turning the l.h. rotary selector. The arrow on the l.h. edge of the display points to the selected program.
Automatic mode
Heating (day mode / setback mode) and cylinder heating in accordance with the switching times program (1, 2 or 3), heating circuit pumps, mixer circuit pumps, cylinder primary pumps and
DHW circulation pumps are started and stopped within the enabled time according to demand (mixer circuit pump only in heating systems with a mixer circuit).
30 61 872_0407
30 61 872_0407
Control level 1
Summer mode (heating OFF)
Summer mode (heating OFF) means only cylinder heating in accordance with the switching times program. Frost protection for the central heating system and anti-seizing pump protection are enabled.
Constant DHW and central heating operation
The switching times program (1, 2 or 3) for heating and cylinder heating are disabled. With this setting, the day mode for central heating and cylinder heating are enabled for 24 hours. The heating circuit pump, mixer circuit pump and cylinder primary pump are started and stopped according to demand. The DHW circulation pump is started and stopped in accordance with the switching times program (mixer circuit pump only for heating systems with mixer circuit). No summer/winter changeover.
Constant setback mode
The switching times program (1, 2 or 3) for heating is disabled. With this setting, the heating operates in setback mode for 20 hours. The heating circuit and mixer circuit pumps are started and stopped according to demand.
The cylinder primary pump and the DHW circulation pumps are started and stopped in accordance with the switching times program (1, 2 or 3) (mixer circuit pump only for heating systems with mixer circuit).
Summer/winter changeover and ECO/RED are enabled.
Standby mode
Burner and circulation pumps are OFF, cylinder heating and pasteurisation are OFF, frost protection and anti-seizing pump protection are enabled.
Frost protection:
At outside temperatures below the set value (factory setting +2 °C), the boiler and mixer circuit pumps (mixer circuit pump only in heating systems with mixer circuit) run permanently, the mixers open.
Anti-seizing pump protection:
After no more than 24 hours idle, the pumps will run for approx. 20 seconds. This prevents the pumps from seizing up.
Flue gas test
The flue gas test is required by your flue gas inspector or a specialist contractor for measuring the emissions.
- This selection is not available if the BM programming module is installed as remote control (e.g. in a living room). In that case, the emissions test mode is activated at the boiler control unit via the heating water temperature selector and is indicated by the signal ring flashing in yellow.
- If the BM programming module is integrated into the boiler control unit, activating the emissions test mode is then indicated by an arrow in the display (next to the chimney sweep symbol) as well as by the signal ring flashing in yellow.
For the flue gas test function, see the next page.
1 3
Control level 1
Function: Flue gas test
Freestanding boilers:
The heating system will not operate in weather-compensated mode, when the emission test is running. Instead it operates at maximum output and tries to hold a mean constant boiler water temperature of 60 °C. Only the burner will operate, i.e.
the pump is OFF, if the boiler water temperature is lower than
60 °C. The boiler circuit pump will be started when the boiler water temperature exceeds 60 °C. The DHW cylinder primary pump only runs until the set DHW temperature has been reached. The burner is switched OFF when the max. boiler water temperature has been reached, if the heating energy supplied cannot be transferred.
Wall mounted boilers:
In emissions test mode, the heating system will not operate in weather-compensated mode, but with maximum output. Any previous cycle block will be cancelled. The heating circuit pump runs permanently.
The emissions test mode terminates either after 15 minutes or automatically, if the maximum flow temperature has been exceeded. For a repeat activation, turn the heating water temperature selector or the l.h. rotary selector (program selector) first anti-clockwise and then back into position .
14
Temperature selection
By turning the r.h. rotary selector, the required room temperature can be raised or lowered by a maximum of 4 K by turning the selector respectively anti-clockwise or clockwise. Subject to the direction of rotation, the arrow on the r.h. side of the display drifts either up or down.
Example:
+1: The set room temperature is raised by approx. 1 K.
- 1: The set room temperature is reduced by approx. 1 K.
If two arrows are displayed one above the other, the selected value will be between both.
Example:
Arrow 1 +1, arrow 2 +2: The set room temperature is raised by approx. 1.5 K.
0 corresponds to the selected room temperature (factory setting: day mode 20 °C, setback mode 12 °C).
The current room temperature will not be captured, if the BM programming module is integrated into the boiler control unit or if it is operated as remote control with room influence switched
OFF. The selected room temperatures are simply reference and calculating values for the heating curve; therefore the actual room temperature can deviate from these values.
30 61 872_0407
Example:
dhw TEMP
30 61 872_0407
Control level 1
Info pushbutton
All available set and actual temperatures, burner starts and hours run as well as other system values can be displayed with the Info pushbutton.
Pressing the Info pushbutton several times displays the following values in sequence, subject to the relevant sensor being connected. Any circuits that are not connected are skipped, as only available values can be displayed.
The relevant parameters are displayed if additional programming modules BM are integrated into the Wolf control system or are installed as remote control units.
*
*
*
*
*
*
*
*
*
*
*
*
*
Display
DHW TEMP
Solar dhw 1 dhw SOL 24H
Collector 1
Collect 24H
Return
Flow rate opERATION H
Sol. output
OUTPUT 24 H
OUTPUT K
MIX VALVE 1
(mixer 2-7)
WH
OUTPUT MWH
SOL STATUS
OUT TEMP
ES AVERAGE
ES MAX MIN
ROOM TEMP
MODE HC
BOILER TEMP
RETURN
STATUS HG
BURN RUN H
BURN START
Name
Actual DHW cylinder temp., heating (°C)
Set DHW temp., heating (°C)
Actual DHW temp., solar heating system (°C)
Max. temp., solar cylinder sensor (°C)
Min. temp., solar cylinder sensor (°C)
Collector temp., solar heating system (°C)
Max. temp., collector, solar heating system (°C)
Min. collector temp., solar heating system (°C)
Return temp., solar heating system (°C)
Throughput of the solar circuit (l / min)
Hours run, solar circuit pump (h) **
Current output, solar heating system (kW)
Current yield, day, solar heating system (kWh) **
Total yield, solar heating system (kWh) **
Total yield, solar heating system (MWh) **
DHW heating, solar heating system
Pasteurisation
(0 = not successful / 1 = successful)
Outside temperature (°C)
Average outside temp. (°C)
Max. outside temp. (°C, 0 to 24 h)
Min. outside temp. (°C, 0 to 24 h)
Actual room temp. (°C)
Set room temp. (°C)
Operating mode, heating circ. (sun, moon, standby)
Actual boiler water temp. (°C)
Set boiler water temp. (°C)
Actual mixer temp. (°C)
Set mixer temp. (°C)
Mixer circuit operating mode (sun, moon, standby)
Actual return temp. (°C)
Boiler status
Burner hours run
Boiler burner starts
* No values are displayed for modules that are not connected
(mixer module MM, solar module SM).
** This value can be reset to 0 by holding down the rotary selector for at least 10 seconds.
1 5
16
Control level 1
Single cylinder heating pushbutton
Pressing the single cylinder heating pushbutton enables an unscheduled single cylinder heating, if DHW is required outside the selected DHW switching times. To signal this event, the tap symbol flashes in the display during the unscheduled cylinder heating. The single cylinder heating terminates automatically after one hour, and the control unit continues to operate in accordance with the current switching times program.
Pressing the single cylinder heating pushbutton again terminates this function early.
Heating pushbutton
To avoid the need for changing the switching times program during bank holidays, parties or illness, the day temperature can be selected by pressing the Heating pushbutton, independent of the Switching times program or the program selection.
After pressing the Heating pushbutton, heating mode will be displayed automatically for three hours. Pressing the r.h. rotary selector enables the selection of the required time in hours or days (up to 30 days).
Pressing the r.h. rotary selector enables the Heating function.
To signal this event, the sun symbol flashes in the display during the unscheduled heating operation.
This function is stopped automatically after the set time has expired (hours or days).
Pressing the Heating pushbutton again terminates this function early.
Setback pushbutton
To avoid the need for changing the switching times program during absence or holidays, the setback temperature can be selected by pressing the Setback pushbutton, independent of the Switching times program or the program selection.
After pressing the Setback pushbutton, setback mode will be displayed automatically for three hours. Pressing the r.h. rotary selector enables the selection of the required time in hours or days (up to 30 days).
Pressing the r.h. rotary selector enables the Setback function.
To signal this event, the moon symbol or Standby (ECO/RED function) flashes in the display during the unscheduled setback.
This function is stopped automatically after the set time has expired (hours or days).
Pressing the Setback pushbutton again terminates this function early.
30 61 872_0407
Display
Room temperature, boiler water temperature, mixer circuit temperature or DHW temperature, solar heating system
The room temperature is shown on the display if the BM programming module is installed as remote control (e.g. in a living room). The boiler water temperature will be displayed if the module is integrated into the boiler; the mixer circuit temperature will be displayed, if the unit is integrated into the mixer module, and the DHW temperature of the solar heating system is displayed if the module is fitted into the solar module.
Time and outside temperature
Time and outside temperature are displayed alternately (subject to an outside temperature sensor being installed).
30 61 872_0407
Day
The display shows the day of the week that is currently selected.
1 = Monday
2 = Tuesday
...
7 = Sunday
Status display
the following five symbols indicate the current operating state of your heating system.
Heating mode
Setback mode
Heating OFF, frost protection enabled
DHW heating enabled
Flue gas test active
Symbols flashing
The Heating pushbutton has been pressed
(see Heating pushbutton)
The Setback pushbutton has been pressed
(see Setback pushbutton)
Pushbutton 1 x WW has been pressed
(see Single cylinder heating pushbutton)
1 7
18
DISPLAY
Display
Function displays:
Boiler in heating mode
Boiler in DHW mode
Boiler pump ON
Burner ON
Mixer circuit pump mixer 1 ON
Mixer circuit pump mixer 2 ON
Programmable output ON
BUS connection enabled
Solar circuit pump enabled
Right hand arrow
selected temperature
Left hand arrow
selected heating program
Submenu available
30 61 872_0407
Overview
Display
BASIC SET
Time prog
EXPERT
RETURN
Control level 2 – Summary
Pressing the r.h. rotary selector leads to control level 2, where you can select the menu levels shown in the summary by turning the rotary selector clockwise.
Pressing the Info pushbutton enables the recall of the standard display, irrespective of which submenu is currently active.The
system also returns to the standard display automatically when no adjustment is made for more than a minute.
All available set and actual temperatures, burner starts and hours run as well as other system values can be displayed. This scan is identical to that initiated via the Info pushbutton.
Setting the most important parameters of the heating control unit, such as time, day, active time program, day temperature, setback temperature, heating curve, room influence, automatic summer/winter changeover, ECO/RED selection, DHW temperature, language and key lock.
Optional adjustments and explanations to the individual parameters in the chapter on standard settings.
Changing the switching times programs for heating, cylinder heating, DHW circulation and mixer circuit pumps (mixer circuit pump only for heating systems with mixer circuit). Optional adjustments and modification of the individual switching times programs in the chapter on time programs.
Setting the Contractor parameters of the heating system and the boilers.
Optional adjustments and explanations to the individual parameters in the chapter, "Contractors".
Return to the standard display.
30 61 872_0407 1 9
20
Control level 2 – Standard settings
Parameter overview, standard settings
(Settings and functions on the following pages)
Parameter
Time
Day
Time program
Day temp.
Setback temp.
Heating curve Boiler circuit
Mixer circuit
Room influence ON / OFF
Summer/winter changeover
ECO/RED -10 to 40 °C
DHW temp.
Freestanding boiler
Wall mounted boiler with cylinder
Wall mounted combi boiler
Language
Pushbutton lock
Setting range Factory setting
0 to 24 h
1 (Mon) to 7 (Sun)
1 / 2 / 3
5 to 30 °C
-
-
1
20 °C
5 to 30 °C
0 to 3.0
0 to 3.0
OFF
0 to 40 °C
10 °C
15 to 60 °C
16 °C
1.2
0.8
20 °C
55 °C
55 °C
55 °C
German
15 to 65 °C
40 to 65 °C
German, English,
French, Dutch,
Spanish,
Portuguese,
Italian, Czech,
Polish, Slovakian,
Hungarian,
Russian,
Greek, Turkish
ON / OFF OFF
T i m e
Time
08:30
Setting range: 0 to 24 h
Press the r.h. rotary selector to change to control level 2. Turn the r.h. rotary selector clockwise to select the Standard settings submenu and confirm the selection by pressing the r.h. rotary selector again.
The time is changed by pressing (display indication flashes) and then turning the r.h. rotary selector.
Turning slowly
Turning quickly
= Changing the minutes
= Changing the hour
After setting or changing the current time, pressing the r.h.
rotary selector again confirms the input.
Pressing the Info pushbutton returns the standard display.
There will be no automatic change between summer and winter time. Reset the time if the control unit has been disconnected from the power supply longer than 48 hours.
The time will be displayed automatically if a radio clock module is connected. However, the time cannot then be changed.
30 61 872_0407
Control level 2 – Standard settings
Day
Day
Press the r.h. rotary selector to change to control level 2. Turn the r.h. rotary selector clockwise to select the Standard settings submenu and confirm the selection by pressing the r.h. rotary selector again. Select the Day parameter by turning the rotary selector further clockwise.
08:30
Setting range: 1 (Mon) to 7 (Sun)
The day is changed by pressing (display indication flashes) and then turning the r.h. rotary selector. After setting or changing the current day (1 = Monday .... 7 = Sunday), pressing the r.h.
rotary selector again confirms the input.
Pressing the Info pushbutton returns the standard display.
Reset the day if the control unit has been disconnected from the power supply longer than 48 hours. The time will be displayed automatically if a radio clock module is connected. However, the time cannot then be changed.
Time program
Time prog
1
Factory setting: 1
Setting range: 1 / 2 / 3
Individual settings: _______
Press the r.h. rotary selector to change to control level 2. Turn the r.h. rotary selector clockwise to select the Standard settings submenu and confirm the selection by pressing the r.h. rotary selector again. Select the Time program parameter by turning the rotary selector further clockwise.
The time program 1, 2 or 3 is selected by pressing (display indication flashes) and then turning the r.h. rotary selector.
After selecting the time program, pressing the r.h. rotary selector again confirms the input.
Pressing the Info pushbutton returns the standard display.
Please note:
You can match the switching times to individual requirements.
For setting options and explanations to the programming of switching times, see the chapter on switching times programming.
30 61 872_0407 2 1
Info
Control level 2 – Standard settings
If several heating circuits are connected, that heating circuit is selected at this point the settings of which are to be changed.
If settings are made for the mixer circuits (day temperature, setback temperature, heating curve, room influence, SU / WI changeover, ECO/RED) at the programming module, call up the respective value from the mixer module. It may, therefore, take several seconds before the value can be changed.
22
Day temperature
(set room temperature, heating mode)
TEMP DAY
20.0
°C
Factory setting: 20 °C
Setting range: 5 to 30 °C
Individual settings:
Heating circuit: ____________
Mixer circuit 1: ____________
Mixer circuit 2: ____________
Mixer circuit 3: ____________
Mixer circuit 4: ____________
Mixer circuit 5: ____________
Mixer circuit 6: ____________
Mixer circuit 7: ____________
Press the r.h. rotary selector to change to control level 2. Turn the r.h. rotary selector clockwise to select the Standard settings submenu and confirm the selection by pressing the r.h. rotary selector again. Select the Day temperature parameter by turning the rotary selector further clockwise.
Note:
If more than one heating circuit is present in the heating system
(mixer circuit 1 up to mixer circuit 7), select heating circuit (HK) or mixer circuit 1 ...7 (mixer 1...7) by turning the r.h. rotary selector again clockwise at the standard settings menu level, and confirm the selection by pressing the r.h. rotary selector. Select the Day temperature parameter by turning the rotary selector further clockwise.
The day temperature is changed by pressing (display indication flashes) and then turning the r.h. rotary selector. After selecting the day program, pressing the r.h. rotary selector again confirms the setting.
Pressing the Info pushbutton returns the standard display.
Please note:
A different day temperature can be selected for each of the heating circuits remotely controlled by this programming module.
For control units that are purely room temperature-dependent
(Room influence OFF parameter or programming module only integrated into the boiler control unit), the selected day temperature is only an approximation and serves as calculation value for the heating curve.
30 61 872_0407
Control level 2 – Standard settings
Setback temperature
(set room temperature, setback mode)
RED TEMP
16.0
°C
Factory setting: 16 °C
Setting range: 5 to 30 °C
Individual settings:
Heating circuit: ____________
Mixer circuit 1: ____________
Mixer circuit 2: ____________
Mixer circuit 3: ____________
Mixer circuit 4: ____________
Mixer circuit 5: ____________
Mixer circuit 6: ____________
Mixer circuit 7: ____________
Press the r.h. rotary selector to change to control level 2. Turn the r.h. rotary selector clockwise to select the Standard settings submenu and confirm the selection by pressing the r.h. rotary selector again. Select the Setback temperature parameter by turning the rotary selector further clockwise.
Note:
If more than one heating circuit is present in the heating system
(mixer circuit 1 up to mixer circuit 7), select heating circuit (HK) or mixer circuit 1 ...7 (mixer 1...7) by turning the r.h. rotary selector again clockwise at the standard settings menu level, and confirm the selection by pressing the r.h. rotary selector. Select the Setback temperature parameter by turning the rotary selector further clockwise.
The setback temperature is changed by pressing (display indication flashes) and then turning the r.h. rotary selector.
After selecting the setback temperature, pressing the r.h. rotary selector again confirms the setting.
Pressing the Info pushbutton returns the standard display.
Please note:
A different setback temperature can be selected for each of the heating circuits remotely controlled by this programming module.
The selected day temperature is only an approximation for control units that are purely room temperature-dependent (Room influence OFF parameter or programming module only integrated into the boiler control unit).
Example of a changeover between day temperature and setback temperature with a preset heating program:
Set room temperature °C
20°C
16°C
Setback temperature
16 °C
Day temperature 20 °C
0:00 6:00 22:00 24:00
Time
30 61 872_0407 2 3
24
Control level 2 – Standard settings
Heating curve
GRADIENT
1.2
Factory setting:
Boiler circuit: 1.2
Mixer circuit: 0.8
Setting range: 0 to 3.0
Individual settings:
Heating circuit: ____________
Mixer circuit 1: ____________
Mixer circuit 2: ____________
Mixer circuit 3: ____________
Mixer circuit 4: ____________
Mixer circuit 5: ____________
Mixer circuit 6: ____________
Mixer circuit 7: ____________
The Heating curve parameter will not be displayed when the system is regulated only in room temperaturedependent mode.
Press the r.h. rotary selector to change to control level 2. Turn the r.h. rotary selector clockwise to select the Standard settings submenu and confirm the selection by pressing the r.h. rotary selector again. Select the Heating curve parameter by turning the rotary selector further clockwise.
Note:
If more than one heating circuit is present in the heating system
(mixer circuit 1 up to mixer circuit 7), select heating circuit (HK) or mixer circuit 1 ...7 (mixer 1...7) by turning the r.h. rotary selector again clockwise at the standard settings menu level, and confirm the selection by pressing the r.h. rotary selector.
Select the Heating curve parameter by turning the rotary selector further clockwise.
The Heating curve parameter is set by pressing (display indication flashes) and then turning the r.h. rotary selector.
After changing the Heating curve parameter, pressing the r.h.
rotary selector again confirms the setting.
Pressing the Info pushbutton returns the standard display.
Please note:
A different heating curve can be selected for each of the heating circuits remotely controlled by this programming module.
Function explained
Heating curve
This setting will be made by the heating contractor for each heating circuit separately, subject to the heating system, the thermal insulation of the building and the relevant climatic zone.
Setting the slope will match the heating water temperature to these conditions.
The following diagram indicates an example applicable to the following heating system:
- Climate zone with an average minimum outside temperature of -14 °C
- Radiator for flow/return temperatures 60/50 °C, with direct control
- Thermal building insulation in accordance with current regulations
For all other conditions, match the slope to the prevailing circumstances. The slope must always be set so that, at the min.
outside temperature, the maximum flow temperature for the radiators or the underfloor heating system will be achieved.
As rule of thumb, a slope of 1.0 can be used for a radiator heating system, and a slope of 0.4 for underfloor heating systems in a well insulated house. Similarly, a slope of 1.4 can be used for a radiator heating system, and a slope of 0.8 for underfloor heating systems in a less well insulated house.
30 61 872_0407
Control level 2 – Standard settings
100
90
80
70
60
50
40
30
20
10
0
20
Set room temperature [°C ]
(Parallel offset)
10
5
0 -10 -20
Aussentemperatur [°C]
Outside temperature [°C ]
-30 -40
Factory setting:
Day temperature: 20 °C
Setback temperature: 16 °C
Temperature selection:
Heating curve:
S/W switch:
ECO/RED:
0
1.2
20 °C
10 °C
The set room temperature is influenced by the Day temperature parameter, Setback temperature and the position of the r.h.
rotary selector (temperature selection).
The following example illustrates the interaction between the different parameters.
Day mode
Setback mode
1.2
1.0
0.8
0.6
0.4
0.2
1 Summer/winter changeover
2 ECO/RED
3 Setback stop
4 Maximum limit
30 61 872_0407
Outside temperature (°C)
2 5
26
Control level 2 – Standard settings
Room influence
ROOM INFLu
OFF
Factory setting: OFF
Setting range: ON / OFF
Individual settings:
Heating circuit: ____________
Mixer circuit 1: ____________
Mixer circuit 2: ____________
Mixer circuit 3: ____________
Mixer circuit 4: ____________
Mixer circuit 5: ____________
Mixer circuit 6: ____________
Mixer circuit 7: ____________
The Room influence parameter will not be displayed if the BM programming module is integrated into the boiler control unit.
Press the r.h. rotary selector to change to control level 2. Turn the r.h. rotary selector clockwise to select the Standard settings submenu and confirm the selection by pressing the r.h. rotary selector again. Select the Room influence parameter by turning the rotary selector further clockwise.
Note:
If more than one heating circuit is present in the heating system
(mixer circuit 1 up to mixer circuit 7), select heating circuit (HK) or mixer circuit 1 ...7 (mixer 1...7) by turning the r.h. rotary selector again clockwise at the standard settings menu level, and confirm the selection by pressing the r.h. rotary selector.
Select the Room influence parameter by turning the rotary selector further clockwise.
The Room influence parameter is set by pressing (display indication flashes) and then turning the r.h. rotary selector.
After changing the Room influence parameter, pressing the r.h.
rotary selector again confirms the setting.
Pressing the Info pushbutton returns the standard display.
Please note:
A Room influence can be switched ON or OFF for each of the heating circuits remotely controlled by this programming module.
Function explained
Room influence
Using room influence, room temperature fluctuations due to external heat or cold (e.g. solar irradiation, woodburning stove or open windows) can be compensated. Room influence will only work if the BM programming module is operated as remote control. A room temperature sensor is integrated into the programming module that captures the actual room temperature and compares it with the set value (day or setback temperature).
Activating room influence results in a correction of the weathercompensated calculated flow temperature via a room temperature sensor, either upwards (actual room temperature lower than the set room temperature) or downwards (actual room temperature higher than the set room temperature). The level of temperature correction can be set via system parameter A00 (see the
"Contractor" chapter).
30 61 872_0407
Control level 2 – Standard settings
Summer/winter changeover, subject to outside temperature
W/S SWITCH
20.0
°C
Factory setting: 20 °C
Setting range: 0 to 40 °C
Individual settings:
Heating circuit: ____________
Mixer circuit 1: ____________
Mixer circuit 2: ____________
Mixer circuit 3: ____________
Mixer circuit 4: ____________
Mixer circuit 5: ____________
Mixer circuit 6: ____________
Mixer circuit 7: ____________
The summer/winter changeover parameter will not be displayed when the system is regulated only in room temperature-dependent mode (no outside temperature sensor).
Press the r.h. rotary selector to change to control level 2. Turn the r.h. rotary selector clockwise to select the Standard settings submenu and confirm the selection by pressing the r.h. rotary selector again. Select the summer/winter changeover parameter by continuing to turn the selector clockwise.
Note:
If more than one heating circuit is present in the heating system
(mixer circuit 1 up to mixer circuit 7), select heating circuit (HK) or mixer circuit 1 ...7 (mixer 1...7) by turning the r.h. rotary selector again clockwise at the standard settings menu level, and confirm the selection by pressing the r.h. rotary selector.
Select the summer/winter changeover parameter by continuing to turn the selector clockwise.
The summer/winter changeover parameter is set by pressing
(display indication flashes) and then turning the r.h. rotary selector. After changing the summer/winter changeover parameter, pressing the r.h. rotary selector again confirms the setting.
Pressing the Info pushbutton returns the standard display.
Please note:
A different summer/winter changeover can be selected for each of the heating circuits remotely controlled by this programming module.
30 61 872_0407 2 7
Control level 2 – Standard settings
Function explained
Summer/winter changeover, subject to outside temperature
The control unit constantly calculates an average outside temperature over several hours, i.e. during day and night operation (setback mode).
- The heating system will be immediately switched OFF, if the adjusted outside temperature exceeds the preselected set value.
- The heating system will be automatically switched ON, if the adjusted average temperature falls more than 2 K below the preselected set value.
The DHW cylinder heating continues in accordance with the selected switching times program.
Example 1:
Temperature setting 20 °C.
Time setting: 3 h
Average temperature over the last 3 h = 21 °C.
The heating system remains OFF (pumps OFF, mixer closed).
Example 2:
Temperature setting 20 °C.
Time setting: 3 h
Average temperature over the last 3 h = 17 °C.
The heating system is switched ON.
Example 3:
Temperature setting 18 °C.
Time setting: 0 h
At outside temperatures above 18 °C, the heating system is switched OFF. At outside temperatures below 16 °C, the heating system is switched ON.
28 30 61 872_0407
Control level 2 – Standard settings
ECO/RED
ECO-RED
10.0
°C
Factory setting: 10 °C
Setting range: -10 to 40 °C
Individual settings:
Heating circuit: ____________
Mixer circuit 1: ____________
Mixer circuit 2: ____________
Mixer circuit 3: ____________
Mixer circuit 4: ____________
Mixer circuit 5: ____________
Mixer circuit 6: ____________
Mixer circuit 7: ____________
The ECO/RED parameter will not be displayed if the system is regulated only in room temperature-dependent mode.
Press the r.h. rotary selector to change to control level 2. Turn the r.h. rotary selector clockwise to select the Standard settings submenu and confirm the selection by pressing the r.h. rotary selector again. Select the ECO/RED parameter by turning the rotary selector further clockwise.
Note:
If more than one heating circuit is present in the heating system
(mixer circuit 1 up to mixer circuit 7), select heating circuit (HK) or mixer circuit 1 ...7 (mixer 1...7) by turning the r.h. rotary selector clockwise again at the standard settings menu level, and confirm the selection by pressing the r.h. rotary selector.
Select the ECO/RED parameter by turning the rotary selector further clockwise.
The ECO/RED parameter is set by pressing (display indication flashes) and then turning the r.h. rotary selector. After changing the ECO/RED parameter, pressing the r.h. rotary selector again confirms the setting.
Pressing the Info pushbutton returns the standard display.
Please note:
The ECO/RED function can be set differently for each of the heating circuits remotely controlled by this programming module.
30 61 872_0407 2 9
Function explained
ECO/RED
Control level 2 – Standard settings
The function is similar to the summer/winter changeover.
However, it only applies to the setback mode.
The control unit constantly calculates an average outside temperature over several hours.
- In setback mode, the heating system will be immediately switched OFF, if the adjusted outside temperature exceeds the preselected set value.
- The heating system will be automatically switched to setback mode, if the adjusted average temperature falls more than
2 K below the preselected set value.
The DHW cylinder heating continues in accordance with the selected switching times program.
Example 1:
Temperature setting 10 °C.
Time setting: 3 h
Average temperature over the last 3 h = 11 °C.
The control unit will not switch over from heating mode to setback mode in accordance with the switching times program but instead switches OFF (ECO) immediately (pumps OFF, mixer closed).
Example 2:
Temperature setting 10 °C.
Time setting: 3 h
Average temperature over the last 3 h = 7 °C.
The control unit switches from heating mode to setback mode
(RED) in accordance with the switching program.
The aim is to switch the central heating OFF automatically when high outside temperatures prevail at night.
30 30 61 872_0407
Control level 2 – Standard settings
DHW temperature
DHW TEMP
55.0
°C
The DHW temperature parameter will not be displayed when the heating system provides no DHW heating (no cylinder sensor installed).
Press the r.h. rotary selector to change to control level 2. Turn the r.h. rotary selector clockwise to select the Standard settings submenu and confirm the selection by pressing the r.h. rotary selector again. Select the DHW temperature parameter by turning the rotary selector further clockwise.
Factory setting: 55 °C
Setting range:
Freestanding boiler: 15 to 60 °C
Wall mounted boilers:15 to 65 °C
The DHW temperature is changed by pressing (display indication flashes) and then turning the r.h. rotary selector. After selecting the DHW temperature, pressing the r.h. rotary selector again confirms the setting.
Individual settings: _______
Pressing the Info pushbutton returns the standard display.
Please note:
This parameter enables the selection of the required DHW temperature.
The DHW will be heated to the selected value if DHW heating is enabled via the switching times program.
Where higher DHW temperatures than 60 / 65 °C are required, enable these via the Contractor parameter HG23 (see chapter
"Contractor, boiler parameters").
NB
Always ensure that cold water is mixed in with hot water, when the DHW temperature is set above 60 °C or when operating the pasteurisation system at a temperature higher than 60 °C
(risk of scalding).
Language
Language
Press the r.h. rotary selector to change to control level 2. Turn the r.h. rotary selector clockwise to select the Standard settings submenu and confirm the selection by pressing the r.h. rotary selector again. Select the Language parameter by turning the rotary selector further clockwise.
The Language is changed by pressing (display indication flashes) and then turning the r.h. rotary selector. After selecting the language, pressing the r.h. rotary selector again confirms the setting.
Factory setting: German
Setting range:
German / English / French /
Dutch / Spanish / Portuguese /
Italian / Czech / Polish /
Slovakian / Hungarian / Russian /
Greek / Turkish
Pressing the Info pushbutton returns the standard display.
Individual settings: _______
30 61 872_0407 3 1
32
Control level 2 – Standard settings
Pushbutton lock
KEY LOCK
OFF
Factory setting: OFF
Setting range: ON / OFF
Individual settings: _______
Press the r.h. rotary selector to change to control level 2. Turn the r.h. rotary selector clockwise to select the Standard settings submenu and confirm the selection by pressing the r.h. rotary selector again. Select the Pushbutton lock parameter by turning the rotary selector further clockwise.
The pushbutton lock is changed by pressing (display indication flashes) and then turning the r.h. rotary selector. After selecting the pushbutton lock, pressing the r.h. rotary selector again confirms the setting.
Pressing the Info pushbutton returns the standard display.
Please note:
The Pushbutton lock parameter is designed to prevent an unintentional adjustment of the heating system (e.g. through children or when cleaning).
If the Pushbutton lock parameter is set to ON, the pushbutton lock will be activated automatically one minute after the last adjustment.
No adjustments or scans can be implemented when the pushbutton lock is enabled. If, nevertheless, a pushbutton or rotary selector is activated, then the display shows KEY LOCK.
The pushbutton lock can be lifted for a single adjustment or to display the set/actual values by holding down the r.h. rotary selector for approx. one second.
To disable the pushbutton lock permanently, the Pushbutton lock parameter must be set to OFF again (for setting, see above).
30 61 872_0407
Control level 2 – Time program
Setting switching times for time program
At the factory, three non-volatile time programs are preset. The active time program is selected via the Standard settings parameter
Time prog (see standard settings).
Changing the Standard settings parameter Time prog switches the ON and OFF time blocks for heating, DHW and DHW circulation over to the relevant time program.
The following table shows the factory-set switching times.
The switching times of the mixer circuits will not be displayed if only heating circuits are controlled (no mixer circuit installed).
Time Block Switch.
program time
Time prog. 1 Mo-Fr
Time prog. 2 Mo-Fr
Time prog. 3
Sa-Su
Sa-Su
Mon
Tue
Wed
Thu
Fr
Sa
Su
2
3
3
1
3
1
2
1
2
3
1
2
2
3
3
1
1
2
2
3
3
1
3
1
2
1
2
2
3
3
1
1
2
ON
HK
OFF ON
Mixer
OFF ON
DHW
OFF
DHW circ. line
ON OFF
6:00 22:00 5:00 21:00 5:30 22:00 6:00 6:30
17:00 18:30
7:00 23:00 6:00 22:00 6:30 23:00 6:30 7:00
11:00 12:00
17:00 18:30
6:00 8:00 5:00 7:00 5:00 6:00 6:00 6:15
15:00 22:00 14:00 21:00 17:00 18:00
7:00
5:30
5:30
5:30
5:30
5:30
5:30
5:30
22:00
21:00
21:00
21:00
21:00
21:00
21:00
21:00
6:00
4:30
4:30
4:30
4:30
4:30
4:30
4:30
21:00
20:00
20:00
20:00
20:00
20:00
20:00
20:00
6:00
16:00
5:00
15:00
5:00
15:00
5:00
15:00
5:00
15:00
5:00
15:00
5:00
15:00
5:00
15:00
7:00
21:00
7:00
21:00
7:00
21:00
7:00
21:00
7:00
21:00
7:00
21:00
7:00
21:00
7:00
21:00
6:30
16:30
6:00
17:00
6:00
17:00
6:00
17:00
6:00
17:00
6:00
17:00
6:00
17:00
6:00
17:00
6:45
17:00
6:30
17:30
6:30
17:30
6:30
17:30
6:30
17:30
6:30
17:30
6:30
17:30
6:30
17:30
30 61 872_0407 3 3
Control level 2 – Time program
Programming example
For DHW heating, switching time 1 is to be changed in time program 1 as follows: from: SA - SU 6:00 h ON to:
SA - SU 21:00 h OFF
SA - SU 8:00 h ON
SA - SU 22:00 h OFF
Press the r.h. rotary selector to change to control level 2. Turn the r.h. rotary selector clockwise to select the Time prog menu level and confirm the selection by pressing the r.h. rotary selector again. Select the DHW parameter by turning the rotary selector further clockwise.
Push the r.h. rotary selector and select the block SA-SU, then confirm the selection by pressing the r.h. rotary selector again.
Switching time 1 will then be shown.
The start time is changed by pressing (display flashes 6:00) and then turning the r.h. rotary selector. After selecting the start time, pressing the r.h. rotary selector again confirms the setting; the display then changes automatically to the stop time
(display flashes 21:00). Turning the r.h. rotary selector changes the stop time, which is then confirmed by pressing the r.h.
rotary selector again.
Pressing the Info pushbutton returns the standard display.
Notes:
- You can adjust the switching times program in steps of
15 minutes.
- Switching times must always be programmed in chronological order.
Correct: Switching time 1: 6:00 – 10:00 h
Switching time 2: 15:00 – 22:00 h
Incorrect: Switching time 1: 15:00 – 22:00 h
Switching time 2: 6:00 – 10:00 h
- When forming a time block, a time entry beyond midnight must be made according to the following example:
Example: In time program 1, central heating should take place from 16:00 h to 3:00 h the following day. For this, set the following times:
Switching time 1: 0:00 h – 3:00 h
Switching time 2: 16:00 h – 24:00 h
34 30 61 872_0407
Code scan
CODE-NO
- - - -
Control level 2 – Contractor
Press the r.h. rotary selector to change to control level 2. Turn the r.h. rotary selector clockwise to select the menu level
Contractor and confirm the selection by pressing the r.h. rotary selector again.
The display shows the code scan.
The correct code is set by pressing (display indication flashes) and then turning the r.h. rotary selector from 0 to 1. After changing the code from 0 to 1, pressing the r.h. rotary selector again confirms the setting; you are then at the Contractor level.
Factory setting: 1
Overview
System
Setting the system parameters for the heating control unit. For the optional adjustments and explanation of individual parameters, see chapter "System parameters".
Boiler 1
30 61 872_0407
The boiler parameters (e.g. maximum boiler water temperature, input 1, output 1) can be adjusted via the BM programming module. The boiler parameters may vary, subject to the respective boiler version.
Possible adjustments and explanations regarding the individual parameters are shown in the respective boiler or control unit installation instructions.
After selecting the parameter, the details are obtained from the boiler control unit and displayed approx. 5 seconds later.
The currently selected value will be shown in the display and can be modified, subject to the parameter being available in the boiler control unit.
A display of four lines indicates that the parameter is not available in the connected boiler control unit.
3 5
36
Mix VALVE 1
Solar
OTHERS
Control level 2 – Contractor
The menu level Mixer will not be displayed if only heating circuits are controlled (no mixer circuit installed).
The parameters for mixer circuits 1-7 (e.g. configuration, heating curve gap) can be adjusted via the BM programming module.
Possible adjustments and explanations regarding the individual parameters are shown in the installation instructions of the mixer module or boiler.
The menu level Solar will not be displayed if no solar module is installed.
Parameters (e.g. start-up differential, shutdown differential) can be adjusted via the BM programming module.
Possible adjustments and explanations regarding the individual parameters are shown in the solar module installation instructions.
Other parameters (e.g. fuel consumption, screed drying, etc.) can be adjusted via the BM programming module. Possible adjustments and explanations regarding the individual parameters are shown in the respective boiler or control unit installation instructions.
30 61 872_0407
Control level 2 – Contractor
System parameter overview, Contractor menu
(Settings and functions on the following pages)
Parameters
A00
Room influence
A01
Heat-up optimisation
A02
Max. heat-up time
A03
Required heat-up time
A04
Adjusted outside temperature sensor
A05
Room temperature sensor matching
A06
External room temperature sensor
A07
Pasteurisation function
A08
Service message
A09
Frost protection level
A10
Parallel DHW operation
A11
Room temperature-dependent
Summer/winter changeover
A12
Setback stop
A13
Minimum DHW temperature
Setting range Factory setting
1 to 20 K / K
0 / 1
0 to 180 min
4 K / K
0
0
-
0 to 24 h
-5 to +5 K
0 to 1
0 to 8
0 to 104 weeks
-20 to +10 °C
0 / 1
OFF / ON
-
3 h
0 K
1
0
0
+2 °C
0
ON
OFF, -39 to 0 °C
0 to 60 °C
-16 °C
40 °C
30 61 872_0407 3 7
Control level 2 – Contractor
Room influence
Parameter A00
A00
4
Factory setting: 4 K / K
Setting range: 1 to 20 K / K
Individual settings: _______
With the r.h. rotary selector, select the Room influence system parameter A00 from the Contractor menu level (after entering the correct code).
The Room influence parameter is changed by pressing (display indication flashes) and then turning the r.h. rotary selector.
After setting the Room influence parameter, pressing the r.h.
rotary selector again confirms the setting.
Pressing the Info pushbutton returns the standard display.
Note:
Small room influencing factor
!
little effect on the flow temperature.
Greater room influencing factor
!
stronger effect on the flow temperature.
Thermostat function
Function explained
Room influence
38
The programming module will also function as a remote control; if it is fitted in a wall mounting base and is connected as a remote control, and the room influence (standard settings) has been enabled. If the room temperature is more than 1 K higher than the set room temperature, the heating circuit pump will be switched OFF (exception frost protection). The heating circuit pump will only restart, if the actual room temperature falls below the required set room temperature.
If this is not required, disable the room influence (standard settings) or the room temperature-dependent summer/winter changeover (parameter A11).
Using room influence, room temperature fluctuations due to external heat or cold (e.g. solar irradiation, woodburning stove or open windows) can be compensated. Room influence will only function if the BM programming module is operated as remote control. A room temperature sensor is integrated into the programming module that captures the actual room temperature and compares it with the set value (day or setback temperature). A set value deviation is multiplied with the set room influencing factor (0 to 20 K / K) and the heating curve.
The boiler or mixer is adjusted by this value.
Example:
Set room temperature 20 °C
Heating curve: 1.2
Actual room temperature 18 °C (e.g. after airing)
!
deviation 2 K
Room influence boiler circuit: Setting 4 K / K
Deviation 2 K x room influence 4 K / K x heating curve 1.2 = 10 K
The heating water temperature is raised by 10 °C to quickly raise the room temperature to the set value of 20 °C.
30 61 872_0407
Control level 2 – Contractor
Heat-up optimisation
Parameter A01
A01
0
Factory setting: 0
Setting range: 0 to 2
Individual settings: _______
With the r.h. rotary selector, choose the Heat-up optimisation system parameter A01 from the Contractor menu level (after entering the correct code).
The Heat-up optimisation parameter is changed by pressing
(display indication flashes) and then turning the r.h. rotary selector. After setting the Heat-up optimisation parameter, pressing the r.h. rotary selector again confirms the setting.
Pressing the Info pushbutton returns the standard display.
Please note:
The heat-up optimisation calculates the required heat-up time in setback mode, enabling the required room temperature to be achieved at the time selected by the time program.
The calculation can be implemented subject to the outside or the room temperature. The heat-up time optimisation is switched ON with parameter A02 (maximum heat-up time).
The settings have the following meaning:
0
!
Programming the heat-up OFF
1
!
Weather-compensated heat-up optimisation
2
!
Room-temperature-dependent heat-up optimisation
Maximum heat-up time
Parameter A02
A02
0
Factory setting: 0
Setting range: 0 to 180 min
Individual settings: _______
With the r.h. rotary selector, choose the Maximum heat-up time system parameter A02 from the Contractor menu level (after entering the correct code).
The Maximum heat-up time parameter is changed by pressing
(display indication flashes) and then turning the r.h. rotary selector. After setting the Maximum heat-up time parameter, pressing the r.h. rotary selector again confirms the setting.
Pressing the Info pushbutton returns the standard display.
Please note:
The poorer the building insulation, the longer the maximum heatup time.
30 61 872_0407 3 9
Control level 2 – Contractor
Function explained
Maximum heat-up time
This parameter specifies the maximum heat-up time. Starting from the changeover command of the time switch (minus selected maximum heat-up time), the boiler control unit calculates the latest possible start-up time for the changeover point, so that the required room temperature is achieved at the selected time.
Heat-up optimisation will not take place, if 0 has been entered for maximum heat-up time.
Example:
Start time heating mode in accordance with the time program:
6:00 h
Maximum heat-up time: 120 min
From 4:00 h, the boiler control unit starts to calculate the latest start-up point "t”, so that the required room temperature will be achieved by 6:00 h.
40
Required heat-up time
Parameter A03
A03
----
This parameter will only be displayed if the Heat-up optimisation parameter A01 has been enabled.
With the r.h. rotary selector, choose the required Heat-up time system parameter A03 from the Contractor menu level (after entering the correct code).
The required Heat-up time parameter indicates the last heat-up time that was required in minutes.
This parameter is merely an indicator and cannot be changed.
Pressing the Info pushbutton returns the standard display.
30 61 872_0407
Control level 2 – Contractor
Adjusted outside temperature
Parameter A04
A04
3
Factory setting: 3 h
Setting range: 0 to 24 h
Individual settings: _______
With the r.h. rotary selector, choose the Adjusted outside temperature system parameter A04 from the Contractor menu level (after entering the correct code).
The Adjusted outside temperature parameter is changed by pressing (display indication flashes) and then turning the r.h.
rotary selector. After setting the Adjusted outside temperature parameter, pressing the r.h. rotary selector again confirms the setting.
Pressing the Info pushbutton returns the standard display.
Please note:
For some automatic functions (e.g. summer/winter changeover,
ECO/RED), the control unit calculates over several hours an average outside temperature using the current outside temperature. With the Average outside temperature parameter you can select over how many hours the boiler control unit should calculate an average value. If this parameter is set to 0 h, the control unit will no longer calculate an adjusted value; instead the adjusted value will always be equal to the current outside temperature.
The outside temperature display at control level 1 will not be adjusted.
Room temperature sensor matching
Parameter A05
A05
0.0
°C
Factory setting: 0
Setting range: -5 to +5 K
Individual settings: _______
With the r.h. rotary selector, choose the Room temperature sensor matching system parameter A05 from the Contractor menu level (after entering the correct code).
The Room temperature sensor matching parameter is changed by pressing (display indication flashes) and then turning the r.h. rotary selector. After setting the Room temperature sensor matching parameter, pressing the r.h. rotary selector again confirms the setting.
Pressing the Info pushbutton returns the standard display.
30 61 872_0407 4 1
Control level 2 – Contractor
Please note:
The current display can be changed by + / - 5 K, to match the room temperature display to the installation conditions or other thermometers. The corrected display value will be applied to all calculations of relevant functions.
Example:
The remote control indicates a room temperature of 20 °C.
In the living area, a temperature of 22 °C is measured with a thermometer.
The set value must be changed to +2 °C. That way, the actual temperature measured by the remote control will always be indicated 2 °C higher.
42
External sensor
Parameter A06
A06
1
Factory setting: 1
Setting range: 0 to 1
Individual settings: _______
With the r.h. rotary selector, choose the External sensor system parameter A06 from the Contractor menu level (after entering the correct code).
The External sensor parameter is changed by pressing (display indication flashes) and then turning the r.h. rotary selector.
After setting the External sensor parameter, pressing the r.h.
rotary selector again confirms the setting.
Pressing the Info pushbutton returns the standard display.
Please note:
If the programming module is used as remote control fitted into a wall mounted base, the terminal 5 / 6 of the terminal strip inside the wall mounting base (see chapter "Installation"), an external room temperature sensor or an external outside temperature sensor can be connected. This sensor can have a function allocated via the External sensor system parameter A06.
The settings have the following meaning:
0
!
External room temperature sensor
1
!
External outside temperature sensor
30 61 872_0407
Control level 2 – Contractor
Pasteurisation function
Parameter A07
A07
0
Factory setting: 0
Setting range: 1 to 8
Individual settings: _______
With the r.h. rotary selector, choose the Pasteurisation function system parameter A07 from the Contractor menu level (after entering the correct code).
The Pasteurisation function parameter is changed by pressing
(display indication flashes) and then turning the r.h. rotary selector. After setting the Pasteurisation function parameter, pressing the r.h. rotary selector again confirms the setting.
Pressing the Info pushbutton returns the standard display.
Please note:
• Systems without solar module:
If pasteurisation has been enabled, the DHW cylinder will be heated to 65 °C during the first cylinder heating of the selected day. This set temperature will be maintained for one hour.
• Systems with solar module:
The pasteurisation function will be safeguarded by the boiler or the solar heating system, if pasteurisation has been enabled.
a. Pasteurisation by the solar heating system
The pasteurisation function via the boiler will be blocked if the solar yield has achieved a cylinder temperature in excess of
65 °C for at least one hour. Blocking the pasteurisation by the boiler is indicated at the info level STATUS SOL.
b. Pasteurisation by the boiler
If the solar yield is insufficient for a pasteurisation, the set
DHW temperature is set to 65 °C for one hour at 18:00 h on the selected day.
The settings have the following meaning:
0
!
Pasteurisation disabled
1 to 7
!
Pasteurisation once a week (1 = Mon; 7 = Sun)
8
!
Daily pasteurisation
30 61 872_0407 4 3
Control level 2 – Contractor
Service message
Parameter A08
A08
0
Factory setting: 0
Setting range: 1 to 104 weeks
Individual settings: _______
With the r.h. rotary selector, choose the Service message system parameter A08 from the Contractor menu level (after entering the correct code).
The Service message parameter is changed by pressing
(display indication flashes) and then turning the r.h. rotary selector. After setting the Service message parameter, pressing the r.h. rotary selector again confirms the setting.
Pressing the Info pushbutton returns the standard display.
Please note:
Enabling the Service message parameter, e.g. set value greater than 0, the display will show Service after expiry of the selected number of weeks. You can acknowledge this message by pressing the Setback pushbutton (control level 1). Afterwards, the cycle restarts again.
The settings have the following meaning:
0 weeks
!
Service message disabled
52 weeks
!
Annual service message
44
Frost protection limit
Parameter A09
A09
2.0
°C
Factory setting: 2 °C
Setting range: -20 to +10 °C
Individual settings: _______
With the r.h. rotary selector, choose the Frost protection limit system parameter A09 from the Contractor menu level (after entering the correct code).
The Frost protection limit parameter is changed by pressing
(display indication flashes) and then turning the r.h. rotary selector. After setting the Frost protection limit parameter, pressing the r.h. rotary selector again confirms the setting.
Pressing the Info pushbutton returns the standard display.
The boiler circuit pump operates constantly if the outside temperature stays below the selected value.
The burner starts and heats the boiler up to the minimum boiler water temperature, if the boiler water temperature falls below the permanently set value of +5 °C.
Note:
Only change the factory setting if you can ensure that the heating system and its components will not freeze up at low outside temperatures.
30 61 872_0407
Control level 2 – Contractor
Parallel DHW operation
Parameter A10
A10
0
Factory setting: 0
Setting range: 0 / 1
Individual settings: _______
NB
With the r.h. rotary selector, choose the Parallel DHW operation system parameter A10 from the Contractor menu level (after entering the correct code).
The Parallel DHW operation parameter is changed by pressing
(display indication flashes) and then turning the r.h. rotary selector. After setting the Parallel DHW operation parameter, pressing the r.h. rotary selector again confirms the setting.
Pressing the Info pushbutton returns the standard display.
The boiler circuit pump is switched OFF during DHW cylinder heating with DHW priority (0). The boiler energy will then be used exclusively for heating the DHW cylinder. The cylinder primary pump will only start, if the boiler water temperature is
5 °C higher than the actual cylinder temperature. The burner shuts down and the heating circuit pump is started, as soon as the cylinder has reached its set temperature. The cylinder primary pump runs on for the time selected under parameter
HG19 (cylinder primary pump run-on time).
The heating circuit pump continues to operate in parallel DHW
mode (1). The cylinder primary pump starts, if the boiler water temperature is 5 °C warmer than the cylinder temperature. The cylinder is fully heated up when the cylinder has reached the selected water temperature. The cylinder primary pump runs on for the maximum period selected under parameter HG19
(cylinder primary pump run-on time).
In the parallel DHW mode (1), the heating circuit can temporarily be operated at a higher temperature.
For wall mounted boilers, this parameter has no function.
30 61 872_0407 4 5
46
Control level 2 – Contractor
Room temperaturedependent summer/ winter changeover
Parameter A11
A11
ON
Factory setting: ON
Setting range: ON / OFF
Individual settings: _______
With the r.h. rotary selector, choose the Room temperaturedependent summer/winter changeover parameter A11 from the
Contractor menu level (after entering the correct code).
The Room temperature-dependent summer/winter changeover parameter is set by pressing (display indication flashes) and then turning the r.h. rotary selector. After changing the Room temperature-dependent summer/winter changeover parameter, pressing the r.h. rotary selector again confirms the setting.
Pressing the Info pushbutton returns the standard display.
This parameter is only active if room influence is enabled.
Function explained
Room temperaturedependent s u m m e r / w i n t e r changeover
Using room influence, room temperature fluctuations due to external heat or cold (e.g. solar irradiation, woodburning stove or open windows) can be compensated. With room influence enabled or in case of simple room control, if the room temperature exceeds the selected set room temperature by 1 K, then the system changes over from winter to summer operation, subject to this parameter being enabled.
The summer/winter changeover can be enabled / disabled via this parameter.
The settings have the following meaning:
OFF
!
Summer/winter changeover OFF
ON
!
Summer/winter changeover ON
Example 1:
The summer/winter changeover (ON) prevents the area being overheated, if room influence is enabled and the accommodation is only heated by a boiler.
Example 2:
A summer/winter changeover can occur, if a room, where the programming module is installed (e.g. living room) is heated by a second heat source (e.g. a woodburning stove), and room influence is enabled. This would result in other rooms getting cold.
Remedy: Disable room temperature-dependent summer/winter changeover (OFF).
30 61 872_0407
Control level 2 – Contractor
Setback stop
Parameter A12
A12
- 16.0
°C
Factory setting: -16 °C
Setting range: OFF, -39 to 0 °C
Individual settings: _______
With the r.h. rotary selector, choose the Setback stop system parameter A12 from the Contractor menu level (after entering the correct code).
The Setback stop parameter is changed by pressing (display indication flashes) and then turning the r.h. rotary selector.
After setting the Setback stop parameter, pressing the r.h. rotary selector again confirms the setting.
Pressing the Info pushbutton returns the standard display.
Please note:
The boiler control unit returns from setback mode to heating mode, if the adjusted outside temperature falls below the selected value.
Otherwise, if the adjusted outside temperature lies below the radiator design temperature, the required room temperature would not be able to be achieved for a considerable period of time after the temperature setback.
Example 1:
Setting: -16 °C
Adjusted outside temperature: -16 °C
There will also be no changeover to setback mode, even outside the selected switching times.
Example 2:
Setting -16 °C
Adjusted outside temperature: -10 °C
Outside the selected switching times, the system changes from day mode to setback mode.
Set Setback stop parameter to OFF, if no setback stop is required.
30 61 872_0407 4 7
48
Control level 2 – Contractor
Minimum DHW temperature
Parameter A13
A13
40.0
°C
Factory setting: 40 °C
Setting range: 0 to 40 °C
Individual settings: _______
With the r.h. rotary selector, choose the Minimum DHW temperature parameter A13 from the Contractor menu level
(after entering the correct code).
The Minimum DHW temperature parameter is changed by pressing (display indication flashes) and then turning the r.h.
rotary selector. After setting the Minimum DHW temperature parameter, pressing the r.h. rotary selector again confirms the setting.
Pressing the Info pushbutton returns the standard display.
Please note:
The setting for the minimum DHW temperature is enabled when a solar extension module is connected. This parameter has no function for the heating system if no solar module is connected.
The set DHW temperature will be adjusted to the minimum DHW temperature (parameter A13) until 14:00 h the following day, if the solar heating has been completed successfully (selected
DHW temperature is exceeded at the solar cylinder sensor).
The boiler provides no cylinder heating, when the selected DHW temperature is not achieved.
Only when the minimum DHW temperature is not achieved and cylinder heating has been enabled by the DHW time program, will the boiler heat the cylinder to the minimum DHW temperature.
The set DHW temperature remains at the value of the selected
DHW temperature, if solar heating is not completed successfully.
Pressing the pushbutton Single cylinder heating sets the required
DHW from minimum DHW temperature to DHW temperature
(standard settings parameter), even if the solar heating was successful.
30 61 872_0407
Boiler 1
Control level 2 – Contractor
The boiler parameters (e.g. maximum boiler water temperature, input 1, output 1) can be adjusted via the BM programming module. The boiler parameters may vary, subject to the respective boiler version.
Possible adjustments and explanations regarding the individual parameters are shown in the respective boiler or control unit installation instructions.
After selecting the parameter, the details are obtained from the boiler control unit and displayed approx. 5 seconds later.
The currently selected value will be shown in the display and can be modified, subject to the parameter being available in the boiler control unit.
A display of four lines indicates that the parameter is not available in the connected boiler control unit.
Changing the boiler parameters HG...
With the r.h. rotary selector, choose the boiler parameter to be modified (HG..) from the Contractor menu level (after entering the correct code).
The boiler parameter to be modified (HG..) is changed by pressing (display indication flashes) and then turning the r.h.
rotary selector. After setting the boiler parameter to be modified
(HG..), pressing the r.h. rotary selector again confirms the setting.
Pressing the Info pushbutton returns the standard display.
NB
An incorrect adjustment of these parameters can result in a faulty boiler operation.
30 61 872_0407 4 9
50
Control level 2 – Contractor
Boiler parameter overview, Contractor menu
(Setting and function in the installation instructions of the boiler or the boiler control unit)
Parameters
HG00
Matching the pipe length
HG01
Burner switching differential
HG02
Low end fan speed HZ
HG03
High end fan speed WW
HG04
High end fan speed HZ
HG06
Pump operating mode
HG07
Boiler circuit pump run-on time
HG08
Maximum limit boiler circuit TV-max.
HG09
Burner cycle block
HG10
HG11
HG12 eBUS address
DHW quick start
Gas type
HG13
HG14
Programmable input E1
Programmable output A1
HG15
Cylinder hysteresis
HG16
Pump rate HK, minimum
HG17
Pump rate HK, maximum
HG19
Cylinder primary pump run-on time
HG20
Max. cylinder heating time
HG21
Minimum boiler temperature TK-min.
HG22
Maximum boiler water temperature TK-max.
HG23
Maximum DHW temperature
HG24
DHW sensor operating mode
HG25
Boiler excess temperature during cylinder heating
HG26
Boiler soft start
HG27
Burner stage during cylinder heating
HG28
Burner operating mode
HG29
Modulation block
HG30
Modulation dynamic
HG31
Blocking time, burner stage 2
HG32
HG33
HG34
Return temperature raising
Hysteresis time eBUS feed
HG50
Test functions
30 61 872_0407
Mix valve 1
Changing the mixer parameter MI...
30 61 872_0407
Control level 2 – Contractor
The menu level Mixer will not be displayed if only heating circuits are controlled (no mixer circuit installed).
The parameters for mixer circuits 1-7 (e.g. configuration, heating curve gap) can be adjusted via the BM programming module.
Possible adjustments and explanations regarding the individual parameters are shown in the installation instructions of the mixer module or boiler.
After selecting the parameter, the details are obtained from the mixer module and displayed approx. 5 seconds later.
With the r.h. rotary selector, choose the mixer parameter to be modified (MI..) from the Contractor menu level (after entering the correct code).
The mixer parameter to be modified (MI..) is changed by pressing
(display indication flashes) and then turning the r.h. rotary selector. After setting the mixer parameter to be modified (MI..), pressing the r.h. rotary selector again confirms the setting.
Pressing the Info pushbutton returns the standard display.
Mixer parameter overview, Contractor menu
(Setting and function in the installation instructions of the mixer module or the boiler control unit.)
Parameters
MI 01
Minimum limit mixer circuit TV-min.
MI 02
Maximum limit mixer circuit TV-max.
MI 03
Heating curve gap
MI 04
MI 05
Screed drying
MI 06
MI 07
Configuration
Mixer circuit pump run-on time
P range, mixer
MI 08
Set return temperature
MI 09
MI 10
MI 12
Max. cylinder heating time eBUS feed
MI 11
Hysteresis, bypass sensor
Primary pump block
MI 13
Primary pump run-on time
MI 14
MI 15
Constant temperature dTAus (shutdown differential)
MI 16 dTEin (start-up differential)
MI 17
MI SO
Excess boiler temperature during cylinder heating
Relay test
5 1
Solar
Changing the mixer parameter SOL...
Control level – Contractor
The menu level MSolar will not be displayed if only heating circuits are controlled (no solar circuit installed).
Solar module parameters (e.g. start-up differential, shutdown differential) can be adjusted via the BM programming module.
Possible adjustments and explanations regarding the individual parameters are shown in the solar module installation instructions.
After selecting the parameter, the details are obtained from the solar module and displayed approx. 5 seconds later.
With the r.h. rotary selector, choose the solar parameter to be modified (SOL..) from the Contractor menu level (after entering the correct code).
The solar parameter to be modified (SOL..) is changed by pressing (display indication flashes) and then turning the r.h.
rotary selector. After setting the solar parameter to be modified
(SOL..), pressing the r.h. rotary selector again confirms the setting.
Pressing the Info pushbutton returns the standard display.
Solar parameter overview, Contractor menu
(Setting and function in the installation instructions of the solar module.)
Parameter
SOL 01
Start-up differential
SOL 02
SOL 03
Shutdown differential
Collector protection function
SOL 04
Critical collector temperature
SOL 05
Maximum collector temperature
SOL 06
Maximum cylinder temperature
SOL 07
SOL 08
Cylinder allocation
Capturing the heat volume
SOL 09
Pulse transducer, flow rate
SOL 10
SOL 11
Medium selection eBUS feed
SOL SO
Relay test
52 30 61 872_0407
OTHERS
Control level 2 – Contractor
Other parameters (e.g. screed drying) can be adjusted via the
BM programming module.Possible adjustments and explanations regarding the individual parameters are shown in the respective boiler or control unit installation instructions.
Changing other parameters SO...
With the r.h. rotary selector, choose the parameter to be modified
(SO..) from the Contractor menu level (after entering the correct code).
The parameter to be modified (SO..) is changed by pressing
(display indication flashes) and then turning the r.h. rotary selector. After setting the parameter to be modified (SO..), pressing the r.h. rotary selector again confirms the setting.
Pressing the Info pushbutton returns the standard display.
Other parameter overview, Contractor menu
Parameter
SO 01
N / A
SO 02
N / A
SO 03
N / A
SO 04
N / A
SO 05
N / A
SO 06
N / A
SO 07
Screed drying, direct heating circuit
SO 08
Screed temperature
30 61 872_0407 5 3
Screed drying, direct heating circuit
Parameter SO 07
Parameter SO 08
Control level 2 – Contractor
If an underfloor heating system is started for the first time in new buildings, the set flow temperature may, as an option, be controlled independent of the outside temperature either to a constant value or to control the set flow temperature in accordance with an automatic screed drying program.
If this function has been enabled (setting 1 or 2), it can be terminated by resetting parameter SO 07 to 0.
SO 07 = 0 no function
SO 07 = 1 constant temperature heating circuit
The heating circuit is heated to the set flow temperature. The set flow temperature is regulated permanently to the temperature selected in parameter SO 08.
To change the constant temperature for screed drying, proceed as follows:
1.
Press the r.h. rotary selector
2.
Turn the r.h. rotary selector clockwise until
EXPERT
is displayed.
3.
Press the r.h. rotary selector.
4.
CODE-NO
will be displayed.
5.
Press the r.h. rotary selector to be able to enter the contractor code.
6.
Set code to 1.
7.
Press the r.h. rotary selector to be able to confirm the code.
8.
Turn the r.h. rotary selector clockwise until
OTHERS
is displayed.
9.
Press the r.h. rotary selector.
10. Turn the r.h. rotary selector clockwise until
SO 08
is displayed.
11. Press the r.h. rotary selector.
12. Select the required constant temperature in accordance with the heat-up curve by turning the r.h. rotary selector.
13. Press the r.h. rotary selector.
14. Press the Info pushbutton to return to the standard display.
SO 07 = 2 Screed drying function
For the first two days, the set flow temperature will remain constant at 25 °C. It will then be automatically raised every day
(at 0.00 h) by 5 °C up to the screed temperature (SO 08). That temperature will then be held for two days. Subsequently, the flow temperature is automatically reduced again in 5 °C steps per day to 25 °C. The program sequence is terminated after a further two days.
54 30 61 872_0407
Control level 2 – Contractor / Reset
55
50
45
40
35
30
25
20
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
Screed drying runtime (days)
Fig.:
Flow temperature progress over time during screed drying
(parameter SO 08 = 50 °C)
NB
Agree the time sequence and the maximum flow temperature with the screed contractor, otherwise the screed may be damaged, particularly through cracking.
The screed drying program continues uninterrupted after a power failure. The remaining time in days is shown on the display.
Reset
30 61 872_0407
Observe the following steps to implement a reset:
- The ON / OFF switch of the boiler control unit must be set to O (OFF).
- Press and hold down the rotary selector of the programming module whilst setting the ON / OFF switch to I (ON).
- Keep holding down the reset button for at least 2 seconds after the system has started.
All parameters (individual settings) are returned to their factory settings by a reset. As a check, EEPROM will be shown afterwards for approx. 3 seconds in the programming module display.
5 5
Settings report
Standard settings parameters
Wolf recommends you complete the settings report carefully and to keep it safe to enable a quick solution to be found during service and in case of a full reset.
Parameters
Time
Day
Time program
Day temp.
Boiler circuit
Mixer circuit 1
Mixer circuit 2
Mixer circuit 3
Mixer circuit 4
Mixer circuit 5
Mixer circuit 6
Mixer circuit 7
Setback temp. Boiler circuit
Mixer circuit 1
Mixer circuit 2
Mixer circuit 3
Mixer circuit 4
Mixer circuit 5
Mixer circuit 6
Mixer circuit 7
Heating curve Boiler circuit
Mixer circuit 1
Mixer circuit 2
Mixer circuit 3
Mixer circuit 4
Mixer circuit 5
Mixer circuit 6
Mixer circuit 7
Room influence Boiler circuit
Mixer circuit 1
Mixer circuit 2
Mixer circuit 3
Mixer circuit 4
Mixer circuit 5
Mixer circuit 6
Mixer circuit 7
Setting range
0 to 24 h
1 (Mon) to 7 (Sun)
1 / 2 / 3
5 to 30 °C
5 to 30 °C
5 to 30 °C
5 to 30 °C
5 to 30 °C
5 to 30 °C
5 to 30 °C
5 to 30 °C
5 to 30 °C
5 to 30 °C
5 to 30 °C
5 to 30 °C
5 to 30 °C
5 to 30 °C
5 to 30 °C
5 to 30 °C
0 to 3.0
0 to 3.0
0 to 3.0
0 to 3.0
0 to 3.0
0 to 3.0
0 to 3.0
0 to 3.0
ON / OFF
ON / OFF
ON / OFF
ON / OFF
ON / OFF
ON / OFF
ON / OFF
ON / OFF
For further parameters, see next page.
0.8
0.8
0.8
0.8
0.8
OFF
OFF
OFF
16 °C
16 °C
16 °C
16 °C
1.2
0.8
0.8
20 °C
20 °C
20 °C
20 °C
16 °C
16 °C
16 °C
16 °C
Factory setting
-
-
1
20 °C
20 °C
20 °C
20 °C
OFF
OFF
OFF
OFF
OFF
Individual setting
56 30 61 872_0407
Settings report
Standard settings parameters
Parameters
Summer/winter changeover
Boiler circuit
Mixer circuit 1
Mixer circuit 2
Mixer circuit 3
Mixer circuit 4
Mixer circuit 5
ECO/RED
Mixer circuit 6
Mixer circuit 7
Boiler circuit
Mixer circuit 1
Mixer circuit 2
Mixer circuit 3
Mixer circuit 4
Mixer circuit 5
Mixer circuit 6
Mixer circuit 7
DHW temperature
Freestanding boiler
Wall mounted boiler with cylinder
Wall mounted combi boiler
Language
Setting range
0 to 40 °C
0 to 40 °C
0 to 40 °C
0 to 40 °C
0 to 40 °C
0 to 40 °C
0 to 40 °C
0 to 40 °C
-10 to 40 °C
-10 to 40 °C
-10 to 40 °C
-10 to 40 °C
-10 to 40 °C
-10 to 40 °C
-10 to 40 °C
-10 to 40 °C
15 to 60 °C
15 to 65 °C
40 to 65 °C
German, English,
French, Dutch,
Spanish,
Portuguese,
Italian, Czech,
Polish, Slovakian,
Hungarian,
Russian,
Greek, Turkish
Factory setting
20 °C
20 °C
20 °C
20 °C
20 °C
20 °C
20 °C
20 °C
10 °C
10 °C
10 °C
10 °C
10 °C
10 °C
10 °C
10 °C
60 °C
60 °C
60 °C
German
Individual setting
30 61 872_0407 5 7
Settings report, time programs
Wolf recommends you complete the settings report carefully and to keep it safe to enable a quick solution to be found during service and in case of a full reset.
58
For further time programs, see next page.
30 61 872_0407
Time program
Block Switch.
Time prog. 1 Mo-Fr
time
1
Sa-Su
2
3
1
Time prog. 2 Mo-Fr
Sa-Su
3
1
2
1
2
2
3
Time prog. 3 MON
TUE
WED
THU
FRI
SAT
SUN
1
2
3
1
2
3
2
3
3
1
3
1
2
2
3
1
2
3
3
1
1
2
Mixer 5
ON OFF
Mixer 6
ON OFF
Mixer 7
ON OFF ON
DHW
OFF
DHW circ. line
ON OFF
Operating mode, boiler status / Settings report, system parameters
Operating mode
Boiler status
Boiler status
0
Standby
1
Emission test mode
2
Soft start
3
Heat demand (heating mode)
5
6
Heat demand with cycle block
Cycle block
7
Frost protection – heating
8
Soft start
11
DHW draw-off
12
DHW reheating
13
14
15
16
Minimum combi time
DHW quick start reheating
Cylinder mode
Frost protection – cylinder
17
Pump run-on – cylinder
18
Boil dry
19 dt output reduction
20
21
22
23
Parallel cylinder mode
Max. cylinder heating time exceeded
Sensor operating mode 2, contact closed
Sensor operating mode 3, contact closed
Wolf recommends you complete the settings report carefully and to keep it safe to enable a quick solution to be found during service and in case of a full reset.
Parameter
A00
Room influence
A01
Heat-up optimisation
A02
Max. heat-up time
A03
Required heat-up time
A04
Adjusted outside temp. sensor
A05
A06
Room sensor matching
External room temp. sensor
A07
Pasteurisation function
A08
A09
A10
A11
A12
A13
Service message
Frost protection level
Parallel DHW operation
Room temperature-dependent summer/winter changeover
Setback stop
Minimum DHW temp.
Setting range
1 to 20 K / K
0 / 1
0 to 180 min
-
0 to 24 h
-5 to +5 K
0 to 1
0 to 8
0 to 104 weeks
-20 to +10 °C
0 / 1
OFF / ON
OFF, -39 to 0°C
0 to 60 °C
Factory setting
4 K / K
0
0
-
3 h
0 K
1
0
0
+2 °C
0
ON
-16 °C
40 °C
Individual setting
-
60 30 61 872_0407
Sensor resistances
NTC
Sensor resistances
Temp.
°C
-13
-12
-11
-10
-9
-8
-21
-20
-19
-18
-17
-16
-15
-14
-7
-6
7
8
9
10
5
6
3
4
-1
0
1
2
-5
-4
-3
-2
11
12
13
Resist.
Ohm
51393
48487
45762
43207
40810
38560
36447
34463
32599
30846
29198
27648
26189
24816
23523
22305
21157
20075
19054
18091
17183
16325
15515
14750
14027
13344
12697
12086
11508
10961
10442
9952
9487
9046
8629
Temp.
°C
22
23
24
25
26
27
18
19
20
21
14
15
16
17
28
29
42
43
44
45
38
39
40
41
34
35
36
37
30
31
32
33
46
47
48
Boiler sensor, cylinder sensor, solar cylinder sensor, outside temperature sensor, flow sensor, central sensor
Resist.
Ohm
8233
7857
7501
7162
6841
6536
6247
5972
5710
5461
5225
5000
4786
4582
4388
4204
2887
2772
2662
2558
2458
2362
2271
2183
4028
3860
3701
3549
3403
3265
3133
3007
2100
2020
1944
Resist.
Ohm
1870
1800
1733
1669
1608
1549
1493
1438
1387
1337
1289
1244
1200
1158
1117
1078
791
765
740
716
693
670
649
628
1041
1005
971
938
906
876
846
818
608
589
570
Temp.
°C
57
58
59
60
61
62
53
54
55
56
49
50
51
52
63
64
77
78
79
80
73
74
75
76
69
70
71
72
65
66
67
68
81
82
83
Temp.
°C
92
93
94
95
96
97
88
89
90
91
84
85
86
87
98
99
108
109
110
111
112
113
114
115
100
101
102
103
104
105
106
107
116
117
118
Resist.
Ohm
431
418
406
393
382
371
552
535
519
503
487
472
458
444
360
349
270
262
255
248
241
235
228
222
339
330
320
311
302
294
285
277
216
211
205
30 61 872_0407 6 1
Fault messages
If a fault is indicated by the signal ring of the control unit flashing red, a fault code is displayed via the Wolf-control accessory with eBUS capability that allows a cause to be allocated using the following table.
This list of fault messages is designed to allow your heating contractor to trace the fault more easily.
Note: Faults that are not listed may be faults of the air-condition or ventilation control.
No.
Fault
1 TB excess temperature
4 No flame established
5 Flame failure during
Cause
The external temp. limiter has shut down the system.
No flame established during the burner start
Flame failure during the safety time
6 TW excess temperature The boiler water temp. has exceeded the limit for the TW (e.g. 95 °C)
7 STBA - excess temperature The temperature limiter has shut down the system
8 No flue gas damper response Flue gas damper or damper feedback faulty
11 False flame indication A flame is recognised before the burner starts
12 Boiler sensor faulty The boiler water temp. sensor or sensor lead is faulty
13 Flue gas temp. sensor faulty The flue gas sensor or sensor lead is faulty
14 Cylinder sensor faulty The DHW temp. sensor or sensor lead is faulty
15 Outside temperature sensor The outside temperature sensor is faulty (short faulty circuit or break, wireless reception interference, battery of the wireless outside temperature sensor dead), power supply boiler interrupted or boiler fuse blown / tripped
16 Return sensor faulty
17 Fault modulation current
20 Faulty gas valve V1
21 Faulty gas valve V2
The return sensor or the sensor lead is faulty
The modulation current is outside its set range
The gas valve is faulty
The gas valve is faulty
22 Lack of air
23 Faulty air pressure switch
24 Gas fan, fault
25
26
Gas fan, fault
Gas fan, fault
30 CRC fault, boiler
31 CRC fault, burner
32 Power failure 24 V
The air pressure switch does not switch ON
The air pressure switch does not switch OFF
The gas fan does not reach the required pre-purging speed
The fan does not reach the ignition speed
The fan does not stop
Internal device error
Internal device error
24 V power supply faulty
62 30 61 872_0407
Fault messages
No.
Fault
33 CRC fault, factory setting
34 CRC fault, BCC
35 BCC missing
Cause
Internal device error
Faulty boiler coding card
Boiler coding card was removed
36
37
CRC fault, BCC
Incorrect BCC
38 BCC no. invalid
39 BCC system error
Faulty boiler coding card
The boiler coding card is incompatible with the control unit PCB
Faulty boiler coding card
Faulty boiler coding card
40
41
Faulty flow limiter
Faulty flow limiter
The flow limiter does not switch OFF or ON
The return temperature is at least 12 K higher than the flow temperature
The cylinder heating takes longer than permitted 52 Max. cylinder heating time exceeded
60 Siphon back pressure The siphon or the flue gas system is blocked
61 Flue gas system back pressure The flue gas system is blocked
64 Pulse transducer faulty The pulse transducer of the solar module is faulty or the solar heating system has no circulation
70
71
Mixer circuit sensor faulty
Sensor faulty
72 Return sensor faulty
76 Cylinder sensor faulty
The mixer circuit sensor or the sensor lead is faulty
The cylinder sensor of the solar module or the multi-function sensor input E1 of the mixer module is faulty
The return sensor of the sensor module is faulty
The cylinder sensor or the sensor lead is faulty
78
79
Central sensor faulty
Sensor faulty
The central sensor or the sensor lead is faulty
The multi-function sensor input E1 of the boiler control units R1, R2, R3 or the multi-function sensor input E2 of the mixer module or the collector sensor of the solar moduleis faulty
80 Outside temperature sensor The outside temperature sensor or the sensor lead accessory controller is faulty at the accessory controller is faulty
81 EEPROM fault
82 Oil level fault
91 Fault eBUS parameter
97 Bypass pump faulty
Internal equipment error at the accessory controller
The oil tank is empty or check the oil level transducer
One BUS address was allocated more than once
The bypass pump of the mixer module is faulty
30 61 872_0407 6 3
Specification
Specification
Supply voltage: eBUS 15-24 V
Power consumption: Max. 0.5 W
Protection: Wall mounting base: IP 30
Boiler: as per control unit protection level
Battery backup:
Ambient temp.:
> 48 h
0....50 °C
Storage temperature: -20....+60 °C
Data memory: EEPROM (non-volatile)
Wolf GmbH · Postfach 1380 · D-84048 Mainburg · Tel. +49-8751/74-0 · Fax +49-8751/741600 · Internet: www.wolf-heiztechnik.de
64 30 61 872_0407
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 3 Safety instructions
- 4 Standards / Regulations
- 5 Installation / Wall mounting base installation
- 6 Electrical connection, remote control
- 6 Remote switching contact
- 7 Outside temperature sensor
- 8 Boiler integration
- 9 Integration into a gas fired boiler
- 10 Module installation
- 11 eBUS interface settings
- 12 Overview
- 12 Description l.h. / r.h. rotary selector
- 12 Symbol description
- 14 Function: Flue gas test / temperature selection
- 15 Info pushbutton
- 16 Single cylinder heating pushbutton
- 16 Heating pushbutton
- 16 Setback pushbutton
- 17 Display
- 19 Control level 2 – Summary
- 20 Standard settings
- 20 Parameters overview, standard settings
- 21 Time program
- 22 Day temperature
- 23 Setback temperature
- 24 Heating curve
- 26 Room influence
- 27 S/W changeover, subject to outside temp
- 29 ECO/RED
- 31 DHW temperature
- 31 Language
- 32 Pushbutton lock
- 35 Code scan
- 36 Overview, Contractor menu
- 37 Summary – system parameters
- 38 Room influence (A00)
- 39 Heat-up optimisation (A01)
- 39 Maximum heat-up time (A02)