TECHNICAL DATA

& SERVICE MANUAL

OUTDOOR UNIT: AER608SH

AER609SH

AER612SH

SPLIT SYSTEM AIR CONDITIONER

Model No.

AER608SH

AER609SH

AER612SH

Product Code No.

387007130

387007131

387007132

0.8180.261.0 05/2002

IMPORTANT!

Please read before installation

This air conditioning system meets strict safety and operating standards.

For the installer or service person, it is important to install or service the system so that it operates safely and efficiently.

For safe installation and trouble-free operation, you must:

• Carefully read this instruction booklet before beginning.

• Follow each installation or repair step exactly as shown.

• Observe all local, state and national electrical codes.

• Pay close attention to all warning and caution notices given in this manual.

•The unit must be supplied with a dedicated electrical line.

WARNING

This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.

CAUTION

This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.

If necessary, get help

These instructions are all you need for most installation sites and maintenance conditions.

If you require help for a special problem, contact our sale/service outlet or your certified dealer for additional instructions.

In case of improper installation

The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.

SPECIAL PRECAUTIONS

• During installation, connect before the refrigerant system and then the wiring one; proceed in the reverse orden when removing the units.

WARNING

When wiring

ELECTRICAL SHOCK CAN CAUSE SEVERE

PERSONAL INJURY OR DEATH. ONLY A QUALIFIED,

EXPERIENCED ELECTRICIANS SHOULD ATTEMPT

TO WIRE THIS SYSTEM.

• Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked, to ensure the grounding.

• Highly dangerous electrical voltages are used in this system.

Carefully refer to the wiring diagram and these instructions when wiring.

Improper connections and inadequate grounding can cause

accidental injury and death.

Ground the unit following local electrical codes.

• The Yellow/Green wire cannot be used for any connection different from the ground connection.

• Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.

• Do not allow wiring to touch the refrigerant tubing, compressor, or any moving parts of the fan.

• Do not use multi-core cable when wiring the power supply and control lines. Use separate cables for each type of line.

When transporting

Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminium fins on the air conditioner can cut your fingers.

When installing...

... In a ceiling or wall

Make sure the ceiling/wall is strong enough to hold the unit-weight.

It may be necessary to build a strong wooden or metal frame to provide added support.

... In a room

Properly insulate any tubing run inside a room to prevent

"sweating", which can cause dripping and water damage to walls and floors.

... In moist or uneven locations

Use a raised concrete base to provide a solid level foundation for the outdoor unit.

This prevents damage and abnormal vibrations.

... In area with strong winds

Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.

... In a snowy area (for heat pump-type systems)

Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.

When connecting refrigerant tubing

• Keep all tubing runs as short as possible.

• Use the flare method for connecting tubing.

• Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them; screw by hand and then tighten the nut with a torque wrench for a leak-free connection.

• Check carefully for leaks before starting the test run.

NOTE:

Depending on the system type, liquid and gas lines may be either narrow or wide. Therefore, to avoid confusion, the refrigerant tubing for your particular model is specified as narrow tube for liquid, wide tube for gas.

When servicing

• Turn the power OFF at the main power board before opening the unit to check or repair electrical parts and wiring.

• Keep your fingers and clothing away from any moving parts.

• Clean up the site after the work, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.

• Ventilate the room during the installation or testng the refrigeration system; make sure that, after the installation, no gas leaks are present, because this could produce toxic gas and dangerous if in contact with flames or heat-sources.

2

Table of Contents

1. OPERATING RANGE

2. SPECIFICATIONS

2-1 Unit specifications

2-2 Major Component specifications

2-3 Other Component specifications

3. DIMENSIONAL DATA

4. REFRIGERANT FLOW DIAGRAM

5. PERFORMANCE DATA

5-1 Performance Charts

5-2 Cooling Capacity

5-3 Heating Capacity

6. ELECTRICAL DATA

6-1 Electrical characteristics

6-2 Electric Wiring Diagram

6-3 System Wiring Diagram

13

15

15

18

21

22

22

25

25

Page

4

8

11

5

5

12

3

1. OPERATING RANGE

Cooling

Heating

Temperature

Maximum

Minimum

Maximum

Minimum

Indoor Air Intake Temp.

32°C D.B. / 23°C W.B.

19°C D.B. / 14°C W.B.

27°C D.B.

-

Outdoor Air Intake Temp.

43°C D.B.

19°C D.B.

24°C D.B. / 18°C W.B.

-8°C D.B. / -9°C W.B.

4

2. SPECIFICATIONS

2-1 Unit Specifications

AER608SH

Power source

Voltage rating

Performance *

Capacity

Air circulation (High)

Moisture removal (High)

Electrical Rating

Available voltage range

Running amperes

Power input

Power factor

C.O.P.

Compressor locked rotor amperes

AWR608HL

kW

BTU/h m³/h

Liters/h

W

%

V

A

W/W

A

Cooling

2,30

7843

220 - 240V ~ 50Hz

230V

Heating

2.65

9045

430

0,9

Cooling

-

Heating

198 ~ 264

4.0

890

97

2.6

20

4.0

860

94

3.1

20

Features

Fan speed

Compressor

Refrigerant / Amount charged at shipment

Refrigerant control

Operation Sound

Refrigerant tubing connections

Hi g dB-A

Max. allowable tubing length at shipment

Refrigerant tube diameter

Narrow tube

Wide tube m mm(in.) mm(in.)

Dimensions & Weight

Unit dimensions

Package dimensions

Weight

Shipping volume

Height

Width

Depth

Height

Width

Depth

Net

Shipping

43

1(Hi)

Rotary (Hermetic)

R407C / 770

Capillary tube

Flare type

7.5

6,35 (1/4)

9,52 (3/8)

45 mm mm mm mm mm

540

700

265

568

815 mm kg

343

35.0

kg m

3

38.0

0.16

DATA SUBJECT TO CHANGE WITHOUT NOTICE

Remarks:

Rating conditions are:

Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.

Outdoor air temperature 35°C D.B. / 24°C W.B.

Heating: Indoor air temperature 20°C D.B.

Outdoor air temperature 7°C D.B. / 6°C W.B.

* For other INDOOR UNITS' MODELS, please refer to catalogue

5

AER609SH

Power source

Voltage rating

220 - 240V ~ 50Hz

230V

Performance *

Capacity

Air circulation (High)

Moisture removal (High)

AWR609HL

kW

BTU/h m³/h

Liters/h

Cooling

2,50

8532

450

Heating

3.40

11604

1.1

Cooling

-

Heating

Electrical Rating

Available voltage range

Running amperes

Power input

Power factor

C.O.P.

Compressor locked rotor amperes

Features

Fan speed

Compressor

Refrigerant / Amount charged at shipment

Refrigerant control

Operation Sound

Refrigerant tubing connections

Hi g dB-A

Max. allowable tubing length at shipment

Refrigerant Narrow tube m mm(in.) tube diameter Wide tube mm(in.)

Dimensions & Weight

Unit dimensions

V

A

W

%

W/W

A

Package dimensions

Weight

Shipping volume

Height

Width

Depth

Height

Width

Depth

Net

Shipping

4.7

1040

96

2.4

24

43

198 ~ 264

1(Hi)

Rotary (Hermetic)

R407C / 990

Capillary tube

Flare type

7.5

6,35 (1/4)

9,52 (3/8)

4.7

1050

97

3.2

24

45 mm mm mm mm mm mm kg kg

540

700

265

568

815

343

35.0

38.0

m

3 0.16

DATA SUBJECT TO CHANGE WITHOUT NOTICE

Remarks:

Rating conditions are:

Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.

Outdoor air temperature 35°C D.B. / 24°C W.B.

Heating: Indoor air temperature 20°C D.B.

Outdoor air temperature 7°C D.B. / 6°C W.B.

* For other INDOOR UNITS' MODELS, please refer to catalogue

6

AER612SH

Power source

Voltage rating

220 - 240V ~ 50Hz

230V

Performance *

Capacity

Air circulation (High)

Moisture removal (High)

AWR612HL

kW

BTU/h m³/h

Liters/h

Cooling

3,10

10580

470

Heating

4.10

13993

1.5

Cooling

-

Heating

Electrical Rating

Available voltage range

Running amperes

Power input

Power factor

C.O.P.

Compressor locked rotor amperes

Features

Fan speed

Compressor

Refrigerant / Amount charged at shipment

Refrigerant control

Operation Sound

Refrigerant tubing connections

Hi g dB-A

Max. allowable tubing length at shipment

Refrigerant Narrow tube m mm(in.) tube diameter Wide tube mm(in.)

Dimensions & Weight

Unit dimensions

V

A

W

%

W/W

A

Package dimensions

Weight

Shipping volume

Height

Width

Depth

Height

Width

Depth

Net

Shipping

6.2

1300

91

2.4

33

45

198 ~ 264

1(Hi)

Rotary (Hermetic)

R407C / 1150

Capillary tube

Flare type

7.5

6,35 (1/4)

12,7 (1/2)

6.6

1400

92

2.9

33

47 mm mm mm mm mm mm kg kg

540

700

265

568

815

343

35.0

38.0

m

3 0.16

DATA SUBJECT TO CHANGE WITHOUT NOTICE

Remarks:

Rating conditions are:

Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.

Outdoor air temperature 35°C D.B. / 24°C W.B.

Heating: Indoor air temperature 20°C D.B.

Outdoor air temperature 7°C D.B. / 6°C W.B.

* For other INDOOR UNITS' MODELS, please refer to catalogue

7

2-2 Major Component Specifications

Outdoor Unit:

AER608SH

Compressor

Type

Compressor model

Nominal output

Compressor oil…Amount

Coil resistance (Ambient temp. 25°C)

Overload relay

Safety devices Type

Operating Temp. Open

Close

Run capacitor

Fan & Fan Motor

Type

Q'ty ……. Dia.

Fan motor model…Q'ty

No. Of poles…rpm (230 V, High)

Nominal output

Coil resistance (Ambient temp. 25 °C )

Safety devices Type

Operating temp. Open

Close

Run capacitor

Heat Exch. Coil

Coil

Rows

Fin pitch

Face area

External Finish

W cc.

°C

°C

µF

VAC

Rotary (Hermetic)

80225245F C-RN75H5A

750

FV68S…470

C-R: 3.38

C-S: 7.49

External (OLR T)

CS-7C115

115 ± 3

95 ± 5

20

400

W

°C

°C

µF

VAC

Propeller

1…. Ø 370

UE6-21ST5P…1

6…832

25.05

BRN-WHT: 242.4

WHT-YEL: 408.1

Thermal protector

130 ± 5

83 ± 15

1.5

450 mm m

2

Aluminium plate fin / Copper tube

1

1.3

0.353

Acrylic baked-on enamel finish

DATA SUBJECT TO CHANGE WITHOUT NOTICE

8

Outdoor Unit:

AER609SH

Compressor

Type

Compressor model

Nominal output

Compressor oil…Amount

Coil resistance (Ambient temp. 25°C)

Overload relay

Safety devices Type

Operating Temp. Open

Close

Run capacitor

W cc.

Heat Exch. Coil

Coil

Rows

Fin pitch

Face area

External Finish

°C

°C

µF

VAC

Fan & Fan Motor

Type

Q'ty ……. Dia.

Fan motor model…Q'ty

No. Of poles…rpm (230 V, High)

Nominal output

Coil resistance (Ambient temp. 25 °C )

Safety devices Type

Operating temp. Open

Close

Run capacitor

W

°C

°C

µF

VAC mm m

2

Rotary (Hermetic)

80228345 C-RN90H5B

900

FV68S…470

C-R: 3.07

C-S: 6.69

External (OLR T)

CS-7C115

115 ± 3

95 ± 5

25

400

Propeller

1…. Ø 370

UE6-21ST5P…1

6…832

25.05

BRN-WHT: 242.4

WHT-YEL: 408.1

Thermal protector

130 ± 5

83 ± 15

1.5

450

Aluminium plate fin / Copper tube

1

1.2

0.353

Acrylic baked-on enamel finish

9

Outdoor Unit:

AER612SH

Compressor

Type

Compressor model

Nominal output

Compressor oil…Amount

Coil resistance (Ambient temp. 25°C)

Overload relay

Safety devices Type

Operating Temp. Open

Close

Run capacitor

W cc.

Heat Exch. Coil

Coil

Rows

Fin pitch

Face area

External Finish

°C

°C

µF

VAC

Fan & Fan Motor

Type

Q'ty ……. Dia.

Fan motor model…Q'ty

No. Of poles…rpm (230 V, High)

Nominal output

Coil resistance (Ambient temp. 25 °C )

Safety devices Type

Operating temp. Open

Close

Run capacitor

W

°C

°C

µF

VAC mm m

2

Rotary (Hermetic)

80235645B C-RN110H5B

1100

FV68S…520

C-R: 1.962

C-S: 5.38

External (OLR T)

CS-7C115

115 ± 3

95 ± 5

25

400

Propeller

1…. Ø 370

UE6-21ST5P…1

6…832

25.05

BRN-WHT: 242.4

WHT-YEL: 408.1

Thermal protector

130 ± 5

83 ± 15

1.5

450

Aluminium plate fin / Copper tube

2

1.4

0.333

Acrylic baked-on enamel finish

10

2-3 Other Component Specifications

4-way Valve (20S)

Coil rating

Coil resistance Ω (at 20°C)

4-way Valve (20S)

Coil rating

Coil resistance

4-way Valve (20S)

Coil rating

Coil resistance

Ω (at 20°C)

Ω (at 20°C)

AER608SH

SRF-01AJ504D1 (Coil) STF-0101Z (Valve)

AC 220/240 V, 50 Hz, 6W

1402 ± 7%

AER609SH

SRF-01AJ504D1 (Coil) STF-0101Z (Valve)

AC 220/240 V, 50 Hz, 6W

1402 ± 7%

AER612SH

SRF-01AJ504D1 (Coil) STF-0201Z (Valve)

AC 220/240 V, 50 Hz, 6W

1402 ± 7%

11

3. DIMENSIONAL DATA

4 – ø12 holes

470

Air intake

116

Air discharge

700 10

Wide tube service valve

ø9.52 (3/8") 7000/9000 BTU/h

ø12.7 (1/2") 12000 BTU/h

Narrow tube service valve

ø6.35 (1/4")

255

170

Unit : mm

12

4. REFRIGERANT FLOW DIAGRAM

Indoor Unit: Outdoor Unit:

AER608SH

Indoor unit

Wide tube

Wide tube service valve

Muffler

O.D.

ø9.52 mm

(3/8 ")

Outdoor unit

Accumulator

4-way valve

Narrow tube

O.D.

ø6.35 mm

(1/4")

Narrow tube service valve

Capillary tube

Capillary tube

Strainer

Strainer

Check valve

Indoor Unit:

Indoor unit

Wide tube

Wide tube service valve

Muffler

O.D.

ø9.52 mm

(3/8 ")

Outdoor Unit:

Outdoor unit

Accumulator

AER609SH

4-way valve

Cooling cycle

Heating cycle

Narrow tube

Narrow tube service valve

Strainer

O.D.

ø6.35 mm

(1/4")

Capillary tube

Check valve

Capillary tube

Strainer

Cooling cycle

Heating cycle

13

Indoor Unit:

Indoor unit

Wide tube

Wide tube service valve

Outdoor Unit:

AER612SH

Outdoor unit

Accumulator

Muffler

4-way valve

O.D.

ø12.7 mm

(1/2 ")

Narrow tube

Narrow tube service valve

Accumulator

Capillary tube

O.D.

ø6.35 mm

(1/4")

Strainer

Check valve

Capillary

Strainer

Cooling cycle

Heating cycle

Insulation of Refrigerant Tubing

IMPORTANT

Because capillary tubing is used in the outdoor unit, both the wide and narrow tubes of this air conditioner become cold. To prevent heat loss and wet floors due to dripping of condensation, both tubes must be well insulated with a proper insulation material. The thickness of the insulation should be a min. 8 mm.

CAUTION

After a tube has been insulated, never try to bend it into a narrow curve because it can cause the tube to break or crack.

Thickness:

Min. 8 mm

Wide tube

Insulation

Thickness:

Min. 8 mm

Narrow tube

14

5. PERFORMANCE DATA

5-1 Performance charts

AER608SH

n Cooling Characteristics

3

2

1

20

6

5

4

11

10

9

8

7

Indoor inlet air

D.B. (°C)

32

27

19

25 30 35 40

Outdoor inlet air D.B. temp. (°C)

45 n Heating Characteristics

11

10

9

Indoor inlet air

D.B. (°C)

8

7

6

5

4

27

15

19

3

2

1

-10 -5 0 5

7

10 15 20

Outdoor inlet D.B. temp. (°C)

25

0,70

0,60

0,50

0,40

0,30

0,20

0,10

Indoor inlet air

D.B. (°C)

32

27

19

0,00

20 25 30 35

Outdoor inlet air D.B. (°C)

40 45

2,00

1,80

1,60

1,40

2,60

2,40

2,20

Indoor inlet air

D.B. (°C)

27

20

15

1,20

1,00

-10 -5 0 5

7

10 15

Outdoor inlet air D.B. (°C)

20 25

Notes:

Overload prevention operates to protect the air conditioner when outdoor ambient temperature reaches extremely high values in heating mode.

Points of Rating condition

Data referred to AWR608HL

15

AER609SH

n Cooling Characteristics

6

5

4

3

2

1

20

11

10

9

8

7

Indoor inlet air

D.B. (°C)

32

27

19

25 30 35 40

Outdoor inlet air D.B. temp. (°C)

45 n Heating Characteristics

11

10

9

8

7

4

3

6

5

Indoor inlet air

D.B. (°C)

27

32

15

27

19

2

1

-10 -5 0 5

7

10 15 20

Outdoor inlet D.B. temp. (°C)

25

0,60

0,50

0,40

0,30

0,20

0,10

Indoor inlet air

D.B. (°C)

32

27

19

0,00

20 25 30 35

Outdoor inlet air D.B. (°C)

40 45

2,40

2,20

2,00

1,80

1,60

1,40

Indoor inlet air

D.B. (°C)

27

20

15

1,20

1,00

-10 -5 0 5

7

10 15

Outdoor inlet air D.B. (°C)

20 25

Notes:

Overload prevention operates to protect the air conditioner when outdoor ambient temperature reaches extremely high values in heating mode.

Points of Rating condition

Data referred to AWR609HL

16

AER612SH

n Cooling Characteristics

6

5

4

3

2

1

20

11

10

9

8

7

Indoor inlet air

D.B. (°C)

25 30 35 40

Outdoor inlet air D.B. temp. (°C)

32

27

19

45 n Heating Characteristics

11

10

9

8

7

4

3

6

5

Indoor inlet air

D.B. (°C)

27

20

15

2

1

-10 -5 0 5

7

10 15 20

Outdoor inlet D.B. temp. (°C)

25

0,60

0,50

0,40

0,30

0,20

0,10

Indoor inlet air

D.B. (°C)

32

27

19

0,00

20 25 30 35

Outdoor inlet air D.B. (°C)

40 45

2,80

2,60

2,40

2,20

2,00

1,80

1,60

1,40

Indoor inlet air

D.B. (°C)

27

20

15

1,20

1,00

-10 -5 0 5

7

10 15

Outdoor inlet air D.B. (°C)

20 25

Notes:

Overload prevention operates to protect the air conditioner when outdoor ambient temperature reaches extremely high values in heating mode.

Points of Rating condition

Data referred to AWR612HL

17

5-2 Cooling Capacity

OUTDOOR UNIT:

INDOOR UNIT:

AER608SH

AWR608HL

220 - 240V ~ 50Hz

RATING CAPACITY

COMP. POWER INPUT

AIR FLOW RATE

EVAPORATOR

ENT.TEMP. °C

W.B.

TC:

15

17

19

21

23

SHC:

CM:

D.B.

21

23

25

27

29

31

21

23

25

27

29

31

SHC

TC

CM

SHC

SHC

SHC

TC

CM

SHC

SHC

SHC

SHC

SHC

SHC

SHC

SHC

TC

CM

21

23

25

27

29

31

23

25

27

29

31

25

27

29

31

SHC

SHC

SHC

SHC

SHC

TC

SHC

SHC

SHC

SHC

SHC

SHC

TC

CM

CM

SHC

SHC

SHC

SHC

TOTAL COOLING CAPACITY

SENSIBLE HEAT CAPACITY

COMPRESSOR INPUT

1,14

1,35

1,56

1,77

1,97

2,97

1,17

1,38

1,59

1,79

2,00

2,21

2,78

0,74

0,76

1,12

1,32

1,53

1,74

2,32

2,49

0,70

1,39

1,60

1,81

20

2,32

0,68

1,61

1,82

2,02

2,23

2,32

2,02

2,23

2,43

2,30 kW

0,802 kW

430 m³/h moisture removal max comp input

CONDENSER

OUTDOOR AMBIENT TEMP. °C

25

2,18

0,70

1,49

1,69

1,89

2,09

2,18

2,18

2,36

0,73

1,31

1,50

1,70

1,90

2,10

2,30

30

2,12

0,73

1,47

1,66

1,85

2,05

2,12

2,12

2,27

0,75

1,27

1,46

1,66

1,85

2,04

2,23

2,02

2,16

0,78

1,22

1,41

1,61

35

2,02

0,75

1,42

1,61

1,80

2,00

2,02

1,80

1,99

2,16

2,65

0,72

2,50

0,75

2,42

0,78

2,30

0,80

1,10

1,29

1,48

1,67

1,85

2,05

2,65

0,77

1,08

1,27

1,46

1,64

1,84

2,80

0,79

1,05

1,23

1,41

1,62 kW kW kW

1,05

1,24

1,43

1,62

1,82

2,71

1,06

1,26

1,45

1,64

1,83

2,03

2,56

0,80

0,82

1,02

1,21

1,40

1,60

1,00

1,19

1,38

1,58

1,77

2,56

1,01

1,21

1,40

1,67

1,78

1,98

2,44

0,82

0,85

0,96

1,15

1,35

1,54

RATING CONDITIONS

Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.

Outdoor air temperature 35°C D.B. / 24°C W.B.

NOTE: Data referred to AWR608HL

1,89

2,03

0,80

1,16

1,35

1,55

40

1,89

0,78

1,36

1,55

1,74

1,89

1,89

1,74

1,93

2,03

2,16

0,83

0,94

1,13

1,33

1,52

1,71

2,40

0,95

1,15

1,34

1,53

1,73

1,92

2,29

0,85

0,87

0,90

1,09

1,29

1,48

0,9 l/h

0,902 kW

1,75

1,87

0,83

1,09

1,28

1,47

43

1,75

0,81

1,29

1,48

1,67

1,75

1,75

1,67

1,86

1,87

1,99

0,85

0,87

1,06

1,25

1,45

1,64

2,23

0,88

1,08

1,27

1,46

1,65

1,85

2,11

0,88

0,90

0,84

1,03

1,23

1,42

18

OUTDOOR UNIT:

INDOOR UNIT:

AER609SH

AWR609HL

220 - 240V ~ 50Hz

RATING CAPACITY

COMP. POWER INPUT

AIR FLOW RATE

EVAPORATOR

ENT.TEMP. °C

W.B.

D.B.

TC:

SHC:

CM:

15

17

19

21

23

2,50 kW

0,963 kW

450 m³/h

21

23

25

27

29

31

21

23

25

27

29

31

TC

CM

SHC

SHC

SHC

SHC

SHC

SHC

TC

CM

SHC

SHC

SHC

SHC

SHC

SHC

21

23

25

27

29

31

TC

CM

SHC

SHC

SHC

SHC

SHC

SHC

TC

CM

SHC 23

25

27

29

31

SHC

SHC

SHC

SHC

TC

CM

1,47

1,70

1,92

2,14

3,23

0,85

25

27

29

SHC

SHC

SHC

1,21

1,44

1,67

31 SHC 1,89

TOTAL COOLING CAPACITY

SENSIBLE HEAT CAPACITY

COMPRESSOR INPUT

2,88

0,78

1,27

1,50

1,73

1,94

2,17

2,40

3,03

0,82

1,24

20

2,53

0,73

1,75

1,98

2,20

2,43

2,53

2,53

2,71

0,76

1,51

1,74

1,97

2,19

2,42

2,64

1,38

1,58

1,79

2,00

3,04

0,91

1,14

1,34

1,54

1,76

2,72

0,84

1,19

1,40

1,60

1,81

2,01

2,22

2,88

0,88

1,18 moisture removal max comp input

CONDENSER

OUTDOOR AMBIENT TEMP. °C

25 30 35

2,37

0,79

1,62

2,30

0,85

1,59

2,19

0,91

1,54

1,84

2,05

2,27

2,37

2,37

1,80

2,01

2,22

2,30

2,30

1,75

1,96

2,17

2,19

2,19

2,57

0,81

1,42

1,63

1,85

2,06

2,28

2,49

2,47

0,87

1,38

1,59

1,80

2,01

2,22

2,42

2,35

0,93

1,33

1,53

1,74

1,95

2,16

2,35 kW kW kW

2,63

0,90

1,15

1,36

1,57

1,78

1,99

2,20

2,78

0,94

1,14

1,34

1,55

1,76

1,97

2,95

0,97

1,10

1,31

1,52

1,73

1,29

1,50

1,71

1,92

2,78

1,02

1,04

1,25

1,46

1,67

2,50

0,96

1,10

1,31

1,52

1,73

1,93

2,15

2,65

0,99

1,08

RATING CONDITIONS

Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.

Outdoor air temperature 35°C D.B. / 24°C W.B.

NOTE: Data referred to AWR608HL

1,23

1,44

1,65

1,86

2,60

1,08

0,98

1,18

1,40

1,60

2,35

1,02

1,03

1,24

1,46

1,66

1,88

2,08

2,49

1,05

1,02

40

2,05

0,96

1,47

1,68

1,89

2,05

2,05

2,05

2,21

0,99

1,26

1,47

1,68

1,89

2,10

2,21

1,1 l/h

1,14 kW

1,15

1,36

1,57

1,78

2,42

1,14

0,91

1,12

1,33

1,54

2,16

1,08

0,96

1,17

1,38

1,59

1,79

2,01

2,29

1,11

0,94

43

1,90

1,02

1,40

1,61

1,82

1,90

1,90

1,90

2,03

1,05

1,18

1,39

1,60

1,81

2,02

2,03

19

OUTDOOR UNIT:

INDOOR UNIT:

AER612SH

AWR612HL

220 - 240V ~ 50Hz

RATING CAPACITY

COMP. POWER INPUT

AIR FLOW RATE

EVAPORATOR

ENT.TEMP. °C

W.B.

D.B.

TC:

SHC:

CM:

15

17

19

21

23

3,10 kW

1,206 kW

470 m³/h

21

23

25

27

29

31

21

23

25

27

29

31

SHC

SHC

SHC

SHC

SHC

TC

CM

TC

CM

SHC

SHC

SHC

SHC

SHC

SHC

TC

CM

SHC

21

23

25

27

29

31

23

25

27

29

31

25

27

29

SHC

SHC

SHC

SHC

SHC

SHC

TC

CM

SHC

SHC

SHC

SHC

SHC

TC

CM

SHC

SHC

SHC

1,57

1,86

2,14

2,41

2,65

4,00

1,06

1,50

1,78

2,07

31 SHC 2,35

TOTAL COOLING CAPACITY

SENSIBLE HEAT CAPACITY

COMPRESSOR INPUT

2,69

2,97

3,75

1,02

1,54

1,82

2,10

2,38

20

3,13

0,91

2,17

2,46

2,73

3,01

3,13

3,13

3,35

0,95

1,87

2,16

2,44

2,72

3,00

3,27

3,57

0,98

1,48

1,74

1,99

2,24

2,49

2,76

3,57

1,10

1,46

1,71

1,96

2,21

OUTDOOR AMBIENT TEMP. °C

25 30 35

2,94

0,99

2,01

2,85

1,06

1,97

2,72

1,13

1,91

2,28

2,54

2,81

2,94

2,94

3,18

1,02

1,76

2,24

2,49

2,76

2,85

2,85

3,06

1,10

1,71

2,17

2,43

2,69

2,72

2,72

2,91

1,17

1,64

2,48

3,77

1,14

1,41

1,66

1,91

2,18

2,03

2,30

2,56

2,83

3,09

3,37

1,06 moisture removal max comp input

CONDENSER kW kW kW

1,97

2,23

2,49

2,75

3,01

3,26

1,13

1,43

1,69

1,95

2,21

2,47

2,73

3,45

1,17

1,41

1,66

1,93

2,18

2,45

3,65

1,21

1,37

1,62

1,89

2,15

1,90

2,16

2,42

2,68

2,91

3,10

1,21

1,36

1,62

1,88

2,05

2,40

2,66

3,29

1,24

1,34

1,60

1,86

2,12

2,38

3,45

1,28

1,29

1,55

1,81

2,07

RATING CONDITIONS

Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.

Outdoor air temperature 35°C D.B. / 24°C W.B.

NOTE: Data referred to AWR608HL

1,28

1,54

1,81

2,06

2,33

2,58

3,09

1,32

1,26

1,52

1,79

2,04

2,30

3,23

1,35

1,21

1,47

1,73

1,99

1,82

2,08

2,34

2,60

2,74

2,91

1,28

40

2,55

1,21

1,83

2,09

2,35

2,55

2,55

2,55

2,74

1,24

1,56

1,5 l/h

1,426 kW

1,19

1,45

1,71

1,97

2,22

2,49

2,84

1,39

1,17

1,43

1,68

1,95

2,21

3,01

1,43

1,13

1,39

1,65

1,91

1,73

1,98

2,24

2,50

2,52

2,68

1,35

43

2,35

1,28

1,73

1,99

2,25

2,35

2,35

2,35

2,52

1,32

1,46

20

5-3 Heating Capacity

120

110

100

90

80

70

60

50

40

30

20

10

0

–8 –5 0 5

7

10 15

Outdoor temperature (

°

C D.B.)

NOTE

1) … Point of Rating condition

Black dot in the chart indicate the following rating condition.

Indoor : 20

°

C D.B.

Outdoor : 7

°

C D.B. / 6

°

C W.B.

2) Above characteristics indicate instantaneous operation, which does not take into consideration defrost operation.

3) Fan speed : High

4) Because this air conditioner heats a room by drawing in the heat of the outside air (heat pump system), the heating efficiency will fall off when the outdoor temperature is very low. If sufficient heat cannot be obtained with this air conditioner, use another heating appliance in conjunction with it.

NOTE: Data referred to Hi-Wall models AWR608HL

AWR609HL

AWR612HL

21

6. ELECTRICAL DATA

6-1 Electrical characteristics

OUTDOOR UNIT:

AER608SH

COOLING performance at

Rating conditions Running Amps.

Power input

Full load conditions Running Amps.

Power input

A

Kw

A

Kw

Indoor Unit

Fan Motor

0,11

0,025

0,11

0,025

Outdoor unit

Fan Motor Compressor

230V 1-Phase 50 Hz

0,28

0,063

0,28

0,063

Rating Conditions: Indoor Air Temperature 27°C D.B. / 19°C W.B.

Outdoor Air Temperature 35°C D.B.

Full Load Conditions: Indoor Air Temperature 32°C D.B. / 23°C W.B.

Outdoor Air Temperature 43°C D.B.

3,61

0,802

4,11

0,902

HEATING performance at

Rating conditions Running Amps.

Power input

Full load conditions Running Amps.

Power input

A

Kw

A

Kw

Indoor Unit

Fan Motor

0,11

0,025

0,11

0,025

230V 1-Phase 50 Hz

0,28

0,063

0,28

NOTE: Data referred to indoor unit AWR608HL model.

For other indoor unit models there could be some differences.

Outdoor unit

Fan Motor

0,063

Rating Conditions: Indoor Air Temperature 20°C D.B.

Outdoor Air Temperature 7°C D.B. / 6°C W.B.

Full Load Conditions: Indoor Air Temperature 27°C D.B.

Outdoor Air Temperature 24°C D.B. / 18°C W.B.

Compressor

3,61

0,772

3,91

0,812

Complete Unit

4,0

0,890

4,5

0,990

Complete Unit

4,0

0,860

4,3

0,900

22

OUTDOOR UNIT:

AER609SH

COOLING performance at

Rating conditions Running Amps.

Power input

Full load conditions Running Amps.

Power input

A

Kw

A

Kw

Indoor Unit

Fan Motor

0,12

0,027

0,12

0,027

Outdoor unit

Fan Motor Compressor

230V 1-Phase 50 Hz

0,28

0,063

0,28

0,063

Rating Conditions: Indoor Air Temperature 27°C D.B. / 19°C W.B.

Outdoor Air Temperature 35°C D.B.

Full Load Conditions: Indoor Air Temperature 32°C D.B. / 23°C W.B.

Outdoor Air Temperature 43°C D.B.

4,3

0,963

5,1

1,140

HEATING performance at

Rating conditions Running Amps.

Power input

Full load conditions Running Amps.

Power input

A

Kw

A

Kw

Indoor Unit

Fan Motor

0,12

0,027

0,12

0,027

230V 1-Phase 50 Hz

0,28

0,063

0,28

NOTE: Data referred to indoor unit AWR609HL model.

For other indoor unit models there could be some differences.

Outdoor unit

Fan Motor

0,063

Rating Conditions: Indoor Air Temperature 20°C D.B.

Outdoor Air Temperature 7°C D.B. / 6°C W.B.

Full Load Conditions: Indoor Air Temperature 27°C D.B.

Outdoor Air Temperature 24°C D.B. / 18°C W.B.

Compressor

4,3

0,973

4,8

1,080

Complete Unit

4,7

1,040

5,5

1,230

Complete Unit

4,7

1,050

5,2

1,170

23

OUTDOOR UNIT:

AER612SH

COOLING performance at

Rating conditions Running Amps.

Power input

Full load conditions Running Amps.

Power input

A

Kw

A

Kw

Indoor Unit

Fan Motor

0,13

0,031

0,13

0,031

Outdoor unit

Fan Motor Compressor

230V 1-Phase 50 Hz

0,28

0,063

0,28

0,063

Rating Conditions: Indoor Air Temperature 27°C D.B. / 19°C W.B.

Outdoor Air Temperature 35°C D.B.

Full Load Conditions: Indoor Air Temperature 32°C D.B. / 23°C W.B.

Outdoor Air Temperature 43°C D.B.

5,79

1,206

6,79

1,426

HEATING performance at

Rating conditions Running Amps.

Power input

Full load conditions Running Amps.

Power input

A

Kw

A

Kw

Indoor Unit

Fan Motor

0,13

0,031

0,13

0,031

230V 1-Phase 50 Hz

0,28

0,063

0,28

NOTE: Data referred to indoor unit AWR612HL model.

For other indoor unit models there could be some differences.

Outdoor unit

Fan Motor

0,063

Rating Conditions: Indoor Air Temperature 20°C D.B.

Outdoor Air Temperature 7°C D.B. / 6°C W.B.

Full Load Conditions: Indoor Air Temperature 27°C D.B.

Outdoor Air Temperature 24°C D.B. / 18°C W.B.

Compressor

6,19

1,306

6,89

1,346

Complete Unit

6,2

1,300

7,2

1,520

Complete Unit

6,6

1,400

7,3

1,440

24

6-2 Electric Wiring Diagram

6-3 System Wiring Diagram

25

Via Varese, 90 - 21013 Gallarate - Va - Italy

Tel. +39 0331 755111 - Fax +39 0331 776240 www.argoclima.it