TECHNICAL DATA
& SERVICE MANUAL
OUTDOOR UNIT: AER608SH
AER609SH
AER612SH
SPLIT SYSTEM AIR CONDITIONER
Model No.
AER608SH
AER609SH
AER612SH
Product Code No.
387007130
387007131
387007132
0.8180.261.0 05/2002
IMPORTANT!
Please read before installation
This air conditioning system meets strict safety and operating standards.
For the installer or service person, it is important to install or service the system so that it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
• Carefully read this instruction booklet before beginning.
• Follow each installation or repair step exactly as shown.
• Observe all local, state and national electrical codes.
• Pay close attention to all warning and caution notices given in this manual.
•The unit must be supplied with a dedicated electrical line.
WARNING
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
CAUTION
This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.
If necessary, get help
These instructions are all you need for most installation sites and maintenance conditions.
If you require help for a special problem, contact our sale/service outlet or your certified dealer for additional instructions.
In case of improper installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
• During installation, connect before the refrigerant system and then the wiring one; proceed in the reverse orden when removing the units.
WARNING
When wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE
PERSONAL INJURY OR DEATH. ONLY A QUALIFIED,
EXPERIENCED ELECTRICIANS SHOULD ATTEMPT
TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked, to ensure the grounding.
• Highly dangerous electrical voltages are used in this system.
Carefully refer to the wiring diagram and these instructions when wiring.
Improper connections and inadequate grounding can cause
accidental injury and death.
• Ground the unit following local electrical codes.
• The Yellow/Green wire cannot be used for any connection different from the ground connection.
• Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.
• Do not allow wiring to touch the refrigerant tubing, compressor, or any moving parts of the fan.
• Do not use multi-core cable when wiring the power supply and control lines. Use separate cables for each type of line.
When transporting
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminium fins on the air conditioner can cut your fingers.
When installing...
... In a ceiling or wall
Make sure the ceiling/wall is strong enough to hold the unit-weight.
It may be necessary to build a strong wooden or metal frame to provide added support.
... In a room
Properly insulate any tubing run inside a room to prevent
"sweating", which can cause dripping and water damage to walls and floors.
... In moist or uneven locations
Use a raised concrete base to provide a solid level foundation for the outdoor unit.
This prevents damage and abnormal vibrations.
... In area with strong winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
... In a snowy area (for heat pump-type systems)
Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.
When connecting refrigerant tubing
• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them; screw by hand and then tighten the nut with a torque wrench for a leak-free connection.
• Check carefully for leaks before starting the test run.
NOTE:
Depending on the system type, liquid and gas lines may be either narrow or wide. Therefore, to avoid confusion, the refrigerant tubing for your particular model is specified as narrow tube for liquid, wide tube for gas.
When servicing
• Turn the power OFF at the main power board before opening the unit to check or repair electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after the work, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.
• Ventilate the room during the installation or testng the refrigeration system; make sure that, after the installation, no gas leaks are present, because this could produce toxic gas and dangerous if in contact with flames or heat-sources.
2
Table of Contents
1. OPERATING RANGE
2. SPECIFICATIONS
2-1 Unit specifications
2-2 Major Component specifications
2-3 Other Component specifications
3. DIMENSIONAL DATA
4. REFRIGERANT FLOW DIAGRAM
5. PERFORMANCE DATA
5-1 Performance Charts
5-2 Cooling Capacity
5-3 Heating Capacity
6. ELECTRICAL DATA
6-1 Electrical characteristics
6-2 Electric Wiring Diagram
6-3 System Wiring Diagram
13
15
15
18
21
22
22
25
25
Page
4
8
11
5
5
12
3
1. OPERATING RANGE
Cooling
Heating
Temperature
Maximum
Minimum
Maximum
Minimum
Indoor Air Intake Temp.
32°C D.B. / 23°C W.B.
19°C D.B. / 14°C W.B.
27°C D.B.
-
Outdoor Air Intake Temp.
43°C D.B.
19°C D.B.
24°C D.B. / 18°C W.B.
-8°C D.B. / -9°C W.B.
4
2. SPECIFICATIONS
2-1 Unit Specifications
AER608SH
Power source
Voltage rating
Performance *
Capacity
Air circulation (High)
Moisture removal (High)
Electrical Rating
Available voltage range
Running amperes
Power input
Power factor
C.O.P.
Compressor locked rotor amperes
AWR608HL
kW
BTU/h m³/h
Liters/h
W
%
V
A
W/W
A
Cooling
2,30
7843
220 - 240V ~ 50Hz
230V
Heating
2.65
9045
430
0,9
Cooling
-
Heating
198 ~ 264
4.0
890
97
2.6
20
4.0
860
94
3.1
20
Features
Fan speed
Compressor
Refrigerant / Amount charged at shipment
Refrigerant control
Operation Sound
Refrigerant tubing connections
Hi g dB-A
Max. allowable tubing length at shipment
Refrigerant tube diameter
Narrow tube
Wide tube m mm(in.) mm(in.)
Dimensions & Weight
Unit dimensions
Package dimensions
Weight
Shipping volume
Height
Width
Depth
Height
Width
Depth
Net
Shipping
43
1(Hi)
Rotary (Hermetic)
R407C / 770
Capillary tube
Flare type
7.5
6,35 (1/4)
9,52 (3/8)
45 mm mm mm mm mm
540
700
265
568
815 mm kg
343
35.0
kg m
3
38.0
0.16
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Remarks:
Rating conditions are:
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
Heating: Indoor air temperature 20°C D.B.
Outdoor air temperature 7°C D.B. / 6°C W.B.
* For other INDOOR UNITS' MODELS, please refer to catalogue
5
AER609SH
Power source
Voltage rating
220 - 240V ~ 50Hz
230V
Performance *
Capacity
Air circulation (High)
Moisture removal (High)
AWR609HL
kW
BTU/h m³/h
Liters/h
Cooling
2,50
8532
450
Heating
3.40
11604
1.1
Cooling
-
Heating
Electrical Rating
Available voltage range
Running amperes
Power input
Power factor
C.O.P.
Compressor locked rotor amperes
Features
Fan speed
Compressor
Refrigerant / Amount charged at shipment
Refrigerant control
Operation Sound
Refrigerant tubing connections
Hi g dB-A
Max. allowable tubing length at shipment
Refrigerant Narrow tube m mm(in.) tube diameter Wide tube mm(in.)
Dimensions & Weight
Unit dimensions
V
A
W
%
W/W
A
Package dimensions
Weight
Shipping volume
Height
Width
Depth
Height
Width
Depth
Net
Shipping
4.7
1040
96
2.4
24
43
198 ~ 264
1(Hi)
Rotary (Hermetic)
R407C / 990
Capillary tube
Flare type
7.5
6,35 (1/4)
9,52 (3/8)
4.7
1050
97
3.2
24
45 mm mm mm mm mm mm kg kg
540
700
265
568
815
343
35.0
38.0
m
3 0.16
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Remarks:
Rating conditions are:
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
Heating: Indoor air temperature 20°C D.B.
Outdoor air temperature 7°C D.B. / 6°C W.B.
* For other INDOOR UNITS' MODELS, please refer to catalogue
6
AER612SH
Power source
Voltage rating
220 - 240V ~ 50Hz
230V
Performance *
Capacity
Air circulation (High)
Moisture removal (High)
AWR612HL
kW
BTU/h m³/h
Liters/h
Cooling
3,10
10580
470
Heating
4.10
13993
1.5
Cooling
-
Heating
Electrical Rating
Available voltage range
Running amperes
Power input
Power factor
C.O.P.
Compressor locked rotor amperes
Features
Fan speed
Compressor
Refrigerant / Amount charged at shipment
Refrigerant control
Operation Sound
Refrigerant tubing connections
Hi g dB-A
Max. allowable tubing length at shipment
Refrigerant Narrow tube m mm(in.) tube diameter Wide tube mm(in.)
Dimensions & Weight
Unit dimensions
V
A
W
%
W/W
A
Package dimensions
Weight
Shipping volume
Height
Width
Depth
Height
Width
Depth
Net
Shipping
6.2
1300
91
2.4
33
45
198 ~ 264
1(Hi)
Rotary (Hermetic)
R407C / 1150
Capillary tube
Flare type
7.5
6,35 (1/4)
12,7 (1/2)
6.6
1400
92
2.9
33
47 mm mm mm mm mm mm kg kg
540
700
265
568
815
343
35.0
38.0
m
3 0.16
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Remarks:
Rating conditions are:
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
Heating: Indoor air temperature 20°C D.B.
Outdoor air temperature 7°C D.B. / 6°C W.B.
* For other INDOOR UNITS' MODELS, please refer to catalogue
7
2-2 Major Component Specifications
Outdoor Unit:
AER608SH
Compressor
Type
Compressor model
Nominal output
Compressor oil…Amount
Coil resistance (Ambient temp. 25°C)
Overload relay
Safety devices Type
Operating Temp. Open
Close
Run capacitor
Fan & Fan Motor
Type
Q'ty ……. Dia.
Fan motor model…Q'ty
No. Of poles…rpm (230 V, High)
Nominal output
Coil resistance (Ambient temp. 25 °C )
Safety devices Type
Operating temp. Open
Close
Run capacitor
Heat Exch. Coil
Coil
Rows
Fin pitch
Face area
External Finish
W cc.
Ω
°C
°C
µF
VAC
Rotary (Hermetic)
80225245F C-RN75H5A
750
FV68S…470
C-R: 3.38
C-S: 7.49
External (OLR T)
CS-7C115
115 ± 3
95 ± 5
20
400
W
Ω
°C
°C
µF
VAC
Propeller
1…. Ø 370
UE6-21ST5P…1
6…832
25.05
BRN-WHT: 242.4
WHT-YEL: 408.1
Thermal protector
130 ± 5
83 ± 15
1.5
450 mm m
2
Aluminium plate fin / Copper tube
1
1.3
0.353
Acrylic baked-on enamel finish
DATA SUBJECT TO CHANGE WITHOUT NOTICE
8
Outdoor Unit:
AER609SH
Compressor
Type
Compressor model
Nominal output
Compressor oil…Amount
Coil resistance (Ambient temp. 25°C)
Overload relay
Safety devices Type
Operating Temp. Open
Close
Run capacitor
W cc.
Ω
Heat Exch. Coil
Coil
Rows
Fin pitch
Face area
External Finish
°C
°C
µF
VAC
Fan & Fan Motor
Type
Q'ty ……. Dia.
Fan motor model…Q'ty
No. Of poles…rpm (230 V, High)
Nominal output
Coil resistance (Ambient temp. 25 °C )
Safety devices Type
Operating temp. Open
Close
Run capacitor
W
Ω
°C
°C
µF
VAC mm m
2
Rotary (Hermetic)
80228345 C-RN90H5B
900
FV68S…470
C-R: 3.07
C-S: 6.69
External (OLR T)
CS-7C115
115 ± 3
95 ± 5
25
400
Propeller
1…. Ø 370
UE6-21ST5P…1
6…832
25.05
BRN-WHT: 242.4
WHT-YEL: 408.1
Thermal protector
130 ± 5
83 ± 15
1.5
450
Aluminium plate fin / Copper tube
1
1.2
0.353
Acrylic baked-on enamel finish
9
Outdoor Unit:
AER612SH
Compressor
Type
Compressor model
Nominal output
Compressor oil…Amount
Coil resistance (Ambient temp. 25°C)
Overload relay
Safety devices Type
Operating Temp. Open
Close
Run capacitor
W cc.
Ω
Heat Exch. Coil
Coil
Rows
Fin pitch
Face area
External Finish
°C
°C
µF
VAC
Fan & Fan Motor
Type
Q'ty ……. Dia.
Fan motor model…Q'ty
No. Of poles…rpm (230 V, High)
Nominal output
Coil resistance (Ambient temp. 25 °C )
Safety devices Type
Operating temp. Open
Close
Run capacitor
W
Ω
°C
°C
µF
VAC mm m
2
Rotary (Hermetic)
80235645B C-RN110H5B
1100
FV68S…520
C-R: 1.962
C-S: 5.38
External (OLR T)
CS-7C115
115 ± 3
95 ± 5
25
400
Propeller
1…. Ø 370
UE6-21ST5P…1
6…832
25.05
BRN-WHT: 242.4
WHT-YEL: 408.1
Thermal protector
130 ± 5
83 ± 15
1.5
450
Aluminium plate fin / Copper tube
2
1.4
0.333
Acrylic baked-on enamel finish
10
2-3 Other Component Specifications
4-way Valve (20S)
Coil rating
Coil resistance Ω (at 20°C)
4-way Valve (20S)
Coil rating
Coil resistance
4-way Valve (20S)
Coil rating
Coil resistance
Ω (at 20°C)
Ω (at 20°C)
AER608SH
SRF-01AJ504D1 (Coil) STF-0101Z (Valve)
AC 220/240 V, 50 Hz, 6W
1402 ± 7%
AER609SH
SRF-01AJ504D1 (Coil) STF-0101Z (Valve)
AC 220/240 V, 50 Hz, 6W
1402 ± 7%
AER612SH
SRF-01AJ504D1 (Coil) STF-0201Z (Valve)
AC 220/240 V, 50 Hz, 6W
1402 ± 7%
11
3. DIMENSIONAL DATA
4 – ø12 holes
470
Air intake
116
Air discharge
700 10
Wide tube service valve
ø9.52 (3/8") 7000/9000 BTU/h
ø12.7 (1/2") 12000 BTU/h
Narrow tube service valve
ø6.35 (1/4")
255
170
Unit : mm
12
4. REFRIGERANT FLOW DIAGRAM
Indoor Unit: Outdoor Unit:
AER608SH
Indoor unit
Wide tube
Wide tube service valve
Muffler
O.D.
ø9.52 mm
(3/8 ")
Outdoor unit
Accumulator
4-way valve
Narrow tube
O.D.
ø6.35 mm
(1/4")
Narrow tube service valve
Capillary tube
Capillary tube
Strainer
Strainer
Check valve
Indoor Unit:
Indoor unit
Wide tube
Wide tube service valve
Muffler
O.D.
ø9.52 mm
(3/8 ")
Outdoor Unit:
Outdoor unit
Accumulator
AER609SH
4-way valve
Cooling cycle
Heating cycle
Narrow tube
Narrow tube service valve
Strainer
O.D.
ø6.35 mm
(1/4")
Capillary tube
Check valve
Capillary tube
Strainer
Cooling cycle
Heating cycle
13
Indoor Unit:
Indoor unit
Wide tube
Wide tube service valve
Outdoor Unit:
AER612SH
Outdoor unit
Accumulator
Muffler
4-way valve
O.D.
ø12.7 mm
(1/2 ")
Narrow tube
Narrow tube service valve
Accumulator
Capillary tube
O.D.
ø6.35 mm
(1/4")
Strainer
Check valve
Capillary
Strainer
Cooling cycle
Heating cycle
Insulation of Refrigerant Tubing
IMPORTANT
Because capillary tubing is used in the outdoor unit, both the wide and narrow tubes of this air conditioner become cold. To prevent heat loss and wet floors due to dripping of condensation, both tubes must be well insulated with a proper insulation material. The thickness of the insulation should be a min. 8 mm.
CAUTION
After a tube has been insulated, never try to bend it into a narrow curve because it can cause the tube to break or crack.
Thickness:
Min. 8 mm
Wide tube
Insulation
Thickness:
Min. 8 mm
Narrow tube
14
5. PERFORMANCE DATA
5-1 Performance charts
AER608SH
n Cooling Characteristics
3
2
1
20
6
5
4
11
10
9
8
7
Indoor inlet air
D.B. (°C)
32
27
19
25 30 35 40
Outdoor inlet air D.B. temp. (°C)
45 n Heating Characteristics
11
10
9
Indoor inlet air
D.B. (°C)
8
7
6
5
4
27
15
19
3
2
1
-10 -5 0 5
7
10 15 20
Outdoor inlet D.B. temp. (°C)
25
0,70
0,60
0,50
0,40
0,30
0,20
0,10
Indoor inlet air
D.B. (°C)
32
27
19
0,00
20 25 30 35
Outdoor inlet air D.B. (°C)
40 45
2,00
1,80
1,60
1,40
2,60
2,40
2,20
Indoor inlet air
D.B. (°C)
27
20
15
1,20
1,00
-10 -5 0 5
7
10 15
Outdoor inlet air D.B. (°C)
20 25
Notes:
Overload prevention operates to protect the air conditioner when outdoor ambient temperature reaches extremely high values in heating mode.
Points of Rating condition
Data referred to AWR608HL
15
AER609SH
n Cooling Characteristics
6
5
4
3
2
1
20
11
10
9
8
7
Indoor inlet air
D.B. (°C)
32
27
19
25 30 35 40
Outdoor inlet air D.B. temp. (°C)
45 n Heating Characteristics
11
10
9
8
7
4
3
6
5
Indoor inlet air
D.B. (°C)
27
32
15
27
19
2
1
-10 -5 0 5
7
10 15 20
Outdoor inlet D.B. temp. (°C)
25
0,60
0,50
0,40
0,30
0,20
0,10
Indoor inlet air
D.B. (°C)
32
27
19
0,00
20 25 30 35
Outdoor inlet air D.B. (°C)
40 45
2,40
2,20
2,00
1,80
1,60
1,40
Indoor inlet air
D.B. (°C)
27
20
15
1,20
1,00
-10 -5 0 5
7
10 15
Outdoor inlet air D.B. (°C)
20 25
Notes:
Overload prevention operates to protect the air conditioner when outdoor ambient temperature reaches extremely high values in heating mode.
Points of Rating condition
Data referred to AWR609HL
16
AER612SH
n Cooling Characteristics
6
5
4
3
2
1
20
11
10
9
8
7
Indoor inlet air
D.B. (°C)
25 30 35 40
Outdoor inlet air D.B. temp. (°C)
32
27
19
45 n Heating Characteristics
11
10
9
8
7
4
3
6
5
Indoor inlet air
D.B. (°C)
27
20
15
2
1
-10 -5 0 5
7
10 15 20
Outdoor inlet D.B. temp. (°C)
25
0,60
0,50
0,40
0,30
0,20
0,10
Indoor inlet air
D.B. (°C)
32
27
19
0,00
20 25 30 35
Outdoor inlet air D.B. (°C)
40 45
2,80
2,60
2,40
2,20
2,00
1,80
1,60
1,40
Indoor inlet air
D.B. (°C)
27
20
15
1,20
1,00
-10 -5 0 5
7
10 15
Outdoor inlet air D.B. (°C)
20 25
Notes:
Overload prevention operates to protect the air conditioner when outdoor ambient temperature reaches extremely high values in heating mode.
Points of Rating condition
Data referred to AWR612HL
17
5-2 Cooling Capacity
OUTDOOR UNIT:
INDOOR UNIT:
AER608SH
AWR608HL
220 - 240V ~ 50Hz
RATING CAPACITY
COMP. POWER INPUT
AIR FLOW RATE
EVAPORATOR
ENT.TEMP. °C
W.B.
TC:
15
17
19
21
23
SHC:
CM:
D.B.
21
23
25
27
29
31
21
23
25
27
29
31
SHC
TC
CM
SHC
SHC
SHC
TC
CM
SHC
SHC
SHC
SHC
SHC
SHC
SHC
SHC
TC
CM
21
23
25
27
29
31
23
25
27
29
31
25
27
29
31
SHC
SHC
SHC
SHC
SHC
TC
SHC
SHC
SHC
SHC
SHC
SHC
TC
CM
CM
SHC
SHC
SHC
SHC
TOTAL COOLING CAPACITY
SENSIBLE HEAT CAPACITY
COMPRESSOR INPUT
1,14
1,35
1,56
1,77
1,97
2,97
1,17
1,38
1,59
1,79
2,00
2,21
2,78
0,74
0,76
1,12
1,32
1,53
1,74
2,32
2,49
0,70
1,39
1,60
1,81
20
2,32
0,68
1,61
1,82
2,02
2,23
2,32
2,02
2,23
2,43
2,30 kW
0,802 kW
430 m³/h moisture removal max comp input
CONDENSER
OUTDOOR AMBIENT TEMP. °C
25
2,18
0,70
1,49
1,69
1,89
2,09
2,18
2,18
2,36
0,73
1,31
1,50
1,70
1,90
2,10
2,30
30
2,12
0,73
1,47
1,66
1,85
2,05
2,12
2,12
2,27
0,75
1,27
1,46
1,66
1,85
2,04
2,23
2,02
2,16
0,78
1,22
1,41
1,61
35
2,02
0,75
1,42
1,61
1,80
2,00
2,02
1,80
1,99
2,16
2,65
0,72
2,50
0,75
2,42
0,78
2,30
0,80
1,10
1,29
1,48
1,67
1,85
2,05
2,65
0,77
1,08
1,27
1,46
1,64
1,84
2,80
0,79
1,05
1,23
1,41
1,62 kW kW kW
1,05
1,24
1,43
1,62
1,82
2,71
1,06
1,26
1,45
1,64
1,83
2,03
2,56
0,80
0,82
1,02
1,21
1,40
1,60
1,00
1,19
1,38
1,58
1,77
2,56
1,01
1,21
1,40
1,67
1,78
1,98
2,44
0,82
0,85
0,96
1,15
1,35
1,54
RATING CONDITIONS
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
NOTE: Data referred to AWR608HL
1,89
2,03
0,80
1,16
1,35
1,55
40
1,89
0,78
1,36
1,55
1,74
1,89
1,89
1,74
1,93
2,03
2,16
0,83
0,94
1,13
1,33
1,52
1,71
2,40
0,95
1,15
1,34
1,53
1,73
1,92
2,29
0,85
0,87
0,90
1,09
1,29
1,48
0,9 l/h
0,902 kW
1,75
1,87
0,83
1,09
1,28
1,47
43
1,75
0,81
1,29
1,48
1,67
1,75
1,75
1,67
1,86
1,87
1,99
0,85
0,87
1,06
1,25
1,45
1,64
2,23
0,88
1,08
1,27
1,46
1,65
1,85
2,11
0,88
0,90
0,84
1,03
1,23
1,42
18
OUTDOOR UNIT:
INDOOR UNIT:
AER609SH
AWR609HL
220 - 240V ~ 50Hz
RATING CAPACITY
COMP. POWER INPUT
AIR FLOW RATE
EVAPORATOR
ENT.TEMP. °C
W.B.
D.B.
TC:
SHC:
CM:
15
17
19
21
23
2,50 kW
0,963 kW
450 m³/h
21
23
25
27
29
31
21
23
25
27
29
31
TC
CM
SHC
SHC
SHC
SHC
SHC
SHC
TC
CM
SHC
SHC
SHC
SHC
SHC
SHC
21
23
25
27
29
31
TC
CM
SHC
SHC
SHC
SHC
SHC
SHC
TC
CM
SHC 23
25
27
29
31
SHC
SHC
SHC
SHC
TC
CM
1,47
1,70
1,92
2,14
3,23
0,85
25
27
29
SHC
SHC
SHC
1,21
1,44
1,67
31 SHC 1,89
TOTAL COOLING CAPACITY
SENSIBLE HEAT CAPACITY
COMPRESSOR INPUT
2,88
0,78
1,27
1,50
1,73
1,94
2,17
2,40
3,03
0,82
1,24
20
2,53
0,73
1,75
1,98
2,20
2,43
2,53
2,53
2,71
0,76
1,51
1,74
1,97
2,19
2,42
2,64
1,38
1,58
1,79
2,00
3,04
0,91
1,14
1,34
1,54
1,76
2,72
0,84
1,19
1,40
1,60
1,81
2,01
2,22
2,88
0,88
1,18 moisture removal max comp input
CONDENSER
OUTDOOR AMBIENT TEMP. °C
25 30 35
2,37
0,79
1,62
2,30
0,85
1,59
2,19
0,91
1,54
1,84
2,05
2,27
2,37
2,37
1,80
2,01
2,22
2,30
2,30
1,75
1,96
2,17
2,19
2,19
2,57
0,81
1,42
1,63
1,85
2,06
2,28
2,49
2,47
0,87
1,38
1,59
1,80
2,01
2,22
2,42
2,35
0,93
1,33
1,53
1,74
1,95
2,16
2,35 kW kW kW
2,63
0,90
1,15
1,36
1,57
1,78
1,99
2,20
2,78
0,94
1,14
1,34
1,55
1,76
1,97
2,95
0,97
1,10
1,31
1,52
1,73
1,29
1,50
1,71
1,92
2,78
1,02
1,04
1,25
1,46
1,67
2,50
0,96
1,10
1,31
1,52
1,73
1,93
2,15
2,65
0,99
1,08
RATING CONDITIONS
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
NOTE: Data referred to AWR608HL
1,23
1,44
1,65
1,86
2,60
1,08
0,98
1,18
1,40
1,60
2,35
1,02
1,03
1,24
1,46
1,66
1,88
2,08
2,49
1,05
1,02
40
2,05
0,96
1,47
1,68
1,89
2,05
2,05
2,05
2,21
0,99
1,26
1,47
1,68
1,89
2,10
2,21
1,1 l/h
1,14 kW
1,15
1,36
1,57
1,78
2,42
1,14
0,91
1,12
1,33
1,54
2,16
1,08
0,96
1,17
1,38
1,59
1,79
2,01
2,29
1,11
0,94
43
1,90
1,02
1,40
1,61
1,82
1,90
1,90
1,90
2,03
1,05
1,18
1,39
1,60
1,81
2,02
2,03
19
OUTDOOR UNIT:
INDOOR UNIT:
AER612SH
AWR612HL
220 - 240V ~ 50Hz
RATING CAPACITY
COMP. POWER INPUT
AIR FLOW RATE
EVAPORATOR
ENT.TEMP. °C
W.B.
D.B.
TC:
SHC:
CM:
15
17
19
21
23
3,10 kW
1,206 kW
470 m³/h
21
23
25
27
29
31
21
23
25
27
29
31
SHC
SHC
SHC
SHC
SHC
TC
CM
TC
CM
SHC
SHC
SHC
SHC
SHC
SHC
TC
CM
SHC
21
23
25
27
29
31
23
25
27
29
31
25
27
29
SHC
SHC
SHC
SHC
SHC
SHC
TC
CM
SHC
SHC
SHC
SHC
SHC
TC
CM
SHC
SHC
SHC
1,57
1,86
2,14
2,41
2,65
4,00
1,06
1,50
1,78
2,07
31 SHC 2,35
TOTAL COOLING CAPACITY
SENSIBLE HEAT CAPACITY
COMPRESSOR INPUT
2,69
2,97
3,75
1,02
1,54
1,82
2,10
2,38
20
3,13
0,91
2,17
2,46
2,73
3,01
3,13
3,13
3,35
0,95
1,87
2,16
2,44
2,72
3,00
3,27
3,57
0,98
1,48
1,74
1,99
2,24
2,49
2,76
3,57
1,10
1,46
1,71
1,96
2,21
OUTDOOR AMBIENT TEMP. °C
25 30 35
2,94
0,99
2,01
2,85
1,06
1,97
2,72
1,13
1,91
2,28
2,54
2,81
2,94
2,94
3,18
1,02
1,76
2,24
2,49
2,76
2,85
2,85
3,06
1,10
1,71
2,17
2,43
2,69
2,72
2,72
2,91
1,17
1,64
2,48
3,77
1,14
1,41
1,66
1,91
2,18
2,03
2,30
2,56
2,83
3,09
3,37
1,06 moisture removal max comp input
CONDENSER kW kW kW
1,97
2,23
2,49
2,75
3,01
3,26
1,13
1,43
1,69
1,95
2,21
2,47
2,73
3,45
1,17
1,41
1,66
1,93
2,18
2,45
3,65
1,21
1,37
1,62
1,89
2,15
1,90
2,16
2,42
2,68
2,91
3,10
1,21
1,36
1,62
1,88
2,05
2,40
2,66
3,29
1,24
1,34
1,60
1,86
2,12
2,38
3,45
1,28
1,29
1,55
1,81
2,07
RATING CONDITIONS
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
NOTE: Data referred to AWR608HL
1,28
1,54
1,81
2,06
2,33
2,58
3,09
1,32
1,26
1,52
1,79
2,04
2,30
3,23
1,35
1,21
1,47
1,73
1,99
1,82
2,08
2,34
2,60
2,74
2,91
1,28
40
2,55
1,21
1,83
2,09
2,35
2,55
2,55
2,55
2,74
1,24
1,56
1,5 l/h
1,426 kW
1,19
1,45
1,71
1,97
2,22
2,49
2,84
1,39
1,17
1,43
1,68
1,95
2,21
3,01
1,43
1,13
1,39
1,65
1,91
1,73
1,98
2,24
2,50
2,52
2,68
1,35
43
2,35
1,28
1,73
1,99
2,25
2,35
2,35
2,35
2,52
1,32
1,46
20
5-3 Heating Capacity
120
110
100
90
80
70
60
50
40
30
20
10
0
–8 –5 0 5
7
10 15
Outdoor temperature (
°
C D.B.)
NOTE
1) … Point of Rating condition
Black dot in the chart indicate the following rating condition.
Indoor : 20
°
C D.B.
Outdoor : 7
°
C D.B. / 6
°
C W.B.
2) Above characteristics indicate instantaneous operation, which does not take into consideration defrost operation.
3) Fan speed : High
4) Because this air conditioner heats a room by drawing in the heat of the outside air (heat pump system), the heating efficiency will fall off when the outdoor temperature is very low. If sufficient heat cannot be obtained with this air conditioner, use another heating appliance in conjunction with it.
NOTE: Data referred to Hi-Wall models AWR608HL
AWR609HL
AWR612HL
21
6. ELECTRICAL DATA
6-1 Electrical characteristics
OUTDOOR UNIT:
AER608SH
COOLING performance at
Rating conditions Running Amps.
Power input
Full load conditions Running Amps.
Power input
A
Kw
A
Kw
Indoor Unit
Fan Motor
0,11
0,025
0,11
0,025
Outdoor unit
Fan Motor Compressor
230V 1-Phase 50 Hz
0,28
0,063
0,28
0,063
Rating Conditions: Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions: Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43°C D.B.
3,61
0,802
4,11
0,902
HEATING performance at
Rating conditions Running Amps.
Power input
Full load conditions Running Amps.
Power input
A
Kw
A
Kw
Indoor Unit
Fan Motor
0,11
0,025
0,11
0,025
230V 1-Phase 50 Hz
0,28
0,063
0,28
NOTE: Data referred to indoor unit AWR608HL model.
For other indoor unit models there could be some differences.
Outdoor unit
Fan Motor
0,063
Rating Conditions: Indoor Air Temperature 20°C D.B.
Outdoor Air Temperature 7°C D.B. / 6°C W.B.
Full Load Conditions: Indoor Air Temperature 27°C D.B.
Outdoor Air Temperature 24°C D.B. / 18°C W.B.
Compressor
3,61
0,772
3,91
0,812
Complete Unit
4,0
0,890
4,5
0,990
Complete Unit
4,0
0,860
4,3
0,900
22
OUTDOOR UNIT:
AER609SH
COOLING performance at
Rating conditions Running Amps.
Power input
Full load conditions Running Amps.
Power input
A
Kw
A
Kw
Indoor Unit
Fan Motor
0,12
0,027
0,12
0,027
Outdoor unit
Fan Motor Compressor
230V 1-Phase 50 Hz
0,28
0,063
0,28
0,063
Rating Conditions: Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions: Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43°C D.B.
4,3
0,963
5,1
1,140
HEATING performance at
Rating conditions Running Amps.
Power input
Full load conditions Running Amps.
Power input
A
Kw
A
Kw
Indoor Unit
Fan Motor
0,12
0,027
0,12
0,027
230V 1-Phase 50 Hz
0,28
0,063
0,28
NOTE: Data referred to indoor unit AWR609HL model.
For other indoor unit models there could be some differences.
Outdoor unit
Fan Motor
0,063
Rating Conditions: Indoor Air Temperature 20°C D.B.
Outdoor Air Temperature 7°C D.B. / 6°C W.B.
Full Load Conditions: Indoor Air Temperature 27°C D.B.
Outdoor Air Temperature 24°C D.B. / 18°C W.B.
Compressor
4,3
0,973
4,8
1,080
Complete Unit
4,7
1,040
5,5
1,230
Complete Unit
4,7
1,050
5,2
1,170
23
OUTDOOR UNIT:
AER612SH
COOLING performance at
Rating conditions Running Amps.
Power input
Full load conditions Running Amps.
Power input
A
Kw
A
Kw
Indoor Unit
Fan Motor
0,13
0,031
0,13
0,031
Outdoor unit
Fan Motor Compressor
230V 1-Phase 50 Hz
0,28
0,063
0,28
0,063
Rating Conditions: Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions: Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43°C D.B.
5,79
1,206
6,79
1,426
HEATING performance at
Rating conditions Running Amps.
Power input
Full load conditions Running Amps.
Power input
A
Kw
A
Kw
Indoor Unit
Fan Motor
0,13
0,031
0,13
0,031
230V 1-Phase 50 Hz
0,28
0,063
0,28
NOTE: Data referred to indoor unit AWR612HL model.
For other indoor unit models there could be some differences.
Outdoor unit
Fan Motor
0,063
Rating Conditions: Indoor Air Temperature 20°C D.B.
Outdoor Air Temperature 7°C D.B. / 6°C W.B.
Full Load Conditions: Indoor Air Temperature 27°C D.B.
Outdoor Air Temperature 24°C D.B. / 18°C W.B.
Compressor
6,19
1,306
6,89
1,346
Complete Unit
6,2
1,300
7,2
1,520
Complete Unit
6,6
1,400
7,3
1,440
24
6-2 Electric Wiring Diagram
6-3 System Wiring Diagram
25
Via Varese, 90 - 21013 Gallarate - Va - Italy
Tel. +39 0331 755111 - Fax +39 0331 776240 www.argoclima.it