Silver Series Operator Interface Terminals

Addendum to Installation and Operation Manual

Operator Interface Terminals

0600-0067-0000 Rev. D

May 2011

1241 Bundy Boulevard, Winona, Minnesota USA 55987

Phone: +1 (507) 454-5300, Fax: +1 (507) 452-4507 http://www.watlow.com

©2011 Watlow. All rights reserved.

TC

Table of Contents

Chapter 1: Introduction .................................................................................. 3

Additional Resources ................................................................................. 3

Chapter 2: Install and Wiring ......................................................................... 4

Connecting via Modbus RTU (232/485) ..................................................... 4

Connecting via Modbus TCP (Ethernet) ..................................................... 4

Chapter 3: Communications Basics ............................................................. 5

About Gateways, Controllers and PLCs ..................................................... 5

Parameter Register Addresses .................................................................. 6

Address Maps ............................................................................................ 7

Choosing the Communications Drivers ...................................................... 8

Addressing Parameters in Multiple Controllers .......................................... 8

Address Offsets in Multi-Loop Controllers .................................................. 9

Accessing Parameters via EZ-ZONE RUI Gateways and RM Access

Modules ..................................................................................................... 9

Data Types ............................................................................................... 10

Important Things to Know ........................................................................ 10

Chapter 4: Programming Tutorials ............................................................. 11

Create a First Project ............................................................................... 11

Create a Popup Window .......................................................................... 14

Create a Meter in a Popup Window ......................................................... 15

Add a Numeric Display ............................................................................. 17

Add Increment and Decrement Buttons ................................................... 19

Add an Option List for Control Mode ........................................................ 22

Add a Button to Close the Popup Window ............................................... 24

Edit the Startup Window ........................................................................... 25

Compile and Download the Project .......................................................... 28

Log Data .................................................................................................. 31

Create a Graph ........................................................................................ 35

Use Recipes ............................................................................................. 39

EZ-ZONE

®

is a registered trademark of Watlow

 2 

Silver Series OIT Watlow Addendum

1

Chapter 1: Introduction

The Silver Series Operator Interface Terminals (OITs) are powerful human machine interfaces for equipment and processes. EasyBuilder5000 is easy-to-use and flexible software for creating the windows, buttons, displays, gauges and other screen items with which operators interact on the OIT. The purpose of this addendum is to quickly get you up and running with the OIT and software when used with Watlow controllers.

Chapter 2: Install and Wiring provides information needed to physically connect the Silver Series OIT

to power and Watlow products.

Chapter 3:Introduction provides definitions and information necessary for using an OIT with Watlow

controllers and other devices. Familiarity with these concepts is assumed in the tutorials that follow.

Chapter 4: Programming Tutorials walks you through the steps of getting Watlow controllers

communicating, creating user interfaces and using powerful user interface features such as trending, data logging and recipes with Watlow controllers.

Additional Resources

In addition to this addendum the following resources are available for learning about Silver Series OITs and EZware-5000 programming software:

Silver Series Installation and Operation Manual—available at Watlow.com in the Download

Center’s User Manuals section; search for “Silver Series”.

Watlow Silver Series OIT Installation Guide—available at Watlow.com in the Download Center’s

User Manuals section; search for “Silver Series”.

EZ-ZONE ALL Modbus register list in Excel—available at Watlow.com in the Download Center’s

User Manuals section; search for “EZ-ZONE ALL”

Silver Series Secrets video tutorial series—available at Watlow.com in the Download Center’s

Training and Education section.

EZware-5000 Software Download for Silver Series OITs—the latest version of software for programming Silver Series OITs from Watlow is always available at Watlow.com in the Download

Center’s Software and Demos section; search for “Silver Series”.

Silver Series Sample Projects—available at Watlow.com in the Download Center’s Software and

Demos section; search for “Silver Series”.

Silver Series Frequently Asked Questions—along with other documents addressing specific topics related to using Silver Series OITs is available at Watlow.com in the Download Center’s Training and

Education section.

 3 

Silver Series OIT Watlow Addendum

2

Chapter 2: Install and Wiring

Consult the Silver Series Installation and Operation Manual for detailed information on installing and wiring the OITs. This chapter provides important additional information regarding connecting to and communicating with Watlow controllers.

Connecting via Modbus RTU (232/485)

The tables below indicate to which pins on the Silver Series OIT’s DB9 connectors the Watlow EZ-

ZONE

®

screw terminals should connect.

Connecting via 485 2-wire

Silver Series OIT

TS00-0043-0000

TS00-0043-E000

TS00-0070-0000

TS00-0100-0000

Watlow Cable

1

Watlow EZ-ZONE

Function COM1 COM3 COM1 COM3

T-/R- 1 7 1 6

Wire Color Terminals Function

White/Brown CA T-/R-

T+/R+ 2 8 2 9 Brown CB T+/R+

Common 5 5 5 5 Blue CC Common

1

Supports COM1 only. Cable part number: 0219-0374-0000 for TS00-0070-0000 and TS00-0100-0000

or part number 0219-0388-0000 for TS00-0043-0000 and TS00-0043-E0000

Connecting via 232

Silver Series OIT

TS00-0043-0000

TS00-0043-E000

TS00-0070-0000

TS00-0100-0000

Function

TXD

RXD

Common

COM1

6

9

5

Watlow EZ-ZONE

COM1 COM2 COM3 Terminals Function

3 4 7 C2 RD

2

5

6

5

8

5

C3

C5

TX

Common

Connecting via Modbus TCP (Ethernet)

With standard Ethernet cables connect the controller(s) and the Silver Series OIT to an Ethernet switch or connect the controller directly to the OIT.

Determining or Setting the OIT’s IP Address

If you connect the OIT to an Ethernet network in order to download programs or communicate with controllers via Ethernet, you must ensure the OIT has a unique IP address and you will need to know that address in order to communicate from your PC with the OIT.

To read or set the OIT’s IP address:

• Connect a USB mouse to the OIT, if desired and supported.

• Apply power to the OIT.

• Once the OIT is powered up, click the lower right corner of the OIT screen.

• When the button with the arrow or angle bracket appears, click it.

• On the menu bar click the setting button (the one with the wrench or gear icon).

• Enter the password. (By default this is 111111.)

 4 

Silver Series OIT Watlow Addendum

• The IP address is listed in the System settings window on the Network tab. (If Auto Get IP

Address is selected, the IP Address is not editable. If you want to configure the OIT for a fixed address, select IP address get from below, and enter the IP address here.

• Click OK to close the System settings window on the OIT.

Hints for using the Virtual Keyboard to enter the OIT password and IP addresses:

• If you do not see the Virtual Keyboard it may be minimized; click the X on the menu bar.

• Make sure the cursor is in the Password or IP address field on the System Settings dialog.

• Enter the password by clicking only the keys on the Virtual keyboard. If you click the caption bar or other part of the Virtual keyboard window, your keystrokes are not entered in the System

Settings dialog.

• You can tell the password key strokes are being entered if you hear the key chirp from the OIT and see stars (******) appearing in the password field.

• If you cannot see the Password field, arrange the Virtual Keyboard and System Settings dialog then make sure the cursor is in the Password field.

• If you are entering the password on the Virtual Keyboard but stars aren’t appearing in the

Password field, make sure the Password field has focus. If you do not see the text insertion cursor ( | ) in the Password field, it does not have focus. Click in the Password field to give it focus then click keys, but nothing else on the Virtual Keyboard.

• One you have entered the password and the stars appear in the Password field, you can minimize the Virtual Keyboard by clicking the minimize button at the upper right corner to access the check boxes and buttons on the System Settings dialog.

3

Chapter 3: Communications

Basics

The Silver Series OIT can communicate with Watlow controllers via Modbus TCP or Modbus RTU.

This section defines terms you will encounter and provides information about Modbus communications that will help you create a user interface with the Silver Series OIT for equipment and machines that include Watlow controllers.

About Gateways, Controllers and PLCs

The Silver Series OIT can communicate with a variety of devices. Because many of these devices are

Programmable Logic Controllers (PLCs), EasyBuilder5000 refers to devices in many places generically as “PLCs”. Don’t let this confuse you. When you are setting up the OIT to communicate with a Watlow product, from the OIT’s point of view the controller is a PLC.

This addendum refers to configuring the Silver Series OIT to communicate with “controllers”, but the instructions apply equally to limit controllers and gateways such as the EZ-ZONE

®

RUI Gateway.

 5 

Silver Series OIT Watlow Addendum

Parameter Register Addresses

The Modbus RTU and Modbus TCP communications protocols assume that each device’s memory is organized in blocks of like-data. Each data block contains either read-only data or read/write data and either bit-size data or word-size (16-bit) data. For example, the Coils data block contains read/write bits and the Input Register data block contains read-only words.

Within each of these data blocks there is a range of memory locations. The data blocks are often referred to by the first digit of their address range. For example, the Holding Registers are often referred to as,

“the 4x registers”. The Modbus standard defines both a numbering scheme and an addressing scheme for the memory locations in the data blocks. The table below illustrates this information for the four most commonly discussed data blocks.

Name

Coils

Discrete Inputs

Input Registers

Holding Registers

Number

0x

1x

Access

Data

Size

Memory Location

Numbers

(Absolute)

Read/Write 1 bit 1 to 65,536

Read-Only 1 bit 100,001 to 165,536

3x

4x

Read-Only Word 300,001 to 365,536

Read/Write Word 400,001 to 465,536

Memory Location

Addresses

(Relative)

0 to 65,535

0 to 65,535

0 to 65,535

0 to 65,535

Because the location numbering scheme includes the data block number, it is helpful to think of it as an

absolute address. The absolute address specifies the address completely or absolutely in that it says which data block and which address contains a piece of data. Because the location addresses do not include the data block number, it is helpful to think of them as relative addresses. They specify where to look relative to the starting point of the data block.

Some software and device manufacturers document the use of their products in terms of the numbering scheme while others use the addresses. In either case the manufacturer typically calls the numbers he supplies, “the addresses.” So to use any two products together you need to know whether or not you have to convert the specified “address” in order to get the result you want.

EasyBuilder5000’s Modbus drivers call the data block, “Device type” and for “Address” expect the memory location’s absolute address without the data block number. For example, to access a value in a holding register with absolute address 401,905, for Device type you select the data block “4x” and enter

“1905” in the Address field. The following illustrates setting this address in EasyBuilder5000.

(072)

Watlow controllers use only the 4x registers. Therefore, you will set the Device type to 4x to access any parameter in a Watlow controller. Watlow manuals specify relative addresses. Therefore, you must add one (1) to an address found in a Watlow manual (other than this manual) before you enter it in

EasyBuilder5000.

Silver Series OIT

 6 

Watlow Addendum

For example, the EZ-ZONE PM Integrated Controller Models User’s Manual lists the relative address for Heat Power as 1904. To monitor the heat power with the Silver Series OIT, you will add one (1) to the relative address and enter “1905” in the Address field in EasyBuilder5000.

(073)

In summary, when setting an address for a screen object to read or write from a Watlow controller:

• For the Device type select 4x.

• Set the Address to a value that is one greater than the relative Modbus address listed in the

Watlow controller manual.

Address Maps

Some EZ-ZONE products have user-selectable address maps. Select the desired map with the Data Map parameter on the Setup Page’s Communications menu in the controller. The Data Map affects the parameter addresses at which values are read and written. The Data Map setting applies to all the parameters in the controller. Generally Map 2 provides access to more parameters.

For example, the EZ-ZONE PM Integrated Controller Models User’s Manual lists Map1 and Map 2 addresses for Process Value for Analog Inputs 1 and 2. If the Data Map parameter is set to Map 1 then the Process Value for Analog Input 2 is read at address 441 (the listed address plus one), but if Data

Map is set to Map 2 then the Process Value for Analog Input 2 is read at address 451. The address for the Process Value for Analog Input 1 is the same for Map 1 and Map 2.

Silver Series OIT

 7 

(078)

Watlow Addendum

Choosing the Communications Drivers

When you create a project using EasyBuilder5000 you select the drivers necessary to communicate with the Watlow controllers and any other devices with which the Silver Series OIT must communicate. For

Watlow controllers, you select one of these drivers:

Modbus RTU Master—used with Watlow controllers that support Modbus RTU and communicate via RS-232 or RS-485.

Modbus TCP/IP Master—used with Watlow controllers that support Modbus TCP and communicate via Ethernet.

Using the Modbus RTU Master Driver to Communicate via 485

When you set up the Silver Series OIT to communicate via 485, you add a Modbus RTU Master device to the device list in the System Parameter Settings. Only one driver is required for each COM port on the

OIT to which controllers are connected. This is regardless of the number of controllers that are connected to that 485 COM port. Think of the Modbus RTU Master device as a driver for the COM port not as a driver for the controllers themselves. That is why you choose the Modbus RTU Master driver rather than the Modbus RTU Slave driver. The controllers are slaves; the OIT’s COM port is the master.

Using the Modbus RTU Master Driver to Communicate via 232

When you set up the OIT to communicate via a 232 COM port, you add a Modbus RTU Master device to the device list in the System Parameter Settings. When using 232 on a COM port, only one controller can be connected to that port.

Using the Modbus TCP/IP Master Driver to Communicate via Ethernet

When you set up the OIT to communicate with controllers via Ethernet, you add one Modbus TCP/IP

Master device to the device list in the System Parameter Settings dialog for each controller that has an

IP address with which you will communicate. For example, if the OIT must communicate with three EZ-

ZONE controllers via Ethernet, add three Modbus TCP/IP Master devices to the device list in the

System Parameter Settings dialog each configured to communicate with one controller.

Addressing Parameters in Multiple Controllers

Normally the Silver Series OIT assumes that any register address you enter when communicating via

Modbus RTU is associated with the controller at the network address you set in the PLC default station

no field in the Device Properties under the System Parameter Settings.

To read or write data from a register in another controller on a 485 network, enter the network address and register address separated by the number sign or hash mark (#). For example “3#2501” accesses register 2501 in the controller with the Modbus network address 3.

(074)

Silver Series OIT

 8 

Watlow Addendum

Address Offsets in Multi-Loop Controllers

In controllers with more than one loop of control, more than one limit etc., there is more than one instance of each parameter for these duplicated functions. The manuals for controllers such as the EZ-

ZONE RM, list the Modbus address and an offset for these parameters. Add the offset to the address

once to get the address of the second instance of the parameter, add it twice to get the third instance and so on.

For example, the address of the Heat Power for Loop 1 is listed in the EZ-ZONE RM manual as 2244 with an offset of 70. The following table lists the addresses of the Heat Power parameter for each of the four possible loops in the controller. The table also reminds you to add one (1) to the relative addresses from the controller manuals before entering the parameter address in EasyBuilder5000.

Loop Address + Offset(s)

1 2224

2 2224 + 70

3 2224 + 70 + 70

4 2224 + 70 + 70 + 70

Convert Relative

Address

2224 + 1

2294 + 1

2364 + 1

2434 + 1

Enter in

EasyBuilder5000

2225

2295

2365

2435

Accessing Parameters via EZ-ZONE RUI Gateways and RM

Access Modules

Multiple EZ-ZONE devices can communicate with the Silver Series OIT via one or more EZ-ZONE

RUI Gateways or EZ-ZONE RM Access modules. When ordered with either the Modbus TCP or

Modbus RTU communications option, an RUI Gateway or RM Access module allows a Silver Series

OIT to communicate with multiple EZ-ZONE controllers without purchasing communication options in each controller.

In such a system the Silver Series OIT is connected to and configured to communicate with the gateway.

The gateway presents itself as a single device on the Modbus network; the OIT does not communicate with the controllers, only with the gateway. The gateway is configured by the user with an address offset for each controller connected to it. That address offset is added to the parameter addresses for the controller.

For example, consider three EZ-ZONE PM controllers connected to an RUI Gateway configured with an offset of 0 for the first controller, 5000 for the second controller and 10,000 for the third controller. The table below indicates the addresses that must be entered in EasyBuilder5000 to access the set point value in the three PM controllers.

PM Set Point Plus Gateway Offset

1

2

3

2172

2172

2172

2172 + 0

2172 + 5000

2172 + 10000

Convert Relative

Address

2172 + 1

7172 + 1

12172 + 1

Enter in

EasyBuilder5000

2173

7173

12173

Silver Series OIT

 9 

Watlow Addendum

Data Types

The Silver Series OIT’s Modbus drivers support a variety of data types. The Watlow manuals specify the data type of each parameter. However the terminology is not precisely the same. The table below correlates the data types indicated in the Watlow documentation with the data types you should select when configuring a screen object in EasyBuilder5000.

EZ-ZONE User’s

Manuals

uint dint float

EZ-ZONE ALL

Modbus List

Enumeration, unsigned 8-bit,

Event, unsigned 16-bit signed 32-bit

IEEE Float

EasyBuilder5000

16-bit Unsigned

32-bit Signed

32-bit Float

Important Things to Know

Note:

Make sure the Modbus Word Order is set to Word Low High in the controller.

That is the setting that works with the Silver Series OIT.

Note:

Examples in this manual use the map 1 addresses. If the controller’s Data Map is set to 2, the examples may not work.

Caution: When you use a multi-state switch object to set an enumerated parameter in a controller, each time the user clicks the switch, the setting selected by the switch is sent to the controller. When it is desirable to go directly from one setting to another without intermediate settings, use a set word object or an option list to set the parameter instead.

Silver Series OIT

 10 

Watlow Addendum

4

Chapter 4: Programming

Tutorials

The following sections guide you through creating a first project using EasyBuilder5000 and a Silver

Series OIT that communicates with a Watlow controller.

Create a First Project

The following procedure guides you through the process of configuring a Silver Series OIT to communicate with a Watlow Controller.

1) To launch

EasyBuilder5000: on the Windows task bar click

Start, click All

Programs, click

Watlow, click

EZware-5000 and click EasyBuilder

5000.

2) In the Welcome to

EasyBuilder5000 dialog, for Model, choose the OIT model you have.

3) For Display Mode choose Landscape.

4) Make sure Use

template is selected.

5) Click OK.

(001)

Note: If you have previously created a project, that project will open. In that case from the File menu, choose New to create a blank project for this tutorial and to see the Welcome dialog.

Note: The TS00-0070-0000 and TS00-0100-0000 are supported by the same driver.

Note: The TS00-0043-0000 and TS00-0043-E000 are supported by the same driver.

Silver Series OIT

 11 

Watlow Addendum

6) In the System

Parameter

Settings dialog, in the Device List, select the Local

PLC 1 device and click Settings…

7) For PLC type, choose the appropriate driver.

See the table below.

8) For PLC I/F, choose the appropriate hardware interface.

See the table below.

9) For PLC default

station no. type the controller’s address. Typically this is 1 for the first controller.

10) Click Settings…

(003)

For part numbers like… with…

STxx-xxx-xxxx

PMxxxxx-1xxxxxx

RMCxxxx-xxxx1xx

RMHx-xxxx-x1xx

RMLx-xxxx-x1xx

RMSx-xxxx-x1xx

Modbus RTU

For PLC type choose…

Modbus RTU Master

For PLC I/F choose…

RS-485 2W

(002)

Silver Series OIT

 12 

Watlow Addendum

For part numbers like… with… For PLC type choose… For PLC I/F choose…

PMxxxxx-2xxxxxx

EZKx-2xxx-xxxx

RMAx-x2xx-xxxx

Modbus RTU Modbus RTU Master RS-232 or RS-485 2W*

PMxxxxx-3xxxxxx

EZKx-3xxx-xxxx

RMAx-x3xx-xxxx

Modbus TCP Modbus TCP/IP Master

Other Watlow Controllers Modbus RTU Modbus RTU Master

Ethernet

RS-232 or RS-485 2W*

*Both 232 and 485 are available; choose the one to which you have connected the OIT.

11) For the Modbus RTU

Master…

• For COM, choose the communications port to which you have connected the controller. Typically this is COM 1.

• For Baud rate, choose the rate that is set in the controller.

(004)

• For Data bits, choose 8 Bits.

• For Parity, choose None.

• For Stop bits, choose 1 Bit.

• For multiple controllers on the same port, for Turn around delay (ms), enter 15 and for Send

ACK delay (ms) enter 15.

• Click OK.

12) For the Modbus

TCP/IP Master…

• For IP address, enter the IP address of the controller.

• Click OK.

13) Click OK to close the

Device Properties dialog.

14) To set up communications with controllers connected to other COM ports or to configure additional controllers communicating via Ethernet:

(005)

• Click New...

• Repeat from step 7 above.

Silver Series OIT

 13 

Watlow Addendum

15) Click OK to close the System Parameter Settings dialog.

16) Save the project:

• From the File menu, choose Save.

• In File name type First Project.mtp.

• Click Save.

Create a Popup Window

This example assumes you have created a project that configured to communicate with a Watlow controller and that project is open in EasyBuilder5000.

1) From the Window menu, choose Open

Window.

2) Click New…

(006)

3) Click Base Window.

4) Ensure the Name is

Window_011 and the

Window no. is 11.

5) Set Width to 420.

6) Set Height to 300 (272 for the 4.3 in. OIT).

7) To set the background color to white:

• In the Background group, next to Color click .

• Select the white color swatch in the Basic

colors group.

• Click OK.

(007)

8) In the Popup window group, set Start pos. X to 120 (0 for the 4.3 in. OIT).

Silver Series OIT

 14 

(008)

Watlow Addendum

9) In the Popup window group, set Start pos. Y to 120 (0 for the 4.3 in. OIT).

10) Click OK.

11) In the Open Window dialog, select Window_11.

12) Click Open.

13) From the File menu choose Save.

Create a Meter in a Popup Window

This example assumes you have created a popup window in a project that is configured to communicate with a Watlow Controller and that window is open in EasyBuilder5000.

1) From the Objects menu, choose Meter

Display.

2) Click the General tab.

3) In Description type

Heat Power.

4) Click Settings…

5) For PLC name choose

Modbus RTU Master or Modbus TCP/IP

Master.

6) For Device type choose 4x.

(009)

7) For Address enter the address of the heat power for your controller. See the table.

8) Select the data type in the field below the

Address field. See the table.

9) Click OK.

(075)

For this controller…

RMCxxxx-xxxxxxx

RMHx-xxxx-x1xx

PMxxxxx-xxxxxxx

STxx-xxMx-xxxx

ST via RUI Gateway

Other Controllers

This parameter…

Heat Power

Heat Power

Heat Power

Heat Power

Heat Power

Enter this

Address*…

2245

4125

1905

237

1901

Choose this

Data Type…

32-bit Float

32-bit Float

32-bit Float

32-bit Float

32-bit Float

Consult the controller manual.

*These addresses have already been changed to the absolute form required for EasyBuilder5000 by adding 1 to the value listed in the Watlow manual. Enter them as listed

Silver Series OIT

 15 

Watlow Addendum

10) Click the Outline tab.

11) In Degree set Start

degree to 270.

12) In Degree set End

degree to 90.

13) In Background uncheck Full circle.

14) In Tick marks check

Enable.

15) For Tick marks

Color, select black.

16) In Tick marks set

Main scale to 6.

17) In Tick marks set Sub

scale to 1.

18) In Tick marks set

Length to 6.

19) Click the Limits tab.

20) Set Value Zero to 0.

21) Set Value Span to

100.

22) Check Range limits

Enable.

23) Set Width to 3.

(010)

(011)

24) Click OK.

25) Move the cursor with the outline of the meter to position it and click to place the meter in

Window_11.

26) Resize the meter with the corner handles to make it smaller, if necessary

Silver Series OIT

 16 

Watlow Addendum

27) Double-click the meter to open the Meter

Display Object’s

Properties dialog.

28) Click the Profile tab.

29) Set X to 140.

30) Set Y to 60.

31) Set Width to 140.

32) Set Height to 140.

33) Click OK.

34) From the File menu choose Save.

(012)

Add a Numeric Display

This example assumes you have created a window in a project that is configured to communicate with a

Watlow Controller and that window is open in EasyBuilder5000.

1) On the Objects menu, click Numeric/ASCII then choose Numeric

Display.

2) Click the General tab.

3) In Description type

Actual Closed Loop Set

Point.

4) For PLC name choose

Modbus RTU Master or Modbus TCP/IP

Master.

(013)

Silver Series OIT

 17 

Watlow Addendum

5) For Address choose 4x and enter the address of the Closed Loop

Working/Active Set

Point for your controller. See the table.

6) Click the Numeric

Format tab.

7) In Data format set the data type. See the table.

8) On the Font tab set

Align to Right.

(013)

For this controller…

RMCxxxx-xxxxxxx

RMHx-xxxx-x1xx

PMxxxxx-xxxxxxx

STxx-xxMx-xxxx

ST via RUI Gateway

Other Controllers

This parameter…

Closed Loop

Working/Active

Set Point

(Read Only)

Enter this

Address*…

2513

5233

2173

204

Choose this

Data Type…

32-bit Float

32-bit Float

32-bit Float

32-bit Float

2173 32-bit Float

Consult the controller manual.

*These addresses have already been changed to the absolute form required for EasyBuilder5000 by adding 1 to the value listed in the Watlow manual.

Enter them as listed.

9) Click OK.

10) Move the cursor with the outline to position the display field and click to place it.

11) Adjust the size of the field as needed.

12) From the File menu choose Save.

(014)

Silver Series OIT

 18 

Watlow Addendum

Add Increment and Decrement Buttons

This example assumes you have created a window in a project that is configured to communicate with a

Watlow Controller and that window is open in EasyBuilder5000.

To add a button that increments the set point:

1) On the Objects menu, click Button then choose Set Word.

2) Click the General tab.

3) In Description type

Increment Set Point.

4) For PLC name choose

Modbus RTU Master or Modbus TCP/IP

Master.

5) Click Setting…

6) For Device type choose 4x.

7) For Address enter the address of the User Set

Point for your controller.

8) Select the data type for the parameter in the field below the

Address field.

(015)

For this controller…

RMCxxxx-xxxxxxx

RMHx-xxxx-x1xx

PMxxxxx-xxxxxxx

STxx-xxMx-xxxx

ST via RUI Gateway

This parameter…

Closed Loop

Set Point

(Read/Write)

Enter this

Address*…

2501

5221

2161

Choose this

Data Type…

32-bit Float

32-bit Float

32-bit Float

22 32-bit Float

2161 32-bit Float

Other Controllers Consult the controller manual.

*These addresses have already been changed to the absolute form required for EasyBuilder5000 by adding 1 to the value listed in the Watlow manual.

Enter them as listed.

9) Click OK.

10) In Attribute for Set

Style choose Press and

hold increment

(JOG++).

11) Set Inc. value to 1.

12) Set Upper Limit to 100 or a value that is safe for your controller’s set point.

13) Set JOG delay to 0.5 seconds.

14) Click the Shape tab.

15) Check Use shape.

Silver Series OIT

 19 

Watlow Addendum

16) Click Shape

Library…

17) Click Select Lib…

18) Select Arrows 1.plb.

19) Click Open.

20) Locate the button with the triangular arrow pointing up and click it.

21) Click OK to close the

Shape Library.

22) Click OK to close the

New Set Word Object

dialog.

23) Click to place the button.

24) Use the handles to adjust the size of the button.

25) Drag the button to place it as desired on the screen.

26) From the File menu choose Save.

(016)

(017)

Silver Series OIT

 20 

Watlow Addendum

To add a button that decrements the set point:

1) Click the increment button to select it.

2) From the Edit menu, choose Copy.

3) From the Edit menu, choose Paste.

4) Drag the new button to an appropriate position.

5) Deselect the button by clicking on the window’s background or another item in the window.

(018)

6) Double click the new button to edit its properties.

7) On the General tab change:

Description to Decrement Set Point

Set Style to Press and hold decrement (JOG--).

8) Set Bottom Limit to 0.

9) On the Shape tab click Shape Library…

10) Locate the button with the triangular arrow pointing down and click it.

11) Click OK to close the Shape Library.

12) Click OK to close the Set Word Object Properties dialog.

13) From the File menu choose Save.

Silver Series OIT

 21 

Watlow Addendum

Add an Option List for Control Mode

This example assumes you have created a window in a project that communicates with a Watlow

Controller and that window is open in EasyBuilder5000.

1) On the Objects menu, click Button then choose Option List.

2) Click the General tab.

3) In Description type

Control Mode.

4) Set Mode to Drop-

down list.

5) Set No. of states to 3.

6) In the Control address group:

(019)

• For PLC name choose

Modbus RTU Master or

Modbus TCP/IP Master.

• Click Setting…

• For Device type choose

4x.

• In Address enter the address of the Control

Mode. See the table.

• Select the data type in the field below the

Address field.

• Click OK to close the

Address dialog

For this controller…

RMCxxxx-xxxxxxx

RMHx-xxxx-x1xx

PMxxxxx-xxxxxxx

STxx-xxMx-xxxx

ST via RUI Gateway

Other Controllers

This parameter…

Control Mode

Enter this

Address*…

2221

4101

Choose this

Data Type…

16-bit Unsigned

16-bit Unsigned

1881 16-bit Unsigned

222 16-bit Unsigned

1881

Consult the controller manual.

16-bit Unsigned

*These addresses have already been changed to the absolute form required for EasyBuilder5000 by adding 1 to the value listed in the Watlow manual.

Enter them as listed.

7) Click the Mapping tab.

Silver Series OIT

 22 

Watlow Addendum

8) In the Values column type the numeric and text values that corresponds to each option you want to include. See the table.

9) Click OK to close the

New Option List

Object dialog.

10) Position the cursor near the bottom center of the window layout and click to place the multi-state switch.

(You may have to move the other objects around to fit everything.)

11) From the File menu choose Save.

State

0

1

2

3 (error)

Value Enumerated Value

10 Auto

54

62

Manual

Off

(022)

(020)

Silver Series OIT

 23 

Watlow Addendum

Add a Button to Close the Popup Window

This example assumes you have created a window in a project that communicates with a Watlow

Controller and that window is open in EasyBuilder5000.

1) On the Objects menu, click Button then choose Function Key.

2) On the General tab, in

Description type Close

Window.

3) Select Close window.

4) On the Shape tab, uncheck Use shape.

(023)

5) Check Use picture.

6) Click Picture

Library…

7) Click Select Lib…

8) Select Computer.flb.

9) Click Open.

10) Locate the circular grey button with the white x and click to select it.

11) Click OK to close the

Picture Library.

12) On the Label tab, make sure Use label is not checked.

(024)

13) Click OK to close the New Function Key Object dialog.

14) Click to place the function key in the upper right.

15) Double-click the function key to open the Function Key Object’s Properties dialog.

Silver Series OIT

 24 

Watlow Addendum

16) Click the Profile tab

17) Set Position X to 375.

18) Set Position Y to 5.

19) Set Size Width to 40.

20) Set Size Height to 40.

21) Click OK.

22) From the File menu choose Save.

(025)

Edit the Startup Window

This example assumes you have created a popup window open in EasyBuilder5000 in a project that is configured to communicate with a Watlow Controller.

To add text to the start up window:

1) From the Window menu, choose 1 10 –

Initial.

2) From the Draw menu choose Text.

3) Set these text

Attributes:

• Choose a Font.

• Set Color to white.

• Set Size to 14.

• Set Align to Left.

4) Edit Content to read,

This is the Startup

Screen.

5) Click OK.

(026)

Silver Series OIT

 25 

Watlow Addendum

6) Position the cursor centered in the top third of the window layout and click to place the text.

7) From the File menu choose Save.

Add a Numeric Display to the main window:

1) On the Objects menu, click Numeric/ASCII and choose Numeric

Display.

2) Click the General tab.

3) In Description type

Process Variable.

4) For PLC name choose

Modbus RTU Master or Modbus TCP/IP

Master.

5) For Address choose

4x.and enter the address of the Analog

Input 1 Process Value.

See the table.

(027)

For this controller…

RMCxxxx-xxxxxxx

RMHx-xxxx-x1xxx

PMxxxxx-xxxxxxx

STxx-xxMx-xxxx

ST via RUI Gateway

Other Controllers

This parameter…

Analog Input 1

Process Value

Enter this

Address*…

Choose this

Data Type…

361 32-bit Float

381 32-bit Float

361 32-bit Float

20 32-bit Float

361

Consult the controller manual.

32-bit Float

*These addresses have already been changed to the absolute form required for EasyBuilder5000 by adding 1 to the value listed in the Watlow manual.

Enter them as listed.

6) Click the Numeric

Format tab.

7) In Data format set the data type.

8) Set Right of decimal

Pt. to 1.

9) On the Font tab set

Align to Right.

10) Click OK.

(028)

(029)

Silver Series OIT

 26 

Watlow Addendum

11) Move the cursor with the outline to position the display field in the center of the screen and click to place it.

12) From the File menu choose Save.

To create a function key on Window10:

1) On the Objects menu, click Button then choose Function Key.

2) On the General tab, in

Description type Loop

1 Settings.

3) Select Display popup

window.

4) For Style choose No

title bar.

5) For Window no. select

11. Window_011.

6) Click the Shape tab.

7) Check Use shape.

8) Click Shape Library…

(031)

9) In the Library list select Buttons 1.

10) Click one of the buttons to select it.

11) Click OK to close the Shape Library.

12) Click the Label tab.

13) Check Use label.

14) Set Color to black.

15) Set Size to 16.

16) Set Align to Left.

17) In Content type Loop 1.

18) Click OK.

Silver Series OIT

 27 

(030)

Watlow Addendum

19) Position the cursor and click to place the function key.

20) From the File menu choose Save.

Compile and Download the Project

This example assumes you have a project that is ready to compile and load into an OIT.

To compile the project:

1) From the Tools menu, choose Compile.

2) Click Compile.

3) After the project is compiled, click Close.

(032)

(034)

To download via Ethernet or via a USB cable:

1) If downloading via Ethernet, determine the OIT’s IP address:

• If you don’t already know the OIT’s IP address, follow the instructions in Determining or

Setting the OIT’s IP Address on page 4, note the IP address for use below.

2) If downloading via a USB cable:

• Connect the USB cable to the OIT.

• Apply power to the OIT.

Silver Series OIT

 28 

Watlow Addendum

• Connect the USB cable to a USB port on the computer.

• If this is the first time you have connected the OIT to the computer via the USB port, locate a follow the procedure in the EasyBuilder 5000 help, “How Do I Install the Maple Systems USB driver?”

3) In EasyBuilder5000 from the Tools menu, choose Download.

4) Select Ethernet or

USB cable.

5) For Ethernet, in HMI

IP select or enter the

OITs IP address.

6) Set Password to the

OITs password

(111111 by default).

7) Check Firmware, if not already checked.

8) Check Reboot HMI

after download, if not already checked.

9) Click Download.

(035)

10) Once the download is complete, click Exit.

Silver Series OIT

 29 

Watlow Addendum

To download the project via a USB drive to an OIT equipped with a USB Host port:

1) Connect at USB drive to the PC

2) From the Tools menu choose Build Data for

USB Disk or CF Card

Download…

3) Click Browse…

4) Locate and select the

USB drive.

Note: Do not select a sub directory of the USB drive.

Select the root.

5) Click OK to close the

Browse For Folder dialog.

(038)

(039)

6) Click Build.

7) When the files are transferred successfully, click OK.

8) Click Exit to close the USB Disk/CF Card Data dialog.

9) Remove the USB drive from the PC.

To download the from the USB drive to the OIT:

1) Connect a USB mouse to the OIT.

2) Apply power to the OIT.

3) Once the OIT is powered up, connect the USB drive to it.

4) When the download/Upload screen appears on the OIT click Download.

Note: You only have a few seconds to do this before the screen times out. If you miss it, disconnect the

USB drive and connect it again.

Silver Series OIT

 30 

Watlow Addendum

5) With the Virtual Keyboard enter the Password. (By default this is 111111.)

Note: If you have difficulty entering the password, see the hints below.

6) On the Download Settings dialog make sure Download Project Files is checked.

7) Click OK.

8) In the Pick a Directory dialog expand the usbdisk folder by clicking the plus (+) next to it.

9) Select the folder that represents the USB drive in the usbdisk folder.

Note: The OIT represents the USB drive with a folder icon and a name it assigns such as disk_a_1. You can inspect the contents to be sure you pick the right one. The compiled project is in a directory called mt8000, but be sure to select the USB drive not a sub folder before proceeding.

10) Click OK.

11) Once the project downloads and runs, you can remove the USB drive from the OIT.

Log Data

This example assumes you have a project with at least one controller.

There are two steps to log data with the OIT:

• Copy data from the controller to contiguous local OIT memory with the Data Transfer (Timebased) object—this is necessary only if you want to log more than one parameter in the same file or show multiple parameters together in a Trend Display (graph) or a History Data Display

(table).

• Create a data log with the Data Sampling object.

Note: This example uses specific addresses internal to the OIT. If you have used one or more of these for other purposes you will have to choose appropriate addresses for your project.

Silver Series OIT

 31 

Watlow Addendum

To copy data to the OIT’s local memory:

1) From the Objects menu choose Data

Transfer (Time-

based).

2) For each item to be logged in the file:

• Click New…

(041)

• In Description type a description of the data to be copied such as

“PV 1”.

• For Address type choose Word.

• For Interval choose a value that is the same as or less than the amount of time you want between data samples.

• In No. of words type word size of the parameter’s data type.

See table.

Data Type

Float

16-bit integer

32-bit integer

No. of words

2

1

2

(042)

• For Source address

PLC name choose

Modbus RTU Master or

Modbus TCP/IP

Master.

• For Source address device type choose 4x.

• In Source address

Address type the address of the parameter to be logged.

For this controller…

RMCxxxx-xxxxxxx

RMHx-xxxx-x1xxx

PMxxxxx-xxxxxxx

STxx-xxMx-xxxx

ST via RUI Gateway

Other Controllers

This parameter…

Analog Input 1

Process Value

Enter this

Address*…

Choose this

Data Type…

361 32-bit Float

381 32-bit Float

361 32-bit Float

20 32-bit Float

361

Consult the controller manual.

32-bit Float

*These addresses have already been changed to the absolute form required for EasyBuilder5000 by adding 1 to the value listed in the Watlow manual.

Enter them as listed.

• For Destination address PLC name choose the OIT (“Local HMI” by default).

• For Destination address device type choose LW.

• In Destination address Address type the local address at which to save the data to be logged.

Silver Series OIT

 32 

Watlow Addendum

Note: Pick a range of addresses with room to store all the data that must be displayed. For example, use

200 for the first parameter to be logged then for each additional parameter increment the address by the size in words of the previous data. For example, typically you log floats such as process variables and set points which each require two words to store. In that case if the first process variable is copied to 200, set the next parameter to copy to 202 so on. In this example, a process variable, a set point and the heat output power are logged.

• Click OK.

3) Click Exit to close the

Data Transfer (Timebased) Object window.

(043)

To set up data sampling to log the data:

1) From the Objects menu choose Data

Sampling.

2) Click New…

(044)

Silver Series OIT

 33 

Watlow Addendum

3) In Description type a description for the set of data such as “Loop

1”.

4) For Sampling mode choose Time-based.

5) For Sampling time

interval choose the time between samples.

6) For Read address

PLC name choose the

OIT (“Local HMI” by default).

7) For Read address device type choose

LW.

8) In Read address

Address type the first address to which data was copied. In the example, this is 200.

9) In Max. data records type the number of records to save in a file.

10) Click Data Format…

11) For each item to be logged in the file:

• Click New…

• For Data type choose the data type of the item being logged. Typically

32-bit Float).

• Enter a description for the item to be logged, for example “PV 1”.

• Click OK.

(046)

(045)

(047)

Silver Series OIT

 34 

Watlow Addendum

12) Click Exit to close the

Data Format window.

(048)

13) Check one or more locations to which to save the data (Save to

USB 1 or Save to

HMI memory).

14) In Folder name type a name for the folder in which the data log file should be created such as “datalog”.

15) Click OK to close the

Data Sampling

Object set up window.

16) Click Exit to close the

Data Sampling

Object window.

(049)

(050)

Create a Graph

This example assumes you have a project with at least one controller and that you have previously configured a time-based data sampling object.

To create and open a window to use for the trend.

1) From the Window menu, choose Open

Window.

2) Click New…

(056)

Silver Series OIT

 35 

Watlow Addendum

3) Click Base Window.

(007)

4) In Name type Trend.

5) Click OK.

6) In the Window list select Trend.

7) Click Open.

To create buttons to open the Trend window and return to the first window:

1) Select window 10.

2) Select the function key on that screen by clicking it once.

(064)

(065)

3) From the Edit menu, choose Copy.

4) From the Edit menu, choose Paste.

5) Place the copy next to the original.

6) Click on the screen background to deselect the button.

7) Double-click the copy to open the Function Key Object’s Properties window.

8) Edit the Description to read Trend Graph

Window.

9) Choose Change full-

screen window.

10) For Window no. choose 12. Trend.

11) Click the Label tab.

12) Edit the Content to read Trend.

13) Click OK to close the Function Key Object’s Properties window.

14) Select the function key on that screen by clicking it once.

(066)

(057)

Silver Series OIT

 36 

Watlow Addendum

15) From the Edit menu, choose Copy.

16) Select window 12 Trend.

17) From the Edit menu, choose Paste.

18) Position the button centered at the bottom of the screen.

19) Edit the new button’s properties so that it changes to full-screen window 10 Initial and is labeled “Back”.

To create a trend graph:

1) From the Objects menu choose Trend

Display.

2) In Description type a description of the trend such as “Loop 1 PV,

SP and Heat vs. Time”.

3) For Data Sampling

Object index choose the data sampling object you previously configured.

4) For Trend type choose Real-time.

5) For Distance between data samples/X axis time range choose Time.

(051)

6) In Distance type the number of seconds the width of the trend graph will represent. For example, if you want to see two minutes of data at once, type 120.

7) Click the Trend tab.

8) Choose a Frame color and a Background color.

(052)

Silver Series OIT

 37 

Watlow Addendum

9) Click the Channel tab.

10) For each channel to be graphed:

• In the Data sampling object group check

Display.

• For Color choose a color that contrasts with the background color.

• In Zero type the value that should be graphed at the bottom of the yaxis.

• In Span type the value that should be graphed at the top of the y-axis.

11) Click OK.

(076)

Note: Keep in mind that while you can choose a different zero and span for each pen, you don’t want to confuse users, so it may be best to graph all the channels against the same zero an span values.

12) Place and size the trend object.

13) Optional: In the Trend

Display Object

Properties dialog

Trend tab enable the

Grid and set it up to display the time.

Silver Series OIT

 38 

(053)

(054)

Watlow Addendum

14) Optional: Use the

Scale tool to add a scale and labels with the Text tool. Color coordinate these or add a legend if the trend channels don’t all have the same zero and span.

(055)

Use Recipes

This example assumes you have a project with at least one controller in which the recipe memory has not already been used for something else.

In this example we will create a recipe that has five parameters from one controller. For each parameter we will create a data transfer object that saves the parameter’s value in the recipe in the OIT. For these objects the source addresses are the parameters’ Modbus addresses in the controller and the destination addresses are RW (recipe word) addresses in the OIT. See the table.

Note: This example uses specific addresses internal to the OIT. If you have used one or more of these for other purposes you will have to choose appropriate addresses for your project.

To create a recipe window and link it to the other screens:

1) Create and open a window to use for viewing, saving and loading recipes called “Recipe

Manager”.

2) Create a button on window 10 Initial that opens the Recipe Manager window.

3) Create a button on the Recipe Manager window that opens window 10 Initial.

Note: Refer to the Trend example if necessary.

Repeat the following steps to add a data transfer object to the Recipe Manager screen for each parameter you want to save in a recipe. Refer to the table below for addresses etc.:

Parameter

Closed Loop Set Point

Alarm High Set Point

Heat Proportional Band

Integral

Derivative

*ST via RUI Gateway

“Source” Address in Controller

RMC RMH PM ST ST GTW*

2501 5221 2161 22

1741 2661 1481 98

2231 4111 1891 233

2235 4115 1895 227

2237 4117 1897 229

2161

1481

1897

1891

1893

Size in

Words

2

2

2

2

2

“Destination”

Recipe

Address

0

2

4

6

8

Silver Series OIT

 39 

Watlow Addendum

1) From the Objects menu choose Data

Transfer (Trigger-

based).

2) In Description type

“Recipe Save:” and the name of the name of the parameter

(such as “Loop 1 Set

Point”.

3) For Source address

PLC name choose

Modbus RTU Master or Modbus TCP/IP

Master.

4) For Source address choose 4x and enter the address of the parameter.

5) In No. of words type word size of the parameter’s data type. See Table.

6) Click Setting…

7) For Destination

address PLC name choose the OIT

(Local HMI by default).

Data Type

Float

16-bit integer

32-bit integer

No. of words

2

1

2

(060)

8) For Destination address Device type choose RW to store recipes in the battery backed up recipe word memory.

9) In Destination address Address type 0 for the first item in the recipe (Increment this by the previous item’s No of words for each subsequent recipe item. For example, if the first item was a 16-bit integer, the address of the second item is 1. If the second item is a float, the address of the third item is 3.)

10) If you want to store more than one recipe:

• Check Destination address Index register.

• For Destination address Index choose INDEX 0 (16-bit).

Silver Series OIT

 40 

Watlow Addendum

11) Click OK to close the Address dialog

12) For Mode choose External Trigger.

13) For Trigger address PLC name choose the OIT (Local HMI by default).

14) For Trigger address Device type choose LB to use an internal bit to cause the OIT to store values in a recipe.

15) In Trigger address Address type 500.

16) Click the Label tab.

17) Check Use label.

18) Set State to 0.

19) In Content type the name of the parameter.

20) Click OK.

21) Place the Data Transfer (Trigger-based) object on the screen.

Repeat the following steps to create the data transfer items that will load recipes in to the controller:

Note: For the data transfer objects that load the recipe from the OIT to the controller, the source addresses are RW (recipe words) addresses in the OIT and the destination addresses are the parameters’

Modbus addresses in the controller.

Parameter

Closed Loop Set Point

Alarm High Set Point

Heat Proportional Band

Integral

Derivative

*ST via RUI Gateway

“Source”

Recipe

Address

0

2

4

6

8

Size in

Words

2

2

2

2

2

“Destination” Address in Controller

RMC RMH PM ST ST GTW*

2501 5221 2161 22 2161

1741 2661 1481 98

2231 4111 1891 233

1481

1897

2235 4115 1895 227

2237 4117 1897 229

1891

1893

Silver Series OIT

 41 

Watlow Addendum

1) From the Objects menu choose Data

Transfer (Trigger-

based).

2) In Description type

“Recipe Load:” and the name of the parameter (such as

“Loop 1 Set Point”).

3) For Source address

PLC name choose the OIT.

4) For Source address choose RW and type the recipe address for the item.

(062)

5) If you set up the recipe save to use and index register:

• Click Source address Settings…

• Check Source address Index register

• For Source address Index choose INDEX 0 (16-bit).

• Click OK to close the Address dialog.

6) In No. of words type word size of the parameter’s data type.

7) For Destination address PLC name choose Modbus RTU Master or Modbus TCP/IP Master.

8) In Destination address Address choose 4x and enter the controller address of the parameter.

9) For Mode choose External Trigger.

10) For Trigger address PLC name choose the OIT (Local HMI by default).

11) For Trigger address Device type choose LB to use an internal bit to cause the OIT to load recipe values in to a controller.

12) In Trigger address Address type 501.

13) Click the Label tab.

14) Check Use label.

15) Enter the name of the parameter to display.

16) Click OK.

17) Place the Data Transfer (Trigger-based) object on the screen.

Silver Series OIT

 42 

Watlow Addendum

To create a button to trigger the data transfer objects to copy the values currently in the controller to the corresponding recipe memory in the OIT:

1) On the Objects menu, point to

Button and choose

Set Bit.

2) In Description type

“Save Recipe”.

3) For PLC name choose the OIT

(Local HMI by default).

4) For Address choose

LB and type 500.

(063)

5) For Set style Choose Momentary.

6) Click the Label tab.

7) Check Use label.

8) In Content for state 0 type “Save to OIT”.

9) Click OK.

10) Place the button.

To create a button to trigger the data transfer objects to copy the values currently in the OIT’s recipe memory to the controller:

1) On the Objects menu, point to Button and choose Set Bit.

2) In Description type “Load Recipe”.

3) For PLC name choose the OIT (Local HMI by default).

4) For Address choose LB and type 501.

5) For Set style Choose Momentary.

6) Click the Label tab.

7) Check Use label.

8) In Content for state 0 type “Load from OIT”.

9) Click OK.

10) Place the button.

Note: Using pictures for buttons may help operators.

Silver Series OIT

 43 

Watlow Addendum

Optional: To see what you are copying from the controller to the OIT’s recipe memory, create an object displaying the current value in the controller next to each Data Transfer (Trigger-based) object. Create a label that indicates what the fields are such as “Current Controller Values”.

Optional: To see or edit directly what is saved in recipe memory create a data entry object for each recipe item. These objects should display the values of the data in the RW memory at the recipe addresses. Create a label that indicates what the fields are such as “Recipe

Values”.

(068)

Optional: The values in the RW addresses are automatically saved in non-volatile memory every five minutes, but adding a button that momentarily sets LB-

9029 forces the values to be saved and can avoid lost data in the event the power is shut off too soon after editing a recipe.

Optional: If you want to store more than one recipe in the OIT, set up the data transfer objects to use indexing for the RW addresses.

(071)

Silver Series OIT

 44 

Watlow Addendum

Address indexing allows a screen object to display and set the value of different memory locations depending on the value in the index. In this example we use LW-9200 as the address index. Whatever value the index is set to is added to the address in the data transfer (and recipe display) objects. When the index value is zero, the first recipe is used. When the index is 10 the second recipe is used. When the index is 20 the third recipe is used. A multi-state switch is used to set the value of the index when the user selects the recipe.

Controller Memory

2161: (Lp 1 Set Point)

1481: (Lp 1 Hi Alarm)

1891: (Lp 1 Heat PB)

1895: (Lp 1 Integral)

1897: (Lp 1 Derivative)

Recipe Selector

Multi-State Switch

Address = LW 9200

“Recipe 1” = State 0 = 0

“Recipe 2” = State 1 = 10

“Recipe 3” = State 2 = 20

Data Transfer Objects

Data Transfer Object 1

(Lp 1 Set Point)

Address = RW 0 + index

Data Transfer Object 2

(Lp 1 Hi Alarm)

Address = RW 2 + index

Data Transfer Object 3

(Lp 1 Heat PB)

Address = RW 4 + index

Data Transfer Object 4

(Lp 1 Integral)

Address = RW 6 + index

Data Transfer Object 5

(Lp 1 Derivative)

Address = RW 8 + index

LW Memory

LW 9200: address index

RW Memory

Recipe 1 (index = 0)

RW 0: (Lp 1 Set Point)

RW 2: (Lp 1 Hi Alarm)

RW 4: (Lp 1 Heat PB)

RW 6: (Lp 1 Integral)

RW 8: (Lp 1 Derivative)

Recipe 2 (index = 10)

RW 10: (Lp 1 Set Point)

RW 12: (Lp 1 Hi Alarm)

RW 14: (Lp 1 Heat PB)

RW 16: (Lp 1 Integral)

RW 18: (Lp 1 Derivative)

Recipe 3 (index = 20)

RW 20: (Lp 1 Set Point)

RW 22: (Lp 1 Hi Alarm)

RW 24: (Lp 1 Heat PB)

RW 26: (Lp 1 Integral)

RW 28: (Lp 1 Derivative)

Note:

You can also use the address index to create one screen that displays data for one loop at a time with a multi-state switch or option list that allow users to switch from one loop to another.

Silver Series OIT

 45 

Watlow Addendum

To select the recipe to save to or load from create a multi-state switch to select the recipe as follows:

1) On the Objects menu point to Buttons and choose Multi-State

Switch.

2) In Description type

“Recipe Selector”.

3) Click Read address

Setting…

4) For PLC name choose the OIT

(Local HMI by default).

5) Check System tag.

6) For Device type choose LW-9200

(16bit) : address

index 0.

(069)

7) Click OK to close the Address dialog.

8) Click Write address

Setting…

9) For PLC name choose the OIT

(Local HMI by default).

10) Check System tag.

11) For Device type choose LW-9200 (16bit) : address index 0.

12) Click OK to close the Address dialog.

13) For Switch style choose JOG+.

14) For No. of states choose the number of recipes you want to store.

15) For Cyclical choose Enable.

16) Check User-defined mapping.

Silver Series OIT

 46 

Watlow Addendum

17) Click Set…

18) For each state enter the appropriate offset

Value. For state 0 enter 0. For state 1 enter a value that will offset the beginning of the second recipe beyond the end of the first in the recipe memory.

19) Click OK to close the State mapping window.

(070)

Note: The first recipe is selected with the multi-state switch in its state

0. This recipe stores its values in the memory locations you entered in the data transfer objects with no offset from address indexing, so for state 0 the Value is 0. Calculate the minimum offset for the second recipe by finding the sum of the number of words in memory used to store the items in one recipe. The second recipe (state 1 for the multistate switch) should set the offset to this sum. The third recipe (state 2) should set the offset to twice the sum. The fourth recipe (state 3) should set the offset to three times the sum. And so on.

20) Click the Label tab.

21) Check Use label.

22) In Content enter a label indicating which recipe is selected. (For state 0 type “Recipe 1”, for state 1 type “Recipe 2” etc.)

23) Click OK and place the Multi-State Switch object on the screen.

To create a button to save the recipes in non-volitile memory:

1) On the Objects menu point to Buttons and choose Set Bit.

2) In Description type “Save Recipes”.

3) Click Write address Setting…

4) For PLC name choose the OIT (Local HMI by default).

5) Check System tag.

6) For Device type choose LB-9029 : save all rcipe data to machine (set ON).

7) Click OK to close the Address dialog.

8) For Set style choose Momentary.

9) Click the Label tab.

10) Check Use label.

11) In Content enter, “Save Recipes”.

12) Click OK and place the Set Bit object on the screen.

Silver Series OIT

 47 

Watlow Addendum

How to Reach Us

Corporate Headquarters

Watlow Electric Manufacturing Company

12001 Lackland Road

St. Louis, MO 63146

Sales: 1-800-WATLOW2

Manufacturing Support: 1-800-4WATLOW

Email: [email protected]

Website: www.watlow.com

From outside the USA and Canada:

Tel: +1 (314) 878-4600

Fax: +1 (314) 878-6814

Europe

Watlow France

Tour d'Asnières.

4 Avenue Laurent Cély

92600 Asnières sur Seine

France

Tél: + 33 (0)1 41 32 79 70

Télécopie: + 33(0)1 47 33 36 57

Email: [email protected]

Website: www.watlow.fr

Watlow Ibérica, S.L.U.

C/Marte 12, Posterior, Local 9

E-28850 Torrejón de Ardoz

Madrid - Spain

T. +34 91 675 12 92

F. +34 91 648 73 80

Email: [email protected]

Website: www.watlow.es

Latin America

Watlow de México S.A. de C.V.

Av. Fundición No. 5

Col. Parques Industriales

Querétaro, Qro. CP-76130

Mexico

Tel: +52 442 217-6235

Fax: +52 442 217-6403

Watlow GmbH

Postfach 11 65, Lauchwasenstr. 1

D-76709 Kronau

Germany

Tel: +49 (0) 7253 9400-0

Fax: +49 (0) 7253 9400-900

Email: [email protected]

Website: www.watlow.de

Watlow Italy S.r.l.

Viale Italia 52/54

20094 Corsico MI

Italy

Tel: +39 024588841

Fax: +39 0245869954

Email: [email protected]

Website: www.watlow.it

Asia and Pacifi c

Watlow Singapore Pte Ltd.

16 Ayer Rajah Crescent,

#06-03/04,

Singapore 139965

Tel: +65 6773 9488 Fax: +65 6778 0323

Email: [email protected] Website: www.watlow.com.sg

Watlow UK Ltd.

Linby Industrial Estate

Linby, Nottingham, NG15 8AA

United Kingdom

Telephone: (0) 115 964 0777

Fax: (0) 115 964 0071

Email: [email protected]

Website: www.watlow.co.uk

From outside The United Kingdom:

Tel: +44 115 964 0777

Fax: +44 115 964 0071

Watlow Korea Co., Ltd.

#1406, E&C Dream Tower, 46, Yangpyeongdong-3ga

Yeongdeungpo-gu, Seoul 150-103

Republic of Korea

Tel: +82 (2) 2628-5770 Fax: +82 (2) 2628-5771

Website: www.watlow.co.kr

Watlow Australia Pty., Ltd.

4/57 Sharps Road

Tullamarine, VIC 3043

Australia

Tel: +61 3 9335 6449

Fax: +61 3 9330 3566

Website: www.watlow.com

Watlow Electric Manufacturing Company (Shanghai) Co. Ltd.

Room 501, Building 10, KIC Plaza

290 Songhu Road, Yangpu District

Shanghai, China 200433

China

Phone:

Local: 4006 Watlow (4006 928569)

International: +86 21 3381 0188

Fax: +86 21 6106 1423

Email: [email protected]

Website: www.watlow.cn

Watlow Malaysia Sdn Bhd

1F-17, IOI Business Park

No.1, Persiaran Puchong Jaya Selatan

Bandar Puchong Jaya

47100 Puchong, Selangor D.E.

Malaysia

Tel: +60 3 8076 8745 Fax: +60 3 8076 7186

Email: [email protected]

Website: www.watlow.com

瓦特龍電機股份有限公司

80143 高雄市前金區七賢二路189號 10樓之一

電話: 07-2885168 傳真: 07-2885568

Watlow Electric Taiwan Corporation

10F-1 No.189 Chi-Shen 2nd Road Kaohsiung 80143

Taiwan

Tel: +886-7-2885168 Fax: +886-7-2885568

Your Authorized Watlow Distributor

ワトロー・ジャパン株式会社

〒101-0047 東京都千代田区内神田1-14-4

四国ビル別館9階

Tel: 03-3518-6630 Fax: 03-3518-6632

Email: [email protected] Website: www.watlow.co.jp

Watlow Japan Ltd.

1-14-4 Uchikanda, Chiyoda-Ku

Tokyo 101-0047

Japan

Tel: +81-3-3518-6630 Fax: +81-3-3518-6632

Email: [email protected] Website: www.

watlow.co.jp

TOTAL

CU ST ER

S ATIS CTIIO N

3 Year Warranty

advertisement