RemoDAQ-8054
V1.1 2010.2.2
User’s Manual
Beijing Gemotech Intelligent Technology Co.,Ltd
RemoDAQ-8054 User’s Manual
Copyright Notice
This document is copyrighted, 2005, by Beijing
Gemotech Intelligent Technology Co.,Ltd
All rights are reserved. Beijing Gemotech Intelligent
Technology Co. , Ltd reserves the right to make improvements to the products described in this manual at any time without notice.
No part of this manual may be reproduced, copied, translated or transmitted in any form or by any means without the prior written permission of Beijing Gemotech Intelligent
Technology Co.,Ltd. Information provided in this manual is intended to be accurate and reliable. However, Beijing
Gemotech Intelligent Technology Co.,Ltd assumes no responsibility for its use, or for any infringements upon the rights of third parties, which may result from its use.
Acknowledgments
RemoDAQ is a trademark of Beijing Gemotech
Intelligent Technology Co.,Ltd.
Edition 1.1
Feb. 2009
1
RemoDAQ-8054 User’s Manual
Additional Information and Assistance
1. Visit the gemotech websites at www. gemotech. cn where you can find the latest information about the product.
2. Contact your distributor, sales representative, or
gemotech 's customer service center for technical support if you need additional assistance. Please have the following information ready before you call: z Product name and serial number z Description of your peripheral attachments z Description of your software (operating system, version,application software, etc.) z A complete description of the problem z The exact wording of any error messages
2
RemoDAQ-8054 User’s Manual
Table of Contents
1 Introduction .............................................................................................. 4
1.1 Pin Assignment & Specifications .............................................. 4
1.2 Block Diagram ........................................................................... 5
1.3 Application Wiring .................................................................... 5
1.4 Default Setting ........................................................................... 6
1.5 Jumper Setting............................................................................ 6
1.6 Install List .................................................................................. 6
2 Initialization & Installation ...................................................................... 7
2.1 Installation Guideline ................................................................. 7
2.2 Software Installation .................................................................. 7
2.3 Basic configuration and hook-up ............................................... 8
2.4 Baudrate and Checksum .......................................................... 10
3 Command Set ......................................................................................... 12
3.1 %AANNTTCCFF .................................................................... 15
3.2 $AA2 ........................................................................................ 17
3.3 $AA6 ........................................................................................ 18
3.4 $AAF ........................................................................................ 19
3.5 $AAM ...................................................................................... 20
3.6 @AA ........................................................................................ 21
3.7 ~AAO(Data)............................................................................. 22
3
RemoDAQ-8054 User’s Manual
1 Introduction
The RemoDAQ-8000 Series is a set of intelligent sensor to computer interface modules containing built in microproces- sor. They are remotely controlled through a simple set of commands issued in ASCII format and transmitted in RS-485 protocol. They provide signal conditioning, isolation, ranging,
A/D and D/A conversion, data comparison, digital commun- ication, timer/counter, wireless communication, collection
AC and other functions.
RemoDAQ-8054 is the 8-channel cable
ON/OFF
detecti- on module that are used in telecommunications profession specially, LED shows the
ON/OFF
state of 8-channel cable, each channel has a LED state of instructing this road. When cable shorts , LED OFF;When cable broken road, LED ON.
Its power supply also with other module
is difference, for
44~58Vdc.
1.1 Pin Assignment & Specifications
Channel:8
Power:44V~58VDC
Power consumption:1.6W
Operating Temperature:-20 ~ 70° C
Humidity:5 ~ 95%, non-condensing
4
RemoDAQ-8054 User’s Manual
1.2 Block Diagram
1.3 Application Wiring
Dry Contact Input
5
RemoDAQ-8054 User’s Manual
1.4 Default Setting
z Address:01 z Baudrate:9600 bps z Type:40 z
Checksum disable z JP1 disconnection:disconnection INIT* pin with the
GND pin,natural work mode
1.5 Jumper Setting
JP1:Select INIT* pin with the GND pin whether connect
Disconnection:Don’t connect INIT* pin with the GND pin
Connection:Connect INIT* pin with the GND pin
1.6 Install List
Baudrate Setting (CC)
Type Setting (TT)
Type=40
Data format setting(FF)
7 6 5 4 3 2 1 0
0 *1 0
*
1:Checksum:0=Disabled 1=Enable
Read DIO data format
(Data1)(Data2)
@AA Data:
RemoDAQ-8054 DI(0-7) 00 ~ FF 00 00
6
RemoDAQ-8054 User’s Manual
2 Initialization & Installation
2.1 Installation Guideline
Figure 2-1 Power Supply Connections
We advise that the following standard colors (as indicated on the modules) be used for power lines:
+Vs (R) Red
GND (B) Black
We advice that the following standard colors (as indicated on the modules) be used for the communication lines:
DATA+ (Y) Yellow
DATA- (G) Green
2.2 Software Installation
1. If you have already installed “RemoDAQ-8000 Utility” then skip other steps.
2. Backup your software diskette.
3. Insert “RemoDAQ-8000 Utility” disc into CD-ROM:
4. Change drive to the path of CD-ROM. For example,
7
RemoDAQ-8054 User’s Manual your drive of CD-ROM is F:then change the drive to F:
5. Find the setup of “RemoDAQ-8000 Utility” and run it.
6. Please follow the steps of setup program then you can successfully install the RemoDAQ-8000 Utility
2.3 Basic configuration and hook-up
Before placing a module in an existing network, the module should be configured. Though all modules are initially configured at the factory, it is recommended to check that the baud rate is set correctly.
Default Factory Settings
Baud rate: 9600 Bit/sec.
Address: 01 (hexadecimal)
Checksum:disable
The basic hook-up for module configuration is shown below.
Figure 2-2 Layout for Initialization the RemoDAQ module
The following items are required to configure a module:a
8
RemoDAQ-8054 User’s Manual
RemoDAQ converter module, a personal computer with RS-
232 port (baudrate set to 9600) and theRemoDAQ utility software.
Configuration with the RemoDAQ Utility Software
The easiest way to configure the RemoDAQ module is by using the RemoDAQ utility software:an easy-to-use menu- structured program will guide you through every step of the configuration.
Configuration with the RemoDAQ command set
RemoDAQ modules can also be configured by issuing direct commands from within a terminal emulation program that is part of the RemoDAQ utility software.
The following example guides you through the setup of an analog input module. Assume that RemoDAQ-8054 still has its default settings (baud rate 9600 and address 01h). Before the module is reconfigured, it is first requested to send its default settings.
To change the configuration setting of the analog input module, the following command is issued:
%0107400600(cr)
% = change configuration
01 = target module at address 00 to:
07 = change address to 07 hexadecimal
40 = set input range to Type 40
06 = set baud rate to 9600
00 = set integration time to 50 ms (60 Hz) disable checksum set data format to engineering units
9
RemoDAQ-8054 User’s Manual
(See Chapter 3, Command Set for a full description of the syntax of the configuration command for module)
When the module received the configuration command it will respond with its new address:!07(cr)
NOTICE: All reconfiguration except changing of baud rate
and checksum values can be done dynamically, i.e. the modules need not to be reset. When changing the baud rate or checksum, these changes should be made for all connected devices. After reconfiguration, all modules should be powered down and powered up to force a reboot and let the changes take effect.
2.4 Baudrate and Checksum
RemoDAQ modules contain EEPROMs to store configuration information and calibration constants. The
EEPROM replaces the usual array of switches and pots required to specify baudrate, input/output range etc.
All of the RemoDAQ modules can be configured remotely through their communication ports, without having to physically alter pot or switch settings.
Forcing the module in the INIT* state does not change any parameters in the module’s EEPROM. When the module is in the INIT* state with its INIT* and GND terminals shorted, all configuration settings can be changed and the module will respond to all other commands normally.
Changing Baud rate and Checksum
10
RemoDAQ-8054 User’s Manual
Baud rate and checksum settings have several things in common:
¾ They should be the same for all modules and host computer.
¾ Their setting can only be changed by putting a module in the
INIT* state.
¾
Changed settings can only take effect after a module is rebooted
To alter baudrate or checksum settings you must perform the following steps:
¾ Power on all components except the RemoDAQ Module.
¾ Power the RemoDAQ module on while shorting the
INIT* and GND terminals
¾ Wait at least 7 seconds to let self calibration and ranging take effect.
¾ Configure the checksum status and/or the baud rate.
¾ Switch the power to the RemoDAQ Module OFF.
¾ Remove the grounding of the INIT* terminal and power the module on.
¾ Wait at least 7 seconds to let self calibration and ranging take effect.
¾ Check the settings (If the baud rate has changed, the settings on the host computer should be changed accordingly.)
11
RemoDAQ-8054 User’s Manual
3 Command Set
Introduction
To avoid communication conflicts when several devices try to send data at the same time, all actions are instigated by the host computer. The basic form is a command/response protocol with the host initiating the sequence.
When modules are not transmitting they are in listen mode.
The host issues a command to a module with a specified address and waits a certain amount of time for the module to respond. If no response arrives, a timeout aborts the sequence and returns control to the host.
Changing RemoDAQ’s configuration might require the module to perform auto calibration before changes can take effect. Especially when changing the range, the module has to perform all stages of auto calibration that it also performs when booted. When this process is under way, the module does not respond to any other commands.
The command set includes the exact delays that might occur when modules are reconfigured.
Syntax
[delimiter character][address][command][data][checksum]
[carriage return]
Every command begins with a delimiter character. There are four valid characters:a dollar sign $, a pound sign #, a percentage sign % and an at sign @.
12
RemoDAQ-8054 User’s Manual
The delimiter character is followed by a two-character address (hexadecimal) that specifies the target module. The actual two-character command follows the address.
Depending on the command, an optional data segment follows the command string. An optional two character checksum may be appended to the total string. Every command is terminated by a carriage return (cr).
Calculate Checksum:
1. Calculate ASCII sum of all characters of command(or response) string except the character return(cr).
2. Mask the sum of string with 0ffh.
Example:
Command string:$012(cr)
Sum of string=‘$’+‘0’+‘1’+‘2’=24h+30h+31h+32h=B7h
The checksum is B7h,and [CHK] = “B7”
Command string with checksum:$012B7(cr)
Response string:!01200600(cr)
Sum of string:‘!’+‘0’+‘1’+‘2’+‘0’+‘0’+‘6’+‘0’+‘0’
=1h+30h+31h+32h+30h+30h+36h+30h+30h=1AAh
The checksum is AAh,and [CHK] = “AA”
Response string with checksum:!01200600AA(cr)
13
RemoDAQ-8054 User’s Manual
General Command Sets
Command Syntax Command Name Command Description
Sets the address,input range,
%AANNTTCCFF Configuration baudrate,dataformat,checksum status
$AA6
$AAF
$AAM
@AA Dight I/O status
Return the configuration parameters for the module
Digital I/O value
Returns the values of the digital I/O channel in the addressed module
Read firmware version
Return the firmware version code
Read module name Return the module name
Returns the status of the digital I/O channel in the addressed module.
Notes
3.1
3.2
3.3
3.4
3.5
3.6
3.7
14
RemoDAQ-8054 User’s Manual
3.1 %AANNTTCCFF
Name:Configuration
Description:Sets address, type code, baudrate, data format
Syntax:%AANNTTCCFF(cr)
% delimiter character.
AA address of setting module (00-FF)
NN New address (00-FF)
TT New type
CC New baudrate
FF New data format
When changing baudrate or checksum, we should INIT* termination land.
7
6 5 4 3 2 1 0
Not used
Checksum status
0: Disable
1: Enable
Figure 3-1 Data format setting of AI modules
Response:!AA(cr) if the command was valid.
?AA(cr) if an invalid operation was entered. If the INIT* terminal was not grounded when attempting to change baud rate or checksum settings.
Syntax error or communication error may get no response.
! command is valid.
15
RemoDAQ-8054 User’s Manual
? command is invalid.
AA address of setting module (00-FF)
(cr) is the terminating character, carriage return (0Dh)
Example:
Command:%0102400600(cr) Response:!02(cr)
Change address from 01 to 02,type 40 , baud rate 9600, integration time 50 ms (60 Hz), engineering units data format and no checksum checking or generation.
The response indicates that the command was received.
Table 3-1 Input Rang Codes (Type Code)
TT=40
Table 3-2 Baudrate Code
16
RemoDAQ-8054 User’s Manual
3.2 $AA2
Name:Configuration Status
Description:
The command requests the return of the configuration data from the analog input module at address AA.
Syntax:$AA2(cr)
$ delimiter character.
AA address of reading module(00~FF)
2 the Configuration Status command.
(cr) the terminating character, carriage return (0Dh).
Response:!AATTCCFF(cr) if the command is valid.
?AA(cr)if an invalid operation was entered.
Syntax error or communication error may get no response.
! command is valid.
? command is invalid.
AA address of module(00~FF)
TT represents the type code.
CC represents the baud rate code.
FF data format
(Also see the %AANNTTCCFF configuration command)
Example:
Command:$012 Response:!01400600
Read address 01 configuration,return success.
17
RemoDAQ-8054 User’s Manual
3.3 $AA6
Name:Read Digital I/O Value
Description:Asks a specified input module to return the status of the digital I/O channel.
Syntax:$AA6 (cr)
$ delimiter character.
AA address of reading module(00~FF)
6 read digital I/O statues command.
(cr) is the terminating character, carriage return (0Dh).
Response:!(data)(cr) if the command is valid.
?AA(cr) if an invalid operation was entered.
Syntax error or communication error may get no response.
! command is valid.
? command is invalid. data digital input/output value
Example:
Command:$016 Response:!0F0000
Read address 01 DIO state,return 0F0000
18
RemoDAQ-8054 User’s Manual
3.4 $AAF
Name:Read Firmware Version
Description:The command requests the module at address
AA to return the version code of its firmware.
Syntax:$AAF (cr)
$ delimiter character.
AA address of reading module(00~FF)
F identifies the version command.
(cr) is the terminating character, carriage return (ODh)
Response: !AA(data)(cr) if the command is valid.
?AA (cr) if an invalid command was issued.
Syntax error or communication error may get no response.
! command is valid.
? command is invalid.
AA address of response module(00~FF)
Data is the version code of the module’s firmware.
Example:
Command:$01F Receive:!0120051201
Read address 01 firmware version,return version 20051201
Command:$02F Receive:!0120040101
Read address 02 firmware version,return version 20040101
19
RemoDAQ-8054 User’s Manual
3.5 $AAM
Name:Read Module Name
Description:The command requests the module at address
AA to return its name.
Syntax:$AAM (cr)
$ delimiter character.
AA address of reading module(00~FF)
M the Read Module Name command.
(cr) is the terminating character, carriage return (ODh)
Response:!AA(data)(cr) if the command is valid.
?AA(cr) if an invalid command was issued.
Syntax error or communication error may get no response.
! command is valid.
? command is invalid.
AA address of response module(00~FF)
data the name of the module
Example:
Command:$01M Receive:!018054
Read address 01 module name,return name 8054.
20
RemoDAQ-8054 User’s Manual
3.6 @AA
Name:Read Digital I/O Status
Description:The addressed of module is instructed to return the value of its DI/O channels.
Syntax:@AA (cr)
@ delimiter character.
AA address of reading module(00~FF)
(cr) represents terminating character, carriage return (0Dh).
Response:>(data)(cr) if the command was valid
?AA(cr) if an invalid command was issued.
Syntax error or communication error may get no response.
! command is valid.
? command is invalid. data DIO status
Example:
Command:@01 Receive:>0F00
Read address 01 DIO state,return0F00,express Cable0-
Cable3 channel open circuit,Cable4-Cable7 channel short circuit
21
RemoDAQ-8054 User’s Manual
3.7 ~AAO(Data)
Name:Set Module Name
Description:Set the module name and return
success or error.
Syntax:~AAO(Data) (cr)
$ delimiter character.
AA address of setting module(00~FF)
O Set Module Name command.
Data new name for module,max 6 characters
(cr) is the terminating character, carriage return (ODh)
Response:!AA(cr) if the command is valid.
?AA(cr) if an invalid command was issued.
Syntax error or communication error may get no response.
! command is valid.
? command is invalid.
AA address of response module(00~FF)
Example:
Command:~01O8054 Receive:!01
Set address 01 module name to 8054,return success.
Command:$01M Receive:!018054
Read address 01 module name,return 8054.
22
advertisement