V680 Series ID Sensor Units User's Manual


Add to my manuals
213 Pages

advertisement

V680 Series ID Sensor Units User's Manual | Manualzz
RFID System
V680 Series
User’s Manual
ID Sensor Units
CS1W-V680C11
CS1W-V680C12
CJ1W-V680C11
CJ1W-V680C12
P
ER
H
ER D2
A
HE
T/R RR
1
C1
80
V6 RUN
C
ER 1
AD
HE /R
T
/E
RM
NO
P
ER
H
ER D2
A
HE
T/R RR
2
C1
80
V6 RUN
C
ER 1
AD
HE /R
T
/E
RM
NO
R
R
/ER
/ER
RM
RM
NO
NO
ST
ST
TE
TE
ON
ON
1
AD
AD
HE
HE
2
AD
HE
V
24
DC UT
P
IN
+
-
Man. No.: Z271-E1-05
Introduction
Thank you for purchasing an ID Sensor Unit for a V680/V680S-series RFID System. This manual describes
the functions, performance, and application methods needed for optimum use of your V680/V680S-series
RFID System.
Please observe the following items when using the V680/V680S-series RFID System.
• Allow the V680/V680S-series RFID System to be installed and operated only by qualified specialist with a
sufficient knowledge of electrical systems.
• Read and understand this manual before attempting to use the V680/V680S-series RFID System and use
the V680/V680S-series RFID System correctly.
• Keep this manual in a safe and accessible location so that it is available for reference when required.
READ AND UNDERSTAND THIS DOCUMENT
Section 1 Features and System Configuration
Introduction SECTION 1
Introduction
Section 2 CS-series ID Sensor Units
SECTION 2
Section 3 CJ-series ID Sensor Units
SECTION 3
Section 4 Data Exchange with the CPU Unit
SECTION 4
Section 5 ID Sensor Unit Functions
SECTION 5
Section 6 Controlling the ID Sensor Unit
SECTION 6
Section 7 Troubleshooting Alarms and Errors
SECTION 7
Section 8 Appendices
SECTION 8
RFID System
CS1W-V680C11
CS1W-V680C12
CJ1W-V680C11
CJ1W-V680C12
ID Sensor Unit
ID Sensor Unit
ID Sensor Unit
ID Sensor Unit
User's Manual
Introduction
Introduction
READ AND UNDERSTAND THIS DOCUMENT
Please read and understand this document before using the products. Please consult your OMRON representative if you have any questions or comments.
WARRANTY
OMRON’s exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)
from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS IN
ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY.
In no event shall responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON’S
ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
SUITABILITY FOR USE
THE PRODUCTS CONTAINED IN THIS DOCUMENT ARE NOT SAFETY RATED. THEY ARE NOT DESIGNED OR RATED FOR ENSURING SAFETY OF
PERSONS, AND SHOULD NOT BE RELIED UPON AS A SAFETY COMPONENT OR PROTECTIVE DEVICE FOR SUCH PURPOSES. Please refer to separate catalogs for OMRON's safety rated products.
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer’s application or use of the product.
At the customer’s request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product, machine,
system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible uses
of the products, nor is it intended to imply that the uses listed may be suitable for the products:
• Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this document.
• Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles, safety
equipment, and installations subject to separate industry or government regulations.
• Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM
AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT IS PROPERLY RATED AND INSTALLED FOR THE
INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PERFORMANCE DATA
Performance data given in this document is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the
result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON Warranty
and Limitations of Liability.
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made. However,
some specifications of the product may be changed without any notice. When in doubt, special model numbers may be assigned to fix or establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical,
or proofreading errors, or omissions.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user’s programming of a programmable product, or any consequence thereof.
COPYRIGHT AND COPY PERMISSION
This document shall not be copied for sales or promotions without permission. This document is protected by copyright and is intended solely for use in conjunction with the product. Please notify us before copying or reproducing this document in any manner, for any other purpose. If copying or transmitting this
document to another, please copy or transmit it in its entirety.
2
RFID System
User's Manual
Introduction
Introduction
Safety Precautions
 Signal Words Used in This Manual
The following signal words and symbols are used in this manual to indicate precautions that must be observed
to ensure safe use of the V680-series ID Sensor Unit. The precautions provided here contain important safety
information. You must observe these precautions.
The following signal words and symbols are used in this manual.
WARNING
Indicates a potentially hazardous situation which, if not avoided, will result in minor or
moderate injury, or may result in serious injury or death. Additionally there may be
significant property damage.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in minor
or moderate injury or in property damage.
 Meanings of Alert Symbols
General Caution
Indicates general cautionary, warning, or danger level information.
Electrical Shock Caution
Indicates possibility of electric shock under specific conditions.
General Prohibition
Indicates a general prohibition.
Disassembly Prohibition
Indicates that disassembly is prohibited to prevent electric shock.
General Mandatory Action
Indicates a general action that must be performed by the user.
RFID System
User's Manual
3
Introduction
Introduction
 Warnings
WARNING
Never attempt to disassemble any Units while power is being supplied. Doing so may result in
serious electrical shock or electrocution.
Never touch any of the terminals while power is being supplied. Doing so may result in
serious electrical shock or electrocution.
Provide safety measures in external circuits, l.e., not in the PLC (CPU Unit including associated Units), in
order to ensure safety in the system if an abnormality occurs due to malfunction of the PLC or another
external factor affecting the PLC operation. Not doing so may result in serious accidents.
Emergency stop circuits, interlock circuits, limit cuicuits, and similar safety measures must be provided in
external control circuits.
The PLC will turn OFF all outputs when its self-diagnosis function detects any error or when a severe failure
alarm (FALS) instruction is executed. As a countermeasure for such errors, external safety measures must
be provided to ensure safety in the system.
The PLC outputs may remain ON or OFF due to deposition or burning of the output relays or
destruction of the output transistors, As a countermeasure for such problems, external
safety measures must be provided to ensure safety in the system.
This Product is not designed or rated for ensuring safety of persons. Do not use it for such
purposes.
CAUTION
Execute online edit only after confirming that no adverse effects will be caused by extending
the cycle time. Otherwise, the input signals may not be readable.
4
RFID System
User's Manual
Introduction
Introduction
Precautions for Safe Use
Be sure to observe the following precautions to ensure safe use of the Product.
1. Do not attempt to disassemble, repair, or modify the Product.
2. Tighten the Backplane mounting screws and terminal block screws securely.
3. Be sure to use crimp terminals of the specified size for wiring.
4. If any cable has a locking mechanism, make sure that it has been locked before using the cable.
5. Make sure the power supplied by the DC Power Supply Unit is within the rated power supply voltage
(24 VDC +10%/15%) before using the Product.
6. When using the CS1W-V680C12, make sure the power supplied by the DC power supply for external
inputs is within the rated power supply voltage (24 VDC +10%/15%) before using the Product.
7. Do not connect the power supply in reverse.
8. Use crimp terminals for wiring. Do not connect bare stranded wires directly to terminals.
9. Do not allow water or wires to enter the Product through gaps in the case. Otherwise, fire or electric shock
may occur.
10. Turn OFF the power to the Product before attaching or removing an Amplifier or Antenna.
11. If multiple Antennas are mounted near each other, communications performance may decrease due to
mutual interference. Refer to information on installing Antenna in the RFID System V680 Series User's
Manual for Amplifiers, Antennas, and RF Tags (FRAM) (Cat. No. Z248), V680 Series RFID System
Amplifier/RF Tags (EEPROM) User's Manual (Cat. No. Z262), and Heat-resistive RFID System V680
Series User's Manual (Cat. No. Z221) and check to make sure there is no mutual interference.
12. If an error is detected in the Product, immediately stop operation and turn OFF the power supply. Consult
with an OMRON representative.
13. Dispose of the Product as industrial waste.
14. Observe all warnings and precautions given in the body of this manual.
15. Do not use thinners, benzenes, acetones, and kerosenes for cleaning.
RFID System
User's Manual
5
Introduction
Introduction
Precautions for Correct Use
Always observe the following precautions to prevent operation failure, malfunctions, and adverse effects on
performance and equipment.
1. Installation Environment
Do not use the Product in the following locations.
• Locations exposed to any flammable, explosive, or corrosive gasses
• Locations exposed to dust, metallic powder, or salts
• Locations not within the specified operating temperature range
• Locations subject to rapid changes in temperature or condensation
• Locations not within the specified operating humidity range
• Locations subject to direct vibration or shock outside the specified ranges
• Locations subject to spray of water, oil, or chemicals
2. Installation
• This Product uses a frequency band of 13.56 MHz to communicate with RF Tags. Some transceivers,
motors, inverters, switching power supplies, etc., generate electrical noise that will affect these communications. If any of these devices are located in the vicinity of the Product, they may affect
communications with RF Tags, and may possibly damage the RF Tags. Prior to using the Product in
the vicinity of any of these devices, perform a test to determine whether the Product can be used
under the resulting influence.
• Observe the following precautions to minimize the effects of normal noise.
(1) Ground the ground terminal on the Product and all metal objects in the vicinity of the Product to
100 or less.
(2) Do not use the Product near high-voltage or high-current lines.
• The Product is not waterproof. Do not use it in an environment where mist is present.
• Do not expose the Product to chemicals that adversely affect the Product materials.
• Use a tightening torque of 0.4 Nm hen mounting the Product.
3. Storage
• Locations exposed to any flammable, explosive, or corrosive gasses
• Locations exposed to dust, metallic powder, or salts
• Locations not within the specified operating temperature range
• Locations subject to rapid changes in temperature or condensation
• Locations not within the specified operating humidity range
• Locations subject to direct vibration or shock outside the specified ranges
• Locations subject to spray of water, oil, or chemicals
6
RFID System
User's Manual
Introduction
Introduction
Precautions for Users of V600-series ID Sensor Units
Precautions for Users of V600-series ID Sensor Units
 Differences between the V600-series and V680-series ID Sensor Units
The following features were added to the V680-series ID Sensor Units in comparison to the V600series Units. Functions are upwardly compatible, so V600-series Units can be easily replaced with
V680-series Units.
Commands
• Read with Error Correction
• Write with Error Correction
• UID Read
• Noise Measurement
Communications specifications
• FIFO trigger
• FIFO repeat
• Multi-access trigger
• Multi-access repeat
DM Area settings
• UID Addition Setting
• Write Protection Disable Setting
• Antenna Connection Setting (V680-H01)
• Results Monitor Output Setting
• Test Operation Setting
• Run/Test Switching Method Setting
Test Operations
(Set in the DM Area)
• Range level measurement
• Read/Write speed level measurement
• Noise level measurement
• Communications success rate measurement
CIO Area outputs
Run/Test Bit
(Only when using the Run/Test Switching Method Setting is enabled in the DM Area.)
CIO Area inputs
• Antenna Error Flag (9C)
• ID System Error 1 (79)
• ID System Error 2 (7E)
• ID System Error 3 (7F)
• Error Correction Flag (77)
• Results Output Monitor
Run Mode: Communications time or noise level
Test Mode: Result contents of tests
Others
If a command error or data storage area error occurs in a V600-series ID Sensor Unit, the
Error End Flag will not be turned ON. With a V680-series ID Sensor Unit, the Error End Flag
will be turned ON for these errors.
 FIFO trigger, FIFO repeat, Multi-access trigger, and
Multi-access repeat specification cannot be used for
communicating with V680-D1KP@@ RF Tags.
With a V600-series ID Sensor Unit, command errors and data storage errors are not monitored in the Processing Results Monitor, but a V680-series ID Sensor Unit will monitor them
and use an error code of E014.
RFID System
User's Manual
7
Introduction
Introduction
Meanings of Symbols
8
Meanings of Symbols
Indicates particularly important points related to a function, including precautions and application advice.
Indicates page numbers containing relevant information.
Indicates reference to helpful information and explanations for difficult terminology.
RFID System
User's Manual
Introduction
Introduction
Table of Contents
Introduction
1
Safety Precautions
3
Precautions for Safe Use
5
Precautions for Correct Use
6
Precautions for Users of V600-series ID Sensor Units
7
Meanings of Symbols
8
Table of Contents
9
Features and System Configuration
11
Outline of Features and Functions
12
Using Heat-resistive RF Tags (V680-D1KP58HTN and V680-D1KP58HT)
15
Using V680S-D8KF@@ RF Tags
20
System Configuration
21
Functions by Application
27
CS-series ID Sensor Units
29
Specifications
30
Operating Procedure
32
Part Names and Functions
38
Connections and Wiring
41
CJ-series ID Sensor Units
45
Specifications
46
Operating Procedure
48
Part Names and Functions
54
Connections and Wiring
57
Data Exchange with the CPU Unit
61
Outline of Data Exchange
62
Initial Settings Data
65
I/O Data Allocations
67
RFID System
User's Manual
9
Introduction
Introduction
ID Sensor Unit Functions
Operating Modes
78
Communications Specifications
85
Parameter Settings in DM Area
93
RF Tag Memory
99
Write Protection
101
RF Tag Service Life Check
108
RF Tag Memory Check
112
RF Tag Memory Error Correction
114
Controlling the ID Sensor Unit
117
ID Sensor Unit Operation
118
Communications Commands
125
Communications Time
141
Troubleshooting Alarms and Errors
145
Indicators and Error Check Flowcharts
146
ID Sensor Unit Alarms
148
CPU Unit Errors
151
Restarting Special I/O Units
152
Troubleshooting
153
Appendices
157
Dimensions
158
Sample Programming
160
Data Coding Tables
204
Degree of Protection
208
Revision History
10
77
RFID System
User's Manual
210
SECTION 1
SECTION 1
Features and System Configuration
12
Using Heat-resistive RF
Tags (V680-D1KP58HTN and V680-D1KP58HT)
15
Using V680S-D8KF@@ RF Tags
20
System Configuration
21
Functions by Application
27
RFID System
User's Manual
Features and System Configuration
Outline of Features and Functions
11
SECTION 1
Features and System Configuration
Outline of Features and Functions
• SYSMAC CS-series ID Sensor Units
SECTION 1
One-channel ID Sensor Unit
Two-channels ID Sensor Unit
(CS1W-V680C11)
(CS1W-V680C12)
Outline of Features and Functions
V680C11
RUN
ERC
ERP
ERH
T/R
V680C12
RUN
ERC
HEAD1
T/R
ERP
ERH
HEAD2
T/R
NORM/ERR
NORM/ERR
TEST
NORM/ERR
TEST
ON
ON
HEAD1
HEAD
HEAD2
DC24V
INPUT
These ID Sensor Units are used in SYSMAC CS-series PLCs to read and write data for V680-series RF Tags.
There are two models: a One-channel ID Sensor Unit (CS1W-V680C11) and a Two-channels ID Sensor Unit
(CS1W-V680C12).
12
RFID System
User's Manual
SECTION 1
Features and System Configuration
• SYSMAC CJ-series ID Sensor Units
Two-channels ID Sensor Unit
(CJ1W-V680C11)
(CJ1W-V680C12)
SECTION 1
One-channel ID Sensor Unit
Outline of Features and Functions
These ID Sensor Units are used in SYSMAC CJ-series PLCs to read and write data for V680-series RF Tags.
There are two models: a One-channel ID Sensor Unit (CJ1W-V680C11) and a Two-channels ID Sensor Unit
(CJ1W-V680C12).
CS1W-V680C11
CS1W-V680C12
Amplifier/
Antennas
V680 Series (V680-HA63@/V680-H@@)
Maximum
number of
connected
Antennas
1
2
RF Tags
V680 Series (V680-D@@F@@ or V680-D@@P@@)
Commands
Read
Write
Bit Set
Bit Clear
Mask Bit Write
Calculation Write
Data Fill
Data Check
Number of Writes Control
Read with Error Correction
Write with Error Correction
UID Read
Noise Measurement
Read
Write
Bit Set
Bit Clear
Mask Bit Write
Calculation Write
Data Fill
Data Check
Number of Writes Control
Copy
Read with Error Correction
Write with Error Correction
UID Read
Noise Measurement
CJ1W-V680C11
CJ1W-V680C12
1
2
Read
Write
Bit Set
Bit Clear
Mask Bit Write
Calculation Write
Data Fill
Data Check
Number of Writes Control
Read with Error Correction
Write with Error Correction
UID Read
Noise Measurement
Read
Write
Bit Set
Bit Clear
Mask Bit Write
Calculation Write
Data Fill
Data Check
Number of Writes Control
Copy
Read with Error Correction
Write with Error Correction
UID Read
Noise Measurement
• An RFID system consists of an ID Sensor Unit in a CS-series/CJ-series CPU Rack or CS-series/CJ-series
Expansion Rack, one or two Antennas connected to the ID Sensor Unit, and RF Tags connected to moving
bodies.
• The ID Sensor Unit operates through the Antennas to write data from the CS/CJ-series CPU Unit to the RF
Tags and read data from the RF Tags to the CS/CJ-series CPU Unit.
RFID System
User's Manual
13
SECTION 1
Features and System Configuration
■ Differences between Version 1.2 and Pre-Version 1.2
The following functions have been added to version 1.2 in comparison to pre-version 1.2. Functions are
upwardly compatible, so pre-version 1.2 can be replaced with version 1.2.
SECTION 1
 CA1D Mode Setting Added for RF Tag Memory
If you are using a V680-CA1D/-CA2D ID Controller, always set the RF Tag memory setting to CA1D
Outline of Features and Functions
Mode. Setting the RF Tag memory setting to CA1D Mode enables reading and writing Heat-resistant
RF Tags (V680-D1KP58HTN and V680-D1KP58HT) that were written by the V680-CA1D/-CA2D.
 New Data Transfer Setting
In addition to cyclically transferring 160 bytes/scan, Intelligent I/O Instructions can now be used to
transfer up to 2,048 bytes in one scan.
 Parameters Added to Data Memory Allocation
DM Area allocations now include a RF Tag memory setting and data transfer setting.
Refer to DM Area Allocations and Contents on page 65 for details on the DM Area.
p. 65
A label on the side of the ID Sensor Unit shows the version for Units with version 1.2 or newer.
• CJ1W-V680C1@
• CS1W-V680C1@
Version
Version
A different memory map may be used when reading or writing Heat-resistant RF Tags that were written by the V680CA1D/-CA2D from a Reader/Writer that is manufactured by a company other than OMRON. Refer to Operation When
RF Tag Memory Setting Is Set to Standard Mode in this section.
p. 18
14
RFID System
User's Manual
SECTION 1
Features and System Configuration
This section provides information for using Heat-resistive RF Tags (V680-D1KP58HTN or V680-D1KP58HT).
If you are not using a Heat-resistive RF Tag, set the RF Tag memory setting to Standard Mode.
If you are using Heat-resistive RF Tags (V680-D1KP58HTN or V680-D1KP58HT), write the data again
after saving data at a high temperature even if it is not necessary to change the data. A "high temperature" is one between 110C and 200C.
Using a Controller for a Heat-resistant RFID System (V680CA1D/-CA2D)
If you are using Heat-resistive RF Tags (V680-D1KP58HTN or V680-D1KP58HT) and also using a
V680-CA1D/-CA2D ID Controller, set the RF Tag memory setting of the ID Sensor Unit (version 1.2 or
newer) to CA1D Mode.
A label on the side of the ID Sensor Unit shows the version for Units with version 1.2 or newer.
• CJ1W-V680C1@
• CS1W-V680C1@
Version
Version
Using Heat-resistive RF Tags (V680-D1KP58HTN and V680-D1KP58HT)
Precautions for Saving Data at High Temperatures
SECTION 1
Using Heat-resistive RF Tags (V680-D1KP58HTN
and V680-D1KP58HT)
If you are not using the V680-CA1D/-CA2D, the RF Tag memory setting does not need to be changed.
Refer to information in System Configuration.
 Combining the V680-CA1D/-CA2D with Other V680-series Models
When using other models of Controller with the V680-CA1D/-CA2D, make sure that the version allows
setting the RF Tag memory setting to CA1D Mode.
To use the CS/CJ1W-V680C1@, it must be version 1.2 or newer.
To use the V680-CD5D01-V2, it must be version 2.3 or newer.
To use the V680-CH@D, it must be version 1.1 or newer.
A label on the side of the ID Sensor Unit shows the version for Units with version 1.2 or newer.
• CJ1W-V680C1@
• CS1W-V680C1@
Version
Version
RFID System
User's Manual
15
SECTION 1
Features and System Configuration
Precautions when Setting the RF Tag Memory Setting to CA1D
Mode
SECTION 1
■ Applicable RF Tags
Only the V680-D1KP@@ RF Tags can be used when the RF Tag memory setting is set to CA1D Mode.
V680-D@KF@@ RF Tags cannot be used.
Using Heat-resistive RF Tags (V680-D1KP58HTN and V680-D1KP58HT)
 RF Tags That Can Be Used
 RF Tags That Cannot Be Used
Model
Model
V680-D1KP58HT
V680-D2KF52M
V680-D1KP58HTN
V680-D2KF52M-BT01
V680-D1KP52MT
V680-D2KF52M-BT11
V680-D1KP52M-BT01
V680-D8KF67
V680-D1KP52M-BT11
V680-D8KF67M
V680-D1KP53M
V680-D8KF68
V680-D1KP66T
V680-D32KF68
V680-D1KP66MT
V680S-D2KF67
V680S-D2KF67M
V680S-D2KF68
V680S-D2KF68M
V680S-D8KF67
V680S-D8KF67M
V680S-D8KF68
V680S-D8KF68M
■ CA1D Mode Setting for RF Tag Memory and Write Protection
When setting the RF Tag memory setting to CA1D Mode, always disable write protection.
Set word m+2 (Write Protection Setting) in the DM Area to 01 to disable write protection.
Refer to DM Area Allocations and Contents on page 65 for details on the DM Area.
p. 65
16
RFID System
User's Manual
SECTION 1
Features and System Configuration
■ Combining ID Sensor Units and ID Controllers
The address maps in the RF Tags for the V680-D1KP@@ (except for the V680-D1KP58HT) are
reversed between the V680-CA1D/-CA2D ID Controller and CS/CJ1W-V680C1@ ID Sensor Units (with
sion 2.1 or older) ID Controller and CS/CJ1W-V680C1@ ID Sensor Units (with RF Tag memory setting
set to Standard Mode for version 1.2 or newer). Therefore, when you use RF Tags with a V680-CA1D/Controller or ID Sensor Units that are used for the same RF Tags.
Reading/writing
OK
CS/CJ1W-V680C1@
(Version 1.2 or newer:
RF Tag memory setting
set to CA1D Mode.)
V680-CA1D/-CA2D
Address map in RF
Tags reversed.
Reading/writing
OK
Using Heat-resistive RF Tags (V680-D1KP58HTN and V680-D1KP58HT)
CA2D ID Controller, always set the RF Tag memory setting to CA1D Mode in any other models of ID
SECTION 1
RF Tag memory setting set to CA1D Mode for version 1.2 or newer), and the V680-CA5D01-V2 (ver-
CS/CJ1W-V680C1@
CS/CJ1W-V680C1@
(Pre-version 1.2)
(Version 1.2 or newer:
RF Tag memory setting
set to Standard Mode.)
RFID System
User's Manual
17
SECTION 1
Features and System Configuration
■ Operation When RF Tag Memory Setting Is Set to Standard Mode
When data that was written to a V680-D1KP58HTN RF Tag with the V680-CA1D/-CA2D ID Controller
is read from a CS/CJ1W-V680C1@ ID Sensor Unit, the data is read from addresses that are reversed
SECTION 1
in one-block (eight-byte) units.
If you are going to use an ID Sensor Unit in the same line as a V680-CA1D/-CA2D ID Controller, use
an ID Sensor Unit with version 1.2 or newer and set the RF Tag memory setting to CA1D Mode.
Using Heat-resistive RF Tags (V680-D1KP58HTN and V680-D1KP58HT)
18
Address
0000 hex
0001 hex
0002 hex
0003 hex
0004 hex
0005 hex
0006 hex
0007 hex
:
:
03E0 hex
03E1 hex
03E2 hex
03E3 hex
03E4 hex
03E5 hex
03E6 hex
03E7 hex
RFID System
User's Manual
Data written with
V680-CA1D/-CA2D
Data read with CS/CJ1W-V680C1@
(pre-version 1.2) or CS/CJ1W-V680C1@
(version 1.2 or newer with RF Tag
memory setting set to Standard Mode)
01 hex
23 hex
45 hex
67 hex
89 hex
AB hex
CD hex
EF hex
:
:
00 hex
00 hex
00 hex
00 hex
00 hex
00 hex
00 hex
00 hex
00 hex
00 hex
00 hex
00 hex
00 hex
00 hex
00 hex
00 hex
:
:
01 hex
23 hex
45 hex
67 hex
89 hex
AB hex
CD hex
EF hex
Addresses are
reversed by block.
SECTION 1
Features and System Configuration
■ Operation When RF Tag Memory Setting Is Set to CA1D Mode
If the RF Tag memory setting for the CS/CJ1W-V680C1@ (version 1.2 or newer) is set to CA1D Mode,
data is read from or written to addresses that are reversed in block units for the V680-D1KP@@ (except
from the same addresses as those to which data was written by the V680-CA1D/-CA2D.
0000 hex
0001 hex
0002 hex
0003 hex
0004 hex
0005 hex
0006 hex
0007 hex
:
:
03E0 hex
03E1 hex
03E2 hex
03E3 hex
03E4 hex
03E5 hex
03E6 hex
03E7 hex
Data read with CS/CJ1W-V680C1@
(version 1.2 or newer with RF Tag
memory setting set to CA1D Mode)
Using Heat-resistive RF Tags (V680-D1KP58HTN and V680-D1KP58HT)
Address
Data written with
V680-CA1D/-CA2D
SECTION 1
for the V680-D1KP58HT) in the same way as for the V680-CA1D/-CA2D. Therefore, data can be read
01 hex
01 hex
23 hex
23 hex
45 hex
45 hex
67 hex
67 hex
89 hex
89 hex
AB hex
AB hex
CD hex
CD hex
EF hex
EF hex
: Same as data read with :
:
:
V680-CA1D/-CA2D.
00 hex
00 hex
00 hex
00 hex
00 hex
00 hex
00 hex
00 hex
00 hex
00 hex
00 hex
00 hex
00 hex
00 hex
00 hex
00 hex
RFID System
User's Manual
19
SECTION 1
Features and System Configuration
Using V680S-D8KF@@ RF Tags
To use the CS/CJ1W-V680C1@, it must be version 1.24 or newer. (Production since October 2014)
SECTION 1
Using V680S-D8KF @@ RF Tags
20
RFID System
User's Manual
SECTION 1
Features and System Configuration
System Configuration
SECTION 1
Basic System Configuration
 CS-series PLCs
One-channel ID Sensor Unit
Two-channel ID Sensor Unit
System Configuration
CPU Unit
24 V DC
power
supply
Amplifier
Antenna
RF Tag
Workpiece
(moving body)
Moves
Workpiece
(moving body)
Note: The above example uses one One-channel ID Sensor Unit (CS1W-V680C11) and one Twochannels ID Sensor Unit (CS1W-V680C12).
The V680-H01 Antenna can be connected to only the One-channel ID Sensor Unit (CS1W-V680C11).
It cannot be connected to the Two-channels ID Sensor Unit (CS1W-V680C12).
For details on Antennas, Amplifiers, and RF Tags, refer to the following manuals:
RFID System V680 Series User's Manual for Amplifiers, Antennas, and RF Tags (FRAM) (Cat. No. Z248),
V680 Series RFID System Amplifier/RF Tags (EEPROM) User's Manual (Cat. No. Z262), and
Heat-resistive RFID System V680 Series User's Manual (Cat. No. Z221).
RFID System
User's Manual
21
SECTION 1
Features and System Configuration
 CJ-series PLCs
One-channel ID Sensor Unit
CPU Unit
SECTION 1
Two-channel ID Sensor Unit
System Configuration
Amplifier
Antenna
RF Tag
Workpiece
(moving body)
Moves
Workpiece
(moving body)
Note: The above example uses one One-channel ID Sensor Unit (CJ1W-V680C11) and one Twochannels ID Sensor Unit (CJ1W-V680C12).
The V680-H01 Antenna can be connected to only the One-channel ID Sensor Unit (CJ1W-V680C11).
It cannot be connected to the Two-channels ID Sensor Unit (CJ1W-V680C12).
For details on Antennas, Amplifiers, and RF Tags, refer to the following manuals:
RFID System V680 Series User's Manual for Amplifiers, Antennas, and RF Tags (FRAM) (Cat. No. Z248),
V680 Series RFID System Amplifier/RF Tags (EEPROM) User's Manual (Cat. No. Z262), and
Heat-resistive RFID System V680 Series User's Manual (Cat. No. Z221).
22
RFID System
User's Manual
SECTION 1
Features and System Configuration
Mounting Restrictions
 CS-series PLCs
• These Units can be mounted to a CS-series CPU Rack or CS-series Expansion Rack.
• The number of Units per CPU Rack or Expansion Rack depends on the maximum supply current of
the Power Supply Unit and current consumption of other Units on the Rack.
mounted.
CS1W-V680C11
Power Supply Unit
CS1W-V680C12
V680-HA63@ Amplifier
connected
V680-H01 Antenna connected
V680-HA63@ Amplifier
connected
C200HW-PA204
C200HW-PA204S
C200HW-PA204R
C200HW-PD204
5
2
10
C200HW-PA209R
9
4
10
System Configuration
The following table lists the maximum number of Units per Rack when only ID Sensor Units are
SECTION 1
CS-series ID Sensor Units are classified as CS-series Special I/O Units.
The V680-H01 Antenna can be connected to only the One-channel ID Sensor Unit (CS1W-V680C11).
It cannot be connected to the Two-channels ID Sensor Unit (CS1W-V680C12).
 CJ-series PLCs
CJ-series ID Sensor Units are classified as CJ-series Special I/O Units.
• These Units can be mounted to a CJ-series CPU Rack or CJ-series Expansion Rack.
• The number of Units per CPU Rack or Expansion Rack depends on the maximum supply current of
the Power Supply Unit and current consumption of other Units on the Rack.
The following table lists the maximum number of Units per Rack when only ID Sensor Units are
mounted.
CJ1W-V680C11
CJ1W-V680C12
Power Supply Unit
V680-HA63@ Amplifier
connected
V680-H01Antenna connected
V680-HA63@ Amplifier
connected
CJ1W-PA205R
4
2
2
CJ1W-PA202
2
1
1
The V680-H01 Antenna can be connected to only the One-channel ID Sensor Unit (CJ1W-V680C11).
It cannot be connected to the Two-channels ID Sensor Unit (CJ1W-V680C12).
The I/O words allocated to Special I/O Units are determined by the setting of the unit number switches on the front of the Unit.
They are not affected by the slots (positions) in which the Units are mounted.
RFID System
User's Manual
23
SECTION 1
Features and System Configuration
Mounting Units
 CS-series PLCs
SECTION 1
Use the following procedure to mount an ID Sensor Unit to the Backplane.
1. Lock the top of the ID Sensor Unit into the slot on the Backplane.
System Configuration
Hook
Backplane
2. Rotate the Unit downwards as shown in the following diagram. While making sure to align the Unit
connector properly with the connectors on the Backplane, and then tighten the mounting screws
securely to a tightening torque of 0.4 N·m
3. To remove the Unit, first loosen the mounting screws using a Phillips screwdriver.
Mounting screw
Leave enough space below each Rack, as shown in the
following diagram, for mounting and removing the Units.
20 mm min.
Backplane
20 mm min.
Phillips screwdriver
24
RFID System
User's Manual
SECTION 1
Features and System Configuration
 CJ-series PLCs
ID Sensor Units are connected as I/O Units in the system configuration, as shown below.
SECTION 1
CPU Unit
System Configuration
Power Supply Unit
ID Sensor Units
End Cover
(included with CPU Unit)
Use the following procedure to connect an ID Sensor Unit.
1. Align the connectors and press in firmly on the Units to connect them completely.
Hook
Hook holes
Connector
2. Move the yellow sliders on the top and bottom of the Unit to the lock position to secure the Units. The
sliders should click into place.
Move the sliders to the back
until they click into place.
Slider
Locked
Released
3. Attach an End Cover to the Unit on the right end of the Rack.
The CJ-series PLC may not operate properly if the sliders are not locked firmly into place.
RFID System
User's Manual
25
SECTION 1
Features and System Configuration
Unit Handling Precautions
• Be sure to turn OFF the power supply to the PLC before installing or disconnecting Units, or
connecting lines.
SECTION 1
• To reduce the influence of electrical noise, wire input and output lines in separate ducts from highvoltage and power lines.
• When wiring a Unit, leave the label in place on the top of the Unit to prevent wire clippings or other
System Configuration
materials from getting inside the Unit. When wiring has been completed, remove the label to ensure
proper heat dissipation.
 CS-series PLCs
Remove the label after
wiring has been completed.
 CJ-series PLCs
Remove the label after
wiring has been completed.
26
RFID System
User's Manual
SECTION 1
Features and System Configuration
Functions by Application
Function
Reference
Adjusting communications timing with RF Tags
Examples:
• Communicating with RF Tags stopped in front of the Antenna
• Communicating with RF Tags passing by the Antenna
Communications Specifications
Protecting RF Tag memory from being overwritten by incorrect data
Write Protection
p. 101
Managing RF Tag life
RF Tag Service Life Check
p. 108
Checking the suitability of RF Tag memory
RF Tag Memory Check
p. 112
Checking RF Tag memory and correcting one-bit errors.
RF Tag Memory Error Correction
p. 114
p. 78
p. 85
RFID System
User's Manual
Functions by Application
Test Mode
SECTION 1
Application
Performing communications tests with RF Tags without programming
the CPU Unit
27
SECTION 1
Features and System Configuration
MEMO
SECTION 1
Functions by Application
28
RFID System
User's Manual
SECTION 2
CS-series ID Sensor Units
SECTION 2
30
Operating Procedure
32
Part Names and Functions
38
Connections and Wiring
41
RFID System
User's Manual
CS-series ID Sensor Units
Specifications
29
SECTION 2
CS-series ID Sensor Units
Specifications
General Specifications
General specifications conform to those of SYSMAC CS-series Special I/O Units.
Performance Specifications
SECTION 2
CS1W-V680C11
CS1W-V680C12
Unit classification
Special I/O Unit
Specifications
Influence on CPU
Unit's cycle time
0.15 ms
External power supply
Internal current
consumption
0.3 ms
---
24 VDC +10%/-15%, 360 mA
V680-HA63@ Amplifier connected: 5 VDC, 260 mA
24 VDC, 125 mA
V680-H01 Antenna connected: 5 VDC, 260 mA
24 VDC, 280 mA
Dimensions
5 VDC, 320 mA
24 VDC, 0 mA
35 x 130 x 101 mm (W x H x D)
Weight
180 g max.
300 g max.
Mounting location
CS-series CPU Rack or CS-series Expansion Rack
(Cannot be mounted to C200H Expansion I/O Racks or SYSMAC BUS Slave Racks.)
No. of Units per Rack
V680-HA63@ Amplifier connected: 5 per Rack
V680-H01Antenna connected: 2 per Rack
(See note 1.)
10 per Rack
(See note. 1)
Connectable Antennas
(See note 2.)
V680-series Amplifiers (V680-HA63@)
V680-series Antennas (V680-H@@)
One channel
V680-series Amplifiers (V680-HA63@)
V680-series Antennas (V680-H@@)
One or two channels
Applicable RF Tags
V680-series RF Tags (V680-D@@)
No. of allocated unit
numbers
No. of allocated words
1
2
10 words
20 words
Control protocol
Special protocol
Data exchange
methods with CPU Unit Special I/O Unit Area in
CIO Area: CIO 2000 to
CIO 2959
Special I/O Unit words in
DM Area: D20000 to
D29599
Data transfer quantity
Constant data exchange
of 10 words/Unit
100 words/Unit
transferred when power
is turned ON or when
restarting the Unit
2,048 bytes max. (160 bytes/scan) (See note 3.)
CPU Unit to
ID Sensor Unit
Unit controls, communications
processing specification,
data storage area specification
ID Sensor Unit to
CPU Unit
Unit information, results information,
processing results monitor
CPU Unit to ID
Sensor Unit
System Settings, Auto Wait Time
Setting, Write Protection Disable
Setting, Antenna Connection Setting,
Results Monitor Output, Test Setting,
Run/Test Switching Method Setting
2,048 bytes max./channel (160 bytes/scan) (See note 3.)
Run Mode
Test Mode
Operating modes
Diagnostic function
Note 1.
· Communications tests
· Range level measurements
· Read speed level measurements
· Write speed level measurements
· Noise level measurements
· Communications success rate measurements
(1) CPU watchdog timer
(2) Communications error detection with RF Tag
(3) Antenna power supply error
“Rack” indicates either the CPU Rack or an Expansion Rack.
2. The V680-H01 Antenna can be connected only to the CS1W-V680C11 ID Sensor Unit.
It cannot be used with the CS1W-V680C12 ID Sensor Unit.
3. If using Intelligent I/O Instructions is specified as the data transfer method, up to 2,048 bytes can be
transferred in one scan.
30
RFID System
User's Manual
SECTION 2
CS-series ID Sensor Units
Communications Specifications
CS1W-V680C11
CS1W-V680C12
Communications
specification
Read
Write
Bit Set/Bit Clear
Mask Bit Write
Calculation Write
Data Fill
Data Check
Number of Writes Control
Copy
Read with Error Correction
Write with Error Correction
UID Read
Noise Measurement
Specifications
Commands
Read
Write
Bit Set/Bit Clear
Mask Bit Write
Calculation Write
Data Fill
Data Check
Number of Writes Control
Read with Error Correction
Write with Error Correction
UID Read
Noise Measurement
SECTION 2
(1) RF Tag Communications Speed (Normal Mode or High-speed Mode)
(2) Write Verification
(3) Auto Wait Time Setting
Communications controls (4) UID Addition Setting
(5) Write Protection Disable Setting
(6) Antenna Connection Setting (One-channel ID Sensor Unit (CS1W-V680C11))
(7) Results Monitor Output Setting
Single trigger
Single auto
Repeat auto
FIFO trigger (See note)
FIFO repeat (See note)
Multi-access trigger (See note)
Multi-access repeat (See note)
Note: FIFO trigger, FIFO repeat, Multi-access trigger, and Multi-access repeat specification cannot be
used for communicating with V680-D1KP@@ RF Tags.
RFID System
User's Manual
31
SECTION 2
CS-series ID Sensor Units
Operating Procedure
The operating procedure for an ID Sensor Unit is shown in the following flowchart.
Set switch on front of Unit
• Turn OFF the test switch on the front of the Unit.
SECTION 2
Operating Procedure
Installation and settings
Wire
Set unit number
Turn ON PLC power
Create I/O tables
Set words allocated in DM Area
Set switch on front of Unit
• System Settings
• Auto Wait Time Setting
• Write Protection Setting
• Antenna Connection Setting
• Results Monitor Output
• Test Setting
• Run/Test Switching Method Setting
• OR, turn ON Special I/O Unit Restart Bit.
• Turn ON the test switch on the front of the Unit.
• Place PLC in PROGRAM mode.
Test communications
Change DIP switch on front of Unit
Operation
Trail operation
Turn PLC power OFF and ON
• Set unit number switches on front of Unit.
Turn ON PLC power
• OR, turn ON Special I/O Unit Restart Bit.
Ladder program operation
• When using CX-Programmer V3.0 or later with the CS1W-V680C12, “I” will be displayed before addresses for inputs in the
ladder diagram and “Q” will be displayed before addresses for outputs for operation data. In the CX-Programmer's I/O Table
Window, select SIOU/C200H ASCII Unit (A) and then, from the Enter SIOU Details Window, set the Address per Unit to 2, the
Input Words to 3, and the Output Words to 7, and select the Repeat IN/OUT for each Address per Unit option.
• When using CX-Programmer V2.0 or later with the CS1W-V680C11, “I” will be displayed in the ladder diagram before address
for inputs and “Q” will be displayed before addresses for outputs for operation data.
• When using the CS1W-V680C12, turn ON the power supply for external inputs at the same time or after the CPU Unit power
supply is turned ON.
32
RFID System
User's Manual
SECTION 2
CS-series ID Sensor Units
Operating Procedure Example
The following is an operating procedure example for the following conditions.
Reading 10 Bytes of Data from RF Tag Address 0010 (Hex) Using a Trigger
CS-series CPU Unit
CS1W-V680C11
V680C11
RUN
ERC
ERP
ERH
T/R
Read command
RF Tag
NORM/ERR
Address (hex)
7
0
SECTION 2
Special I/O
Unit in CIO
Area
TEST
ON
15
00
D1000
01
02
D1001
03
04
05
D1003
07
08
D1004
09
0A
06
→: Read data storage order
0
0
0
0
0
0
0
0
0
0
1
2
3
4
5
6
7
8
9
A
Operating Procedure
D1002
HEAD
Read data
0010
0011
0012
0013
0014
0015
Communi- 0016
cations
0017
0018
0019
• Special I/O Unit in CIO Area Settings
Unit number: 00
Command: Read
Communications specification: Trigger
Read data storage order: Leftmost  Rightmost
First RF Tag read address: 0010 hex
Number of RF Tag read bytes: 10 bytes
Read data storage destination: D1000 to D1004
RFID System
User's Manual
33
SECTION 2
CS-series ID Sensor Units
 ID Sensor Unit Settings
1. Test switch (Set on Unit’s front panel.)
TEST
P
ER
H
ER D2
HEA
T/R /ERR
C12
80
V6 RUN
C
ER 1
D
HEA R
T/
RM
NO
/ERR
SECTION 2
RM
NO
ST
TE
ON
ON
Test switch
D1
HEA
D2
HEA
V
24
DC T
PU
IN
Operating Procedure
+
-
2. Mounting and Installation
3. Unit Number Setting
32
6 54
32
1 09
87
87
1 09
6 54
Set the unit number to 1, and the
following words will be allocated
to the Unit as a Special I/O Unit.
• CIO Area: CIO 2010 to CIO 2019
• DM Area: D20100 to D20199
4. PLC Power Supply ON
Power supply ON
• When using the CS1W-V680C12, turn ON the external input power supply at the same time or after the CPU Unit power supply
5.
34
is turned ON.
RFID System
User's Manual
SECTION 2
CS-series ID Sensor Units
 Creating I/O Tables
Always create the I/O tables after turning ON the PLC power supply.
The I/O tables can be created from a CS/CJ-series Programming Console or a CX-Programmer
(Support Software used to control a PLC, e.g., to create programs or change operating modes).
SECTION 2
Peripheral port
Operating Procedure
Programming Console
 Initial Settings
1. Make the settings in the words allocated to Special I/O Units in the DM Area.
For information on setting the Special I/O Unit words in the DM Area, refer to Parameter Settings in DM Area on page
93.
p. 93
Peripheral port
Programming Console
RFID System
User's Manual
35
SECTION 2
CS-series ID Sensor Units
First word allocated to Unit in DM Area: m = D20000 + (100 × 0) = D20000
DM
address
D20000
Meaning
Contents
15 14 13 12 11 10
UID Addition
SECTION 2
Not used
0: Enabled
1: Disabled
6
5
4
0: Verification
1: No verification
3
2
1
0
0: Normal
1: High-speed
Operating Procedure
Not used
Write Protection Disable
00: V680 method
01: Disabled
00: V600 method
Not used
Not used
D20003
Not used
Not used
D20005
to
D20049
D20050
7
Auto Wait Time
Setting range: 0000 to 9999 (×0.1 s)
Factory setting: 0000 (infinite)
D20001
D20004
8
Speed
0: Disabled
1: Enabled
D20002
9
Test Mode Disable Write Verification Communications
Not used
Not used
Antenna Connection
0: Standard Antenna
1: V680-H01
Results Monitor Output
0: Communications time
1: Noise level
Not used
Test Operation
00: Communications test
A0: Distance level
B0: Read speed level
B1: Write speed level
C0: Noise level
C1: Communications success rate
C2: Retry counts
D20051
Number of Test Bytes
Setting range: 0000 to 0800 (byte)
D20052
to
D20079
D20080
Test Antenna
01: Antenna 1
02: Antenna 2
Not used
Run/Test
㩷Switching Method
Not used
1: CPU Unit
0: Test switch
D20081
D20082
to
D20089
D20090
D20091
to
D20099
RF Tag Memory Setting
1: CA1D Mode
0: Standard Mode
Not used
Not used
Not used
Not used
2. PLC Power Supply OFF and ON
Power supply OFF → ON
(or turn ON the Unit Restart Bit)
36
RFID System
User's Manual
Data Transfer Setting
1: Use Intelligent I/O Instructions
0: Use cyclic transfer
SECTION 2
CS-series ID Sensor Units
 Ladder Programming
Peripheral port
SECTION 2
Programming Console
Number of Bytes to Read, and Read Data Storage Destination in CIO n+1 to CIO n+6 allocated in the Special
I/O Unit Area (here, CIO 2011 to CIO 2016).
First word allocated to Unit in CIO Area: CIO 2000 + 10 × 0 = CIO 2000
Word
address
Contents
Meaning
15
CIO 2001 00
0
0
14
13
12
11
10
9
8
Command
7
10
First read address
CIO 2003 00
0A
Number of read bytes
00
Read data storage location (rightmost 4 digits)
00
Data storage area
00
---
CIO 2005 0
0
CIO 2006 00
Bank specification*
*: Always 0 when DM Area is specified.
Execution input
ID Busy
Test Mode
2007.00
2007.14
4
3
2
1
0
Data order
Read data storage location (leftmost 2 digits)
---: Ignored.
Unit Busy
MOV
Waiting for
command
execution
(work bit)
5
Communications
specification
CIO 2002 00
CIO 2004 10
6
Operating Procedure
Set the Command, Communications Specification, Read Data Storage Order, First RF Tag Read Address,
2007.15
#0000
Specification of command,
communications specification,
and read data storage order.
2001
0010.01
MOV
Specification of first read address.
#0010
2002
MOV
Specification of number of read bytes.
#000A
2003
MOVL
Read data storage location
#00001000
2004
Waiting for command execution
(work bit)
Waiting for command
execution (work bit)
0010.01
Command Execution Bit
0010.01
2000.00
Abort input
ID Busy
Waiting for abort
(work bit)
2007.00
Abort Bit
2000.02
Waiting for Abort
(work bit)
0010.02
0010.02
Normal End Flag
Normal end
2007.01
Used to time getting read data.
Error End Flag
Error end
2007.02
Used to time getting results information.
RFID System
User's Manual
37
SECTION 2
CS-series ID Sensor Units
Part Names and Functions
Part Names
CS1W-V680C11
(front)
SECTION 2
V680C11
RUN
ERC
CS1W-V680C12
(front)
V680C12
RUN
ERC
HEAD1
T/R
ERP
ERH
T/R
ERP
ERH
HEAD2
T/R
NORM/ERR
NORM/ERR
Unit number switches
Part Names and Functions
TEST
TEST
Test switch
ON
ON
Connector for Amplifier/Antenna 1
HEAD1
HEAD
Connector for Amplifier/Antenna 2
HEAD2
DC24V
INPUT
Antenna power supply terminals
(Back)
Backplane
connector
38
Status indicators
NORM/ERR
RFID System
User's Manual
(Side)
Terminal
block
SECTION 2
CS-series ID Sensor Units
Indicators
Indicators show the operating status of the Units.
The relationship between the indicator status and the Units status is shown in the following table.
Indicator
Name
RUN
RUN
Color
Green
Meaning
❍ Lit
The ID Sensor Unit is operating normally.
SECTION 2
● Not lit The ID Sensor Unit is stopped.
Unit error
Red
ERH
(Error at CPU Unit)
CPU Unit error
Red
ERP
(Antenna Power Error)
Antenna power
error
Red
HEAD1
(Antenna
1)
Communicating
Yellow
❍ Lit
An error has occurred in the ID Sensor Unit.
● Not lit No error has occurred in the ID Sensor Unit.
❍ Lit
An error has occurred in the CPU Unit.
● Not lit No error has occurred in the CPU Unit.
T/R
❍ Lit
An error has occurred in the power supply to the Antenna.
● Not lit The power supply to the Antenna is normal.
❍ Lit
Communications are active.
● Not lit Communications not being performed with the RF Tag.
NORM/ERR
Normal end
Green
❍ Lit
Communications with the RF Tag ended normally.
● Not lit The indicator is not Iit in all other cases.
Error end
Red
T/R
Communicating
Yellow
NORM/ERR
Normal end
Green
❍ Lit
Communications with the RF Tag ended in an error.
● Not lit The indicator is not Iit in all other cases.
HEAD2
(Antenna
2)
❍ Lit
Part Names and Functions
ERC
(Error in Controller)
Communications are active.
● Not lit Communications not being performed with the RF Tag.
❍ Lit
Communications with the RF Tag ended normally.
● Not lit The indicator is not Iit in all other cases.
Error end
Red
❍ Lit
Communications with the RF Tag ended in an error.
● Not lit The indicator is not Iit in all other cases.
Unit Number Switches
Data exchange between the CPU Unit and ID Sensor Unit is performed using words allocated to the
Unit in the Special I/O Unit Area and in Special I/O Unit words the DM Area. The words allocated to the
ID Sensor Unit in these two areas are determined by the setting of the unit number switches on the
Unit’s front panel.
CS1W-V680C11
32
6 54
32
1 09
87
87
1 09
CS1W-V680C12
Words allocated
in DM Area
Words allocated in
Special I/O Unit
Area
Words allocated
in DM Area
Switch
No.
Unit
No.
Words allocated in
Special I/O Unit
Area
0
Unit 0
CIO 2000 to
CIO 2009
D20000 to D20099
CIO 2000 to
CIO 2019
D20000 to D20199
1
Unit 1
CIO 2010 to
CIO 2019
D20100 to D20199
CIO 2010 to
CIO 2029
D20100 to D20299
:
:
:
:
:
:
94
Unit 94
CIO 2940 to
CIO 2949
D29400 to D29499
CIO 2940 to
CIO 2959
D29400 to D29599
95
Unit 95
CIO 2950 to
CIO 2959
D29500 to D29599
(Cannot be set)
RFID System
User's Manual
39
6 54
SECTION 2
CS-series ID Sensor Units
Test Switch
The test switch on the Unit’s front panel is used to switch between RUN Mode and Test Mode. Specify
using the test switch in the Run/Test Switching Method Setting in the DM Area to enable using this
switch.
Status
SECTION 2
TEST
ON
Part Names and Functions
40
RFID System
User's Manual
Description
OFF
RUN mode (factory setting)
ON
Test Mode
SECTION 2
CS-series ID Sensor Units
Connections and Wiring
Connecting the Amplifier or Antenna
 Connection Method
SECTION 2
1. Holding the base of the connector, align the
white mark on the Unit with the white mark
on the connector and insert the connector.
Base of connector
Connections and Wiring
2. Press in on the connector until it locks in
place.
Ring
• The connector will not lock into place if you hold onto the ring. Always hold onto the base of the connector.
The antenna that can be connected with the connector for Amplifier/Antenna is only V680-H01.
 Removal Method
1. Hold onto the ring and pull straight out.
Base of connector
Ring
The connector cannot be removed if you hold onto the base of the connector. Never pull on the cable with excessive
force. The connectors may be broken or damaged.
Connecting or disconnecting the connector with power to the Unit turned ON may cause the Unit to be damaged or
malfunction.
RFID System
User's Manual
41
SECTION 2
CS-series ID Sensor Units
Wiring the External Power Supply (CS1W-V680C12 Only)
Wire the power supply as shown below.
CS1W-V680C12
SECTION 2
Connection Example
Connections and Wiring
Line filter
+24 V DC
0V
M3 self-lifting screws are used as the connection terminals for the power supply. When necessary, use
the following crimp terminals. The tightening torque is approximately 0.58 N·m.
 Examples of Applicable Crimp Connectors
Manufacturer
Model number
J.S.T Mfg. Co., Ltd.
1.25-N3A
J.S.T Mfg. Co., Ltd.
1.25-Y3A
Applicable wire size
AWG26 to 18
Shape
Forked
6.5 mm max.
(For M3 terminal)
 Recommended DC Power Supplies (Compact, DIN Track-mountable,
manufactured by OMRON)
Model number
S8VS-03024
Output capacity
24 VDC, 1.3 A
Input voltage
100 to 240 VAC
• Although adequate measures have been taken inside the ID Sensor Unit for noise entering on the power supply line, supplying
power through a line filter can be used to greatly attenuate ground noise.
• Although the rated power consumption of the CS1W-V680C12 is 360 mA at 24 VDC, be sure to consider the surge current
when determining capacities.
• When using the CS1W-V680C12, turn ON the power supply for external inputs at the same time or after the CPU Unit power
supply is turned ON.
42
RFID System
User's Manual
SECTION 2
CS-series ID Sensor Units
Wiring for Safety and Noise Immunity
Antenna Cable and I/O Signal Lines
Wire the Antenna cable and I/O signal lines in separate ducts from power circuit cables both inside and
outside the control panel.
(2)
(1)
SECTION 2
(1)
(1)
(1): I/O cables
(2): Power lines
(2)
Conduits
Floor ducts
Suspended ducts
If the same ducts must be used, shielded cables can be used to increase resistance to noise. If a
shielded cable is used, connect one end of the shield to ground.
• Countermeasures for Inductive Loads
Connections and Wiring
(2)
If I/O is connected to an inductive load, connect a surge killer or diode in parallel with the load.
IN
OUT
Diode
L
DC input
COM
Relay contact output
Triac output
COM
L
Surge killer
OUT
Relay contact output
Transistor output
+
COM
Diode
• Use surge killers and diodes that meet the following conditions:
Surge killer
Resistance: 50 Ω
Capacitance: 0.47 μF
Voltage: 200 V
Diode
Inrush withstand voltage: 3 times load voltage min.
Average rectified current: 1 A
RFID System
User's Manual
43
SECTION 2
CS-series ID Sensor Units
• Noise Countermeasures for External Wiring
Consider the following items when wiring external lines, such as Antenna cable, I/O lines, power supply
lines, and high-power lines.
• When using multiconductor cables for signal lines, do not use the same cable for both I/O lines and
other control lines.
• When Racks are installed in parallel with each other, keep them separated by at least 300 mm.
SECTION 2
Antenna cables
and PLC I/O lines
Connections and Wiring
SYSMAC power supply
lines and general
control circuit lines
Low-power cables
Control cables
High-power cables
300 mm min.
300 mm min.
Power lines
Ground to 100 Ω or less.
• When placing cables in the same duct, separate them with grounded iron plates.
PLC I/O lines
SYSMAC power supply
lines and general
control circuit lines Power lines
Iron plate
200 mm min.
Ground to 100 Ω or less.
44
RFID System
User's Manual
SECTION 3
CJ-series ID Sensor Units
Operating Procedure
48
Part Names and Functions
54
Connections and Wiring
57
RFID System
User's Manual
CJ-series ID Sensor Units
46
SECTION 3
Specifications
45
SECTION 3
CJ-series ID Sensor Units
Specifications
General Specifications
General specifications conform to those of SYSMAC CJ-series Special I/O Units.
Performance Specifications
CJ1W-V680C11
CJ1W-V680C12
Unit classification
Special I/O Unit
SECTION 3
Influence on CPU Unit's cycle
time
Internal current consumption
0.15 ms
0.3 ms
V680-HA63@ Amplifier connected: 5 VDC, 260 mA
24 VDC, 130 mA
V680-H01 Antenna connected:
5 VDC, 260 mA
24 VDC, 280 mA
Specifications
Dimensions
5 VDC, 320 mA max.
24 VDC, 260 mA max.
31 x 90 x 65 mm (W x H x D)
Weight
120 g max.
Mounting location
No. of Units per Rack
Connectable Antennas (See
note 2.)
130 g max.
CJ-series Rack or CJ-series Expansion Rack
(Cannot be mounted to C200H Expansion I/O Racks or SYSMAC BUS Slave Racks.)
CJ1W-PA205R:
V680-HA63@ Amplifier connected:
V680-H01Antenna connected:
CJ1W-PA202:
V680-HA63@ Amplifier connected:
V680-H01Antenna connected:
(See note 1.)
2 per Rack
1per Rack
V680-series Amplifiers (V680-HA63@)
V680-series Antennas (V680-H@@)
One channel
Applicable RF Tags
V680-series Amplifiers (V680-HA63@)
V680-series Antennas (V680-H@@)
One or two channels
V680-series RF Tags (V680-D@@)
No. of allocated unit numbers
1
No. of allocated words
20 words
Special protocol
Special I/O Unit Area:
CIO 2000 to CIO 2959
Special I/O Unit words in
DM Area: D20000 to
D29599
Data transfer quantity
2
10 words
Control protocol
Data exchange methods
with CPU Unit
CJ1W-PA205R: 2
CJ1W-PA202: 1
(See note 1.)
4 per Rack
2 per Rack
Constant data exchange
of 10 words/Unit
100 words/Unit
transferred when power
is turned ON or when
restarting the Unit
2,048 bytes max. (160 bytes/scan) (See note 3.)
CPU Unit to ID
Sensor Unit
Unit controls, communications
processing specification,
data storage area specification
ID Sensor Unit to
CPU Unit
Unit information, results information,
processing results monitor
CPU Unit to ID
Sensor Unit
System Settings, Auto Wait Time
Setting, Write Protection Disable
Setting, Antenna Connection Setting,
Results Monitor Output, Test Setting,
Run/Test Switching Method Setting
2,048 bytes max./channel (160 bytes/scan) (See note 3.)
Run Mode
Test Mode
Operating modes
Diagnostic functions
Note 1.
• Communications tests
• Range level measurements
• Read speed level measurements
• Write speed level measurements
• Noise level measurements
• Communications success rate measurements
(1) CPU watchdog timer
(2) Communications error detection with RF Tag
(3) Antenna power supply error
“Rack” indicates either the CPU Rack or an Expansion Rack.
2. The V680-H01 Antenna can be connected only to the CJ1W-V680C11 ID Sensor Unit.
It cannot be used with the CJ1W-V680C12 ID Sensor Unit.
3. If using Intelligent I/O Instructions is specified as the data transfer method, up to 2,048 bytes can be
transferred in one scan.
46
RFID System
User's Manual
SECTION 3
CJ-series ID Sensor Units
Communications Function Specifications
CJ1W-V680C11
Communications
control
Read
Write
Bit Set/Bit Clear
Mask Bit Write
Calculation Write
Data Fill
Data Check
Number of Writes Control
Copy
Read with Error Correction
Write with Error Correction
UID Read
Noise Measurement
Specifications
Communications
specification
Read
Write
Bit Set/Bit Clear
Mask Bit Write
Calculation Write
Data Fill
Data Check
Number of Writes Control
Read with Error Correction
Write with Error Correction
UID Read
Noise Measurement
SECTION 3
Commands
CJ1W-V680C12
(1) RF Tag Communications Speed (Normal Mode or High-speed Mode)
(2) Write Verification
(3) Auto Wait Time Setting
(4) UID Addition Setting
(5) Write Protection Disable Setting
(6) Antenna Connection Setting (One-channel ID Sensor Unit (CJ1W-V680C11))
(7) Results Monitor Output Setting
Single trigger
Single auto
Repeat auto
FIFO trigger (See note)
FIFO repeat (See note)
Multi-access trigger (See note)
Multi-access repeat (See note)
Note: FIFO trigger, FIFO repeat, Multi-access trigger, and Multi-access repeat specification cannot be
used for communicating with V680-D1KP@@ RF Tags.
RFID System
User's Manual
47
SECTION 3
CJ-series ID Sensor Units
Operating Procedure
The operating procedure for an ID Sensor Unit is shown in the following flowchart.
Set switch on front of Unit
• Turn OFF the test switch on the front of the Unit.
SECTION 3
Installation and settings
Wire
Set unit number
Turn ON PLC power
Create I/O tables
Operating Procedure
Set words allocated in DM Area
Operation
Trail operation
Turn PLC power OFF and ON
Set switch on front of Unit
• Set unit number switches on front of Unit.
• System Settings
• Auto Wait Time Setting
• Write Protection Setting
• Antenna Connection Setting
• Results Monitor Output
• Test Settings
• Run/Test Switching Method Setting
• OR, turn ON Special I/O Unit Restart Bit.
• Turn ON the test switch on the front of the Unit.
• Place PLC in PROGRAM mode.
Test communications
Change DIP switch on front of Unit
Turn ON PLC power
• OR, turn ON Special I/O Unit Restart Bit.
Ladder program operation
• When using CX-Programmer V3.0 or later with the CJ1W-V680C12, “I” will be displayed before addresses for inputs in the
ladder diagram and “Q” will be displayed before addresses for outputs for operation data. In the CX-Programmer’s I/O Table
Window, select SIOU/C200H ASCII Unit (A) and then, from the Enter SIOU Details Window, set the Address per Unit to 2, the
Input Words to 3, and the Output Words to 7, and select the Repeat IN/OUT for each Address per Unit option.
• When using CX-Programmer V2.0 or later with the CJ1W-V680C11, “I” will be displayed in the ladder diagram before address
for inputs and “Q” will be displayed before addresses for outputs for operation data.
48
RFID System
User's Manual
SECTION 3
CJ-series ID Sensor Units
Operating Procedure Example
The following is an operating procedure example for the following conditions.
Reading 10 Bytes of Data from RF Tag Address 0010 Using a Trigger.
CJ-series CPU Unit
CJ1W-V680C11
Special I/O
Unit Area
RF Tag
Read command
15
D1000
00
01
02
03
04
D1002
05
06
D1003
07
08
D1004
09
0A
Read data
→: Read data storage order
0
0
0
0
0
0
0
0
0
0
0
1
2
3
4
5
6
7
8
9
A
SECTION 3
D1001
0010
0011
0012
0013
0014
0015
Communi- 0016
cations
0017
0018
0019
7
Address (hex)
Operating Procedure
• Special I/O Unit Area Settings
Unit number: 00
Command: Read
Communications specification: Trigger
Read data storage order: Leftmost  Rightmost
First RF Tag read address: 0010 hex
Number of RF Tag read bytes: 10 bytes
Read data storage destination: D1000 to D1004
RFID System
User's Manual
49
SECTION 3
CJ-series ID Sensor Units
 ID Sensor Unit Settings
1. Test Switch (Set on Unit's front panel.)
TEST
ON
Test switch
SECTION 3
Operating Procedure
2. Mounting and Installation
3. Unit Number Setting
1 09
6 54
87
32
1 09
6 54
87
32
Set the unit number to 1, and the
following words will be allocated
to the Unit as a Special I/O Unit.
• CIO Area: CIO 2010 to CIO 2019
• DM Area: D20100 to D20199
4. PLC Power Supply ON
Power Supply ON
50
RFID System
User's Manual
SECTION 3
CJ-series ID Sensor Units
 Creating I/O Tables
Always create the I/O tables after turning ON the PLC power supply. The I/O tables can be created
from the Programming Console or CX-Programmer.
Peripheral port
SECTION 3
Programming Console
1. Make the settings in the words allocated to Special I/O Units in the DM Area.
For information on setting the Special I/O Unit words in the DM Area, refer to Parameter Settings in DM Area on page
93.
Operating Procedure
 Initial Settings
p. 93
Peripheral port
Programming Console
RFID System
User's Manual
51
SECTION 3
CJ-series ID Sensor Units
First word allocated to Unit in DM Area: m = D20000 + (100  0) = D20000
DM
address
D20000
Meaning
Contents
15 14 13 12 11 10
UID Addition
0: Disabled
1: Enabled
9
8
7
6
5
4
2
1
0
Test Mode Disable Write Verification Communications Speed
0: Normal
0: Verification
0: Enabled
1: No verification 1: High-speed
1: Disabled
Auto Wait Time
Setting range: 0000 to 9999 (×0.1 s)
Factory setting: 0000 (infinite)
D20001
Write Protection Disable
00: V680 method
01: Disabled
10: V600 method
D20002
SECTION 3
Operating Procedure
Not used
Not used
Not used
Not used
Not used
Antenna Connection
0: Standard Antenna
1: V680-H01
Not used
Not used
Not used
Results Monitor Output
0: Communications time
1: Noise level
D20003
D20004
D20005
to
D20049
D20050
3
Not used
Test Operation
00: Communications test
A0: Distance level
B0: Read speed level
B1: Write speed level
C0: Noise level
C1: Communications success rate
C2: Retry counts
Test Antenna
01: Antenna 1
02: Antenna 2
D20051
Number of Test Bytes
Setting range: 0000 to 0800 (byte)
D20052
to
D20079
D20080
Not used
Not used
Run/Test
Switching Method
1: CPU Unit
0: Test switch
Not used
D20081
D20082
to
D20089
RF Tag Memory Setting
1: CA1D Mode
0: Standard Mode
Not used
D20090
Data Transfer Setting
1: Use Intelligent I/O Instructions
0: Use cyclic transfer
Not used
D20091
to
D20099
Not used
2. PLC Power Supply OFF and ON
Power supply OFF → ON
(or turn ON the Unit Restart Bit)
52
RFID System
User's Manual
SECTION 3
CJ-series ID Sensor Units
 Ladder Programming
Peripheral port
Programming Console
Set the Command, Communications Specification, Read Data Storage Order, First RF Tag Read
Address, Number of Bytes to Read, and Read Data Storage Destination in CIO n+1 to CIO n+6
SECTION 3
allocated in the Special I/O Unit Area (here, CIO 2001 to CIO 2006).
First word allocated to Unit in CIO Area: CIO 2000 + 10  0 = CIO 2000
CIO 2001
Contents
Meaning
15
00
0
0
14
13
12
11
10
9
8
Command
CIO 2002
00
10
First read address
CIO 2003
00
0A
Number of read bytes
CIO 2004
10
00
Read data storage location (rightmost 4 digits)
CIO 2005
0
CIO 2006
00
0
7
6
5
Communications
specification
00
Data storage area
00
---
Bank specification*
4
3
2
1
0
Data order
Read data storage location (leftmost 2 digits)
Operating Procedure
Word
address
*: Always 0 when DM Area is specified. ---: Ignored.
Execution input
ID Busy
Waiting for
command
execution
(work bit)
2007.00
Test Mode
Unit Busy
2007.14
2007.15
MOV
#0000
Specification of command,
communications specification,
and read data storage order.
2001
0010.01
MOV
Specification of first read address.
#0010
2002
MOV
Specification of number of read bytes.
#000A
2003
MOVL
Read data storage location
#00001000
2004
Waiting for command execution
(work bit)
0010.01
Waiting for command
execution (work bit)
Command Execution Bit
0010.01
2000.00
Abort input
ID Busy
Waiting for abort
(work bit)
2007.00
Abort Bit
2000.02
Waiting for Abort
(work bit)
0010.02
Normal End Flag
0010.02
Normal end
2007.01
Used to time getting read data.
Error End Flag
Error end
2007.02
Used to time getting results information.
RFID System
User's Manual
53
SECTION 3
CJ-series ID Sensor Units
Part Names and Functions
Part Names
CJ1W-V680C11
(front)
V680C11
RUN ERC
T/R NORM/ERR
ERP ERH
CJ1W-V680C12
(front)
V680C12
RUN ERC
T/R NORM/ERR
ERP ERH
T/R NORM/ERR
HEAD1
HEAD2
Status indicators
Unit number switches
SECTION 3
TEST
TEST
Test switch
ON
ON
Part Names and Functions
Connector for Amplifier/Antenna 1
HEAD
HEAD1
Connector for Amplifier/Antenna 2
HEAD2
(Side)
Slider
Expansion connector
Slider
54
RFID System
User's Manual
SECTION 3
CJ-series ID Sensor Units
Indicators
The indicators show the operating status of the Unit. The relationship between the indicator status and
the Unit status is shown in the following table.
Indicator
Name
Color
Meaning
RUN
RUN
Green
❍ Lit
ERC
(Error in Controller)
Unit error
Red
❍ Lit
ERH
(Error at CPU Unit)
CPU Unit error
Red
ERP
(Antenna Power Error)
Antenna power
error
Red
HEAD1
(Antenna
1)
T/R
Communicating
Yellow
NORM/ERR
Normal end
Green
❍ Lit
Error end
Red
❍ Lit
The ID Sensor Unit is operating normally.
● Not lit The ID Sensor Unit is stopped.
An error has occurred in the ID Sensor Unit.
● Not lit No error has occurred in the ID Sensor Unit.
❍ Lit
An error has occurred in the CPU Unit.
❍ Lit
An error has occurred in the power supply to the Antenna.
● Not lit The power supply to the Antenna is normal.
Communications are active.
● Not lit Communications not being performed with the RF Tag.
Communications with the RF Tag ended normally.
● Not lit The indicator is not Iit in all other cases.
Communications with the RF Tag ended in an error.
● Not lit The indicator is not Iit in all other cases.
HEAD2
(Antenna
2)
T/R
Communicating
Yellow
❍ Lit
Communications are active.
● Not lit Communications not being performed with the RF Tag.
NORM/ERR
Normal end
Green
❍ Lit
Error end
Red
❍ Lit
Communications with the RF Tag ended normally.
Part Names and Functions
❍ Lit
SECTION 3
● Not lit No error has occurred in the CPU Unit.
● Not lit The indicator is not Iit in all other cases.
Communications with the RF Tag ended in an error.
● Not lit The indicator is not Iit in all other cases.
Unit Number Switches
Data exchange between the CPU Unit and ID Sensor Unit is performed using words allocated to the
Unit in the Special I/O Unit Area and in the Special I/O Unit words in the DM Area. The words allocated
to the ID Sensor Unit in these two areas are determined by the setting of the unit number switches on
the Unit’s front panel.
CJ1W-V680C11
1 09
6 54
87
32
1 09
Switch
No.
Unit
No.
Words allocated in
Special I/O Unit
Area
Words allocated
in DM Area
Words allocated in
Special I/O Unit
Area
Words allocated
in DM Area
0
Unit 0
CIO 2000 to
CIO 2009
D20000 to D20099
CIO 2000 to
CIO 2019
D20000 to D20199
1
Unit 1
CIO 2010 to
CIO 2019
D20100 to D20199
CIO 2010 to
CIO 2029
D20100 to D20299
:
:
:
:
:
:
94
Unit 94
CIO 2940 to
CIO 2949
D29400 to D29499
CIO 2940 to
CIO 2959
D29400 to D29599
95
Unit 95
CIO 2950 to
CIO 2959
D29500 to D29599
6 54
87
CJ1W-V680C12
32
(Cannot be set)
RFID System
User's Manual
55
SECTION 3
CJ-series ID Sensor Units
Test Switch
The test switch on the Unit’s front panel is used to switch between Run Mode and Test Mode. Specify
using the test switch in the Run/Test Switching Method Setting in the DM Area to enable using this
switch.
Status
TEST
ON
SECTION 3
Part Names and Functions
56
RFID System
User's Manual
Description
OFF
Run Mode (factory setting)
ON
Test Mode
SECTION 3
CJ-series ID Sensor Units
Connections and Wiring
Connecting the Antenna
 Connection Method
1. Holding the base of the connector, align the
white mark on the Unit with the white mark on
the connector and insert the connector.
2. Press in on the connector until it locks in
Base of connector
SECTION 3
place.
Ring
Connections and Wiring
The connector will not lock into place if you hold onto the ring. Always hold onto the base of the connector.
The antenna that can be connected with the connector for Amplifier/Antenna is only V680-H01.
 Removal Method
1. Hold onto the ring and pull straight out.
Base of connector
Ring
The connector cannot be removed if you hold onto the base of the connector. Never pull on the cable with excessive
force. The connectors may be broken or damaged.
Connecting or disconnecting the connector with power to the Unit turned ON may cause the Unit to be damaged or
malfunction.
RFID System
User's Manual
57
SECTION 3
CJ-series ID Sensor Units
Wiring for Safety and Noise Immunity
Antenna Cable and I/O Signal Lines
Wire the Antenna cable and I/O signal lines in separate ducts from power circuit cables both inside and
outside the control panel.
(1): I/O cables
(2): Power lines
(1)
(1)
(2)
(1)
(2)
SECTION 3
(2)
Floor ducts
Conduits
Connections and Wiring
Suspended ducts
If the same ducts must be used, shielded cables can be used to increase resistance to noise. If a
shielded cable is used, connect one end of the shield to ground.
• Countermeasures for Inductive Loads
If I/O is connected to an inductive load, connect a surge killer or diode in parallel with the load.
IN
Diode
L
OUT
DC input
Relay contact output
Triac output
COM
L
COM Surge killer
OUT
Relay contact output
Transistor output
Use surge killers and diodes that meet the following conditions:
Surge Killers
Resistance: 50 Ω
Capacitance: 0.47 μF
Voltage:
200 V
Diodes
Inrush withstand voltage: 3 times load voltage min.
Average rectified current: 1 A
58
RFID System
User's Manual
+
COM Diode
SECTION 3
CJ-series ID Sensor Units
• Noise Countermeasures for External Wiring
Consider the following items when wiring external lines, such as the Antenna cable, I/O lines, power
supply lines, and high-power lines.
• When using multiconductor cables for signal lines, do not use the same cable for both I/O lines and
other control lines.
• When Racks are installed in parallel with each other, keep them separated by at least 300 mm.
Low-power cables
Antenna cables and
PLC I/O lines
Control cables
High-power cables
SECTION 3
SYSMAC power supply
lines and general
control circuit lines
300 mm min.
300 mm min.
Power lines
Connections and Wiring
Ground to 100 Ω or less.
• When placing cables in the same duct, separate them with grounded iron plates.
SYSMAC power supply
lines and general
PLC I/O lines control circuit lines Power lines Iron plate
200 mm min.
Ground to 100 Ω or less.
RFID System
User's Manual
59
SECTION 3
CJ-series ID Sensor Units
MEMO
SECTION 3
Connections and Wiring
60
RFID System
User's Manual
SECTION 4
Data Exchange with the CPU Unit
62
Initial Settings Data
65
I/O Data Allocations
67
SECTION 4
Outline of Data Exchange
Data Exchange with the CPU Unit
RFID System
User's Manual
61
SECTION 4
Data Exchange with the CPU Unit
Outline of Data Exchange
Data is exchanged between the CS/CJ-series CPU Unit and CS1W-V680C11/C12 or CJ1W-V680C11/C12 ID Sensor
Unit through I/O words allocated in the Special I/O Unit Area and initial setting words allocated in the DM Area.
• I/O Data
Words are allocated in the Special I/O Unit Area of the CPU Unit for ID Sensor Unit I/O data, including
Unit Controls, commands, results information, etc., according to the unit number. This data is
exchanged continuously during the I/O refresh period.
• Initial Settings Data
Words are allocated to the ID Sensor Unit in the DM Area of the CPU Unit for ID Sensor Unit initial
settings, including the System Settings and Auto Wait Time Settings, Test Settings, etc., according to the
unit number. This data is transferred when the power supply is turned ON or when restarting the Unit.
• Test Settings Data
SECTION 4
Words are allocated to the ID Sensor Unit in the DM Area of the CPU Unit for test settings, including
the Test Operation, Test Antenna, and Number of Test Bytes according to the unit number. This data is
transferred when the power supply is turned ON.
Outline of Data Exchange
SYSMAC CS/CJ-series CPU Unit
ID Sensor Unit
CS1W-V680C11/CJ1W-V680C11
I/O Data
Special I/O Unit Area
10 words
CIO 2000 + 10 × n
to CIO 2000 + 10 × n + 6
Output data
CIO 2000 + 10 × n + 7
to CIO 2000 + 10 × n + 9
• Output data
• Input data
Exchanged continuously.
Input data
I/O refresh period
Initial Settings
DM Area
D20000 + 100 × n
D20000 + 100 × n + 1
D20000 + 100 × n + 2
D20000 + 100 × n + 3
D20000 + 100 × n + 4
D20000 + 100 × n + 5
System Settings
Auto Wait Time
Write Protection Disable
Antenna Connection
Results Monitor Output
(Not used.)
Initial settings are transferred:
System Settings, Auto Wait
Time Setting, Write Protection Disable
Setting, Antenna Connection Setting,
Results Monitor Output, Run/Test
Switching Method Setting, etc.
Power turned ON
or Unit restarted.
Test Settings Data
to D20000 + 100 × n + 49
D20000 + 100 × n + 50 Test Settings
Test Operation, Test Antenna,
Number of Test Bytes
100 words
D20000 + 100 × n + 52
Entered Test Mode.
(Not used.)
to D20000 + 100 × n + 79
D20000 + 100 × n + 80 Run/Test Switching Method
D20000 + 100 × n + 81 Tag Memory Setting
D20000 + 100 × n + 82 (Not used.)
to D20000 + 100 × n + 89
D20000 + 100 × n + 90 Data Transfer Setting
D20000 + 100 × n + 91
(Not used.)
to D20000 + 100 × n + 99
SYSMAC CS/CJ-series CPU Unit
ID Sensor Unit
Special I/O Unit Area
to CIO 2010 + 10 × n + 6
CIO 2010 + 10 × n+ 7
to CIO 2010 + 10 × n + 9
I/O refresh period
Input data
DM Area
D20000 + 100 × n
D20000 + 100 × n + 1
D20000 + 100 × n + 2
D20000 + 100 × n + 3
D20000 + 100 × n + 4
D20000 + 100 × n + 5
System Settings
Auto Wait Time
Write Protection Disable
to D20000 + 100 × n + 49
D20000 + 100 × n + 50 Test Settings
Test Settings
(Antennas 1
and 2)
50 words
Initial Settings
Power turned ON
or Unit restarted.
D20000 + 100 × n + 52 (Not used.)
to D20000 + 100 × n + 79
D20000 + 100 × n + 80 Run/Test Switching Method
D20000 + 100 × n + 81 Tag Memory Setting
D20000 + 100 × n + 82
(Not used.)
to D20000 + 100 × n + 89
D20000 + 100 × n + 90 Data Transfer Setting
D20000 + 100 × n + 91 (Not used.)
to D20000 + 100 × n + 99
D20100 + 100 × n System Settings
D20100 + 100 × n + 1 Auto Wait Time
Antenna 2
50 words
Reserved
50 words
62
RFID System
User's Manual
D20100 + 100 × n + 2
D20100 + 100 × n + 3
D20100 + 100 × n + 4
D20100 + 100 × n + 5
Write Protection Disable
Antenna Connection
Results Monitor Output
(Not used.)
to D20100 + 100 × n + 49
D20100 + 100 × n + 50 (Not used.)
to D20100 + 100 × n + 99
• Output data
• Input data
Exchanged continuously.
• Output data
• Input data
Exchanged continuously.
Antenna Connection
Results Monitor Output
(Not used.)
Antenna 2
Antenna 1
50 words
Antenna 1
CIO 2010 + 10 × n Output data
Antenna 2
Antenna 2
10 words
CIO 2000 + 10 × n + 7 Input data
to CIO 2000 + 10 × n + 9
Antenna 1
Antenna 1
10 words
CS1W-V680C12/CJ1W-V680C12
I/O Data
CIO 2000 + 10 × n Output data
to CIO 2000 + 10 × n + 6
Initial settings are transferred:
System Settings, Auto Wait
Time Setting, Write Protection
Disable Setting, Antenna
Connection Setting, Results
Monitor Output, Run/Test
Switching Method Setting, etc.
Initial settings are transferred:
System Settings, Auto Wait
Time Setting, Write Protection
Disable Setting, Antenna
Connection Setting, Results
Monitor Output, RUN/TEST
Switch Mode Setting, etc.
Test Settings Data
Test Operation, Test Antenna,
Number of Test Bytes
Entered Test Mode.
SECTION 4
Data Exchange with the CPU Unit
Unit Number Setting
The words allocated to the ID Sensor Unit in the Special I/O Unit Area and in the DM Area are
determined by the unit number setting on the Unit’s front panel.
CS1W-V680C11/C12
32
87
6 54
32
1 09
87
1 09
P
ER
H
ER D2
HEA
T/R /ERR
6 54
C12
80
V6 RUN
C
ER 1
D
HEA R
T/
RM
NO
/ERR
RM
NO
ST
TE
ON
D1
HEA
D2
HEA
V
24
DC T
PU
IN
+
-
SECTION 4
CJ1W-V680C11/C12
1 09
Outline of Data Exchange
6 54
87
32
1 09
6 54
87
32
CS1W-V680C11/
CJ1W-V680C11
CS1W-V680C12/
CJ1W-V680C12
Switch
No.
Unit
No.
0
Unit 0
CIO 2000 to CIO 2009 D20000 to D20099 CIO 2000 to CIO 2019 D20000 to D20199
1
Unit 1
CIO 2010 to CIO 2019 D20100 to D20199 CIO 2010 to CIO 2029 D20100 to D20299
:
:
:
94
Unit 94
CIO 2940 to CIO 2949
D29400 to D29499 CIO 2940 to CIO 2959
95
Unit 95
CIO 2950 to CIO 2959
D29500 to D29599
Words allocated in
Special I/O Unit Area
Words allocated
in DM Area
:
Words allocated in
Special I/O Unit Area
Words allocated
in DM Area
:
:
D29400 to D29599
(Cannot be set)
• If the same unit number is set for more than one Special I/O Unit, a fatal error (No. duplication error on CX-Programmer or Unit
Number Duplication on Programming Console), and the PLC will not operate.
• When a Two-channels ID Sensor Unit (CS1W-V680C12 or CJ1W-V680C12) is used, two unit numbers are allocated.
RFID System
User's Manual
63
SECTION 4
Data Exchange with the CPU Unit
Special I/O Unit Restart Bits
Unit operation can be restarted after DM Area settings have been changed or after an error has been
corrected by turning the power supply to the PLC OFF and ON or by turning ON the Special I/O Unit
Restart Bit.
• CS-series Special I/O Unit Restart Bits
Bit address
Function
Unit 1 Restart Bit
A50300
Unit 16 Restart Bit
...
Unit 15 Restart Bit
...
A50215
Unit 95 Restart Bit
• CJ-series Special I/O Unit Restart Bits
Function
Unit 0 Restart Bit
Unit 1 Restart Bit
...
A50200
A50201
...
A50215
Unit 15 Restart Bit
A50300
Unit 16 Restart Bit
A50715
The Unit will be restarted when the
corresponding bit is turned ON.
After the Unit has finished
restarting, the corresponding bit
will be automatically turned OFF.
...
Outline of Data Exchange
Bit address
...
SECTION 4
A50715
The Unit will be restarted when the
corresponding bit is turned ON.
After the Unit has finished
restarting, the corresponding bit
will be automatically turned OFF.
...
Unit 0 Restart Bit
A50201
...
A50200
Unit 95 Restart Bit
• Exchanged data will be all zeros while the Unit is being restarted.
• Replace the ID Sensor Unit if an error cannot be cleared even after turning the power supply OFF and ON or after turning ON
the Special I/O Unit Restart Bit.
64
RFID System
User's Manual
SECTION 4
Data Exchange with the CPU Unit
Initial Settings Data
DM Area Allocations and Contents
The initial settings for the ID Sensor Unit are performed using the words allocated to the ID Sensor Unit
as a Special I/O Unit in the DM Area.
SYSMAC CS-/CJ-series PLC
ID Sensor Unit
CS1W-V680C11/CJ1W-V680C11
Transferred automatically
according to unit
number when power is
turned ON or the Special
I/O Unit Restart Bit is
turned ON.
Unit 95 D29500 to D29599
Initial Settings Data
D20000 + 100 × n to
Unit n D20000 + 100 × n + 99
Initial Settings
System Settings
m
Auto Wait Time
m+1
m+2
Write Protection Disable
m+3
Antenna Connection
m+4
Results Monitor Output
to
(Not used)
m+50
Test Settings
m+51
Test Settings
to
(Not used)
m+80
Run/Test Switching Method
m+81
Tag Memory Setting
(Not used)
to
m+90
Data Transfer Setting
to
(Not used)
(m = D20000 + 100 × Unit No.)
SECTION 4
Special I/O Unit Words in DM Area
Allocated Words
Unit 0 D20000 to D20099
Unit 1 D20100 to D20199
Unit 2 D20200 to D20299
Unit 3 D20300 to D20399
Unit 4 D20400 to D20499
Unit 5 D20500 to D20599
Unit 6 D20600 to D20699
Unit 7 D20700 to D20799
Unit 8 D20800 to D20899
Unit 9 D20900 to D20999
Unit 10 D21000 to D21099
SYSMAC CS-/CJ-series PLC
Special I/O Unit Words in DM Area
Allocated Words
Unit 0 D20000
to D20199 D20100
Unit 1
to D20299
Unit 2 D20200
to D20399 D20300
Unit 3
to D20499
Unit 4 D20400
to D20599 D20500
Unit 5
to D20699
Unit 6 D20600
to D20799 D20700
Unit 7
to D20899
Unit 8 D20800
to D20999 D20900
Unit 9
to D21099
Unit 10 D21000
to D21199
ID Sensor Unit
CS1W-V600C12/CJ1W-V600C12
Initial Settings
m
System Settings
Transferred automatically
according to unit
number when power is
turned ON or the Special
I/O Unit Restart Bit is
turned ON.
Unit n D20000 + 100 × n to
D20100 + 100 × n + 99
Unit 94
D29400 to D29599
m+1
m+2
m+3
m+4
to
m+50
m+51
Auto Wait Time
Write Protection Disable
Antenna Connection
Results Monitor Output
(Not used)
Test Settings
Test Settings
(Not used)
to
m+80
Run/Test Switching Method
m+81
Tag Memory Setting
(Not used)
to
m+90
Data Transfer Setting
to
(Not used)
m+100 System Settings
m+101 Auto Wait Time
m+102 Write Protection Disable
m+103 Antenna Connection
m+104 Results Monitor Output
(Not used)
to
(m = D20000 +100 × Unit No.)
• The words allocated to the ID Sensor Unit as a Special I/O Unit in the DM Area are determined by the setting of the unit
number switches on the Unit's front panel. Set unit numbers so that the same words are not allocated to more than one Unit.
(Refer to p. 63 for the setting method.)
• If the same unit number is set for more than one Special I/O Unit, a fatal error (No. duplication error on CX-Programmer or Unit
Number Duplication on Programming Console), and the PLC will not operate.
RFID System
User's Manual
65
SECTION 4
Data Exchange with the CPU Unit
DM Area Contents (Same for Run or Test Mode)
The following initial settings are set in the words allocated in the DM Area.
DM Area address
Antenna 1 of
CS1W-V680C11,
CS1W-V680C12,
CJ1W-V680C11, or
CJ1W-V680C12
Antenna 2 of
CS1W-V680C12 or
CJ1W-V680C12
Bit No.
Type
UID Addition Setting
Test Mode Disable Setting
0: Enabled
1: Disabled
p. 93
04 to 07
Setting for Write Verification
0: Verification
1: No verification
p. 94
00 to 03
RF Tag Communications
Speed Setting
0: Normal mode
1: High-speed mode
p. 94
00 to 15
The RF Tag timeout time
when the Communications
Specification is single auto or
repeat auto. An RF Tag
Missing Error will be
returned if this value is
exceeded.
0001 to 9999 (0.1s)
0000: Infinite
p. 95
m+100
SECTION 4
m+101
System Settings
Auto Wait Time
Setting
Initial Settings Data
08 to 15
Not used.
Write Protection
00 to 07 Disable Setting
Write Protection Disable
(V680 method/Disabled/
V600 method)
04 to 15
Not used.
Antenna Connection
00 to 03 Setting
Antenna Connection
04 to 15
Not used.
Results Monitor
00 to 03 Output Setting
Results Monitor Output
0: Communications time
1: Noise level
Test Operation
00: Communications test
A0: Range level
B0: Read speed level
B1: Write speed level
C0: Noise level
C1: Communications
success rate
00 to 07
Test Antenna
01: Antenna 1
02: Antenna 2
---
00 to 15
Number of Test Bytes
0000 to 0800 hex (bytes)
Not used.
m+80
---
04 to 15 Run/Test Switching
Method Setting
00 to 03 (Both Antennas 1 and
2)
m+81
---
m+2
m+3
m+4
m+102
m+103
m+104
08 to 15
m+50
Reference
p. 93
08 to 11
m+1
Setting
0: Disabled
1: Enabled
12 to 15
m
Description
Test Settings
(Both Antennas 1 and
2)
---
--00: V680 method
01: Disabled
02: V600 method
--0: Standard Antenna
1: V680-H01
---
--p. 95
--p. 96
--p. 96
p. 97
m+51
Run/Test Switching Method
Setting
04 to 15
m+90
---
Not used.
RF Tag Memory Setting
00 to 03 (Both Antennas 1 and 2) RF Tag Memory Setting
04 to 15
Not used.
Data Transfer Setting
(Both Antennas 1 and
00 to 03 2)
Data Transfer Setting
• First word allocated to Unit in DM Area: m = D20000 + 100  Unit number
66
RFID System
User's Manual
--0001: CPU Unit
0000: Test switch
--0: Standard Mode
1: CA1D Mode
--0: Use cyclic transfer
1: Use Intelligent I/O
Instructions
p. 98
SECTION 4
Data Exchange with the CPU Unit
I/O Data Allocations
Special I/O Unit Area Allocations and Contents
I/O data exchange for the ID Sensor Unit is performed using the words allocated to the ID Sensor Unit
as a Special I/O Unit in the Special I/O Unit Area.
ID Sensor Unit
CS1W-V680C11/CJ1W-V680C11
SYSMAC CS-/CJ-series PLC
Unit n
I/O Data
I/O refresh period
Refreshed every scan
during PLC's I/O
refresh period.
Outputs (CPU to ID
Sensor Unit) are
refreshed first,
followed by inputs
(ID Sensor Unit to
CPU Unit).
n to
n+6
Output refresh data
n+7 to
n+9
Input refresh data
(n = CIO 2000 + 10 × unit No.)
SECTION 4
Unit 0
Unit 1
Unit 2
Unit 3
Unit 4
Unit 5
Unit 6
Unit 7
Unit 8
Unit 9
Unit 10
Special I/O Unit Area
Allocated Words
CIO 2000 to CIO 2009
CIO 2010 to CIO 2019
CIO 2020 to CIO 2029
CIO 2030 to CIO 2039
CIO 2040 to CIO 2049
CIO 2050 to CIO 2059
CIO 2060 to CIO 2069
CIO 2070 to CIO 2079
CIO 2080 to CIO 2089
CIO 2090 to CIO 2099
CIO 2100 to CIO 2109
I/O Data Allocations
CIO 2000 + 10 × n to
CIO 2000 + 10 × n + 9
Unit 95 CIO 2950 to CIO 2959
ID Sensor Unit
SYSMAC CS-/CJ-series PLC
Special I/O Unit Area
Allocated Words
Unit 0
Unit 2
Unit 4
Unit 6
Unit 8
Unit 10
Unit n
CIO 2000
to CIO 2019 CIO 2010
Unit 1
CIO 2020 to CIO 2029
to CIO 2039 CIO 2030
Unit 3
CIO 2040 to CIO 2049
to CIO 2059 CIO 2050
Unit 5
CIO 2060 to CIO 2069
to CIO 2079 CIO 2070
Unit 7
CIO 2080 to CIO 2089
to CIO 2099 CIO 2090
Unit 9
CIO 2100 to CIO 2109
CS1W-V680C12/CJ1W-V680C12
I/O Data
I/O refresh period
n
to n+6
Refreshed every scan
during PLC's I/O
refresh period.
Outputs (CPU to ID
Sensor Unit) are
refreshed first,
followed by inputs
(ID Sensor Unit to
CPU Unit).
n+7
to n+ 9
n+10
to n+16
n+17
to n+19
Antenna 1
Output refresh data
Antenna 1
Input refresh data
Antenna 2
Output refresh data
Antenna 2
Input refresh data
(n = CIO 2000 + 10 × unit No.)
to CIO 2119
CIO 2000 + 10 × n to
CIO 2010 + 10 × n + 9
Unit 94 CIO 2940 to CIO 2959
• The words allocated to the ID Sensor Unit in the Special I/O Unit Area are determined by the setting of the unit number
switches on the Unit's front panel. Set unit numbers so that the same words are not allocated to more than one Unit. (Refer to
p. 63 for the setting method.)
• If the same unit number is set for more than one Special I/O Unit, a fatal error (No. duplication error on CX-Programmer or Unit
Number Duplication on Programming Console), and the PLC will not operate.
RFID System
User's Manual
67
SECTION 4
Data Exchange with the CPU Unit
Special I/O Unit Bit Allocations
The words in the Special I/O Unit Area are allocated as shown in the following table.
 Outputs
Word address
I/O
Antenna 1 of
CS1W-V680C11, Antenna 2 of
CS1W-V680C12, CS1W-V680C12 Bit No.
or
CJ1W-V680C11,
CJ1W-V680C12
or
CJ1W-V680C12
Output n
n+10
SECTION 4
I/O Data Allocations
n+1
n+11
15
Type
Bit name
Unit Controls Run/Test Bit
03 to 14
---
Not used
02
Abort Bit
Execution is aborted if this bit is
turned ON during command
execution.
If communications are aborted for
an FIFO trigger communications
specification, prohibiting
communications with any RF Tags
inside the interrogation zone will
be cleared.
01
Error Reset Bit
If this bit is turned ON while the ID
Sensor Unit is waiting for the
Command Execution Bit to be
turned ON, the Results
Information (CIO n+8) will be
cleared.
00
Command
Execution Bit
When this bit is turned ON, the ID
Sensor Unit will interpret the
command and start execution.
08 to 15 Command
Command Code
Specify the command to be
executed.
04 to 07
Communications
Specification
Specify the communications
method with the RF Tag.
00 to 03
Processing
Specification
Specify details of command
execution.
n+12
00 to 15
Processing
Address
Specify the processing start
address in the RF Tag.
n+3
n+13
00 to 15
Number of
Processing Bytes
Specify the number of processing
bytes in the RF Tag
n+4
n+14
00 to 15 Data Storage Data Storage
Specify the storage word address
Area
Word Address
in BCD.
(rightmost 4 digits)
n+5
n+15
12 to 15
Data Storage Area Specify the data storage area.
08 to 11
Bank Specification If the EM Area is specified, specify
the bank number.
00 to 07
Data Storage
Word Address
(leftmost 2 digits)
Specify the storage word address
in BCD.
00 to 15 Option
Command Option
Specify command option.
n+16
• First word allocated to Unit in CIO Area: n = CIO 2000 + 10  Unit number
RFID System
User's Manual
Turn ON for Test Mode, turn OFF
for Run Mode.
(Enabled only when DM=m+80 is
0001.)
n+2
n+6
68
Description
SECTION 4
Data Exchange with the CPU Unit
Command and Option Settings
Type
Command
Word
address
Command
name
Name
Option
n+1
Command
Code
(hex)
Communications Specification (hex)
(See note 2.)
Processing
Specification (hex)
(See
note 3.)
Data storage
order
0: Leftmost
 Rightmost
1: Rightmost
 Leftmost
n+3
n+6
Data stored in
Data Storage
Area
(See note 4.)
Reference
Processing
Address
(hex)
Number of
Processing
Bytes (hex)
0000 to
FFFF
0001 to
0800
---
Read data
Page 126
0000 to
FFFF
0001 to
0800
---
Write data
Page 127
0000 to
FFFF
0001 to
0004
---
Designation
Data for Bit Set
Page 128
0000 to
FFFF
0001 to
0004
---
Designation
Page 129
Data for Bit Clear
0000 to
FFFF
---
Designation
Write data
Data for Mask
0000 to FFFE
Page 130
Command
Option
00
Write
01
Bit Set
02
Bit Clear
03
Mask Bit Write
04
Calculation Write
05
0: Add
1: Subtract
0000 to
FFFF
0001 to
0004
Operation
Calculation
value
result
0000 to FFFF
Page 132
Data Fill
06
0: Bytes
1: Words
0000 to
FFFF
0001 to
0800
0000: All
Fill data
--0000 to FFFF
Page 133
Data Check
07
0: Calculation 0000 to
1: Verification FFFD
0003 to
0800
---
Page 134
Number of Writes
Control
08
0: Add
1: Subtract
0000 to
FFFD
---
No. to add
Result of number Page 135
0000 to 00FF of writes
calculation
Copy
(See note 1.)
09
---
Read
address
0000 to
FFFF
0001 to
0800
Write address --0000 to FFFF
Page 136
Read with Error
Correction
0A
0001 to
01FE
---
Read data
Page 137
0B
0000 to
FFFA
0001 to
01FE
---
Write data
Page 138
UID Read
0C
Data storage
order
0: Leftmost
 Rightmost
1: Rightmost
 Leftmost
0000 to
FFFA
Write with Error
Correction
0: Trigger
1: Single auto
2: Repeat auto
3. FIFO trigger
4. FIFO reader
5. Multi-access
trigger
6. Multi-access
repeat
---
---
---
Read data
Page 139
Noise
Measurement
10
0: Trigger
---
---
---
---
Measurement
results
Page 140
0: Trigger
1: Single auto
---
I/O Data Allocations
Read
SECTION 4
0: Trigger
1: Single auto
2: Repeat auto
3. FIFO trigger
4. FIFO repeat
5. Multi-access
trigger
6. Multi-access
repeat
n+2
Note 1. The Copy command cannot be used on the CS1W-V680C11/CJ1W-V680C11.
2. Refer to Communications Specifications for communications specifications.
p. 85
3. Refer to Designating Processing Specifications for designation methods.
p. 70
4. Refer to Designating Data Storage Areas for designation methods.
p. 70
RFID System
User's Manual
69
SECTION 4
Data Exchange with the CPU Unit
• Designating Processing Specifications
Commands
Processing Specification
Read
Write
Bit Set
Bit Clear
Mask Bit Write
Read with Error Correction
Write with Error Correction
UID Read
0: Leftmost to Rightmost
RF Tag
Address Bit
7
(hex)
0010
0
0011
0
0012
0
0013
0
0014
0
0015
0
0016
0
0017
0
0018
0
0019
0
CPU Unit Memory
Bit
0
1
2
3
4
5
6
7
8
9
A
Bit
Bit
15
00
D1000
D1001
01
02
03
04
D1002
05
06
D1003
07
08
D1004
09
0A
→: Read data storage order
1: Rightmost to Leftmost
RF Tag
SECTION 4
Address Bit
7
(hex)
0
0010
0
0011
0
0012
0
0013
0
0014
0
0015
0
0016
0
0017
0
0018
0
0019
Bit
CPU Unit Memory
0
I/O Data Allocations
1
2
3
4
5
6
7
8
9
A
Calculation Write
Number of Writes Control
0: Add
1: Subtract
Data Fill
0: Bytes (Rightmost 8 bits)
1: Words
Data Check
0: Calculation (write)
1: Verification
Bit
Bit
15
00
D1000
D1001
02
01
04
03
D1002
06
05
D1003
08
07
D1004
0A
09
→: Read data storage order
• Designating Data Storage Areas
Word address
Area
n+5
n+4
Bit No.
15 to 12
11 to 08
07 to 00
15 to 00
Specifiable range
Area specification
Bank
specification
Address
(leftmost 2 digits)
Address
(rightmost 4 digits)
DM
D00000 to D32767
0 hex
Always 0
000000 to 032767 (BCD)
CIO
CIO 0000 to CIO 6143
1 hex
Always 0
000000 to 006143 (BCD)
WR
W000 to W511
2 hex
Always 0
000000 to 000511 (BCD)
HR
H000 to H511
3 hex
Always 0
000000 to 000511 (BCD)
AR
A000 to A959
4 hex
Always 0
000000 to 000959 (BCD)
EM
E00000 to E32767
5 hex
0 to C hex
000000 to 032767 (BCD)
TIM
T0000 to T4095
6 hex
Always 0
000000 to 004095 (BCD)
CNT
C0000 to C4095
7 hex
Always 0
000000 to 004095 (BCD)
• If there is a mistake in designating the command and option, the Command Error Flag (CIO n+8, bit 00) in the Results
Information will turn ON, and the command will not be executed.
• If there is a mistake in designating the data storage area, the Data Storage Area Specification Error Flag (CIO n+8, bit 01) in
the Results Information will turn ON, and the command will not be executed.
70
RFID System
User's Manual
SECTION 4
Data Exchange with the CPU Unit
 Inputs
Word address
I/O
Input
Antenna 1 of
CS1W-V680C11,
CS1W-V680C12,
CJ1W-V680C11,
or
CJ1W-V680C12
n+7
Antenna 2 of
CS1W-V680C12
or
CJ1W-V680C12
n+17
Bit No.
Unit
Status
Unit Busy Flag
Turns ON when there is an ID Sensor Unit
error.
14
Test Mode Flag
Turns ON during Test Mode.
13
Antenna Power
Supply Error Flag
Turns ON when there is an error in the Unit
power supply or the external power supply.
12
Memory Error
Flag
Turns ON when there is an error in ID
Sensor Unit memory.
11
Antenna Error
Flag
The DM Area setting and V680-H01
Antenna connection status do not match.
Too many Antennas are connected or the
specified power consumption has been
exceeded.
03 to 10
---
Not used
02
Error End Flag
Turns ON when there is an ID Sensor Unit
error.
01
Normal End Flag
Turns ON for one scan when processing
ends normally.
00
ID Busy Flag
Turns ON while communications are in
progress.
15
Description
RFID System
User's Manual
I/O Data Allocations
Bit name
SECTION 4
Type
71
SECTION 4
Data Exchange with the CPU Unit
Word address
I/O
Input
(cont’d)
Antenna 1 of
CS1W-V680C11,
CS1W-V680C12,
CJ1W-V680C11,
or
CJ1W-V680C12
n+8
SECTION 4
I/O Data Allocations
72
RFID System
User's Manual
Antenna 2 of
CS1W-V680C12
or
CJ1W-V680C12
n+18
Bit No.
15
Type
Bit name
Results Antenna Error
Informa- Flag (Error Code:
tion
7C)
Description
Turns ON when an error occurs because
an Antenna is not connected.
Turns ON when the power is not correctly
supplied to the Antenna.
14
Verification Error
Flag
(Error Code: 71)
Turns ON when data cannot be written correctly to the RF Tag (only when verification
is specified).
13
RF Tags Address
Error Flag
(Error Code: 7A)
Turns ON when execution is not possible
because the processing address is not
specified correctly.
12
RF Tag Communications Error
Flag
(Error Code: 70)
Turns ON when communications cannot be
completed normally because an error
occurred in communications with the RF
Tag.
11
Write Protection
Error Flag
(Error Code: 7D)
Turns ON when an attempt is made to write
to a write-protected area.
Turns ON when the RF Tag is not an applicable model.
10
RF Tag Missing
Error Flag (Error
Code: 72)
Turns ON when the communications specification is designated as a trigger but there
is no RF Tag in the Antenna’s interrogation
zone.
Turns ON when there is no RF Tag in the
Antenna’s interrogation zone before the
Auto Wait Time elapses.
09
ID System Error 1
(Error Code: 79)
System error
08
ID System Error 2
(Error Code: 7E)
System error
07
ID System Error 3
(Error Code: 7F)
System error
05 to 06
---
Not used
04
Status Flag
(Error Code: 76)
Turns ON for a Calculation Write command
if addition results in an overflow or subtraction results in an underflow.
Turns ON when a difference is found for the
verification results for a Data Check command.
Turns ON when the specified number of
writes is exceeded for a Number of Writes
Control command.
Turns ON for a Copy command if an error
occurs when writing after data has been
read.
Turns ON when a 2-bit or larger memory
error cannot be corrected by the Read with
Error Correction command.
03
Error Correction
Flag
(Error Code: 77)
Turns ON when a 1-bit error correction was
performed for a read error.
02
---
Not used
01
Data Storage Area Turns ON when an illegal area is specified
Specification Error for the data storage area.
Flag
(Error Code: 14)
00
Command Error
Flag
(Error Code: 14)
Turns ON when there is an error in the setting for the Command, Communications
Specification, Processing Address, or
Number of Processing Bytes.
Turns ON when an attempt is made to execute the Copy command for the CS1WV680C11/CJ1W-V680C11.
SECTION 4
Data Exchange with the CPU Unit
Word address
Antenna 1 of
CS1W-V680C11,
CS1W-V680C12,
CJ1W-V680C11,
or
CJ1W-V680C12
I/O
Input
(cont’d)
n+9
Antenna 2 of
CS1W-V680C12
or
CJ1W-V680C12
n+19
Bit No.
Type
Bit name
00 to 15 Monitor
Description
Processing
Results Monitor
Run Mode
Word address
n+9
Bit No.
15 to 12
11 to 08
0
07 to 04
0
03 to 00
When the power supply is turned ON or communications
are started
0
At a normal end
Processing time (1 to 9999  10 ms) (hex) or Noise level (C0000 to
C099)
At an error end
E
0
0
I/O Data Allocations
• Processing Results Monitor Data
SECTION 4
■ Run Mode
 Communications Time
Normal end:
Processing time (1 to 9999 x 10 ms)
Max. error: 10 ms
Error end: “E0” + “Error Code”
Other: “0000”
 Noise Level
Communications end: “C0” + “00” to “99”
Measurement error: “E0” + “Error Code”
Other: “0000”
■ Test Mode
Normal end: “Command code” + <Results>
Error end: “E0” + “Error Code”
Other: “0000”
Cleared when the power supply is turned
ON or command execution starts.
Error code
Communications Test Mode
Word address
n+9
Bit No.
15 to 12
11 to 08
0
07 to 04
When the power supply is turned ON or communications
are started
0
0
At a normal end
Processing time (1 to 9999  10 ms) (hex)
At an error end
E
0
03 to 00
0
Error code
Range Level Measurement
Word address
n+9
Bit No.
15 to 12
11 to 08
07 to 04
03 to 00
At a normal end
A
0
Range level measurement
results (00 to 06)
At an error end
E
0
Error code
When a V680-H01 Antenna is connected, tests other than the communications test cannot be performed. No matter
which test is set, only the RF Tag communications test operation will be performed.
RFID System
User's Manual
73
SECTION 4
Data Exchange with the CPU Unit
Read Speed Level Measurement
Word address
n+9
Bit No.
15 to 12
11 to 08
07 to 04
03 to 00
When the power supply is turned ON or communications
are started
0
0
0
0
At a normal end
B
0
Read speed level measurement
results (EE, 01 to 06)
At an error end
E
0
Error code
When a V680-H01 Antenna is connected, tests other than the communications test cannot be performed. No matter
which test is set, only the RF Tag communications test operation will be performed.
Write Speed Level Measurement
Word address
n+9
SECTION 4
Bit No.
15 to 12
11 to 08
07 to 04
03 to 00
I/O Data Allocations
When the power supply is turned ON or communications
are started
0
0
0
0
At a normal end
B
1
Write speed level measurement
results (EE, 01 to 06)
At an error end
E
0
Error code
When a V680-H01 Antenna is connected, tests other than the communications test cannot be performed. No matter
which test is set, only the RF Tag communications test operation will be performed.
Noise Level
Word address
n+9
Bit No.
15 to 12
11 to 08
07 to 04
03 to 00
At a normal end
C
0
Noise level measurement
results (00 to 99)
At an error end
E
0
Error code
When a V680-H01 Antenna is connected, tests other than the communications test cannot be performed. No matter
which test is set, only the RF Tag communications test operation will be performed.
Read Communications Success Rate Measurement
Word address
n+9
Bit No.
15 to 12
11 to 08
07 to 04
03 to 00
At a normal end
C
1
Communications success rate
measurement results (EE, 01 to
99) (100%: FF)
At an error end
E
0
Error code
When a V680-H01 Antenna is connected, tests other than the communications test cannot be performed. No matter
which test is set, only the RF Tag communications test operation will be performed.
74
RFID System
User's Manual
SECTION 4
Data Exchange with the CPU Unit
• Error Codes
Error classification
Error Codes
Communications error with 7C
RF Tag
71
Error
Antenna error
Verification error
7A
RF Tag address error
70
RF Tag communications error
7D
Write protect error
72
RF Tag missing error
79
ID system error 1
7E
ID system error 2
7F
ID system error 3
76
Status error
77
Error corrected
Data storage area specification error, command error
SECTION 4
Host communications error 14
I/O Data Allocations
RFID System
User's Manual
75
SECTION 4
Data Exchange with the CPU Unit
MEMO
SECTION 4
I/O Data Allocations
76
RFID System
User's Manual
SECTION 5
ID Sensor Unit Functions
Communications Specifications
85
Parameter Settings in DM Area
93
RF Tag Memory
99
Write Protection
101
RF Tag Service Life Check
108
RF Tag Memory Check
112
RF Tag Memory Error Correction
114
RFID System
User's Manual
ID Sensor Unit Functions
78
SECTION 5
Operating Modes
77
SECTION 5
ID Sensor Unit Functions
Operating Modes
The ID Sensor Unit has two operating modes: Run Mode and Test Mode
There are two ways to switch between the two operating modes.
1. The test switch on the Unit's front panel
2. A software switch in memory
Run Mode
In Run Mode, communications are performed when the Command Execution Bit (CIO n, bit 0) in the
Special I/O Unit Area is turned ON. All commands can be used in this mode. Communications results
and Unit status are shown on the status indicators and in the Unit Status (CIO n+7), Results
Information (CIO n+8), and Processing Results Monitor (CIO n+9) in the Special I/O Unit Area.
Test Mode
SECTION 5
Test Mode is used to simulate actual operation. By using Test Mode, communications capability can be
measured easily in the actual operating environment. Test Mode is also useful for checking the
installation and checking the system while it is operating. The following five operations can be
performed in Test Mode.
Operating Modes
Operation
Description
RF Tag communications test
Executes communications with an RF Tag and outputs the results to
the Processing Results Monitor (CIO n+9) in the Special I/O Unit Area.
When using a Two-channels ID Sensor Unit, the test will be performed
alternately for Antennas 1 and 2.
Range level measurement
Measures the Antenna and RF Tag installation distance in relation to
the RF Tag interrogation zone. The measurement results are output to
the Processing Results Monitor (CIO n+9) in the Special I/O Unit Area.
The results can also be checked on the Amplifiers operation indicators.
Write/read speed level measurement
Measures the number of times that communications can be performed
consecutively based on the speed that RF Tags pass through the
Antenna interrogation zone. The measurement results are output to
the Processing Results Monitor (CIO n+9) in the Special I/O Unit Area.
The results can also be checked on the Amplifiers operation indicators.
Noise level measurement
Measures the ambient noise level in the installation environment. The
measurement results are output to the Processing Results Monitor
(CIO n+9) in the Special I/O Unit Area.
Communications success rate
measurement
Communicates 100 times with an RF Tag with no retries. The
measurement results are output to the Processing Results Monitor
(CIO n+9) in the Special I/O Unit Area.
When a V680-H01 Antenna is connected, tests other than the communications test cannot be performed. No matter
which test is set, only the RF Tag communications test operation will be performed.
• If the ID Sensor Unit is changed to Test Mode while a command is being executed, command execution will be
completed and then Test Mode will be entered.
• If an ID Sensor Unit error occurs, communications will stop regardless of the operating mode.
• First word allocated to Unit in CIO Area: n = CIO 2000 + 10  Unit number
78
RFID System
User's Manual
SECTION 5
ID Sensor Unit Functions
 Using the Test Mode
1. Set the operation in Test Mode
The operation to be performed in Test Mode is set in the DM Area. The settings are listed in the following table.
Test Operation
• Communications test
• Range level
• Read speed level
• Write speed level
• Noise level
• Communications success rate
Test Antenna
• Antenna 1
• Antenna 2
Number of Test Bytes
0000 to 0800 hex (bytes)
Run/Test Switching Method
• CPU Unit
• Test switch
For details on the settings for the operation in Test Mode, refer to Test Settings and Run/Test Switching Method Setting.
SECTION 5
p. 97
The Test Operation is started using the method set in the DM Area
To start Test Mode using the switch on the front of the Unit, set DM m+80 to 0000.
To start Test Mode using bit 15 of CIO n+0, set DM m+80 to 0001.
The test that is performed cannot be changed after entering Test Mode, even if the test settings in DM m+50 and DM
Operating Modes
2. Turn ON the test switch.
m+51 are changed. Always set the test settings in DM m+50 and DM m+51 before entering Test Mode.
Run Mode
Test Mode
Test Switch
or
CIO ((n+0), bit 15)
DM (m+50) and (m+51)
Set the test settings.
RFID System
User's Manual
79
SECTION 5
ID Sensor Unit Functions
 Communications Test
A communications test is used to execute communications with an RF Tag and output the
communications results to the Processing Results Monitor (CIO n+9) in the Special I/O Unit Area.
When using a Two-channels ID Sensor Unit, RF Tag communications are executed alternately for
Antennas 1 and 2.
The communications test checks only the read operation and does not check the write operation.
The communications test will be performed with the contents that was set in advance in DM m+50 and DM m+51.
In the communications test, communications are executed alternatively for Antennas 1 and 2, regardless of the
specified Antenna number.
1. Set the method to use to switch between Run Mode and Test Mode.
SECTION 5
To start Test Mode using the switch on the front of the Unit, set DM m+80 to 0000.
To start Test Mode using bit 15 of CIO n+0, set DM m+80 to 0001.
Operating Modes
After setting DM Area data with the Support Software, reset the power supply to the PLC or turn ON the Special I/O Unit
Restart Bit. The DM Area settings will be transferred to the ID Sensor Unit when the power supply turns ON or when the
Special I/O Unit Restart Bit is turned ON.
2. Set the operation to perform in Test Mode.
Set DM m+50 to 0000 and set the number of test bytes in DM m+51.
DM Area addresses are given in reference to “m,” where m = D20000 + 100  Unit number.
3. Turn ON the test switch.
The operation in Test Mode is started using the method set in the DM Area.
To start Test Mode using the switch on the front of the Unit, set DM m+80 to 0000.
To start Test Mode using bit 15 of (CIO n+0), set DM m+80 to 0001.
4. Communications with the RF Tag will begin.
Communications will be performed with the RF Tag and the communications results will be output to the Processing Results
Monitor (CIO n+9) in the Special I/O Unit Area.
80
RFID System
User's Manual
SECTION 5
ID Sensor Unit Functions
 Range Level Measurement
A range level measurement allows for easy checking of the installation positions of Antennas and RF
Tags.
This test operation measures the Antenna and RF Tag installation distance in relation to the RF Tag
interrogation zone. The measurement results are output to the Processing Results Monitor (CIO n+9)
in the Special I/O Unit Area. The measurement results can also be checked on the Amplifiers operation
indicators.
The range level changes dramatically depending on the ambient environment. Use it as a guide for the installation
position and test operation sufficiently in Run Mode using the actual installation environment. Levels higher than range
level 4 may not be displayed, but this does not indicate an error and performance in Run Mode will not be affected.
The communications test will be performed with the contents that was set in advance in DM m+50 and DM m+51.
SECTION 5
1. Set the method to use to switch between Run Mode and Test Mode.
To start Test Mode using the switch on the front of the Unit, set DM m+80 to 0000.
To start Test Mode using bit 15 of CIO n+0, set DM m+80 to 0001.
Restart Bit. The DM Area settings will be transferred to the ID Sensor Unit when the power supply turns ON or when the
Special I/O Unit Restart Bit is turned ON.
2. Set the operation to perform in Test Mode.
Operating Modes
After setting DM Area data with the Support Software, reset the power supply to the PLC or turn ON the Special I/O Unit
Set DM m+50 to A00X and set the number of test bytes in DM m+51.
Note: Set X to 1 to specify Antenna 1, and set X to 2 to specify Antenna 2.
DM Area addresses are given in reference to “m,” where m = D20000 + 100 Unit number.
3. Turn ON the test switch.
Measuring the range level is started using the method set in the DM Area.
To start Test Mode using the switch on the front of the Unit, set DM m+80 to 0000.
To start Test Mode using bit 15 of CIO n+0, set DM m+80 to 0001.
4. Range level measurement will begin.
The range level will be measured, and the communications results will be output to the Processing Results Monitor (CIO n+9) in
the Special I/O Unit Area. The measurement results can also be checked on the Amplifier's operation indicators.
RFID System
User's Manual
81
SECTION 5
ID Sensor Unit Functions
 Write/Read Speed Level Measurement
A speed level measurement allows for easy checking of the RF Tag's speed of movement and number
of usable bytes. This operation measures the number of times that communications can be performed
consecutively based on the speed that RF Tags pass through the Antenna interrogation zone and
outputs the measurement results to the Processing Results Monitor (CIO n+9) in the Special I/O Unit
Area. The measurement results can also be checked on the Amplifier's operation indicators.
The speed level measurement operation simulates writing data. Data is not actually written to the RF Tag.
The speed level measurement will be performed with the contents that was set in advance in DM m+50 and DM m+51.
1. Set the method to use to switch between Run Mode and Test Mode.
SECTION 5
To start Test Mode using the switch on the front of the Unit, set DM m+80 to 0000.
To start Test Mode using bit 15 of (CIO n+0), set DM m+80 to 0001.
Operating Modes
After setting DM Area data with the Support Software, reset the power supply to the PLC or turn ON the Special I/O Unit
Restart Bit. The DM Area settings will be transferred to the ID Sensor Unit when the power supply turns ON or when the
Special I/O Unit Restart Bit is turned ON.
2. Set the operation to perform in Test Mode.
Set DM m+50 to B00X (read) or B10X (write), and set the number of test bytes in DM m+51.
Note: Set X to 1 to specify Antenna 1, and set X to 2 to specify Antenna 2.
DM Area addresses are given in reference to “m,” where m = D20000 + 100  Unit number.
3. Turn ON the test switch.
Measuring the speed level is started using the method set in the DM Area.
To start Test Mode using the switch on the front of the Unit, set DM m+80 to 0000.
To start Test Mode using bit 15 of (CIO n+0), set DM m+80 to 0001.
4. Speed level measurement will begin.
The speed level will be measured, and the communications results will be output to the Processing Results Monitor (CIO n+9) in
the Special I/O Unit Area. The measurement results can also be checked on the Amplifier's operation indicators.
82
RFID System
User's Manual
SECTION 5
ID Sensor Unit Functions
 Noise Level Measurement
A noise level measurement enables checking for spatial noise, noise sources, and the effectiveness of
noise countermeasures.
This operation measures the ambient noise level in the installation environment and outputs the
measurement results to the Processing Results Monitor (CIO n+9) in the Special I/O Unit Area.
The noise level measurement will be performed with the contents that was set in advance in DM m+50 and DM m+51.
1. Set the method to use to switch between Run Mode and Test Mode.
To start Test Mode using the switch on the front of the Unit, set DM m+80 to 0000.
To start Test Mode using bit 15 of (CIO n+0), set DM m+80 to 0001.
After setting DM Area data with the Support Software, reset the power supply to the PLC or turn ON the Special I/O Unit
Special I/O Unit Restart Bit is turned ON.
2. Set the operation to perform in Test Mode.
Operating Modes
Set DM m+50 to C00X.
SECTION 5
Restart Bit. The DM Area settings will be transferred to the ID Sensor Unit when the power supply turns ON or when the
Note: Set X to 1 to specify Antenna 1, and set X to 2 to specify Antenna 2.
DM Area addresses are given in reference to “m,” where m = D20000 + 100  Unit number.
3. Turn ON the test switch.
Measuring the noise level is started using the method set in the DM Area.
To start Test Mode using the switch on the front of the Unit, set DM m+80 to 0000.
To start Test Mode using bit 15 of (CIO n+0), set DM m+80 to 0001.
4. Noise level measurement will begin.
The noise level will be measured, and the communications results will be output to the Processing Results Monitor (CIO n+9) in
the Special I/O Unit Area.
RFID System
User's Manual
83
SECTION 5
ID Sensor Unit Functions
 Communications Success Rate Measurement
The communications success rate measurement is used to check the communications success rate.
The ID Sensor Unit communicates 100 times with a RF Tag and outputs the measurement results to
the Processing Results Monitor (CIO n+9) in the Special I/O Unit Area.
The communications success rate is measured using read operations.
The communications success rate measurement will be performed with the contents that was set in advance in DM
m+50.
1. Set the method to use to switch between Run Mode and Test Mode.
To start Test Mode using the switch on the front of the Unit, set DM m+80 to 0000.
To start Test Mode using bit 15 of (CIO n+0), set DM m+80 to 0001.
SECTION 5
After setting DM Area data with the Support Software, reset the power supply to the PLC or turn ON the Special I/O Unit
Restart Bit. The DM Area settings will be transferred to the ID Sensor Unit when the power supply turns ON or when the
Operating Modes
Special I/O Unit Restart Bit is turned ON.
2. Set the operation to perform in Test Mode.
Set DM m+50 to C10X and set the number of test bytes in DM m+51.
Note: Set X to 1 to specify Antenna 1, and set X to 2 to specify Antenna 2.
DM Area addresses are given in reference to “m,” where m = D20000 + 100  Unit number.
3. Turn ON the test switch
Measuring the communications success rate is started using the method set in the DM Area.
To start Test Mode using the switch on the front of the Unit, set DM m+80 to 0000.
To start Test Mode using bit 15 of (CIO n+0), set DM m+80 to 0001.
4. Communications success rate measurement will begin.
The communications success rate will be measured and the measurement results will be output to the Processing Results
Monitor (CIO n+9) in the Special I/O Unit Area.
84
RFID System
User's Manual
SECTION 5
ID Sensor Unit Functions
Communications Specifications
There are seven execution sequences that can be used to communicate with the RF Tag. The sequence is
specified in the Communications Specification (CIO n+1, bits 04 to 07) in the command settings in the Special
I/O Unit Area.
Name
Trigger
0
When the Command Execution Bit turns ON, communications are performed with the
RF Tag in the interrogation zone and processing is ended.
1
After the Command Execution Bit turns ON, the ID Sensor Unit waits until an RF Tag
is detected in the interrogation zone, communications are performed, and processing
is ended.
2
The operation for a single auto specification is repeated. Once communications have
been completed with a specific RF Tag, communications will not be performed with it
again even if it remains in the interrogation zone. Processing is ended when the
Abort Bit is turned ON.
3
When the ID Sensor Unit receives a command, it communicates with an RF Tag and
returns a response. After communicating, all further operations with that RF Tag are
prohibited. The ID Sensor Unit communicates with only one RF Tag in the
interrogation zone. If an RF Tag that has been communicated with for a trigger
specification is within the interrogation zone, the ID Sensor Unit will not communicate
with it a second time.
4
When the ID Sensor Unit receives a command, it waits until an RF Tag is detected
within the interrogation zone, then returns a response. After communicating, all
further operations with that RF Tag are prohibited. After returning the response, the
ID Sensor Unit again waits for an RF Tag to approach it, and continues repeating the
operation until the Abort Bit turns ON.
5
When the ID Sensor Unit receives a command, it communicates with all RF Tags in
the interrogation zone, returns responses in order. After communicating, all further
operations with those RF Tags are prohibited. If there are no RF Tags in the
interrogation zone, the ID Sensor Unit will return an RF Tag missing error.
6
When the ID Sensor Unit receives a command, it waits for RF Tags to approach it. It
communicates with each RF Tag in the interrogation zone, and returns responses in
order. After communicating, all further operations with those RF Tags are prohibited.
After returning the responses, the ID Sensor Unit again waits for RF Tags to
approach it, and continues repeating the operation until the Abort Bit turns ON.
Single auto
Repeat auto
FIFO trigger
(See note)
FIFO repeat
(See note)
Multi-access trigger
(See note)
Multi-access repeat
(See note)
Communications Specifications
Description
SECTION 5
Communications
specification
Note: FIFO trigger, FIFO repeat, Multi-access trigger, and Multi-access repeat specification cannot be
used for communicating with V680-D1KP@@ RF Tags.
RFID System
User's Manual
85
SECTION 5
ID Sensor Unit Functions
Trigger
When a trigger is specified, communications are performed with the RF Tag when the Command
Execution Bit (CIO n, bit 0) in the Special I/O Unit Area turns ON and command execution is ended
when communications have been completed. If there is no RF Tag in the interrogation zone when the
Command Execution Bit turns ON, RF Tag Missing Error Flag (CIO n+8, bit 10) in the Results
Information in the Special I/O Unit Area will turn ON and an error code (E072) will be stored in the
Processing Results Monitor (CIO n+9). Use a sensor or other method to detect the presence of an RF
Tag before turning ON the Command Execution Bit.
Communications are
performed with an RF Tag
already in the
interrogation zone when
the Command Execution
Bit turns ON.
RF Tag
Interrogation zone
SECTION 5
Antenna
Communications Specifications
86
Trigger Specification
Note: Results are returned on whether
an RF Tag is detected.
Command Execution Bit
ID Busy Flag
Normal End Flag
Results
ID Tag Missing Error
Error End Flag
Results
Communications with
RF Tag
Comm. A
Comm. B
RF Tag movement
RF Tag A
RFID System
User's Manual
RF Tag B (missing)
SECTION 5
ID Sensor Unit Functions
Single Auto
With a single auto specification, the presence of an RF Tag is automatically detected, and
communications are performed, eliminating the need for detecting the RF Tag as is required for a
trigger specification. Command execution is ended as soon as communications are completed with
one RF Tag. Execution can also be ended by turning ON the Abort Bit (CIO n, bit 02) while the ID
Sensor Unit is waiting for the RF Tag.
An RF Tag is detected
as it enters the
interrogation zone and
communications are
performed.
RF Tag
Interrogation zone
Antenna
SECTION 5
Single Auto Specification
Command Execution Bit
Communications Specifications
Abort Bit
ID Busy Flag
Normal End Flag
Error End Flag
Communications with
RF Tag
RF Tag movement
Waiting for
RF Tag
Results
Waiting for RF Tag
Abort processing
Comm. A
RF Tag A
RF Tag B (missing)
RFID System
User's Manual
87
SECTION 5
ID Sensor Unit Functions
Repeat Auto
With a repeat auto specification, the presence of an RF Tag is automatically detected, and
communications are performed, eliminating the need for detecting the RF Tag as is required for a
trigger specification. As opposed to a single auto specification, command execution is not ended when
communications with the first RF Tag have been completed, rather the ID Sensor Unit waits for the next
RF Tag. Once communications have been completed with a specific RF Tag, communications will not
be performed with it again even if it remains in the interrogation zone. Repeat Auto execution can also
be ended by turning ON the Abort Bit (CIO n, bit 02).
RF Tag B
RF Tag are detected
as they enter the
interrogation zone
and communications
are performed.
RF Tag A
Interrogation zone
Antenna
SECTION 5
Repeat Auto Specification
Communications Specifications
88
Command Execution Bit
Abort Bit
ID Busy Flag
Results
Normal End Flag
Error End Flag
Communications with
RF Tag
Waiting for
RF Tag
Results
Waiting for
RF Tag
Comm. A
Results
Waiting for
RF Tag
Comm. B
Abort processing
Comm. C
RF Tag movement
RF Tag A
RFID System
User's Manual
RF Tag B
RF Tag C
SECTION 5
ID Sensor Unit Functions
FIFO Trigger
With a FIFO trigger communications specification, communications are executed with a RF Tag when a
command is sent. After communicating, the ID Sensor Unit returns a response. Operations are
prohibited for RF Tags that have completed communications until they leave the interrogation zone.
After the ID Sensor Unit sends a response, it will wait for the next command. If there is no RF Tag in the
interrogation zone when the ID Sensor Unit receives the command from the CPU Unit, the ID Sensor
Unit will return an RF Tag missing error.
With the FIFO trigger communications specification, even if there are RF Tags in the interrogation zone
that have completed communications, the ID Sensor Unit can still communicate with the next RF Tag.
(Commands will be accepted for an Antenna that is not processing a command.)
The Controller communicates with an RF Tag
in the interrogation zone when a command is
received from the CPU Unit. If there is no RF
Tag, an RF Tag missing error will be returned
in the response.
SECTION 5
An RF Tag that has completed
communications and for which
operations are prohibited.
RF Tag
Communications Specifications
Interrogation zone
Antenna
FIFO Trigger specification:
FIFO Trigger specification
FIFO Trigger specification
FIFO Trigger specification
Note: Results will be returned whether
an RF Tag is present.
Command Execution Bit
Abort Bit
ID Busy Flag
Tag missing error
Normal End Flag
Error End Flag
Communications with
RF Tag
Results
Comm. A
Results
Results
Comm. C
Comm. B
RF Tag movement
RF Tag A
RF Tag movement
RF Tag B
RF Tag C (missing)
RF Tag A
communications
completed
To communicate with RF Tags in the interrogation zone that have completed communications, turn ON the Abort Bit in
the Special I/O Unit Area (CIO n, bit 02) to cancel processing.
When using the V680-D2KF@@/-D@KF68/V680S-D2KF6@ with a FIFO trigger specification, the normal
communications speed will be used regardless of the setting in DM m+0.
FIFO trigger specification cannot be used for communicating with V680-D1KP@@ RF Tags.
RFID System
User's Manual
89
SECTION 5
ID Sensor Unit Functions
FIFO Repeat
With a FIFO repeat communications specification, the ID Sensor Unit automatically detects RF Tags
that enter the interrogation zone after a command is sent and communicates with them repeatedly.
Operations are prohibited for RF Tags that have completed communications until they leave the
interrogation zone. After communicating, the ID Sensor Unit returns a response. ID Sensor Unit
processing ends when the Abort Bit is turned ON. The ID Sensor Unit will wait for the next command.
With the FIFO repeat communications specification, even if there are RF Tags in the interrogation zone
that have completed communications, the ID Sensor Unit can still communicate with the next RF Tag.
(Commands will be accepted for an Antenna that is not processing a command.)
RF Tags are detected as
they enter the interrogation
zone and communications
are performed.
An RF Tag that has completed
communications and for which
operations are prohibited.
RF Tag
SECTION 5
Interrogation zone
Communications Specifications
Antenna
FIFO Repeat Specification:
FIFO Repeat specification
Command Execution Bit
Abort Bit
ID Busy Flag
Waiting for RF Tag
Communications with
RF Tag
Comm. A
Results
Results
Results
Normal End Flag
Error End Flag
Waiting for new RF Tag
Waiting for new RF Tag
Comm. B
Abort processing
Comm. C
RF Tag movement
RF Tag A
RF Tag movement
RF Tag B
RF Tag A
communications
completed
RF Tag C
RF Tag B
communications
completed
When using the V680-D2KF@@/-D@KF68/V680S-D2KF6@ with a FIFO repeat specification, the normal
communications speed will be used regardless of the setting in DM m+0.
FIFO repeat specification cannot be used for communicating with V680-D1KP@@ RF Tags.
90
RFID System
User's Manual
SECTION 5
ID Sensor Unit Functions
Multi-access Trigger
With a multi-access trigger communications specification, communications are executed with multiple
RF Tags when a command is sent. The ID Sensor Unit sends responses sequentially as
communications with the RF Tags in the interrogation zone are completed. Move the results data
stored in the Data Storage Area to another area before the results data from the next RF Tag is stored.
After the ID Sensor Unit has completed communications with all of the RF Tags in the interrogation
zone, the ID Busy Flag will turn OFF, and the ID Sensor Unit will wait for the next command.
(Commands will be accepted for an Antenna that is not processing a command.)
When the Command Execution Bit (CIO n, bit 00)
is turned ON, the ID Sensor Unit will
communicate with all RF Tags in the interrogation
zone. If there are no RF Tags in the interrogation
zone, an RF Tag missing error will be returned.
RF Tag
SECTION 5
Antenna
Communications Specifications
Multi-access Trigger Specification
Multi-access Trigger specification
Note: Results will be returned whether
or not an RF Tag is present.
Command Execution Bit
Abort Bit
Note: After communications with all RF Tags in the
interrogation zone have been completed, the
ID Busy Flag will turn OFF.
ID Busy Flag
Results
Results
Results
Normal End Flag
Error End Flag
Communications with
RF Tag
RF Tag movement
RF Tag movement
RF Tag movement
Comm. A
Comm. B
Comm. C
RF Tag A
RF Tag B
RF Tag C
When using the V680-D2KF@@/-D@KF68/V680S-D2KF6@ with a multiple-access trigger specification, the normal
communications speed will be used regardless of the setting in DM m+0.
Multi-access trigger specification cannot be used for communicating with V680-D1KP@@ RF Tags.
RFID System
User's Manual
91
SECTION 5
ID Sensor Unit Functions
Multi-access Repeat
With a multi-repeat communications specification, the ID Sensor Unit automatically detects multiple RF
Tags that enter the interrogation zone and communicates with them repeatedly when a command is
sent. The ID Sensor Unit sends responses sequentially as communications with the RF Tags in the
interrogation zone are completed. Move the results data stored in the data storage area to another
area before the results data from the next RF Tag is stored. Even after the ID Sensor Unit has sent the
responses, the ID Sensor Unit continues to automatically detect RF Tags that enter the interrogation
zone and communicates with them repeatedly. Operations are prohibited for RF Tags that have
completed communications until they leave the interrogation zone. ID Sensor Unit processing ends
when the Abort Bit is turned ON. The ID Sensor Unit will wait for the next command. (Commands will
be accepted for an Antenna that is not processing a command.)
RF Tags are detected as they
enter the interrogation zone
and communications are
performed.
SECTION 5
RF Tag
Communications Specifications
Antenna
Multi-access Repeat Specification
Multi-access Repeat Specification
Command Execution Bit
Abort Bit
ID Busy Flag
Results
Normal End Flag
Error End Flag
Communications with
RF Tag
RF Tag movement
RF Tag movement
RF Tag movement
Waiting for new RF Tag
Waiting for RF Tag
Comm. A
Results
Results
Comm. B
Abort processing
Comm. C
RF Tag A
RF Tag B
RF Tag C
When using the V680-D2KF@@/-D@KF68/V680S-D2KF6@ with a multi-access repeat specification, the normal
communications speed will be used regardless of the setting in DM m+0.
Multi-access repeat specification cannot be used for communicating with V680-D1KP@@ RF Tags.
92
RFID System
User's Manual
SECTION 5
ID Sensor Unit Functions
Parameter Settings in DM Area
The following parameter settings can be adjusted to the user application to optimize the performance and
reliability of the ID Sensor Unit.
• System Settings
• Auto Wait Time Setting
• Write Protection Disable Setting
• Antenna Connection Setting
• Results Monitor Output Setting
• Test Settings
• Run/Test Switching Method Setting
Although the default settings can be used for most applications without any problems, the parameters can be
changed to optimize the system.
System Settings
 UID Addition Setting
DM Area address
Antenna 2 of
CS1W-V680C12 or
CJ1W-V680C12
Bit No.
m
m+100
12 to 15
Description
0
UID not added
1
UID added
Default
0
(Not added)
Note: If adding the UID is specified, the UID (8 bytes) will be appended to the front of the read
response data.
If using Intelligent I/O Instructions is specified as the data transfer method, set the IORD service control information
area address information in D00004 to D00007 to 1. The first four words of data will be the UID data.
Parameter Settings in DM Area
Antenna 1 of
CS1W-V680C11,
CS1W-V680C12,
CJ1W-V680C11, or
CJ1W-V680C12
SECTION 5
These settings are used to set whether or not a UID will be added to the read command response.
 Test Mode Disable Setting
This setting can be used to disable entering Test Mode using the test switch on the front panel of the ID
Sensor Unit. The test switch can be disabled to prevent accidentally entering Test Mode.
DM Area address
Antenna 1 of
CS1W-V680C11,
CS1W-V680C12,
CJ1W-V680C11, or
CJ1W-V680C12
Antenna 2 of
CS1W-V680C12 or
CJ1W-V680C12
Bit No.
m
m+100
08 to 11
Description
0
Test switch enabled.
1
Test switch disabled (always Run Mode).
Default
0
(Enabled)
RFID System
User's Manual
93
SECTION 5
ID Sensor Unit Functions
 Verification Setting
Verification can be enabled for write operations, or verification can be disabled to shorten the
communications time. The verification setting is valid for all commands except for Read and Data
Check with a processing specification of verification.
DM Area address
Antenna 1 of
CS1W-V680C11,
CS1W-V680C12,
CJ1W-V680C11,
or
CJ1W-V680C12
Antenna 2 of
CS1W-V680C12
or
CJ1W-V680C12
m
m+100
Bit No.
04 to 07
Description
0
Verify write operations.
1
Do not verify write operations.
Default
0
(Verification)
 Communications Speed Setting
High-speed communications can be set whenever the communications method is set to trigger, single
auto, or repeat auto.
SECTION 5
Parameter Settings in DM Area
94
DM Area address
Antenna 1 of
CS1W-V680C11,
CS1W-V680C12,
CJ1W-V680C11,
or
CJ1W-V680C12
Antenna 2 of
CS1W-V680C12
or
CJ1W-V680C12
m
m+100
Bit No.
00 to 03
Description
0
Communications speed setting: Normal
1
Communications speed setting: High speed
Default
0
(normal)
• First word allocated to Unit in DM Area: m = D20000 + 100  Unit number
After setting DM Area data with the Support Software, reset the power supply to the PLC or turn ON the Special I/O Unit Restart
Bit. The DM Area settings will be transferred to the ID Sensor Unit when the power supply turns ON or when the Special I/O Unit
Restart Bit is turned ON.
RFID System
User's Manual
SECTION 5
ID Sensor Unit Functions
Auto Wait Time Setting
If a normal response is not received in communications with an RF Tag when the RF Tag has been
detected, retry processing will be performed to resend the same command. Retry processing is
performed until the Auto Wait Time has expired while the ID Sensor Unit is waiting for an RF Tag. The
RF Tag wait status begins for a single auto specification, when command execution is started. From
the second RF Tag for a repeat auto specification, it begins when communications with the previous
RF Tag have been completed.
Command Execution Bit
ID Busy Flag
Normal End Flag
RF Tag Missing Error
Results
Error End Flag
Waiting for RF Tag,
Auto Wait Time exceeded.
Waiting for RF Tag
Communications with
RF Tag
Results
Comm. A
RF Tag movement
RF Tag B (missing)
RF Tag A
Antenna 2 of
CS1W-V680C12 or
CJ1W-V680C12
Bit No.
Type
m+1
m+101
00 to 15
0000 to 9999
Description
1 to 9999  0.1 s
0: Infinite (Time not monitored)
Default
0
(Infinite)
• First word allocated to Unit in DM Area: m = D20000 + 100  Unit number
After setting DM Area data with the Support Software, reset the power supply to the PLC or turn ON the Special I/O Unit
Restart Bit. The DM Area settings will be transferred to the ID Sensor Unit when the power supply turns ON or when the
Special I/O Unit Restart Bit is turned ON.
Parameter Settings in DM Area
Antenna 1 of
CS1W-V680C11,
CS1W-V680C12,
CJ1W-V680C11, or
CJ1W-V680C12
SECTION 5
DM Area address
Write Protection Disable Setting
The write protection disable setting can be used to disable the write protection settings in RF Tags.
DM Area address
Antenna 1 of
Antenna 2 of
CS1W-V680C11,
CS1W-V680C12
CS1W-V680C12,
CJ1W-V680C11, or CJ1W-V680C12
or CJ1W-V680C12
m+2
m+102
Bit No.
00 to 07
Description
00
Write protection enabled using V680 method
01
Write protection disabled.
02
Write protection enabled using V600 method
Default
00 (Write
protection
enabled using
V680 method)
First word allocated to Unit in DM Area: m = D20000 + 100  Unit number
After setting DM Area data with the Support Software, reset the power supply to the PLC or turn ON the Special I/O Unit
Restart Bit. The DM Area settings will be transferred to the ID Sensor Unit when the power supply turns ON or when the
Special I/O Unit Restart Bit is turned ON.
RFID System
User's Manual
95
SECTION 5
ID Sensor Unit Functions
Antenna Connection Setting
The Antenna connection setting can be used to set whether or not a V680-H01 Antenna is connected
to the ID Sensor Unit.
DM Area address
Antenna 1 of
CS1W-V680C11,
CS1W-V680C12,
CJ1W-V680C11, or
CJ1W-V680C12
Antenna 2 of
CS1W-V680C12 or
CJ1W-V680C12
Bit No.
m+3
m+103
00 to 03
Description
0
Standard Antenna connected.
1
V680-H01 Antenna connected.
Default
0
(Standard)
First word allocated to Unit in DM Area: m = D20000 + 100  Unit number
After setting DM Area data with the Support Software, reset the power supply to the PLC or turn ON the Special I/O Unit
Restart Bit. The DM Area settings will be transferred to the ID Sensor Unit when the power supply turns ON or when the
SECTION 5
Special I/O Unit Restart Bit is turned ON.
The V680-H01 Antenna can be connected to only a One-channel ID Sensor Unit. It cannot be connected to a Twochannels ID Sensor Unit.
Parameter Settings in DM Area
Results Monitor Output Setting
DM Area address
Antenna 1 of
CS1W-V680C11,
CS1W-V680C12,
CJ1W-V680C11, or
CJ1W-V680C12
Antenna 2 of
CS1W-V680C12 or
CJ1W-V680C12
Bit No.
Description
0
m+4
m+104
00 to 03
Communications time
Noise level
1
Default
0
(communications
time)
First word allocated to Unit in DM Area: m = D20000 + 100  Unit number
After setting DM Area data with the Support Software, reset the power supply to the PLC or turn ON the Special I/O Unit
Restart Bit. The DM Area settings will be transferred to the ID Sensor Unit when the power supply turns ON or when the
Special I/O Unit Restart Bit is turned ON.
96
RFID System
User's Manual
SECTION 5
ID Sensor Unit Functions
Test Settings
The test settings are used to set the operation, Antenna, and number of test bytes used in Test Mode.
DM Area address
Bit No.
Type
Test Settings
(Both Antennas 1 and 2)
Description
Test Operation
00: Communications test
A0: Range level
B0: Read speed level
B1: Write speed level
C0: Noise level
C1: Communications success rate
Test Antenna
01: Antenna 1
02: Antenna 2
Number of Test Bytes
0000 to 0800 hex (bytes)
08 to 15
m+50
00 to 07
m+51
00 to 15
Setting value
First word allocated to Unit in DM Area: m = D20000 + 100  Unit number
You can switch between Run Mode and Test Mode by using the test switch or by using bit 15 of CIO
n+0.
m+80
00 to
03
Type
Run/Test Switching Method
Setting
(Both Antennas 1 and 2)
Description
Run/Test Switching
Method Setting
Set value
1: CPU Unit
0: Test switch
First word allocated to Unit in DM Area: m = D20000 + 100  Unit number
After setting DM Area data with the Support Software, reset the power supply to the PLC or turn ON the Special I/O Unit
Restart Bit. The DM Area settings will be transferred to the ID Sensor Unit when the power supply turns ON or when the
Parameter Settings in DM Area
DM Area address Bit No.
SECTION 5
Run/Test Switching Method Setting
Special I/O Unit Restart Bit is turned ON.
RF Tag Memory Setting
This setting can be used to set the RF Tag memory map to the map that is used with ID Controllers for
Heat-resistant RFID Systems (V680-CA1D/-CA2D).
DM Area address Bit No.
m+81
00 to
03
Type
RF Tag Memory Setting
(Both Antennas 1 and 2)
Description
RF Tag Memory Setting
Set value
1: CA1D Mode
0: Standard Mode
RFID System
User's Manual
97
SECTION 5
ID Sensor Unit Functions
Data Transfer Setting
The data transfer method for the Read, Write, Read with Error Correction, and Write with Error
Correction command can be set to cyclic transfer or to the IORD/IOWR instructions.
Cyclic data transfers will be used for all other commands regardless of the setting of the data transfer
method. If the IORD/IOWR instructions are executed to transfer data when cyclic data transfer is
specified, data will not be transferred and an error will occur.
DM Area address Bit No.
m+90
00 to
03
Type
Data Transfer Setting
(Both Antennas 1 and 2)
Description
Data Transfer Setting
Set value
0: Use cyclic transfer
0: Use Intelligent I/O Instructions
First word allocated to Unit in DM Area: m = D20000 + 100  Unit number.
After setting word m+90 in the DM Area with the Support Software, reset the power supply to the PLC or turn ON the
Special I/O Unit Restart Bit. The setting in m+90 in the DM Area will be transferred to the ID Sensor Unit when the
power supply turns ON or when the Special I/O Unit Restart Bit is turned ON.
SECTION 5
Parameter Settings in DM Area
98
RFID System
User's Manual
SECTION 5
ID Sensor Unit Functions
RF Tag Memory
The memory access area for the ID Sensor Unit is 64 Kbytes from addresses 0000 to FFFF (hex). The area
that can actually be accessed is determined by the memory capacity of the RF Tag.
 V680-D1KP@@ RF Tags
Address
(hex)
Bit 7
Bit 0
0000
Write protection settings
Block
(8 bytes)
0003
User area
0006
0007
0008
0009
Block
(8 bytes)
SECTION 5
000F
0010
03E6
03E7
RF Tag Memory
1 byte
 V680-D2KF@@ and V680S-D2KF@@ RF Tags
Address
(hex)
Bit 7
Bit 0
0000
Write protection settings
Block
(8 bytes)
0003
0006
User area
0007
0008
Block
(8 bytes)
0009
000F
0010
07CE
07CF
1 byte
RFID System
User's Manual
99
SECTION 5
ID Sensor Unit Functions
 V680-D8KF@@ RF Tags
Address
(hex)
0000
Bit 7
Bit 0
Write protection settings
Block
(8 bytes)
0003
0006
0007
User area
0008
0009
Block
(8 bytes)
000F
0010
1FFE
1FFF
1 byte
SECTION 5
 V680-D32KF68 RF Tags
Address
(hex)
Bit 7
Bit 0
0000
RF Tag Memory
Write protection settings
Block
(8 bytes)
0003
0006
User area
0007
0008
0009
Block
(8 bytes)
000F
0010
7FE6
7FE7
1 byte
 V680S-D8KF@@ RF Tags
Address
(hex)
0000
Bit 7
Bit 0
Write protection settings
Block
(32 bytes)
0003
001E
001F
User area
0020
0021
Block
(32 bytes)
003F
0040
1FFE
1FFF
1 byte
100
RFID System
User's Manual
SECTION 5
ID Sensor Unit Functions
Write Protection
The write protection function is provided so that product model numbers and other important product
information stored in the RF Tags can be protected from being lost though careless write operations. We
recommend that write protection be set after important data has been written.
Either of two write protection methods can be used, the V680 method or the V600 method. The method can be changed by
setting DM m+2 (Write Protection Disable Setting). Normally use the V680 method. If a V600 system is replaced with the V680,
the V600 method can be used to enable using the current RF Tag memory map, eliminating the need to change system
programming.
Setting Write Protection Using the V680 Method
Write protection is set in four bytes of RF Tag addresses 0000 to 0003 (hex). The setting for the most
significant bit of address 0000 (hex) specifies whether or not write protection is enabled for the RF Tag.
Write Protection Setting Area in RF Tag Memory Map
7
0000
Enable/
Disable
Bit
6
5
4
3
2
1
0
SECTION 5
Address
(hex)
Upper two digits of start address (00 to 7F)
Lower two digits of start address (00 to FF)
0002
Upper two digits of end address (00 to FF)
0003
Lower two digits of end address (00 to FF)
Write Protection
0001
• The most significant bit of address 0000 (hex) is the Write-protect Bit.
ON: Enable write protection
OFF: Disable write protection
• Write Protection Setting Ranges
Start address: 0000 to 7FFF hex
End address: 0000 to FFFF hex
If write protection is enabled, write separately to the write protection setting area (addresses 0000 to 0003 hex) and the rest of
the RF Tag (addresses 0004 hex and higher). If the MSB of address 0000 hex is ON and you write both the write protection
setting area (addresses 0000 to 0003 hex) and following addresses at the same time, a write protection error will occur.
If write protection is disabled, you can use the write protection setting area (addresses 0000 to 0003 hex) as normal user
memory. If you use the write protection setting area (addresses 0000 to 0003 hex) as normal user memory, be sure to disable
write protection in the ID Sensor Unit.
RFID System
User's Manual
101
SECTION 5
ID Sensor Unit Functions
• Write Protection Setting Example
Start Address Lower Than End Address
All addresses from the start address to the end address, inclusive, will be write-protected.
Address
(hex)
0000
0001
0002
0003
Upper digit
1
0
0
0
0
0
8
0
0
0
0
1
0
1
0
0
0
0015 hex
0
1
0120 hex
0
1
0
0
Write-protected
5
0
0
0
0
0
0
0
1
0
0000 hex
Lower digit
1
1
0
0
0
2
0
03E7 hex
Start Address Equals End Address
SECTION 5
Only the set address (1 byte) will be write-protected.
Address (hex)
0000
Write Protection
0001
0002
0003
Upper digit
1
0
0
Lower digit
0
0
0
8
0
0
1
0
0
0
0
0
0
0
0
0121 hex
0
0
0
0
0
0
1
1
2
0
0000 hex
0
0
1
0
0
Write-protected
1
1
0
2
0
0
0
03E7 hex
End Address Exceeds Last RF Tag Address
All addresses from the start address to the final address in the RF Tag, inclusive, will be write-protected.
Address (hex)
0000
0001
0002
0003
Upper digit
1
0
0
0
0
0
Lower digit
0
0
0
0
0
0
0
0
0
0
0
0
8
0
1
1
1
1
3
1
F
0
0
0
1
1
3
0
1
0000 hex
1
1
1
1
F
0300 hex
03E7 hex
The write protection setting area in the RF Tag is not write-protected.
102
RFID System
User's Manual
Write-protected
SECTION 5
ID Sensor Unit Functions
Start Address Greater Than End Address
All addresses from the start address to the final address and all addresses from address 0004 hex to
the end address in the RF Tag, inclusive, will be write-protected.
Address (hex)
0000
0001
0002
Upper digit
1
0
0
Lower digit
0
0
0
8
0
0
0
0
0
0
1
0
0
0
0
0
0
0
0
1
0
1
2
1
0
0
0
0
0
1
0
0
0003
0
1
0
1
5
0000 hex
0004 hex
End address
0120 hex
Write Protection
0015 hex
SECTION 5
Write-protected
Start address
Write-protected
03E7 hex
The write protection setting area in the RF Tag is not write-protected.
Clearing Write Protection Using the V680 Method
To temporarily clear write protection, e.g., to overwrite the write-protected data, turn OFF the MSB of
address 0000 hex in the RF Tag.
Application Precaution for Write Protection
Write protection is implemented by the ID Sensor Unit. It will not be effective for Reader Writers from other companies.
RFID System
User's Manual
103
SECTION 5
ID Sensor Unit Functions
Setting Write Protection Using the V600 Method
With the V600 Series, different write protection setting methods are used for EEPROM Data Carriers
(V600-D23P@@) (without batteries) and SRAM Data Carriers (with batteries). When using V600
commands with the V680-series ID Sensor Unit, the data memory setting in the ID Sensor Unit and the
type of RF Tags can be selected to enable using the previous write protection setting method.
• Using EEPROM RF Tags (V680-D1KP@@)
V600 EEPROM Write Protection Method
• Using FRAM RF Tags (V680-D2K/8K/32KF@@)
V600 SRAM Write Protection Method
The ID Sensor Unit will automatically switch between the V600 EEPROM write protection method and the V600 SRAM
write protection method. No user setting is required.
SECTION 5
 V600 EEPROM Write Protection Method
(The following information applies when the V600 write protection
method is set and V680-D1KP@@ RF Tags are used.)
Write protection is set by writing the end address to be protected in address 0000 hex of the RF Tag.
The area between address 0001 hex and the end address will be write-protected. The status of the
most significant bit of address 0000 hex determines whether write protection is enabled.
Write Protection
Therefore, addresses 0080 to 03E7 hex cannot be set as the end address.
If the end address is set to 00 hex, however, all addresses from 0001 to 03E7 hex will be protected.
Memory Map of Write Protection Setting Area for V600 EEPROM Write Protection Method
Address (hex)
7
0000
Enable/
Disable Bit
6
5
4
3
2
1
0
End address
• Setting of MSB of Address 0000 Hex
ON: Write protection enabled
OFF: Write protection disabled
• End Address Setting Range
End address: 00 or 01 to 7F hex
If write protection is enabled, write separately to the write protection setting area (address 0000 hex) and the rest of the RF Tag
(addresses 0001 hex and higher). If the MSB of address 0000 hex is ON and you write both the write protection setting area
(address 0000 hex) and following addresses at the same time, a write protection error will occur.
104
RFID System
User's Manual
SECTION 5
ID Sensor Unit Functions
Write Protection Setting Examples
The following settings would write-protect addresses 0001 through 0012 hex:
Address
(hex)
0000
Upper digit
1
0
0000 hex
Lower digit
0
0
0
0
8
0
0
0012 hex
0
Write-protected
03E7 hex
End Address Set to 00 Hex
The entire memory except address 0000 hex is write-protected by setting the end address to 00
hex, as shown below.
Address
(hex)
0000
Upper digit
1
0
Lower digit
0
0
0
0
8
0
0000 hex
0
Write-protected
0
03E7 hex
SECTION 5
The write protection setting area in the RF Tag is not write-protected.
Write protection is set by writing the start address and the end address to be protected in addresses
0002 to 0005 hex of the RF Tag. The area between the start address and the end address will be writeprotected. The status of the most significant bit of address 0002 hex determines whether write
protection is enabled.
If the V600 SRAM write protection method is being used and write protection is enabled in the ID
Sensor Unit, addresses 0000 and 0001 hex will always be write-protected (regardless of the write
protection enable/disable setting in the RF Tag).
Memory Map of Write Protection Setting Area for V600 EEPROM Write Protection Method
Address (hex)
7
0002
Enable/
Disable Bit
6
5
4
3
2
1
Write Protection
 V600 SRAM Write Protection Method
(The following information applies when the V600 write protection
method is set and V680-D2K/8K/32KF@@ RF Tags are used.)
0
Upper two digits of start address (00 to 7F hex)
0003
Lower two digits of start address (00 to FF hex)
0004
Upper two digits of end address (00 to FF hex)
0005
Lower two digits of end address (00 to FF hex)
• Setting of MSB of Address 0002 Hex
ON: Write protection enabled
OFF: Write protection disabled
• Range in RF Tag for Which Write Protection Can Be Set
Start address: 0006 to 7FFF hex
End address: 0006 to FFFF hex
If write protection is enabled, write separately to the write protection setting area (addresses 0002 to 0005 hex) and the
rest of the RF Tag (addresses 0006 hex and higher). If the MSB of address 0002 hex is ON and you write both the write
protection setting area (addresses 0002 to 0005 hex) and following addresses at the same time, a write protection error
will occur.
RFID System
User's Manual
105
SECTION 5
ID Sensor Unit Functions
• RF Tag Write Protection Setting Examples
Start Address Lower Than End Address
All addresses from the start address to the end address, inclusive, will be write-protected.
Address
(hex)
0000
0001
0002
0003
Upper digit
1
0
0
0
0
0
8
0
0
0
0
1
0
1
0
0
0
0015 hex
0
1
0120 hex
0
1
0
0
Write-protected
5
0
0
0
0
0
0
0
1
0
0000 hex
Lower digit
1
1
0
0
0
2
0
7FE7 hex
Start Address Equals End Address
SECTION 5
Only the set address (1 byte) will be write-protected.
Address (hex)
0000
Write Protection
0001
0002
0003
Upper digit
1
0
0
0
0
0
Lower digit
0
0
0
0
1
0
0
0
0
0
0
0
8
0
1
0
0
0
1
0121 hex
1
0
0
0
0
2
0
0000 hex
0
Write-protected
0
1
0
0
0
2
1
7FE7 hex
End Address Exceeds Last RF Tag Address
All addresses from the start address to the final address in the RF Tag, inclusive, will be write-protected.
Address (hex)
0000
0001
0002
0003
Upper digit
1
0
0
Lower digit
0
0
0
8
0
0
1
1
1
1
1
0
0
1
1
1
1
3
0
0
0
0
1
1
1
1
1
1
1
1
0
0
F
F
0000 hex
1
F
F
0300 hex
Write-protected
7FE7 hex
The write protection setting area in the RF Tag is not write-protected.
Addresses 0000 and 0001 hex will always be write-protected (regardless of the write protection enable/disable setting in
the RF Tag).
106
RFID System
User's Manual
SECTION 5
ID Sensor Unit Functions
Start Address Greater Than End Address
All addresses from the start address to the final address and all addresses from address 0006 hex to
the end address in the RF Tag, inclusive, will be write-protected.
Address (hex)
0002
0003
0004
Upper digit
1
0
0
Lower digit
0
0
0
8
0
0
0
0
0
1
0
0
0
0
0
0
0
0
1
0
0
0
0
0
0
1
0
1
0
0005
1
1
2
0
0
0
1
5
0000 hex
0004 hex
End address
0120 hex
Write Protection
0015 hex
SECTION 5
Write-protected
Start address
Write-protected
7FE7 hex
The write protection setting area in the RF Tag is not write-protected.
Addresses 0000 and 0001 hex will always be write-protected (regardless of the write protection enable/disable setting in
the RF Tag).
Clearing Write Protection Using the V600 Method
To temporarily clear write protection, e.g., to overwrite the write-protected data, turn OFF the MSB of
the following address in the RF Tag.
• V600 EEPROM write protection method:
0000 hex
• V600 SRAM write protection method:
0002 hex
• V680 write protection method:
0000 hex
Application Precaution for Write Protection
Write protection is implemented by the ID Sensor Unit. It will not be effective for Reader Writers from other companies.
RFID System
User's Manual
107
SECTION 5
ID Sensor Unit Functions
RF Tag Service Life Check
The Number of Writes Control command can be used to determine whether the RF Tag write limit has been
exceeded. Detecting when the write life has been exceeded for an RF Tag is performed by using the Number
of Writes Control command that determines whether the write count (100,000 times or a user specified value)
for an RF Tag has been exceeded.
There are two ways to manage the number of writes. One is to add to the number of writes and then detect
when the total exceeds 100,000 writes. The other is to subtract from a user-specified number of writes and
then detect whether the write count has been exceeded.
 Number of Writes Control 1 (Life Control = Preset Number of Writes)
The Number of Writes Control Area consists of 3 bytes from the
start address. The Number of Writes Control command is
executed with an Add specification. The specified numbers of
writes are added and the total is written to the control area.
SECTION 5
When the value in the number of writes control area exceeds
the preset number of writes (100,000 writes) (0186A0 hex), the
Upper digit
Middle digit
3 bytes
Lower digit
Status Flag (CIO n+8, bit 04) in the Results Information turns
ON. If the value in the control area already exceeds 100,000
RF Tag Service Life Check
writes, the value will not be changed.
• Application Method
The life of the RF Tag can be managed by updating the number of writes value when data is written to
the address most frequently written. (The life of EEPROM RF Tags is 100,000 writes for any one data
block (8 bytes), so the number of writes must be counted for the address that is written most
frequently.) It is also possible to confirm the number of writes without updating the number of writes
value.
Write stage
Data written
No. of writes updated/
life checked
Life confirmation
stage
108
Area start
address
RFID System
User's Manual
Life checked
SECTION 5
ID Sensor Unit Functions
• Application Example
The following example uses 3 bytes starting at address 0010 (hex) as the number of writes control
area.
1) A Write command is executed to clear the control area.
Bit
Bit
Address 7
0
(hex)
000F
0010
0011
0012
0013
0
0
0
0
0
0
2) The Number of Writes Control command is executed with an Add specification and the number of
writes set to 4.
Bit
0
Bit
7
0
0
4
3) The Number of Writes Control command is executed with an Add specification and the number of
writes set to 5.
Address
(hex)
000F
0010
0011
0012
0013
Bit
0
Bit
7
0
0
0
RF Tag Service Life Check
0
0
0
SECTION 5
Address
(hex)
000F
0010
0011
0012
0013
0
0
9
4) The following illustration shows memory status when the total number of writes has reached 100,000
writes. If the Number of Writes Control command is executed with an Add specification and the
number of writes set to 5, the Status Flag (CIO n+8, bit 04) in the Results Information will turn ON.
Bit
Bit
Address 7
0
(hex)
000F
0010
0
1
0011
8
6
0012
A
0
0013
For any one RF Tag, use only an Add specification or a Subtract specification for the Number of Writes Control command. If both
specifications are used for the same RF Tag, the number of writes control will not be possible.
RFID System
User's Manual
109
SECTION 5
ID Sensor Unit Functions
 Number of Writes Control 2 (Life Control = User Setting)
The Number of Writes Control Area consists of 3 bytes from the
start address. The Number of Writes Control command is
executed with a Subtract specification. The specified number of
writes is subtracted and the result is written to the control area.
Therefore, to enable control of the number of writes, the
maximum number of writes must be written to the Number of
Area start
address
Upper digit
Middle digit
3 bytes
Lower digit
Writes Control Area beforehand. The user-specified number of
writes can be set to up to 16,700,000. The specified number of
writes for EEPROM RF Tags, however, is 100,000 writes
(0186A0 hex) at 25C max., so be sure to set the number of
writes to 100,000 or less. When the value in the number of writes control area is less than 0, the Status
Flag (CIO n+8, bit 04) in the Results Information turns ON. If the value in the control area is already
less than 0, the value will not be changed.
• Application Method
SECTION 5
RF Tag Service Life Check
110
A user-specified number of writes can be used for life control by writing the desired value in the
Number of Writes Control Area in advance. The life of the RF Tag can be managed by updating the
number of writes value when data is written to the address most frequently written. (The RF Tag has a
limited life for any one block of 8 bytes, so the number of writes must be counted for the address that is
written most frequently.) It is also possible to confirm the number of writes without updating number of
writes value.
Write stage
Data written
No. of writes updated/
life checked
Life confirmation
stage
RFID System
User's Manual
Life checked
SECTION 5
ID Sensor Unit Functions
• Application Example
The following example uses 3 bytes starting at address 0010 (hex) as the number of writes control
area.
1) A Write command is executed to set the control area to 100,000 writes.
(Leftmost)Bit
Address 7
(hex)
000F
0010
0
0011
8
0012
A
0013
Bit(Rightmost)
0
1
6
0
2) The Number of Writes Control command is executed with a Subtract specification and the number of
writes set to 5.
Bit(Rightmost)
0
SECTION 5
1
6
B
3) The following illustration shows memory status when the total number of writes has reached
100,000 writes. If the Number of Writes Control command is executed with a Subtract specification
and the number of writes set to 5, the Status Flag (CIO n+8, bit 04) in the Results Information will
turn ON.
(Leftmost)Bit
Address 7
(hex)
000F
0010
0
0011
0
0012
0
0013
RF Tag Service Life Check
(Leftmost)Bit
Address 7
(hex)
000F
0010
0
0011
8
0012
9
0013
Bit(Rightmost)
0
0
0
0
For any one RF Tag, use only an Add specification or a Subtract specification for the Number of Writes Control command. If both
specifications are used for the same RF Tag, the number of writes control will not be possible
RFID System
User's Manual
111
SECTION 5
ID Sensor Unit Functions
RF Tag Memory Check
The Memory Check command performs an RF Tag memory check. A CRC (Cyclic Redundancy Check) code
calculation, write, and comparison are made using the check block unit specified by the user. The CRC code
is calculated from the generated polynomial expression X16 + X12 + X5 + 1.
A memory check is performed by using the Data Check command
Address (hex)
with a Calculation processing specification to write the check code
00
and a Verification processing specification to verify the check code.
01
The start address and the number of bytes determine the specified
check block. All but the last 2 bytes are the area to calculate and the
last 2 bytes are the check code area.
When the Data Check command is executed to write the check code,
the CRC code is calculated for the area to calculate and written in the
Area start
address
Area for check
code calculation
(number of check block
bytes minus 2)
Number of
check block
bytes
check code area.
CRC (upper digit)
SECTION 5
CRC (lower digit)
Check code
area (2 bytes)
RF Tag Memory Check
When the Data Check command is executed to verify the check code, the CRC code is calculated for the area
to calculate and compared with the data in the check code area. If the calculated code is the same as the data
in the check code area, the Normal End Flag (CIO n+7, bit 01) in Unit Status will turn ON. If they are not the
same, the Error End Flag (CIO n+7, bit 02) in Unit Status will turn ON, and the Status Flag (CIO n+8, bit 04) in
the Results Information will turn ON as a warning.
• Application Method
After writing the data, the Data Check command is executed with a Calculation processing specification to
calculate and write the check code. Before reading the data, the Data Check command is executed with a
Verification processing specification to verify the check code. This enables detecting internal data corruption
that might occur in the RF Tag when the data is not being accessed.
Write stage
Data written
Check code calculated
Read stage
Check code verified
Data read
112
RFID System
User's Manual
SECTION 5
ID Sensor Unit Functions
• Application Example
The following example checks the data in addresses 0010 to 0012 (hex).
1) Assume that the following data is initially in memory.
Address
(hex)
Bit
0
Bit
7
000F
0010
0011
0012
0013
0014
0015
1
3
5
2
4
6
2) The Data Check command is executed to calculate the check code for 5 bytes beginning with
address 0010 (hex). The CRC Code 5CD6 hex calculated from the data “123456” is written to
addresses 0013 and 0014 (hex).
SECTION 5
Bit
0
2
4
6
C
6
3) The Data Check command is executed to verify the check code for 5 bytes beginning with address
0010 (hex). If the data is normal, the Normal End Flag in Unit Status (CIO n+7, bit 01) is turned ON.
Address
(hex)
000F
0010
0011
0012
0013
0014
0015
RF Tag Memory Check
Bit
Address 7
(hex)
000F
0010
1
0011
3
0012
5
5
0013
0014
D
0015
Bit
0
Bit
7
1
3
5
5
D
2
4
6
C
6
If the check codes are not the same, the Error End Flag (CIO n+7, bit 02) in Unit Status is turned ON.
Bit
Address 7
(hex)
000F
0010
0
0011
3
0012
5
5
0013
0014
D
0015
Bit
0
0
4
6
C
6
Data error
RFID System
User's Manual
113
SECTION 5
ID Sensor Unit Functions
RF Tag Memory Error Correction
The Write with Error Correction command can be used to write an RF Tag memory check code and error
correction code to the five bytes of memory after the write data. The Read with Error Correction command
performs a RF Tag memory check and makes 1-bit memory error corrections.
Address (hex)
When a 1-bit memory error is corrected, the
0000
Error Correction Flag (CIO n+8, bit 03) in the
0001
Results Information will turn ON to warn that a
1-bit memory error occurred, and the normal
Area start
address
data with the error corrected will be returned.
Memory check
code calculation
Error correction code
area
calculation area
When a 2-bit or larger memory error is detected,
the Status Flag (CIO n+8, bit 04) in the Results
Information turn ON to warn that a fatal error
Area end
address
Memory check code (upper digits)
occurred, and the read data will not be returned.
Memory check code (lower digits)
Error correction code (upper digits)
Error correction code (middle digits)
SECTION 5
Error correction code (lower digits)
RF Tag Memory Error Correction
 Example of RF Tag Memory Error Correction
In the following example, the data in addresses 0010 to 0015 (hex) is checked.
1. Send the Write with Error Correction Command.
• First word allocated to Special I/O Unit in CIO Area: CIO 20000 + 10 x 0 = CIO 20000
Meaning
Word
address
Contents
15 14 13 12 11 10
User's Manual
5
4
00
10
First address to process
CIO 2003
00
06
Number of bytes to process
CIO 2004
11
00
Data storage location (lower 4 digits)
0
00
00
Command code
Data storage
area
Bank designation*
(always 0)
00
*: Always 0 when DM Area is specified, --- : Ignored.
RFID System
6
CIO 2002
CIO 2006
114
7
Communications
specification
0B
0
0
8
CIO 2001
CIO 2005
0
9
---
3
2
1
Data order
Data storage location
(upper 2 digits)
0
SECTION 5
ID Sensor Unit Functions
2. Data is written to addresses 0010 to 0015 (hex), then an RF Tag memory check code and a error
correction code (5 bytes) are written to addresses 0016 to 001A (hex).
CS-series CPU Unit Memory
Bit 15
RF Tag
Bit 00
Address Bit 7
(hex)
Bit 0
D1100
32
31
㩷
0010
31
D1101
34
33
Send Write ID Tag
Memory Error Correction
0011
32
D1102
36
35
0012
33
0013
34
0014
35
: Write
data storage order
Write data
memory check code
calculation area
(
)
0015
36
0016
FD
Memory check code (upper digits)
0017
11
Memory check code (lower digits)
0018
00
Error correction code (upper digits)
0019
0C
Error correction code (middle digits)
001A
3C
Error correction code (lower digits)
3. Send the Read with Error Correction command.
• First word allocated to Special I/O Unit in CIO Area: CIO 20000 + 10 x 0 = CIO 20000
Contents
15 14 13 12 11 10
7
6
5
4
Communications
specification
00
10
First address to process
CIO 2003
00
06
Number of bytes to process
CIO 2004
11
00
Data storage location (lower 4 digits)
CIO 2006
00
00
Command code
Data storage
area
Bank specification *
(always 0)
00
3
2
1
0
Data order
Data storage location
(upper 2 digits)
---
*: Always 0 when DM Area is specified, --- : Ignored.
● If the Data Is Normal
● If a 1-bit Memory Error Is Corrected
The Normal End Flag in Unit Status (CIO n+7,
The Error End Flag in Unit Status (CIO n+7, bit
bit 01) turns ON.
02) is turned ON, and the Error Correction Flag
RF Tag Memory Error Correction
CIO 2002
0
0
8
0B
0
0
9
CIO 2001
CIO 2005
SECTION 5
Meaning
Word
address
(CIO n+8, bit 03) in the Results Information is
turned ON as a warning.
● If a Memory Error of 2 Bits or More Is Detected
The Error End Flag in Unit Status (CIO n+7, bit
02) is turned ON, and the Status Flag (CIO
n+8, bit 04) in the Results Information is turned
ON.
RFID System
User's Manual
115
SECTION 5
ID Sensor Unit Functions
MEMO
SECTION 5
RF Tag Memory Error Correction
116
RFID System
User's Manual
SECTION 6
Controlling the ID Sensor Unit
ID Sensor Unit Operation
118
Communications Commands
125
Communications Time
141
SECTION 6
Controlling the ID Sensor Unit
RFID System
User's Manual
117
SECTION 6
Controlling the ID Sensor Unit
ID Sensor Unit Operation
The user program in the CS/CJ-series CPU Unit is used to operate the ID Sensor Unit. The ID Sensor Unit
performs communications with RF Tags through the Antenna according to data set in the Special I/O Unit
Area of the CS/CJ-series CPU Unit.
Outline of Operation
User Program
MOV, OUT, etc.
Unit controls
Commands
Data storage area
Special I/O
Unit Area
CIO n to
CIO n+6
Command
interpretation
and
execution
CIO n+7 to
CIO n+9
Execution
results
Data storage
area
Storing
read data.
Getting
write data.
MOV, LD, etc.
Unit status
Results information
Processing results monitor
SECTION 6
Read data
Calculation results
Write data
ID Sensor Unit Operation
118
RF Tag
ID Sensor Unit
Amplifier or Antenna
CS/CJ-series CPU Unit
• The ID Sensor Unit will complete execution of any command that is being executed even if the CPU Unit is changed to
PROGRAM Mode.
• If an ID Sensor Unit error occurs, communications will stop regardless of the operating mode.
• First word allocated to Unit in CIO Area: n = CIO 2000 + 10  Unit number
RFID System
User's Manual
SECTION 6
Controlling the ID Sensor Unit
Commands Used to Read Data (Cyclic Data Transfer for Read,
Read with Error Correction, and UID Read)
CS/CJ-series CPU Unit
(1)(2)
CIO n to
CIO n+6
(3)(4)
CIO n+7
(4)
CIO n+8
to CIO n+9
(4)
Data storage
area
(4)
RF Tag
Amplifier or Antenna
Special I/O
Unit Area
ID Sensor Unit
Read
data
address, and other parameters for reading RF Tag data in the Special I/O Unit Area.
2) Use the user program to turn ON the Command Execution Bit (CIO n, bit 00) in the Special I/O Unit
3) When the ID Sensor Unit detects that the Command Execution Bit has turned ON, it turns ON the ID
Busy Flag (CIO n+7, bit 00).
4) The ID Sensor Unit reads the data from the RF Tag, places the Results Information (CIO n+8) and
Processing Results Monitor information (word n+9) in the Special I/O Unit Area, places the data
read from the RF Tag in the data storage words, turns OFF the ID Busy Flag (CIO n+7, bit 00), and
ID Sensor Unit Operation
Area.
SECTION 6
1) Use the user program to set the processing address, number of processing bytes, data storage word
turns ON the Normal End Flag (CIO n+7, bit 01) for one scan.
5) Use the Results Information (CIO n+8), the Processing Results Monitor information (CIO n+9), and
the read data stored in the data storage words in the user program only after the Normal End Flag
(CIO n+7, bit 01) turns ON. The Results Information (CIO n+8) will be held until the Error Reset Bit
(CIO n, bit 01) is turned ON or until the next communications command is received.
• Data is transferred to the data storage words at a rate of 160 bytes per scan.
RFID System
User's Manual
119
SECTION 6
Controlling the ID Sensor Unit
Commands Used to Read Data (Intelligent I/O Instruction Data
Transfer for Read and Read with Error Correction)
CS/CJ-series CPU Unit
(1)(2)
CIO n to
CIO n+6
(3)(4)
CIO n+7
(4)
CIO n+8
to CIO n+9
(4)
Data storage
area
(5)
RF Tag
Amplifier or Antenna
Special I/O
Unit Area
ID Sensor Unit
Read
data
SECTION 6
1) Use the user program to set the processing address, number of processing bytes, data storage word
address, and other parameters for reading RF Tag data in the Special I/O Unit Area.
2) Use the user program to turn ON the Command Execution Bit (CIO n, bit 00) in the Special I/O Unit
ID Sensor Unit Operation
Area.
3) When the ID Sensor Unit detects that the Command Execution Bit has turned ON, it turns ON the ID
Busy Flag (CIO n+7, bit 00).
4) The ID Sensor Unit reads the data from the RF Tag, places the Results Information (CIO n+8) and
Processing Results Monitor information (word n+9) in the Special I/O Unit Area, turns OFF the ID
Busy Flag (CIO n+7, bit 00), and turns ON the Normal End Flag (CIO n+7, bit 01) for one scan.
5) Use the IORD instruction in the user program to transfer the read data to the data storage words
after the Normal End Flag (CIO n+7, bit 01) turns ON. Then use the Results Information (CIO n+8),
the Processing Results Monitor information (CIO n+9), and the read data.
The Results Information (CIO n+8) will be held until the Error Reset Bit (CIO n, bit 01) is turned ON
or until the next communications command is received.
• By using the IORD instruction, up to 2,048 bytes of data can be transferred in one scan.
120
RFID System
User's Manual
SECTION 6
Controlling the ID Sensor Unit
Commands Used to Write Data (Cyclic Data Transfer for Write,
Bit Set, Bit Clear, Mask Bit Write, Calculation Write, Data Fill,
Data Check, Number of Writes Control, and Write with Error
Correction)
ID Sensor Unit
CS/CJ-series CPU Unit
Special I/O
Unit Area
(3)
(2)(3)
CIO n to
CIO n+6
(4)(6)
CIO n+7
Data storage
area (1)
(6)
(5)
Write
data
RF Tag
CIO n+8
to CIO n+9
SECTION 6
Amplifier or Antenna
(6)
1) Use the user program to set the write data in the data storage area.
address, and other parameters for writing RF Tag data in the Special I/O Unit Area.
3) Use the user program to turn ON the Command Execution Bit (CIO n, bit 00) in the Special I/O Unit
Area.
4) When the ID Sensor Unit detects that the Command Execution Bit has turned ON, it turns ON the ID
ID Sensor Unit Operation
2) Use the user program to set the processing address, number of processing bytes, data storage word
Busy Flag (CIO n+7, bit 00).
5) The ID Sensor Unit reads the write data from the data storage words to internal memory and then
writes the data to the RF Tag.
6) The ID Sensor Unit writes the data to the RF Tag, places the Results Information (CIO n+8) and
Processing Results Monitor information (word n+9) in the Special I/O Unit Area, turns OFF the ID
Busy Flag (CIO n+7, bit 00), and turns ON the Normal End Flag (CIO n+7, bit 01) for one scan.
The Results Information (CIO n+8) will be held until the Error Reset Bit (CIO n, bit 01) is turned ON or
until the next communications command is received.
• Data is transferred to the data storage words at a rate of 160 bytes per scan.
RFID System
User's Manual
121
SECTION 6
Controlling the ID Sensor Unit
Commands Used to Write Data (Intelligent I/O Instruction Data
Transfer for Write and Write with Error Correction)
CS/CJ-series CPU Unit
Special I/O
Unit Area
ID Sensor Unit
(3)
(2)(4)
CIO n to
CIO n+6
(5)(6)
CIO n+7
Data storage
area (1)
(6)
(3)
Write
data
RF Tag
CIO n+8
to CIO n+9
Amplifier or Antenna
(6)
1) Use the user program to set the write data in the data storage area.
SECTION 6
2) Use the user program to set the processing address, number of processing bytes, data storage word
address, and other parameters for writing RF Tag data in the Special I/O Unit Area.
ID Sensor Unit Operation
3) Use the IOWR instruction in the user program to transfer the write data in the data storage words to
the ID Sensor Unit.
4) Use the user program to turn ON the Command Execution Bit (CIO n, bit 00) in the Special I/O Unit
Area.
5) When the ID Sensor Unit detects that the Command Execution Bit has turned ON, it turns ON the ID
Busy Flag (CIO n+7, bit 00).
6) The ID Sensor Unit writes the data to the RF Tag, places the Results Information (CIO n+8) and
Processing Results Monitor information (word n+9) in the Special I/O Unit Area, turns OFF the ID
Busy Flag (CIO n+7, bit 00), and turns ON the Normal End Flag (CIO n+7, bit 01) for one scan.
The Results Information (CIO n+8) will be held until the Error Reset Bit (CIO n, bit 01) is turned ON or
until the next communications command is received.
• By using the IOWR instruction, up to 2,048 bytes of data can be transferred in one scan.
122
RFID System
User's Manual
SECTION 6
Controlling the ID Sensor Unit
Copy Command
The following example shows writing the data from RF Tag A for Antenna 1 to RF Tag B for Antenna 2.
CS/CJ-series CPU Unit
(5)
CIO n+8
to CIO n+9
RF Tag A
(3)
CIO n+7
RF Tag B
CIO n to
CIO n+6
Antenna 1
Amplifier 1
(1)(2)
Antenna 2
Amplifier 2
Special I/O
Unit Area
ID Sensor Unit
(4)
Read
data
(5)
Data storage
area
1) Use the user program to set the processing address, number of processing bytes, data storage word
2) Use the user program to turn ON the Command Execution Bit (CIO n, bit 00) in the Special I/O Unit
3) When the ID Sensor Unit detects that the Command Execution Bit has turned ON, it turns ON the ID
Busy Flag (CIO n+7, bit 00).
4) The ID Sensor Unit will read data from RF Tag A and write it to RF Tag B.
5) The ID Sensor Unit writes the data to the RF Tag, places the Results Information (CIO n+8) and
Processing Results Monitor information (word n+9) in the Special I/O Unit Area, turns OFF the ID
ID Sensor Unit Operation
Area.
SECTION 6
address, and other parameters for copying RF Tag data in the Special I/O Unit Area.
Busy Flag (CIO n+7, bit 00), and turns ON the Normal End Flag (CIO n+7, bit 01) for one scan.
The Results Information (CIO n+8) will be held until the Error Reset Bit (CIO n, bit 01) is turned ON or
until the next communications command is received.
RFID System
User's Manual
123
SECTION 6
Controlling the ID Sensor Unit
Noise Measurement Command
CS/CJ-series CPU Unit
(1)(2)
Amplifier
Special I/O
Unit Area
ID Sensor Unit
CIO n to
CIO n+6
(3)(4)
CIO n+7
(4)
CIO n+8
to CIO n+9
(4)
Data storage
area
(4)
Noise
measurement
results
1) Use the user program to set the storage words for noise measurement data and other parameters in
the Special I/O Unit Area.
SECTION 6
2) Use the user program to turn ON the Command Execution Bit (CIO n, bit 00) in the Special I/O Unit
Area.
ID Sensor Unit Operation
3) When the ID Sensor Unit detects that the Command Execution Bit has turned ON, it turns ON the ID
Busy Flag (CIO n+7, bit 00).
4) The ID Sensor Unit measures the noise around the Antenna, places the Results Information (CIO
n+8) and Processing Results Monitor information (word n+9) in the Special I/O Unit Area, places the
noise measurement results in the data storage words, turns OFF the ID Busy Flag (CIO n+7, bit 00),
and turns ON the Normal End Flag (CIO n+7, bit 01) for one scan.
5) Use the Results Information (CIO n+8), the Processing Results Monitor information (CIO n+9), and
noise measurement results in the data storage words in the user program only after the Normal End
Flag (CIO n+7, bit 01) turns ON.
124
RFID System
User's Manual
SECTION 6
Controlling the ID Sensor Unit
Communications Commands
Commands
Command name
Read
Command
code
00
Function
Reads data from the RF Tag's memory.
Writes data to the RF Tag's memory.
02
Sets the specified bits of the specified area in the RF Tag.
Bit Clear
03
Clears the specified bits of the specified area in the RF Tag.
04
Masks the specified bits in the specified area of the RF Tag and writes data to the bits
that are not masked.
05
Writes the calculation result between memory data and the specified data to the RF
Tag.
Data Fill
06
Writes the specified data to the specified area of the RF Tag.
Data Check
07
Calculates and verifies check codes for RF Tag memory.
Number of Writes Control
08
Controls RF Tag write life.
09
Writes the data read from an RF Tag by one Antenna to the RF Tag for the other
Antenna.
This command is supported by Two-channels ID Sensor Units only.
0A
Reads data from the RF Tag's memory.
Also uses a memory check code to check data reliability.
0B
Writes data to the RF Tag's memory.
Also writes the memory check code for the data reliability checking to the memory of
the RF Tag.
UID Read
0C
Reads the RF Tag's ID code.
Noise Measurement
10
Measures the noise and returns the noise level as the measurement result.
Mask Bit Write
Calculation Write
Copy
Read with Error Correction
Write with Error Correction
• The Data Fill command will write data to the user area in the RF Tag regardless of the setting of write protection
• If there is an error in the command or option specifications, the Command Error Flag (CIO n+8, bit 00) in the Results
Information will turn ON and the command will not be executed.
RFID System
User's Manual
Communications Commands
01
Bit Set
SECTION 6
Write
125
SECTION 6
Controlling the ID Sensor Unit
Command Descriptions
 Read
Reads the specified number of bytes from the specified start address in the RF Tag.
Up to 2,048 bytes (i.e., 1,024 words) can be read with one command execution.
Word address
Antenna 1 of
CS1W-V680C11,
CS1W-V680C12,
CJ1W-V680C11,
or CJ1W-V680C12
Antenna 2 of
CS1W-V680C12
or
CJ1W-V680C12
Bit No.
Type
08 to 15
Bit name
Command Code
00 hex
Communications
Specification
p. 85
Specify the communications method with
the RF Tag.
04 to 07
n+1
Description
n+11
Command
0
Trigger
1
Single Auto
2
Repeat Auto
3
FIFO trigger
4
FIFO repeat
5
Multi-access trigger
6
Multi-access repeat
SECTION 6
Communications Commands
Specify the read data storage order.
00 to 03
Processing
Specification
p. 70
Specify the first RF Tag address to read,
Setting range: 0000 to FFFF hex
Specify the number of RF Tag read bytes.
Setting range: 0001 to 0800 hex
0
Leftmost  Rightmost
1
Rightmost  Leftmost
n+2
n+12
00 to 15
Processing
Address
n+3
n+13
00 to 15
Number of
Processing Bytes
n+4
n+14
00 to 15
Specify the read data storage destination.
Data Storage
p. 70
Word Address
(rightmost 4 digits)
12 to 15
08 to 11
n+5
n+15
Data
storage
area
n+16
00 to 15
Bank Specification
Data Storage
Word Address
(leftmost 2 digits)
00 to 07
n+6
Data Storage Area
Option
Command Option
Not used
• Check the memory capacity of the RF Tag before setting the Processing Address and Number of Processing Bytes. If
the Processing Address and Number of Processing Bytes are not suitable for the RF Tags for which communications
are being performed, the RF Tag Address Error Flag (CIO n+8, bit 13) will turn ON.
126
RFID System
User's Manual
SECTION 6
Controlling the ID Sensor Unit
 Write
Writes the specified number of bytes of data beginning at the specified start address in the RF Tag.
Up to 2,048 bytes (i.e., 1,024 words) can be written with one command execution.
Word address
Antenna 1 of
CS1W-V680C11,
CS1W-V680C12,
CJ1W-V680C11,
or CJ1W-V680C12
Antenna 2 of
CS1W-V680C12
or
CJ1W-V680C12
Bit No.
Type
08 to 15
Bit name
Command code
01 hex
Communications
Specification
p. 85
Specify the communications method with
the RF Tag.
04 t 07
n+1
Description
n+11
Command
0
Trigger
1
Single auto
2
Repeat auto
3
FIFO trigger
4
FIFO repeat
5
Multi-access trigger
6
Multi-access repeat
Specify number of RF Tag write bytes
Setting range: 0001 to 0800 hex
Leftmost  Rightmost
1
Rightmost  Leftmost
n+2
n+12
00 to 15
Processing
Address
n+3
n+13
00 to 15
Number of
Processing Bytes
n+4
n+14
00 to 15
Data Storage
Specify the write data storage destination.
Word Address
p. 70
(rightmost 4 digits)
12 to 15
08 to 11
n+5
n+15
Data
storage
area
n+16
00 to 15
Bank Specification
Data Storage
Word Address
(leftmost 2 digits)
00 to 07
n+6
Data Storage Area
Option
Command Option
Not used.
Communications Commands
Specify the first RF Tag address to write.
Setting range: 0000 to FFFF hex
0
SECTION 6
Specify the write data storage order.
00 to 03
Processing
Specification
p. 70
• Verification will not be performed if No Verification is set for writing.
• Check the memory capacity of the RF Tag before setting the Processing Address and Number of Processing Bytes. If
the Processing Address and Number of Processing Bytes are not suitable for the RF Tags for which communications
are being performed, the RF Tag Address Error Flag (CIO n+8, bit 13) will turn ON.
RFID System
User's Manual
127
SECTION 6
Controlling the ID Sensor Unit
 Bit Set
Reads the specified number of bytes from the specified start address and sets the specified bits to 1.
For the Designation Data, set a hexadecimal value with the bits to be set to 1 turned ON.
Up to 4 bytes (i.e., 2 words) can be specified for one command execution.
The following example shows specifying 0120 hex for 2 bytes of data to set bit 0 in byte 1 and bit 5 in
byte 2.
Bit
7
Data Written to
RF Tag
Bit
Bit
7
0
Designation Data in
Data Storage Area
Bit
Bit
7
0
RF Tag Data
Bit
0
1
10000000
1
00000001
2
00000001
2
00100000
=
1
10000001
2
00100001
The data in boxes is set.
Word address
Antenna 1 of
CS1W-V680C11,
CS1W-V680C12,
CJ1W-V680C11,
or CJ1W-V680C12
Antenna 2 of
CS1W-V680C12
or
CJ1W-V680C12
Bit No.
Type
08 to 15
Bit name
SECTION 6
Command
02 hex
Communications
Specification
p. 85
Specify the communications method with
the RF Tag.
04 to 07
Communications Commands
n+1
n+11
Command
Processing
Specification
p. 70
00 to 03
Description
0
Trigger
1
Single auto
2
Repeat auto
3
FIFO trigger
4
FIFO repeat
5
Multi-access trigger
6
Multi-access repeat
Specify the storage order for the
Designation Data.
0
Leftmost  Rightmost
1
Rightmost  Leftmost
n+2
n+12
00 to 15
Processing
Address
Specify the first RF Tag address to write.
Setting range: 0000 to FFFF hex
n+3
n+13
00 to 15
Number of
Processing Bytes
Specify number of RF Tag bytes to write.
Setting range: 0001 to 0004 hex
n+4
n+14
00 to 15
Data Storage
Specify the write data storage destination.
Word Address
p. 70
(rightmost 4 digits)
12 to 15
08 to 11
n+5
n+15
Data
storage
area
n+16
00 to 15
Bank Specification
Data Storage
Word Address
(leftmost 2 digits)
00 to 07
n+6
Data Storage Area
Option
Command Option
Not used
• Data status will not be changed for any bit that is OFF in the Designation Data.
• Verification will not be performed if No Verification is set for writing.
• Check the memory capacity of the RF Tag before setting the Processing Address and Number of Processing Bytes. If
the Processing Address and Number of Processing Bytes are not suitable for the RF Tag for which communications
are being performed, the RF Tag Address Error Flag (CIO n+8, bit 13) will turn ON.
128
RFID System
User's Manual
SECTION 6
Controlling the ID Sensor Unit
 Bit Clear
Reads the specified number of bytes from the specified start address and clears the specified bits to 0.
For the Designation Data, set a hexadecimal value with the bits to be cleared to 0 turned ON.
Up to 4 bytes (i.e., 2 words) can be specified for one command execution.
The following example shows specifying 100140 hex for 3 bytes of data to clear bit 4 in byte 1, bit 0 in
byte 2, and bit 6 in byte 3.
RF Tag Data
Bit
7
Bit
0
10000000
1
2
00100001
2
3
00000001
3
1
Data Written to
RF Tag
Bit
Bit
7
0
Designation Data in
Data Storage Area
Bit
Bit
7
0
1
10000000
00000001
2
00100000
01000000
3
00000001
00010000
=
The data in boxes is cleared.
Word address
Antenna 1 of
CS1W-V680C11,
CS1W-V680C12,
CJ1W-V680C11,
or CJ1W-V680C12
Antenna 2 of
CS1W-V680C12
or
CJ1W-V680C12
Bit No.
Type
08 to 15
Bit name
03 hex
Communications
Specification
p. 85
Specify the communications method with the RF
Tag.
Command
00 to 03
Trigger
1
Single auto
2
Repeat auto
3
FIFO trigger
4
FIFO repeat
5
Multi-access trigger
6
Multi-access repeat
Processing
Specification
p. 70
Specify the storage order for the Designation
Data.
Specify the first RF Tag address to write.
Setting range: 0000 to FFFF hex
0
Leftmost  Rightmost
1
Rightmost  Leftmost
n+2
n+12
00 to 15
Processing
Address
n+3
n+13
00 to 15
Number of
Processing Bytes
Specify number of RF Tag bytes to write.
Setting range: 0001 to 0004 hex
n+4
n+14
00 to 15
Data Storage Word
Address (rightmost
4 digits)
Specify the write data storage destination.
p. 70
12 to 15
08 to 11
n+5
n+15
Data
storage
area
n+16
00 to 15
Data Storage Area
Bank Specification
Data Storage Word
Address (leftmost
2 digits)
00 to 07
n+6
Communications Commands
n+11
0
SECTION 6
Command code
04 to 07
n+1
Description
Option
Command Option
Not used
• Data status will not be changed for any bit that is OFF in the Designation Data.
• Verification will not be performed if No Verification is set for writing.
• Check the memory capacity of the RF Tag before setting the Processing Address and Number of Processing Bytes. If
the Processing Address and Number of Processing Bytes are not suitable for the RF Tag for which communications
are being performed, the RF Tag Address Error Flag (CIO n+8, bit 13) will turn ON.
RFID System
User's Manual
129
SECTION 6
Controlling the ID Sensor Unit
 Mask Bit Write
Reads the 2 bytes of data from the specified start address, masks it with the specified mask data, and
writes data to the bits that are not masked. For the mask data, set a hexadecimal value with the bits to
be masked turned ON.
Each command execution processes 2 bytes (i.e., 1 word).
Example for a Masked Bit Write
RF Tag Data
Bit
7
1
2
Data Written to
RF Tag
Bit
Bit
7
0
Data Specified
for Option
Bit
Bit
7
0
Bit
0
00010010
1
11110000
00110100
2
00001111
=
1
00011101
2
11000100
The data in boxes is held.
Write Data in
Data Storage Area
Bit
Bit
7
0
1
00001101
2
11000000
Word address
SECTION 6
Antenna 1 of
CS1W-V680C11,
CS1W-V680C12,
CJ1W-V680C11,
or CJ1W-V680C12
Antenna 2 of
CS1W-V680C12
or
CJ1W-V680C12
Bit No.
Type
08 to 15
Communications Commands
n+1
04 hex
Communications
Specification
p. 85
Specify the communications method with
the RF Tag.
n+11
Command
00 to 03
0
Trigger
1
Single auto
2
Repeat auto
3
FIFO trigger
4
FIFO repeat
5
Multi-access trigger
6
Multi-access repeat
Processing
Specification
p. 70
Specify the write data storage order.
0
Leftmost  Rightmost
1
Rightmost  Leftmost
n+2
n+12
00 to 15
Processing
Address
Specify the first RF Tag address to write.
Setting range: 0000 to FFFE hex
n+3
n+13
00 to 15
Number of
Processing Bytes
Not used
n+4
n+14
00 to 15
Specify the write data storage destination.
Data Storage
p. 70
Word Address
(rightmost 4 digits)
08 to 11
n+5
n+15
Data
storage
area
n+6
RFID System
n+16
00 to 15
Data Storage Area
Bank Specification
Data Storage
Word Address
(leftmost 2 digits)
00 to 07
User's Manual
Description
Command code
04 to 07
12 to 15
130
Bit name
Option
Command Option
Mask data (0000 to FFFE hex)
SECTION 6
Controlling the ID Sensor Unit
• The bits that are turned ON in the data set for the Command Option will be masked and will not be changed. Write
data will be written to the data storage area for bits that are OFF in the write data.
• Verification will not be performed if No Verification is set for writing.
• Check the memory capacity of the RF Tag before setting the Processing Address and Number of Processing Bytes. If
the Processing Address and Number of Processing Bytes are not suitable for the RF Tag for which communications
are being performed, the RF Tag Address Error Flag (CIO n+8, bit 13) will turn ON.
• The mask data is always specified leftmost to rightmost regardless of the processing specification.
SECTION 6
Communications Commands
RFID System
User's Manual
131
SECTION 6
Controlling the ID Sensor Unit
 Calculation Write
Reads the specified number of bytes from the specified start address, performs the specified
calculation with the data specified for the Command Option, and writes the result.
The calculation result is stored in the data storage area.
Up to 4 bytes (i.e., 2 words) can be specified for one command execution.
Example for Additions
RF Tag Data
Bit
7
Data Written to
RF Tag
Bit
Bit
7
0
Data Specified
for Option
Bit
Bit
7
0
Bit
0
1
11111110
1
00000011
2
11111111
2
00000000
3
00000001
=
1
00000001
2
00000000
3
00000010
Word address
Antenna 1 of
CS1W-V680C11,
CS1W-V680C12,
CJ1W-V680C11,
or CJ1W-V680C12
Antenna 2 of
CS1W-V680C12
or
CJ1W-V680C12
Bit No.
Type
08 to 15
Bit name
SECTION 6
Command code
05 hex
Communications
Specification
p. 85
Specify the communications method with
the RF Tag.
07 to 04
Communications Commands
n+1
Description
n+11
Command
0
Trigger
1
Single auto
2
Repeat auto
3
FIFO trigger
4
FIFO repeat
5
Multi-access trigger
6
Multi-access repeat
Specify the calculation method.
00 to 03
Processing
Specification
p. 70
Specify the first RF Tag address to write.
Setting range: 0000 to FFFF hex
Specify number of RF Tag write bytes.
Setting range: 0001 to 0004 hex
0
Add
1
Subtract
n+2
n+12
00 to 15
Processing
Address
n+3
n+13
00 to 15
Number of
Processing Bytes
n+4
n+14
00 to 15
Data Storage
Specify the calculation result storage area.
Word Address
p. 70
(rightmost 4 digits)
12 to 15
08 to 11
n+5
n+15
Data
storage
area
n+16
00 to 15
Bank Specification
Data Storage
Word Address
(leftmost 2 digits)
00 to 07
n+6
Data Storage Area
Option
Command Option
Calculation data
• If an addition results in an overflow or a subtraction results in an underflow, the Status Flag (CIO n+8, bit 04) will turn
ON and the number of writes data will not be changed.
• Verification will not be performed if No Verification is set for writing.
• Check the memory capacity of the RF Tag before setting the Processing Address and Number of Processing Bytes. If
the Processing Address and Number of Processing Bytes are not suitable for the RF Tag for which communications
are being performed, the RF Tag Address Error Flag (CIO n+8, bit 13) will turn ON.
132
RFID System
User's Manual
SECTION 6
Controlling the ID Sensor Unit
 Data Fill
Writes the designated fill data to the RF Tag beginning from the specified start address.
The maximum amount of data that can be written in a single execution is 2,048 bytes (1,024 words), or
to the entire remaining area after the specified start address.
Word address
Antenna 1 of
CS1W-V680C11,
CS1W-V680C12,
CJ1W-V680C11,
or CJ1W-V680C12
Antenna 2 of
CS1W-V680C12
or
CJ1W-V680C12
Bit No.
Type
08 to 15
Bit name
Command code
06 hex
Communications
Specification
p. 85
Specify the communications method with
the RF Tag.
04 o 07
n+1
n+11
Command
n+12
00 to 15
n+3
n+13
00 to 15
n+4
n+14
00 to 15
12 to 15
08 to 11
n+5
n+15
n+16
00 to 15
Single auto
2
Repeat auto
3
FIFO trigger
4
FIFO repeat
5
Multi-access trigger
6
Multi-access repeat
Specify the fill data size.
0
Bytes (Command option rightmost 8
bits)
1
Words
Processing
Address
Specify the first RF Tag address to write.
Setting range: 0000 to FFFF hex
Number of
Processing Bytes
Specify number of RF Tag write bytes
Setting range: 0000, 0001 to 0800 hex
0000 hex: Fill data is written to the RF
Tag's end address.
Data Storage
Not used
Word Address
(rightmost 4 digits)
Data
storage
area
Data Storage Area
Bank Specification
Data Storage
Word Address
(leftmost 2 digits)
00 to 07
n+6
Trigger
1
Option
Command Option
Communications Commands
n+2
0
SECTION 6
Processing
Specification
p. 70
00 to 03
Description
Fill data
Setting range: 0000 to FFFF hex
• If the Number of Processing Bytes is 0000 hex, data will be written to user area of the RF Tag from the start address
to the end address.
• The Data Fill command will write data to the user area in the RF Tag regardless of the setting of write protection.
• Verification will not be performed if No Verification is set for writing.
• Check the memory capacity of the RF Tag before setting the Processing Address and Number of Processing Bytes. If
the Processing Address and Number of Processing Bytes are not suitable for the RF Tag for which communications
are being performed, RF Tag Address Error Flag (CIO n+8, bit 13) will turn ON.
RFID System
User's Manual
133
SECTION 6
Controlling the ID Sensor Unit
 Data Check
Finds the CRC code for the data area from the specified start address to 2 bytes less than the specified
number of bytes and writes 2 bytes of data.
From 3 to 2,048 bytes of data can be specified for one command execution.
Word address
Antenna 1 of
CS1W-V680C11,
CS1W-V680C12,
CJ1W-V680C11,
or CJ1W-V680C12
Antenna 2 of
CS1W-V680C12
or
CJ1W-V680C12
Bit No.
Type
08 to 15
n+1
n+11
04 to 07
Bit name
Command code
07 hex
Communications
specification
p. 85
Specify the communications method with
the RF Tag.
Processing
Specification
Command
00 to 03
p. 70
SECTION 6
Communications Commands
n+2
n+12
00 to 15
Processing
Address
n+3
n+13
00 to 15
Number of
Processing Bytes
n+4
n+14
00 to 15
12 to 15
08 to 11
n+5
n+15
n+16
00 to 15
0
Trigger
1
Single auto
Specify the process.
0
CRC calculation
1
CRC verification
Specify the Data Check Start address in
the RF Tag.
Setting range: 0000 to FFFD hex
Specify the number of bytes in the data
check range in the RF Tag plus 2 bytes.
Setting range: 0003 to 0800 hex
No used
Data Storage
Word Address
(rightmost 4 digits)
Data
storage
area
Data Storage Area
Bank Specification
Data Storage
Word Address
(leftmost 2 digits)
00 to 07
n+6
Description
Option
Command Option
No used
• Verification will not be performed if No Verification is set for writing.
• The last 2 bytes of the check area is the check code area. Do not write user data to these bytes.
• Check the memory capacity of the RF Tag before setting the Processing Address and Number of Processing Bytes. If
the Processing Address and Number of Processing Bytes are not suitable for the RF Tag for which communications
are being performed, RF Tag Address Error (CIO n+8, bit 13) will turn ON.
134
RFID System
User's Manual
SECTION 6
Controlling the ID Sensor Unit
 Number of Writes Control
Uses 3 bytes of data from the specified start address as the Number of Writes Control Area and writes
data to the RF Tag.
The number of writes for one command execution can be from 0 to 255.
Word address
Antenna 1 of
CS1W-V680C11,
CS1W-V680C12,
CJ1W-V680C11,
or CJ1W-V680C12
n+1
Antenna 2 of
CS1W-V680C12
or
CJ1W-V680C12
Bit No.
Type
Bit name
Description
08 to 15
Command code
08 hex
Specify the communications method with
the RF Tag.
04 to 07
Communications
Specification
p. 85
n+11
Command
00 to 03
0
Trigger
1
Single auto
Specify the count update method.
Processing
Address
Specify the start address of the Number of
Writes Control Area in the RF Tag.
Setting range: 0000to FFFD hex
Not used
0
Add
1
Subtract
n+12
00 to 15
n+3
n+13
00 to 15
Number of
Processing Bytes
n+4
n+14
00 to 15
Data Storage
Specify the count update results storage
Word Address
area.
(rightmost 4 digits)
p. 70
12 to 15
08 to 11
n+5
n+15
Data
storage
area
n+16
00 to 15
Bank Specification
Data Storage
Word Address
(leftmost 2 digits)
00 to 07
n+6
Data Storage Area
Option
Command Option
Number of writes
Setting range: 0000 to 00FF hex
• Verification will not be performed if No Verification is set for writing.
Communications Commands
n+2
SECTION 6
Processing
Specification
p. 70
• Check the memory capacity of the RF Tag before setting the Processing Address and Number of Processing Bytes. If
the Processing Address and Number of Processing Bytes are not suitable for the RF Tag for which communications
are being performed, the RF Tag Address Error Flag (CIO n+8, bit 13) will turn ON.
RFID System
User's Manual
135
SECTION 6
Controlling the ID Sensor Unit
 Copy (Two-channels ID Sensor Units Only)
This command is supported by Two-channels ID Sensor Units only. Data is read from the RF Tag for
one Antenna and written to the memory of an RF Tag in the interrogation zone for the other Antenna.
Writing to the second RF Tag is always performed with a trigger
Word address
Antenna 1 of
CS1W-V680C12
or CJ1W-V680C12
n+1
Antenna 2 of
CS1W-V680C12
or
CJ1W-V680C12
Bit No.
Type
Bit name
Description
08 to 15
Command code
09 hex
Specify the communications method for
the RF Tag to be read.
04 to 07
Communications
Specification
p. 85
n+11
Command
00 to 03
0
Trigger
1
Single auto
Processing
Specification
p. 70
Not used
SECTION 6
n+2
n+12
00 to 15
---
Processing
Address
Specify the first RF Tag address to read.
Setting range: 0000 to FFFF hex
n+3
n+13
00 to 15
---
Number of
Processing Bytes
Specify the number of RF Tag read bytes
Setting range: 0001 to 0800 hex
n+4
n+14
00 to 15
Communications Commands
12 to 15
08 to 11
n+5
n+15
Data Storage
Not used
Word Address
(rightmost 4 digits)
Data
storage
area
n+16
00 to 15
Bank Specification
Data Storage
Word Address
(leftmost 2 digits)
00 to 07
n+6
Data Storage Area
Option
Command Option
Specify the first RF Tag address to write.
Setting range: 0000 to FFFF hex
• If the Command Execution Bit is turned ON in the Unit Controls for Antenna 1, data will be read from the RF Tag for
Antenna 1 and written to the RF Tag for Antenna 2.
• If the Command Execution Bit is turned ON in the Unit Controls for Antenna 2, data will be read from the RF Tag for
Antenna 2 and written to the RF Tag for Antenna 1.
• The Communications Specification for the Antenna that writes data will always be a trigger regardless of the specified
communications method.
• The Status Flag (CIO n+8, bit 04) in the Results Information will turn ON if an error occurs in the Antenna that writes
data.
• Confirm that the Antenna that writes data is not communicating before turning ON the Command Execution Bit. If the
Antenna that writes data is communicating, the Status Flag (CIO n+8, bit 04) in the Results Information will turn ON.
• Confirm the capacity of both the RF Tag being read and the one being written before using this command. If the
Processing Address and Number of Processing Bytes for the Antenna that write data are not suitable for the RF Tag
being communicated with, the Status Flag (CIO n+8, bit 04) in the Results Information will turn ON.
136
RFID System
User's Manual
SECTION 6
Controlling the ID Sensor Unit
 Read with Error Correction
Reads the data from the RF Tag from an area written by the Write with Error Correction Command, and
performs an error check and 1-bit error correction.
Up to 510 bytes (i.e., 255 words) can be specified for one command execution.
Word address
Antenna 1 of
CS1W-V680C11,
CS1W-V680C12,
CJ1W-V680C11,
or CJ1W-V680C12
Antenna 2 of
CS1W-V680C12
or
CJ1W-V680C12
Bit No.
Type
08 to 15
Bit name
Command code
0A hex
Communications
Specification
p. 85
Specify the communications method with
the RF Tag.
04 to 07
n+1
n+11
Command
0
Trigger
1
Single auto
2
Repeat auto
3
FIFO trigger
4
FIFO repeat
5
Multi-access trigger
6
Multi-access repeat
Processing
Specification
p. 70
Specify the read data storage order.
0
Leftmost  Rightmost
1
Rightmost  Leftmost
n+12
00 to 15
Processing
Address
Specify the first RF Tag address to read.
Setting range: 0000 to FFFA hex
n+3
n+13
00 to 15
Number of
Processing Bytes
Specify the number of RF Tag read bytes.
Setting range: 0001 to 01FE hex
n+4
n+14
00 to 15
Data Storage
Specify the read data storage destination.
Word Address
p. 70
(rightmost 4 digits)
12 to 15
08 to 11
n+5
n+15
Data
storage
area
n+16
00 to 15
Bank Specification
Data Storage
Word Address
(leftmost 2 digits)
00 to 07
n+6
Data Storage Area
Option
Command Option
Communications Commands
n+2
SECTION 6
00 to 03
Description
No used
• Be sure to read the same area that was written by the Write with Error Correction Command.
• Check the memory capacity of the RF Tag before setting the Processing Address and Number of Processing Bytes. If
the Processing Address and Number of Processing Bytes are not suitable for the RF Tag for which communications
are being performed, the RF Tag Address Error Flag (CIO n+8, bit 13) will turn ON.
• The five bytes of data after the area extending from the Processing Address for the Number of Processing Bytes is the
check code area. Do not write any data to the check code area.
• Check the memory capacity of the RF Tag before setting the Processing Address and Number of Processing Bytes. If
the Processing Address and Number of Processing Bytes are not suitable for the RF Tag for which communications
are being performed, the RF Tag Address Error Flag (CIO n+8, bit 13) will turn ON.
RFID System
User's Manual
137
SECTION 6
Controlling the ID Sensor Unit
 Write with Error Correction
Writes the designated data to the RF Tag beginning from the specified start address, and writes the RF
Tag memory check code and error correction code to the next 5 bytes of memory. Do not change this
code. It is required by the Read with Error Correction command.
Up to 510 bytes (i.e., 255 words) can be specified for one command execution.
Word address
Antenna 1 of
CS1W-V680C11,
CS1W-V680C12,
CJ1W-V680C11,
or CJ1W-V680C12
Antenna 2 of
CS1W-V680C12
or
CJ1W-V680C12
Bit No.
Type
08 to 15
Bit name
Command code
0B hex
Communications
Specification
p. 85
Specify the communications method with
the RF Tag.
04 to 07
n+1
Description
n+11
Command
0
Trigger
1
Single auto
2
Repeat auto
SECTION 6
3
FIFO trigger
4
FIFO repeat
5
Multi-access trigger
6
Multi-access repeat
Communications Commands
Specify the write data storage order.
00 to 03
Processing
Specification
p. 70
Specify the first RF Tag address to write.
Setting range: 0000 to FFFA hex
Specify the number of RF Tag write bytes.
Setting range: 0001 to 01FE hex
0
Leftmost  Rightmost
1
Rightmost  Leftmost
n+2
n+12
00 to 15
Processing
Address
n+3
n+13
00 to 15
Number of
Processing Bytes
n+4
n+14
00 to 15
Data Storage
Specify the write data storage destination
Word Address
p. 70
(rightmost 4 digits)
12 to 15
08 to 11
n+5
n+15
Data
storage
area
n+16
00 to 15
Bank Specification
Data Storage
Word Address
(leftmost 2 digits)
00 to 07
n+6
Data Storage Area
Option
Command Option
Not used
• Verification will not be performed if No Verification is set for writing.
• Check the memory capacity of the RF Tag before setting the Processing Address and Number of Processing Bytes. If
the Processing Address and Number of Processing Bytes are not suitable for the RF Tag for which communications
are being performed, the RF Tag Address Error Flag (CIO n+8, bit 13) will turn ON.
• The five bytes of data after the area extending from the Processing Bytes is the check code area. Do not write any
data to the check code area.
• Check the memory capacity of the RF Tag before setting the Processing Address and Number of Processing Bytes. If
the Processing Address and Number of Processing Bytes are not suitable for the RF Tag for which communications
are being performed, the RF Tag Address Error Flag (CIO n+8, bit 13) will turn ON.
138
RFID System
User's Manual
SECTION 6
Controlling the ID Sensor Unit
 UID Read
Reads the ID code from the RF Tag.
Word address
Antenna 1 of
CS1W-V680C11,
CS1W-V680C12,
CJ1W-V680C11,
or CJ1W-V680C12
Antenna 2 of
CS1W-V680C12
or
CJ1W-V680C12
Bit No.
Type
08 to 15
Bit name
Command code
0C hex
Communications
Specification
p. 85
Specify the communications method with
the RF Tag.
04 to 07
n+1
n+11
Command
00 to 03
Description
0
Trigger
1
Single auto
2
Repeat auto
3
FIFO trigger
4
FIFO repeat
5
Multi-access trigger
6
Multi-access repeat
Specify the read data storage order.
Not used
0
Leftmost  Rightmost
1
Rightmost  Leftmost
SECTION 6
Processing
Specification
p. 70
n+12
00 to 15
Processing
Address
n+3
n+13
00 to 15
Number of
Processing Bytes
n+4
n+14
00 to 15
Data Storage
Specify the read data storage destination.
Word Address
p. 70
(rightmost 4 digits)
12 to 15
08 to 11
n+5
n+15
Data
storage
area
n+16
00 to 15
Bank Specification
Data Storage
Word Address
(leftmost 2 digits)
07 to 11
n+6
Data Storage Area
Option
Command Option
Not used
RFID System
User's Manual
Communications Commands
n+2
139
SECTION 6
Controlling the ID Sensor Unit
 Noise Measurement
Checks the noise level when the command is received.
Word address
Antenna 1 of
CS1W-V680C11,
CS1W-V680C12,
CJ1W-V680C11,
or CJ1W-V680C12
Antenna 2 of
CS1W-V680C12
or
CJ1W-V680C12
Bit No.
Type
08 to 15
n+1
n+11
04 to 07
00 to 03
Command code
10 hex
Communications
Specification
p. 85
Not used
Command Processing
Specification
Not used
n+12
00 to 15
Processing
Address
n+3
n+13
00 to 15
Number of
Processing Bytes
n+4
n+14
00 to 15
Data Storage
Specify the data storage destination.
Word Address
p. 70
(rightmost 4 digits)
08 to 11
n+5
n+15
Data
storage
area
Communications Commands
n+6
RFID System
n+16
00 to 15
Data Storage Area
Bank Specification
Data Storage
Word Address
(leftmost 2 digits)
00 to 07
User's Manual
Description
n+2
12 to 15
SECTION 6
140
Bit name
Option
Command Option
Not used
SECTION 6
Controlling the ID Sensor Unit
Communications Time
RF Tag Communications Time
V680-HA63A, V680-HS@@, V680-D1KP@@, V680-H01-V2, and V680-D1KP@@
RF Tag communications
speed
Command
Communications time
N: Number of processed bytes
Normal Mode
Read
T = 1.3N + 31
Write with verification
T = 2.1N + 58
Write with no verification
T = 1.8N + 56
Read
T = 1.0N + 29
Write with verification
T = 1.8N + 51
Write with no verification
T = 1.5N + 47
Communications time (ms)
Communications speed: Normal Mode
Communications speed: High-speed Mode
2,500
2,000
Write with verification
1,500
Write with no verification
1,000
2,500
Communications time (ms)
High-speed Mode
2,000
Write with verification
1,500
SECTION 6
Read
500
Write with no verification
1,000
500
Read
200
400
600
800
1,000
0
1,200
200
400
No. of bytes processed
600
800
1,000
1,200
No. of bytes processed
V680-HA63B, V680-HS@@, and V680-D2KF@@/V680S-D2KF@@
RF Tag communications
speed
Command
Communications time
N: Number of processed bytes
Normal Mode
Read
T = 1.2N + 30
Write with verification
T = 2.4N + 49
Write with no verification
T = 1.2N + 49
Read
T = 0.9N + 27
Write with verification
T = 1.7N + 49
Write with no verification
T = 0.9N + 41
High-speed Mode (See
note.)
Communications Time
0
Note: When using a multi-access or FIFO communications specification, the Normal Mode
Communications speed: Normal Mode
Communications speed: High-speed Mode
Communications time (ms)
Communications time (ms)
communications speed will be used even if the High-speed Mode is set.
5,000
4,500
4,000
Write with verification
3,500
3,000
Write with no verification
2,500
2,000
5,000
4,500
4,000
3,500
3,000
Write with verification
2,500
Write with no verification
2,000
Read
1,500
1,500
1,000
1,000
500
500
0
500
1,000
1,500
2,000
2,500
No. of bytes processed
0
Read
500
1,000
1,500
2,000
2,500
No. of bytes processed
RFID System
User's Manual
141
SECTION 6
Controlling the ID Sensor Unit
V680-HA63B, V680-HS@@, V680-D8KF@@, and V680-D32KF@@
RF Tag communications
speed
Command
Communications time
N: Number of processed bytes
Normal Mode
Read
T = 1.3N + 30
Write with verification
T = 1.6N + 59
High-speed Mode (See
note.)
Write with no verification
T = 1.3N + 50
Read
T = 0.8N + 25
Write with verification
T = 1.1N + 41
Write with no verification
T = 0.9N + 40
Note: When using a multi-access or FIFO communications specification, the Normal Mode
communications speed will be used even if the High-speed Mode is set.
Communications speed: High-speed Mode
3,500
Communications time (ms)
Communications time (ms)
Communications speed: Normal Mode
3,000
Write with no verification
Write with verification
2,500
Read
2,000
1,500
3,500
3,000
2,500
Write with verification
2,000
1,500
1,000
500
500
SECTION 6
1,000
0
500
1,000
1,500
2,000
0
2,500
Write with no
verification
Read
500
1,000
No. of bytes processed
1,500
2,000
2,500
No. of bytes processed
Communications Time
V680-HA63B, V680-HS@@, V680S-D8KF@@
RF Tag communications
speed
Command
Communications time
N: Number of processed bytes
Normal Mode
Read
T = 0.6N + 58
High-speed Mode (See
note.)
Write with verification
T = 1.2N + 137
Write with no verification
T = 0.6N + 91
Read
T = 0.6N + 58
Write with verification
T = 1.2N + 137
Write with no verification
T = 0.6N + 91
Note: When using V680S-D8KF@@ RF Tags, the Normal Mode communications speed will be used
even if the High-speed Mode is set.
3,000
2,500
Write with verification
2,000
Write with no verification
1,500
1,000
Communications speed: High-speed Mode
Communications time (ms)
Communications time (ms)
Communications speed: Normal Mode
3,000
2,500
Write with verification
2,000
1,500
Write with no verification
1,000
Read
Read
500
0
500
1,000
1,500
2,000
500
2,500
No. of bytes processed
142
RFID System
User's Manual
0
500
1,000
1,500
2,000
2,500
No. of bytes processed
SECTION 6
Controlling the ID Sensor Unit
RF Tag Travel Speed
The RF Tag travel speed can be calculated using the following formula.
Travel speed = Travel distance in interrogation zone/communications time
The communications time is given in the graphs on the previous page. The travel distance in the
interrogation zone depends on the Antenna and the RF Tag. Refer to the user manual for the Antenna
and RF Tag.
Travel distance in
interrogation zone
RF Tag
Interrogation zone
Antenna
• Communications error processing is not included in the above calculation formula.
RFID System
User's Manual
Communications Time
part of the area.
• The above calculation formula is provided only as a guideline. Perform tests with the actual system before application.
SECTION 6
• The travel speed will change with the communications range and axis displacement. We recommend using the widest
143
SECTION 6
Controlling the ID Sensor Unit
 TAT Calculation
The time from when the CS/CJ-series CPU Unit turns ON the ID Sensor Unit’s Command Execution Bit
until the RF Tag is communicated with and execution results are returned (i.e. the TAT, or Turnaround
Time) can be calculated with the following formula.
TAT = Coefficient  Cycle time + Communications time
Name
Description
Coefficient
(Number of Processing Bytes/160) + 3 (See note.)
Cycle time
Cycle time of the CS/CJ-series CPU Unit
Communications time The communications time between the ID Sensor Unit and RF Tag (as previously described)
Note: Round OFF the result of the Number of Processing Bytes/160.
SECTION 6
Communications Time
144
RFID System
User's Manual
SECTION 7
Troubleshooting Alarms and Errors
Indicators and Error Check Flowcharts
146
ID Sensor Unit Alarms
148
CPU Unit Errors
151
Restarting Special I/O Units
152
Troubleshooting
153
SECTION 7
Troubleshooting Alarms and Errors
RFID System
User's Manual
145
SECTION 7
Troubleshooting Alarms and Errors
Indicators and Error Check Flowcharts
Status Indicators
If an alarm or error occurs in the ID Sensor Unit, the ERC indicator or ERH indicator will light on the
Unit's front panel.
CS1W-V680C11
CS1W-V680C12
V680C11
RUN
ERC
V680C12
RUN
ERC
HEAD1
T/R
ERP
ERH
T/R
NORM/ERR
NORM/ERR
CJ1W-V680C11
V680C11
RUN ERC
T/R NORM/ERR
RUN
Name
RUN
CJ1W-V680C12
T/R NORM/ERR
ERP ERH
T/R NORM/ERR
HEAD1
HEAD2
Color
Green
NORM/ERR
V680C12
RUN ERC
ERP ERH
Indicator
ERP
ERH
HEAD2
T/R
Meaning
❍ Lit
The ID Sensor Unit is operating normally.
● Not lit The ID Sensor Unit is stopped.
SECTION 7
Indicators and Error Check Flowcharts
146
ERC
(Error in Controller)
Unit error
ERH
(Error at CPU Unit)
CPU Unit error
Red
ERP
(Antenna Power Error)
Antenna power
error
Red
HEAD1
(Antenna
1)
Communicating
Yellow
T/R
Red
❍ Lit
An error has occurred in the ID Sensor Unit.
● Not lit No error has occurred in the ID Sensor Unit.
❍ Lit
An error has occurred in the CPU Unit.
● Not lit No error has occurred in the CPU Unit.
❍ Lit
An error has occurred in the power supply to the Antenna.
● Not lit The power supply to the Antenna is normal.
❍ Lit
Communications are active.
● Not lit Communications not being performed with the RF Tag.
NORM/ERR
Normal end
Green
❍ Lit
Communications with the RF Tag ended normally.
● Not lit The indicator is not Iit in all other cases.
Error end
Red
Communicating
Yellow
❍ Lit
Communications with the RF Tag ended in an error.
● Not lit The indicator is not Iit in all other cases.
HEAD2
(Antenna
2)
T/R
❍ Lit
Communications are active.
● Not lit Communications not being performed with the RF Tag.
NORM/ERR
Normal end
Green
❍ Lit
Communications with the RF Tag ended normally.
● Not lit The indicator is not Iit in all other cases.
Error end
Red
❍ Lit
Communications with the RF Tag ended in an error.
● Not lit The indicator is not Iit in all other cases.
RFID System
User's Manual
SECTION 7
Troubleshooting Alarms and Errors
Error Check Flowchart
Use the following flowchart to check the error if an error occurs in the ID Sensor Unit.
Error occurs
ERC indicator
lit?
Lit
RUN indicator
lit?
Lit
An alarm occurred during
ID Sensor Unit operation.
p. 148
Not lit
Not lit
Check the initial setting data
for the ID Sensor Unit.
p. 149
ERH indicator
lit?
Not lit
Lit
RUN indicator
lit?
Lit
An error occurred in the
CPU Unit.
p. 151
Not lit
Check the unit number setting.
p. 151
Troubleshooting
p. 153
SECTION 7
Indicators and Error Check Flowcharts
RFID System
User's Manual
147
SECTION 7
Troubleshooting Alarms and Errors
ID Sensor Unit Alarms
The ERC indicator will light when the ID Sensor Unit detects an alarm. The relevant Alarm Flag will be turned on
in the Unit Status (CIO n+7) (and, for a Two-channels ID Sensor Unit, (CIO n+17)) in the Special I/O Unit Area.
Word address
Antenna 1 of
Antenna 2 of
CS1W-V600C11,
CS1W-V600C12 Bit No.
CS1W-V600C12,
or
CJ1W-V600C11,
CJ1W-V600C12
or CJ1W-V600C12
I/O
Type
n+7
Unit Busy Flag
Turns ON when there is an ID Sensor Unit error.
14
Test Mode Flag
Turns ON during Test Mode.
13
Antenna Power
Turns ON when there is an error in the Unit’s power
Supply Error Flag supply or the external power supply.
Unit
Status
11
n+17
Description
15
12
Input
Bit name
EEPROM error
Turns ON when there is an error in reading EEPROM.
Antenna Error
Flag
The DM Area setting and V680-H01 Antenna
connection status do not match.
Too many Antennas are connected or the specified
power consumption has been exceeded.
03 to 10
---
Not used
Error End Flag
02
Turns ON for one scan when processing ends in an
error.
01
Normal End Flag Turns ON for one scan when processing ends
normally.
00
ID Busy Flag
Turns ON while communications are in progress.
 Both ERC and RUN Indicators Lit
CS1W-V680C11
SECTION 7
V680C11
RUN
ERC
CS1W-V680C12
V680C12
RUN
ERC
HEAD1
T/R
ERP
ERH
T/R
NORM/ERR
ERP
ERH
HEAD2
T/R
NORM/ERR
ID Sensor Unit Alarms
CJ1W-V680C11
V680C11
RUN ERC
NORM/ERR
CJ1W-V680C12
T/R NORM/ERR
V680C12
RUN ERC
T/R NORM/ERR
ERP ERH
T/R NORM/ERR
HEAD1
HEAD2
ERP ERH
Lit:
Not Lit:
If both the ERC and RUN indicators are lit, an alarm occurred during Unit operation.
The Unit Busy Flag in the Unit Status (CIO n+7) (for a Two-channels ID Sensor Unit, CIO n+17 for
Antenna 2) will turn ON.
The Unit will recover from this alarm automatically when the cause of the alarm is removed.
Word address
Antenna 1 of
Antenna 2 of
CS1W-V600C11,
CS1W-V600C12 Name of alarm
CS1W-V600C12,
CJ1W-V600C11, or CJ1W-V600C12
or CJ1W-V600C12)
n+7
Meaning
Unit response
n+17
Bit 15
ID Sensor Unit A CPU error
Unit operation
CPU Error Flag occurred during will stop.
ID Sensor Unit
operation
• First word allocated to Unit in CIO Area: n = CIO 2000 + 10  Unit number
148
RFID System
User's Manual
Correction
• Turn the power supply OFF and ON or
turn ON the Special I/O Unit Restart Bit.
• Replace the ID Sensor Unit if the error
persists even though the Unit is reset.
SECTION 7
Troubleshooting Alarms and Errors
 ERC Indicator Lit and RUN Indicator Not Lit
CS1W-V680C11
V680C11
RUN
ERC
CS1W-V680C12
V680C12
RUN
ERC
HEAD1
T/R
ERP
ERH
T/R
NORM/ERR
ERP
ERH
HEAD2
T/R
NORM/ERR
CJ1W-V680C11
V680C11
RUN ERC
T/R NORM/ERR
ERP ERH
NORM/ERR
CJ1W-V680C12
V680C12
RUN ERC
T/R NORM/ERR
ERP ERH
T/R NORM/ERR
HEAD1
HEAD2
Lit:
Not lit:
If the ERC indicator is lit and the RUN indicator is not lit, an alarm occurred in the ID Sensor Unit
immediately after the power supply was turned ON or immediately after the Unit was restarted as a
Special I/O Unit.
The Alarm Flags in the Unit Status (CIO n+7) (for a Two-channels ID Sensor Unit, (CIO n+17) for
Antenna 2) will turn ON.
Word address
Antenna 1 of
CS1W-V600C11,
CS1W-V600C12,
CJ1W-V600C11,
or
CJ1W-V600C12)
Antenna 2 of
CS1W-V600C12
or
CJ1W-V600C12
n+7
n+17
Unit response
Correction
ID Sensor Unit An error occurred in Unit operation
CPU Error Flag the ID Sensor Unit will stop.
when the power
supply was turned
ON or immediately
after the Unit was
restarted.
• Turn the power supply OFF and ON or
turn ON the Special I/O Unit Restart
Bit.
• Replace the ID Sensor Unit if the error
persists even though the Unit is reset.
EEPROM Error An error occurred
Flag
when memory read
was read.
• Turn the power supply OFF and ON or
turn ON the Special I/O Unit Restart
Bit.
• Replace the ID Sensor Unit if the error
persists even though the Unit is reset.
Unit operation
will stop.
• First word allocated to Unit in CIO Area: n = CIO 2000 + 10  Unit number
RFID System
User's Manual
ID Sensor Unit Alarms
Bit 12
Meaning
SECTION 7
Bit 15
Name of alarm
149
SECTION 7
Troubleshooting Alarms and Errors
Error name
Word
Word
(CIO n+8)
(CIO n+9)
(CIO n+18 (See note.2)) (CIO n+19 (See note.2))
Error
Correction
Bit 12
E070
An error occurred in communications • Check for excessive noise.
with a RF Tag, preventing a normal
• Check the travel speed.
end.
• Check the distance between the
Antenna and RF Tag.
Verification Error
Flag
Bit 14
E071
The correct data could not be written
to the RF Tag.
(Occurs only when verification is set
for a write operation.)
• Check the travel speed. (Page 143)
• Check for excessive noise.
RF Tag Missing
Error Flag
Bit 10
E072
• The communications specification
was for a trigger, but there was no
RF Tag in the interrogation zone.
• The communications specification
was for single auto, but the Auto
Wait Time expired.
• The Antenna and RF Tag are too
far apart.
• The axis is out of alignment.
ID System Error 1
Bit 09
E079
System error
Please consult your OMRON
representative.
ID System Error 2
Bit 08
E07E
System error
Please consult your OMRON
representative.
ID System Error 3
Bit 07
E07F
System error
Please consult your OMRON
representative.
Status Flag
Bit 04
E076
• An overflow or underflow occurred
for a Calculation Write command.
• The data did not verify for a Data
Check command.
• The number of writes was
exceeded for a Number of Writes
Control command.
• An error occurred in the data for a
Read with Error Correction command.
• Check the data settings.
SECTION 7
RF Tag
Communications
Error Flag
• Replace the RF Tag.
ID Sensor Unit Alarms
• An error occurred while writing for a (See note.1)
Copy command.
RF Tag Address
Error Flag
Bit 13
E07A
The RF Tag address specified in the
command is not correct.
• Specify the address correctly.
Antenna Error Flag
Bit 15
E07C
An Antenna error occurred.
• Check 24 VDC input.
(CS1W-V680C12 only)
• Check the Antenna.
Write Protection
Error Flag
Bit 11
E07D
An attempt was made to write to a
write-protected area.
• Specify the address and number of
bytes correctly.
• Clear write protection. (Page 95)
Error Correction
Flag
Bit 03
E077
Read with Error Correction
performed a 1-bit error correction.
Data Storage Area
Bit 01
Specification Error Flag
E014
The data storage area specification
is not correct.
Specify the data storage area
specification correctly.
Command Error
Flag
E014
The command to the ID Sensor Unit
is not correct.
Specify the command correctly.
Bit 00
---
Note 1: The following errors may occur while writing for a Copy command. Confirm the steps to handle each error.
• RF Tag communications error
• RF Tag verification error
• RF Tag missing error
• RF Tag address error
• Antenna error
• Write protection error
Note 2: CIO n+8, CIO n+9 are error information of Antenna 1 (Head No.1).
CIO n+18, CIO n+19 are error information of Antenna 2 (Head No.2).
150
RFID System
User's Manual
SECTION 7
Troubleshooting Alarms and Errors
CPU Unit Errors
The ERH indicator will light when the ID Sensor Unit cannot operate because an error occurred on the I/O bus
to the CPU Unit or when data cannot be refreshed as a Special I/O Unit.
 Both ERH and RUN Indicators Lit
CS1W-V680C11
V680C11
RUN
ERC
ERP
ERH
T/R
NORM/ERR
V680C12
RUN
ERC
HEAD1
T/R
ERP
ERH
HEAD2
T/R
NORM/ERR
CJ1W-V680C11
V680C11
RUN ERC
CS1W-V680C12
T/R NORM/ERR
ERP ERH
NORM/ERR
CJ1W-V680C12
V680C12
RUN ERC
T/R NORM/ERR
ERP ERH
T/R NORM/ERR
HEAD1
HEAD2
Lit:
Not lit:
The ERH and RUN indicators will light when an error occurs on the I/O bus or a WDT (watchdog timer)
error occurs in the CPU Unit, preventing data from being correctly refreshed for the ID Sensor Unit as a
Special I/O Unit. If this happens, either turn the power supply OFF and ON or restart the system. Refer
to the SYSMAC CS/CJ-series Programmable Controllers Operation Manual for details.
Error name
Error
An error occurred in data transfer between the CPU
Unit and the ID Sensor Unit.
CPU Unit monitor error
An error occurred because there was no response
from the CPU Unit.
CPU Unit WDT error
An error occurred in the CPU Unit.
Unit operation will stop.
SECTION 7
I/O bus error
Unit response
CPU Unit Errors
 ERH Indicator Lit and RUN Indicator Not Lit
CS1W-V680C11
V680C11
RUN
ERC
ERP
ERH
T/R
NORM/ERR
V600C12
RUN
ERC
HEAD1
T/R
ERP
ERH
HEAD2
T/R
NORM/ERR
CJ1W-V680C11
V680C11
RUN ERC
CS1W-V680C12
T/R NORM/ERR
NORM/ERR
CJ1W-V680C12
V680C12
RUN ERC
HEAD1
T/R NORM/ERR
HEAD2
ERP ERH
ERP ERH
T/R NORM/ERR
Lit:
Not lit:
There is an error in the unit number setting for the ID Sensor Unit.
Error name
Error
Unit number duplication
The same unit number is set for more than one Unit or
was set to a value that is not between 00 and 95.
Special I/O Unit setting
error
The model of Special I/O Unit registered in the I/O
table does not agree with the model of Special I/O Unit
mounted in the system.
Unit response
Unit operation will stop.
RFID System
User's Manual
151
SECTION 7
Troubleshooting Alarms and Errors
Restarting Special I/O Units
To restart operation after changing settings in the DM Area or after removing the cause of an error,
either turn the PLC's power supply OFF and ON or turn ON the Special I/O Unit Restart Bit.
• CS-series Special I/O Unit Restart Bits
Bit address
Function
Unit 1 Restart Bit
A50300
Unit 16 Restart Bit
...
Unit 15 Restart Bit
...
A50215
A50715
The Unit will be restarted when the
corresponding bit is turned ON.
After the Unit has finished
restarting, the corresponding bit
will be automatically turned OFF.
...
Unit 0 Restart Bit
A50201
...
A50200
Unit 95 Restart Bit
• CJ-series Special I/O Unit Restart Bits
Bit address
Unit 1 Restart Bit
...
A50201
...
Unit 0 Restart Bit
A50300
Unit 16 Restart Bit
The Unit will be restarted when the
corresponding bit is turned ON.
After the Unit has finished
restarting, the corresponding bit
will be automatically turned OFF.
...
Unit 15 Restart Bit
...
A50215
A50715
SECTION 7
Unit 95 Restart Bit
• If an error persists even though the power supply is turned OFF and ON or the Special I/O Unit Restart Bit is turned
ON, replace the ID Sensor Unit, Power Supply Unit, or CPU Unit.
Restarting Special I/O Units
152
Function
A50200
RFID System
User's Manual
SECTION 7
Troubleshooting Alarms and Errors
Troubleshooting
Main Check Flowchart
Use the Main Check Flowchart according to the nature of the error.
Main Check
Are system
connections normal?
Error
p. 21
Go to System Connections Check Flowchart.
p. 154
Normal
Are RF Tag
communications normal?
Error
Go to Communications Check Flowchart.
p. 155
Normal
OK
SECTION 7
Troubleshooting
RFID System
User's Manual
153
SECTION 7
Troubleshooting Alarms and Errors
System Connections Check Flowchart
START
Connectors and
cables OK?
YES
NO
Correct connection.
Cycle PLC power or turn ON
Special I/O Unit Restart Bit.
NO
ERH indicator lit?
External
power supply voltage
within the specified
range?
YES
YES
SECTION 7
Current
consumption
for all Units on
Rack < Power Supply
Unit capacity?
Supply rated voltage
to external power terminals.
NO
Change configuration to not
exceed power supply capacity.
Troubleshooting
NORM/ERR
indicator lit red?
YES
NO
Clear D2000 + (unit
number × 100) in DM Area.
Cycle PLC power or turn ON
Special I/O Unit Restart Bit.
YES
Turn ON test switch
on Unit's front panel
(to enter Test Mode).
T/R or NORM/ERR
flashing for either Antenna?
NO
YES
OK
154
NO
RFID System
User's Manual
Replace the ID Sensor Unit.
SECTION 7
Troubleshooting Alarms and Errors
Communications Check Flowchart
START
Clear DM m in words
allocated in DM Area.
Cycle PLC power or turn ON
Special I/O Unit Restart Bit.
Turn ON test switch
on front panel.
T/R and
NORM/ERR indicators
flashing for each
Antenna?
NO
YES
CIO n+9 = E070?
YES
Distance
between RF Tag and
Antenna OK?
YES
NO
NO
Correct distance.
CIO n+9 = E071?
YES
Travel speed OK?
YES
Alignment OK?
NO
NO
Reduce travel speed.
Adjust system to maintain
a consistent distance.
RF Tag OK?
YES
RF Tag OK?
YES
NO
Replace RF Tag.
YES
NO
NO
Replace RF Tag.
CIO n+9 = E07C?
YES
NO
CIO n+9 = E07A?
YES
NO
Is the Antenna
connection OK?
YES
Antenna OK?
YES
Amplifier OK?
YES
NO
NO
NO
Connect the Antenna correctly.
Replace Antenna.
Replace Amplifier.
Is the set address correct?
YES
YES
NO
SECTION 7
Set the correct address.
CIO n+9 = E07D?
YES
NO
Is the write protection
setting OK?
YES
NO
CIO n+9 = E076?
YES
NO
Has a 09 command
been sent?
YES
NO
Has a 05 command
been sent?
YES
An overflow or underflow
occurred for a Calculation Write
command
CIO n+9 = E079,
E07E, or E07F?
Replace RF Tag.
NO
Are two or more
RF Tags present in Antenna’s
communications
area?
YES
Is the moving speed
of RF Tag OK?
YES
Is the distance
between the Antenna and
RF Tag OK?
NO
NO
NO
Make sure that only one RF Tag is
within the communications area.
Reduce the speed.
Adjust the distance.
Has a 07 command
been sent?
NO
Has a 08 command
been sent?
NO
Has a 0A command
been sent?
YES
YES
YES
The data did not verify for
a Data Check command
The number of writes was
exceeded fo a Number of
Writes Control command
An error occurred in the
data for a Read with
Error Correction command
YES
RF Tag OK?
YES
NO
Replace RF Tag.
Troubleshooting
Clear the write
protection setting.
NO
YES
NO
Please consult your
OMRON representative.
CIO n+9 not 0000?
YES
OK
NO
RF Tag OK?
YES
NO
Replace RF Tag.
Replace the
ID Sensor Unit.
• First word allocated to Unit in DM Area: m = D20000 + 100  Unit number
• First word allocated to Unit in CIO Area: n = CIO 2000 + 10  Unit number
RFID System
User's Manual
155
SECTION 7
Troubleshooting Alarms and Errors
MEMO
SECTION 7
Troubleshooting
156
RFID System
User's Manual
SECTION 8
Appendices
Dimensions
158
Sample Programming
160
Data Coding Tables
204
Degree of Protection
208
SECTION 8
Appendices
RFID System
User's Manual
157
SECTION 8
Appendices
Dimensions
CS1W-V680C11
(193)
3 × 4 = 12
Six operation
status indicators
Switches
1
11.9
130
20.8
52.4
0
5.6
35.5
123
9
Connector
101
35
CS1W-V680C12
(193)
3 × 4 = 12
Switches
Dimensions
0
1
11.9
Connectors
8
51
25
130
20.8
5.6
35.5
123
9
52.4
SECTION 8
Eight operation
status indicators
3.6
15
35
Terminals
158
RFID System
User's Manual
With cover:
16.5
101
SECTION 8
Appendices
CJ1W-V680C11
(140)
21
10.5
2.7
4.9
Six operation
status indicators
65
4.5
2.7
17.3
18.1
29
20
4.7
90
5.5
12.5
4.5
7.7
Switches
31
Connector
CJ1W-V680C12
(140)
21
10.5
2.7
4.9
Eight operation
status indicators
65
4.5
18.1
17.3
29
20
4.7
29.2
12.5
4.5
2.7
Dimensions
90
5.5
SECTION 8
7.7
Switches
31
Connectors
RFID System
User's Manual
159
SECTION 8
Appendices
Sample Programming
Read, Communications Specification: Trigger
• Outline
This example shows how to read the memory of an RF Tag that is present in the interrogation zone for
Antenna 1.
When the Command Execution
Bit is turned ON, the Unit will
read the memory of an RF Tag
in the interrogation zone.
RF Tag
Interrogation zone
Antenna 1
Address
(hex)
0010
0011
0012
0013
0014
0015
0016
0017
0018
0019
RF Tag
Bit 7
Bit 0
0
0
0
0
0
0
0
0
0
0
1
2
3
4
5
6
7
8
9
A
CS-series CPU Unit memory
Read command
executed
Bit 15
Bit 00
××
××
D1000
××
××
D1001
××
××
D1002
D1003
××
××
01
02
D1004
03
04
D1005
05
06
D1006
07
08
D1007
09
0A
D1008
→: Read data storage order
UID
Read data
Unit Settings
SECTION 8
Item
Setting
00
Unit's front panel unit number switches: 00
Sample Programming
Operating mode
Run Mode
Unit's front panel test switch: OFF
System Settings
UID Addition Setting: Enabled
Test Mode Disable Setting: Enabled
Setting for Write Verification: Verification
RF Tag Communications Speed Setting:
Normal Mode
Data transfer setting: Cyclic
Set in the Special I/O Unit words in DM Area.
Auto Wait Time Setting
Infinite
Command
Read
Communications specification Trigger
Read data storage order
Leftmost  Rightmost
Read start address
0010 hex
Number of bytes to read
10 bytes
Read data storage destination D1000 to D1004
160
Setting location
Unit number
RFID System
User's Manual
Set in the Special I/O Unit Area.
SECTION 8
Appendices
First word allocated to Unit in DM Area: m = D20000 + (100  0) = D20000
DM
address
D20000
Meaning
Contents
1
0
D20001
0
15
0
14
13
12
UID Addition Setting
11
10
9
8
7
Test Mode Disable
Setting
0000
6
5
4
Setting for Write
Verification
3
2
1
0
RF Tag
Communications
Speed Setting
Auto Wait Time Setting
First word allocated to Unit in CIO Area: n = CIO 2000 + (10  0) = CIO 2000
Word
address
CIO 2001
Meaning
Contents
0
0
0
15
0
14
13
12
11
10
9
8
7
6
5
4
Communications
specification
Command code
CIO 2002
00
10
First read address
CIO 2003
00
0A
Number of read bytes
CIO 2004
10
00
Read data storage location (rightmost 4 digits)
CIO 2005
CIO 2006
0
0
00
00
00
Data storage area
Bank specification
(Always 0)
3
2
1
0
Data order
Read data storage location (leftmost 2
digits)
---
---: Ignored.
SECTION 8
Sample Programming
RFID System
User's Manual
161
SECTION 8
Appendices
• Programming Example
When the execution input turns ON, settings are made in the Special I/O Unit Area using the MOV and
MOVL instructions and the command is executed. When communications with the RF Tag have been
completed, the Normal End Flag (CIO n+7, bit 01) or Error End Flag (CIO n+7, bit 02) is turned ON.
Read data can be used after the Normal End Flag (CIO n+7, bit 01) has been turned ON.
To end command execution while waiting for the RF Tag, turn ON the Abort Input.
Execution input
ID Busy
Test Mode
Unit Busy
MOV
Waiting for command
execution (work bit)
2007.00
2007.14
2007.15
#0000
Specification of command,
communications specifications
and read data storage order.
2001
0010.01
MOV
Specification of first read address.
#0010
2002
MOV
Specification of number of read bytes.
#000A
2003
MOVL
Read data storage location
#00001000
2004
Waiting for command
execution (work bit)
SECTION 8
Command Execution Bit
0010.01
Normal End Flag
Sample Programming
162
0010.01
Waiting for command execution
(work bit)
2007.01
2000.00
Normal end
Used to time getting
read data.
Error End Flag
2007.02
RFID System
User's Manual
Error end
Used to time getting
results information.
SECTION 8
Appendices
• Timing Chart (CIO n = CIO 2000 + (10 x 0) = CIO 2000)
Command Execution Bit
CIO n, bit 00
Command
CIO n+1 to n+4
Read
Read
ID Busy
CIO n+7, bit 00
Communications
1 scan
processing
Waiting for
RF Tag
Normal End
CIO n+7, bit 01
1 scan
Normal end
Error End
CIO n+7, bit 02
Results Information
CIO n+8
Data storage area
0000
Results Information
stored.
0000
Missing error
Read data
• If communications with the RF Tag fail or an error occurs, communications will be aborted at that
point, the error flags in the Results Information (CIO n+8) will turn ON accordingly, and the error code
will be placed in the Processing Results Monitor (CIO n+9). The previous read data will not be
changed.
• To confirm the execution results from the user program, use the ON status of the Normal End Flag or
Error End Flag in the Unit Status.
• Do not turn ON the Command Execution Bit during command execution (i.e., while the ID Busy Flag
is ON). It will be ignored.
SECTION 8
Sample Programming
RFID System
User's Manual
163
SECTION 8
Appendices
Read, Communications Specification: Trigger, Data Transfer:
Intelligent I/O Instructions
• Outline
This example shows how to read the memory of an RF Tag that is present in the interrogation zone for
Antenna 1.
When the Command
Execution Bit is turned ON,
the Unit will read the memory
of an RF Tag in the
interrogation zone.
RF Tag
Interrogation zone
Antenna 1
Address
(hex)
0010
0011
0012
0013
0014
0015
0016
0017
0018
0019
RF Tag
Bit 7
CS-series CPU Unit memory
Bit 0
0
0
0
0
0
0
0
0
0
0
1
2
3
4
5
6
7
8
9
A
Read command
executed
D1000
D1001
D1002
D1003
D1004
D1005
D1006
D1007
D1008
Bit 15
××
××
××
××
01
03
05
07
09
Bit 00
××
××
××
××
02
04
06
08
0A
UID
Read data
→: Read data storage order
SECTION 8
Unit Settings
Item
Setting
Setting location
Sample Programming
Unit number
00
Unit's front panel unit number switches: 00
Operating mode
Run Mode
Unit's front panel test switch: OFF
System Settings
UID Addition Setting: Disabled
Test Mode Disable Setting: Enabled
Setting for Write Verification: Verification
RF Tag Communications Speed Setting:
Normal Mode
Data Transfer Setting: Intelligent I/O
Instructions
Set in the Special I/O Unit words in DM Area.
Auto Wait Time Setting
Infinite
Command
Read
Set in the Special I/O Unit Area.
Communications specification Trigger
Read data storage order
Leftmost  Rightmost
Read start address
0020 hex
Number of bytes to read
512 bytes
Read data storage destination D20920 to D21431
164
RFID System
User's Manual
Set in IORD instruction.
SECTION 8
Appendices
First word allocated to Unit in DM Area: m = D20000 + (100  0) = D20000
DM
address
D20000
Meaning
Contents
1
0
0
15
0
14
13
12
UID Addition Setting
11
10
9
8
7
Test Mode Disable
Setting
6
5
4
Setting for Write
Verification
D20001
0000
Auto Wait Time Setting
D20090
0001
Data Transfer Setting
3
2
1
0
RF Tag
Communications
Speed Setting
First word allocated to Unit in CIO Area: n = CIO 2000 + (10  0) = CIO 2000
Word
address
CIO 2001
Meaning
Contents
0
0
0
15
0
14
13
12
11
10
9
8
7
6
5
4
Communications
specification
Command code
CIO 2002
00
10
Read start address
CIO 2003
00
0A
Number of bytes to read
CIO 2004
10
00
---
CIO 2005
00
00
---
CIO 2006
00
00
---
3
2
1
0
Data order
---: Ignored.
SECTION 8
Sample Programming
RFID System
User's Manual
165
SECTION 8
Appendices
• Programming Example
The following ladder programming uses the Read command and the IORD instruction to read 512
bytes of data. The IORD instruction is executed twice to read 256 bytes (128 words) each time.
When the execution input turns ON, settings are made in the Special I/O Unit Area using MOV
instructions and the command is executed. When communications with the RF Tag have been
completed, the Normal End Flag (CIO n+7, bit 01) or Error End Flag (CIO n+7, bit 02) is turned ON.
The IORD instruction is executed after the Normal End Flag (CIO n+7, bit 01) turns ON.
To end command execution while waiting for the RF Tag, turn ON the Abort Input.
Waiting for command
execution (work bit)
ID Busy
Test Mode
Unit Busy
2007.00
2007.14
2007.15
MOV
0010.00
#0000
Specification of command,
communications
specifications, and read data
storage order.
2001
MOV
Specification of first
read address.
#0020
2002
MOV
Specification of number
of read bytes.
#0200
2003
ASL
Command execution
command start (work bit 2)
0010
Waiting for command
execution (work bit 2)
Command execution command
0010.01
2000.00
ASL
IORD execution (work bit 3)
0010
Error End Flag
Error end
2007.02
SECTION 8
IORD execution
(work bit 3)
Normal End Flag
IORD
0010.02
2007.01
#0000
Sample Programming
#00800000
D20920
IORD
First word specification
Number of words specification
Source unit number
First destination word specification
Results information
is read here.
P_EQ
ASL
IORD execution
(work bit 4)
0010
P_ER
Error end
IORD execution
(work bit 4)
IORD
0010.03
#0000
#00800000
IORD
First word specification
Number of words specification
Source unit number
First destination word specification
D21048
P_EQ
Normal end
P_ER
Error end
MOV
#0000
0100
166
RFID System
User's Manual
Clears work words
SECTION 8
Appendices
• Timing Chart (CIO n = CIO 2000 + (10 x 0) = CIO 2000)
Command Execution Bit
CIO n, bit 00
Command
Read
Read
CIO n+1 to n+4
ID Busy
CIO n+7, bit 00
Communications
1 scan
processing
Waiting for
RF Tag
Normal End
CIO n+7, bit 01
1 scan
Error End
CIO n+7, bit 02
Results Information
CIO n+8
0000
Results Information
stored.
0000
Missing error
IORD execution request
• If communications with the RF Tag fail, the bits in the Results Information (CIO n+8) will turn ON
accordingly, and the error code will be placed in the Processing Results Monitor (CIO n+9). The
previous read data will not be changed.
• To confirm the execution results from the user program, use the ON status of the Normal End Flag or
Error End Flag. These flags show the Unit status.
• Do not turn ON the Command Execution Bit during command execution (i.e., while the ID Busy Flag
is ON). It will be ignored.
• Execute the IORD instruction after the Normal End Flag turns ON.
SECTION 8
Sample Programming
RFID System
User's Manual
167
SECTION 8
Appendices
Read, Communications Specification: Single Auto
• Outline
This example shows how to read the memory of an RF Tag as it enters the interrogation zone for
Antenna 1.
An RF Tag is detected when it
enters the interrogation zone
and the contents of memory is
read.
RF Tag
Interrogation zone
Antenna 1
CS-series CPU Unit memory
RF Tag
Address Bit
7
(hex)
0010
0
0011
0
0012
0
0013
0
0014
0
0015
0
0016
0
0017
0
0018
0
0019
0
Bit
0
1
2
3
4
5
6
7
8
9
A
Bit
15
Read command
executed
Bit
00
D1000
D1001
01
02
03
04
D1002
05
06
D1003
07
08
D1004
09
0A
→: Read data storage order
• Unit Setting Example
Item
SECTION 8
Sample Programming
168
Setting
Setting location
Unit number
00
Unit’s front panel unit number switches: 00
Operating mode
Run Mode
Unit’s front panel test switch: OFF
System Settings
UID Addition Setting: Disabled
Set in the Special I/O Unit words in DM Area.
Test Mode Disable Setting: Enabled
Setting for Write Verification: Verification
RF Tag Communications Speed Setting: Normal Mode
Auto Wait Time Setting
Infinite
Command
Read
Communications
specification
Single auto
Read data storage order Leftmost  Rightmost
Read start address
0010 hex
Number of bytes to read 10 bytes
Read data storage
destination
RFID System
User's Manual
D1000 to D1004
Set in the Special I/O Unit Area.
SECTION 8
Appendices
First word allocated to Unit in DM Area: m = D20000 + (100  0) = D20000
DM
address
D20000
Meaning
Contents
0
0
D20001
0
15
0
14
13
12
UID Addition Setting
11
10
9
8
7
Test Mode Disable
Setting
0000
6
5
4
Setting for Write
Verification
3
2
1
0
RF Tag
Communications
Speed Setting
Auto Wait Time Setting
First word allocated to Unit in CIO Area: n = CIO 2000 + (10  0) = CIO 2000
Word
address
CIO 2001
Meaning
Contents
0
0
1
15
0
14
13
12
11
10
9
8
7
6
5
4
Communications
specification
Command code
CIO 2002
00
10
First read address
CIO 2003
00
0A
Number of read bytes
CIO 2004
10
00
Read data storage location (rightmost 4 digits)
CIO 2005
CIO 2006
0
0
00
00
00
Data storage area
Bank specification
(Always 0)
3
2
1
0
Data order
Read data storage location
(leftmost 2 digits)
---
---: Ignored.
SECTION 8
Sample Programming
RFID System
User's Manual
169
SECTION 8
Appendices
• Programming Example
When the execution input turns ON, settings are made in the Special I/O Unit Area using the MOV and
MOVL instructions and the command is executed. When communications with the RF Tag have been
completed, the Normal End Flag (CIO n+7, bit 01) or Error End Flag (CIO n+7, bit 02) is turned ON.
Read data can be used after the Normal End Flag (CIO n+7, bit 01) has been turned ON.
To end command execution while waiting for the RF Tag, turn ON the Abort Input.
Execution input
ID Busy
Test Mode
Unit Busy
2007.00
2007.14
2007.15
MOV
Waiting for command
execution (work bit)
#0010
Specification of command,
communications specifications
and read data storage order.
2001
0010.01
MOV
Specification of first read address.
#0010
2002
MOV
Specification of number of read bytes.
#000A
2003
MOVL
Read data storage location
#00001000
2004
Waiting for command
execution (work bit)
0010.01
SECTION 8
Command Execution Bit
0010.01
2000.00
Sample Programming
Abort input
ID Busy
Waiting for abort
(work bit)
2007.00
Abort Bit
0010.02
Normal End Flag
2007.01
2000.02
Waiting for Abort
(work bit)
0010.02
Normal end
Used to time getting
read data.
Error End Flag
2007.02
170
Waiting for command execution
(work bit)
RFID System
User's Manual
Error end
Used to time getting
results information.
SECTION 8
Appendices
• Timing Chart (CIO n = CIO 2000 + (10 x 0) = CIO 2000)
Command Execution Bit
CIO n, bit 00
Abort Bit
CIO n, bit 02
Command
CIO n+1 to n+4
Read
Read
ID Busy
CIO n+7, bit 00
Communications 1
scan
processing
Waiting for
RF Tag
Normal End/Error End
CIO n+7, bits 01/02
Results Information
CIO n+8
Data storage area
0000
Results Information
stored.
0000
Read data
• If communications with the RF Tag fail or an error occurs, communications will be aborted at that
point, the error flags in the Results Information (CIO n+8) will turn ON accordingly, and the error code
will be placed in the Processing Results Monitor (CIO n+9). The previous read data will not be
changed.
• If the Abort Bit is turned ON while waiting for an RF Tag, communications will be aborted at that point.
The Results Information (CIO n+8) will always be 0000 hex in this case.
• To confirm the execution results from the user program, use the ON status of the Normal End Flag or
Error End Flag in the Unit Status.
• Do not turn ON the Command Execution Bit during command execution (i.e., while the ID Busy Flag
is ON). It will be ignored.
SECTION 8
Sample Programming
RFID System
User's Manual
171
SECTION 8
Appendices
Read, Communications Specification: Repeat Auto
• Outline
This example shows how to repeatedly read the data in the memory of RF Tags from Antenna 2. An
auto wait time is set so that operation will be ended if an RF Tag is not detected within a specified
period of time.
RF Tags are detected every time one
enters the communications area and the
contents of memory is read.
RF Tag B
RF Tag A
Communications
area
Antenna 2
RF Tag
Address
(hex)
0010
0011
0012
0013
0014
0015
0016
0017
0018
0019
CS-series CPU Unit memory
Bit
Bit
7
0
0
0
0
0
0
0
0
0
0
0
1
2
3
4
5
6
7
8
9
A
Bit
15
Read command
executed
Bit
00
E0_1000
E0_1001
02
01
04
03
E0_1002
06
05
E0_1003
08
07
E0_1004
0A
09
→: Read data storage order
• Unit Settings Example
Item
Setting
SECTION 8
Sample Programming
Unit number
01
Unit’s front panel unit number switches: 01
Operating mode
Run Mode
Unit’s front panel test switch: OFF
System Settings
UID Addition Setting: Disabled
Test Mode Disable Setting: Enabled
Setting for Write Verification: Verification
RF Tag Communications Speed Setting:
Normal Mode
Set in the Special I/O Unit words in DM Area.
Auto Wait Time Setting
15 s
Command
Read
Communications specification Repeat auto
Read data storage order
Rightmost  Leftmost
Read Start address
0010 hex
Number of bytes to read
10 bytes
Read data storage destination E0_1000 to E0_1004
172
Setting location
RFID System
User's Manual
Set in the Special I/O Unit Area.
SECTION 8
Appendices
First word allocated to Unit in DM Area: m = D20000 + (100  (0 + 1)) = D20100
DM
address
D20100
Meaning
Contents
0
0
D20101
0
15
0
14
13
12
UID Addition Setting
11
10
9
8
7
Test Mode Disable
Setting
0150
6
5
4
Setting for Write
Verification
3
2
1
0
RF Tag
Communications
Speed Setting
Auto Wait Time Setting
First word allocated to Unit in CIO Area: n = CIO 2000 + 10  (0+ 1) = CIO 2010
Word
address
CIO 2011
Meaning
Contents
0
0
2
15
1
14
13
12
11
10
9
8
7
6
5
4
Communications
specification
Command code
CIO 2012
00
10
First read address
CIO 2013
00
0A
Number of read bytes
CIO 2014
10
00
Read data storage location (rightmost 4 digits)
CIO 2015
CIO 2016
5
0
00
00
00
Data storage area
3
2
1
0
Data order
Read data storage location
(leftmost 2 digits)
Bank specification
---
---: Ignored.
SECTION 8
Sample Programming
RFID System
User's Manual
173
SECTION 8
Appendices
• Programming Example
When the execution input turns ON, settings are made in the Special I/O Unit Area using the MOV and
MOVL instructions and the command is executed. When communications with the RF Tag have been
completed, the Normal End Flag (CIO n+7, bit 01) or Error End Flag (CIO n+7, bit 02) is turned ON.
Read data can be used after the Normal End Flag (CIO n+7, bit 01) has been ON.
If more than 15 seconds elapse while waiting for the RF Tag, the operation will be ended.
Execution input ID Busy
Test Mode
Unit Busy
2017.14
2017.15
MOV
Waiting for command
execution (work bit)
2017.00
#0021
Specification of command,
communications specifications
and read data storage order.
2011
0010.01
MOV
Specification of first read address.
#0010
2012
MOV
Specification of number of read bytes.
#000A
2013
MOVL
Read data storage location
#50001000
2014
Waiting for command
execution (work bit)
SECTION 8
Command Execution Bit
0010.01
Normal End Flag
Sample Programming
174
0010.01
Waiting for command execution
(work bit)
2017.01
2010.00
Normal end
Used to time getting
read data.
Error End Flag
Error end
2017.02
RFID System
User's Manual
Used to time getting
results information.
SECTION 8
Appendices
• Timing Chart (CIO n = CIO 2000 + 10 x (0 + 1) = CIO 2010)
Command Execution Bit
CIO n, bit 00
Command
Read
CIO n+1 to n+4
ID Busy
CIO n+7, bit 00
Waiting for
RF Tag
Communications
1 scan
processing
Waiting for
RF Tag
Communications
1 scan
processing
Waiting for
RF Tag
More than 15 s
elapsed.
Normal End
CIO n+7, bit 01
1 scan
Error End
CIO n+7, bit 02
Results Information
CIO n+8
Data storage area
0000
Normal end
0000
Normal end
Read data A
Missing error
Read data B
• If communications with the RF Tag fail or an error occurs, communications will be aborted at that point, the
error flags in the Results Information (CIO n+8) will turn ON accordingly, and the error code will be placed in
the Processing Results Monitor (CIO n+9). The previous read data will not be changed.
• If an auto wait time is set and the set time expires while waiting for an RF Tag, the command operation will be
aborted at that point, the RF Tag Missing Error Flag (CIO n+8, bit 10) in the Results Information will turn ON,
and an error code will be placed in the Processing Results Monitor (CIO n+9).
• When the communications specification is set to repeat auto, either the Normal End Flag or the Error End
Flag will turn ON every scan for consecutive scans. The execution results can be correctly determined by
using the ON status of both the Normal End Flag and the Error End Flag in Unit Status.
• To confirm the execution results from the user program, use the ON status of the Normal End Flag or Error
End Flag in the Unit Status.
• Do not turn ON the Command Execution Bit during command execution (i.e., while the ID Busy Flag is ON).
It will be ignored.
SECTION 8
Sample Programming
RFID System
User's Manual
175
SECTION 8
Appendices
Read, Communications Specification: FIFO Trigger
• Outline
This example shows how to read the memory of an RF Tag that is present in the interrogation zone for
Antenna 1.
When the Command Execution Bit is turned
ON, the Unit communicates with an RF Tag in
the Antenna's interrogation zone. If there is
no RF Tag, an RF Tag missing error will be
returned in the response.
An RF Tag that has completed
communications and for which
operations are prohibited.
RF Tag
Interrogation zone
Antenna
RF Tag
Address
Bit 7
(hex)
0010
0011
0012
0013
0014
0015
0016
0017
0018
0019
CS-series CPU Unit memory
Bit 0
0
0
0
0
0
0
0
0
0
0
1
2
3
4
5
6
7
8
9
A
Bit 15
Read command
executed
D1002
D1003
D1004
01
03
05
07
09
Bit 00
02
04
06
08
0A
→: Read data storage order
SECTION 8
• Unit Settings Example
Item
Setting
Setting location
Sample Programming
Unit number
00
Unit’s front panel unit number switches: 00
Operating mode
Run Mode
Unit’s front panel test switch: OFF
System Settings
UID Addition Setting: Disabled
Test Mode Disable Setting: Enabled
Setting for Write Verification: Verification
RF Tag Communications Speed Setting:
Normal Mode
Set in the Special I/O Unit words in DM Area.
Auto Wait Time Setting
Infinite
Command
Read
Communications specification FIFO trigger
Read data storage order
Leftmost  Rightmost
Read Start address
0010 hex
Number of bytes to read
10 bytes
Read data storage destination D1000 to D1004
176
D1000
D1001
RFID System
User's Manual
Set in the Special I/O Unit Area.
SECTION 8
Appendices
First word allocated to Unit in DM Area: m = D20000 + (100  0) = D20000
DM
address
D20000
Meaning
Contents
0
0
D20001
0
15
0
14
13
12
UID Addition Setting
11
10
9
8
7
Test Mode Disable
Setting
0000
6
5
4
Setting for Write
Verification
3
2
1
0
RF Tag
Communications
Speed Setting
Auto Wait Time Setting
First word allocated to Unit in CIO Area: n = CIO 2000 + (10  0) = CIO 2000
Word
address
CIO 2001
Meaning
Contents
0
0
3
15
1
14
13
12
11
10
9
8
7
6
5
4
Communications
specification
Command code
CIO 2002
00
10
First read address
CIO 2003
00
0A
Number of read bytes
CIO 2004
10
00
Read data storage location (rightmost 4 digits)
CIO 2005
CIO 2006
0
0
00
00
00
Data storage area
Bank specification
(Always 0)
3
2
1
0
Data order
Read data storage location
(leftmost 2 digits)
---
---: Ignored.
SECTION 8
Sample Programming
RFID System
User's Manual
177
SECTION 8
Appendices
• Programming Example
When the execution input turns ON, settings are made in the Special I/O Unit Area using the MOV and
MOVL instructions and the command is executed. When communications with the RF Tag have been
completed, the Normal End Flag (CIO n+7, bit 01) or Error End Flag (CIO n+7, bit 02) is turned ON.
Read data can be used after the Normal End Flag (CIO n+7, bit 01) has been ON.
To end command execution while waiting for the RF Tag, turn ON the Abort input.
Execution input
ID Busy
Test Mode
Unit Busy
2007.14
2007.15
MOV
Waiting for command
execution (work bit)
2007.00
#0030
Specification of command,
communications specifications
and read data storage order.
2001
0010.01
MOV
Specification of first read address.
#0010
2002
MOV
Specification of number of read bytes.
#000A
2003
MOVL
Read data storage location
#00001000
2004
Waiting for command execution
(work bit)
Waiting for command
execution (work bit)
SECTION 8
Command Execution Bit
0010.01
Normal End Flag
Sample Programming
178
0010.01
2007.01
2000.00
Normal end
Used to time getting
read data.
Error End Flag
Error end
2007.02
RFID System
User's Manual
Used to time getting
results information.
SECTION 8
Appendices
• Timing Chart (CIO n = CIO 2000 + (10 x 0) = CIO 2000)
Command Execution Bit
CIO n, bit 00
Command
CIO n+1 to n+4
Read
Read
ID Busy
CIO n+7, bit 00
Communications
1 scan
processing
Waiting for
RF Tag
Normal End
CIO n+7, bit 01
1 scan
Error End
CIO n+7, bit 02
Results Information
CIO n+8
Data storage area
0000
Results Information
stored.
0000
Missing error
Read data
• If communications with the RF Tag fail or an error occurs, communications will be aborted at that
point, the error flags in the Results Information (CIO n+8) will turn ON accordingly, and the error code
will be placed in the Processing Results Monitor (CIO n+9). The previous read data will not be
changed.
• To confirm the execution results from the user program, use the ON status of the Normal End Flag or
Error End Flag in the Unit Status.
• Do not turn ON the Command Execution Bit during command execution (i.e., while the ID Busy Flag
is ON). It will be ignored.
SECTION 8
Sample Programming
RFID System
User's Manual
179
SECTION 8
Appendices
Read, Communications Specification: FIFO Repeat
• Outline
This example shows how to repeatedly read the memory of RF Tags as they enter the interrogation
zone for Antenna 1.
RF Tags are detected
as they enter the interrogation zone
and communications are
performed for each one.
An RF Tag that has
completed
communications and for
which operations are
prohibited.
RF Tag
Interrogation zone
Antenna
RF Tag
Address
(hex)
0010
0011
0012
0013
0014
0015
0016
0017
0018
0019
Bit
CS-series CPU Unit memory
Bit
7
0
0
0
0
0
0
0
0
0
0
0
1
2
3
4
5
6
7
8
9
A
Bit
15
Read command
executed
D1000
D1001
01
02
03
04
D1002
05
06
D1003
07
08
D1004
09
0A
→: Read data storage order
SECTION 8
• Unit Settings Example
Item
Setting
Setting location
Sample Programming
Unit number
00
Unit's front panel unit number switches: 00
Operating mode
Run Mode
Unit's front panel test switch: OFF
System Settings
UID Addition Setting: Disabled
Test Mode Disable Setting: Enabled
Setting for Write Verification: Verification
RF Tag Communications Speed Setting:
Normal Mode
Set in the Special I/O Unit words in DM Area.
Auto Wait Time Setting
15 s
Command
Read
Communications specification FIFO repeat
Read data storage order
Leftmost  Rightmost
Read Start address
0010 hex
Number of bytes to read
10 bytes
Read data storage destination D1000 to D1004
180
Bit
00
RFID System
User's Manual
Set in the Special I/O Unit Area.
SECTION 8
Appendices
First word allocated to Unit in DM Area: m = D20000 + (100  0) = D20000
DM
address
D20000
Meaning
Contents
0
0
D20001
0
15
0
14
13
12
UID Addition Setting
11
10
9
8
7
Test Mode Disable
Setting
0150
6
5
4
Setting for Write
Verification
3
2
1
0
RF Tag
Communications
Speed Setting
Auto Wait Time Setting
First word allocated to Unit in CIO Area: n = CIO 2000 + (10  0) = CIO 2000
Word
address
CIO 2001
Meaning
Contents
0
0
4
15
0
14
13
12
11
10
9
8
7
6
5
4
Communications
specification
Command code
CIO 2002
00
10
First read address
CIO 2003
00
0A
Number of read bytes
CIO 2004
10
00
Read data storage location (rightmost 4 digits)
CIO 2005
CIO 2006
0
0
00
00
00
Data storage area
Bank specification
(Always 0)
3
2
1
0
Data order
Read data storage location
(leftmost 2 digits)
---
---: Ignored.
SECTION 8
Sample Programming
RFID System
User's Manual
181
SECTION 8
Appendices
• Programming Example
When the execution input turns ON, settings are made in the Special I/O Unit Area using the MOV and
MOVL instructions and the command is executed. When communications with the RF Tag have been
completed, the Normal End Flag (CIO n+7, bit 01) or Error End Flag (CIO n+7, bit 02) is turned ON.
Read data can be used after the Normal End Flag (CIO n+7, bit 01) has been ON.
To end command execution while waiting for the RF Tag, turn ON the Abort Input.
Execution input
ID Busy
Test Mode
Unit Busy
MOV
Waiting for command
execution (work bit)
2007.00
2007.14
2007.15
#0040
Specification of command,
communications specifications
and read data storage order.
2001
0010.01
MOV
Specification of first read address.
#0010
2002
MOV
Specification of number of read bytes.
#000A
2003
MOVL
Read data storage location
#00001000
2004
Waiting for command execution
(work bit)
Waiting for command
execution (work bit)
Command Execution Bit
SECTION 8
0010.01
Normal End Flag
Sample Programming
182
0010.01
2007.01
2000.00
Normal end
Used to time getting
read data.
Error End Flag
Error end
2007.02
RFID System
User's Manual
Used to time getting
results information.
SECTION 8
Appendices
• Timing Chart (CIO n = CIO 2000 + (10 x 0) = CIO 2000)
Command Execution Bit
CIO n, bit 00
Command
Read
CIO n+1 to n+4
ID Busy
CIO n+7, bit 00
Waiting for
RF Tag
Communications
processing
1 scan
Waiting for
RF Tag
Communications
1 scan
processing
Waiting for
RF Tag
More than 15 s
elapsed.
Normal End
CIO n+7, bit 01
1 scan
Error End
CIO n+7, bit 02
Results Information
CIO n+8
Data storage area
0000
Normal end
0000
Read data A
Normal end
Missing error
Read data B
• If communications with the RF Tag fail or an error occurs, communications will be aborted at that
point, the error flags in the Results Information (CIO n+8) will turn ON accordingly, and the error code
will be placed in the Processing Results Monitor (CIO n+9). The previous read data will not be
changed.
• If an auto wait time is set and the set time expires while waiting for an RF Tag, the command
operation will be aborted at that point, the RF Tag Missing Error Flag (CIO n+8, bit 10) in the Results
Information will turn ON, and an error code will be placed in the Processing Results Monitor (CIO
n+9).
• When the communications specification is set to repeat auto, either the Normal End Flag or the Error
End Flag will turn ON every scan for consecutive scans. The execution results can be correctly
determined by using the ON status of both the Normal End Flag and the Error End Flag in Unit
Status.
Error End Flag in the Unit Status.
is ON). It will be ignored.
RFID System
User's Manual
Sample Programming
• Do not turn ON the Command Execution Bit during command execution (i.e., while the ID Busy Flag
SECTION 8
• To confirm the execution results from the user program, use the ON status of the Normal End Flag or
183
SECTION 8
Appendices
Read, Communications Specification: Multi-access Trigger
• Outline
This example shows how to read the memory of all RF Tags present in the interrogation zone for
Antenna 1.
When the Command Execution Bit is turned ON,
the Unit will communicate with all RF Tags in the
interrogation zone. If there are no RF Tags in the
interrogation zone, an RF Tag missing error will be
returned.
RF Tag
Antenna
RF Tag
Address
(hex)
0010
0011
0012
0013
0014
0015
0016
0017
0018
0019
CS-series CPU Unit memory
Bit
Bit
7
0
0
0
0
0
0
0
0
0
0
0
1
2
3
4
5
6
7
8
9
A
Bit
15
Bit
00
D1000
D1001
01
02
03
04
D1002
05
06
D1003
07
08
D1004
09
0A
→: Read data storage order
Read command
executed
SECTION 8
• Unit Setting Example
Item
Setting
Setting location
Sample Programming
Unit number
00
Unit's front panel unit number switches: 00
Operating mode
Run Mode
Unit's front panel test switch: OFF
System Settings
UID Addition Setting: Disabled
Test Mode Disable Setting: Enabled
Setting for Write Verification: Verification
RF Tag Communications Speed Setting:
Normal Mode
Set in the Special I/O Unit words in DM Area.
Auto Wait Time Setting
Infinite
Command
Read
Set in the Special I/O Unit Area.
Communications specification Multi-access trigger
Read data storage order
Leftmost  Rightmost
Read Start address
0010 hex
Number of bytes to read
10 bytes
Read data storage destination D1000 to D1004
When communications with the RF Tags have been completed, the ID Sensor Unit sends the response sequentially.
Move the result data stored in the data storage area to another area before the data from the next RF Tag is stored.
184
RFID System
User's Manual
SECTION 8
Appendices
First word allocated to Unit in DM Area: m = D20000 + (100  0) = D20000
DM
address
D20000
Meaning
Contents
0
0
D20001
0
15
0
14
13
12
UID Addition Setting
11
10
9
8
7
Test Mode Disable
Setting
0000
6
5
4
Setting for Write
Verification
3
2
1
0
RF Tag
Communications
Speed Setting
Auto Wait Time Setting
First word allocated to Unit in CIO Area: n = CIO 2000 + (10  0) = CIO 2000
Word
address
CIO 2001
Meaning
Contents
0
0
5
15
0
14
13
12
11
10
9
8
7
6
5
4
Communications
specification
Command code
CIO 2002
00
10
First write address
CIO 2003
00
0A
Number of write bytes
CIO 2004
10
00
Read data storage location (rightmost 4 digits)
CIO 2005
CIO 2006
0
0
00
00
00
Data storage area
Bank specification
(Always 0)
3
2
1
0
Data order
Read data storage location
(leftmost 2 digits)
---
---: Ignored.
SECTION 8
Sample Programming
RFID System
User's Manual
185
SECTION 8
Appendices
• Programming Example
When the execution input turns ON, settings are made in the Special I/O Unit Area using the MOV and
MOVL instructions and the command is executed. When communications with the RF Tag have been
completed, the Normal End Flag (CIO n+7, bit 01) or Error End Flag (CIO n+7, bit 02) is turned ON.
Read data can be used after the Normal End Flag (CIO n+7, bit 01) has been ON.
To end command execution while waiting for the RF Tag, turn ON the Abort Input.
Execution input
ID Busy
Test Mode
Unit Busy
MOV
Waiting for command
execution (work bit)
2007.00
2007.14
2007.15
#0050
Specification of command,
communications specifications
and read data storage order.
2001
0010.01
MOV
Specification of first read address.
#0010
2002
MOV
Specification of number of read bytes.
#000A
2003
MOVL
Read data storage location
#00001000
2004
Waiting for command execution
(work bit)
Waiting for command
execution (work bit)
SECTION 8
Command Execution Bit
0010.01
Normal End Flag
Sample Programming
186
0010.01
2007.01
2000.00
Normal end
Used to time getting
read data.
Error End Flag
Error end
2007.02
RFID System
User's Manual
Used to time getting
results information.
SECTION 8
Appendices
• Timing Chart (CIO n = CIO 2000 + (10 x 0) = CIO 2000)
When communications with all RF Tags in
the communications area have been
completed, the ID Busy Flag will turn OFF.
Command Execution Bit
CIO n, bit 00
Command
Read
Read
CIO n+1 to n+4
ID Busy
CIO n+7, bit 00
Communications
processing
1 scan
Communications
processing
1 scan
Normal End
CIO n+7, bit 01
Error End
CIO n+7, bit 02
Results Information
CIO n+8
0000
Data storage area
Results Information
stored.
0000
Results Information
stored.
Read data
• If communications with the RF Tag fail or an error occurs, communications will be aborted at that
point, the error flags in the Results Information (CIO n+8) will turn ON accordingly, and the error code
will be placed in the Processing Results Monitor (CIO n+9). The previous read data will not be
changed.
• To confirm the execution results from the user program, use the ON status of the Normal End Flag or
Error End Flag in the Unit Status.
• Do not turn ON the Command Execution Bit during command execution (i.e., while the ID Busy Flag
is ON). It will be ignored.
SECTION 8
Sample Programming
RFID System
User's Manual
187
SECTION 8
Appendices
Read, Communications Specification: Multi-access Repeat
• Outline
This example shows how to repeatedly read the memory of RF Tags as they enter the interrogation
zone for Antenna 1.
RF Tags are detected as
they enter the interrogation zone
and communications
are performed.
RF Tag
Antenna
RF Tag
Address
(hex)
0010
0011
0012
0013
0014
0015
0016
0017
0018
0019
CS-series CPU Unit memory
Bit
Bit
7
0
0
0
0
0
0
0
0
0
0
0
1
2
3
4
5
6
7
8
9
A
Bit
15
Read command
executed
01
02
03
04
D1002
05
06
D1003
07
08
D1004
09
0A
→: Read data storage order
SECTION 8
• Unit Settings Example
Item
Setting
Setting location
Sample Programming
Unit number
00
Unit's front panel unit number switches: 00
Operating mode
Run Mode
Unit's front panel test switch: OFF
System Settings
UID Addition Setting: Disabled
Test Mode Disable Setting: Enabled
Setting for Write Verification: Verification
RF Tag Communications Speed Setting:
Normal Mode
Set in the Special I/O Unit words in DM Area.
Auto Wait Time Setting
15 s
Command
Read
Communications specification Multi-access repeat
Read data storage order
Leftmost  Rightmost
Read Start address
0010 hex
Number of bytes to read
10 bytes
Read data storage destination D1000 to D1004
188
Bit
00
D1000
D1001
RFID System
User's Manual
Set in the Special I/O Unit Area.
SECTION 8
Appendices
First word allocated to Unit in DM Area: m = D20000 + (100  0) = D20000
DM
address
D20000
Meaning
Contents
0
0
D20001
0
15
0
14
13
12
UID Addition Setting
11
10
9
8
7
Test Mode Disable
Setting
0150
6
5
4
Setting for Write
Verification
3
2
1
0
RF Tag
Communications
Speed Setting
Auto Wait Time Setting
First word allocated to Unit in CIO Area: n = CIO 2000 + (10  0) = CIO 2000
Word
address
CIO 2001
Meaning
Contents
0
0
6
15
0
14
13
12
11
10
9
8
7
6
5
4
Communications
specification
Command code
CIO 2002
00
10
First write address
CIO 2003
00
0A
Number of write bytes
CIO 2004
10
00
Read data storage location (rightmost 4 digits)
CIO 2005
CIO 2006
0
0
00
00
00
Data storage area
Bank specification
(Always 0)
3
2
1
0
Data order
Read data storage location
(leftmost 2 digits)
---
---: Ignored.
SECTION 8
Sample Programming
RFID System
User's Manual
189
SECTION 8
Appendices
• Programming Example
When the execution input turns ON, settings are made in the Special I/O Unit Area using the MOV and
MOVL instructions and the command is executed. When communications with the RF Tag have been
completed, the Normal End Flag (CIO n+7, bit 01) or Error End Flag (CIO n+7, bit 02) is turned ON.
Read data can be used after the Normal End Flag (CIO n+7, bit 01) has been ON.
To end command execution while waiting for the RF Tag, turn ON the Abort Input.
Execution input
ID Busy
Test Mode
Unit Busy
Waiting for command
execution (work bit)
2007.00
2007.14
2007.15
MOV
#0060
Specification of command,
communications specifications
and read data storage order.
2001
0010.01
MOV
Specification of first read address.
#0010
2002
MOV
Specification of number of read bytes.
#000A
2003
MOVL
Read data storage location
#00001000
2004
Waiting for command execution
(work bit)
Waiting for command
execution (work bit)
SECTION 8
Command Execution Bit
0010.01
Normal End Flag
Sample Programming
190
0010.01
2007.01
2000.00
Normal end
Used to time getting
read data.
Error End Flag
2007.02
RFID System
User's Manual
Error end
Used to time getting
results information.
SECTION 8
Appendices
• Timing Chart (CIO n = CIO 2000 + (10 x 0) = CIO 2000)
Command Execution Bit
CIO n, bit 00
Command
CIO n+1 to n+4
Read
ID Busy
CIO n+7, bit 00
Communications
processing
1 scan
Communications
1 scan
processing
Waiting for
RF Tag
More than 15 s
elapsed.
Normal End
CIO n+7, bit 01
1 scan
Error End
CIO n+7, bit 02
Results Information
0000
Normal end
0000
Normal end
Missing error
CIO n+8
Data storage area
Read data A
Read data B
• If communications with the RF Tag fail or an error occurs, communications will be aborted at that
point, the error flags in the Results Information (CIO n+8) will turn ON accordingly, and the error code
will be placed in the Processing Results Monitor (CIO n+9). The previous read data will not be
changed.
• If an auto wait time is set and the set time expires while waiting for an RF Tag, the command
operation will be aborted at that point, the RF Tag Missing Error Flag (CIO n+8, bit 10) in the Results
Information will turn ON, and an error code will be placed in the Processing Results Monitor (CIO
n+9).
• When the communications specification is set to repeat auto, either the Normal End Flag or the Error
End Flag will turn ON every scan for consecutive scans. The execution results can be correctly
determined by using the ON status of both the Normal End Flag and the Error End Flag in Unit
Status.
Error End Flag in the Unit Status.
is ON). It will be ignored.
RFID System
User's Manual
Sample Programming
• Do not turn ON the Command Execution Bit during command execution (i.e., while the ID Busy Flag
SECTION 8
• To confirm the execution results from the user program, use the ON status of the Normal End Flag or
191
SECTION 8
Appendices
Write, Communications Specification: Trigger
 Outline
This example shows how to write data to the memory of an RF Tag in the interrogation zone of
Antenna 1.
When the Command Execution Bit
is turned ON, the Unit will write
data to the memory of an RF Tag
in the interrogation zone.
RF Tag
Interrogation zone
Antenna 1
RF Tag
CS-series CPU Unit memory
D1100
D1101
D1102
D1103
Bit
Bit
15
00
02
04
06
08
01
03
05
07
Write command
executed
→: Write data storage order
Address Bit
7
(hex)
0010
0
0011
0
0012
0
0013
0
0014
0
0015
0
0016
0
0017
0
Bit
0
1
2
3
4
5
6
7
8
 Unit Settings Example
Item
Setting location
Unit number
55
Unit’s front panel unit number switches: 55
Operating mode
Run Mode
Unit’s front panel test switch: OFF
System Settings
UID Addition Setting: Disabled
Test Mode Disable Setting: Enabled
Setting for Write Verification: Verification
RF Tag Communications Speed Setting:
Normal Mode
Data transfer setting: Cyclic
Set in the Special I/O Unit words in DM Area.
Auto Wait Time Setting
Infinite
Command
Write
SECTION 8
Sample Programming
192
Setting
Communications specification Trigger
Write data storage order
Rightmost  Leftmost
Write Start address
0010 hex
Number of bytes to write
8 bytes
Write data storage destination D1000 to D1004
RFID System
User's Manual
Set in the Special I/O Unit Area.
SECTION 8
Appendices
First word allocated to Unit in DM Area: m = D20000 + (100  55) = D25500
DM
address
D25500
Meaning
Contents
0
0
D25501
0
15
0
14
13
12
UID Addition Setting
11
10
9
8
7
Test Mode Disable
Setting
0000
6
5
4
Setting for Write
Verification
3
2
1
0
RF Tag
Communications
Speed Setting
Auto Wait Time Setting
First word allocated to Unit in CIO Area: n = CIO 2000 + (10  55) = CIO 2550
Word
address
Meaning
Contents
CIO 2551
01
0
15
1
14
13
12
11
10
9
8
7
6
5
4
Communications
specification
Command code
CIO 2552
00
10
First write address
CIO 2553
00
08
Number of write bytes
CIO 2554
11
00
Read data storage location (rightmost 4 digits)
CIO 2555
CIO 2556
0
0
00
00
00
Data storage area
Bank specification
(Always 0)
3
2
1
0
Data order
Write data storage location
(leftmost 2 digits)
---
---: Ignored.
SECTION 8
Sample Programming
RFID System
User's Manual
193
SECTION 8
Appendices
• Programming Example
When the execution input turns ON, settings are made in the Special I/O Unit Area using the MOV and
MOVL instructions and the command is executed. When communications with the RF Tag have been
completed, the Normal End Flag (CIO n+7, bit 01) or Error End Flag (CIO n+7, bit 02) is turned ON.
Execution input
ID Busy
Test Mode
Unit Busy
MOV
Waiting for command
execution (work bit)
2557.00
2557.14
2557.15
#0101
Specification of command,
communications specifications
and write data storage order.
2551
0010.01
MOV
Specification of first write address.
#0010
2552
MOV
Specification of number of write bytes.
#0008
2553
MOVL
Write data storage location
#00001100
2554
Waiting for command
execution (work bit)
0010.01
Waiting for command execution
(work bit)
Command Execution Bit
0010.01
2550.00
SECTION 8
Normal End Flag
Normal end
2557.01
Error End Flag
Sample Programming
194
2557.02
RFID System
User's Manual
Error end
Used to time getting
results information.
SECTION 8
Appendices
• Timing Chart (CIO n = CIO 2000 + (10 x 55) = CIO 2550)
Command Execution Bit
CIO n, bit 00
Command
CIO n+1 to n+4
Write
Write
ID Busy
CIO n+7, bit 00
Communications
1 scan
processing
Waiting for
RF Tag
Normal End
CIO n+7, bit 01
1 scan
Error End
CIO n+7, bit 02
0000
Data storage area
Normal end
0000
Missing error
Write data
• To confirm the execution results from the user program, use the ON status of the Normal End Flag or
Error End Flag in the Unit Status.
• Do not turn ON the Command Execution Bit during command execution (i.e., while the ID Busy Flag
is ON). It will be ignored.
SECTION 8
Sample Programming
RFID System
User's Manual
195
SECTION 8
Appendices
Write, Communications Specification: Trigger, Data Transfer:
Intelligent I/O Instructions
 Outline
This example shows how to write data to the memory of an RF Tag that is present in the interrogation
zone for Antenna 1.
When the Command
Execution Bit is turned ON,
the Unit will write data to the
memory of an RF Tag in the
interrogation zone.
RF Tag
Interrogation zone
Antenna 1
RF Tag
CS-series CPU Unit memory
Bit
Bit
15
00
D20920
D20921
D20922
D20923
02
04
06
08
01
03
05
07
Write command
executed
→: Write data storage order
Address
(hex)
0020
0021
0022
0023
0024
0025
0026
0027
Bit
Bit
7
0
0
0
0
0
0
0
0
0
1
2
3
4
5
6
7
8
 Unit Settings Example
Item
Setting
SECTION 8
Sample Programming
Unit number
00
Unit's front panel unit number switches: 00
Operating mode
Run Mode
Unit's front panel test switch: OFF
System Settings
UID Addition Setting: Disabled
Test Mode Disable Setting: Enabled
Setting for Write Verification: Verification
RF Tag Communications Speed Setting:
Normal Mode
Data Transfer Setting: Intelligent I/O
Instructions
Set in the Special I/O Unit words in DM Area.
Auto Wait Time Setting
Infinite
Command
Write
Set in the Special I/O Unit Area.
Communications specification Trigger
Write data storage order
Rightmost  Leftmost
Write Start address
0020 hex
Number of bytes to write
512 bytes
Write data storage destination D20920 to D21431
196
Setting location
RFID System
User's Manual
Set in IOWR instruction.
SECTION 8
Appendices
First word allocated to Unit in DM Area: m = D20000 + (100  0) = D20000
DM
address
D20000
Meaning
Contents
0
0
0
15
0
14
13
12
UID Addition Setting
11
10
9
8
7
Test Mode Disable
Setting
6
5
4
Setting for Write
Verification
D20001
0000
Auto Wait Time Setting
D20090
0001
Data Transfer Setting
3
2
1
0
RF Tag
Communications
Speed Setting
First word allocated to Unit in CIO Area: n = CIO 2000 + (10  0) = CIO 2000
Word
address
Meaning
Contents
13
12
11
10
9
8
7
6
CIO 2002
00
20
Write start address
CIO 2003
02
00
Number of bytes to write
CIO 2004
00
00
---
00
---
00
---
CIO 2006
0
00
5
4
Communications
specification
01
0
1
14
CIO 2001
CIO 2005
0
15
Command code
3
2
1
0
Data order
---: Ignored.
SECTION 8
Sample Programming
RFID System
User's Manual
197
SECTION 8
Appendices
• Programming Example
Execute the IOWR instruction before starting execution of the write command.
When the command execution input turns ON, settings are made in the Special I/O Unit Area using
MOV instructions and the command is executed. When communications with the RF Tag have been
completed, the Normal End Flag (CIO n+7, bit 01) or Error End Flag (CIO n+7, bit 02) is turned ON.
The following ladder programming uses the Write command and the IOWR instruction to write 512
bytes of data.
The IOWR instruction is executed twice to write 256 bytes (128 words) each time.
IOWR execution
(work bit 1)
ID Busy
Test Mode
Unit Busy
2007.00
2007.14
2007.15
IOWR
0010.00
#0000
D20920
IOWR
First word specification
First source word specification
Number of words specification
Destination unit number
#00800000
P_EQ
ASL
IOWR execution
(work bit 2)
0010
P_ER
Error end
IOWR execution
(work bit 2)
IOWR
0010.01
#0000
D21048
IOWR
First word specification
First source word specification
Number of words specification
Destination unit number
#00800000
P_EQ
ASL
Waiting for command
execution (work bit 3)
0010
P_ER
Error end
Waiting for command
execution (work bit 3)
SECTION 8
MOV
0010.02
#0101
Specification of command,
communications
specifications, and write
data storage order.
2001
MOV
Sample Programming
Specification of write
start address.
#0020
2002
MOV
Specification of number
of write bytes.
#0200
2003
ASL
Waiting for command
execution (work bit 4)
0010
Command execution
command start (work bit 4)
Command execution command
0010.03
2000.00
MOV
Clears work words
#0000
0010
Normal End Flag
Normal end
2007.01
Error End Flag
Error end
2007.02
198
RFID System
User's Manual
SECTION 8
Appendices
• Timing Chart (CIO n = CIO 2000 + (10 x 55) = CIO 2550)
Command Execution Bit
CIO n, bit 00
Command
CIO n+1 to n+4
Write
Write
ID Busy
CIO n+7, bit 00
Communications
1 scan
processing
Waiting for
RF Tag
Normal End
CIO n+7, bit 01
1 scan
Error End
CIO n+7, bit 02
Results Information
CIO n+8
0000
Normal end
0000
Missing error
IOWR execution request
Data storage area
Write data
• To confirm the execution results from the user program, use the ON status of the Normal End Flag or
Error End Flag. These flags show the Unit status.
• Do not turn ON the Command Execution Bit during command execution (i.e., while the ID Busy Flag
is ON). It will be ignored.
• Execute the IOWR instruction before executing the write command.
SECTION 8
Sample Programming
RFID System
User's Manual
199
SECTION 8
Appendices
Copy, Communications Specification: Single Auto
• Outline
This example shows how to read data from the memory of an RF Tag A when it enters the interrogation
zone for Antenna 1 and then write the data to RF Tag B in the interrogation zone for Antenna 2.
2. The data is written to the RF
Tag in the interrogation zone
when the read operation is
finished.
1. The RF Tag is detected when it
enters the interrogation zone and
the contents of memory is read.
RF Tag (A)
RF Tag (B)
Interrogation
zone
Antenna 1
Antenna 2
RF Tag (A)
Bit
Address Bit
7
0
(hex)
0020
0
0
0021
0
1
0022
0
2
0023
0
3
0024
0
4
002E
002F
1
1
Copy command
executed
5
6
RF Tag (B)
Bit
Address Bit
7
0
(hex)
0010
0
0
0011
0
1
0012
0
2
0013
0
3
0014
0
4
001E
001F
1
1
5
6
• Unit Setting Example
Item
Setting location
Unit number
77
Unit's front panel unit number switches: 77
Operating mode
Run Mode
Unit’s front panel test switch: OFF
System Settings
UID Addition Setting: Disabled
Test Mode Disable Setting: Enabled
Setting for Write Verification: Verification
RF Tag Communications Speed Setting:
Normal Mode
Set in the Special I/O Unit words in DM Area.
Auto Wait Time Setting
Infinite
Command
Copy
SECTION 8
Sample Programming
200
Setting
Communications specification Trigger
Read start address
0020 hex
Number of read/write bytes
16 bytes
Write start address
0010 hex
RFID System
User's Manual
Set in the Special I/O Unit Area.
SECTION 8
Appendices
First word allocated to Unit in DM Area: m = D20000 + (100  77) = D27700
DM
address
D27700
Meaning
Contents
0
0
D27701
0
15
0
14
13
12
UID Addition Setting
11
10
9
8
7
Test Mode Disable
Setting
0000
6
5
4
3
2
1
0
RF Tag
Communications
Speed Setting
Setting for Write
Verification
Auto Wait Time Setting
First Word Allocated to Unit in CIO Area: n = CIO 2000 + (10  77) = CIO 2770
Word
address
Meaning
Contents
14
13
11
10
9
8
7
6
5
CIO 2772
00
20
First processing address
CIO 2773
00
10
Number of processing bytes
CIO 2776
00
0
00
Command code
00
0
00
10
4
3
Communications
specification
09
CIO 2775
0
12
CIO 2771
CIO 2774
0
15
2
1
0
---
-----
---
--Command option
---: Ignored.
SECTION 8
Sample Programming
RFID System
User's Manual
201
SECTION 8
Appendices
• Programming Example
When the execution input turns ON, settings are made in the Special I/O Unit Area using the MOV
instruction and the command is executed. Data is read from the memory of RF Tag A and written to the
memory of RF Tag B. When communications with RF Tag B have been completed, the Normal End
Flag (CIO n+7, bit 01) or Error End Flag (CIO n+7, bit 02) is turned ON.
Execution input
ID Busy
Test Mode
Unit Busy
Waiting for command
execution (work bit)
2777.00
2777.14
2777.15
MOV
Specification of command,
communications specifications
#0900
2771
0010.01
MOV
Specification of first read address.
#0020
2772
MOV
Specification of number of
read (write) bytes.
#0010
2773
MOV
Write data storage location
#0010
2776
Waiting for command execution
(work bit)
Waiting for command
execution (work bit)
0010.01
Command Execution Bit
SECTION 8
0010.01
Normal End Flag
Normal end
2777.01
Sample Programming
202
2770.00
Error End Flag
Error end
2777.02
RFID System
User's Manual
Used to time getting
results information.
SECTION 8
Appendices
• Timing Chart (CIO n = CIO 2000 + (10  77) = CIO 2770)
Command Execution Bit
CIO n, bit 00
Abort Bit
CIO n, bit 02
Command
Copy
CIO n+1 to n+6
ID Busy
CIO n+7, bit 00
Antenna 1
processing
Antenna 2
processing
1 scan
Normal End/Error End
CIO n+7, bits 01/02
Results Information
CIO n+8
0000
Results Information
stored.
Data storage area
• To confirm the execution results from the user program, use the ON status of the Normal End Flag or
Error End Flag in the Unit Status.
• Do not turn ON the Command Execution Bit during command execution (i.e., while the ID Busy Flag
is ON). It will be ignored.
SECTION 8
Sample Programming
RFID System
User's Manual
203
SECTION 8
Appendices
Data Coding Tables
Special I/O Unit Words Allocated in DM Area
First word allocated to Antenna 1: m = D20000 + (100  Unit number)
First word allocated to Antenna 2: m = D20000 + (100  (Unit number + 1))
 System Settings: DM m (= D2@@00)
Meaning
DM address
15 14 13 12 11 10
D2@@00
9
8
UID
Test Mode
Addition Setting Disable Setting
UID Addition
Setting (BCD)
0: Disabled
1: Enabled
7
6
5
4
3
2
0
Setting for Write Tag Communications
Speed Setting
Verification
Setting for Write
Verification (BCD)
Test Mode Disable
Setting (BCD)
0: Enabled
1: Disabled
1
Tag Communications
Speed Setting (BCD)
0: Normal Mode
1: High-speed Mode
0: Verification
1: No verification
 Auto Wait Time Setting: DM m+1 (= D2@@01)
Meaning
DM address
15 14 13 12 11 10
D2@@01
Auto Wait Time Setting
SECTION 8
0000: Infinity (not monitored)
0001 to 9999 (hex) × 0.1 s
Data Coding Tables
204
RFID System
User's Manual
9
8
7
6
5
Auto Wait Time Setting
4
3
2
1
0
SECTION 8
Appendices
Words Allocated in Special I/O Unit Area in CIO Area
First word allocated to Antenna 1: n = CIO 2000 + (10  Unit number)
First word allocated to Antenna 2: n = CIO 2000 + (10  (Unit number + 1))
 Unit Controls: CIO n (= CIO 2@@0)
Meaning
Word address
15 14 13 12 11 10
CIO 2@@0
9
8
7
6
5
4
3
2
1
0
Not used
Run/Test Bit
Abort Bit
OFF: Run Mode
ON: Test Mode
OFF: Not effective
ON: Command aborted
Error Reset Bit
OFF: Not effective
ON: Results information (n+8) cleared
Command Execution Bit
OFF: Waiting for command
OFF to ON: Command executed
 Command: Words (CIO n+1) to (CIO n+3) (= CIO 2@@1 to CIO 2@@3)
Meaning
Word address
15 14 13 12 11 10
CIO 2@@1
9
8
7
6
5
4
3
Communications
specification
Command code
2
1
0
Processing
specification
SECTION 8
Applicable
command
Command
code (BCD)
Proc spec
(BCD)
Applicable
command
Applicable
command
00
Read
0: Trigger
Read
01
Write
1: Auto
Write
02
Bit Set
2: Repeat auto
Bit Set
03
Bit Clear
3: FIFO Trigger
Bit Clear
04
Mask Bit Write
4: FIFO Repeat
Mask Bit Write
05
Calculation Write
5: Multi-access trigger Calculation Write
Read with Error Correction
06
Data Fill
6: Multi-access repeat Data Fill
Write with Error Correction
07
Data Check
Read with Error Correction
08
No. of Write Control
Write with Error Correction
09
Copy
0A
Read with Error Correction
0B
Write with Error Correction
0C
UID Read
10
Noise Measurement
Data storage
order
0: Leftmost to
rightmost
1: Rightmost to
leftmost
Read
Write
Bit Set
Bit Clear
Mask Bit Write
UID Read
Calculation Write
UID Read
0: Add
1: Subtract
0: Trigger
Data Check
0: Bytes
Data Fill
1: Auto
No. of Write Control
1: Words
Copy
0: Calculate
---: Noise Measurement Noise Measurement
Data Coding Tables
Com spec
(BCD)
Data Check
1: Verify
0: Add
1: Subtract
No. of Write
Control
---
Copy
Noise Measurement
---: Undefined (No setting required)
RFID System
User's Manual
205
SECTION 8
Appendices
Meaning
Word address
15 14 13 12 11 10
CIO 2@@2
8
7
6
5
4
3
2
1
0
Processing address
Number of bytes to process
CIO 2@@3
No.of bytes
(hex)
9
Applicable
command
Applicable
command
Processing
address (hex)
0001 to 0800 Read
Write
0001 to 0004 Bit Set
Bit Clear
Mask Bit Write
--0001 to 0004 Calculation Write
Data Fill
0000 (All)
0001 to 0800
0003 to 0800 Data Check
--No. of Write Control
0001 to 0800 Copy
0001 to 01FE Read with Error Correction
Write with Error Correction
--UID Read
--Noise Measurement
0000 to FFFF
(Settable
addresses depend
on ID Tag.)
0000 to FFFD
Read
Write
Bit Set
Bit Clear
Mask Bit Write
Calculation Write
Data Fill
Data Check
No. of Write Control
Read Address
0000 to FFFF
00000 to FFFA
(See note.)
-----
Copy
Read with Error Correction
Write with Error Correction
UID Read
Noise Measurement
---: Undefined (No setting required)
---: Undefined (No setting required)
Note: The range of addresses that can be set
depends on the RF Tag.
SECTION 8
 Data Storage Area: Words (CIO n+4) to (CIO n+5)
(= CIO 2@@4 to CIO 2@@5)
Data Coding Tables
Meaning
Word address
15 14 13 12 11 10
CIO 2@@4
CIO 2@@5
206
RFID System
User's Manual
8
7
6
5
4
3
2
1
0
Data storage word (rightmost 4 digits)
Data storage
area
Setting Applicable
(hex)
Area
0
1
2
3
4
5
6
7
9
DM
CIO
WR
HR
AR
EM
TIM
CNT
Bank
No.
Bank No. Applicable
(hex)
area
0
0 to C
0
DM
CIO
WR
HR
AR
EM
TIM
CNT
Data storage word
(leftmost 2 digits)
Leftmost 2
digits (BCD)
Rightmost
4 digits (BCD)
000000 to 032767
000000 to 006143
000000 to 000511
000000 to 000511
000000 to 000959
000000 to 032767
000000 to 004095
Applicable
area
DM
CIO
WR
HR
AR
EM
TIM
CNT
SECTION 8
Appendices
 Command Option: CIO n+6 (= CIO 2@@6)
Meaning
Word address
15 14 13 12 11 10
CIO 2@@6
Command option
--Mask specified data
0000 to FFFE
Operation data
0000 to FFFF
Fill data
0000 to FFFF
--Number of writes
0000 to FFFF
Write address
0000 to FFFF
-----
9
8
7
6
5
4
3
2
1
0
Command option
Applicable
command
Read
Write
Bit Set
Bit Clear
Mask Bit Write
Calculation
Write
Data Fill
Data Check
No. of Writes
Control
Copy
Read with Error Correction
Write with Error Correction
UID Read
Noise Measurement
---: Not defined (No setting necessary.)
SECTION 8
Data Coding Tables
RFID System
User's Manual
207
SECTION 8
Appendices
Degree of Protection
IP-@@ degrees of protection given in this document were confirmed by OMRON based on the test conditions
given below. Confirm satisfactory sealing performance in the actual operating environment and under the
actual operating conditions before use.
IP = International Protection mark
 IEC (International Electrotechnical Commission)
Standards (IEC60529: 2001)
IP-@ @
(B)
(A)
(A): First symbol: Degree of protection against solid materials
Degree
Protection
No protection
0
50-mm dia.
Protects against penetration of any solid object such as a hand that is 50 mm or more in diameter.
1
12.5-mm dia.
2
Protects against penetration of any solid object such as a finger that is 12.5 mm or more in diameter.
Any object with a diameter of 12 mm, such as a finger, will not reach a hazardous part even if it
penetrates 80 mm.
Protects against penetration of any solid object such as a wire that is 2.5 mm or more is diameter.
2.5 mm
3
SECTION 8
1 mm
Degree of Protection
Protects against penetration of dust of a quantity that may malfunction the protect or obstruct the
safety operation of the product.
5
Protects against penetration of all dust.
6
(B): Second symbol: Degree of protection against water
Degree
Protection
Test method (with pure water)
0
No protection
Not protected against water.
1
Protection against water
drops
Protects against vertical drops Water is dropped
of water towards the product. vertically towards the
product from the test
machine for 10 min.
2
208
Protects against penetration of any solid object such as a wire that is 1 mm or more in diameter.
4
RFID System
User's Manual
Protection against water
drops
Protects against drops of
water approaching at a
maximum angle of 15 to the
left, right, back, and front of
vertical towards the product.
No test
Water is dropped for
2.5 min each (i.e., 10 min
in total) towards the
product inclined 15 to the
left, right, back, and front
from the test machine.
200 mm
15°
200 mm
SECTION 8
Appendices
Degree
Protection
Test method (with pure water)
3
Protection against sprinkled Protects against sprinkled
water
water approaching at a
maximum angle of 60 from
vertical towards the product.
Water is sprinkled at a
maximum angle of 60 to
the left and right from
vertical for 10 min from
the test machine.
4
Protection against water
spray
Protects against water spray
approaching at any angle
towards the product.
Water is sprayed at any
angle towards the product
for 10 min from the test
machine.
5
Protection against water jet
spray
Protects against water jet
spray approaching at any
angle towards the product.
Water is jet sprayed at
any angle towards the
product for 1 min per
square meter for at least 3
min in total from the test
machine.
6
7
8
Protection against highpressure water jet spray
Protection underwater
Protection underwater
(See note.)
Protects against highpressure water jet spray
approaching at any angle
towards the product.
Water is jet sprayed at
any angle towards the
product for 1 min per
square meter for at least 3
min in total from the test
machine.
Resists the penetration of
water when the product is
placed underwater at
specified pressure for a
specified time.
The product is placed 1 m
deep in water (if the
product is 850 mm max.
in height) for 30 min.
Can be used continuously
underwater.
The test method is
determined by the
manufacturer and user.
Water rate is 0.07
liter/min per hole.
Water rate is 0.07
liter/min per hole.
2.5 to 3 m
12.5 liter/min
Diameter of discharging nozzle: 6.3 mm
2.5 to 3 m
100 liter/min
Diameter of discharging nozzle: 12.5 mm
1m
90°
60°
30°
10ᴾᶒᶍᴾ15 cm
0°
Degree of Protection
About IPX9K
IPX9K is a protection standard regarding high temperature and high-pressure water which is defined
by the German standard (DIN 40050 PART9).
Water is sprayed on 80 C hot water with the water pressure of 80 to 100BAR from a nozzle to the
test piece.
Amount of water is 14 to 16 liters/minute.
The distance between the test piece and a nozzle is 10 to 15 cm, and the directions of waterdrainage are 0 degrees, 30 degrees, 60 degrees, and 90 degrees horizontally.
They are evaluated with the test piece is rotating on a horizontal plane by 30 seconds in each
direction.
SECTION 8
Note: OMRON Test Method
Usage condition: 10 m or less under water in natural conditions
1. No water ingress after 1 hour under water at 2 atmospheres of pressure.
2. Sensing distance and insulation resistance specifications must be met after 100 repetitions of half hour in 5C water
and half hour in 85C water.
 Oil resistance (OMRON in-house standard)
Protection
Oil-resistant
No adverse affect from oil drops or oil spray approaching from any direction.
Oil-proof
Protects against penetration of oil drops or oil spray approaching from any direction.
Note. Oil resistance has been tested using a specific oil as defined in the OMRON test method. (JIS C 0920:2003, Appendix 1)
RFID System
User's Manual
209
Revision History
A manual revision code appears as a suffix to the catalog number at the bottom of the front and rear pages.
Man. No.: Z271-E1-05
Revision code
210
Revision code
Date
01
December 2007
02
August 2010
02A
December 2010
02B
May 2011
Revised contents
Original production
Added information for Heat-resistive RF Tags (V680-D1KP58HTN and V680D1KP58HT).
Added information on RF Tag memory setting and data transfer setting.
Made other minor corrections.
Minor corrections (p.67, 95)
Minor corrections (p.150)
03
December 2011
Added items for V680-D1KP52M-BT01, V680-D1KP52M-BT11, V680-D2KF52MBT01, and V680-D2KF52M-BT11 RF Tag, and made other minor corrections.
04
February 2014
Added items for V680S-D2KF67/-D2KF67M/-D2KF68/-D2KF68M RF Tags.
Deleted items for V680-D2KF67 RF Tags.
and made other minor corrections.
05
October 2014
Added items for V680S-D8KF67/-D8KF67M/-D8KF68/-D8KF68M RF Tags.
and made other minor corrections.
RFID System
User’s Manual
OMRON Corporation
Industrial Automation Company
Authorized Distributor:
Tokyo, JAPAN
Contact: www.ia.omron.com
Regional Headquarters
OMRON EUROPE B.V.
Wegalaan 67-69-2132 JD Hoofddorp
The Netherlands
Tel: (31)2356-81-300/Fax: (31)2356-81-388
OMRON ELECTRONICS LLC
One Commerce Drive Schaumburg,
IL 60173-5302 U.S.A.
Tel: (1) 847-843-7900/Fax: (1) 847-843-7787
OMRON ASIA PACIFIC PTE. LTD.
No. 438A Alexandra Road # 05-05/08 (Lobby 2),
Alexandra Technopark,
Singapore 119967
Tel: (65) 6835-3011/Fax: (65) 6835-2711
OMRON (CHINA) CO., LTD.
Room 2211, Bank of China Tower,
200 Yin Cheng Zhong Road,
PuDong New Area, Shanghai, 200120, China
Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200
© OMRON Corporation 2007 All Rights Reserved.
In the interest of product improvement,
specifications are subject to change without notice.
Printed in Japan
Man. No. Z271-E1-05
1014

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

advertisement