O p e r a t i n g I n s t r u c t i o n s f o r Z H R V 2 - S L C D V o l t a g e R e l a y
o Function Features
l Built-in high-performance micro controller with high reliability and strong resistance to interference. l Voltage value and fault message displayed through LCD .
l Protection against over-voltage, under-voltage, phase failure, unbalance and phase sequence is available. l Protection parameters are set through keys, and the protection function can be turned on and off freely. l True RMS value measurement, voltage measurement accuracy
≤1%. l Measurement frequency 45Hz~65Hz .
l
Three-phase voltage value query through keys .
l Testing and manual reset can be conducted through keys. l Three-phase four-wire system features N-phase failure protection.
o Model and Connotation
Unbalance delay time
Phase sequence protection
Start-reset delay time
Automatic
0.1~20s
ON-OFF
0.3~30s
ON-OFF inactivating protection function.
o Operating Instructions
0.1s
0.1s
2s
ON
0.3s
ON
Operation settings are made according to operating instructions for
ZHRV2-S/M415relay. The setting process of ZHRV2-S/M240 relay is the same with that of ZHRV2-S/M, but the displayed set values are different.
Parameter setting
Press and hold down key MD for 3 seconds to get into parameter setting interface:
Rated supply voltage code: M 240, M415
M 240:220-230-240 VAC ( three-phase four-wire system )
M 415:380-400-415 VAC ( three-phase threewire system )
LCD Display
ZHRV2 Series Voltage Relay
o Main Technical Parameters
Over-voltage
Rated supply voltage M415:AC200V~500V
Rated supply frequency
Fixed lag value
M240:AC125V~300V
50/60Hz
M415:6V
M240:5V
Phase failure, phase ≤0.2s sequence
Voltage measurement error ≤1% (the entire setting range)
Over-voltage time setting
Under-voltage setting
Time delay error
Measurement accuracy
Rated insulation voltage
±10%+0.1s
1%, true RMS value measurement
415V
Under-voltage time setting
Type and maximum rating of short-circuit protector
RT36-00 5A
Protection grade
Pollution class
Electrical life
Mechanical life
Height above sea level
Operating temperature
IP20
3
10
5
10
6
≤2000m
-5℃~40℃
Phase sequence setting
Unbalance ratio setting
Permissible relative humidity ≤50% (40℃) (without condensation)
Storage temperature -25℃~55℃, up to 70℃ within a short period of time (24h)
Contact parameters Ith:5A;AC-15:AC240V/1.5A
AC415V/0.95A
Unbalance operation time setting
Technical parameters
Over-voltage
Setting range Step Factory default
0FF-381V~500V 1V operation value 0FF-221V~300V 1V
437V
253V
Over-voltage delay time
0.1~20s 0.1s 2s
Under-voltage operation value
260V~379V-
OFF
150V~219V-
OFF
0.1~20s Under-voltage delay time
Unbalance ratio
OFF-5%~20%
1V
1V
0.1s
1%
323V
187V
2s
8%
Remarks
M415
M240
M415
M240
Start and reset time setting
Automatic reset mode setting l Press to change the set values, and long press this key to accelerate the "minus" or "plus". l When setting the parameters, the relay would automatically exit the menu if the key is not pressed for 60 consecutive seconds.
O p e r a t i n g I n s t r u c t i o n s f o r Z H R V 2 - S L C D V o l t a g e R e l a y l After over-voltage protection, under-voltage protection or unbalance protection is turned off, the menu would not display operation time setting process.
l Over-voltage and under-voltage function diagram
Over-voltage threshold value
Lag value
LCD block code
Block code interpretation
Lag value
Under-voltage threshold
L1-L2
NORMAL
L1-L2 phase, other phases switched through keys
Normal indication; this block code flashes in case of start and reset delay
Fault indication; output relay NO disconnected l Unbalance protection function diagram
FAULT
SET
U
U>
Menu setting indication
Unbalance ratio
Lag ratio
U<
Over-voltage fault indication or over-voltage parameter setting indication
Under-voltage fault indication or under-voltage parameter setting indication
PHS.SEQ
PHS.FAILS
Phase sequence fault indication or phase sequence parameter setting indication
Phase failure fault indication
ASY Unbalance fault indication or unbalance parameter setting indication
Test
Press key T/R for 0.5 second to test relay operation:
Tr: Start and reset delay time
To: Over-voltage delay time
Tu: Under-voltage delay time
Ta: Unbalance delay time
o Overall Dimensions
l This key would be valid only under normal conditions of power supply. l Other keys are invalid when testing the functions.
Three-phase voltage query
Press key MD to inquire three-phase voltage:
Example of over-voltage fault when U>the set voltage value of
450V
o Function Sequence Diagram (automatic reset mode)
l
Phase failure and sequence function diagram
Phase sequence protection
Phase failure protection
o Wiring Diagram
u Wiring diagram of a threephase three-wire system u Wiring diagram of a threephase four-wire system
Load Load