USER MANUAL

Add to my manuals
40 Pages

advertisement

USER MANUAL | Manualzz

Quick

Reference

USER MANUAL

pCO 5

GB

4472010_02 - 1405

Index

User interface (PGD1) .................................................................................................................... 4

Start-up procedure ......................................................................................................................... 5

Menu structure and navigation ..................................................................................................... 6

User operating procedures............................................................................................................ 7

Main menu ....................................................................................................................................... 8

Main menu - General monitoring ..................................................................................................................................... 8

Main menu - System monitoring ...................................................................................................................................... 9

Main menu - Circuit 1 monitoring .................................................................................................................................... 9

Main menu - Circuit 2 monitoring (visible if present) ..................................................................................................... 10

Main menu - General circuits monitoring ...................................................................................................................... 10

In / Out Menu ................................................................................................................................. 11

In / Out Menu - External temperature monitoring .......................................................................................................... 11

In / Out Menu - Fans monitoring (common or circuit 1) ................................................................................................ 11

In / Out Menu - Defrost monitoring circuit 1 / circuit 2 .................................................................................................. 12

In / Out Menu - Analogue input monitoring (1) .............................................................................................................. 13

In / Out Menu - Analogue input monitoring (2) .............................................................................................................. 13

In / Out Menu - Analogue input monitoring (3) .............................................................................................................. 13

In / Out Menu - Analogue input monitoring (4) (only on units with two circuits) ............................................................ 14

In / Out Menu - Analogue input monitoring (5) (only on units with two circuits) ............................................................ 14

In / Out Menu - Digital input monitoring (1) ................................................................................................................... 14

In / Out Menu - Digital input monitoring (2) ................................................................................................................... 15

In / Out Menu - Digital input monitoring (3) ................................................................................................................... 15

In / Out Menu - Digital input monitoring (4) ................................................................................................................... 15

In / Out Menu - Digital input monitoring (5) ................................................................................................................... 16

In / Out Menu - Digital input monitoring (6) ................................................................................................................... 16

In / Out Menu - Digital output monitoring (1) ................................................................................................................. 17

In / Out Menu - Digital output monitoring (2) ................................................................................................................. 17

In / Out Menu - Digital output monitoring (3) ................................................................................................................. 17

In / Out Menu - Digital output monitoring (4) ................................................................................................................. 18

In / Out Menu - Digital output monitoring (5) ................................................................................................................. 18

In / Out Menu - Digital output monitoring (6) ................................................................................................................. 18

ON / OFF Menu ............................................................................................................................. 19

ON / OFF Menu - Switching unit on or off...................................................................................................................... 19

SYSTEM Menu .............................................................................................................................. 19

SYSTEM Menu - Selecting the operating mode ............................................................................................................ 19

SYSTEM Menu - Setting main setpoints ........................................................................................................................ 20

SYSTEM Menu - Setting secondary setpoints ............................................................................................................... 20

SYSTEM Menu - Time-clock settings (A) and (B) ......................................................................................................... 21

SYSTEM Menu - Time-clock settings (C) and (D) ......................................................................................................... 21

SYSTEM Menu - Copy time-clock settings function ...................................................................................................... 22

SYSTEM Menu - Setting change-over based on external temperature ........................................................................ 22

SYSTEM Menu - Setting change-over based on calender ........................................................................................... 23

INSTALLER Menu (Password 0000) ............................................................................................ 23

INSTALLER Menu- Insert password to access menus .................................................................................................. 23

INSTALLER Menu- Enabling digital inputs ID3 and ID4 ................................................................................................ 24

INSTALLER Menu- Addressing BMS supervisor system .............................................................................................. 24

INSTALLER Menu- Enabling primary functions by BMS ............................................................................................... 24

INSTALLER Menu- Addressing secondary supervisor system (not opto-isolated) ....................................................... 25

INSTALLER Menu- Selecting control for water production............................................................................................ 25

INSTALLER Menu- Setting parameters for cooling control ........................................................................................... 25

INSTALLER Menu- Setting parameters for heating control ........................................................................................... 26

INSTALLER Menu- Setting ambient curve parameters for cooling ............................................................................... 26

INSTALLER Menu- Setting ambient curve parameters for heating ............................................................................... 26

INSTALLER Menu- Configuring pumps ......................................................................................................................... 27

INSTALLER Menu- Setting pump anti-freeze function .................................................................................................. 27

INSTALLER Menu- Setting fans anti-icing function ....................................................................................................... 27

INSTALLER Menu- Setting pump operation during use of anti-freeze heaters ............................................................. 28

INSTALLER Menu- Setting multi-function input ............................................................................................................. 28

INSTALLER Menu- Configuration of capacity limit from multi-function input (if enabled) ............................................. 28

INSTALLER Menu- Configuration of variable setpoint from multi-function input (if enabled) ....................................... 29

INSTALLER Menu- Configuration of variable setpoint from multi-function input (if enabled) ....................................... 29

INSTALLER Menu- Configuration of NTC signal from multi-function input (if enabled) ................................................ 29

INSTALLER Menu- Monitoring compressor hour counter circuit 1................................................................................ 29

INSTALLER Menu - Operation Silent Night Set ............................................................................................................. 30

INSTALLER Menu - Management of electrical heaters ................................................................................................. 30

INSTALLER Menu - Enabling boiler ............................................................................................................................... 30

INSTALLER Menu - Set temperature of integration and substitution ............................................................................ 30

INSTALLER Menu- Monitoring compressor hour counter circuit 2 (if present) ............................................................. 31

INSTALLER Menu- Monitoring number of compressor starts circuit 1 .......................................................................... 31

INSTALLER Menu- Monitoring number of compressor starts circuit 2 (if present) ....................................................... 31

INSTALLER Menu- Monitoring pump operating hours .................................................................................................. 31

INSTALLER Menu- Monitoring unit configurator and test info ....................................................................................... 32

INSTALLER Menu- Monitoring unit configurator and test info ....................................................................................... 32

CLOCK Menu ................................................................................................................................ 32

CLOCK Menu - Setting system date and time .............................................................................................................. 32

CLOCK Menu - Setting automatic time change (summer/winter time) ......................................................................... 33

CLOCK Menu - Setting holidays ................................................................................................................................... 33

Alarm summary table ................................................................................................................... 34

Alarm history and memory .......................................................................................................... 37

Alarm history ................................................................................................................................ 37

Quick reference ............................................................................................................................ 40

4

User interface (PGD1)

The unit control panel allow the quick setting and display of the unit’s operating parameters. The board memorises all the default settings and any modifi cations. By installing the remote control panel PGD1 it is possible to remotely replicate all the functions and the settings available on the unit. After a power failure the unit is capable of an automatic restart, retaining the original settings.

INTERFACE CONTROL KEYS:

Control keys

The user interface consists of a graphic display with six navigation keys; the display is arranged through a menu hierarchy, activated by pressing the navigation keys. The default display of these menus is the main screen. The navigation between the various parameters is by using the arrow keys located to the right of the display. These keys are also used for the modifi cation of the selected parameter.

Prg

Esc

Control keys

Key Function

Prg

ALARM key

Displays the list of active and historical alarms

(red LED on = active alarm)

MENU ACTIVATION key

• Pressing this key activates the navigation between menus

(orange LED on = winter operating mode active)

Esc

EXIT MENU key

• Pressing this key returns to the previous menu

NAVIGATION (+) key

• Pressing this key when navigating between menu/parameters passes to the next menu/parameter

• Pressing this key when modifying a parameter increases the value of the selected parameter

NAVIGATION (enter) key

• Pressing this key when navigating between menus allows entry to the selected menu

• Pressing this key when navigating between parameters allows selection of the parameter displayed to modify it

• Pressing the key when modifying a parameter confirms the modification of the parameter value selected

NAVIGATION (-) key

• Pressing this key when navigating between menu/parameters passes to the previous menu/parameter

• Pressing this key when modifying a parameter decreases the value of the selected parameter

Start-up procedure

After having powered up the unit the control board will carry out preliminary operations before being ready for use. This initial procedure takes around 60 seconds to complete. During the initial loading procedure two screens are displayed: a start-up screen and a screen to select the system language.

These screens are detailed in the table below.

WARNING: The system language can be set on the screen displayed at the startup or can be modifi ed at any time through the appropriate screen contained in the

Installer menu.

Display on the unit

Wait please

Installer

Language: ENGLISH

Pussh ENTER for change

ESC to confirm

6s A

Start-up procedure

Index

A

B

Display/Parameter

Remaining time for software loading: this value shows the remaining time to starting the software loaded on the unit, and passing the to system language selection

System language: this parameter shows the current language set for the system. To change the language follow the instructions shown on the screen.

Remaining time to select the language: this value shows the remaining time to modify the language. When the time elapses the display goes to the main screen (Main screen -

General monitoring).

WARNING: It is possible to modify the system language at any time using the appropriate screen contained in the

Installer menu. (Menu password = 0000).

B

C

Time show mask: 20

C

5

Menu structure and navigation

Both the functions to control the unit and the operating information are displayed on the unit mounted control panel.

All the functions and information are arranged in screens which in turn are grouped into menus.

During the normal operation of the unit the main screen is displayed, from which it is possible to access the selection of the other operating menus.

The menus are displayed through the rotation of the icons that they represent. Once the desired icon is selected the chosen menu is entered, permitting the display or modifi cation of the parameters that it is made up from. The procedure for navigating the menus, or changing parameters, is explained in detail in the chapter “User operating procedures”.

The adjacent drawing shows the relation between the various menus and the navigation keys used.

The operating menus are arranged as in the following drawing:

I

A

B

C

H D

!

WARNING: Improper selection of the parameters in the

Installer menu may cause malfunctions of the unit. It is recommended that these parameters are only modifi ed by personnel qualifi ed in the installation and confi guration of the unit.

G E

F

G

H

I

Index Icon

A ---

B

C

D

E

F

Menu

MAIN

IN/OUT

Menu function

The screens in this menu display the current conditions of the unit (unit status, setpoints,circuit data, etc.)

This menu contains advanced information on the unit operation

ON/OFF This menu permits the unit to be enabled or disabled, and provides information on the status

SYSTEM

RECOVERY

INSTALLER

This menu permits the selection of the operating modes, the water setpoints and the time-clock for the system

If the unit includes heat recovery, this menu permits the setting of the parameters associated with the heat recovery

This menu contains the settings useful for the installer (enabling digital inputs, BMS configuration, control, pumps, etc.)

WARNING: This menu is password protected. The password is: 0000

ASSISTANCE This menu is only accessible to qualified personnel

FACTORY This menu is only accessible to qualified personnel

CLOCK This menu contains the clock settings for the system control (date, hour, calender)

6

!

User operating procedures

To check or modify the operating parameters of the unit it is necessary to use the interface of the control panel on the unit. The basic operations that the user must be capable of, for the correct use of the unit, are:

(1) Moving from one menu to the next.

(2) Selecting and modifying a parameter.

In this manual the parameters that can be modifi ed by the user are identifi ed by the icon ( ).

1

Moving between menus

(a) To move between the menus, the order in which they are displayed is shown in the previous page, enter the menu selection mode by pressing the key (

Prg

).

2

Selecting and modifying a menu

(a) Once in the menu selected, by following the procedure (

1

), it is possible to move between the screens using the arrow keys: the key ( ) to move to the previous parameter, and the key ( ) to move to the next parameter.

previous parameter

(b) Once in the menu selection mode it is possible to move between menus using the arrow keys: the key ( ) to move to the previous menu, and the key ( ) to move to the next menu.

previous menu next menu

(c) When the desired menu is seen press the key (

)to enter the menu. Press the key(

Esc

) to return to the menu selection mode.

next parameter

(c) When the desired parameter is seen press the key ( ) to enter the parameter. To exit the parameter and return to the parameter selection mode press the key (

Esc

).

WARNING: Once a parameter is selected by pressing the key ( ), the parameter selection mode is automatically accessed and in this mode the desired parameter values can be set with the following procedure:

(1) Pressing the key ( ) causes a flashing cursor to appear on the first modifiable field of the parameter. If no modifiable fields are displayed then the cursor will not appear.

(2) Pressing the key ( ) or the key ( ), the value of the field can be increased or decreased.

(3) Pressing the key ( ) confirms the modification of the field value, saving it in memory. On the basis of the type of parameter selected the number of modifiable fields can change.

entering a menu exiting a menu entering a parameter exiting a parameter

7

8

Main menu

During normal operation the fi rst screen of the Main menu is displayed on the unit. This menu consists of several screens with different information on the operating status of the system which can be navigated using the arrow keys. In these screens the information is read only and no parameters can be changed.

WARNING: If no keys are pressed for at least 5 minutes during the use of the control panel the software automatically return to the main screen of this menu.

!

A

B

C

D

Aermec

14.3

O C

14.9

O C

C1:

1

Display on the unit

EV

I

Thu 10:59

CN

C1

MIX

C2

37%

49%

49%

WARNING: Several icons can appear in this screen to show specifi c states of the system, and the icons can be:

( LC ) low load function active

L

C2:

Main menu - General monitoring

F

G

H

E

( LT ) ) low leaving temperature anti-freeze function is active (compressors switched off)

( HT ) high leaving water temperature prevention is active (compressors switched off)

( ) anti-freeze heater active (set point: 4.0°C - differential: 1.0K)

( ) the return water temperature is dropping so new requests for cooling load are disabled

Index

A

I

B

C

D

E

F

G

H

Display/Parameter

System supply water temperature: shows the water temperature leaving the heat exchanger

System return water temperature: shows the water temperature entering the heat exchanger

Pump active: the icon appears if the unit pump operates, if the unit is supplied with a pump. The number next to the pump indicates which of the pumps is active

Compressor status circuit 1: the icon shows the current status of the compressors present in circuit 1, which can be:

• On ( )

• Off ( )

• Disabled ( )

• In alarm ( )

• Part load operation lasting 10 minutes (P)

Compressor status circuit 2: the icon shows the current status of the compressors present in circuit 2, which are the same as those available on circuit 1

Fan speed circuit 1: the value shows the percentage speed of the fans on circuit 1

Common fan speed: the value shows the percentage speed of the common fans between two circuits

Fan speed circuit 2: the value shows the percentage speed of the fans on circuit 2

System capacity demand: this element presents the system capacity demand as a bar graphic between 0 and 10

WARNING: Based on the operating mode of either heating or cooling the heat exchanger changes role. This is shown on the display of the screen by EV = evaporator, CN = condenser

Date and time: shows the current date and time

( ) the return water temperature is rising so new requests for heating load as disabled

L

( F ) the fl ow switch is open so compressors will be switched off whilst the pump attempts to enable the fl ow switch

!

C

E

G

Plant

Display on the unit

Setpoint

7.0

o C

A

Diff. 5.0

o C

Outlet Temp.:

Ep

B

Main menu - System monitoring

Index

A

Display/Parameter

Current setpoint: shows the current system setpoint

B

Operating mode: the icon shows the current operating mode of the system ( = cooling, = heating)

C Differential: shows the current system working differential

8.5

o C

9.0%

29%

D

F

H

WARNING: Several icons can appear in this screen to show specifi c states of the system, and the icons can be:

D

E

F

G

H

Control sensor: these values show the sensor on which the control is based (inlet or outlet), and the current value read by the selected sensor

Proportional error: if the Proportional + Integral function is active, this shows the proportional value

Integral error: if the Proportional + Integral function is active, this shows the integral value

Load request: shows the percentage load required by the system

Capacity output: shows the percentage output to the system

(

OFF

) time-clock is active

( M ) multi-function input is active

( LC ) low load function is active

A

B

G

Display on the unit

Circuit 1

AP: 23.1bar

-> Tc: 39.5

o C

BP: 6.4bar

-> Te: -2.6

o C

Liquid T.

Disc.Temp.:

CP1:

CP2:

0s

0s

14.8

o C

80.8

o C

Main menu - Circuit 1 monitoring

Index

A

Display/Parameter

High pressure: shows the discharge pressure of the circuit

B

C

D

E

F

H

C

D

E

F

G

H

Low pressure: shows the suction pressure of the circuit

Condensing temperature: shows the condensing temperature

Evaporating temperature: shows the evaporating temperature

Liquid temperature: shows the liquid temperature (displayed only for heat pumps models)

Discharge temperature: shows the discharge temperature

Compressor status: the icon represents the compressor status of the circuit. Each compressor is numbered with the code CP, and for each the current status is shown, being:

• On ( )

• Off ( )

Minimum residual time: the value shows how many seconds remain until minimum required On or Off time elapses for the current status of each compressor

9

10

A

B

G

Main menu - Circuit 2 monitoring (visible if present)

Display on the unit Index Display/Parameter

A High pressure: shows the discharge pressure of the circuit

B

Circuit 2

AP: 23.1bar

-> Tc: 39.5

o C

BP: 6.4bar

-> Te: -2.6

o C

T.Liquid:

Disc.Temp.:

CP1:

CP2:

0s

0s

14.8

o C

80.8

o C

E

F

H

C

D

C

D

E

F

G

H

Low pressure: shows the suction pressure of the circuit

Condensing temperature: shows the condensing temperature

Evaporating temperature: shows the evaporating temperature

Liquid temperature: shows the liquid temperature

Discharge temperature: shows the discharge temperature

(displayed only for heat pumps models or unit with total heat recovery)

Compressor status: the icon represents the compressor status of the circuit. Each compressor is numbered with the code CP, and for each the current status is shown, being:

• On ( )

• Off ( )

Minimum residual time: the value shows how many seconds remain until minimum required On or Off time elapses for the current status of each compressor

A

B

C

Display on the unit

Circuits

Total require

Circuit 1:

Circuit 2:

46%

54%

Time between starts:

Main menu - General circuits monitoring

Index Display/Parameter

100%

A

B

C

Total capacity request: shows the current value of total capacity request from the system

Capacity output of circuit 1: shows the current capacity output of the circuit to satisfy the system request

Capacity output of circuit 2: shows the current capacity output of the circuit to satisfy the system request

Residual time to next compressor: shows the remaining time before the next compressor is turned on, if required

D

0s D

In / Out Menu

Display on the unit

In / Out Menu - External temperature monitoring

Index Display/Parameter

Outdoor temp.

Today

Yester

8.2

8.2

o C

6.0

o C o C

10.2

o C

8.3

o C

A

C

E

A

B

C

D

E

External air temperature: shows the current external air temperature

External air temperature (minimum today): shows the minimum external air temperature read today

External air temperature (maximum today): shows the maximum external air temperature read today

External air temperature (minimum yesterday): shows the minimum external air temperature read yesterday

External air temperature (maximum yesterday): shows the maximum external air temperature read yesterday

B D

!

E

A Fan 1

Speed

In / Out Menu - Fans monitoring (common or circuit 1)

Display on the unit Index Display/Parameter

100% B

A

B

Circuit fans: shows which circuit the data refers to, with options of:

• Fans: shows that the fans are common to both circuits

• Fans 1: data refer to the fans of circuit 1

• Fans 2: data refers to the fans of circuit 2

Fan speed: shows the percentage speed at which the fans are operating (common, circuit 1 or circuit 2)

Set:

Diff:

1:Off.

2:Off.

G

0.0bar

0.0bar

23.1bar

22.0bar

H

C

D

F

WARNING: The information contained in this screen can be split into two screens of “Fans circuit 1” and “Fans circuit 2”. The control types can be:

• COMMON control: The fans of both circuits are controlled together, in which case there will be only one screen which summarises the data relating to the fans (as seen in the screen above).

C

D

E

F

Fan setpoint: shows the current fans setpoint

Differential on fan setpoint: shows the current differential applied on the fan setpoint

Fan status circuit 1: shows the current status of the fans, which can be:

• OFF: fans off

• PRE-VENTILATION: fans on in anticipation of compressor

• HIGH PRESSURE: control based on high pressure

• POST-VENTILATION: fans on after compressors switch off

• ANTI-ICING: fans on phase to prevent ice accumulation

• DEFROST: defrost phase

• LOW PRESSURE: control based on low pressure

• MAXIMUM SPEED: fans at maximum speed

• SILENCED: speed reduction to reduce noise levels

Fan pressure circuit 1: shows the current pressure value read

• INDIVIDUAL control: The fans of circuit 1 and circuit 2 are controlled independently, so the system will display two distinctive screens to display the data of the two circuits. In this case the two screens will be successively displayed and will contain the same type of data, except for points (E) and (G) in that (E) is displayed only in the screen

“Fans circuit 1”, whilst (G) is displayed only in the screen “Fans circuit 2”.

G

H

Fan status circuit 2: equivalent values to that of item (E) and this value is only displayed if the fans are common to the two circuits. If not, this value is not displayed but is shown in the following screen “Fans circuit 2”

Fan pressure circuit 2: shows the current pressure value read and is only displayed if the fans are common to both circuits. If not, this value is not displayed but is shown in the following screen “Fans circuit 2”.

11

12

!

A

B

C

E

In / Out Menu - Defrost monitoring circuit 1 / circuit 2

Display on the unit Index Display/Parameter

Defrost

Disabled

High outdoor temp.

Times:

LP aver: 6.4bar

DP: 0.0

Liquid.Temp.:

0s

14.8

o C

D

F

G

WARNING: in the case the unit has two circuits this screen is repeated and the heading of (A) changed to C2, and each screen will provide data for the relevant circuit.

A

B

C

D

E

F

G

Defrost circuit: shows which circuit the values refer to, if a second circuit is present, and provides a second screen for the second circuit:

• Defrost C1: data relating to circuit 1

• Defrost C2: data relating to circuit 2

Defrost information: provides status information on the defrost, which can be:

• DISABLED: defrost disabled

• BYPASS: bypass phase after the compressor start

• DECREASING CALCULATION: phase calculating the decrease of pressure

• AWAITING CYCLE INVERSION: system in pause before cycle inversion

• START DEFROST: defrost in start phase

• DEFROSTING: defrost cycle

• END DEFROST: end of the defrost cycle

• FIRST DEFROST: shows the first defrost phase after a power loss

Additional defrost information: provides additional status information on the defrost:

• HIGH EXTERNAL AIR TEMPERATURE: the external air temperature is above the level for enabling defrost

• CIRCUIT OFF: all the compressors of the circuit are off; defrost is disabled

• LP ABOVE LIMIT: the low pressure is above the level to enable defrost

• MINIMUM TIME BETWEEN DEFROST: defrost is disabled during the period of minimum time between defrosts

• START CP: compressor just started; await the bypass time before calculating the pressure decrease

• NEW LP REFERENCE: a new low pressure value has been taken as reference for the calculation of decreasing pressure;

• START FOR LP LIMIT: start of defrost to overcome the low pressure limit

• START FOR DELTA P: start of defrost to overcome the decreasing value of low pressure

• TEMP. LIQUID OK: the liquid temperature has overcome the limit to define the end of defrost

• MINIMUM DEFROST TIME: defrost continuous until the minimum time is exceeded even if the exit conditions are met

• AWAITING OTHER CIRCUIT: occurs if the fans are common to both circuits and the first circuit to finish defrost awaits the second circuit to finish

• BYPASS FIRST START: the first defrost after a power loss can only occur after the compressor has run for the determined time

• LIQUID TEMP. LOW: liquid temperature below the level that determines the end of defrost

• START FOR DGT: defrost is activated due to the level of the discharge gas temperature exceeding the limit

• FORCED: in the case the fans are common to both circuits this circuit has been forced into defrost due to defrost of the other circuit, even if not required

Defrost time: the value can indicate the maximum time before completing defrost (in the event the normal levels for completion have not been met), or the minimum defrost cycle time (in the event the “TEMP. LIQUID OK” message is displayed), to exit defrost

Low average pressure: shows the average low pressure in the last minute

Delta pressure: shows the accumulated delta pressure to determine activation of defrost

Liquid temperature: shows the liquid temperature to determine exit of the defrost cycle

Inputs pCO5

Display on the unit

In / Out Menu - Analogue input monitoring (1)

Index Display/Parameter

A

B

Analogue input U1: shows the heat exchanger inlet water temperature

Analogue input U2: shows the heat exchanger outlet temperature

Analogue input U3: shows the external air temperature

U1 = Inlet Temp.water

evap.: 14.9

o C

U2 = Output Temp.water

evap.: 18.0

o C

U3 = Ext.Temp:

17.9

o C

A

B

C

C

Display on the unit

In / Out Menu - Analogue input monitoring (2)

Index Display/Parameter

Analogue input U4: shows the discharge gas temperature of circuit 1

Inputs pCO5

A

U4 = Liquid Temp.

circuit 1: 15.3

o C

A

A

C

Inputs pCO5

Display on the unit

In / Out Menu - Analogue input monitoring (3)

Index Display/Parameter

U5 = High press.circ.1:

0.0bar

59.3

o C

U6 = Low press.circ.1:

0.0bar

-28.5

o C

B

D

A

B

C

Analogue input U5: shows the high pressure transducer value read for circuit 1

Conversion HP temperature: this is the conversion value into temperature from the pressure read by the high pressure transducer of circuit 1

Analogue input U6: shows the low pressure transducer value read for circuit 1

Conversion LP temperature: this is the conversion value into temperature from the pressure read by the low pressure transducer for circuit 1

D

13

14

In / Out Menu - Analogue input monitoring (4) (only on units with two circuits)

Display on the unit Index Display/Parameter

Analogue input U7: shows the discharge gas temperature of circuit 2

Ingressi pCO5

A

U7 = Liquid temp.

circuit 2: 15.3

o C

A

A

C

In / Out Menu - Analogue input monitoring (5) (only on units with two circuits)

Display on the unit Index Display/Parameter

Inputs pCO5

U8 = High press.circ.2:

0.0bar

59.3

o C

U9 = Low press.circ.2:

0.0bar

-28.5

o C

B

D

A

B

C

Analogue input U8: shows the high pressure transducer value read for circuit 2

Conversion HP temperature: this is the conversion value into temperature from the pressure read by the high pressure transducer of circuit 2

Analogue input U9: shows the low pressure transducer value read for circuit 2

Conversion LP temperature: this is the conversion value into temperature from the pressure read by the low pressure transducer for circuit 2

D

Display on the unit

Inputs pCO5

ID1: Flow switch

Close

ID2: High press.circ.1

Close

ID3: Fan Overload 1

Close

In / Out Menu - Digital input monitoring (1)

Index Display/Parameter

A

B

C

A

B

C

Digital input ID1: shows the binary status of the input read from the flow switch of the evaporator, which are:

• OPEN: flow switch alarm

• CLOSED: normal operation

Digital input ID2: shows the binary status of the input read from the high pressure pressostat of circuit 1, which are:

• OPEN: high pressure pressostat alarm

• CLOSED: normal operation

Digital input ID3: shows the binary status of the input relating to the circuit breaker of the fans on circuit 1, which can be:

• OPEN: circuit breaker alarm

• CLOSED: normal operation

Inputs pCO5

Display on the unit

In / Out Menu - Digital input monitoring (2)

Index Display/Parameter

ID4: All.Phase Monitor

Close

ID5: Overl.comp1 circ1

Close

ID6: Overl.comp2 circ1

Close

A

B

C

A

B

C

Digital input ID4: shows the binary status read from the input of the phase control device, which can be:

• OPEN: phase control device in alarm

• CLOSED: normal operation

Digital input ID5: shows the binary status of the input relating to the circuit breaker of compressor 1 on circuit 1, which can be:

• OPEN: circuit breaker alarm

• CLOSED: normal operation

Digital input ID6: shows the binary status of the input relating to the circuit breaker of compressor 2 on circuit 1, which can be:

• OPEN: circuit breaker alarm

• CLOSED: normal operation

Inputs pCO5

Display on the unit

In / Out Menu - Digital input monitoring (3)

Index Display/Parameter

ID7: Overl.comp2 circ1

Close

ID8: High press.circ.2

Close

ID9: Fan Overload 2

Close

A

B

C

A

B

C

Digital input ID7: shows the binary status of the input relating to the circuit breaker of compressor 3 on circuit 1, which can be:

• OPEN: circuit breaker alarm

• CLOSED: normal operation

Digital input ID8: shows the binary status of the input read from the high pressure pressostat of circuit 2 (if provided), which are:

• OPEN: high pressure pressostat in alarm

• CLOSED: normal operation

Digital input ID9: shows the binary status of the input relating to the circuit breaker of the fans on circuit 2 (if provided), which can be:

• OPEN: circuit breaker alarm

• CLOSED: normal operation

Inputs pCO5

Display on the unit

In / Out Menu - Digital input monitoring (4)

Index Display/Parameter

ID10:2nd Set enable

Open

ID11:Overl.comp1 circ2

Close

ID12:Overl.comp2 circ2

Close

A

B

C

A

B

C

Digital input ID10: shows the binary status of the input relating to the secondary setpoint function, which are:

• OPEN: secondary setpoint not active

• CLOSED: secondary setpoint active

NOTE: To control this function the installer must use the digital input ID10 and provide a volt free contact for the activation of the secondary setpoint

Digital input ID8: shows the binary status of the input relating to the circuit breaker of compressor 1 on circuit 2, which can be:

• OPEN: circuit breaker alarm

• CLOSED: normal operation

Digital input ID9: shows the binary status of the input relating to the circuit breaker of compressor 2 on circuit 2, which can be:

• OPEN: circuit breaker alarm

• CLOSED: normal operation

15

16

Inputs pCO5

Display on the unit

In / Out Menu - Digital input monitoring (5)

Index Display/Parameter

ID13:Overl.cmp.3 circ.2

Open

ID14:Overl. pump1 plant

Open

ID15:Overl. pump2 plant

Close

A

B

C

A

B

C

Digital input ID13: shows the binary status of the input relating to the circuit breaker of compressor 3 on circuit 2, which can be:

• OPEN: circuit breaker alarm

• CLOSED: normal operation

Digital input ID14: shows the binary status of the input relating to the circuit breaker of pump 1, which can be:

• OPEN: circuit breaker alarm

• CLOSED: normal operation

Digital input ID15: shows the binary status of the input relating to the circuit breaker of pump 2 (visible if present), which can be:

• OPEN: circuit breaker alarm

• CLOSED: normal operation

Display on the unit

Inputs pCO5

ID16:Remote Cool/Heat

Open

ID17:Remote On/Off

Open

ID18:Multifunct Eanble

Open

In / Out Menu - Digital input monitoring (6)

Index Display/Parameter

A

B

C

A

B

C

Digital input ID16: shows the binary status of the input relating to the change of season function, which can be:

• OPEN: remote season change not active

• CLOSED: remote season change active

NOTE: To control this function the installer must use the digital input ID16 and provide a volt free contact for the activation of the remote season changeover

Digital input ID17: shows the binary status of the input relating to the remote ON/OFF function, which can be:

• OPEN: remote ON/OFF remote not active

• CLOSED: remote ON/OFF active

NOTE: To control this function the installer must use the digital input ID17 and provide a volt free contact for the activation of the remote ON/OFF

Digital input ID18: shows the binary status of the input relating to the multi-function U10 (this function is detailed in the

Installer menu), which can be:

• OPEN: multi-function contact not enabled

• CLOSED: multi-function contact enabled

NOTE: To control this function the installer must use the digital input ID18 and provide a volt free contact for the activation of the multi-function

Output pCO5

Display on the unit

In / Out Menu - Digital output monitoring (1)

Index Display/Parameter

NO1: Pump 1

Close

NO2: Comp.1 circ.1

Close

NO3: Comp.2 circ.1

Close

A

B

C

A

B

C

Digital output NO1: shows the binary status of the output relating to pump 1, which can be:

• OPEN: pump 1 not active

• CLOSED: pump 1 active

Digital output NO2: shows the binary status of the output relating to compressor 1 of circuit 1, which can be:

• OPEN: compressor not active

• CLOSED: compressor active

Digital output NO3: shows the binary status of the output relating to compressor 2 of circuit 1, which can be:

• OPEN: compressor not active

• CLOSED: compressor active

Output pCO5

Display on the unit

In / Out Menu - Digital output monitoring (2)

Index Display/Parameter

NO4: Comp.3 circ.1

Open

NO5: VSL circuit 1

Open

NO6: VIC circuit 1

Open

A

B

C

A

B

C

Digital output NO4: shows the binary status of the output relating to compressor 3 of circuit 1, which can be:

• OPEN: compressor not active

• CLOSED: compressor active

Digital output NO5: shows the binary status of the output to the liquid solenoid valve of circuit 1, which can be:

• OPEN: valve not active

• CLOSED: valve active

Digital output NO6: shows the binary status of the output to the reversing valve of circuit 1 (in heat pump models), which can be:

• OPEN: valve not active

• CLOSED: valve active

Display on the unit

Output pCO5

NO7: Fan 1

Open

NO8: Serious alarm

Open

NO9: Comp.1 circ.2

Open

In / Out Menu - Digital output monitoring (3)

Index Display/Parameter

A

B

C

A

B

C

Digital output NO7: shows the binary status of the output to the fans of circuit 1, which can be:

• OPEN: fans not active;

• CLOSED: fans active

Digital output NO8: shows the binary status of the output generated by a serious alarm, which can be:

• OPEN: no alarm present

• CLOSED: alarm present

Digital output NO9: shows the binary status of the output relating to compressor 1 of circuit 2 (visible if present), which can be:

• OPEN: compressor not active

• CLOSED: compressor active

17

18

Output pCO5

Display on the unit

In / Out Menu - Digital output monitoring (4)

Index Display/Parameter

NO10:Comp.2 circ.2

Open

NO11:Comp.3 circ.3

Open

NO12:VSL Circuit 2

Open

A

B

C

A

B

C

Digital output NO10: shows the binary status of the output relating to compressor 2 of circuit 2 (visible if present), which can be:

• OPEN: compressor not active

• CLOSED: compressor active

Digital output NO11: shows the binary status of the output relating to compressor 3 of circuit 2 (visible if present), which can be:

• OPEN: compressor not active

• CLOSED: compressor active

Digital input NO12: shows the binary status of the output to the liquid solenoid valve of circuit 2 (visible if present), which can be:

• OPEN: valve not active

• CLOSED: valve active

Output pCO5

Display on the unit

NO13:Fan 2

NO14:VIC 2

NO15:VSBP1

In / Out Menu - Digital output monitoring (5)

Index Display/Parameter

Open

Open

Open

A

B

C

A

B

C

Digital output NO13: shows the binary status of the output to the fans of circuit 2 (visible if present), which can be:

• OPEN: fans not active

• CLOSED: fans active

Digital output NO14: shows the binary status of the output to the reversing valve of circuit 2 (visible if second circuit present in heat pump models), which can be:

• OPEN: valve not active

• CLOSED: valve active

Digital input NO15: shows the binary status of the output to the bypass solenoid valve of circuit 1 (in heat pump models), which can be:

• OPEN: valve not active

• CLOSED: valve active

Display on the unit

Output pCO5

NO16:VSBP2

Open

NO17:Antifreeze Heater

Open

NO18:Pump 2

Open

In / Out Menu - Digital output monitoring (6)

Index Display/Parameter

A

Digital output NO16: shows the binary status of the output to the bypass solenoid valve of circuit 2 (visible if second circuit present in heat pump models), which can be:

• OPEN: valve not active

• CLOSED: valve active

A

B

C

B

Digital output NO17: shows the binary status of the output to the anti-freeze heater, which can be:

• OPEN: heater not active

• CLOSED: heater active

C

Digital input NO18: shows the binary status of the output relating to pump 2 (visible if present), which can be:

• OPEN: pump 2 not active

• CLOSED: pump 2 active

ON / OFF Menu

Display on the unit

On/Off unit

Plant

Off general

General enable:

ON / OFF Menu - Switching unit on or off

Index Display/Parameter

NO

User modifiable parameters

A

B

A

B

Current status: shows the current status of the unit:

• ENABLED: unit on

• OFF GENERAL: unit in standby

• OFF FOR ALARM: unit in standby due to an alarm

• OFF BY BMS: unit in standby, disabled by the BMS

• OFF BY CLOCK: unit in standby, disabled by time-clock settings

• OFF BY DIG. IN: unit in standby, disabled by digital input

ID8

• OFF BY DISPLAY: unit in standby, disabled from the terminal

• ANTI-ICING: unit forced on to avoid icing

Switching unit on or off: by modifying this parameter it is possible to switch the unit on or off:

• YES: unit on

• NO: unit off

SYSTEM Menu

A

Plant

Display on the unit

SYSTEM Menu - Selecting the operating mode

Index Display/Parameter

Off general

Switch On:

YES

Mode selection:

HEATING

User modifiable parameters

B

C

D

A

B

C

D

Current status: shows the current status of the unit:

• ENABLED: unit on

• OFF GENERAL: unit in standby

• OFF FOR ALARM: unit in standby due to an alarm

• OFF BY BMS: unit in standby, disabled by the BMS

• OFF BY CLOCK: unit in standby, disabled by time-clock settings

• OFF BY DIG. IN: unit in standby, disabled by digital input

ID8

• OFF BY DISPLAY: unit in standby, disabled from the terminal

• ANTI-ICING: unit forced on to avoid icing

Active season: the symbol shows the current operating mode:

• ( ): heating mode

• ( ): cooling mode

Unit enabled: shows if the unit is enabled for operation, which can be:

• OFF: system not enabled for operation

• ON: system enabled for operation

• ON WITH SET2: system enabled for operation with secondary setpoint

• TIME-CLOCK: system enabled to operate under time-clock programme

Selecting the operating mode: by modifying this parameter it is possible to select the operating mode of the unit:

• COOLING: unit produces chilled water

• HEATING: unit unit produces hot water

• BY EXT. TEMP.: operating mode decided automatically by the external air temperature

• BY DIG. IN: operating mode decided by digital input ID16

(input closed = heating)

• BY SUPERV.: operating mode decided by BMS

• BY CALENDAR: operating mode decided automatically based on the season change-over date in the calender

19

20

Display on the unit

SYSTEM Menu - Setting main setpoints

Index

A

Display/Parameter

Main cooling setpoint: shows the operating setpoint used for cooling mode

Plant

Setpoint 1

Main heating setpoint: shows the operating setpoint used for heating mode

7.0

o C

45.0

o C

A

B

B

User modifiable parameters

Display on the unit

SYSTEM Menu - Setting secondary setpoints

Index Display/Parameter

A Secondary cooling setpoint: shows the secondary operating setpoint for cooling mode

Plant

Setpoint 2

Heating secondary setpoint: shows the secondary operating setpoint for heating mode

12.0

o C

40.0

o C

A

B

!

WARNING: There are two possibilities for using the secondary setpoint of the system:

• Enable the system with the secondary setpoint as an option (ON CON SET 2) in the fi rst screen of the System menu.

• Use the digital input ID10, which activates the secondary setpoint when closed.

B

User modifiable parameters

B

E

!

Display on the unit

SYSTEM Menu - Time-clock settings (A) and (B)

Index Display/Parameter

A Day to set: this shows the day for which the first two timeclock values (a) and (b) are programmed. This value can be any day of the week or a HOLIDAY day

Plant

Timezone

Day THURSDAY

ON OFF SEL

A

B

Time-clock start (a): shows the value of the start of the first time-clock a 08:00 10:00 b 11:00 12:00

ON

OFF

D

G

C Time-clock stop (a): shows the value of the stop of the first time-clock

C F

WARNING: All the screens for time-clock programming are only visible if activated in the main screen of the System menu (Enabling = TIME-CLOCK)

D

E

Action associated with time-clock (a): shows the action carried out with the first time-clock, which can be:

• ON: unit enabled with main setpoint

• SET2: unit enabled with secondary setpoint

• OFF: unit in standby

Time-clock start (b): shows the value of the start of the second time-clock

!

WARNING: The values selected for the time-clock

(a) and (b) must follow logically:

B < C < E < F

NOTE: Outside of the four possible time-clock programmes the system will remain OFF

User modifiable parameters

F Time-clock stop (b): shows the value of the stop of the second time-clock

G

Action associated with time-clock (b): shows the action carried out with the first time-clock, which can be:

• ON: unit enabled with main setpoint

• SET2: unit enabled with secondary setpoint

• OFF: unit in standby

B

E

!

Display on the unit

SYSTEM Menu - Time-clock settings (C) and (D)

Index Display/Parameter

A Day to set: this shows the day for which the last two timeclock values (c) and (d) are programmed. This value can be any day of the week or a HOLIDAY day

Plant

Timezone

Day THURSDAY

ON OFF SEL

A

B Time-clock start (c): shows the value of the start of the third time-clock c 13:00 15:00 d 16:00 20:00

ON

OFF

D

G

C

Time-clock stop (c): shows the value of the stop of the third time-clock

C F

WARNING: All the screens for time-clock programming are only visible if activated in the main screen of the System menu (Enabling = TIME-CLOCK)

D

E

Action associated with time-clock (c): shows the action carried out with the first time-clock, which can be:

• ON: unit enabled with main setpoint

• SET2: unit enabled with secondary setpoint

• OFF: unit in standby

Time-clock start (d): shows the value of the start of the fourth time-clock

!

WARNING: The values selected for the time-clock

(a) and (b) must follow logically:

B < C < E < F

NOTE: Outside of the four possible time-clock programmes the system will remain OFF

F Time-clock stop (d): shows the value of the stop of the fourth time-clock

User modifiable parameters

G

Action associated with time-clock (d): shows the action carried out with the first time-clock, which can be:

• ON: unit enabled with main setpoint

• SET2: unit enabled with secondary setpoint

• OFF: unit in standby

21

22

SYSTEM Menu - Copy time-clock settings function

Display on the unit Index Display/Parameter

A Day to copy from: shows from which day the four time-clock programmes are to be copied

Plant

Timezone

Day THURSDAY

Copy to --No

A

C

B

Day to copy to: shows to which day to copy to the selected settings. The time-clock from the reference day can be copied to an individual day of the week, to all remaining days or only for holidays

Make copy: by changing this value to requested copy from the reference day is made for the requested days

B

C

!

WARNING: All the screens for time-clock programming are only visible if activated in the main screen of the System menu (Enabling = TIME-CLOCK)

User modifiable parameters

SYSTEM Menu - Setting change-over based on external temperature

Display on the unit Index Display/Parameter

A Temperature level for cooling: shows the external air temperature value above which cooling mode is automatically activated

Cooling/Heating

Select Cool/Heat with

Outdoor temperature

Temperature level for heating: shows the external air temperature value below which heating mode is automatically activated

Set ON cooling

Set ON heating

23.0

o C

A

18.0

o C B

B

!

WARNING: This screen for automatic control based on external air temperature is only visible if activated in the main screen of the System menu (Selection mode = BY EXT. TEMP.)

User modifiable parameters

SYSTEM Menu - Setting change-over based on calender

Display on the unit Index Display/Parameter

A Date to activate heating mode: shows the date after which the change is made from cooling mode to heating mode

Cooling/Heating

Select Cool/Heat with calendar

Start Heating

Finish Heating

01/OTT

A

01/MAG B

Date to deactivate heating mode: shows the date after which the change is made from heating mode to cooling mode

B

!

WARNING: This screen for automatic control based on calender is only visible if activated in the main screen of the System menu (Selection mode = BY CALENDAR)

User modifiable parameters

INSTALLER Menu

(Password 0000)

INSTALLER Menu- Insert password to access menus

Display on the unit Index Display/Parameter

Access password to menus: the password to be used to access the Installer menus is the default value (0000)

Insert password

A

0000 A

User modifiable parameters

23

24

INSTALLER Menu- Enabling digital inputs ID3 and ID4

Display on the unit Index Display/Parameter

Enabling ID17: shows if the digital input ID3 is enabled for the remote ON/OFF control function (ON = closed, OFF = open)

Input enable

ID17:On/Off plant: N

A

A

User modifiable parameters

INSTALLER Menu- Addressing BMS supervisor system

Display on the unit Index Display/Parameter

Insatller

Supervisor BMS1

Protocol:

BaudRate:

Serial address:

MODBUS

A

19200 baud

B

1 C

A

B

Select protocol: shows which protocol is used to communicate with the BMS, with the supported protocols being:

• MODBUS: protocol Modbus/RS485

• CAREL: protocol by expansion

• pCOWEB: protocol by expansion pCOWEB

• LON: protocoll by expansion LON

Transmission speed: shows the speed of the serial communication

C

Address: shows the address assigned to which communication will be made with the BMS supervisor

User modifiable parameters

INSTALLER Menu- Enabling primary functions by BMS

Display on the unit Index Display/Parameter

A Enable change-over by BMS: shows if the remote changeover by the BMS is enabled

Installer

Supervisor:

Enable cooling/heating by supervisor: YES

Enable On-Off unit by supervisor: YES

A

B

B

Enable ON/OFF by BMS: shows if the remote starting and stopping of the unit by the BMS is enabled

User modifiable parameters

INSTALLER Menu- Addressing secondary supervisor system (not opto-isolated)

Display on the unit Index Display/Parameter

Installer

Address: shows the value of the address for the secondary supervisor system for communications (this serial interface is not opto-isolated so the connection distance permitted is less than the main serial interface)

AerWeb300 BMS2

Address: 1

A

A

NOTE: The use of the second serial link is intended for transmission via the web (AerWeb300), although the serial link can be to a second supervisor system in addition to the main one (BMS1)

User modifiable parameters

INSTALLER Menu- Selecting control for water production

Display on the unit Index Display/Parameter

Installer

Regolation temperature sensor with:

OUTPUT (U2)

A

A

Control sensor: shows which sensor the system bases the control of water produced, which can be:

• OUTLET(U2): the sensor used to control the production of water is that leaving the heat exchanger

• INLET(U1): the sensor used to control the production of water is that entering the heat exchanger

• COMMON OUTLET SENSOR (U3 uPC): the sensor used to control the production of water is the common leaving sensor in the event there are two heat exchangers

Type reg.:

Integ.Time(Ki)

PROP + INT.

600s

B

C

WARNING: Selecting the control based on the entering temperature means that the correct setting for the operating setpoints must consider the addition or subtraction (based on cooling or heating mode) of the differential temperature to the operating setpoint

User modifiable parameters

B

C

Type of control: shows the logic used for the control, which can be:

• PROP+INT: applies proportional and integral control

• PROP: applies proportional control only

Integral time: shows the integral time to add to the proportional control (in the event the type of control selection is proportional and integral)

INSTALLER Menu- Setting parameters for cooling control

Display on the unit Index Display/Parameter

Installer

Cooling regolation

SETPOINT FIXED

Differential: 5.0

o C

A

B

A

Type of setpoint: shows what type of logic is used for the control of the operating setpoint, which can be:

• FIXED SETPOINT: the system will use as the operating setpoint the values set by the user in the System menu screen

(main and secondary setpoints)

• AMBIENT CURVE: the operating setpoint is calculated automatically based on the selected ambient curve

Differential: shows the differential applied between the water inlet and outlet, where such value depends on the flow rate the system operates at

B

User modifiable parameters

25

26

INSTALLER Menu- Setting parameters for heating control

Display on the unit Index Display/Parameter

Installer

Heating regolation

SETPOINT FIXED

Differential: 3.0

o C

A

B

A

Type of setpoint: shows what type of logic is used for the control of the operating setpoint, which can be:

• FIXED SETPOINT: the system will use as the operating setpoint the values set by the user in the System menu screen

(main and secondary setpoints)

• AMBIENT CURVE: the operating setpoint is calculated automatically based on the selected ambient curve

Differential: shows the differential applied between the water inlet and outlet, where such value depends on the flow rate the system operates at

B

User modifiable parameters

INSTALLER Menu- Setting ambient curve parameters for cooling

Display on the unit Index Display/Parameter

A Actual setpoint: shows the current setpoint from the ambient curve

Installer

Setpoint cool

Actual: 12.0

o C A

B Maximum differential on setpoint compensation: shows the maximum change to apply to the original setpoint, when reaching the external temperature specified at point (C)

Compens.

max.

5.0

o C

SET

25.0

o C

B C

T.Ext

35.0

o C

D

C

D

Minimum external air temperature limit: shows the external air temperature at which the maximum differential as specified at point (B) will be applied to the original setpoint

Maximum external air temperature limit: shows the external air temperature at which the original setpoint is applied.

Below this temperature the setpoint is proportionally increased up to the value specified in point (C), where the setpoint will be compensated by the maximum differential specified in point (B)

User modifiable parameters

INSTALLER Menu- Setting ambient curve parameters for heating

Display on the unit Index Display/Parameter

A Actual setpoint: shows the current setpoint from the ambient curve

Installer

Setpoint heat

Actual:

SET

45.0

o C

A

B

Maximum differential on setpoint compensation: shows the maximum change to apply to the original setpoint, when reaching the external temperature specified at point (D)

Compens.

max.

5.0

o C

00.0

o C

B C

T.Ext

10.0

o C

D

C

D

Minimum external air temperature limit: shows the external air temperature at which the original setpoint is applied.

Above this temperature the setpoint is proportionally decreased up to the value specified in point (D), where the setpoint will be compensated by the maximum differential specified in point (B)

Maximum external air temperature limit: shows the external air temperature at which the maximum differential as specified at point (B) will be applied to the original setpoint

User modifiable parameters

Display on the unit

Installer

Numbers of pumps:

Idle time:

INSTALLER Menu- Configuring pumps

Index

A

Display/Parameter

Number of pumps: shows the number of pumps controlled by the unit

WARNING: Modifying this parameter could result in the pumps installed on the unit not being operated

2

A

8h B

Inactivity time: shows the inactivity time for one pump after which it will be activated (in the event that there are several pumps avoids that they stand still for an excessive time)

B

User modifiable parameters

INSTALLER Menu- Setting pump anti-freeze function

Display on the unit Index Display/Parameter

A Enabling anti-freeze function: shows whether to enable the anti-freeze cycle function which activates the pump

Installer

Pump start cicles

Enable N

Circle time:

Pulse time:

30min

2min

Min.Extern.Air Temp.:

5.0

o C

A

B

C

D

B

C

Time cycle: shows the time interval between pump activations

Pump activation time: shows the time period that the pump will be activated for the anti-freeze function

User modifiable parameters

D External air temperature limit: shows the temperature below which the anti-freeze cycle is activated (if enabled)

Display on the unit

INSTALLER Menu- Setting fans anti-icing function

Index Display/Parameter

A Enabling anti-icing function: shows whether to enable the anti-icing function for the fans

Fan

Fan antifreezer/snow function enable:

Ext.Air temp.:

Pulse time off:

Pulse time on:

YES

1.0

o C

120min

C

30s D

A

B

B

C

External air temperature limit: shows the temperature below which the anti-icing cycle is activated (if enabled)

Time off: shows the time interval between the periods of activation for the fans during the anti-icing function

User modifiable parameters

D

Fan activation time: shows the time period that the fans will be activated for the anti-icing function

27

28

INSTALLER Menu- Setting pump operation during use of anti-freeze heaters

Display on the unit Index Display/Parameter

Pump enable: shows whether the pump is activated during the operation of the electric anti-freeze heaters

Installer

Antifreeze Heater

Force ON pumps: YES

A

A

User modifiable parameters

Installer

Multifunction Input

Config. Input (U10)

VARIABLE SETPOINT

Type:

Display on the unit

0-10V

INSTALLER Menu- Setting multi-function input

Index Display/Parameter

A

B

A

Multi-function input: shows which function is assigned to the multi-function input U10, which can be:

• NOT PRESENT: multi-function input disabled

• CAPACITY LIMIT: the input U10 is used to limit the capacity of the unit in a manner proportional to the signal applied at the input U10 (the configuration of the capacity range controlled is available in the next screen, if this option is activated)

• VARIABLE SETPOINT: the input U10 is used to vary the operating setpoint in a manner proportional to the signal applied at the input U10 (the configuration of the variation to the setpoint range is available in the next screen, if this option is activated)

User modifiable parameters

B

WARNING: If the multi-function input is enabled then the status of the input to U10 will shown in the In/Out menu

Type: shows the type of signal used for the multi-function input, which can be:

• 0-10V: input signal 0-10V

• NTC: input signal NTC

• 4-20mA: input signal 4-20mA

INSTALLER Menu- Configuration of capacity limit from multi-function input (if enabled)

Display on the unit Index Display/Parameter

A Minimum capacity limit: shows the minimum capacity limit as a function of the input signal

Installer

Input Multifunction

Power limit:

Maximum capacity limit: shows the maximum capacity limit as a function of the input signal

Minimun limit:

Maximum limit:

0% A

100%

B B

User modifiable parameters

Installer

A

B

Min: 7.0

C

Max: 11.0

o C

Min: 45.0

C

Max: 50.0

o C

C

D

Minimum cooling setpoint: shows the minimum setpoint as a function of the input signal (on input U10)

Maximum heating setpoint: shows the maximum setpoint as a function of the input signal (on input U10)

Minimum heating setpoint: shows the minimum setpoint as a function of the input signal (on input U10)

Maximum heating setpoint: shows the maximum setpoint as a function of the input signal (on input U10)

INSTALLER Menu- Configuration of NTC signal from multi-function input (if enabled)

Display on the unit Index Display/Parameter

A Minimum NTC signal: Shows the minimum temperature which corresponds to the to the minimum value for the function selected to the multi-function input (capacity limitation or variable setpoint)

Installer

Input Multifunction

Config. NTC

Maximum NTC signal: Shows the maximum temperature which corresponds to the to the maximum value for the function selected to the multi-function input (capacity limitation or variable setpoint)

Minimun temp.:

Maximun temp.:

7.0

o C

11.0

o C

A

B

B

User modifiable parameters

INSTALLER Menu- Monitoring compressor hour counter circuit 1

Display on the unit Index Display/Parameter

A

Compressor 1 hour counter: shows the number of running hours for compressor 1 on circuit 1

Hour meter

Circuit 1

Compressor 1:

Compressor 2:

Compressor 3:

0000h

0000h

---h

A

B

C

B

C

Compressor 2 hour counter: shows the number of running hours for compressor 2 on circuit 1 (if present)

Compressor 3 hour counter: shows the number of running hours for compressor 3 on circuit 1 (if present)

29

Fan

Display on the unit

INSTALLER Menu - Operation Silent Night Set

Index Display/Parameter

Control Silent night:

A Enable Silent Night operation: This value indicates whether to enable night mode, this function enables operation muted during the time period specified in the following parameters

Control ON:

Control OFF:

NO

21:00

8:00

A

B

C

B

C

Start time slot night mode function: if the operation is muted nocturnal active, this parameter indicates the time after which this function will be activated

End time slot night mode function: if the operation is muted nocturnal active, this parameter indicates the time after which this function will be disabled

User modifiable parameters

INSTALLER Menu - Management of electrical heaters

Display on the unit Index Display/Parameter

A Number electrical resistors installed: Indicates this value if the number of electric heaters installed (minimum zero, maximum three)

Installer

Additional resistances number:

Power resistance:

0

A Percentage of the power system: This value specifies the percentage power of the individual resistance compared to the total power of the unit;

10%

B B

User modifiable parameters

WARNING: In order to allow proper management of electrical resistances in the system, all resistors must have the same power, also please note that the maximum power of the single resistor, managed by the system is equivalent to

50% of the rated power of the unit

Display on the unit

Installer

Boiler replacement enabled:

INSTALLER Menu - Enabling boiler

Index Display/Parameter

Enable boiler replacement: This parameter specifies whether to enable the boiler when the outside temperature falls below the value of “replacement” specified in the next window, or in the case where the heat pump is in “full alarm”

NO

A

A

30

User modifiable parameters

INSTALLER Menu - Set temperature of integration and substitution

Display on the unit Index Display/Parameter

Installer

Air temp integration

5.0

o C

Air temp replacement

-5.0

o C

A

B

A

B

Temperature integration: this value indicates the outdoor temperature above which the heat pump function without the aid of electrical resistors, while if the outside temperature is lower than this value, but still higher than all atemperatura replacement, the heat pump operates TOGETHER resistances

Temperature integration: this value indicates the outdoor temperature above which the heat pump function without the aid of electrical resistors, while if the outside temperature is lower than this value, but still higher than all atemperatura replacement, the heat pump operates TOGETHER resistances.

User modifiable parameters

INSTALLER Menu- Monitoring compressor hour counter circuit 2 (if present)

Display on the unit Index Display/Parameter

A

Compressor 1 hour counter: shows the number of running hours for compressor 1 on circuit 2

Hour meter

Circuit 2

Compressor 1:

Compressor 2:

Compressor 3:

0000h

0000h

---h

A

B

C

B

C

Compressor 2 hour counter: shows the number of running hours for compressor 2 on circuit 2 (if present)

Compressor 3 hour counter: shows the number of running hours for compressor 3 on circuit 2 (if present)

INSTALLER Menu- Monitoring number of compressor starts circuit 1

Display on the unit Index Display/Parameter

A

Compressor 1 number of starts: shows the number of starts for compressor 1 on circuit 1

Hour meter

Circuit 1

Numbers of starts

Compressor 1:

Compressor 2:

Compressor 3:

0000

0000

---

A

B

C

B

C

Compressor 2 number of starts: shows the number of starts for compressor 2 on circuit 1

Compressor 3 number of starts: shows the number of starts for compressor 3 on circuit 1

INSTALLER Menu- Monitoring number of compressor starts circuit 2 (if present)

Display on the unit Index Display/Parameter

A

Compressor 1 number of starts: shows the number of starts for compressor 1 on circuit 2

Hour meter

Circuit 2

Numbers of starts

Compressor 1:

Compressor 2:

Compressor 3:

0000

0000

---

A

B

C

B

C

Compressor 2 number of starts: shows the number of starts for compressor 1 on circuit 2

Compressor 3 number of starts: shows the number of starts for compressor 3 on circuit 2

INSTALLER Menu- Monitoring pump operating hours

Display on the unit Index Display/Parameter

A

Pump 1 hour counter: shows the number of running hours for pump 1

Hour meter

Pump 2 hour counter: shows the number of running hours for pump 2 (if present)

Pump 1:

Pump 2:

0000h

0000h

A

B

B

31

32

B

INSTALLER Menu- Monitoring unit configurator and test info

Display on the unit Index Display/Parameter

Installer

Aermec S.p.A.

Code:

NRL1400 ooooooo 00

A

A

B

C

D

Configuration code: shows the commercial code which identifies the unit and configuration

Software version: shows the software version installed on the unit

Software version date: shows the date of the software installed on the unit

Test time: shows the time the unit was tested in the factory

Ver.: 0.0.1

Testing date:

10:23

12/03/13

13/06/13

C

E

E

Test date: shows the date the unit was tested in the factory

D

INSTALLER Menu- Monitoring unit configurator and test info

Display on the unit Index Display/Parameter

System language: shows the system language in use, which can be modified by following the instructions on the screen

(ENTER to modify the language)

Installer

Language: ENGLISH

A

Push ENTER for change

A

CLOCK Menu

Display on the unit

CLOCK Menu - Setting system date and time

Index Display/Parameter

A System day: shows the day of the system

Clock

Day: Thursday

13 JULY 2013 Date:

Hour: 14:49

A B

User modifiable parameters

D

C

B System month: shows the month of the system

C System year: shows the year of the system

D System clock: shows the time of the system

B

D

CLOCK Menu - Setting automatic time change (summer/winter time)

Display on the unit Index Display/Parameter

A Enable automatic control: shows if the time change between summer and winter time is carried out automatically

Clock

Automatic change

Hour solar/legal: YES

A

B Time change week: shows which week of the month that the time change is made

Start: in: MARCH

End: in: OCTOBER

F G

LAST SUNDAY at: 02.00

LAST SUNDAY at: 03.00

H I

C

E C

D

Time change day: shows which day of the week that the time change is made

Time change month: shows which month the time change is made

User modifiable parameters

E Time change hour: shows what hour that the time change is made

F Return time change week: shows which week of the month that the return time change is made

G

Return time change day: shows which day of the week that the return time change is made

H Return time change month: shows which month the return time change is made

I Return time change hour: shows what hour that the return time change is made

A

Display on the unit

Calendar

Start End

25/Dic 26/Dic

06/Gen 07/Gen

02/Dic 03/Giu

---

---

---

---

Action

Hol.

Hol.

Off

---

---

B

CLOCK Menu - Setting holidays

Index

A

Display/Parameter

Start date: shows the date of the start of the holiday. The calender can control a maximum of 5 days defined as hlidays, during which time specific actions are carried out

C

B

C

End date: shows the date of the end of the holiday. The calender can control a maximum of 5 days defined as holidays, during which time specific actions are carried out

Action to associate with holiday: shows which action the unit will take during the holiday, which may be:

• OFF: unit will be off during the days selected

• FEST.: unit will be controlled as specified in the time-clock programme called HOLIDAY (for further information refer to the function of the time-clock)

• --- : if no action is specified the unit will be controlled by the manual settings

User modifiable parameters

33

Alarm summary table

The unit provides a display of the possible faults, announced by the fl ashing of the alarm key with the bell symbol located on the left of the display. Pressing the bell key displays the alarm. The reset of the alarm can be automatic, manual or semi-automatic on the basis of the type and severity of the alarm.

To reset the alarm message it is necessary to press the bell key again, but this does not reset the cause of the alarm, but only acknowledges it.

The following table lists the faults that can be generated by the unit and a brief explanation of the possible cause.

Alarm reset types:

Manual reset:

Unit is reset manually by removing and re-applying power.

Automatic reset:

The unit is reset automatically

Semi-automatic reset:

The unit is reset semi-automatically if the alarm is repeated a maximum of three times consecutively, and after a further alarm requires manual reset.

34

AL11

AL12

AL13

AL14

AL15

AL16

AL06

AL07

AL08

AL09

AL10

AL01

AL02

AL03

AL04

AL05

ALARM summary table

Clock battery faulty or not connected

Expansion memory damaged

Phase monitor

---

High pressure sensor circuit 1 faulty or not connected

High pressure sensor circuit 2 faulty or not connected

Low pressure sensor circuit 1 faulty or not connected

Low pressure sensor circuit 2 faulty or not connected

Inlet water temp sensor evap.1 faulty or not connected

Outlet water temp sensor evap.1 faulty or not connected

Outlet water temp sensor evap.com. faulty or not connected

Inlet water temp sensor recovery faulty or not connected

Outlet water temp sensor recovery1 faulty or not connected

Outlet water temp sensor recovery2 faulty or not connected

Outlet water temp sensor recovery common faulty or not connected

External temperature sensor faulty or not connected

Reset

---

Note

---

---

---

---

Analogue input U5

Analogue input U8

Analogue input U6

Analogue input U9

Analogue input U1

Analogue input U2

---

---

---

---

---

---

AL60

AL61

AL62

AL63

AL65

AL48

AL49

AL50

AL59

AL43

AL44

AL45

AL45

AL39

AL40

AL41

AL42

AL29

AL31

AL32

AL33

AL34

AL35

AL38

AL25

AL26

AL27

AL28

AL17

AL18

AL23

AL24

Liquid temperature sensor circuit 1 faulty or not connected

Liquid temperature sensor circuit 2 faulty or not connected

Circuit breaker compressor 1 circuit 1

Thermal alarm system pump 1

Thermal alarm system pump 2

Thermal alarm heat recovery pump 1

Thermal alarm heat recovery pump 2

Fans circuit breaker circuit 1

Fans circuit breaker circuit 2

Low pressure sensor circuit 1

High pressure pressostat circuit 1

High pressure sensor circuit 1

Circuit 1 low pressure sensor (serious)

Circuit 2 low pressure sensor (serious)

Loss of evaporator water flow

Loss of heat recovery water flow

Anti-freeze alarm system inlet/outlet temperature

Anti-freeze alarm system common outlet temperature

Anti-freeze alarm heat recovery 1 inlet/outlet temperature

Anti-freeze alarm heat recovery 2 outlet temperature

Anti-freeze alarm heat recovery common outlet temperature

Expansion IO (uPC) Off-line

Expansion IO (pCOe) Off-line

Discharge gas temperature sensor circuit 1 faulty or not connected

Discharge gas temperature sensor circuit 2 faulty or not connected

Board re-start from lost power

Circuit breaker compressor 2 circuit 1

Circuit breaker compressor 3 circuit 1

Circuit breaker compressor 1 circuit 2

Circuit breaker compressor 2 circuit 2

Circuit breaker compressor 3 circuit 2

Low pressure sensor circuit 2

---

---

Not an alarm

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

35

36

AL66

AL67

AL75

AL76

AL84

AL85

High pressure pressostat circuit 2

High pressure sensor circuit 2

High discharge gas temperature circuit 1

High discharge gas temperature circuit 2

High heat recovery inlet temperature alarm

High system inlet temperature alarm

---

---

---

---

---

---

Alarm history

Each time an alarm is generated it is saved in the “alarm history” memory.

This memory contains the last 100 alarms recorded. For each alarm saved the inlet and outlet water temperatures are also recorded, so that the service personnel can have a clear picture of the unit at the time the alarm occurred.

To access the alarm history:

(a) Press the key ( ) and enter the alarm display.

(b) If any are present, go through the active alarms with the key ( ) and reach the icon that gives access to the alarm history.

(3) Press the key ( ) to enter the alarm history.

(4) To exit the alarm history press the key (

Prg

) or the key (

Esc

).

G

H

L

I

Display on the unit

Allarm

Phase monitor

Active alarms: 05

Allarms

C

AL01

Push key ENTER to go HISTORY alarm

Alarm history and memory

A

B

Index

A

C

D

G

H

I

B

E

F

L

Display/Parameter

Code of active alarm: shows the code for the active alarm currently displayed

Description of active alarm: shows the description of the active alarm currently displayed

Total number of active alarms: shows the total number of active alarms. Active alarms are announced by a red light on the bell labelled key

Alarm history - Alarm time: shows the time of the alarm occurring

Alarm history - Alarm date: shows the date of the alarm occurring

Alarm history - Alarm index: shows the index of alarm (maximum 100) in the alarm history

Alarm history - Alarm code: shows the identifying code of thee alarm

Alarm history - Alarm description: shows the description of the alarm

Alarm history - Temperature IN: shows the water inlet temperature at the time the alarm occurred

Alarm history - Temperature OUT: shows the outlet water temperature at the time the alarm occurred

D E F

7:45

AL10

14/06/13 N o 035

Temp.Outlet.Evap.

broken or disconnected

In: 24.0

o C

Out: 19.0

o C M

M

Alarm history - Refrigerant circuit pressure info: pressing the enter key during the display of the alarm history the water temperature data is replaced by the high (HP) and low (LP) pressure values measured on the refrigerant circuit at the time the alarm occurred

Note: further pressing of the enter key alternates between the water temperatures and the circuit refrigerant pressures

!

THE ALARM HISTORY CANNOT BE CANCELLED and having a limit of 100 alarm histories, any additional new alarms after the index value 99 will incrementally start with the index value 00 and overwrite the old data.

37

Quick reference

!

WARNING: This table refers to the specifi c pages only for the basic operation of the unit and for further information refer to the index of the manual.

Function

Switching the unit on or off

Season settings

(HEAT / COOL)

Setting the water production setpoints

Programming time-clock

Page

19

19

20

21

I dati tecnici riportati nella presente documentazione non sono impegnativi.

AERMEC S.p.A. si riserva la facoltà di apportare in qualsiasi momento tutte le modifiche ritenute necessarie per il miglioramento del prodotto.

Les données mentionnées dans ce manuel ne constituent aucun engagement de notre part.

Aermec S.p.A. se réserve le droit de modifier à tous moments les données considérées nécessaires à l’amelioration du produit.

Technical data shown in this booklet are not binding.

Aermec S.p.A. shall have the right to introduce at any time whatever modifications deemed necessary to the improvement of the product.

Im Sinne des technischen Fortsschrittes behält sich

Aermec S.p.A. vor, in der Produktion Änderungen und Verbesserungen ohne Ankündigung durchzuführen.

Los datos técnicos indicados en la presente documentación no son vinculantes.

Aermec S.p.A. se reserva el derecho de realizar en cualquier momento las modificaciones que estime necesarias para mejorar el producto.

AERMEC S.p.A.

I-37040 Bevilacqua (VR) - Italy

Via Roma, 996 - Tel. (+39) 0442 633111

Telefax (+39) 0442 93730 - (+39) 0442 93566 www.aermec.com - [email protected]

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement

Table of contents