Transmission speed

Storage

Operation

Noise immunity

Vibration/shock resistance

9,600/115,200 bps (ES/EX/SS supports 9,600 bps only)

-25°C ~ 70°C (temperature), 5 ~ 95% (humidity)

0°C ~ 55°C (temperature), 5 ~ 95% (humidity), pollution degree 2

ESD: ±4kV Air Discharge CS: 0.15MHz ~ 80MHz, 10V/m

EFT: Power Line: 2kV Surge : ±1kV

International standard: IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27

(TEST Ea)

Functions

Read and Write

Step

1

2

3

4

RD (PLC → DVPPCC01) WR (DVPPCC01 → PLC)

Set the RD/WR switch to “RD”.

Set the RD/WR switch to “WR” and check if the PLC is in STOP status.

Insert DVPPCC01 to the COM port on the PLC and wait for 5 seconds.

Insert DVPPCC01 into the COM port on the PLC and wait for 5 seconds.

After the reading is completed, “OK” LED will be On. After the writing is completed, “OK” LED will be On.

Remove DVPPCC01 from the PLC. Remove DVPPCC01 from the PLC.

Password/PLC ID/Subroutine Password Protection

When DVPPCC01 is to write the data into a PLC, and the PLC is already locked by a password/PLC ID,

DVPPCC01 will compare the password key in it with the password/PLC ID in the PLC for verification. The data can be written into the PLC only under the successful verification.

How to set a password key in DVPPCC01

1. Write the password key to be set in DVPPCC01 into D1086 and D1087 of the PLC by ISPSoft or WPLSoft.

Set M1086 in the PLC to On.

2. Switch DVPPCC01 to RD and plug the communication port of DVPPCC01 into the COM port of the PLC.

DVPPCC01 then starts to read the program and parameters in the PLC.

3. After the reading is completed, DVPPCC01 will check whether M1086 in the PLC is On. If so, DVPPCC01 will read the values in D1086 and D1087 and the values will be regarded as the password key. After that,

“OK” LED on DVPPCC01 will be On, indicating that all the reading has been completed. Next, remove

DVPPCC01 from the PLC.

The password key consists of 4 digits; each digit represents an 8-bit value and corresponds to an ASCII code

(only visible words are acceptable). D1086 and D1087 store the 4-digit password key. See the password format example (entering password 1234 by WPLSoft) below.

Password key D1086 D1087

Password setting

ASCII code (Hex)

High byte

1 st digit

1 (H31)

Low byte

2 nd digit

2 (H32)

High byte

3 rd digit

3 (H33)

Low byte

4 th digit

4 (H34)

How to set a PLC ID key in DVPPCC01 (if the PLC supports a PLC ID)

1. Write the password key to be set in DVPPCC01 into D1996 ~ D1999 of the PLC by ISPSoft or WPLSoft.

Record the length of PLC ID in D1995.

2. Set the PLC ID in the PLC MPU. The value of the ID should be the same as the PLC ID given in

DVPPCC01.

3. Switch DVPPCC01 to RD and plug the communication port of DVPPCC01 into the COM port of the PLC.

DVPPCC01 then starts to read the program and parameters in the PLC.

4. During the reading, DVPPCC01 will check whether the PLC has a PLC ID. If so, DVPPCC01 will read the values in D1995 ~ D1999 and regard them as the PLC ID set in DVPPCC01. After that, “OK” LED on

DVPPCC01 will be On, indicating that all the reading has been completed. Next, remove DVPPCC01 from the PLC.

The PLC ID key consists of 4 ~ 8 digits; each digit represents an 8-bit value and corresponds to an ASCII code

(only visible words are acceptable). D1995 ~ D1999 store the 4-to-8 digit PLC ID key. See the ID format example (entering password 12345678 by WPLSoft) below.

Entering D1995 = K8:

PLC

ID setting

ASCII code (Hex)

D1997 D1998 D1999

High byte Low byte High byte Low byte High byte Low byte High byte Low byte

1 st digit

1 (H31)

2 nd digit

2 (H33)

3 rd digit

3 (H33)

4 th digit

4 (H34)

5 th digit

5 (H35)

6 th digit

6 (H36)

7 th digit

7 (H37)

8 th digit

8 (H38)

DVPPCC01 reads the subroutine password together with the PLC program. If the subroutine password has been set in the PLC, the password will be read out to PCC01 and become the subroutine password of

On, and write a value in D1088 ( D1088>0).

3. Switch DVPPCC01 to the RD mode and plug the COM port of DVPPCC01 into the COM port of the

PLC.

4. After the reading is completed, the OK LED on DVPPCC01 will be constantly On, indicating the reading has been completed. Next, remove DVPPCC01 from the PLC.

5. After the function of limiting the number of times that the data is written into the PLC is enabled, the ERR

LED on DVPPCC01 will flash if the number of times that the data can be written into the PLC is reached.

Maximum Time for Read/Write

DVP series Time for read/write

ES/EX/EC/SS

38 seconds ~

48 seconds

DVP series

EH/SV/EH2-L/EH2

Time for read/write

20 seconds ~

43 seconds

SA/SX/SC/SS2

13 seconds ~

21 seconds

ES2/EX2/SX2/SA2

19 seconds ~

2 minutes 8 seconds

The time for read/write is only for reference. It varies with the size of the data.

DVP series

SX V3.0 (and above)

EH3/EH3-L/SV2

Time for read/write

19 seconds ~

1 minute 3 seconds

29 seconds ~

1 minute 32 seconds

Error Messages

When DVPPCC01 completes reading the data in the PLC, it will record the model type of the PLC as well. If the capacity of the program to be written into the PLC is different from what has been recorded in DVPPCC01,

DVPPCC01 will not write the program into the PLC, and the ERR LED will start to flash. See the table below for other error messages.

Error message

Indicator

ERR OK

Cause & Suggestion

Internal memory error; connection failure

The hardware of DVPPCC01 malfunctions. Please change it.

Incorrect PLC model

Inconsistent password/PLC ID

ERASE is completed

Flashes

On

Off

Off

Flashes

On

1. Make sure the program in DVPPCC01 is compatible with the connected

PLC model.

2. Data in a DVP10SX series PLC whose firmware version is above 3.00 can not be copied into a DVP10SX series PLC whose firmware version is below

3.00.

1. DVPPCC01 is protected by the password/PLC ID. Please unlock the password/PLC ID, or make the PLC have the same password/PLC ID as

DVPPCC01.

2. The PLC is protected by the password/PLC ID. Please unlock the password/PLC ID, or make DVPPCC01 have the same password/PLC ID as the PLC.

1. Press ERASE button on DVPPCC01 to erase the memory in DVPPCC01.

After this, OK LED will be constantly On.

2. To conduct RD/WR function again in DVPPCC01, re-power the PLC or remove DVPPCC01 and plug it into the PLC again.

The number of times the data can be written into the PLC is reached.

Flashes ON

The number of times the data can be written into the PLC has been reached.

Please switch DVPPCC01 to the RD mode to read the program again.

Operational error; unable to write

Operational error; unable to read

Flash at the same time

Flash alternately

1. DVPPCC01 has no data in it, but still executes the writing. Make sure there is program inside DVPPCC01 and check the operation mode (RD/WR) of

DVPPCC01. Set the PLC to STOP.

2. The communication formats in DVPPCC01 and the PLC are incompatible.

Set the PLC to STOP and re-power it. Make sure the communication format of the PLC is ASCII 9,600, 7, E, 1.

3. The program in DVPPCC01 is illegal. Make sure the program is correct.

4. DVPPCC01 is locked by the PLC ID/subroutine password, but the firmware of the PLC does not support the PLC ID/subroutine password. Please update the PLC firmware or unlock the PLC ID/subroutine password in

DVPPCC01.

1. The PLC is protected by the password/PLC ID. Please unlock the password/PLC ID, or set DVPPCC01 to have the same password/PLC ID as does the PLC.

2. The communication formats in DVPPCC01 and the PLC are incompatible.

Set the PLC to STOP and re-power it. Make sure the communication format of the PLC is ASCII 9,600, 7, E, 1.

注意事項

繁體中文

欲進行資料傳輸前,請預先設定所要使用的模式( RD 或 WR),再插入 PLC 主機 COM 通訊口。

DVPPCC01 讀取 PLC 資料時,在未完成資料傳輸前,請勿中途斷電或拔除 DVPPCC01,以免造成 DVPPCC01

資料遺失。

在 DVPPCC01 傳送接收過程中,改變 DVPPCC01 工作模式(RD 或 WR)並無作用。

僅允許相同系列互相讀寫,亦即機種 DVP14SS11R2 可與機種 DVP14SS11T2 互相讀寫,但無法與機種

DVP14SS211R 或其它系列機種互相讀寫。

產品簡介

DVPPCC01 支援 DVP 全系列 PLC 程式、參數及密碼複製功能。操作原理係透過 PLC 的 COM 通訊口,以通訊

的方式對 PLC 程式、參數執行寫入或讀出的動作。同時 DVPPCC01 亦支援密碼、PLC 識別碼、副程式密碼功能,

以提供安全之資料傳輸。

支援系列及讀∕寫元件種類

資料區塊

適用系列

DVP-ES/EX/EC/SS

DVP-SA/SX/SC

SX V3.00(含)以上

DVP-SS2

DVP-EH/SV/EH2-L/EH2

DVP-ES2/EX2/SX2/SA2

程式區塊

程式( steps)

4K

8K

16K

8K

16K

16K

D 暫存器

D0 ~ D599

D0 ~ D4999

D0 ~ D9999

D0 ~ D4999

D0 ~ D9999

D0 ~ D9999

PLC 參數區塊

M 元件

M0 ~ M1279

M0 ~ M4095

M0 ~ M4095

M0 ~ M4095

M0 ~ M4095

M0 ~ M4095

檔案暫存器

1,600

1,600

10,000

無 /5,000(註 1)

註 1:ES2/EX2 V2.8(含)以上、SA2 V2.42(含)以上、SX2 V2.20(含)以上才有支援檔案暫存器。

註 2:EH3/EH3-L V1.4(含)以上、SV2 V1.2(含)以上才有支援 50,000 個檔案暫存器。

外觀說明

5 6

W R RD

33

300 1 2 3 4 66.3

尺寸單位: mm

電源指示 燈 通訊中指示燈 動作完成指示燈

4 錯誤發生指示燈 5 操作模式:讀出、寫入功能選擇 6 內部資料全部清除按鈕

規格

保存期限 10 年

寫入次數 至少 1 萬次

傳輸速率 9,600/115,200

儲存環境 -25°C ~ 70°C(溫度),5 ~ 95%(濕度)

工作環境 0°C ~ 55°C(溫度),5 ~ 95%(濕度),污染等級 2

Warning

ENGLISH

EN a DVPPCC01 is an OPEN-TYPE device. It should be installed in a control cabinet free of airborne dust, humidity,

PCC01.

Read/Write from DVPPCC01 to PLC

EN electric shock and vibration. To prevent non-maintenance staff from operating DVPPCC01, or to prevent an accident from damaging DVPPCC01, the control cabinet in which DVPPCC01 is installed should be equipped with a safeguard. For example, the control cabinet in which DVPPCC01 is installed can be unlocked with a special tool or key. a DO NOT connect AC power to any of I/O terminals, otherwise serious damage may occur. Please check all wiring again before DVPPCC01 is powered up. After DVPPCC01 is disconnected, Do NOT touch any terminals in a minute. Make sure that the ground terminal on DVPPCC01 is correctly grounded in order to prevent electromagnetic interference.

FR a

DVPPCC01 est un module OUVERT. Il doit être installé que dans une enceinte protectrice (boitier, armoire, etc.) saine, dépourvue de poussière, d’humidité, de vibrations et hors d’atteinte des chocs électriques. La protection doit éviter que les personnes non habilitées à la maintenance puissent accéder à l’appareil (par exemple, une clé ou un outil doivent être nécessaire pour ouvrir a protection).

FR a Ne pas appliquer la tension secteur sur les bornes d’entrées/Sorties, ou l’appareil DVPPCC01 pourra être endommagé. Merci de vérifier encore une fois le câblage avant la mise sous tension du DVPPCC01. Lors de la déconnection de l’appareil, ne pas toucher les connecteurs dans la minute suivante. Vérifier que la terre est bien reliée au connecteur de terre

Introduction

DVPPCC01 supports the function of copying the program, parameters and passwords in DVP series PLC.

DVPPCC01 reads or writes the program and parameters in the PLC through the COM port on the PLC.

DVPPCC01 also supports the password function, the PLC ID function, and the subroutine password function to ensure safe data transmission.

Applicable series

Device type

DVP-ES/EX/EC/SS

DVP-SX V3.00 (and above)

afin d’éviter toute interférence électromagnétique.

Supported PLC Models and Accessible Devices

Program area

Program steps

4k

16k

D register

D0 ~ D599

PLC device area

M device

M0 ~ M1279

File register

None

D0 1,600

D0 ~ D9999 M0 ~ M4095 1,600

DVP-ES2/EX2/SX2/SA2

DVP-EH3/EH3-L/SV2

16k

30k

D9999 10,000

D0 ~ D9999

D0 ~ D11999

M0 ~ M4095

M0 ~ M4095

None/5,000 (Note 1)

10,000/50,000 (Note 2)

Note 1: Only DVP-ES2/EX2 V2.8 (and above), DVP-SA2 V2.42 (and above), and DVP-SX2 V2.20 (and above) support file registers.

Note 2: Only DVP-EH3/EH3-L V1.4 (and above), and DVP-SV2 V1.2 (and above) support 50,000 file registers.

Product Profile

PLC

RUN

STOP

DVPPCC01

No password

With password

No password

With password

No password

Able to read

Able to read (require the correct password entered by WPLSoft)

Read

With password

Incorrect password verification

Unable to read

Able to read

Incorrect password verification

Able to read (require the correct password entered by WPLSoft)

DVPPCC01 Read Write

PLC

No PLC ID

No PLC ID

Able to read

With PLC ID

Incorrect PLC ID verification

No PLC ID

Unable to write

With PLC ID

Unable to write

RUN

With PLC ID

Able to read (require the correct PLC ID Unable to read Unable to write Unable to write

Not supported entered by WPLSoft)

Able to read Unable to read

Incorrect PLC ID

Unable to write Unable to write

Incorrect PLC ID

STOP

No PLC ID

With PLC ID

Not supported

Able to read

Able to read (require the correct PLC ID entered by WPLSoft)

Able to read verification

Unable to read

Unable to read

Able to write

Incorrect PLC ID verification

Able to write verification

Able to write only after the correct PLC ID verification

Unable to write

DVPPCC01 reads/writes the subroutine password together with the PLC program in STOP mode of the

PLC. If the subroutine password is set in both the PLC and PCC01 when PCC01 writes the program into the

PLC, the password in PLC will be replaced by the password set in PCC01. However, PCC01 with the subroutine password is not able to write the program into the PLC which does not support the subroutine password function.

Executing RUN/STOP of PLC

Unable to read

No password

Unable to write

Unable to write

Able to write verification

Write

Incorrect password

With password

Unable to write

Unable to write

Write in with the password

Able to write only after the correct password verification

For DVP-ES/EX/EC series MPU without RUN/STOP switch, DVPPCC01 is able to execute RUN/STOP for the

PLC. Setting method: Plug DVPPCC01 (in WR mode) into the PLC while the PLC is in RUN status (At this time,

DVPPCC01 is unable to write the data into the PLC). After this, ERR LED and OK LED will flash synchronously.

Press the ERASE button while both LEDs are still flashing within 30 sec, and PLC will be switched from RUN to

STOP. Remove DVPPCC01 from the PLC and plug it into it again to start the data transmission automatically.

OK LED will be On when the transmission is completed. Press the ERASE button before OK LED is On for 30 sec and the PLC will be switched from STOP to RUN again.

5 6

WR RD

33

Clearing Data in DVPPCC01

Plug DVPPCC01 into the COM port of the PLC and press the ERASE button before POWER LED is On for 5 sec. When OK LED is On, indicating the data clearing is finished, remove DVPPCC01 to complete the clearing process.

Power indicator

Communication indicator

Operation completion indicator

Specifications

Data retention

Number of write-in times

300

10 years

At least 10,000 times

1 2 3 4 66.3

Unit: mm

4 Error LED

5 Read (RD)/write (WR) switch

6 Data erasing button

Copying Data/Limit on the Number of Times Data Is Copied

When DVPPCC01 writes data into the PLC, users can choose either to copy the program and parameters or simply copy the program by means of M1085, and can limit the number of times that the data is copied by means of M1480.

Flag Status Function Flag Status Function

M1085

On

Off

Copying the program

Copying the PLC parameters and the program

M1480

On

Off

Enabling the function of limiting the number of times that the data is written into the PLC (M1480 needs to be used with D1088.)

Disabling the function of limiting the number of times that the data is written into the PLC

How to set M1085 and M1480:

1. Users have to set M1085 in the PLC to On or Off according to their need.

2. If the users want to limit the number of times the data is written into the PLC, they have to set M1480 to

Troubleshooting

When DVPPCC01 is reading/writing and the ERR LED is constantly On or flashing, see the error message table above for the problem-solving. When DVPPCC01 is reading/writing, and the power supply to the PLC is suddenly cut off, or DVPPCC01 is removed from the PLC, the following scenarios will occur:

1. While reading: The data in DVPPCC01 will be lost. Re-power the PLC or plug DVPPCC01 into the PLC again.

2. While writing: The data in the PLC will be lost. Re-power the PLC or plug DVPPCC01 into the PLC again.

ASCII Code Conversion

The password in the PLC is composed of 4 digits, and each digit represents an 8-bit value which corresponds to one ASCII code. The password only accepts visible words. In WPLSoft or ISPSoft, users are able to enter all visible words. Therefore, the values set in D1086 and D1087 have to be visible words; otherwise, you will not be able to unlock the password in the PLC by WPLSoft or ISPSoft. Accordingly, the PLC ID set in D1995 ~ D1999 should also be visible words.

Hex 0 1 2 3 4 5 6 7 8 9 A B C D E F

ASCII

Hex

ASCII

Hex

10

20

11

21

12

22

13

23

14

24

15

25

16

26

17

27

18

28

19

29

1A

2A

1B

2B

1C

2C

1D

2D

1E

2E

1F

2F

Hex 30 31 32 33 34 35 36 37 38 39 3A 3B 3C 3D 3E 3F

ASCII 0 1 2 3 4 5 6 7 8 9 : ; < = > ?

Hex 40 41 42 43 44 45 46 47 48 49 4A 4B 4C 4D 4E 4F

ASCII @ A B C D E F G H I J K L M N O

Hex 50 51 52 53 54 55 56 57 58 59 5A 5B

ASCII P Q R S T U V W X Y Z ⌧

5C 5D 5E

⌧ ⌧ ⌧

5F

Hex 60 61 62 63 64 65 66 67 68 69 6A 6B 6C 6D 6E 6F

ASCII ` a b C d e f g h i j k l M n o

Hex 70 71 72 73 74 75 76 77 78 79 7A 7B 7C 7D 7E 7F

ASCII p q r s t u v w x y z { | } ~ ⌧

Note: ‘⌧’ represents invisible words. Please do not use it.

雜訊免疫力

耐振動∕衝擊

ESD: ±4KV Air Discharge

EFT: Power Line: 2KV

CS: 0.15MHz ~ 80MHz, 10V/m

Surge : ±1KV

國際標準規範 IEC 61131-2, IEC 68-2-6(TEST Fc)/IEC 61131-2 & IEC 68-2-27(TEST Ea)

功能規格

讀出∕寫入動作方式

在進行以下動作順序之前須先將 PLC 上電。

動作順序 RD 讀出(PLC → DVPPCC01)

1

2

3

4

將 DVPPCC01 讀出/寫入開關撥至 RD

將 DVPPCC01 插入 PLC COM 通訊口,等待 5 秒

讀取完畢 OK 燈號長亮

拔除 DVPPCC01 完成讀取動作

WR 寫入(DVPPCC01 → PLC)

將 DVPPCC01 讀出∕寫入開關撥至 WR,同時確認

PLC 為 STOP 狀態

將 DVPPCC01 插入 PLC COM 通訊口,等待 5 秒

寫入完畢 OK 燈號長亮

拔除 DVPPCC01 完成寫入動作

密碼∕ PLC 識別碼∕副程式密碼保護功能

當 DVPPCC01 要對 PLC 進行資料寫入時,若 PLC 已有密碼∕PLC 識別碼鎖定,DVPPCC01 會以設定於

DVPPCC01 內部的密碼∕PLC 識別碼鑰匙與 PLC 的密碼∕PLC 識別碼作比對驗證,若驗證成功,才能進行資料

寫入的動作。

DVPPCC01 密碼鑰匙設定方式如下:

1. 將預備設定於 DVPPCC01 的密碼鑰匙以 ISPSoft 或 WPLSoft 寫入 PLC 的 D1086 及 D1087,並且將 PLC

M1086 設為 On。

2. 將 DVPPCC01 的讀出∕寫入開關撥至 RD,然後將 DVPPCC01 通訊接頭插入 PLC 的 COM 通訊口,

DVPPCC01 開始讀取 PLC 的程式、參數。

3. 當讀取完成後,DVPPCC01 會判斷 M1086 是否 On,若 M1086 = On,則 DVPPCC01 會接著讀取 D1086 及

D1087 的值,並當成是設定於 DVPPCC01 密碼鑰匙,完成之後 DVPPCC01 “OK” 燈號會長亮,代表完成所

有讀取的動作,接著拔除 DVPPCC01。

密碼鑰匙共四位數,每一位數代表一個 8 位元數值,可對應到一個 ASCII 碼(僅接受可視字元),D1086、D1087

儲存密碼鑰匙的四個位數,其格式如下:(以 WPLSoft 輸入密碼 1234 為例)

密碼鑰匙 D1086 D1087

密碼設定值

ASCII 碼(Hex)

高位元組

位數 1

1(H31)

低位元組

位數 2

2(H32)

高位元組

位數 3

3(H33)

低位元組

位數 4

4(H34)

DVPPCC01 的 PLC 識別碼鑰匙設定方式如下:(若該 PLC 機種有支援 PLC 識別碼)

1. 將預備設定於 DVPPCC01 的 PLC 識別碼鑰匙,利用 ISPSoft 或 WPLSoft 寫入 PLC 的 D1996 ~ D1999,並

將 PLC 識別碼長度紀錄在 D1995。

2. 設定 PLC 主機之 PLC 識別碼,其值與欲給定 DVPPCC01 之 PLC 識別碼相同。

3. 將 DVPPCC01 的讀出∕寫入開關撥至 RD,然後將 DVPPCC01 通訊接頭插入 PLC 的 COM 通訊口,

DVPPCC01 開始讀取 PLC 的程式、參數。

4. 讀取過程中,DVPPCC01 會詢問 PLC 是否有 PLC 識別碼。若 PLC 有 PLC 識別碼,則 DVPPCC01 會接著

讀取 D1995 ~ D1999 的值並當作是設定於 DVPPCC01 的 PLC 識別碼鑰匙。完成之後 DVPPCC01 “OK” 燈

號會長亮,代表完成所有讀取的動作,接著拔除 DVPPCC01。

PLC 識別碼鑰匙共四 ~ 八位數,每一位數代表一個 8 位元數值,可對應到一個 ASCII 碼(僅接受可視字元),

D1995 ~ D1999 儲存密碼鑰匙的四 ~ 八個位數,其格式如下:(以 WPLSoft 輸入 PLC 識別碼 12345678 為例)

輸入 D1995=K8

識別碼設定值

識別碼 D1996

高位元組

位數 1

低位元組

位數 2

D1997

高位元組

位數 3

低位元組

位數 4

D1998

高位元組 低位元組 高位元組 低位元組

位數 5 位數 6

D1999

位數 7 位數 8

ASCII 碼(Hex)

1(H31) 2(H32) 3(H33) 4(H34) 5(H35) 6(H36) 7(H37) 8(H38)

副程式密碼隨著 PLC 程式一起被 DVPPCC01 讀出。若 PLC 程式有副程式密碼,則 DVPPCC01 將此副程式

讀出並設定成 DVPPCC01 之副程式密碼。

DVPPCC01 對 PLC 讀出∕寫入相關動作條件

DVPPCC01 讀出

PLC 狀態 無密碼 有密碼

RUN

STOP

無密碼

有密碼

無密碼

有密碼

PLC 狀態

DVPPCC01

無 PLC 識別碼

RUN 有 PLC 識別碼

不支援

無 PLC 識別碼

STOP 有 PLC 識別碼

不支援

寫入

可讀出

需由 WPLSoft 輸入正

確密碼後才可讀出

可讀出

需由 WPLSoft 輸入正

確密碼後才可讀出

讀出

密碼比對錯誤

無法讀出

無法讀出

密碼比對錯誤

無密碼

無法寫入

無法寫入

可寫入

密碼比對錯誤

有密碼

無法寫入

無法寫入

寫入

連同密碼一起寫入

密碼比對相同後

方可寫入

無 PLC 識別碼 有 PLC 識別碼

可讀出 PLC 識別碼比對錯誤

需由 WPLSoft 輸入

正確 PLC 識別碼後

才可讀出

可讀出

無法讀出

無法讀出

無 PLC 識別碼

無法寫入

無法寫入

有 PLC 識別碼

無法寫入

無法寫入

無法寫入 無法寫入

可讀出 PLC 識別碼比對錯誤

需由 WPLSoft 輸入

正確 PLC 識別碼後

才可讀出

可讀出

無法讀出

無法讀出

可寫入 PLC 識別碼比對錯誤

PLC 識別碼比對錯誤

可寫入

PLC 識別碼比對正確

後方可寫入

無法寫入

副程式密碼隨著 PLC 程式一起被 DVPPCC01 讀出∕寫入。在 PLC 為 STOP 狀態下,DVPPCC01 要對 PLC

進行資料寫入動作時,若 DVPPCC01 及 PLC 皆有副程式密碼保護,則 DVPPCC01 會以本身之副程式密碼

將 PLC 之副程式密碼覆蓋。唯一無法寫入之情況為:PLC 不支援副程式密碼功能,但 DVPPCC01 有副程式

密碼保護 。

執行 PLC RUN/STOP 功能

DVPPCC01 針對 DVP-ES/EX/EC 主機上沒有 RUN/STOP 開關之機種,可將 PLC 做 STOP/RUN 之功能。操作

方式為:當 PLC 在 RUN 狀態,插入 DVPPCC01,DVPPCC01 處於 WR 模式。此時 DVPPCC01 無法寫入資料,

待 DVPPCC01 ERR/OK LED 同步閃爍 30 秒內,按下 ERASE 鈕,可將 PLC 狀態由 RUN 切換至 STOP 狀態。

此時,請重新拔插 DVPPCC01,待資料傳輸完畢後,於 DVPPCC01 OK LED ON 30 秒內,再按下 ERASE 鈕,

即可將 PLC 狀態由 STOP 回歸至 RUN 狀態。

錯誤訊息

指示燈

ERR OK

原因及建議採取措施

操作錯誤,無

法寫入

操作錯誤,無

法讀出

同步閃爍

交替閃爍

1. DVPPCC01 內部無資料但是執行寫入動作。請確認 DVPPCC01 內部是否有程式

以及確認操作模式( RD/WR),並將 PLC 設定為 STOP 模式。

2. DVPPCC01 與 PLC 通訊格式不符時,請將 PLC STOP 後重新上電以確保 PLC

通訊格式為 ASCII 9,600, 7, E, 1。

3. DVPPCC01 內部程式可能不合法,請重新確認 DVPPCC01 內部程式正確性。

4. DVPPCC01 有 PLC 識別碼∕副程式密碼鎖定,但 PLC 韌體不支援 PLC 識別碼

∕副程式密碼功能,請更新 PLC 韌體或解除 PCC01 上 PLC 識別碼∕副程式密

碼。

1. PLC 受到密碼∕PLC 識別碼保護,請解除 PLC 之密碼∕PLC 識別碼鎖定,或設

定 DVPPCC01 與 PLC 有相同之密碼∕PLC 識別碼。

2. DVPPCC01 與 PLC 通訊格式不符時,請將 PLC STOP 後重新上電以確保 PLC

通訊格式為 ASCII 9,600, 7, E, 1。

問題排除

當 DVPPCC01 在讀取∕寫入時 “ERR” 燈號長亮或閃爍,請參考單元 錯誤訊息表來排除錯誤。若 DVPPCC01

讀取∕寫入時, PLC 突然斷電或將 DVPPCC01 由 PLC 拔除,會產生以下狀況:

1. 讀取時:DVPPCC01 資料將會遺失,請將 PLC 重新上電或將 DVPPCC01 重新插入 PLC。

2. 寫入時:PLC 資料將會遺失,請將 PLC 重新上電或將 DVPPCC01 重新插入 PLC。

ASCII 碼轉換表

PLC 的密碼共四位數,每一位數代表一個 8 位元數值,可對應到一個 ASCII 碼,並且僅接受可視字元;以 WPLSoft

或 ISPSoft 輸入可輸入所有的可視字元。因此設定於 D1086、D1087 數值必須為可視字元的範圍,否則將會無法

以 WPLSoft 或 ISPSoft 將 PLC 密碼解開。同樣地,設定於 D1995 ~ D1999 之 PLC 識別碼數值也必須為可視字

元的範圍 。

Hex

ASCII

Hex

ASCII

Hex

0

10

20

1

11

21

2

12

22

3

13

23

4

14

24

5

15

25

6

16

26

7

17

27

8

18

28

9

19

29

A

1A

2A

B

C

D

1B 1C 1D

⌧ ⌧ ⌧

2B 2C 2D

E

F

1E 1F

⌧ ⌧

2E 2F

Hex 30 31 32 33 34 35 36 37 38 39 3A 3B 3C 3D 3E 3F

ASCII 0 1 2 3 4 5 6 7 8 9 : ; < = > ?

Hex 40 41 42 43 44 45 46 47 48 49 4A 4B 4C 4D 4E 4F

ASCII @ A B C D E F G H I J K L M N O

Hex 50 51 52 53 54 55 56 57 58 59 5A 5B 5C 5D 5E 5F

ASCII P Q R S T U V W X Y Z ⌧ ⌧ ⌧ ⌧ ⌧

Hex 60 61 62 63 64 65 66 67 68 69 6A 6B 6C 6D 6E 6F

ASCII ` a b C d e f g h i j k l M n o

Hex 70 71 72 73 74 75 76 77 78 79 7A 7B 7C 7D 7E 7F

ASCII p q r s t u v w x y z { | } ~ ⌧

註:標示 為 ⌧,均為不可視字元,請勿設定。

干扰免疫力

耐振动/冲击

ESD: ±4KV Air Discharge

EFT: Power Line: 2KV

C S: 0.15MHz ~ 80MHz, 10V/m

Surge : ±1KV

国际标准规范 IEC 61131-2, IEC 68-2-6(TEST Fc)/IEC 61131-2 & IEC 68-2-27(TEST Ea)

Αਕఢॾ

᝝΍Ɵᆷˢજү͞ё!

在进行以下动作顺序之前须先将 PLC 上电。

动作顺序 RD 读出(PLC → DVPPCC01)

1

2

3

4

将 DVPPCC01 读出/写入开关拨至 RD

将 DVPPCC01 插入 PLC COM 通讯口,等待 5 秒

读取完毕 “OK” 灯号长亮

拔除 DVPPCC01 完成读取动作

WR 写入(DVPPCC01 → PLC)

将 DVPPCC01 读出/写入开关拨至 WR,同时确认

PLC 为 STOP 状态

将 DVPPCC01 插入 PLC COM 通讯口,等待 5 秒

写入完毕 “OK” 灯号长亮

拔除 DVPPCC01 完成写入动作

૜ቅƟPLC ᙊҾቅƟ̄඀Ԕ૜ቅ᜕ܲΑਕ!

当 DVPPCC01 要对 PLC 进行数据写入时,若 PLC 已有密码/PLC 识别码锁定,DVPPCC01 会以设定于

DVPPCC01 内部的密码/PLC 识别码钥匙与 PLC 的密码/PLC 识别码作比对验证,若验证成功,才能进行数据

写入的动作。

DVPPCC01 密码钥匙设定方式如下:

1. 将预备设定于 DVPPCC01 的密码钥匙以 ISPSoft 或 WPLSoft 写入 PLC 的 D1086 及 D1087,并且将 PLC

M1086 设为 On。

2. 将 DVPPCC01 的读出/写入开关拨至 RD,然后将 DVPPCC01 通讯连接器插入 PLC 的 COM 通讯口,

DVPPCC01 开始读取 PLC 的程序、参数。

3. 当读取完成后,DVPPCC01 会判断 M1086 是否 On,若 M1086 = On,则 DVPPCC01 会接着读取 D1086 及

D1087 的值,并当成是设定于 DVPPCC01 密码钥匙,完成之后 DVPPCC01 “OK” 灯号会长亮,代表完成所

有读取的动作,接着拔除 DVPPCC01。

密码钥匙共四位数,每一位数代表一个 8 位数值,可对应到一个 ASCII 码(仅接受可视字符),D1086、D1087

储存密码钥匙的四个位数,其格式如下:(以 WPLSoft 输入密码 1234 为例)

密码钥匙 D1086 D1087

密码设定值

ASCII 码(Hex)

高字节

位数 1

1(H31)

低字节

位数 2

2(H32)

高字节

位数 3

3(H33)

低字节

位数 4

4(H34)

DVPPCC01 的 PLC 识别码钥匙设定方式如下:(若该 PLC 机种有支持 PLC 识别码)

1. 将预备设定于 DVPPCC01 的 PLC 识别码钥匙,利用 ISPSoft 或 WPLSoft 写入 PLC 的 D1996 ~ D1999,并

将 PLC 识别码长度纪录在 D1995。

2. 设定 PLC 主机的 PLC 识别码,其值与欲给定 DVPPCC01 的 PLC 识别码相同。

3. 将 DVPPCC01 的读出/写入开关拨至 RD,然后将 DVPPCC01 通讯接头插入 PLC 的 COM 通讯口,

DVPPCC01 开始读取 PLC 的程序、参数。

4. 读取过程中,DVPPCC01 会询问 PLC 是否有 PLC 识别码。若 PLC 有 PLC 识别码,则 DVPPCC01 会接着

读取 D1995 ~ D1999 的值并当作是设定于 DVPPCC01 的 PLC 识别码钥匙。完成之后 DVPPCC01 “OK” 灯

号会长亮,代表完成所有读取的动作,接着拔除 DVPPCC01。

DVPPCC01 ྤफ़୻ੵΑਕ!

将 DVPPCC01 插入 PLC COM 通讯口后,必须于电源指示灯亮 5 秒内,按住数据清除按钮(ERASE 键),当 “OK”

灯号长亮,表示数据清除完毕,拔除 DVPPCC01 后即完成清除动作。

ኑᄦΑਕ∕ኑᄦΑਕѨᇴࢨט!

执行写入动作( DVPPCC01 → PLC),可设定 M1085 决定复制的区块,亦可搭配 M1480 限制复制次数。

旗标

M1085

状态

On

Off

功能说明

复制程序区块

PLC 参数或仅复制程序区

旗标

M1480

状态

On

Off

功能说明

启动写入次数限制(需配合

关闭写入次数限制

D1088)

设定方式如下:

1. 依需求将 PLC 之 M1085 设为 On 或 Off。

2. 若需要限制 PLC 之写入次数,则将 M1480 设为 On 并在 D1088 填入设定次数(D1088>0)

3. 将 DVPPCC01 的读出⁄写入开关拨至 RD,然后将 DVPPCC01 通讯接头插入 PLC 的 COM 通讯口。

4. 读取完毕之后 DVPPCC01 “OK” 灯号会长亮,代表完成读取的动作,接着拔除 DVPPCC01。

5. 若有启动限制写入次数 ,并已经超过写入次数则 DVPPCC01 “ ERR ” 灯闪烁 。

᝝΍Ɵᆷˢ౵̂ॡม!

DVP 系列 读写时间 DVP 系列 读写时间 DVP 系列 读写时间

ES/EX/EC/SS

SA/SX/SC/SS2

38 秒~48 秒

13 秒~21 秒

EH/SV/EH2-L/EH2

ES2/EX2/SX2/SA2

*以上读写时间会因为数据大小而有所变动,仅供参考。

19 秒~2 分 08 秒 EH3/EH3-L/SV2 29 秒~1 分 32 秒

!ள૱ྤੈ

DVPPCC01 当读取完成 PLC 的数据后,会同时记录 PLC 的类型,若接下来写入的 PLC 程序容量与 DVPPCC01

记录不同,则 DVPPCC01 不会做写入的动作,同时 “ERR” 灯号会闪烁。其它错误信息指示如下表所示:

错误信息

指示灯

ERR OK

原因及建议采取措施

DVPPCC01

内部存储器错

误、连线失败

DVPPCC01 可能发生硬件故障,请更换。

On Off

机种不符

灯号闪烁 OFF

1. 请确认 DVPPCC01 内部程序是否与连线 PLC 机种相同。

2. DVP10SX11R/T 韧体 V3.00 以上,不可复制到 V3.00 以下。

密码/ PLC 识

别码比对错误

导致

ERASE 完成

On

灯号闪

1. DVPPCC01 受到密码/PLC 识别码保护。请解除 DVPPCC01 的密码/PLC 识别

码锁定,或设定 PLC 与 DVPPCC01 有相同的密码/PLC 识别码。

2. PLC 受到密码/PLC 识别码保护,请解除 PLC 的密码/PLC 识别码锁定,或设定

DVPPCC01 与 PLC 有相同的密码/PLC 识别码。

1. DVPPCC01 按下 ERASE 钮进行内存抹除,当完成后“OK”灯号长亮。

2. 若要再进行 DVPPCC01 的 RD/WR 功能,请将 PLC 重新上电或重新插拔

Off On

DVPPCC01 才可正确动作。

寫入次數用

燈號閃爍 On

限制可寫入的次數已用完,請切換到 READ 模式重新讀取程式。

DVPPCC01 資料清除功能

將 DVPPCC01 插入 PLC COM 通訊口後,必須於電源指示燈亮 5 秒內,按住資料清除按鈕(ERASE 鍵) “OK”

燈號長亮,表示資料清除完畢,拔除 DVPPCC01 後即完成清除動作。

複製功能∕複製功能次數限制

執行寫入動作( DVPPCC01 → PLC),可設定 M1085 決定複製的區塊,亦可搭配 M1480 限制複製次數。

旗標 旗標

M1085

狀態

On

Off

功能說明

複製程式區塊

PLC 參數或僅複製程式區

M1480

狀態

On

Off

功能說明

啟動寫入次數限制(需配合 D1088)

關閉寫入次數限制

設定方式如下:

1. 依需求將 PLC 之 M1085 設為 On 或 Off。

2. 若需要限制 PLC 之寫入次數,則將 M1480 設為 On 並在 D1088 填入設定次數(D1088>0)

3. 將 DVPPCC01 的讀出∕寫入開關撥至 RD,然後將 DVPPCC01 通訊接頭插入 PLC 的 COM 通訊口。

4. 讀取完畢之後 DVPPCC01 “OK” 燈號會長亮,代表完成讀取的動作,接著拔除 DVPPCC01。

5. 若有啟動限制寫入次數 ,並已經超過寫入次數則 DVPPCC01 “ ERR ” 燈閃爍 。

讀出∕寫入最大時間

DVP 系列 讀寫時間 DVP 系列 讀寫時間 DVP 系列 讀寫時間

ES/EX/EC/SS

SA/SX/SC/SS2

38 秒~48 秒

13 秒~21 秒

EH/SV/EH2-L/EH2

ES2/EX2/SX2/SA2 19 秒~2 分 08 秒 EH3/EH3-L/SV2 29 秒~1 分 32 秒

*以上讀寫時間會因為資料大小而有所變動,僅供參考。

異常訊息

DVPPCC01 當讀取完成 PLC 的資料後,會同時記錄 PLC 的類型,若接下來寫入的 PLC 程式容量與 DVPPCC01

紀錄不同,則 DVPPCC01 不會做寫入的動作,同時 “ERR” 燈號會閃爍。其它錯誤訊息指示如下表所示:

錯誤訊息

指示燈

ERR OK

原因及建議採取措施

DVPPCC01 內

部記憶體錯

誤、連線失敗

DVPPCC01 可能發生硬體故障,請更換。

On Off

機種不符

密碼∕ PLC 識

別碼比對錯誤

導致

ERASE 完成

燈號閃爍 Off

1. 請確認 DVPPCC01 內部程式是否與連線 PLC 機種相同。

2. DVP10SX11R/T 韌體 V3.00 以上,不可複製到 V3.00 以下。

On 燈號閃爍

1. DVPPCC01 受到密碼∕PLC 識別碼保護。請解除 DVPPCC01 之密碼∕PLC 識

別碼鎖定,或設定 PLC 與 DVPPCC01 有相同之密碼∕PLC 識別碼。

2. PLC 受到密碼∕PLC 識別碼保護,請解除 PLC 之密碼∕PLC 識別碼鎖定,或設

定 DVPPCC01 與 PLC 有相同之密碼∕PLC 識別碼。

1. DVPPCC01 按下 ERASE 鈕進行記憶體抹除,完成後“OK”燈號長亮。

2. 若要再進行 DVPPCC01 的 RD/WR 功能,請將 PLC 重新上電或重新插拔

Off On DVPPCC01 才可正確動作。

寫入次數用完

燈號閃爍 On

限制可寫入的次數已用完,請切換到 READ 模式重新讀取程式。

ڦຍְี!

简体中文

欲进行数据传输前,请预先设定所要使用的模式( RD 或 WR),再插入 PLC 主机 COM 通讯口。

DVPPCC01 读取 PLC 数据时,在未完成数据传输前,请勿中途断电或拔除 DVPPCC01,以免造成 DVPPCC01

数据遗失。

在 DVPPCC01 传送接收过程中,改变 DVPPCC01 工作模式(RD 或 WR)并无作用。

仅允许相同系列互相读写,亦即机种 DVP14SS11R2 可与机种 DVP14SS11T2 互相读写,但无法与机种

DVP14SS211R 或其它系列机种互相读写。

யݡᖎ̬!

DVPPCC01 支持 DVP 全系列 PLC 程序、参数及密码复制功能。操作原理系透过 PLC 的 COM 通讯口,以通讯

的方式对 PLC 程序、参数执行写入或读出的动作。同时 DVPPCC01 亦支持密码、PLC 识别码、子程序密码功能,

以提供安全之数据传输。

͚೯րЁ́᝝Ɵᆷ̮І჌ᙷ!

资料区块

适用系列

DVP-ES/EX/EC/SS

程序区块

程序( steps)

4K

D 寄存器

D0 ~ D599

PLC 参数区块

M 组件

M0 ~ M1279

档案寄存器

SX V3.00(含)以上 D9999 M4095 1,600

DVP-EH3/EH3-L/SV2 30K D0 ~ D11999 M0 ~ M4095 10,000/50,000(注 2)

注 1:ES2/EX2 V2.8(含)以上、SA2 V2.42(含)以上、SX2 V2.20(含)以上才有支持档案寄存器。

注 2:EH3/EH3-L V1.4(含)以上、SV2 V1.2(含)以上才有支持 50,000 个档案寄存器。

γ៍ᄲځ!

5 6

WR RD

33

300 1 2 3 4 66.3

尺寸单位: mm

电源指示 灯 通讯中指示灯 动作完成指示灯

4 错误发生指示灯 5 操作模式:读出、写入功能选择 6 内部数据全部清除按钮

ఢॾ!

保存期限 10 年

写入次数 至少 1 万次

传输速率 9,600/115,200

储存环境 70°C(温度),5 ~ 95%(湿度)

工作环境 55°C(温度),5 ~ 95%(湿度),污染等级 2

PLC 识别码钥匙共四 ~ 八位数,每一位数代表一个 8 位数值,可对应到一个 ASCII 码(仅接受可视字符), D1995

~ D1999 储存密码钥匙的四 ~ 八个位数,其格式如下:(以 WPLSoft 输入 PLC 识别码 12345678 为例)

输入 D1995=K8

识别码

识别码设定值

ASCII 码(Hex)

D1996

高字节 低字节 高字节

D1997

低字节 高字节

D1998

低字节 高字节

D1999

低字节

位数 1 位数 2 位数 3 位数 4 位数 5 位数 6 位数 7 位数 8

1(H31) 2(H32) 3(H33) 4(H34) 5(H35) 6(H36) 7(H37) 8(H38)

子程序密码随着 PLC 程序一起被 DVPPCC01 读出。若 PLC 程序有子程序密码,则 DVPPCC01 将此子程序

读出并设定成 DVPPCC01 的子程序密码。

DVPPCC01 ၆ PLC ᝝΍Ɵᆷˢ࠹ᙯજү୧І!

读出 写入 DVPPCC01

PLC 状态

无密码

无密码

可读出

有密码

密码比对错误

无密码

无法写入

有密码

无法写入

RUN

有密码

需由 WPLSoft 输入正

确密码后才可读出

无法读出 无法写入 无法写入

无密码

STOP

有密码

PLC 状态

DVPPCC01

无 PLC 识别码

可读出

需由 WPLSoft 输入正

确密码后才可读出

密码比对错误

无法读出

可写入

密码比对错误

连同密码一起写入

密码比对相同后

方可写入

RUN 有 PLC 识别码

不支援

无 PLC 识别码

STOP 有 PLC 识别码

不支援

读出 写入

无 PLC 识别码 有 PLC 识别码

可读出 PLC 识别码比对错误

需由 WPLSoft 输入

正确 PLC 识别码后

才可读出

可读出

无法读出

无法读出

无 PLC 识别码

无法写入

无法写入

有 PLC 识别码

无法写入

无法写入

无法写入 无法写入

可读出 PLC 识别码比对错误

需由 WPLSoft 输入

正确 PLC 识别码后

才可读出

可读出

无法读出

无法读出

可写入 PLC 识别码比对错误

PLC 识别码比对错误

可写入

PLC 识别码比对正确

后方可写入

无法写入

子程序密码随着 PLC 程序一起被 DVPPCC01 读出∕写入。在 PLC 为 STOP 状态下,DVPPCC01 要对 PLC

进行数据写入动作时,若 DVPPCC01 及 PLC 皆有子程序密码保护,则 DVPPCC01 会以本身的子程序密码

将 PLC 的子程序密码覆盖。唯一无法写入的情况为:PLC 不支持子程序密码功能,但 DVPPCC01 有子程序

密码保护 。

ેҖ PLC RUN/STOP Αਕ!

DVPPCC01 针对 DVP-ES/EX/EC 主机上没有 RUN/STOP 开关的机种,可将 PLC 做 STOP/RUN 的功能,操作

方式为:当 PLC 在 RUN 状态,插入 DVPPCC01,DVPPCC01 处于 WR 模式。此时 DVPPCC01 无法写入数据,

待 DVPPCC01 ERR/OK LED 同步闪烁 30 秒内,按下 ERASE 钮,可将 PLC 状态由 RUN 切换至 STOP 状态。

此时,请重新拔插 DVPPCC01,待数据传输完毕后,于 DVPPCC01 OK LED ON 30 秒内,再按下 ERASE 钮,

即可将 PLC 状态由 STOP 回归至 RUN 状态。

操作错误,无

法写入

操作错误,无

法读出

同步闪烁

交替闪烁

1. DVPPCC01 内部无数据但是执行写入动作,请确认 DVPPCC01 内部是否有程序

以及确认操作模式( RD/WR),并将 PLC 设定为 STOP 模式。

2. DVPPCC01 与 PLC 通讯格式不符时,请将 PLC STOP 后重新上电以确保 PLC 通

讯格式为 ASCII 9,600, 7, E, 1。

3. DVPPCC01 内部程序可能不合法,请重新确认 DVPPCC01 内部程序正确性。

4. DVPPCC01 有 PLC 识别码/子程序密码锁定,但 PLC 韧体不支持 PLC 识别码/

子程序密码功能,请更新 PLC 韧体或解除 PCC01 上 PLC 识别码/子程序密码。

1. PLC 受到密码/PLC 识别码保护,请解除 PLC 的密码/PLC 识别码锁定,或设定

DVPPCC01 与 PLC 有相同的密码/PLC 识别码。

2. DVPPCC01 与 PLC 通讯格式不符时,请将 PLC STOP 后重新上电以确保 PLC 通

讯格式为 ASCII 9,600, 7, E, 1。

યᗟଵੵ

当 DVPPCC01 在读取/写入时 “ERR” 灯号长亮或闪烁,请参考单元 错误信息表排除错误 。若 DVPPCC01

读取/写入时, PLC 突然断电或将 DVPPCC01 由 PLC 拔除,会产生以下状况:

1. 读取时:DVPPCC01 数据将会遗失,请将 PLC 重新上电或将 DVPPCC01 重新插入 PLC。

2. 写入时:PLC 数据将会遗失,请将 PLC 重新上电或将 DVPPCC01 重新插入 PLC。

ASCII ቅᖼೱܑ!

PLC 的密码共四位数,每一位数代表一个 8 位数值,可对应到一个 ASCII 码,并且仅接受可视字符;以 WPLSoft

或 ISPSoft 输入可输入所有的可视字符。因此设定于 D1086、D1087 的数值必须为可视字符的范围,否则将会无

法以 WPLSoft 或 ISPSoft 将 PLC 密码解开。同样地,设定于 D1995 ~ D1999 的 PLC 识别码数值也必须为可视

字符的范围。

Hex

ASCII

Hex

ASCII

Hex

0

10

20

1

11

21

2

12

22

3

13

23

4

14

24

5

15

25

6

16

26

7

17

27

8

18

28

9

19

29

A

1A

2A

B C D

⌧ ⌧ ⌧

1B 1C 1D

⌧ ⌧ ⌧

2B 2C 2D

E F

⌧ ⌧

1E 1F

⌧ ⌧

2E 2F

Hex 30 31 32 33 34 35 36 37 38 39 3A 3B 3C 3D 3E 3F

ASCII 0 1 2 3 4 5 6 7 8 9 : ; < = > ?

Hex 40 41 42 43 44 45 46 47 48 49 4A 4B 4C 4D 4E 4F

ASCII @ A B C D E F G H I J K L M N O

Hex 50 51 52 53 54 55 56 57 58 59 5A 5B 5C 5D 5E 5F

ASCII P Q R S T U V W X Y Z ⌧ ⌧ ⌧ ⌧ ⌧

Hex 60 61 62 63 64 65 66 67 68 69 6A 6B 6C 6D 6E 6F

ASCII ` a b C d e f g h i j k l M n o

Hex 70 71 72 73 74 75 76 77 78 79 7A 7B 7C 7D 7E 7F

ASCII p q r s t u v w x y z { | } ~ ⌧

注:标示 为 ⌧,均为不可视字符,请勿设定。

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

advertisement