I N S TA L L AT I O N I N S T R U C T I O N 0 2/ 17
P EM1 1 2 5/0 4 07 17_ A
—
Installation instruction in EI30 fire-rated walls for
AU80, AU80.2, AU81 and AU81.2 mounting boxes
ABB AU80, AU80.2, AU81 and AU81.2 mounting boxes are certified (Certificate No.
VTT-C-12104-17) for installation in EI30 fire-rated walls according to this installation instruction.
Min 200 mm
*)
200
*)
200
—
Installation of vertical combinations
*)
200
*) *) *)
200
*)
200
*)
*)
*) I nstallation in the oppo s i te side of the wall
A P P R OV ED I N S TA L L AT I O N S:
Wall structure:
Type A gypsum board. Steel or wooden frame c/c 600 mm. Min. 70 mm rock wool
30 kg/m³. When boxes are installed to the opposite side of the wall c/c min
200 mm
Box type
Installation height (H)
200 mm from the floor
1100 mm from the floor
100 mm from the ceiling
*)
Steel or wooden frame
Single box
AU80
Combination vertical 2-3 boxes
600 mm
Min 200 mm
—
Installation of horizontal combinations
Combination horizontal 2-3 boxes
AU80.2
Single box
Rock wool 30 kg/m³
AU81
Single box
AU81.2
Single box
= Approved
AU 8 0 + A S 2 7
AU 8 0. 2 AU 81 + A S 2 7 AU 81 . 2
Ro ck wo o l ha s to b e ins t all e d b e hin d b oxe s w h e n m et al b r acket s are use an d insi d e of th e b ox sup p o r t s A S 2 7 an d A S 2 7. 1 2
ABB Oy
P.O. Box 16 (Porvoon Sisäkehä 2)
FI-06101 Porvoo, Finland
Tel. +358 10 22 11
I N S TA L L AT I O N I N S T R U C T I O N 0 2/ 17
P EM1 1 2 5/0 4 07 17_ A
—
Installation instruction in EI60 fire-rated walls for
AU80, AU80.2, AU81 and AU81.2 mounting boxes
ABB AU80, AU80.2, AU81 and AU81.2 mounting boxes are certified (Certificate No.
VTT-C-12104-17) for installation in EI60 fire-rated walls according to this installation instruction.
Min 200 mm
*)
200
*)
200
—
Installation of vertical combinations
*)
200
*) *) *)
200
*)
200
*)
*)
*) I nstallation in the oppo s i te side of the wall
A P P R OV ED I N S TA L L AT I O N S:
Wall structure:
Type A gypsum board. Steel or wooden frame c/c 600 mm. Min. 70 mm rock wool
30 kg/m³. When boxes are installed to the opposite side of the wall c/c min
200 mm
Box type
Installation height (H)
200 mm from the floor
1100 mm from the floor
100 mm from the ceiling
*)
Steel or wooden frame
Single box
AU80
Combination vertical 2-3 boxes
—
Installation of horizontal combinations
600 mm
Min 200 mm
Combination horizontal 2-3 boxes
AU80.2
Single box
Rock wool 30 kg/m³
AU81
Single box
AU81.2
Single box
= Approved
AU 8 0 + A S 2 7 + A S 2 7. 1 2 AU 8 0. 2 AU 81 + A S 2 7 + A S 2 7. 1 2 AU 81 . 2
Ro ck wo o l ha s to b e ins t all e d b e hin d b oxe s w h e n m et al b r acket s are use an d insi d e of th e b ox sup p o r t s A S 2 7 an d A S 2 7. 1 2