ENGINEERING EFFICIENCY SINCE 1935
GAS
610 ECO
PRO 860
This is a quick reference specification sheet, full details
can be found in the Gas 610 Eco Pro installation and
service guide via remeha.co.uk
TECHNICAL SPECIFICATION SHEET
October 2017
HYDRAULICS
OVERVIEW
2 x 7 sections
MODEL : Gas 610 Eco Pro 860
Rated Output kW
(80/60oc)
Rated Output kW (50/30oc)
Water Content ltrs
11oC
71 (per module)
123 - 790
Resistance @
mbar
397 (per module)
850
Resistance @ 20oC mbar
120 (per module)
Weight (dry) kgs
837
1460 x 1862 x 1726
Nom Flow Rate @
l/s
Nom Flow Rate @ 20oC l/s
8.59 (per module)
Overall Dim WxDxH mm
96.58
Min flow Rate m3/h
5.1 (per module)
98.2
Condensate Outlet mm I/D
32 x 2
108.8
Connection size flanged (#)
NW 80
SBEM Seasonal Efficiency %
GCV(1)
Efficiency-Full Load 100% NCV: (2)
Efficiency-Part Load 30% NCV:
(3)
0.15
stand-by Heat Loss % : (*)
BURNER TYPE PRE MIX
Std Fuel Available
Fuel Consumption M3/h
Flame protection
Ignition
Gas connection size BSP
Acoustic level dB (A) at 1 metre (**)
NOx (Dry, 0% O2) Mg/KWh
Min/Max Gas pressure mbar
Natural Gas
85 (max)
Ionisation
Electronic
2 x 2" (F)
58
32
17 - 100 NG
CONCENTRIC FLUE/AIR INLET
Flue diameter mm I/D
Air inlet diameter mm I/D
Residual fan duty Pa
Mass flue gas flow rate kg/hr
Flue gas temperature @ 80/60oC
350
250 x 2
130
276 - 1352
30 - 80
CONTROLS/OPTIONS
STANDARD On/Off 0-10v dc, Open Therm
High limit protection
Volt free common alarm
Manual override
Modulating (10-100%)
Safety interlocks
Hours run indication
Boiler run indication
OPTIONAL Optimising/Compensators for multiple and
single boilers
Gas leak detection option fitted to gas valve
Second return 65mm Flanged 80mm PN16
Water Pressure Switch for system pressure
Air Inlet Filter connects to boiler air supply
Two into one inlet manifold option
11oC
Std operating temp
oC
Max operating temp
oC
4.72 (per module)
20 - 90
90
High limit set point oC
110
Max operating pressure bar
7
Min operating pressure bar
0.8
ELECTRICAL
Power supply
Power consumption W
Modulating input V dc
Start current amps
Fuse rating amps
Controls voltage
Insulation class IP
Run current amps
2 x 230v - 1ph - 50hz
12 - 852
0 - 10
2x4
2 x 10
2 x 24 (max)
X1B
2 x 3.8
(1) In accordance with the Non Domestic Building Services Compliance Guide 2013 Edition-For use
in England
(2) @ 80/60 oC Nett (EN 92/42)
(3) @ 30 oC Nett EN 92/42)
(*) (EN15420) @ 30 oC T = Boiler temperature - ambient temperature (without heat exchanger
insulation kit)
(**) Maximum for room sealed operation
(#) Flow 80mm return 65mm both flanged NW 80 DIN 2576 - (PN16)
© Ours is a policy of continuous development, we therefore reserve the right to alter specification without prior notification. Remeha accept no liability for any loss or damage rising from any errors or omissions that may be inadvertently contained in this