Product information | Samsung MWR-WE10 Product specifications

Add to my manuals
36 Pages

advertisement

Product information | Samsung MWR-WE10 Product specifications | Manualzz

Wired Remote Control

Basic : MWR-WE00

Model : MWR-WE10

Model Code : MWR-WE10

WIRED REMOTE CONTROL

MWR-WE10

1. Precautions

CONTENTS

2. Product Specifications

3. Disassembly and Reassembly

4. Troubleshooting

5. Exploded Views and Parts List

6. PCB Diagram

7. Wiring Diagram

8. Schematic Diagram

Refer to the service manual in the GSPN(see the rear cover) for the more information.

유선리모컨_MWR-WE10_E_33320A(1)_co.indd 1 2010-12-23 오후 5:50:29

Operating Instructions and Installation

Contents

1. Precautions

........................................................................................................................................

1-1

1-1 Precautions for the Service ............................................................................................................. 1-1

1-2 Precautions for the Safety ............................................................................................................... 1-1

2. Product Specifications

...............................................................................................................

2-1

2-1 The Feature of Product .................................................................................................................... 2-1

2-1-1 Features .................................................................................................................................... 2-1

2-1-2 Basic Product Preparation Changes ................................................................................... 2-2

2-2 Product Structure ............................................................................................................................. 2-3

2-3 Product Specifications ..................................................................................................................... 2-3

2-3-1 Environment of Usage ........................................................................................................... 2-3

2-3-2 Functional Development Specifications ............................................................................ 2-4

2-4 Installation Method .......................................................................................................................... 2-13

2-4-1 Wired Remote Control Installation ..................................................................................... 2-13

2-4-2 Tracking Your Indoor Unit from the Wired Remote Controller ..................................... 2-15

2-5 Optional Materials Specifications .................................................................................................. 2-16

2-5-1 Accessories .............................................................................................................................. 2-16

3. Disassembly and Reassembly

...................................................................................................

3-1

4. Troubleshooting

.................................................................................................................................

4-1

4-1 Checklist before Diagnosis ............................................................................................................. 4-1

4-1-1 Wired Remote Control Error Codes ..................................................................................... 4-1

4-1-2 Wired Remote Control Error List .......................................................................................... 4-2

4-2 Troubleshooting by Condition ...................................................................................................... 4-3

4-2-1 LCD Display Does Not Appear ............................................................................................. 4-3

4-2-2 Communication Error or Malfunction ................................................................................ 4-4

4-3 How to Download Micom Software .............................................................................................. 4-5

4-3-1 Micom Software Upgrade Kit ............................................................................................... 4-5

4-3-2 Upgrade Kit Switch setting ................................................................................................... 4-5

4-3-3 Micom Software Upgrading Order ..................................................................................... 4-6

5. Exploded Views and Parts List

..................................................................................................

5-1

6. PCB Diagram

..........................................................................................................................................

6-1

7. Wiring Diagram

...................................................................................................................................

7-1

8. Schematic Diagram

...........................................................................................................................

8-1

Samsung Electronics 1

유선리모컨_MWR-WE10_E_33320A(1)_1.indd 1 2010-12-23 오후 5:51:07

1. Precautions

1-1 Precautions for the Service

● Use the standard parts when replacing the electric parts.

- Confirm the model name, rated voltage, rated current of the electric parts.

● Repair the disconnection of HARNESS securely when repairing the break down.

- If there is any connection error, it causes an abnormal noise and incorrect operation.

● In case that you assemble or disassemble the products with laying it on the side, do work on the work cloth.

- If not, the exterior of products can be scratched.

● Remove dust and foreign materials from harness, connection part, and inspection part thoroughly when repairing the break down.

- It protects the danger of fire such as tracking and short.

● Check the assembly status of parts after repairing the break down.

- It should be same as the status before repairing.

1-2 Precautions for the Safety

● Do not pull any electric wires and do not touch an auxiliary power switch with a wet hand.

- There is a danger of electric shock or fire.

● In case any wire or power plug has been damaged, replace it to eliminate any possible danger.

● Do not bend the power cord by force and do not put any heavy object on the power cord.

- There is a danger of electric shock or fire.

● Ground the product if necessary.

- Be sure to ground the product if there is any danger of electric leakage due to water or moisture.

● Be sure to turn off the auxiliary power switch or pull out the power plug during replacement or repair of electric parts.

- There is a danger of electric shock.

1-1

유선리모컨_MWR-WE10_E_33320A(1)_1.indd 1

Samsung Electronics

2010-12-23 오후 5:51:07

2. Product Specifications

2-1 The Feature of Product

2-1-1 Features

 After 11 years, the introduction of the new technology used in the new products required the development of the control part.

– Global 4Way : 4-directional individual control, sensors that detect human presence, automatic cleaning and S-Plasma ion, etc.

– ERV PLUS, AHU : Humidification, supply of outside air and clean-up, etc.

 Integrated control between systems is necessary due to the growth in the market for ventilation products.

– Remote control integrated between the air conditioner and ERV products is necessary.

– Energy saving is realized through interlocking control.

Master wired remote control

Slave wired remote control

∙∙∙

A maximum of two wired remote controls can be connected; these can be controlled as one group. (Master/Slave)

1) PBA: Main PBA

– SAMSUING 3F4A1HJZZ

– FRAM

– COB TYPE FSTN LCD

– Misconnection prevention relay applied

– Diode for button multiple recognitions applied

2) Application S/W

– Basic control

– Schedule control

– Error display

– Individual control of indoor unit

– ERV individual control

– Integrated control of indoor unit and ERV

– Energy Saving function

3) Product materials: Box, Label, Manual

Samsung Electronics

A maximum of 16 “indoor units and ERV” can be connected to the wired remote control as one group and controlled.

2-1

유선리모컨_MWR-WE10_E_33320A(1)_1.indd 1 2010-12-23 오후 5:51:08

Product Specifications

2-1-2 Basic Product Preparation Changes

Item Basic Model (MWR-WE00) Model made (MWR-WE10)

Ass'y Case

Changes

New Equipment

- New hinge

(Hinge used in folder-type

mobile phones)

- New TOP/BOTTOM/DOOR

- Addition of door button part

Ass'y PCB

New MAIN PBA

- Communication/power

terminal B/L

- Electrolytic CAP SMD type

- Display connector connected

Ass'y LCD

Other

1) Development of new inlay

2) Review of new labels (Option, Door and Box)

3) New User/Installation/Service manuals

4) Application of display communicating method with the application of display IC

5) Compatibility of newly developed set

- Global 4Way, ERV Plus and AHU, etc.

6) New addition of User Mode/Service Mode (many)

7) Software for OPTION function

8) Changing daytime reservation function

New Display

- Application of display

communicating IC to expand

the segment

- Separate development of

LCD PBA including backlight

2-2

유선리모컨_MWR-WE10_E_33320A(1)_1.indd 2

Samsung Electronics

2010-12-23 오후 5:51:09

2-2 Product Structure

 External Dimensions

120.0

19.5

(Unit: mm)

2-3 Product Specifications

2-3-1 Environment of Usage

Classification

General Conditions

Installation

Conditions

Power

Installation

Delivery

Installation Method

Other

2 Temperature for usage

3 Humidity for usage

1 Input

2 Installation space

1 Opening

1

1

No

1 Region

Item

2 Form

3 Parts supply

1

Standard temperature and humidity

Domestic

Standard

2 Confirmation of delivery

Inquiries to Service Center

15 ~ 25°C , 35 ~ 65 %

0°C ~ 40°C (Indoor usage)

Humidity 30%RH ~ 90%RH (conditional to no condensation)

12VDC/500mA

Installing on the wall using the exclusive install bracket

Conform to the appointed order

• Confirm with the delivery check sheet, and repair faulty items.

• Follow the method, usage conditions, and notices according to

the user guide. When a problem occurs during this process,

it supported by places that can provide these services.

- Refer to the Installation guide.

- You must refer to Installation guide and User guide.

Remarks

Samsung Electronics 2-3

유선리모컨_MWR-WE10_E_33320A(1)_1.indd 3 2010-12-23 오후 5:51:09

Product Specifications

2-3-2 Functional Development Specifications

 Display

④ ⑤ ⑨ ⑩ ⑪ ⑫ ⑬

⑦ ⑧  

LED Indicator

(Green : Normal / Red : Need to be checked)

Operation On/Off button

⑳ ⑲

Temperature Setting Button

2-4

유선리모컨_MWR-WE10_E_33320A(1)_1.indd 4

● Without opening the cover of your Wired Remote Controller, you can turn the air-conditioner power On/Off or set the desired temperature.

Samsung Electronics

2010-12-23 오후 5:51:10

Product Specifications

Functional Development Specifications

(cont.)

Display

(cont.)

Classification Indication

Air Conditioner

Related Information

Schedule related information

Ventilator

(ERV) related information

Commom function related information

Function

Displays Air conditioner operation

Displays Quiet/Sleep operation

Displays Indoor temperature/Set temperature

Displays discharge temperature control

Displays CO

2

/power consumption

Displays AC fan speed

Displays Blade selection

Displays Air swing(Up/Dn)

Weekly schedule/Holiday setting displays

Displays Current day() or scheduled day(_)

Displays Schedule number

Displays Scheduled device selection

Displays Current time/summer time/scheduled time

Displays Ventilator(ERV) operation

Displays Clean up

Displays Ventilator(ERV) fan speed

Displays Invalid operation /Filter cleaning (filter cleaning period)

Displays Dust box cleaning alert/check/partial locking/full locking

Displays occupancy detection/Exhaust hood/External interconnection control/Auto clean/ Humidifying/Energy saving/Outdoor air supply intake/

Centralized control

Displays S-Plasma Ion

Displays Indoor CO

2

density

Displays Indoor humidity

Samsung Electronics 2-5

유선리모컨_MWR-WE10_E_33320A(1)_1.indd 5 2010-12-23 오후 5:51:12

Product Specifications

Functional Development Specifications

(cont.)

 Buttons

④ ⑪ ⑩ ⑯ ⑲ ⑭ ⑰  

Classification

Button

Operation On/Off button

Mode button

Function

Turns the air conditioner power On/Off

Selects the desired air conditioner operation

Temperature setting button Sets the desired temperature ③

Air Conditioner

Related

Information

Fan speed button

Air Swing button

Temp. button

Quiet/Sleep button

Changes the air conditioner’s fan speed

Changes the air flow direction to move upward or downward

Checks the indoor temperature

Selects Quiet or Sleep operation for the air conditioner

2-6 Samsung Electronics

유선리모컨_MWR-WE10_E_33320A(1)_1.indd 6 2010-12-23 오후 5:51:13

Product Specifications

Functional Development Specifications

(cont.)

Buttons

(cont.)

Classification

Air Conditioner

Related

Information ⑩

Special

Function

Displays

Ventilator

(ERV) Related

Buttons

Button

Humidity button

Blade button

Occupancy detection button

Outdoor air intake

Schedule Button

User Set Button

Function

Turns the AHU humidifying function On/Off

Selects a blade for individual control

Set the power to automatically turn off if there is nobody in the room

Select the AHU Outdoor intake function

Select the schedule setting function

Select the detailed setting function

Move between items or change the item value Navigational buttons

Set button

ESC button

Delete button

Auto Clean button

Save your new settings

Return to general mode from schedule and detailed setting screens

Cancel the schedule setting

Use the auto cleaning function for your air conditioner

CO2/[kWh] button

Filter Reset button

Display the amount of CO

2

and the power consumption

Turn off the filter cleaning displays (filter using time reset)

S-Plasma Ion button

Operation On/Off button

Mode button

Fan speed button

E.Saver button

Clean up button

Choose the S-Plasma Ion function

Turn the Ventilator(ERV) On/Off

Select the desired operation for the Ventilator(ERV)

Change the fan speed for your Ventilator(ERV)

Begin Energy Saving Operation

Select air purification through the in/out load controls

Samsung Electronics

유선리모컨_MWR-WE10_E_33320A(1)_1.indd 7

2-7

2010-12-23 오후 5:51:14

Product Specifications

Functional Development Specifications

(cont.)

 Detailed Settings (User Settings)

Main Menu Sub Menu

SEG Used

1 2 3 4 5 6

1. If you want to set the detailed settings, press the User Set button.

 You will enter the User Set mode, and the [Main Menu] will be displayed.

2. Refer to the Wired Remote Controller’s User Set list on the next page to select the desired menu.

 Using the []/[] buttons, select a main menu number and press the [] button to enter the sub-menu setting screen.

 Using the []/[] buttons, select a sub-menu number and press the [] button to enter the data setting screen.

 Once you have entered the setting screen, the current setting will be displayed.

 Refer to the chart for data setting.

 Using the []/[] buttons, change the settings and press the [] button to move to the next setting.

 Press the Set button to save the setting and exit to the sub-menu setting screen.

 Press the Esc button to exit to general mode.

● While setting the data, you can use the []/[] buttons to set the range of SEG used.

● While configuring the setting, press the Esc button to exit to the sub-menu setting screen without saving the setting.

2-8

유선리모컨_MWR-WE10_E_33320A(1)_1.indd 8

Samsung Electronics

2010-12-23 오후 5:51:15

Product Specifications

Functional Development Specifications

(cont.)

Detailed Settings (User Settings)

(cont.)

Main

Menu

1

Sub menu

2

3

4

5

Temp limits [°C(°F)]

Functions

All locking

Lower Limit

Upper Limit

SEG Used

1

1,2

3,4

1

Lock of Operation

On/Off button

2

Lock of partial button

Lock of operation selection button

Lock of temperature setting button

Lock of fan speed button

3

4

5

Lock of schedule setting button

6

1 Current Temperature Setting (Year, Month, Date) 1,2/3,4/5,6

2 Current Time Setting (Day, Hour, Minute)

Day/AM/

PM/1,2/3,4

1

1

2

Summer Time Use and Setting Methods

Use of summer time (Y/N)

Summer Time Application

Method

Summer time use (Weekly)

Start (? Month, ? th Sunday)

2

1,2/4

3

4

5

Auto stop

Summer time use (Weekly)

End (? Month, ? th Sunday)

Summer time use (Daily)

Start (? Month, ? th Sunday)

Summer time use (Daily)

End (? Month, ? th Sunday)

1,2/4

1,2/3,4

1,2/3,4

6

7

0

Backlight Time Setting/Checking

Use of LED(Green) (Y/N)

Use of LED (Red) (Y/N)

Ventilator(ERV)

Delay Time

Setting/Checking

Ventilator(ERV) Delay

Application (Y/N)

Delay Time

Reset to user mode defaults

(except the current time)

1,2

3

4

1

3,4

1

10/F

03/22

0

30

0

09/22

5

1

1

0

0

0

10/01/01

Friday/

PM/12/00

0

0

03/F

Default

0

16(61)

30(86)

0

0

0

Range

0~12 hours

16~30°C (61~86°F)

18~30°C (65~86°F)

0-Unlock, 1-Lock

0-Unlock, 1-Lock

0-Unlock, 1-Lock

0-Unlock, 1-Lock

0-Unlock, 1-Lock

0-Unlock, 1-Lock

00~99/1~12/1~31

Sun~Sat/

AM~PM/0~12/0~59

0-No use, 1-Use

0- Weekly,1- Daily

1~12th month/

1~4,F (last week)th week

1~12 month/

1~4,F (last week)th week

Jan~Dec/1~31st day

-

-

Month, date

-

-

-

YY,MM,DD

Day, hour, minute

-

-

Unit

1 hour

1°C(1°F)

1°C(1°F)

-

-

-

Jan~Dec/1~31st day

0~30 sec

0-No use, 1-Use

0-No use, 1-Use

0-No use, 1-Use

30~60 minutes

0-No use, 1-Reset

Month, date

1 sec

-

-

-

1 minute

-

Samsung Electronics

유선리모컨_MWR-WE10_E_33320A(1)_1.indd 9

2-9

2010-12-23 오후 5:51:15

Product Specifications

Functional Development Specifications

(cont.)

 Installation/Service Modes

Main Menu Sub Menu

Data bit

1 2 3 4 5 6

1. If you want to use the various additional functions for your Wired Remote Controller, press the Set and Esc buttons at the same time for more than three seconds.

 You will enter the additional function settings, and the [main menu] will be displayed.

2. Refer to the list of additional functions for your Wired Remote Controller on the next page, and select the desired menu.

 Using the []/[] buttons, select a main menu number and press the [] button to enter the sub-menu setting screen.

 Using the []/[] buttons, select a sub-menu number and press the [] button to enter data setting screen.

 When you enter the setting stage, the current setting will be displayed.

 Refer to the chart for data settings.

 Using the []/[] buttons, select the settings. Press the [] button to move to the next setting.

 Press the Set button to save the settings and exit to the sub-menu setting screen.

 Press the Esc button to exit to normal mode.

● While setting the data, you can use the []/[] buttons to set the range of Data bit.

● While configuring the setting, press the Esc button to exit to the setting sub-menu without saving your changes.

2-10 Samsung Electronics

유선리모컨_MWR-WE10_E_33320A(1)_1.indd 10 2010-12-23 오후 5:51:15

Product Specifications

Functional Development Specifications

(cont.)

Installation/Service Modes

(cont.)

● If your indoor machine does not support the setting mode, then you may not be able to edit the settings or apply your changes.

Main menu

1

2

3

Sub menu

1

2

Function

Wireless remote controller Option setting/checking (1)

Wireless remote controller Option setting/checking (2)

Cooling/Heating selection

Use of wireless remote controller

MAIN/SUB wired remote controller

Temperature unit

Temperature sensor selection

Use of average temperature

Use of Auto mode

Temperature display

AC On/Off button function 5

1

2

1

2

3

4

3

Blade setting/checking

Lock of Blade1

Lock of Blade2

Lock of Blade3

Lock of Blade4

Use of By-Pass mode

4

ERV option

Setting/checking

Use of Auto mode

Use of air purification mode

2

3

Use of external control

Temperature control reference

4

1,2,3

5 Room Temperature compensation

6

7

Temperature compensation value 4,5,6

Number of indoor units

Number of connected units

Number of ERVs

Temperature increment/decrement (°C only)

1,2

3,4

1

3

4

1

1

2

0 Factory option setting 1

5

6

Software code

Software version

Indoor unit room temperature

Indoor unit EVA IN temperature

Indoor unit EVA OUT temperature

Indoor unit EEV step

Indoor unit option checking (1)

Use of central control

Use of drain pump

Use of electric heater

Indoor unit option checking (2)

Use of hot water coil

Use of external control

Use of RPM compensation

Filter time

Heating temperature compensation

EEV stop step in heating

1,2,3

1,2,3

1

2

3

1~6

1~6

1,2,3

1,2,3

2

3

4

1

4

5

1

2

3

4

2

3

4

Data bit

Factory setting

1 0

1

0

0

0

0

1

0

Description

0 – Cooling/Heating,

1 – Cooling only

0 – No use, 0 - Use

0 –MAIN, 1- SUB

0 – Celcius(°C), 1 – Fahrenheit(°F)

0 – Indoor unit,

1 – Wired remote controller

0 – No use, 0 - Use

0 – No use, 0 - Use

0 – Set temperature,

1 - Room temperature

0 – Indoor unit + ERV,

1 – Indoor unit only,

2 – ERV only,

0 – Unlock, 1 – lock

0 – Unlock, 1 – lock

0 – Unlock, 1 – lock

0 – Unlock, 1 – lock

0 – No use, 1 - Use

0 – No use, 1 - Use

0 – No use, 1 - Use

0 – No use, 1 - Use

-9 ~ 40(°C)

-9.9 ~ 9.9(°C)

0 ~ 16

0 ~ 16

0-1°C, 1-0.5°C, 2-0.1°C

0 – Unchanged

1 – Factory setting

Software code

Software version

Room temperature

EVA IN temperature

EVA OUT temperature

EEV step

0 – No use, 1 - Use

0 – No use, 1 - Use

0 – No use, 1 - Use

0 – No use, 1 - Use

0 – No use, 1 - Use

0 – No use, 1 - Use

0 – 2000 hours, 1 – 1000 hours

0-2°C, 1-5°C

0 – 1/80 steps, 1 – 80

0

-

0

0

-

0

0

0

0

0

0

0

0

0

0

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

0.1(°C)

0.1(°C)

-

-

-

-

-

-

-

-

-

-

-

-

°C

-

°C

°C

-

-

-

-

-

-

-

-

Unit

-

-

-

-

-

-

-

-

Samsung Electronics 2-11

유선리모컨_MWR-WE10_E_33320A(1)_1.indd 11 2010-12-23 오후 5:51:15

Product Specifications

Functional Development Specifications

(cont.)

Installation/Service Modes

(cont.)

Main menu

4

Sub menu

1

2

3

1

Function

Indoor unit main address checking

Indoor unit main address setting (outdoor unit reset is needed to set)

Indoor unit RMC address setting/checking

Indoor unit option code setting/checking

Indoor unit option switch setting/checking

Setting/checking the differential value

RPM setting/checking

AHU setting/checking filter performance

5

6

0

2

3

1

2

3

4

5

AHU discharge temperature setting/ checking

Fresh Duct discharge temperature checking humidity setting/checking

Use of discharge temperature control

Cooling discharge temperature

Heating discharge temperature

Cooling discharge temperature

Heating discharge temperature

Use of cold air prevention

Use of humidification when Heating thermo off ERV Plus setting/checking

ERV Plus temperature setting/checking

Use of fan operation in Defrost

Use of humidification when Heating

Cooling

Heating

ERV Plus Auto mode temperature setting/ checking

Set temperature

Set temperature difference

Setting/checking the compensating temperature A under the Heating

EEV control for ERV Plus

Checking the compensating temperature B under the Heating

EEV control for ERV Plus

ERV Plus fan RPM setting/checking

Air supply RPM

Air exhaustion RPM

Factory setting

1)* Data1 is the option setting page. / Data2~6 stand for the option codes.

Option Setting Page Option Code

1 2 3 4 5 6

2

1,2

3,4

3

4

1,2

3,4

1,2

6

1

3,4

5,6

1,2

3,4

1

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

1,2

3,4

5

3,4

1,2

3,4

1

Data bit

1,2

3,4

5,6

1)*

Factory setting

-

-

-

-

1)* -

-

-

-

-

-

-

-

Description

Main address (0~63)

Main address (0~63)

RMC address (00H~2FH)

Indoor unit option code (24 bits)

Refer to the indoor unit installation manual for details

0~30

0~25

0 – Pre

1 – Medium performance

2 –High performance

0 – 30, 1 - 40, 2 - 50

0 – No use, 1 - Use

10 ~25°C

28 ~43°C

13~25

18~30

0 – No use, 1 - Use

0 – No use, 1 - Use

0 – No use, 1 - Use

0 – No use, 1 - Use

15~30°C

15~30°C

15~30°C

5~15°C

0~10°C

0 – Non use of humidifier(0°C)

1 – Use humidifier(10°C)

10~27 RPM

10~27 RPM

0 – No use, 1– Factory setting

1

1 RPM

-

-

1 RPM

1 RPM

-

Unit

-

-

-

-

-

-

1°C

1°C

-

-

1°C

1°C

1°C

-

-

1°C

1°C

1°C

1°C

-

You can set the 24 digits options.

Page

PAGE 1 1 st ~5

Option Settings th digit option setting

How to Move Between Pages

Press the [>] button to go to PAGE 2.

Page

PAGE 4 16

PAGE 2 6 th

PAGE 3 11 th

~10

~15 th th

digit option setting

digit option setting

Press the [>] button to go to PAGE 3.

Press the [>] button to go to PAGE 4.

PAGE 5 21 th

Option Settings

~20 th digit option setting

How to Move Between Pages

Press the [>] button to go to PAGE 5.

th ~24 th digit option setting -

 Regardless of Celsius and Fahrenheit setting, service mode setting is available only with Celsius.

 Maximum no. of Connections: A maximum of 16 "indoor units + ERV" can be connected.

 Separate control between indoor unit and ventilation system (ERV) is possible.

 Integrated control between indoor unit and ventilation system (ERV) is possible.

2-12 Samsung Electronics

유선리모컨_MWR-WE10_E_33320A(1)_1.indd 12 2010-12-23 오후 5:51:16

2-4 Installation Method

2-4-1 Wired Remote Control Installation

1. Push the two hooks at the bottom of your Wired Remote Controller at the same time, and then pull up the front cover to separate it from the rear cover.

Push the two hooks at the same time.

● Insert a flat head screwdriver into the square groove in the upper area of the hook to disassemble it easily.

2. Arrange the power cable and the communication cable so that they fit in the housing along the edges of the rear cover.

If you need more space for the wiring work, you can take it off.

<When the cable is not concealed>

15cm

10cm

<When the cable is concealed>

Samsung Electronics

유선리모컨_MWR-WE10_E_33320A(1)_1.indd 13

2-13

2010-12-23 오후 5:51:16

Product Specifications

Wired Remote Control Installation

(cont.)

3. Using more than two screws, firmly affix the rear cover of the remote controller to the wall, and then connect the power(V1, V2) and communication cables(F3, F4), making sure these cables have reasonable length, to the terminal at the back of the cover.

10mm or more

10mm or more

10mm or more

Screw hole

50mm or more

Rear cover

 Before fixing the rear cover, secure at least

10mm space of upper side, left side,

right side, and 50mm space of bottom side.

 You must fit the screws into

the screw holes.

Indoor unit

Wire (not supplied)

Wired Remote

Controller

PCB terminal

Front cover

 Do not tighten the screws on the

PCB terminal with excessive force.

4. Reassemble your Wired Remote Controller.

● Align the controller with the upper groove first, and insert it by turning it downward as shown in the figure.

After assembly, check and confirm that no wires are stuck in the gap between the rear and front cover.

2-14

● When installing a Wired Remote Controller by using a cable longer than 10m, you must install the communication cable and the power cable separatery. (Electrical interference can cause your Wired Remote Controller to malfunction.)

● When installing your Wired Remote Controller on the wall, consider the size of the wire hole, and select a wire with a proper thickness.

● Wire that is connectable to Wired Remote Controller PCB.

- If you install the Wired Remote Controller by reclaiming, install it according to U-terminal cable specification.

- If you install the Wired Remote Controller by using four pieces of PVC wire, remove the 30cm of the sheath of the cable and install it only with the four pieces of wires. (Recommended specification: AWG21)

● The following are the specs of the compression ring terminal connected to your Wired Remote Controller PCB.

W Stud

F

L

E

G

D

Range of Permitted Wires

AWG

22~16 mm 2

0.25~1.65

Rated

Size mm 2

1.5

Stud

Size mm

3

Basic Size (mm) t øD G E F W L

0.7

3.8

10.0 4.5

6.5

6.0 21.2

 Maximum distance for connecting communication and power cable: 100m t

● Screws on the PCB terminal must be tightened with less than 6N-cm tightening torque. If the tightening torque is greater, it may damage the screw thread.

Samsung Electronics

유선리모컨_MWR-WE10_E_33320A(1)_1.indd 14 2010-12-23 오후 5:51:17

2-4-2 Tracking Your Indoor Unit from the Wired Remote Controller

Product Specifications

Indicates tracking in progress

Displays the total number of units searched

1. Tracking of your Wired Remote Controller will automatically start when you turn on the power after installation.

2. If you want to perform tracking again after installation, then press the Esc and Delete buttons at the same time for more than five seconds.

The system will reset, and tracking will start again.

3. During tracking, the total number of currently searched indoor units and ventilator(ERV) will be displayed.

● If you want to perform tracking again after installation, then press the Esc and Delete buttons at the same time for more than five seconds.

● Only the master Wired Remote Controller can display the total number of indoor units and ventilator(ERV).

- Slave Wired Remote Controllers do not display the total number of units.

Samsung Electronics

유선리모컨_MWR-WE10_E_33320A(1)_1.indd 15

2-15

2010-12-23 오후 5:51:17

2-5 Optional Materials Specifications

2-5-1 Accessories

Item Description

Wired remote control

Cable tie

Cable clamp

Cable clamp

User Manual

Installation Manual

U-terminal

Code No.

DB93-11251B

Q’ty Remark

1

DB65-10099B 2

DB65-10074E 3

6002-000474 5

DB98-32810A 1

DB98-32811A 1

DB60-00444A 6

2-16

유선리모컨_MWR-WE10_E_33320A(1)_1.indd 16

Samsung Electronics

2010-12-23 오후 5:51:17

MEMO

Samsung Electronics

유선리모컨_MWR-WE10_E_33320A(1)_1.indd 17

2-17

2010-12-23 오후 5:51:17

3. Disassembly and Reassembly

No

1

Image Procedure

Push the2 fixing structures at the bottom inwards, and then pull up the front cover to separate it from the rear cover.

(This step is easy when using a flathead screwdriver.)

When assembling, assemble the upper part first as in the

picture, and then insert the bottom hook.

2 Separate the door cover by pushing the bottom-right part of the product sideways.

For assembling or dismantling, leave the door cover

open about 130 degrees as in the image to do the work.

Otherwise, the hinge may be incorrectly assembled,

resulting in faulty operation.

3-1

유선리모컨_MWR-WE10_E_33320A(1)_1.indd 1

3-1

Samsung Electronics

2010-12-23 오후 5:51:18

3-2

No

3

Image

Disassembly and Reassembly

Procedure

Unscrew the 6 screws assembled in the front cover to separate the PBA.

4

5

Separate the PCB cover and the LCD connector to detach the

PBA from the front cover.

Separate the attached rubber keypad.

3-1

Samsung Electronics

유선리모컨_MWR-WE10_E_33320A(1)_1.indd 2

3-2

3-2

2010-12-23 오후 5:51:18

4. Troubleshooting

4-1 Checklist before Diagnosis

4-1-1 Wired Remote Control Error Codes

● The error codes of the wired remote control and the products connected to the remote are shown on the LCD display.

<LCD Display>

 Errors Found in Indoor Unit/Outdoor Unit (Product Group Indication: A)

The product address where the error has occurred and the occurred error code are indicated, displayed one after another.

Example) 101 error occurred in No. 28 indoor unit.

Indoor Unit

 Error Found in Wired Remote Control

The product address where the error is occurred and the occurred error code are indicated, displayed one after another.

Example) 121 error occurred in No. 28 ventilation system (ERV).

Ventilation system (ERV)

 Error Found in Wired Remote Control

Only the occurred error code is indicated. (No indication of the address where error occurred.)

Example) 601 error occurred in wired remote control.

4-1

유선리모컨_MWR-WE10_E_33320A(1)_1.indd 1

Samsung Electronics

2010-12-23 오후 5:51:18

Troubleshooting

4-1-2 Wired Remote Control Error List

Error Display Contents

Communication error between wired remote control ↔ indoor unit/ventilation system (ERV)

(When communication has stopped for 3 minutes after detecting indoor unit/ventilation system

(ERV) and wired remote control)

Communication error between wired remote control ↔ indoor unit/ventilation system (ERV)

(When communication has stopped for 3 minutes after detecting indoor unit/ventilation system

(ERV) and wired remote control)

Tracking 10 or more errors between wired remote control ↔ indoor unit/ventilation system (ERV)

- COM1, COM2 crossing connection error

- When wired remote control is connected to indoor unit COM1 (F1, F2) terminal

- Multiple master error

- Error occurred during installation when two wired remote controls are both set as masters in one communication line (This is not possible to detect if the communication polarity is connected in reversed polarity.)

Remark

When using master remote control

Ventilation system (ERV) is not installed in case of outside gearing.

Indoor unit is not installed in case of outside gearing (when the indoor unit is not detected after outside gearing option setting and tracking are finished).

- Exceeded maximum no. of installation for indoor unit/ventilation system (ERV) (16 equipment devices)

- A reset is required after checking the number of indoor unit/ventilation system (ERV) installations

Can be connected by both master and slave wired remote controls

In case of using outside gear control

- Mixed installation error for °C/°F indoor unit

- Error occurs when mixed indoor units of °C and °F settings are installed

Only detected by the master wired remote control

- Wired remote control °C/°F setting error

- This error occurs if the indoor unit is set in °C while the wired remote control is set in °F or vice versa.

This error occurs when the option settings of the master and slave wired remote controls are different from each other.

Slave wired remote control installation error (when two slave wired remote controls are installed)

Normal operation option setting error (when normal operation is selected with the wired remote control for a ventilation system (ERV) that does not support the normal operation option)

Automatic operation option setting error (when automatic operation is selected with the wired remote control for a ventilation system (ERV) that does not support the automatic operation option)

Temperature sensor open/short error

Only detected by products with a temperature sensor

- FRAM READ/WRITE error

- Damper error [error is detected when there is no input for 100 seconds (time for about 5 revolutions) during damper output]

● Please refer to the Installation guide of each equipment device for the error codes used for the indoor unit, the outdoor unit, and the ventilation system (ERV).

Samsung Electronics 4-2

유선리모컨_MWR-WE10_E_33320A(1)_1.indd 2 2010-12-23 오후 5:51:19

4-2 Troubleshooting by Condition

4-2-1 LCD Display Does Not Appear

Start

Is the connection of the

ASS'Y PBA (DB93-11243A) power cable normal?

Yes

Are the voltages for both the terminals of BD01 input side12V?

Yes

Is the IC03 (7805) output terminal 5V?

Yes

Is the LCD connector properly connected?

Yes

Change of LCD modules

No Check the connection status of the power cable (V1, V2) with ASS'Y PBA (DB93-11243A).

No

GND

12V(-12V)

Check the power of the indoor unit.

GND

5V

No

Change 5V REGULATOR troubled ASS'Y PBA

(DB93-11243A).

No

Change LCD WIRE

No

Change PCB_ASS'Y (DB93-11243A)

4-3

Is it working normally after the change?

End

Yes

Samsung Electronics

유선리모컨_MWR-WE10_E_33320A(1)_1.indd 3 2010-12-23 오후 5:51:19

Troubleshooting

4-2-2 Communication Error or Malfunction

Start

Is the ASS'Y PBA (DB93-11243A) communication cable properly connected?

Yes

Is the resistance between the 2 terminals of ASS'Y PBA (DB93-11243A)

C302 at least 200KΩ?

Yes

Is the resistance between the upper part of ASS'Y PBA (DB93-11243A)

C302 and GND at least 100KΩ?

Yes

Is the resistance between

the lower part of ASS'Y PBA (DB93-11243A)

C302 and GND at least 100KΩ?

Yes

Check the communication of the indoor unit connected to wired remote control (this is not a problem with the wired remote control).

End

Samsung Electronics

No

No

No

No

Check the connection status of the communication cable (F3, F4) and ASS'Y PBA

(DB93-11243A).

Change ASS'Y PBA (DB93-11243A)

GND

200KΩ

Change ASS'Y PBA (DB93-11243A)

GND

100KΩ

Change ASS'Y PBA (DB93-11243A)

GND

100KΩ

4-4

유선리모컨_MWR-WE10_E_33320A(1)_1.indd 4 2010-12-23 오후 5:51:20

4-3 How to Download Micom Software

4-3-1 Micom Software Upgrade Kit

G-man programmer

Power Cabel

4-3-2 Upgrade Kit Switch setting

Upgrade Kit switch

Upgrade Kit USB-RS232 Cable

4-5

유선리모컨_MWR-WE10_E_33320A(1)_1.indd 5

SW 3, 4, = OFF SW 1, 2 = Don't care SW 1, 2 = OFF

Indise switch

SW 1 position

SW 2 position

State

OFF

ON

If switch setting is wrong, then upgrading fails.

Samsung Electronics

2010-12-23 오후 5:51:20

Troubleshooting

4-3-3 Micom Software Upgrading Order

1) Connect the upgrade kit to the PCB download port.

1

2

2) Set the G-man programmer (download program).

2 3

3

① USB-RS232 Cable

② Power Cable

③ 10-pin flat cable

5

4

1. Only SoC software version from Mar. 14 2008 or later can be used.

2. Can't be upgraded with empty software in the Soc.

- Select a COM port and set the Baud rate at 115200bps.

- Select “Indoor.”

- Select the Micom software to download by pressing the "Select File" button.

- Start downloading by pressing the "Download” button.

Samsung Electronics 4-6

유선리모컨_MWR-WE10_E_33320A(1)_1.indd 6 2010-12-23 오후 5:51:20

Troubleshooting

Micom Software Upgrading Order

(cont.)

3) The download is successful if the “Successful” message appears with the upgrade status.

1

2

4) If the "Download has failed" message appears, then check the connection status and start again.

1

4-7

유선리모컨_MWR-WE10_E_33320A(1)_1.indd 7

Samsung Electronics

2010-12-23 오후 5:51:21

Micom Software Upgrading Order

(cont.)

5) Measures to Take if a “Trying to Connect” Message Repeatedly Appears

1

- Check if the connection is normal by pressing the “Check Connection” button.

1

Troubleshooting

2

6) Troubleshooting and Solution for Other Problems

- Bootloader of SOC Micom is damaged. → Change PCB.

- PBA is damaged. → Change PBA.

- Problem found in the upgrade kit. → Change the upgrade kit.

- Problem found in a cable (USB/Power/10-pin flat cable) → Change the relevant cable.

Samsung Electronics

유선리모컨_MWR-WE10_E_33320A(1)_1.indd 8

2

4-8

2010-12-23 오후 5:51:21

5. Exploded Views and Parts List

1

1-3

1-5-4

1-5-3

1-5-2

1-4

1-2

1-5

1-7

1-1

1-6

1-5-1

1-5-5

3

5

7

2

6

4

5-1

유선리모컨_MWR-WE10_E_33320A(1)_1.indd 1

Samsung Electronics

2010-12-23 오후 5:51:21

Parts List

No.

1

1-1

1-2

1-3

1-4

1-5

1-5-1

1-5-2

1-5-3

1-5-4

1-5-5

1-6

1-7

2

5

6

3

4

7

Code No.

Description

DB90-06126B ASS'Y CASE-TOP

DB61-04651A CASE-TOP

DB64-02627B INLAY-BUTTON

DB63-02816A COVER-HINGE

DB61-04729A HINGE-DOOR

DB90-06127B ASS'Y COVER-DOOR

DB63-02815A COVER-DOOR

DB61-04671A GUIDE-LED

DB64-02600A BUTTON-KEY

DB63-02840A COVER-BUTTON

DB98-33083A ASS'Y-DOOR LABEL

DB64-02599A WINDOW-DISPLAY

DB02-00044A TAPE ETC-PROTECTOR

DB61-04652A CASE-BOTTOM

DB93-11266B ASS'Y DISPLAY-WE10

DB93-11243A ASS'Y PCB MAIN-SOLUTION

DB64-02608B BUTTON-RUBBER KEY

DB63-02867A COVER-PCB

6001-001413 SCREW-MACHINE

ASS'Y

ABS

PC

ABS

STS304

ASS'Y

ABS

PC

ABS

ABS

ART PAPER

PC

PET

ASS'Y

ASS'Y

ASS'Y

SILICON

ABS

M2,L5

Specification

Exploded Views and Parts List

Q'TY

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

6

SA/SNA

SA

SNA

SNA

SNA

SNA

SNA

SNA

SNA

SA

SA

SNA

SNA

SNA

SA

SA

SA

SNA

SA

SA

Samsung Electronics

유선리모컨_MWR-WE10_E_33320A(1)_1.indd 2

5-2

2010-12-23 오후 5:51:21

6. PCB Diagram

2 1 10 4 5

3 6

MICOM

S3F4H Micro controller

② FRAM

EEPROM memory

9

③ Clock IC

Clock for scheduler

⑤ 485 Communication part

485 Communication with indoor unit

⑥ Battery

Supply of power in the case of power suspension for Clock IC

⑦ 5V Power

⑨ Temperature sensor ⑩ LCD Control IC

8 7

④ Relay

Prevents misconnection of communication/power

⑧ Doide

In charge of non-polar function for power

6-1 Samsung Electronics

유선리모컨_MWR-WE10_E_33320A(1)_1.indd 1 2010-12-23 오후 5:51:21

7. Wiring Diagram

Development download connector

(ASPRO)

Service download connector

LCD connector

(backlight power and LCD data I2C communication)

Communication connector (485 communication)

Power connector

(12V)

Temperature sensor connector

Samsung Electronics

유선리모컨_MWR-WE10_E_33320A(1)_1.indd 1

7-1

2010-12-23 오후 5:51:21

8. Schematic Diagram

Samsung Electronics

유선리모컨_MWR-WE10_E_33320A(1)_1.indd 1-2

This Document can not be used without Samsung’s authorization.

Power Circuit Part(DC12V)

485 Communication

Download Part

Switch Part

Reset IC Part

Temp. Sensor Part

EEPROM Part

2010-12-23 오후 5:52:04

GSPN(Global Service Partner Network)

Area

North America

Web Site http://service.samsungportal.com

Latin America

CIS

Europe

China http://latin.samsungportal.com

http://cis.samsungportal.com

http://europe.samsungportal.com

http://china.samsungportal.com

Asia

Mideast & Africa http://asia.samsungportal.com

http://mea.samsungportal.com

This Service Manual is a property of Samsung Electronics Co., Ltd.

Any unauthorized use of Manual can be punished under applicable

International and/or domestic law.

© Samsung Electronics Co., Ltd. Dec. 2010.

Printed in Korea.

Code No. DB98-33320A(1)

유선리모컨_MWR-WE10_E_33320A(1)_co.indd 2 2010-12-23 오후 5:50:29