Annexure-K Technical Specifications CAT

Annexure-K Technical Specifications
CAT-6 Cable (Unshielded Twisted Pair Category 6 Cable)
Sr.
No
Minimum Technical Specification
(A)
1
MAKE: D-Link, Tyco, R & M, Systimax
2
Features
Category 6 Unshielded Twisted 4 pair shall be
compliant with ANSI/TIA/EIA-568-C.2, ISO/IEC
11801, CENELEC EN50173-1, CENELEC EN
50288-5-1, IEC 61156-6, IEC 60332-1-2 and UL
444.
Should support 1000BASE-T (1 Gigabit Ethernet)
standard.
Category 6 should operate on bandwidth up to
250MHz as per standard and tested up to 600MHz.
Category 6 can run 1000BASE-T at 100 meters.
Category 6 cable should have UL listed and ETL
verified and ERTL Testing and ROHS.
3
Construction Characteristics
The conductors should be twisted in pairs with four
pairs contained in outer PVC jacket.
Four twisted pairs separated by internal X shaped,
full separator. Half shall not be accepted.
Insulation material should be FR-HDPE.
Maximum average thickness should be 0.22mm and
minimum at any point should be 0.18mm.
Sheath material should be CMR PVC.
Specification
offered by
Bidder
[B]*
Compliance
(Yes/No)
[C]*
Compliance If
(NO) mention
deviation
[D] *
4
Mechanical Characteristics
Copper conductor diameter should be
0.56±0.005mm (23 AWG).
Cable should have high density polyethylene
insulation.
Cable outer diameter should be 6.1 mm nominal.
Pulling force should be 11.5Kg.
Category 6 cable tensile strength should be ˃400N
(90lbf).
Minimum bend radius of Category 6 cable should be
25mm (1in).