TEMPERATURE AND HUMIDITY TRANSMITTERS with 4

TEMPERATURE AND HUMIDITY
TRANSMITTERS with 4-20mA output
temperature*relative humidity*dew point temperature*
absolute humidity*specific humidity*mixing ratio*specific enthalpy
Pxxxx Txxxx
Transmitter T1110, T3110
Transmitter T3113,length 150mm
Transmitter T3117,length 700mm
Transmitter T3111, T3111P
Transmitter T3113D - duct mount
Programmable temperature and humidity transmitters are equipped with temperature and relative humidity sensors.
Measured values are also converted to other humidity interpretation - dew point temperature, absolute humidity, specific
humidity, mixing ratio or specific enthalpy. Degrees Celsius and Fahrenheit are user selectable. Transmitters are available
in wall-mount, duct-mount and bar types. Also types with T+RH probe on a cable are available. Transmitter contains a
microprocessor based control circuitry in a durable plastic case with connection terminals and sensors in a stainless steel
mesh filter. Humidity transmitters are also available with two galvanic isolated 4-20mA outputs. Configuration of outputs
and output range are user adjustable. Computerized design ensures temperature compensation of the humidity sensor
and fail indication. State-of-the-art capacitive polymer sensor ensures excellent calibration long term stability, inertia
against water and condensation.
TECHNICAL PARAMETERS
Relative humidity operating range:
Accuracy of relative humidity output:
Accuracy of temperature output:
Accuracy of temperature output of T4111:
Accuracy and range of dew point temperature output:
Accuracy and range of absolute humidity output:
Accuracy and range of specific humidity output:
Accuracy and range of mixing ratio output:
Accuracy and range of specific enthalpy output:
Temperature operating range of the case:
Temperature operating range of the LCD display:
Range of temperature compensation of RH sensor:
Current outputs - two-wire connection:
Configuration of outputs and output range:
Filtering ability of sensor cover:
Power:
Dimensions of the case with electronics (W x H x D):
Protection of the case with electronics:
40
0 to 100%
±2.5% relative humidity from 5 to 95% at 23°C
±0.4°C from -30 to +100°C, ±0.4% from reading over +100°C
±0.15°C + 0.1% from adjusted output span (without temperat. probe)
±1.5°C at ambient temperature < 25°C and RH>30%,range-60 to+80°C
±3g/m3 at ambient temperature T < 40°C, range 0 to 400 g/m3
±2g/kg at ambient temperature T < 35°C, range 0 to 550 g/kg
±2g/kg at ambient temperature T < 35°C, range 0 to 995 g/kg
± 3kJ/kg at ambient temperature T < 25°C, range: 0 to 995 kJ/kg
-30 to +80°C
readable to +70°C,recommended to switch off LCD over +70°C
-30 to +125°C
4-20mA, galvanic isolated with dual-output models
user adjustable from the PC
0.025mm
9-30Vdc
89 x 73 x 39.5 mm
IP65 electronics, IP40 sensors
TEMPERATURE AND HUMIDITY
TRANSMITTERS with 4-20mA output
TRANSMITTERS ARE AVAILABLE IN THE FOLLOWING MODELS:
MODEL
MAXIMUM
MEASUR.
RANGE OF
VALUE
TEMPERATURE
MEASUREMENT
STEM
LENGTH
OUTPUT 1
75mm
75mm
150mm
700mm
probe cable
1,2,4m
0-100%RH
2)
0-100%RH
2)
0-100%RH
2)
0-100%RH
2)
0-100%RH
RH+T
up to
25bars
-30 to +80°C
-30 to +80°C
1)
-30 to +125°C
1)
-30 to +125°C
1)
-30 to +105°C
probe including
cable
1)
-30 to +105°C
probe including
cable
probe cable
1,2,4m
0-100%RH
T
T
-30 to +80°C
-200 to +600°C
53mm
-
-30 to +80°C
-200to+600°C
RH
RH+T
RH+T
RH+T
RH+T
T1110
T3110
T3113
T3117
T3111
T3111P
T0110
T4111
2)
OUTPUT 22)
2)
2)
-30 to +80°C
2)
-30 to+125°C
2)
-30 to+125°C
2)
-30 to+105°C
2)
-30 to+105°C
2)
-
2)
NOTE
outdoor and indoor use
outdoor and indoor use
duct mount, versions - T3113, T3113D
bar type
T+RH probe with 1m cable.
Diameter 18mm, length 90mm.
Cable lengths 2m or 4m available.
Compressed air up to 25 bars.
T+RH metal probe with 1m cable. Cable
lengths 2m or 4m available. Diameter
18mm, length 110mm, thread G1/2.
outdoor and indoor use
transducer for external Pt1000 probes,
output range adjustable by the user
2) Any value - temperature, relative humidity, dew point
temperature, absolute humidity, specific humidity, mixing ratio or
specific enthalpy can be assigned to each output of dual output
transmitters. Also identical value can be assigned to both outputs.
The T1110 transmitter has only relative humidity output.
Outputs are adjusted to maximum range from the manufacturer.
Output range is user adjustable from the PC by means of the
optional cable SP003 - see photo. Free configuration program for
transmitter adjustment is ready to download anytime from
www.cometsystem.cz.
If different adjustment of outputs and output ranges are required,
please specify required output values (RH, T, Tdp, ..) and required
ranges.
Ordering example: Transmitter T3110, output 1: RH 10 to 90%,
output 2: temperature 0 to 35°C
Ordering example: Transducer T4111, output: -100 to +30°C
Pxxxx Txxxx
1) Maximum temperature only at the measuring end with sensors. Maximum temperature +105°C
for T3111 with cable probe is allowed also for the cable. Near plastic case with electronics maximum
temperature is +80°C. Humidity at temperature over +85°C is limited - see the graph below.
Thermometer T0110
Transducer T4111
relative humidity
relativní vlhkost [%]
100
90
80
70
60
Optional cable SP003 for transmitter adjustment
50
40
+I1
-I1
30
20
U0
10
0
-30
-20
-10
0
10
20
30
40
50
60
70
80
90
100 110 120 130
temperature
teplota [°C]
+
=-
Uss
Rz
SENSOR
Application wiring of transmitter with one 4-20mA output
Included accessory: Traceable calibration certificate from
the manufacturer, instruction manual. Calibration certificate with declared
metrological traceability of etalons is based on requirements of EN ISO/IEC
17025 standard.
Free program TSensor for configuring of the transmitter is ready to
download from www.cometsystem.cz.
Comet probes with Pt1000 sensors are directly connectable to T4111
transducer - see further. There is a symbol /0 behind probe name.
Other optional accessory: see further
Transmitters are directly compatible with sixteen channel
Comet data acquisition system MSx.
+I1
-I1
+I2
-I2
SENSOR
U0
+
U0
Rz2
=-
+
=-
Uss
Uss
Rz1