Installation Guide
GE
Lighting
Lumination LED Luminaires
TM
LAL Series Pendant Accessory Kit
BEFORE YOU BEGIN
Read these instructions completely and carefully.
WARNING/AVERTISSEMENT
RISK OF ELECTRIC SHOCK
• Turn off power before inspection, installation or removal.
• Properly ground electrical enclosure.
RISK OF FIRE
• Follow all NEC and local codes.
• Use only UL approved wire for input/output connections.
• Minimum size 18 AWG (0.75mm2).
• Type IC, inherently protected.
RISQUES DE DÉCHARGES ÉLECTRIQUES
• Coupez l’alimentation avant d’’inspecter, installer ou déplacer le luminaire.
• Assurez-vous de correctement mettre à la terre le boîtier d’alimentation électrique.
RISQUES D’INCENDIE
• Respectez tous les codes NEC et codes locaux.
• N’utilisez que des fils approuvés par UL pour les entrées/sorties de connexion.
Taille minimum 18 AWG (0.75mm2).Minimum size 18 AWG (0.75mm2).
• Type IC, protection inhérente
Save These Instructions
Use only in the manner intended by the manufacturer. If you have any questions, contact the manufacturer.
Provided in the Package
• Pendant bracket (2)
• Suspension cable (2)
• 8-18 x 3/8” screws for bracket installation (8 pieces)
• AC line power cord and grommet
• Dimming power cord and grommet
Tools and Components Required
• For end cover install: Philips headed screwdriver
• Rigid (RMC) or flexible (FMC) metal conduit for supply connection
• UL/cUL approved twist-on-wire connectors, min. 18 AWG
Prepare Electrical Wiring
Electrical Requirements
• The LED driver must be supplied with 120-277 VAC, 60 Hz and connected to an
individual properly grounded branch circuit. Use min. 600V 75°C supply conductor.
Grounding Instructions
• The grounding and bonding of the overall system shall be done in accordance
with National Electric Code (NEC) Article 600 and local codes.
imagination at work
Electrical Connections
1
Carefully unpack unit from its packaging.
Properly inspect for defects before installing.
Wear work gloves to prevent dirt and oil from
being transferred to the luminaire.
2
Remove end covers from all fixtures.
Violet
Gray
Green/Yellow
White
Black
3
Remove holes from knockout plate to make AC
connections. Connect UL-approved conduit.
4
Connect to the AC line with twist-on wire
connectors: Black to live, White to neutral,
Green/yellow to ground, Gray to 1-10V dimming,
Violet to common for 1-10V and DALI dimming.
Use a star washer under
one of the screws to
ensure ground continuity
Through wiring
5
Push wires and connectors into fixture.
6
Fasten the end cap which was removed before.
Attach to luminaire with two 8-18 x 3/8” screws.
Always use a star washer under one of the screws
to ensure ground continuity. Use retained end
covers, star washers and screws.
Wiring Diagrams
Optional Installation: 1-10 Volt Dimming or DALI Lighting Controller
Follow diagram A for 1-10V, diagram B for DALI.
At output side of LED driver, make appropriate connections using twist-on wire connectors.
Follow lighting controller installation instructions.
Line (black)
Neutral (white)
Ground (green)
(1-10) + (violet)
Line
Line (black)
Neutral
Neutral (white)
Ground
(1-10) - (gray)
A
(1-10V) -
PSU
Ground (green)
DALI 1 (violet)
DALI/(1-10V) +
1-10V wiring diagram
Line
Neutral
Ground
DALI 2 (orange)
B
(1-10V) -
PSU
DALI/(1-10V) +
DALI wiring diagram
Pendant Bracket Installation
When the pendant accessory kit is supplied the product must be installed by the following instructions.
1
Place bracket in top channels of the luminaire.
Use two per fixture. Use provided screws to attach
bracket to luminaire. Use two screws per bracket.
Squeeze tip to adjust
3
To adjust height and to level fixture, squeeze tip of
the gripper and pull the suspension cable to the
desired height. Clip the cable with cable cutters to
finish the appearance.
2
Use suspension cable to attach through hole in
bracket to connect to luminaire. Attach gripper
to pendant bracket through hole in bracket with
provided bolt and nut. Use suspension mounting
appropriate for ceiling type.
Ceiling Mounting Method Installation
Loop Method
• Form loop with aluminum sleeve for looping around
building structural member.
• Suitable for looping around building structural member
such as bar joists, strut, purlins, beams roof trusses, etc.
NOTE: Rigid conduit and appropriate conduit
fittings must be used according to local building
codes and safety regulations.
Structural member
To AC line
.)
6 in
m (1
m
406
WARNING:
• Structural member must be strong enough to support
40kg [88 lbs].
• Do not suspend fixture near sharp edges.
WARNING
Risk of Injury. Improper mounting bracket installation
may cause injury or property damage.
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause
harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
CAN ICES-005 (A) / NMB-005 (A)
Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the
instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to
cause harmful interference in which case the user will be required to correct the interference at his own expense.
www.gelighting.com
GE and the GE Monogram are trademarks of the General Electric Company. All other trademarks are the property of their respective owners. Information provided is subject to
change without notice. All values are design or typical values when measured under laboratory conditions. GE Lighting is a business of the General Electric Company. © 2016 GE.
IND308 (Rev 09/28/17)