FTA1000
Full Voltage Starting
Mark IIxg Electric Fire Pump Controller
Description – Firetrol® FTA1000 Full Voltage Fire Pump
Controllers are intended for use with electric motor
driven fire pumps where the capacity of the power
source permits full voltage starting. Full voltage is applied to the motor as soon as the controller is actuated.
The controller monitors, displays and records fire pump
system information.
Full voltage starting is simple and low cost and is preferred whenever the utility or emergency generator set
will permit this type of starting.
Approvals – Firetrol fire pump controllers are listed by
Underwriters’ Laboratories, Inc., in accordance with
UL218, Standard for Fire Pump Controllers, CSA, Standard
for Industrial Control Equipment, and approved by Factory
Mutual. They are built to meet or exceed the requirements of the approving authorities as well as NEMA and
the latest editions of NFPA 20, Installation of Centrifugal
Fire Pumps, and NFPA 70, National Electrical Code.
Standard Features—The following are included as standard with each controller:
• Voltage surge protector
• Main Disconnect Switch sized for connected motor
horsepower and voltage
• Fire pump Circuit Breaker
• Single handle Isolating Disconnect Switch/Circuit
Breaker mechanism
• Motor contactor
• Emergency Manual Run Mechanism to mechanically
close motor contactor contacts in an emergency condition
Product Description
• Built-in Start and Stop push-buttons to bypass automatic start circuits
• Minimum Run Timer / Off Delay Timer
• Daylight Savings Time Option
• Weekly Test Timer
• Elapsed Time Meter
• Door mounted display/interface panel featuring a 128
x 64 pixel backlit LCD Graphical Display, Membrane
Type User Control Push-buttons and easy to read LED
Indicators for:
• POWER AVAILABLE
• ALARM
• TRANSFER SWITCH NORMAL (If unit ordered with
Automatic Power Transfer Switch)
• TRANSFER SWITCH EMERGENCY (If unit ordered with
Automatic Power Transfer Switch)
• SYSTEM PRESSURE LOW
• PUMP RUNNING
• DELUGE OPEN
• REMOTE START
• INTERLOCK ON
• FAIL TO START
• MOTOR OVERLOAD
• EMERGENCY ISO SWITCH OFF (If unit ordered with
Automatic Power Transfer Switch)
• PHASE FAILURE
• PHASE REVERSAL
• AUTOMATIC SHUTDOWN DISABLED
• OVERVOLTAGE
• UNDERVOLTAGE
• Digital Pressure Display
• USB Host Controller and Port
• Solid State Pressure Transducer
• Data Log
• Event Log (3000 Events)
• True RMS Metering with simultaneous 3 Phase Display
of Amps, Volts, Frequency, Pressure and Alarm Messages
• Disk Error message
• Disk Near Full message
• Pressure Error message
• Motor Over 320% message
• Local Start message
• Remote Start message
• Emergency Start message
• Fail To Start message
• Undervoltage message
• Overvoltage message
• NEMA Type 2 (IEC IP22) enclosure
• Suitable for use as Service Equipment
• Each standard controller comes with user configurable
options for:
• Interlock Alarm • Low Pressure Audible
•Low Suction
• Pump Run
• User Defined Input • Weekly Test
Product Description - Options & Modifications
SPECIAL ENCLOSURES
-T
NEMA Type 3R (IEC IP24), Painted Steel
-E
NEMA Type 4 (IEC IP66), Painted Steel
-F
NEMA Type 4X (IEC IP66), #304 Stainless Steel,
Unfinished**
-FXP NEMA Type 4X (IEC IP66), #304 Stainless Steel,
Painted Finish
-FD
NEMA Type 4X (IEC IP66), #316 Stainless Steel,
Unfinished**
-FDB NEMA Type 4X (IEC IP66), 12 Gauge, Seam
Welded, #316 Stainless Steel, Polished and
Brushed Finish
-FDP NEMA Type 4X (IEC IP66), #316 Stainless Steel
Painted Finish
-G
NEMA Type 12 (IEC IP54), Painted Steel
** Unfinished (Not painted, polished or brushed).
CIRCUIT BREAKER OPTION
-N
Intermediate withstand rating
150,000 Amps RMS Sym.
-P
High withstand rating
200,000 Amps RMS Sym
Note: Intermediate and High withstand ratings may not be available for all horsepowers and voltages. Consult factory for availability.
ANTI-CONDENSATION SPACE HEATERS
-H
120 Volt Space Heater
-J
120 Volt Space Heater With Thermostat
-K
120 Volt Space Heater With Humidistat
-L
240 Volt Space Heater
-M
240 Volt Space Heater With Thermostat
-N
240 Volt Space Heater With Humidistat
PRESSURE TRANSDUCERS
-B
0-600 psi (0-42.25 bar) Pressure Transducer for
Fresh Water Service
-C
0-300 psi (0-21.1 bar) Pressure Transducer for
Copper Corrosive Service
-D
0-600 psi (0-42.25 bar) Pressure Transducer for
Corrosive Service
COMBINED AUTOMATIC POWER TRANSFER SWITCHES
FTA950 - Generator/Utility emergency source
FTA951 - Bypass Isolation for Generator/Utility emergency source
ALARMS
-AC
Extra contacts (normally open & normally closed) for
remote indication, pump operating
-AF
Audible and Visible low pump room temperature alarm
-AG
Audible and Visible reservoir low alarm
-AH
Audible and Visible low suction pressure alarm
-AM
Contacts for remote indication, pump fail to start
-AV
Contacts for remote indication,
low pump room temperature (Requires option -AF)
-AW
Contacts for remote indication, reservoir
low (Requires option -AG)
-AY
Contacts for remote indication, low suction pressure (Requires option -AH)
-AZ
Low pump room temperature switch, mounted and wired
-BW
Extra contacts for remote indication,
phase failure/phase reversal
-BY
Contacts for remote indication, pump overload
-COM Low Suction Pressure Alarm, (Includes selectable auto/
manual reset, audible, visible and remote alarms, initiating
pressure switch NOT included)
-CTS
Built-in Low Suction Pressure Alarm
Panel (Includes selectable auto/manual reset, audible, visible and remote alarms and wired and mounted pressure
switch)
-EG
Audible and Visible relief valve discharge alarm
-EH
Contacts for remote indication, relief valve discharge (Requires option -EG)
-EJ
Audible and Visible flow meter on alarm
-EK
Contacts for remote indication, flow meter on (Requires
option -EJ)
-KH
Contacts for remote indication, common output for any
alarm
-JR
Visible jockey pump running indication
-JT
Audible and Visible jockey pump trouble indication
-P
Built-in alarm system (Includes visible supervisory voltage
normal indication and audible pump operating, phase
failure and phase reversal indication)
-PE
Contacts for remote indication, low system pressure (pump
on demand)
-PT
Built-in alarm system, 220 VAC supervisory power (Includes
visible supervisory voltage normal indication and audible
pump operating, phase failure and phase reversal
indication)
MISCELLANEOUS
-ED
Load shed circuits (Selectable power source and adjustable
time delay to remove non-critical loads before starting)
-EL
Series pumping, high zone controller
-EM
Series pumping, mid zone controller(s)
-EN
Series pumping, low zone controller
-FZX
400 VAC Operation (Controller labeled for operation at 380400 VAC - Use with voltage code FZ)
-IEC
CE Marking with Externally Mounted Wet Parts
-IECI
CE Marking with Internally Mounted Wet Parts
-OSP
OSHPD Seismic Certification (State of California) (Requires
Option -SEI)
-PY
Motor space heater output contacts
-STropicalization
-SEI
Seismic Certification (in accordance with IBC)
(Note: Not available on model FTA1500)
-USBX External USB Port
-ZPA
Customized, annual service display message (when factory
programmed or programmed by Firetrol representative
during start-up)
-ZPN
Serial Modbus RTU over Ethernet TCP/IP using 5150 Connectivity Module
-ZPM
Serial Modbus RTU over 2-wire or 4-wire RS485
Export packaging (Wooden crating to conform
to IPPC Standards)
FTA1000 - 1930
111 Corning Road
Suite 120
Cary, North Carolina 27518
P +1 919 460 5200
F +1 919 460 5250
www.firetrol.com
While every precaution has been taken to ensure accuracy and completeness herein, ASCO Power Technologies assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or
for any errors or omissions. Specifications and drawings are subject to change without notice. The ASCO, ASCO Power Services, and ASCO Power Technologies marks are owned by Emerson Electric Co. or its affiliates and
utilized herein under license. ©2017. Printed in USA.
Publication PD1000-50 Rev. G