Instruction Manual
Rack PDU
XP Series
geistglobal.com
Table Of Contents
3
Table of Contents
Specifications
4
Overview
................................................................................................................................... 4
Environmental
................................................................................................................................... 4
Tem perature .......................................................................................................................................................... 4
Hum idity
.......................................................................................................................................................... 4
Elevation
.......................................................................................................................................................... 4
Electrical
................................................................................................................................... 4
Receptacle
...................................................................................................................................
Ratings
4
EMC Verification
................................................................................................................................... 4
Installation
6
Instructions
................................................................................................................................... 6
Guidelines
................................................................................................................................... 6
Mounting
Optional Local Monitoring
7
14
Power
...................................................................................................................................
Meter
14
Current
...................................................................................................................................
Meter
14
Service/Tech Support
15
Service
...................................................................................................................................
and Maintenance
15
More ...................................................................................................................................
Technical Support
15
Revision History
GM1098 RPDU Instruction Manual XP Series
15
© 2017
3
4
RPDU Instruction Manual XP Series
Specifications
Overview
The XP Series products are Power Distribution Units (PDU) intended for connection to a 30 Amp AC
Mains circuit.* The PDUs are designed to be powered by either a single phase or a three phase
AC input circuit. Three phase units can be configured for either a delta or wye input connection.
XP Series PDUs can optionally be configured with a Geist Current Meter that provides local
monitoring and display of each output circuit current.
*Global Versions of the XP Series are intended to be connected to a 32 Amp AC Mains Branch
Circuit
Environmental
Temperature
Operating:
Storage:
10°C (50°F) min 45°C (113°F) max
-25°C (-13°F) min
65°C (149°F) max
Humidity
Operating:
Storage:
5% min 95% max
5% min 95% max
(non-condensing)
(non-condensing)
0 m (0 ft) min
0 m (0 ft) min
2000 m (6561 ft) max
15240 m (50000 ft) max
Elevation
Operating:
Storage:
Electrical
See nameplate for unit ratings.
Receptacle Ratings
NEMA 5-15R or L5-15R
NEMA 5-20R or L5-20R
NEMA 6-20R or L6-20R
IEC-320 C13
IEC-320 C19
125 Volts, 15 Amp
125 Volts, 20 Amp
250 Volts, 20 Amp
125/250 Volt, 15 Amp (per Receptacle Bank)
125/250 Volt, 20 Amp
EMC Verification
This Class A device complies with part 15 of the FCC Rules. Operation is subject to the following
two conditions: (1) This device may not cause harmful interference, and (2) this device must accept
any interference received, including interference that may cause undesired operation.
GM1098 RPDU Instruction Manual XP Series
© 2017
Specifications
5
This Class A digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe A est conforme à la norme NMB-003 du Canada.
Warning: Changes or modifications to this unit not expressly approved by the party responsible for
compliance could void the user’s authority to operate this equipment.
GM1098 RPDU Instruction Manual XP Series
© 2017
6
RPDU Instruction Manual XP Series
Installation
Instructions
1.
2.
3.
4.
5.
Using appropriate hardware, mount PDU to rack (see Mounting section for additional
instructions.
Plug PDU into de-energized 30 Amp branch circuit receptacle.**
Connect devices into PDU’s output receptacles. It is recommended that the devices are
turned off until all devices are connected to PDU
Turn on branch circuit to energize PDU.
Power on devices. Sequential power up is recommended to avoid high inrush current.
**Branch Circuit should be sized based on the PDU’s nameplate electrical rating. A 24 Amp rated
PDU is intended for use on a 30 Amp Branch Circuit. For Global Units a 32 Amp rated PDU is
intended for use on a 32 Amp Branch Circuit.
Guidelines
·
·
·
·
·
·
·
·
·
·
·
If the PDU is installed in a cabinet the ambient temperature of the rack should be no greater
than 45°C.
Install the PDU such that the amount of airflow required for safe operation of equipment is not
compromised.
Mount the PDU so that a hazardous condition is not achieved due to uneven mechanical
loading.
Follow nameplate ratings when connecting equipment to the branch circuit. Take into
consideration the effect that overloading of the circuits might have on over-current protection
and supply wiring.
The PDU relies on the building installation for protection from over-current conditions. A
certified overcurrent protection device is required in the building installation. The overcurrent
protection device should be sized according to the PDU’s nameplate ratings and local/national
electrical codes.
Reliable earthing of rack-mount equipment should be maintained. Particular attention should
be given to supply connections other than direct connections to the branch circuit. The PDU
must be connected to an earthed socket-outlet.***
The PDU is intended for Restricted Access Locations only and only qualified service personnel
should install and access the PDU.
For pluggable equipment, install the PDU so that the input plug or appliance coupler may be
disconnected for service.
Sequential power-up of devices powered by the PDU is recommended to avoid high inrush
current.
Caution: Disconnect all power cords before servicing.
The PDU is intended for use with TN, TT, or IT power supply systems
***XP Series PDUs may optionally be configured as Isolated Ground units. All Isolated Ground
units will be shipped with an enclosure grounding cable. This cable must be connected
between the enclosure and a reliable safety ground.
GM1098 RPDU Instruction Manual XP Series
© 2017
Installation
7
Mounting
Full Length Bracket
Using the full length bracket, mount PDU to rack as shown
Mini "L" Brackets (SLB-4)
GM1098 RPDU Instruction Manual XP Series
© 2017
8
RPDU Instruction Manual XP Series
Using the mini “L” brackets, attach PDU to rack as shown
Vertical Extension Brackets (VCB-1)
Using the vertical extension brackets, attach PDU to rack as shown
Toolless Mounting Hardware (11621)
Secure toolless mounting buttons to PDU as shown. Use toolless buttons with key-holed slots built
into cabinet or with optional Geist key-holed brackets.
GM1098 RPDU Instruction Manual XP Series
© 2017
Mounting
9
Toolless Full Length Bracket (TLFL)
Using full length toolless bracket and toolless mounting buttons, attach PDU to rack as shown
Single Side Mount 2 Unit Brackets (TSMX2)
Using single side mount 2 unit brackets and toolless mounting buttons, attach PDU to rack as shown
GM1098 RPDU Instruction Manual XP Series
© 2017
10
RPDU Instruction Manual XP Series
Offset/Side Mount Brackets (EZB-1)
Using the offset/side mount brackets, attach PDU to rack as shown.
7" Extension Brackets (XB-7)
Using the 7” extension brackets, attach PDU to rack as shown
GM1098 RPDU Instruction Manual XP Series
© 2017
Mounting
11
Flush Mount Brackets (FM)
Using flush mount brackets, attach PDU to rack as shown
Adjustable Mount Brackets (AM)
Using adjustable mount brackets, attach PDU to rack as shown
GM1098 RPDU Instruction Manual XP Series
© 2017
12
RPDU Instruction Manual XP Series
Panel Mount Brackets (PM)
Using panel mount brackets, attach PDU to rack as shown
23" Conversion Mounting Brackets (23-RM)
Using conversion mounting brackets, attach 19” PDU to 23” rack as shown
GM1098 RPDU Instruction Manual XP Series
© 2017
Mounting
13
Cable Mount Bracket (CMB-1)
Attach cable mount bracket to PDU as shown; use tie-wraps to secure cords to bracket
19" Horizontal/Panel Mount Brackets (7938)
Using the 19” horizontal/panel mount brackets, attach PDU to rack as shown
GM1098 RPDU Instruction Manual XP Series
© 2017
14
RPDU Instruction Manual XP Series
Optional Local Monitoring
Power Meter
The Geist PM-1 power meter is a low-power, high accuracy meter capable of measuring true RMS
Current, Voltage, Power, and Power Factor. These values are individually shown on an easy to
read, 4-digit LED Display, which continuously scrolls through the four different measured values.
Each one of these displayed parameters is defined below. The Power Meter will automatically
begin cycling through the displayed values when the PDU is connected to AC Mains power.
·
·
·
·
Current: PDU output current draw measured in true RMS Amps
Voltage: PDU output voltage measured in true RMS Voltage
Power: PDU output power measured in Watts – referred to as real or active power
Power Factor: Ration of real PDU output power to apparent PDU output power****
Power Meter Display
****Real power is the power in a circuit that is transformed from electric to non-electric energy,
while apparent power is the total power supplied to the circuit.
Current Meter
The Geist CM-1 current meter is a low-power, high accuracy meter capable of measuring true RMS
Current. The value of current is continuously shown on an easy to read, 4-digit LED Display. The
Current Meter will automatically begin to display value of output current when the PDU is
connected to AC Mains power.
Current Meter Display
GM1098 RPDU Instruction Manual XP Series
© 2017
Optional Local Monitoring
15
Service/Tech Support
Service and Maintenance
No service or maintenance is required. Do not attempt to open the PDU or you may void the
warranty. No serviceable parts inside. It is recommended that power be removed from the unit
before installing or removing any equipment.
More Technical Support
http://geistglobal.com
Americas
·
1 888 630 4445
Europe and Middle East
·
·
From within the UK 0845 026 3853
From abroad +44 845 026 3853
Asia
·
·
English +1 888 630 4445 (US number)
Chinese +86 755 8663 9505
Email: support@geistglobal.com or contact your distributor
Technical Support Form: http://www.geistglobal.com/Tech-Support
Revision History
Revision
Date
Notes
Approved By
1.0
5/20/2010
Original Published Version
BP
1.1
7/1/2010
Minor Text Edits
BP
1.2
1/24/11
Added Satellite Current Monitoring SC & BP
1.3
3/12/12
Add Packet Power
CG
1.4
6/22/2012
Changed Logo and Web Address
SR
2.0
7/29/2014
Changed Company Name
QN
3.0
5/30/2017
Remove Current Monitor and CM-3 GY
GM1098 RPDU Instruction Manual XP Series
© 2017
Thank You For
Purchasing Geist
geistglobal.com