Metered Rack PDU AP7802B
Overview
The APC by Schneider Electric Metered Rack Power Distribution Unit (PDU) distributes power to devices
in the rack. It has a sensor that measures the current used by the Rack PDU and its attached devices. It
can be monitored through Web, Telnet, SNMP, SSH, or StruxureWare Data Center Expert® interfaces.
Outlets: The PDU has sixteen (16) NEMA 5-20 outlets.
Digital display: A digital display shows aggregate current being used per bank by the Rack PDU.
pdu0365a
Power cord: The 12 ft (3.65 m) power cord terminates with a NEMA L5-30P connector.
Specifications
Electrical
Input connector
NEMA L5-30P
Cord length
12 ft (3.65 m)
Nominal input voltage
120 V
Input frequency
50–60 Hz
Acceptable input voltage
±10% of nominal voltage
Maximum input current total (bank)
24 A
Nominal output voltage
120 V
Maximum output current (outlet)
16 A
Maximum output current (bank)
20 A
Output connectors
(16) NEMA 5-20
Overload protection
(2) 20-A single-pole circuit breakers
Physical
Dimensions (H × W × D)
3.48 × 17.47 × 4.41 in
(8.83 × 44.37 × 11.20 cm)
Shipping dimensions
(H × W × D)
5.50 × 20.00 × 14.50 in
(13.97 × 50.80 × 36.83 cm)
Weight
7.40 lb (2.76 kg)
Shipping weight
11.90 lb (4.44 kg)
Environmental
Elevation (above MSL)
Operating
Storage
10,000 ft (3000 m)
50,000 ft (15 000 m)
Temperature
Operating
Storage
23 to 113°F (–5 to 45°C)
–13 to 149°F (–25 to 65°C)
Humidity
Operating
Storage
5–95%, non-condensing
5–95%, non-condensing
Compliance
Safety
UL/C-UL, VDE
EMC
FCC Class A, ICES-003